model sv - i series geothermal heat pump sv007...

60
Installation, Operation and Maintenance Manual Model SV - i Series Geothermal Heat Pump 8 733 914 818 (2013/8) SV007 Thru SV070 Made in Florida

Upload: dangnhu

Post on 18-May-2018

247 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Installation, Operation and Maintenance Manual

Model SV - i Series Geothermal Heat Pump

8 73

3 91

4 81

8 (2

013/

8)

SV007 Thru SV070

Made in Florida

Page 2: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

2 | SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

CONTENTS

Model Nomenclature.......................................................... 3

General Description........................................................... 4

Moving and Storage ........................................................... 4

Initial Inspection................................................................ 5

Location............................................................................ 5

Water Quality .................................................................... 5

Installation........................................................................ 7Duct Flanges ............................................................... 7Mounting Vertical Units................................................. 7Mounting Horizontal Units ............................................. 7

Converting Horizontal Supply Air Configuration .................. 8

Condensate Connections ................................................... 8

Duct System...................................................................... 9

Piping ............................................................................... 9

Electrical - High Voltage ................................................... 10Models with Dual Power Supplies ................................. 10460 V Models w/ Constant Air Flow Motors ................... 10Transformer Settings for 208/230 V Units .................... 10

Electrical - Low Voltage .................................................... 11

Unit Controls - UPM ......................................................... 12ECM Interface Board .................................................. 12Dehumidification Method Selector ............................... 13Sequence of Operation ............................................... 14General .................................................................... 15Cooling and Heating Modes ......................................... 15UPM Safety Features .................................................. 15

Options........................................................................... 19Extended Range Option .............................................. 19Unit Mounted Non-Fused Disconnect Switch.................. 19Hot Gas Reheat.......................................................... 19DDC Controls ............................................................ 19Internal 2-Way Water Valve ......................................... 19

Application Considerations .............................................. 20Boiler/Cooling Tower Systems ..................................... 20Geothermal Closed Loop Systems ................................ 21

Certified Performance Table ............................................ 22

Fan Motor Options ........................................................... 23Permanent Split Capacitor Motors (PSC)....................... 23Constant Torque Motors (ECM).................................... 25Constant Airflow Motors (ECM).................................... 27

Standard Blower Motor .................................................... 29

Unit Start Up ................................................................... 32

Maintenance ................................................................... 32

Unit Check Out Sheet................................................. 33Customer Data.......................................................... 33Unit Nameplate Data.................................................. 33Operating Conditions................................................. 33Auxiliary Heat ........................................................... 33

Troubleshooting.............................................................. 34

Temperature/Pressure Table ........................................... 39

Waterside Pressure Drop Table ........................................ 44

Compressor Characteristics ............................................ 45

Corner Weights (HZ) ....................................................... 46

Wiring Diagrams ............................................................. 47

Dimensional Drawings..................................................... 54Vertical .................................................................... 54Horizontal ................................................................ 55

Notes ............................................................................. 56

Page 3: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Model Nomenclature | 3Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

MODEL NOMENCLATURE

SAFETY CONSIDERATIONS

SV 018 - 1 VT C - F L T - P ASERIES

SV REVISION LEVELA - Current

SIZE007 FAN/MOTOR OPTIONS009 P - Standard PSC012 A - Constant Airflow ECM015 T - Constant Torque ECM018024 DISCHARGE AIR CONFIGURATION030 T - Top036 S - Straight041 E - End042 B - Bottom048060 RETURN AIR CONFIGURATION070 L - Left

R - RightVOLTAGE

1 208-230/60/1 WATER CONNECTIONS2 277/60/1 F - Front3 208-230/60/34 460/60/3 COAX OPTIONS

C - CopperCABINET CONFIGURATION N - Cupro-Nickel

HZ - HorizontalVT - VerticalCF - Downflow (Counterflow)

R

C

F

D

R

W

R

F

D

R

R

WARNING:Installation and servicing of this equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service the equipment.

