Chapter 3 – Start-up Data 3-4 Firmware Manual 99.08 MOTOR NOM SPEED This parameter matches the ACS 600 to the nominal speed as indicated on the motor rating plate. Note: It is very important to set this parameter exactly to the value given on the motor rating plate to guarantee proper operation of the drive. The motor synchronous speed or another approximate value must not be given instead! Note: The speed limits in Group 20 Limits are linked to the setting of 99.08 MOTOR NOM SPEED. If value of Parameter 99.08 MOTOR NOM SPEED is changed, the speed limit settings change automatically as well. 99.09 MOTOR NOM POWER This parameter matches the ACS 600 to the rated power of the motor, adjustable between 0 kW and 9000 kW. 99.10 MOTOR ID RUN This parameter is used to initiate the Motor Identification Run. During the run, the ACS 600 will identify the characteristics of the motor for optimum motor control. The ID Run takes about one minute. The ID run cannot be performed if the scalar control mode is selected (Parameter 99.04 MOTOR CTRL MODE is set to SCALAR). NO The Motor ID Run is not performed. This can be selected in most applications. The motor model is calculated at first start by magnetising the motor for 20 to 60 s at zero speed. Note: The ID Run (Standard or Reduced) should be selected if: operation point is near zero speed operation at torque range above the motor nominal torque within wide speed range and without any pulse encoder (i.e. without any measured speed feedback) is required. STANDARD Performing the Standard Motor ID Run guarantees that the best possible control accuracy is achieved. The motor must be de-coupled from the driven equipment before performing the Standard Motor ID Run. REDUCED The Reduced Motor ID Run should be selected instead of the Standard ID Run: if mechanical losses are higher than 20 % (i.e. the motor cannot be de-coupled from the driven equipment) if flux reduction is not allowed while the motor is running (i.e. in case of a braking motor in which the brake switches on if the flux is reduced below a certain level).

Upload: agnostic07

Post on 16-Sep-2015

40 views

Category:

Documents


0 download

DESCRIPTION

motor optimization for ABB driver

TRANSCRIPT

  • Chapter 3 Start-up Data

    3-4 Firmware Manual

    99.08 MOTOR NOM

    SPEED

    This parameter matches the ACS 600 to the nominal speed as

    indicated on the motor rating plate.

    Note: It is very important to set this parameter exactly to the value

    given on the motor rating plate to guarantee proper operation of the

    drive. The motor synchronous speed or another approximate value

    must not be given instead!

    Note: The speed limits in Group 20 Limits are linked to the setting of

    99.08 MOTOR NOM SPEED. If value of Parameter 99.08 MOTOR

    NOM SPEED is changed, the speed limit settings change automatically

    as well.

    99.09 MOTOR NOM

    POWER

    This parameter matches the ACS 600 to the rated power of the motor,

    adjustable between 0 kW and 9000 kW.

    99.10 MOTOR ID RUN This parameter is used to initiate the Motor Identification Run. During

    the run, the ACS 600 will identify the characteristics of the motor for

    optimum motor control. The ID Run takes about one minute.

    The ID run cannot be performed if the scalar control mode is selected

    (Parameter 99.04 MOTOR CTRL MODE is set to SCALAR).

    NO

    The Motor ID Run is not performed. This can be selected in most

    applications. The motor model is calculated at first start by magnetising

    the motor for 20 to 60 s at zero speed.

    Note: The ID Run (Standard or Reduced) should be selected if:

    operation point is near zero speed

    operation at torque range above the motor nominal torque within

    wide speed range and without any pulse encoder (i.e. without any

    measured speed feedback) is required.

    STANDARD

    Performing the Standard Motor ID Run guarantees that the best

    possible control accuracy is achieved. The motor must be de-coupled

    from the driven equipment before performing the Standard Motor ID

    Run.

    REDUCED

    The Reduced Motor ID Run should be selected instead of the Standard

    ID Run:

    if mechanical losses are higher than 20 % (i.e. the motor cannot be

    de-coupled from the driven equipment)

    if flux reduction is not allowed while the motor is running (i.e. in case

    of a braking motor in which the brake switches on if the flux is

    reduced below a certain level).

  • Chapter 3 Start-up Data

    Firmware Manual 3-5

    Note: Check the rotation direction of the motor before starting the

    Motor ID Run. During the run the motor will rotate in the forward

    direction.

    WARNING! The motor will run at up to approximately 50 % ... 80 % of

    the nominal speed during the Motor ID Run. BE SURE THAT IT IS

    SAFE TO RUN THE MOTOR BEFORE PERFORMING THE MOTOR

    ID RUN!

    ID Run Procedure To perform the Motor ID Run:

    Note: If parameter values (Group 10 to 98) are changed before the ID

    Run, check that the new settings meet the following conditions:

    20.01 MINIMUM SPEED < 0.

    20.02 MAXIMUM SPEED > 80 % of motor rated speed.

    20.03 MAXIMUM CURRENT > 100*Ihd.

    20.04 MAXIMUM TORQUE > 50 %.

    1. Ensure that the Panel is in the local control mode (L displayed on

    the status row). Press the key to switch modes.

    2. Change the selection to STANDARD or REDUCED:

    3. Press ENTER to verify selection. The following message will be

    displayed:

    LOC

    REM

    1 L ->1242.0 rpm O

    99 START-UP DATA

    10 MOTOR ID RUN

    [STANDARD]

    1 L ->1242.0 rpm O

    ACS 600 55 kW

    **WARNING**

    ID RUN SEL

  • Chapter 3 Start-up Data

    3-6 Firmware Manual

    4. To start the ID Run, press the key. The run enable signal must

    be active (see Parameter 16.01 RUN ENABLE).

    In general it is recommended not to press any control panel keys

    during the ID run. However:

    The Motor ID Run can be stopped at any time by pressing the

    Control Panel key or removing the Run enable signal.

    After the ID Run is started with the key, it is possible to monitor

    the actual values by first pressing the ACT key and then the key.

    Warning when the ID Run is

    started

    Warning during the ID Run Warning after a successfully

    completed ID Run

    1 L -> 1242.0 rpm I

    ACS 600 55 kW

    **WARNING**

    MOTOR STARTS

    1 L -> 1242.0 rpm I

    ACS 600 55 kW

    **WARNING**

    ID RUN

    1 L -> 1242.0 rpm I

    ACS 600 55 kW

    **WARNING**

    ID DONE