module and procontrol p application description · address formation for instance, the following...
TRANSCRIPT
Module and PROCONTROL P Application Description Binary and Analog Control
D KWL 6326 94 E, Edition 04/05 83SR06/R1010
Application Features
This module is used for stored-program binary and analog control tasks on the drive, group and unit control levels. It can be used for the following applications:
The module address is set automatically when the module is plugged into the PROCONTROL - station.
The telegrams received from the bus are checked by the module for error-free transfer by means of their parity bits. - Drive control of unidirectional drives
- Drive control of actuators The telegrams sent from the module to the bus include parity bits to ensure error-free transfer. - Drive control of solenoid valves
- Binary function group control (sequential and logic)
The user program is stored on a non-volatile memory (EEPROM). The application program is installed and modified via bus from the PDDS. - 3-step control
- Continuous control (actuation of actuators via analog output module)
The module is ready for operation as soon as a valid user list has been loaded.
- Signal processing For communicating with operator’s console, process and switchgear, the module requires the following voltages:
The module can be used in three operating modes: US Operating voltage +24 V branched internally to supply the following elements: - Binary control mode
including basic analog functions and variable cycle times
US1 Command outputs B10 and B20 US2 Process contact transmitters (e.g. limit switches) - Analog control mode
(and binary control) at a fixed, selectable cycle time
US3 Torque monitors for actuators UST Pushbuttons of manual control station
- Signal processing mode (and binary and analog control) at a fixed cycle time and disturbance bit output
The US1 voltage is fuse-protected inside the module. The voltages US2, US3 and UST are short-circuit-proof.
The operating voltages and the external logic signals are related to zero conductor Z. The operating mode is selected by using the TXT1 function
block which is the first block indicated in the structure. The following annunciations are indicated on the front of the module by light-emitting diodes: In the case of binary control applications, up to 4 function
group controls, or 16 drive controls or any combination of drive and group controls are possible. One function group control stands for four drive controls.
- ST: Disturbance of the module - SG Module disturbance
For analog control applications, up to 4 control circuits per module can be provided as 3-step controllers or continuous controllers. Furthermore, combinations with binary control functions are possible.
- US1: Fuse failure for US1
Signal lamp ST indicates disturbances of the module and of the data communication with the module. Signal lamp SG indicates pure module disturbances only. The module incorporates hardware interfaces with the control
room and with the switchgear or with the process, respectively. These interfaces can individually be assigned to different functions of the module.
83SR06-E/R1010
Module Design The operating program enables the microprocessor to perform the basic operations of the module.
The memory for the function blocks contains programs prepared to implement the various functions. The module essentially consists of:
- Process interface Function blocks available for one certain operating mode are intended to ensure that the required task is performed without any additional modules being necessary. For instance, in the analog control mode not only single variable analog control can be realized but also a superimposed setpoint control.
- Control room interface - Station bus interface - Processing section
All function blocks as well as their individual inputs and outputs can be called by the user using the programming, diagnosis and display system (PDDS).
Process Interface
In the process interface, the process signals are adapted to the module-internal signal level. The memory for the user program contains information as to:
- how the function blocks are interconnected, Control Room Interface - which module inputs and outputs are allocated to the inputs
and outputs of the function blocks, In the control room interface, the pushbutton commands are adapted to the module-internal signal level, and the module-internal signal levels are adapted to the annunciation lamps in the control room.
- which constants are specified for the individual inputs of the function blocks,
- which parameters are specified for the individual inputs of the function blocks,
- which plant signals are allocated to the individual module inputs and outputs Station Bus Interface
- which function blocks are used to serve the process and control room interfaces, In the station bus interface, the module signals are adapted to
the bus. This essentially involves a parallel/serial conversion. - which sets of limit values are allocated to the analog
values, Processing Section - which module input signals are simulated.
In order to process the signals coming from process, control room and bus, the module is provided with a microprocessor which cooperates with the following memory areas using the module-internal bus:
This information is specified by the user depending on the plant involved.
Contents Memory
medium
Operating program EPROM
Function blocks EPROM
User program (structure, address, parameter limit value and simulation list)
EEPROM
User program (structure, address, parameter limit value and simulation list)
RAM
History values RAM
Current module input and output signals (shared memory)
RAM
For normal operation, the complete user program is stored on an EEPROM. For optimization purposes, a modified copy of the user program can be used in the RAM. After the optimization work has been completed, this copy has to be transferred into the EEPROM.
The setting values (mainly for analog control) can either be specified directly by the user at the respective function block inputs in the form of a value or they can be listed in a separate parameter list.
If limit signals are formed by GRE function blocks, the limit values (4 per GRE) are listed in a limit value list.
Parameter and limit value lists can be changed anytime during operation in on-line fashion. For this purpose, they are assigned to the RAM or EEPROM mode - stored in the RAM or the EEPROM, respectively.
The exchange of information between module and bus system takes place via the memory for module input and output signals. This memory is used as a signal buffer.