DANGER: Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could cause personal injury or death.

CAUTION: When working on equipment, always observe precautions described in the literature, tags, and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing, and place a fire extinguisher close to the work area.

NOTE: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements.

NOTE: All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.

NOTE: To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. Doing so may affect the unit’s warranty. The mechanical components and filters will quickly become clogged with construction dirt and debris, which may cause system damage.

Page 4: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

4 | General Description SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

GENERAL DESCRIPTIONThe SV series water-to-air heat pump provides an unmatched combination of performance, features and flexibility for both high performance new construction applications and replacement of existing water-to-air heat pumps. All units are certified by the Air conditioning, Heating and Refrigeration Institute (AHRI) to AHRI/ANSI/ASHRAE/ISO standard 13256-1 for water-to-air and brine-to-air heat pumps at both Water Loop Heat Pump and Ground Loop Heat Pump application points.

These units are safety listed with Intertek Test Labs (ETL) to cUL standard 1995. These units meet all current applicable requirements of ASHRAE 90.1.

SV series units are designed to operate with entering fluid temperatures between 50°F and 100°F in cooling and 50°F and 80°F in heating with the base configuration. With the extended range option, SV series models can operate with entering fluid temperatures between 40°F and 120°F in cooling and between 20°F and 90°F in heating. SV units can accomodate a wide range of air temperatures, however, standard SV models should not be used for 100% outside air without consulting the factory applications group. 100% outside air routinely requires higher levels of dehumidifcation than is available from equipment designed for return air applications.

SV series units are available in three basic configurations: vertical top supply air (VT), horizontal end supply air or straight through supply air (HZ) and counterflow down supply air (CF). Each of these configurations are available with either left or right hand return air. HZ models can have the supply air field converted from end discharge air to straight through with no extra parts required.

SV units are designed and rated for indoor installation only. SV units should not be installed in environments that fall below freezing or exceed 100°F ambient. SV cabinets are constructed of heavy gauge G-90 galvanized steel and will resist most common types of corrosion for the life of the equipment.

SV series units are offered with a wide range of factory installed options including: PSC, constant torque ECM or constant air flow ECM fan motors, hot gas reheat, tin plated air coils, on board DDC controls, copper or cupro nickel water coils and more.

On board safety features will protect the major unit components from damage under most foreseable installation and operation problems.

MOVING AND STORAGEIf the equipment is not needed for immediate installation upon arrival at the job site, it should be left in its packaging and stored in a clean, dry area. Units must be moved and stored in the normal upright position at all times.

Use caution to avoid damage to filter racks and duct flanges when storing or handling units.

Some options are offered in limited sizes and/or voltages.

NOTE: Never lift or move units by filter racks, external piping or attached options/accessories.

NOTE: Never stack units when transporting them.

NOTE: When storing units:

Do not stack units larger than 6 tons capacity!

Do not stack vertical or counterflow units under 6 tons capacity more than 2 high

Do not stack horizontal units 6 tons capacity more than 3 high

Page 5: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Initial Inspection | 5Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

INITIAL INSPECTIONBe certain to inspect all cartons or crates on each unit as recieved at the job site before signing the freight bill. Verify that all items have been received and that there is no visible damage. Note any damage or shortage on all copies of the freight bill. In the event of damage or a shortage it is the responsiblity of the purchaser to file the necessary claims with the carrier. Concealed damage not discovered until after removing the units from pacakaging must be reported to the carrier within 24 hours of receipt.

LOCATIONLocate the unit in an indoor area that allows easy access to the filter, front access panel and blower access panel, and has enough room for service personnel to perform maintenance and repair work. Provide sufficient room to make fluid, electrical and ductwork connections.

Locate the unit in conditioned space and avoid installation in corrosive environments. If the unit is installed in a confined space, such as a closet, provisons must be made for return air to freely enter the the face of the unit’s air coil.

Unit condensate drains are not internally trapped. Allow room below the unit base for horizontal and counterflow models for an adequate condensate trap.

WATER QUALITY

Maintaining proper water quality is important for insuring a long and trouble free service life for an SV series heat pump.

For closed loop and boiler/tower systems water chemistry can be checked and easily maintained to insure that corrosive elements, dissolved oxygen and pH levels are kept in check. It is important to insure that any additive, antifreeze or corrosion inhibitor that is added to the water loop is compliant with all applicable laws and regulations and is compatible with copper, brass and bronze alloys. Insure that all recommended safety precautions are followed when handling or adding chemicals to the water loop.

For open loop systems, water quality is very important. Table #1 shows acceptable ranges for a variety of water quality factors. The three main concerns in open loop installations are scaling, corrosion and fouling.

In installations with hard water, scaling due to a buildup of carbonates on the heat exchanger wall can gradually degrade the heat pump performance over time. Heat pumps that are affected by scaling may exhibit low suction pressures in heating and high head pressures in cooling with a gradual loss of capacity and efficiency. Scaled heat exchangers can be cleaned by a qualified technician but care should be taken to avoid scaling in the first place.

To limit scaling, water flow rates should be kept at 3 gallons/minute per nominal cooling ton (a 10°F temperature rise in cooling) and care should be taken to avoid air in the water lines from suction side leaks. Cupro-nickel coils are generally recommended.

NOTE: Do not locate the unit above supply piping.---------------------------------------------------------------------Do not locate the unit in areas subject to freezing or in areas subject to temperature or humidity extremes.

NOTE: SV series packaged units are not approved for outdoor installation. Units must be installed in conditioned space that is not subject to extremes of temperature or humidity to avoid cabinet sweating and/or equipment damage.

NOTE: Do not use SV series units for temporary heating, air conditioning or ventilation during construction, especially when plastering, sanding or painting. Care should be taken to avoid introduction of dust, paint or debris into the air coil.

NOTE: Failure to insure proper water quality and flow rates can shorten the life of the heat pump and potentially void the unit warranty.

Page 6: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

6 | Water Quality SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

In installations with high hydrogen sulfide, chlorine or ammonia, corrosion is a potential problem. In these installations a cupro-nickel heat exchanger is recommended along with maintaining proper flow and keeping air out of the system. If water quality is outside of the values in Table #1, then a closed loop is recommended.

Fouling due to iron bacteria can also pose problems in some open loop installations. Iron bacteria fouling can quickly degrade system performance and plug heat exchangers.

Air in the water system will greatly accellerate the fouling or corrosion process.

Table 1: Water Quality

POTENTIAL PROBLEM

Water Characteristic Acceptable Value

Copper Cupro-Nickel

pH (Acidity/Alkalinity) 7-9 7-9

SCALINGHardness (CaCO3, MgCO3) < 350 ppm < 350 ppm

Ryznar Stability Index 6.0 - 7.5 6.0 - 7.5

Langelier Saturation Index -0.5 - +0.5 -0.5 - +0.5

CORROSIONHydrogen Sulfide (H2S) < 0.5 ppm * 10-50 ppm

Sulfates < 125 ppm < 125 ppm

Chlorine < 0.5 ppm < 0.5 ppm

Chlorides < 20 ppm < 150 ppm

Carbon Dioxide < 50 ppm < 50 ppm

Ammonia < 2 ppm < 2 ppm

Ammonia Chloride < 0.5 ppm < 0.5 ppm

Ammonia Nitrate < 0.5 ppm < 0.5 ppm

Ammonia Hydroxide < 0.5 ppm < 0.5 ppm

Ammonia Sulfate < 0.5 ppm < 0.5 ppm

Dissolved Solids < 1,000 ppm < 1,500 ppm

IRON FOULINGIron (Fe2+ Iron Bacteria Potential) < 0.2 ppm < 0.2 ppm

Iron Oxide < 1 ppm < 1 ppm

EROSIONSuspended Solids < 10 ppm, < 600 µm size ** < 10 ppm, < 600 µm size **

Maximum Water Velocity 6 ft/sec 6 ft/sec

* No "rotten egg" smell present at < 0.5 ppm H2S.