2
83SR06-E/R1010
Structuring
During structuring, the neutral inputs and outputs of the individual function blocks are assigned module inputs and outputs - or constants and parameters or outputs of other function blocks (function results) are specified to the function block inputs. Structuring is performed on the basis of the data supplied by the user in the form of a so-called structure list.
The following limit values for the module are to be taken into consideration:
- Max. number of module inputs 287 - Max. number of simulatable module inputs 32 - Max. number of module outputs 223 - Max. number of calculated function results 255 - Max. number of timers 128 - Max. number of parameters 80 - Max. number of limit value sets 16 - Max. number of drive control functions
ASE, ASS, ASM 16 - Max. number of drive control functions
ASI1, ASP 4 - Max. number of group control functions
GSA2, GSV 4 - Max. number of lines in the structure list 2917 - Length of history values list (bytes) 768 - Design of shared memory (see “Addressing”)
One line refers to one entry on the PDDS.
The proper procedure to be followed for structuring the function blocks is described in the function block descriptions.
3
83SR06-E/R1010
Addressing Telegrams received, whose addresses are included in the bus address list, are entered into the sink register of the shared memory. Telegrams received, whose addresses are not included in the bus address list, are ignored by the module.
General
The signal exchange between the module and the bus system takes place via a shared memory. Here, incoming telegrams to be received by the module and calculated function results, which are to leave the module, are buffered.
The allocation list for module inputs contains the respective sink register number for each module input.
Address List for Module Outputs The shared memory has source registers for telegrams to be transmitted and sink registers for telegrams to be received. Register numbers 0 - 63 are defined as source registers, and numbers 64 - 199 as sink registers.
In the address list for module outputs a source register is specified for each signal which is to leave the module; in the case of binary signals an additional source bit is specified, e.g.: The assignments of the module inputs and outputs to the
shared memory registers is determined from the PDDS (programming, diagnosis and display system) on the basis of data supplied by the user.
Output Address
AG1 1, 5
bit no.register no.
(0 - 15)(0 - 63)
The user data are provided in the form of address lists.
Address List for Module Inputs
In the address list for module inputs, the source location address of the telegram to be received is allocated to the module input concerned. Address Formation For instance, the following data refer to one module input: System and station address are set at the station-bus
coupling module (or at the control module) and are transmitted then to all modules of a PROCONTROL station.
Input Address EG1 1, 32, 24, 8, 7
bit no. register no. module no. station no. system no.
(0 - 15)(0 - 63)(0 - 58)(1 - 249)( 0 - 3)
The module addresses are defined by the connections on the backplane. Therefore, the modules automatically adapt to the given definition when they are plugged into their assigned slots.
Limit Value List
The limit value list contains 4 limit values for maximally every 16 GRE function blocks (limit signal generation for an analog value). This list is stored in the EEPROM and - in the case of RAM mode - in the RAM.
In the case of module inputs, which receive their signal through the wired control room interface, a special symbol (”V”) is used instead of the source location address. The module input can be connected to any function block input intended for pushbutton telegrams. Limit value lists can be changed any time from the PDDS and
the POS by using an “order memory” (RAM). In the EEPROM mode these changes are stored in the EEPROM; in the RAM mode they are stored in the RAM. When the user lists are transferred from the RAM into the EEPROM and vice versa, the limit value lists are transferred likewise.
In the case of module inputs receiving their signal through the wired process interface, a special symbol (”V”) is used instead of the source location address. The module input may only be connected with the PRO input of a drive function block.
In the case of module inputs receiving their signal from the process operator station, a special symbol (”L”) will be used instead of the source location address. Inputs of function blocks intended for destination-addressed telegrams will be assigned the sink register with 63 + EG number as an address if ”L” is specified (the EG number must be below 136).
Parameter List
The parameter list contains up to 80 values for function block parameters. It is handled and stored like the limit value list.
The address list for inputs is translated by the PDDS into two module-internal lists, i.e. the bus address list and the allocation list for module inputs.
Simulation List
From the PDDS, it is possible to overwrite signals at a maximum of 32 module inputs with constant values, i.e. to “simulate” the signals normally received from the bus. This simulation list is handled and stored like the limit value list.
The bus address list contains the source addresses and the sink register numbers for all telegrams which are to be used by the module.
4
83SR06-E/R1010
Event Formation Disturbance Bit Evaluation, Reception Monitoring
The telegrams received from the bus may be provided with a fault flag on bit position 0. This fault flag is generated by the source module on the basis of plausibility checks and is set to “1” in the event of specific disturbances (see module and function block descriptions).
During each system cycle the module is requested once by the PROCONTROL system to transmit the information filed in the source registers of the shared memory.
If values change during one cycle time, the change is treated as an “event”.
In order to be able to recognize errors during signal transfer, the module also incorporates a feature that monitors the input telegrams for cyclic renewal. If a signal has not been renewed within a certain time, (e.g. due to failure of the source module), the bit on position 0 is set to “1” in the allocated sink register of the shared memory. Additionally, all binary values in binary value telegrams are set to “0”. In the case of analog values the previous value is retained.