** Equivalent to 30 mesh strainer

Page 7: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Installation | 7Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

INSTALLATIONThe following are instructions to follow for installation of all SV Series components.

Duct FlangesSV heat pumps feature fold-out return and supply air duct flanges. These fold-out flanges allow the heat pumps to more easily fit through doorways and other tight spaces, and also prevent damage in shipping and handling.

It is recommended that all fold-out flanges be folded-out once the heat pump is installed to insure that return and supply air flow is not obstructed. These flanges can be easily folded using standard or duckbill pliers. Once folded out these flanges can be used to support light ductwork loads.

Mounting Vertical UnitsSV Series vertical and counterflow units should be mounted level on a vibration absorbing pad slightly larger than the unit base in order to minimize vibration transmission from the unit to the building structure. See Figure #1. It is generally not necessary to anchor the unit unless required by local code.All major service access for the SV Series vertical and counterflow models is from the front side of the unit. When installing the unit in a confined space such as a closet, insure that the service panel screws are accesible, that the filter can be replaced without damage and that water and electrical connections are accesible. For models with a unit mounted disconnect switch, make sure the switch can be easily seen and operated.To reduce sound transmission, units should be installed using flexible electrical conduit and hose kits. Care should be taken to insure that no part of the unit cabinet is touching part of the building structure. For ducted return applications, a flexible duct connection should be used. Refer to Figure’s #12, #13 and #13.

Figure # 1 Mounting Vertical Units

Mounting Horizontal UnitsWhile horizontal units may be installed on any level surface strong enough to hold their weight, they are typically suspended above a ceiling by threaded rods. The rods are usually attached to the unit corners by hanger bracket kits (P/N 930-008). (See Figure #2).

Figure # 2 Hanger BracketThe rods must be securely anchored to the ceiling. Refer to the hanging bracket assembly and installation instructions (Included with the unit) for details.

Vibration Mounting Pad

Page 8: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

8 | Converting Horizontal Supply Air Configuration SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Horizontal units installed above the ceiling must conform to all local codes. An auxiliary drain pan if required by code, should be at least four inches larger than the bottom of the heat pump.Plumbing connected to the heat pump must not come in direct contact with joists, trusses, walls, etc.. Some applications require an attic floor installation of the horizontal unit. In this case the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing mesh. In both cases, a 3/4" drain connected to this secondary pan should be run to an eave at a location that will be noticeable.

CONVERTING HORIZONTAL SUPPLY AIR CONFIGURATIONThe supply air location on SV Series Horizontal units can be quickly field converted from end blow to straight through or vice-versa. To convert the supply air direction, follow the steps below:1. If connected to power, shut off the unit and

disconnect switch or circuit breaker.2. Unscrew and remove the blower access panel.3. Disconnect the wires from the unit electrical

box to the blower motor. Note which speed taps are wired for units with PSC or constant torque motors.

4. Unscrew and carefully remove the blower panel with the blower and motor attached. Be careful not to damage the refrigerant coils or any other internal unit components.

5. Remove the blower support brackets from the bottom of the blower housing and relocate them to the top of the blower housing.

6. Turn the blower panel 180° so that the blower support brackets are now at the bottom of the blower.

7. Insert the blower panel with the blower and motor into the desired location. Be careful not to damage the refrigerant coils or any other internal unit components. Screw the panel into place.

8. Replace the wires between the blower motor and electrical box. Make sure to connect wires to the proper speed taps.

9. Replace the blower access panel.10. Reconnect power to the unit.

CONDENSATE CONNECTIONSA drain line must be connected to the heat pumpand pitched away from the unit a minimum of 1/8”per foot to allow the condensate to flow away fromthe unit.This connection must be in conformance with localplumbing codes. A trap must be installed in thecondensate line to insure free condensate flow.(Heat Pumps are not internally trapped). A vertical air vent is sometimes required to avoid air pockets.(See Figure #3).

Figure # 3 Condensate Drain

The depth of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included.

Units larger than six tons include an integral angle iron frame with mounting holes present. (See unit horizontal detail drawing).

NOTE: If the unit is located in a crawl space, the bottom of the unit must be at least 4" above grade to prevent flooding of the electrical parts due to heavy rains.

Page 9: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Duct System | 9Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

The horizontal unit should be pitched approximately 1/4” towards the drain in both directions, to facilitate condensate removal. (See Figure #4)

Figure # 4 Pitched Unit

DUCT SYSTEMAll SV Series models are provided with a return air duct flange and supply air duct connections.Refer to unit Dimensional Drawings for physical dimensions of the collar and flange. (Pg#47)A flexible connector is recommended for supply and return air duct connections on metal duct systems. All metal ducting should be insulated with a minimum of 1” (one inch) duct insulation to avoid heat loss or gain and prevent condensate from forming during the cooling operation. Application of the unit to uninsulated duct work is not recommended as the unit’s performance will be adversely affected.

If the unit will be installed in a new installation with new duct work, the installation should be designed using current ASHRAE procedures for duct sizing. If the unit will be connected to an existing duct system, a check should be made to assure that the duct system has the capacity to handle the air required for the unit application. If the duct system is too small, larger duct work must be installed. Be certain to check for existing leaks and repair.

The duct system and all diffusers should be sized to handle the designed air flow quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be insulated. There should be no direct straight air path through the air grill into the heat pump. The return air inlet to the heat pump must have at least one 90° turn away from the space return air grill. If air noise or excessive air flow are a problem, the blower speed can be changed to a lower speed to reduce air flow.

PIPINGSupply and return piping must be as large as the unit connections on the heat pump (larger on long runs). Never use flexible hoses of a smaller inside diameter than that of the water connections on the unit. SV Units are supplied with either a copper or optional cupro-nickel condenser. Copper is adequate for ground water that is not high in mineral content. Refer to Table #1.

In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended. Both the supply and discharge water lines will sweat if subjected to low water temperature. These lines should be insulated to prevent damage from condensation.All manual flow valves used in the system must be ball valves. Globe and gate valves must not be used due to high pressure drop and poor throttling characteristics. Always check carefully for water leaks and repair appropriately. Units are equipped with female pipe thread fittings. Consult the specification sheets for sizes.

Teflon tape sealer should be used when connecting water piping connections to the units to insure against leaks and possible heat exchanger fouling. Do not overtighten the connections. Flexible hoses should be used between the unit and the rigid system to avoid possible vibration. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing.

NOTE: Do not connect discharge ducts directly to the blower outlet.

The factory filter rack should be left in place on a free return system.

Should your well driller express concern regarding the quality of the well water available or should any known hazards exist in your area, we recommend proper testing to assure the well water quality is suitable for use with water source equipment. (Refer to Table #1)

Page 10: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

10 | Electrical - High Voltage SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Pressure/temperature ports are recommended in both the supply and return lines for system flow balancing. The water flow can be accurately set by measuring the water-to- refrigerant heat exchangers water side pressure drop. See the unit specification sheets for the water flow and pressure drop information.

ELECTRICAL - HIGH VOLTAGEAll field installed wiring must comply with the National Electric Code as well as all applicable local codes. Refer to the unit electrical data on the unit name plate for wire and branch circuit protection sizing. Supply power voltage and phasing should match the required voltage and phasing shown on the unit name plate. Operating the unit below the minimum voltage, above the maximum voltage or with incorrect phasing can result in poor system performance or damage to the heat pump. All field wiring should be installed by qualified and trained personnel. Refer to the unit wiring diagram for field connection requirements.