The module recognizes the following occurrences as events:
- Change of status in the case of binary values - Change of an analog value by a permanently set threshold
value of 0.39 % and elapse of a time delay of 200 ms since the last transfer (cyclic or event).
If an event occurs, cyclic operation is interrupted and the new values are given priority and are transferred to the bus. A set disturbance bit does not automatically involve a reaction
in the module. If the disturbance bit of a telegram is to be evaluated, this is to be taken into consideration in the structuring process.
In the binary control mode as well as in the analog control mode, disturbance bits of received telegrams can be used only for module-internal purposes. They are not adopted by telegrams intended for sending.
In the signal processing mode disturbance bits are also adopted by telegrams intended for sending.
5
83SR06-E/R1010
6
Diagnostic and Annunciation Functions Annunciation lamp LM is not only activated by the allocated function block module, but also by module disturbances (see figure 1).
Disturbance Annunciations on the Module Disturbance Annunciation Signals to the Annunciation System On the front panel of the module light-emitting diodes have
the following annunciating functions: The annunciation system and the control diagnosis system (CDS) receive disturbance signals from the control module via bus.
LED designation - Disturbance ST - Module disturbance SG
Diagnosis - Fuse failure US1
Light-emitting diode ST annunciates all disturbances of the module and disturbances of data communication with the module.
The received telegrams and the generation of the telegrams to be sent as well as the internal signal processing are monitored in the processing section of the module for error-free operation (self-diagnosis). Light-emitting diode SG annunciates module disturbances
only. In the event of a disturbance, the type of the disturbance is filed in the diagnosis register and a disturbance annunciation is simultaneously sent to the PROCONTROL system. Additionally, the US1 light-emitting diode annunciates a
failure of the fuse for US1. Upon request, the module transmits a diagnosis telegram containing the data (see figure 2) stored in the diagnosis register (register 246).
Annunciation Signals to the Operator’s Console
A maximum of four lamps can be connected to the manual operator’s console via outputs L10, L20, LM and LH using a direct connection.
It is also possible to scan the current status of the module and the data at any time from the PDDS (remote diagnosis).
The contents of the diagnosis register, the messages from the general disturbance connection SST, the annunciations at the CDS and the ST and SG annunciation at the module are shown in figure 2.
Output LH is only needed when the module is used as a group control module. The direct connection also includes input BLS to which the appropriate flashing voltage is connected for the flashing disturbance light. The voltage for running light BLL is derived from BLS inside the module. The type of annunciation, i.e. steady light, running light or flashing disturbance light, is indicated for each module in the function block descriptions. It is independent of whether these functions are implemented on the control room coupling module or on the control module itself.
Parameter fault Process channel fault
Failure of US1 fuse
Short-circuit at US2, US3, USTChecksum error detectedModule restart executed
Event mode fault
Hardware/control-room interface active
Function blocks incl. activation of annunciation lamp LM
LM&
≥ 1
Bit 15 14
12 9 2
From diagnosis register 246
Figure 1: Disturbance annunciations on the module, LM signaling.
83SR06-E/R1010
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Type S S S S 0 S D S 0 0 0 S 0 S 0 0
Parameter fault Process channel fault Processing fault Checksum error detected
Timer defective Module restart executedBus deactivation defective
Sink monitoring responded
Event mode fault
Wrong firmware PROM Hardware defect of processing section EEPROM not valid Processing initialization active
by bus control module Module address not within 0 - 58 Hardware defect of bus interface
Module not operating
Module not accessible from bus
Module operating Diagnosis register 246
6615 6600 6601 6602
6604 6605 6606
6610
6612
CDS messages *)
ST
SST
D = Dynamic annunciations are cancelled after the contents of the diagnosis register has been transmitted S = Static annunciations disappear automatically upon deactivation
SG
SSG
0 = Not used
Module transmitter disconnected
1 1
1
Figure 2: 83SR06 diagnosis annunciations *) The control diagnosis station (CDS) provides a
description for each annunciation number, including: If, for instance, the annunciation “process channel fault” is indicated in the diagnosis register, the following causes are possible: - explanations as to cause and effect of the disturbance - Fuse US1 is defective (LED for “fuse failure” illuminated) - recommendations for correction. - Short-circuit at output US2, US3 or UST
Thus, fast disturbance elimination is ensured.
7
83SR06-E/R1010
Operating states of the module Changing Structure and Address Lists
Structure and address lists can be transferred from the module into the PDDS, can be changed there and transferred back to the module. The following procedure is possible: Initialization and Bootstrapping including User Lists
The initialization either starts when the module is plugged in or when the voltage supply is connected. - The module should be operating in EEPROM mode
- Copying the complete user program from the EEPROM into the RAM using the PDDS command “KOP”
The initialization procedure establishes a defined initial state of the module. During initialization, disturbance light-emitting diodes ST and SG are on. - Transferring the list to be changed from the EEPROM (or
RAM) into the PDDS and changing it When the module is put into operation for the first time, there is no user program available. The module signals ”Processing fault” and disturbance light-emitting diodes ST and SG are on.
- Transferring the changed list into the module, which automatically means storing it in the RAM,
- Changing-over the module operation from EEPROM mode to RAM mode using PDDS command “UMS”, testing the new list,
First the user program of the PDDS is transferred into the RAM of the module via bus. If the procedure is started with the structure list, the PDDS automatically calls the other lists. For each transfer operation the PDDS checks slot and address in order to avoid transferring the wrong lists. The module checks every list received for plausibility.
- Changing again to EEPROM mode for repeated change, repeating the procedures.
After a successful test, the complete user program can be transferred from the RAM into the non-volatile EEPROM by using:
Now the complete user program can be transferred per PDDS command into the EEPROM.
After this procedure, the module is ready for operation and the disturbance light-emitting diodes ST and SG will go off. - PDDS command “save” (SAV) or
- PDDS commands “copy from RAM into EEPROM” (KOP) and “changing-over from RAM to EEPROM” (UMS)
Normal Operation
The module operates with the user program stored in the EEPROM.
“Save” causes the lists to be copied and, then, an automatic change-over to EEPROM takes place without interference with the processing operation on the module and the command output.
During normal operation, signals coming from the bus and the process and control room interfaces are processed according to the data in the structure list.
In accordance with this procedure, commands are put out to the switchgear or control room interface, respectively, and checkback signals identifying the process status are sent via bus.
After change-overs with the use of the UMS command (from RAM to EEPROM and from EEPROM to RAM), the controllers and the group controls change over to manual mode “MANUAL”, memories and timers are reset, the commands present at the process interface are deactivated. For address changes at module inputs (EGn), the respective shared-memory entries are set to zero until new data are received for the first time after the change-over.
Changing Parameter and Limit Value Lists
Parameters and limit values can be changed any time from the PDDS and the POS (see also “limit value list” and “parameter list”).
Simulation
The PDDS allows constant values to be specified to the module for a maximum of 32 individual module input signals which come from the transfer system during normal operation. In this case, the sink registers specified in the allocation list for module inputs are overwritten by constants. These simulation data as well as the sink register numbers specified so far are stored in the EEPROM during EEPROM mode, i.e. are stored in the RAM during RAM mode.
When the user lists are transferred from the RAM into the EEPROM and vice versa, the simulation data are also transferred.
When a simulation operation is cancelled from the PDDS, the sink register number is again written into the allocation list and the module continues to operate with the value received from the bus.
8
83SR06-E/R1010
Command Functions Command Output
The commands for the connected drive (binary control or step control), which has been assigned to the process interface, are put out via relay outputs B10 and B20. These actuate, in conjunction with command output BV common to both relay outputs, the coupling relay on a two-pole basis.
Activation by Pushbuttons
A maximum of 3 pushbutton commands can be connected to module inputs T10, T20 and TH. These pushbutton commands can be assigned to each drive or group control function or to a pushbutton selection function using an addressing instruction. The internal processing of the pushbutton commands is dependent on the function block activated.
The switching current for the command outputs B10 and B20 is derived from the internally fused voltage US1. The outputs B10 and B20 are provided with a protective circuit inside the module.
The commands of those drive control functions, to which the internal process interface has not been assigned, are put out via bus.
The TF and TL pushbutton commands are to be connected as required for their usage with the individual function blocks (see also function block descriptions).
Checkback Signals from the Process Activation by a Higher-level Automatic System
In the case of the drive control function, to which the process interface has been assigned, the drive-related checkback signals from the process are put through to hardware inputs EZ/EO or EA/EE, UA/UE, MFZ/MFO, STA and VO of the module.
A higher-level automatic system controls the module via the bus.
Release and Protective Commands
The logic combinations for release and protective commands are specified as required for the plant involved. Input signals are put in using the bus.
The other drive control functions receive their process checkback signals from the bus.
Acknowledgement
Depending on its task, the module determines any difference between setpoints and actual values, and indicates these by activating the lamps in the manual control station or the POS, respectively. With binary control, signals can be acknowledged individually by pressing pushbutton T10 or T20.
With analog control, signals can be acknowledged individually by pressing pushbutton TH.
9
83SR06-E/R1010
Operating Modes For each module, the following range of functions can be provided:
The module contains all function blocks for the tasks of binary and analog control and signal processing on the drive, group and unit control levels. For a certain application, a selected number of function blocks is defined for “operating mode”. This is done by using a TXT1 function block which has to be the starting point of the structure list. This function block is then followed by TXT text elements for main function designations and function designations as well as processing functions.
- 4 GSA2/GSV group control functions or
- 4 ASI1/ASP drive control functions or
- 16 ASE/ASS/ASM drive control functions or
- Any possible combination as shown in the figure and the tables below. The function blocks not mentioned here can be used as often as desired within the range of the module.