Power wiring to the heat pump should be enclosed in flexible conduit to minimize the transmission of vibration from the unit cabinet to the building.For heat pumps with unit mounted disconnect switches, field power should be connected to the marked terminals on the disconnect switch. For heat pumps without unit mounted disconnect switches (except for 460 volt units noted below and units with dual power supply), power is connected to the line (L) side of the compressor contactor and the ground lug in the unit electrical box.

Models with Dual Power SuppliesFor models with dual power supplies, one power supply feeds the compressor and a second power supply feeds the unit fan motor and control circuit. The compressor power supply should be connected to the line (L) side of the compressor contactor. The fan motor and control circuit power supply should be connected to a provided terminal block. Care should be taken to insure that each power supply meets the voltage, amperage and phase requirements of its load. Refer to the unit nameplates for requirements.

460 V Models with Constant Air Flow Motors (SV015-SV070)460 volt SV heat pumps with the constant airflow motor option require a properly sized neutral wire with the power supply wiring in addition to the three high voltage wires and the ground wire. These units employ a 265 V motor that requires power from one phase of the 460 V supply and the neutral wire.

For 460 V models with constant air flow motors and a unit mounted disconnect switch, the power wires and neutral wire should be connected to the appropriate terminals on the disconnect switch and its enclosure. For units without a disconnect switch, power and neutral wires should be connected to a provided 4 pole terminal block in the unit electrical box

Transformer Settings for 208/230 V UnitsAs factory built, all 208/230 V units are wired for 230 V operation. For jobsites with a 208 V power supply, the primary leads on the unit transformer will need to be changed from 240 V to 208 V. Refer to the unit wiring diagram for details.

NOTE: Water piping exposed to extreme, low ambient temperatures is subject to freezing

NOTE: Never exceed the recommended water flow rates. Serious damage or erosion of the water to refrigerant heat exchanger could occur.

NOTE: All power connections must be properly torque to avoid the risk of overheating.

WARNING: The power supply ground wire should never be used as a neutral wire.

Page 11: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Electrical - Low Voltage | 11Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

ELECTRICAL - LOW VOLTAGEFor heat pumps with PSC or constant torque fan motors, all thermostat wiring is connected to a terminal block located in the unit electrical box. For heat pumps with a constant air flow fan motor, thermostat wiring is connected to a removable terminal strip located on the ECM motor control board located in the electrical box. Refer to the unit wiring diagram for connection details.

Unless provided with DDC controls, the SV heat pump can be controlled by most commonly available single stage heat pump thermostats. Note that the reversing valve on the SV series is energized when the unit is in the cooling mode. Thermostats should be located on an interior wall away from supply ducts. Avoid locations subject to direct sunlight or drafts, or external walls. Thermostat wiring should be 18 AWG. Refer to the installation instructions for the thermostat for further details.

SV heat pumps are supplied with a 75 VA control transformer as standard. The VA capacity of the transformer should be considered when connecting low voltage accessories to the heat pump such as thermostats or solenoid valves.

Table #2 shows the VA draw of factory mounted components in the SV heat pump. The total VA draw of the heat pump internal components plus any attached accessories must be lower than the VA capacity of the unit control transformer.

WARNING: Never route control wiring through the same conduit as power supply wiring.

Exceptionally long runs of thermostat wire should be avoided to prevent voltage drops in the control circuit.

NOTE: Exceeding the transformer capacity can result in low control voltage, erratic unit operation or damage to the heat pump.