Operating mode Module cycle time Input TXT1
Binary control (and analog basic functions)
can be varied up to max. 700 ms
STR
Analog control (and binary control)
fixed: 50, 100 150, 200 or 250 ms
REG, x x = 50 ms x = 100 ms x = 150 ms x = 200 ms x = 250 ms
Signal processing with distur– bance bit output (and analog and binary control)
fixed: 250 ms MWV
= 1 group control function (GSA2, GSV) or 1 drive control function (ASI1, ASP)
= 1 drive control function (ASS, ASE, ASM)
overall range
The module cycle time is derived from number and type of the function blocks entered into the structure list. The module cycle times indicated as fixed times are minimum cycle times. They apply in case the time resulting from the structure list is shorter. The actually required time is stored in the 205 register and can be read out by the PDDS.
The control room interface of the module is assigned to that binary and analog control function whose TST input, directly or via a selective key function TAW/TAZ, is given the abbreviation “V” for “verdrahtet” (=hard-wired) in the address list. For this purpose, the function block output “lamp signals” (LS1) does not require a module output.
The process interface of the module including the order outputs is assigned to that ASE/ASS/ASM/ASI1 drive control function whose input for “process signals” (PRO) is given the symbol “V” in the address list.
Output AS1 of the ASP drive control function for proportional outputs always has to be connected with the actuator by using the bus and an analog output module.
In case several binary drive control functions, group control functions or analog drive control functions are used on one module, those drive control functions or group control functions not being assigned to a hardware interface receive their specific information from the bus. In that case the process is connected by using input and output modules, and the connection to the control room is made via control room coupling modules or by the process operator station (POS), respectively.
10
83SR06-E/R1010
Function Blocks for Binary Control Mode (STR)
Function Blocks Abbreviations
LIMIT SIGNAL ELEMENT
In this operating mode the function blocks are available for all binary control tasks on the drive, group, and unit control level. Additionally, basic analog functions are provided.
Limit signal for upper limit value GOG
Limit signal for lower limit value GUG Limit signal block GRE The module cycle time can be varied, i.e. is determined only
by the type of function blocks used. ANALOG FUNCTIONS
Disturbance bits set to “1” and coming from telegrams received are not taken over by sent telegrams. Absolute value generator ABS
Limiter BEG Function Blocks Abbreviations Divider DIV
BINARY FUNCTIONS Function generator FKG
Factor variation KVA Switch-off delay element ASV Maximum value selector MAX 2-out-of-3 selection, binary B23 Minimum value selector MIN 2-out-of-4 selection, binary B24 Multiplier MUL M-out-of-N selection BMN Delay element, first order PT1 Expanded bit marshalling BRA1
Dual-BCD-converter DBC1 Square root extractor RAD
Dual-decimal-converter DDC Summing multiplier SMU
Disturbance bit suppression SZU Dynamic OR gate DOD Time variation TVA Switch-on delay element ESV Change-over switch UMS Monostable “flipflop” (break) MOA
Monostable “flipflop” (constant) MOK PUSHBUTTON SELECTION FUNCTIONS
OR gate ODR
RS flipflop RSR Pushbutton selection TAW AND gate UND Pushbutton selection and target value presetting TAZ Counter ZAE
ORGANISATIONAL FUNCTIONS GROUP CONTROL
Text element for designations and remarks TXT Group control function for sequential control GSA2 Text element for operating mode indication TXT1 Group control function for logic control GSV
Criteria call KRA1
Criteria call without time monitoring KRA3
Step SCH1
An exact specification of the function blocks and the procedure of structuring is contained in the function module descriptions.
Selector function, double VW2
Selector function, three-fold VW3
Selector function, four-fold VW4 Selector switch, four-fold WS4
DRIVE CONTROL
Drive control function, unidirectional drive ASE
Drive control function, solenoid valve ASM
Drive control function, actuator ASS
11
83SR06-E/R1010
Function Blocks for Analog Control Mode (REG)
Function Blocks Abbreviations
LIMIT SIGNAL ELEMENT
Limit signal for upper limit value GOG In this operating mode the function blocks are available for all analog control tasks for single-variable and master control. Additionally, the function blocks for drive and group control are provided.
Limit signal block GRE Limit signal for lower limit value GUG
Disturbance bits set to “1” and coming from telegrams received are not taken over into sent telegrams.
ANALOG FUNCTIONS
Absolute value generator ABS The module cycle time may be preset in the form of a fixed minimum cycle time (see inputs in the TXT1 text element). Limiter BEG
Divider DIV In order to achieve precise positioning in the case of the single-variable step controllers, the actuating time of the actuator (0 - 100 %) must be at least 200 times the module cycle, e.g.
Function generator FKG
Integrator INT
Factor variation KVA Actuating time ≥ 10 s at a cycle time of 50 ms.
Maximum value selector MAX Function Blocks Abbreviations Minimum value selector MIN
Multiplier MUL BINARY FUNCTIONS Monitoring and selector function MVN Switch-off delay element ASV Differentiator PDT 2-out-of-3 selection, binary B23 Delay element, first order PT1 2-out-of-4 selection, binary B24 Square root extractor RAD M-out-of-N selection BMN Summing multiplier SMU Expanded bit marshalling BRA1
Dual-BCD-converter DBC1 Disturbance bit suppression SZU
Dual-decimal-converter DDC Time variation TVA
Change-over switch UMS Dynamic OR gate DOD
Switch-on delay element ESV ANALOG CONTROL Monostable “flipflop” (constant) MOK
Manual station HST Monostable “flipflop” (break) MOA PID controller PID1 OR gate ODR PID controller with integrator stop *) PID3 RS flipflop RSR PI controller PIR1 AND gate UND
Counter ZAE PI controller with integrator stop *) PIR3
P controller PRE GROUP CONTROL
Differentiator with derivative action time PTV Group control function for sequential control GSA2
Setpoint integrator SWI Group control function for logic control GSV
Setpoint adjuster SWV1 Criteria call KRA1
PUSHBUTTON SELECTION FUNCTIONS Criteria call without time monitoring KRA3
Step for multi-function SCH1 Pushbutton selection TAW Selector function, double VW2 Pushbutton selection and target value presetting TAZ Selector function, three-fold VW3
ORGANISATIONAL FUNCTIONS Selector function, four-fold VW4 Text element TXT Selector switch, four-fold WS4 Text element for operating mode indication TXT1 DRIVE CONTROL
Drive control function, unidirectional drive ASE
Drive control function, incremental output with expanded capabilities ASI1
An exact specification of the function blocks and the procedure of structuring is contained in the function module descriptions. Drive control function, solenoid valve ASM
Drive control function, proportional output ASP *) From software version P0006 Drive control function, actuator ASS 12
83SR06-E/R1010
Function Blocks for Signal Processing Mode (MWV)
Function Blocks Abbreviations
LIMIT SIGNAL ELEMENT In this operating mode analog arithmetic functions and basic binary functions are available. For enthalpy calculation, a separate function block “ENT” is provided. Additionally, binary and analog control functions can be used.
Limit signal for upper limit value GOG
Limit signal block GRE
Limit signal for lower limit value GUG In this operating mode, disturbance bits set to “1” and coming from telegrams received are taken over into derived and sent data telegrams.
ANALOG FUNCTIONS
Absolute value generator ABS The minimum module cycle time is set to a fixed value, i.e. 250 ms. Limiter BEG
Divider DIV
Enthalpy function ENT Function Blocks Abbreviations Function generator FKG
BINARY FUNCTIONS Integrator INT
Switch-off delay element ASV Factor variation KVA 2-out-of-3 selection, binary B23 Maximum value selector MAX 2-out-of-4 selection, binary B24 Minimum value selector MIN M-out-of-N selection BMN Multiplier MUL Expanded bit marshalling BRA1
Dual-BCD-converter DBC1 Monitoring and selector function MVN
Dual-decimal-converter DDC Differentiator PDT
Delay element, first order PT1 Dynamic OR gate DOD Differentiator with derivative action time PTV Switch-on delay element ESV Square root extractor RAD Monostable “flipflop” (break) MOA Summing multiplier SMU Monostable “flipflop” (constant) MOK Disturbance bit suppression SZU OR gate ODR Time variation TVA RS flipflop RSR Change-over switch UMS AND gate UND
Counter ZAE ANALOG CONTROL
Manual station HST GROUP CONTROL
PID controller PID1 Group control function for sequential control GSA2 PID controller with integrator stop *) PID3 Group control function for logic control GSV PI controller PIR1 Criteria call KRA1 PI controller with integrator stop *) PIR3 Criteria call without time monitoring KRA3 P controller PRE Step for multi-function SCH1 Setpoint integrator SWI Selector function, double VW2 Setpoint adjuster SWV1 Selector function, three-fold VW3
PUSHBUTTON SELECTION FUNCTIONS Selector function, four-fold VW4 Pushbutton selection TAW Selector switch, four-fold WS4 Pushbutton selection and target value presetting TAZ
DRIVE CONTROL ORGANISATIONAL FUNCTIONS Drive control function, unidirectional drive ASE Text element TXT Drive control function, incremental output
with expanded capabilities ASI1 Text element for operating mode indication TXT1 Drive control function, solenoid valve ASM
An exact specification of the function blocks and the procedure of structuring is contained in the function module descriptions.
Drive control function, proportional output ASP
Drive control function, actuator ASS
*) From software version P0006
13
83SR06-E/R1010
Function Diagram
Terminal Designations Connector X21 contains all process inputs and outputs.
The printed circuit board is equipped with connectors X11 and X21.
Connector X11 contains the station-bus interface and the operating voltages US and UD.