Table 2: Low Voltage VA Draw

Standard Construction

Hot Gas Reheat

Component VA Component VA

Blower Relay (PSC motors only) 6-7 Total from

‘Standard’ 22-26

Reversing Valve Solenoid 8-9

Additional Control Relays

12-14

Compressor Contactor 6-8

Hot Gas Reheat Solenoid

8-9

UPM board 2

Total VA draw 22-26 Total VA draw 42-49

Page 12: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

12 | Unit Controls - UPM SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

UNIT CONTROLS - UPMECM Interface BoardThermostat wiring is connected to the 10 pin screw type terminal block on the lower center portion of the ECM Interface Board (Refer to Figure #5, item [5]). In addition to providing a connecting point for thermostat wiring, the interface board also translates thermostat inputs into control commands for the Electronic Commutated Motor (ECM) DC fan motor and displays an LED indication of operating status. The thermostat connections and their functions are as follows:

Figure # 5 [1] Motor harness plug[2] Blower CFM adjustment[3] Motor settings[4] Dehumidification indication[5] Thermostat contact inputs[6] CFM count indicator[7] Thermostat input status indication[8] Reheat digital outputs[9] Thermostat outputs[10] 24 VAC[11] Dehumidification method selector

• CFM Count Indicator (Figure #5, Item [5]) blinks to indicate approximate airflow in CFM and may flicker when unit is off. Each blink of the LED represents approximately 100 CFM of air delivery, for example, if the LED blinks 12 times, pauses, blinks 12 times, etc. the blower is delivering approximately 1200 CFM.

Airflow SelectorThe airflow selector (Figure #5, items [2] & [3]) allows airflow adjustment to meet application requirements and to ease troubleshooting.

ADJUST Selector can be adjusted to NOM, (+), (-), or TEST. NOM, (+) and (-) can be adjusted as needed by application. TEST is used for troubleshooting to override unit airflow to 100%

Figure # 6

CFM LED indication is an approximation. Utilize conventional Test and Balance equipment for accurate airflow measurement.

10 1

789 5 46

3

11

Thermostat Options

Y1 First Stage Compressor Operation

G Fan

O Reversing Valve (energized in cooling)

W1 Auxiliary Electric Heat (runs in conjunction with compressor)

NC Transformer 24 VAC Common (extra connection)

C1 Transformer 24 VAC Common (primary connection)

R Transformer 24 VAC Hot

H Dehumidification Mode

Only one switch can be enabled at a time. Refer to Figure #7 for each airflow setting.

NOTE: CFM Selector (FIg #5, Item [2]) must remain with only “A” being enabled.

Page 13: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Unit Controls - UPM | 13Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

The other DIP switch bank is used to select the proper program in the ECM motor for the unit.

Dehumidification Method SelectorDehumidification method selector (Figure #5, item [11]) is used to select between the following two methods:1. Units equipped with optional Hot Gas Reheat,

on dehumidification call (the “H” terminal on the thermostat is energized) the reheat outputs will energize the hot gas reheat valve in the circuit and the heat pump will start in dehumidification mode. Dehumidificationselector (Figure #5, item [11]) should be selected to ‘YES’.

2. Units without optional Hot Gas Reheat, on dehumidification call, the heat pump fan will operate at a lower speed to increase dehumidification while cooling. Dehumidification selector ((Figure #5, item [11]) should be selected to ‘NO’.

3. To the left of the red and green status LED’s is a row of 1/4” male quick connects. These are used to pass thermostat inputs on to the rest of the control circuit. Remember to always turn off unit power at the circuit breaker before attaching or disconnecting any wiring from these connections to avoid accidental short circuits that can damage unit control components.

Dehumidification indicator LED (Figure #5, item [4]) will energize when dehumidification call is present. Refer to Figure #7.

Figure # 7

NOTE: Do not set the ADJ DIP switch to the (-) setting when electric heaters are installed. Doing so may cause the heaters to cycle on their thermal overload switches, potentially shortening the life of the switches.

NOTE: Always disconnect power before changing jumper positions on the interface board and reset the unit afterward.

In this mode, the heat pump will only dehumidify the space when it is running in cooling mode.