+ +
+
Mon
itorin
g
Con
trol
room
inte
rfac
e Pr
oces
s in
terf
ace
Man
ual s
tatio
n In
terf
ace,
pus
hbut
tons
M
anua
l sta
tion
Inte
rfac
e, la
mps
Sw
itchg
ear i
nter
face
lo
cal
48 V
z06 z
10 z0
8 z30
z32 z
20 z1
4 z18
z16 z
22
b22 z
24 b2
4 z26
b26 b
14 b2
0 b28
b30
b12 b
32
b06
b10
b08
T10 T
H T2
0 TF
TL
Z L1
0 LM L2
0 LH
EZ
UA E
O U
E U
S2 S
TA VO
MFZ
MFO US
3 US
3 B
10 B
V
B20
z1
2 X2
1
US
1 S
T U
ST U
S2 U
S3
US
1
US
T
f f B
LL
BLS
z04
X2
1
Z
* C
onne
ct c
onne
ctor
X11
/d18
with
ZD
to e
nsur
e pr
oper
func
tioni
ng o
f the
mod
ule
(onc
e pe
r sub
rack
).
+
Para
llel/s
erie
l co
nver
sion
Sh
ared
m
emor
y Pr
ozes
sor
Ope
ratio
nal
func
tions
Fu
nktio
n bl
ocks
U
ser
func
tions
R
AM
83SR
06/R
1010
Stat
ion
bus
US
SS
X11
d32
Use
r fu
nctio
ns
EEPR
OM
UD
ZD Z
D Z
D
d02
b02 b
14 d2
6 U
D
d20
d18
SR
A*
Z b32
+5V
SG
14
83SR06-E/R1010
Sta
tion
bus
STA
VO
EA
Sw
itchg
ear
Pla
nt
83S
R06
/R10
10
EE
US
3
A1
12 11K
1AK
1E
1112
53
47
6
1A
12
(B10
)B
A(B
20)
BE
BV
98
10+
+-
Plan
tdi
stur
banc
e
M
L11
L21
L31
F2
F1
K1
K1
A1
6 7
Q4
L11
L1u
A1/
1
L12
(N)
A1/
2
US
SR
AZD
Connection Diagram, Unidirectional Drive
Z
A1
3 4
U<
UA
UE
US
TTA (T
10)
TE (T20
)TF
TL
US
US
ZLA (L
10)
LMLE (L
20)
Ope
rato
r’s c
onso
le
UD
15
83SR06-E/R1010
Stat
ion
bus
STA
VO
EZ
Sw
itchg
ear
Pla
nt
83S
R06
/R10
10
EOU
S3
A112 11
1112
53
47
6
1A
12
(B10
)B
Z(B
20)
BO
BV
98
10+
+-
Pla
ntdi
stur
banc
eL1
1L2
1L3
1F2
US
SR
AZD
Connection Diagram, Actuator
ZU
ST
TZ (T10
)TO (T
20)
TFTL
US
US
ZLZ (L
10)
LMLO (L
20)
Ope
rato
r’s c
onso
le
UD
M
K2
K2 AUF
K1
ZUK2K
1
A15 4
A1
6 7
Q4
L11
L1u
A1/
1
L12
A1/
2K
1
US
2M
FZM
FO
F1
16
83SR06-E/R1010
Sta
tion
bus
STA
VO
EZ
Sw
itchg
ear
Pla
nt
83S
R06
/R10
10
EO
US3
A1
12 11
1112
53
47
6
1A
12
(B20
)B
OB
V
98
10+
+-
Pla
ntdi
stur
banc
e
US
SR
AZD
Connection Diagram, Solenoid Valve
ZU
STTZ (T
10)
TO (T20
)TF
TL
US
US
ZLZ (L
10)
LMLO (L
20)
Ope
rato
r’s c
onso
le
UD
A1
6 7
F1
L1u
A1/
1
A1/
2
US
2
17
83SR06-E/R1010
Connection Diagram, Function Group Control (incl. Hardware/Control Room Interface)
83SR06/R1010
LA LM LE Z TH TA TF
US
TL
US
TE
Z
Drive control level
BLS L10 LM L20 Z TH T10 UST TF TL T20
UD
SRA
ZD
US
LH
Function group control
LH
Manual control station
Process control level
Sta
tion
bus
18
83SR06-E/R1010
Pow
er e
lect
roni
cs e
quip
men
t
Stat
ion
bus
STA
VO
EZ
Plan
t
83S
R06
/R10
10
EOU
S3
(B10
)BZ
(B20
)B
OB
V
US
SR
AZD
Connection Diagram, 3-point Step Controller
ZU
ST
TZ (T10
)TH
TFTL
US
US
ZLH (L
10)
LMLA (L
20)
Ope
rato
r’s c
onso
le
UD
US
2M
FZM
FO
M
US
3
S
_Pos
BU
S
TO (T20
)
19
83SR06-E/R1010
Connection Diagram, Continuous Controller (Activation of Actuator via Analog Output Module)
BU
S
Y
= S
83SR
06/R
1010
LH
LM
LA
Z TH
(T
10)
TZ
UST
TF
US
TL
US
Ope
rato
rs c
onso
le
BLS
(T20
) TO
Plan
t EO
Pos
EZ
Bin
ary
inpu
t A
nalo
g in
put
Ana
log
outp
ut
E H
Stat
ion
bus
Z ZD
SRA
U
D
US
20
83SR06-E/R1010
21
Mechanical Design Contact Assignments of Process Connector X21
Board size: 6 units, 1 division, 160 mm deep View of contact side: Connector: to DIN 41 612
b z
02
04 BLS
06 B10 T10
08 B20 T20
10 BV TH
12 US3 UST
14 STA L10
16 EA L20
18 EE LM
20 VO Z
22 EZ LH
24 EO UA
26 US2 UE
28 MFZ
30 MFO TF
32 US3 TL
1 x for station bus connection, 48-pole, edge-connector type F (X11 connector)
1 x for process connection, 32-pole, edge-connector type F (X21 connector)
Weight: approx. 0.55 kg
View of connector side:
X11
X21
83SR06-E/R1010
Position of Memory Module and View of Module Front Panel:
ST SG
ABB
ST disturbance SG module disturbance
EPROM, programm xxxx = position num1
22
1
83SR06
X11
X21
ABB
US1
0,8A
Failure fuse US1
Fuse US1
ed, Order number: GJR2395441Pxxxx ber indicating applicable software version.
83SR06-E/R1010
Technical Data
In addition to the system data, the following values apply:
Power Supply
Operating voltage US 19,5...30V, typ. 24 V Current consumption US = 24V 100 mA + Output values Operating voltage UD 4,9...5,1V, typ. 5,0V Current consumption UD = 5,0V 220 mA Power dissipation 3...4,3 W depending on power supply and configuration Reference potential, process side Z = 0 V Reference potential, bus side ZD = 0 V
Input Values
Direct connections BLS - Flashing light for disturbance annunciation 0.5 NL E10 - Process checkback signal (EA/EZ) OFF/CLOSED 5 mA at 48 V E20 - Process checkback signal (EE/EO) ON/OPEN 5 mA at 48 V MFZ - Torque monitor CLOSED 5 mA at 48 V MFO - Torque monitor OPEN 5 mA at 48 V STA - Disturbance in the switchgear 5 mA at 48 V T10 - Pushbutton command OFF/CLOSED 1 NL T20 - Pushbutton command ON/OPEN 1 NL TF - Pushbutton command Release 1 NL TH - Pushbutton command STOP/MANUAL/AUTOMATIC 1 NL TL - Pushbutton command Check lamps 1 NL UA - Reclosing device command OFF 1 NL UE - Reclosing device command ON 1 NL VO - Local intervention 5 mA at 48 V
Output Values
MANUAL CONTROL INTERFACE
Pushbutton communication voltage, UST = 24 V / ≤ 30 mA process side, only for inputs T10, T20 and TH For the manual control interface (voltage supply, operating voltage US): L10 - Lamp OFF/CLOSED/MANUAL ≤ 100 mA
L20 - Lamp ON/OPEN/AUTOMATIC ≤100 mA
LM - Lamp ANNUNCIATION ≤100 mA
LH - Lamp MANUAL ≤100 mA The outputs are short-circuit-proof; they have been optimized for incandescent lamps of 24 V / ≤ 100 mA.
CONTACT VOLTAGES
Contact voltage, process section US2 = 48 V / ≤ 30 mA
Contact voltage, process section US3 = 48 V / ≤ 30 mA The outputs are short-circuit-proof.
23
83SR06-E/R1010
PROCESS INTERFACE
Internal voltage supply
Voltage supply for command outputs B10 and B20 US1 = 24 V Fusing for US1 0.8 A quick-acting For the process interface (voltage supply, +24 V, US1 to Z): Loading capacity B10 - command output for OFF/CLOSED IS ≤ 0.3 A, ≤ 10 W
B20 - command output for ON/OPEN IS ≤ 0.3 A, ≤ 10 W
BV - common command output IS ≤ 0.3 A, ≤ 10 W for B10/B20 (wired return line) Service life of the relay output stage ≥ 20 million switching cycles
Initialization time
When voltage is switched on or the module is plugged in 2 ... 22 s
Interference immunity (of process inputs and outputs)
Electrostatic discharge immunity DIN EN 61000-4-2 8 kV / 4 kV Radiated, radio-frequency, electromagnetic field, immunity DIN EN 61000-4-3 10V/m Electrical fast transient/burst immunity DIN EN 61000-4-4 2 kV Surge Immunity DIN EN 61000-4-5 2 kV / 1 kV Conducted disturbances immunity DIN EN 61000-4-6 10 V
24
ORDERING DATA
Order number for complete module: Type: 83SR06-E/R1010 Order no.: GJR2395400R1010
Technical data are subject to change without notice!
ABB Utilities GmbH Postfach 10 03 51 D-68128 Mannheim Kallstadter Straße 1 D-68309 Mannheim Telefon: +49 (0) 621 381-2712 Telefax: +49 (0) 621 381-5958 E-Mail: [email protected] Internet: www.abb.de/utilities
NOTE: We reserve the right to make technical changes or modify the contents of this manual without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction – in whole or in parts – is forbidden without ABB's prior written consent. Copyright© 2004 A B BAll rights reserved