Page 14: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

14 | Unit Controls - UPM SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Sequence of OperationUPM Sequence of Operation (SOO) Flow Chart

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES YES

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

Y1=1

V > 18VAC

HPC = 1

LPC = 1

FRZ > TEMPLIM

CON > 0

INITIALPOWER UP T > ASC OR

RS SEC

TIME > 30SEC

TIME > 120SEC

COUNT = 2

Start Timer

Start Timer

CC Output = On

CC Output = Off

Blink Code On Status LEDReport Alarm Fault

Hard LockoutALR Output = On/Pulse

Blink Code On Status LEDSoft Lockout

Record Alarm Start Counter (If Applicable)

Start Anti Short Cycle

Start Random Start Up

Lockout Can Be Set To 4 Via Dip Switch

Power/Switchs/SensorStatus Check

LEGEND:HPC - HIGH PRESSURE CUTOUTLPC - LOW PRESSURE CUTOUTFRZ - FREEZE PROTECTION CONDITIONCON - CONDENSATE OVERFLOW CONDITIONCC - COMPRESSOR COILASC - ANTI SHORT CYCLERS - RANDDOM START

Page 15: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Unit Controls - UPM | 15Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

GeneralSV series heat pumps are designed to be controlled by a standard 1 heat / 1 cool heat pump thermostat. The heat pump control circuit operates on 24 VAC control voltage regardless of the unit supply voltage. If direct digital control is required then the heat pump needs to be supplied with a DDC control option.

Fan operation is controlled by the “G” terminal on the heat pump thermostat terminal block. When “G” is energized the unit fan motor will start operating. For heat pumps with PSC motors, the fan will immediately ramp up to 100% air flow. For heat pumps with constant torque ECM motors, the fan will ramp up to 100% air flow over a 30 second period. For heat pumps with constant air flow ECM motors the fan will ramp up to 70% air flow over a 30 second period if there is no call for compressor operation (“Y”). If there is a call for compressor operation along with a call for fan operation, then the fan will ramp to 100% air flow.

Compressor operation is controlled by the “Y” terminal on the heat pump thermostat terminal block. When “Y” is energized, a signal to start the compressor is sent to the Unit Protection Module (UPM). The UPM checks a number of safety features before then starting the compressor. If any of the safety features connected to the UPM is in a fault condition, the UPM will not start the compressor and will flash a fault code on the red status LED indicating the nature of the fault.

Additionally the UPM will delay compressor operation randomly on initial start up (random start delay) and will prevent the compressor from restarting with less than 5 minutes of off time (anti short cycle delay). Once all faults are cleared and the time delays are satisfied, the UPM will energize the compressor. The compressor will operate as long as the thermostat calls for “Y” and there are no faults. Refer to the troubleshooting chart for fault diagnostics.

Cooling and Heating ModesSV series heat pumps operate in cooling with the reversing valve energized. When the “O” terminal is energized, the heat pump will be in the cooling mode, however, will not be actively cooling until the “Y” and “G” terminals are also energized. If the “Y” and “G” terminals are energized without the “O” terminal, then the heat pump will operate in the heating mode.

UPM Safety Features

Figure # 8 [1] Board Power Indicator[2] UPM Status LED Indicator[3] Water Coil Freeze Protection Temperature Selection[4] Air Coil Freeze Protection Temperature Selection[5] UPM Board Settings[6] Water Coil Freeze Connection[7] Air Coil Freeze Connection[8] LED Unit Display Connection[9] 24VAC Power Input[10] Compressor Contact Output[11] High Pressure Switch Connection[12] Call for Compressor Y1[13] Low Pressure Switch Connection[14] 24VAC Power Common[15] Condensate Overflow Sensor[16] Dry Contact [17] UPM Ground Standoff

If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit malfunction output or relay.

If the thermostat is provided with a malfunction light powered off of the common (C) side of the transformer, a jumper between “R” and “COM” terminal of “ALR” contacts must be made.

1

2

3

4

5

6 7 9 10

111213

17

1415 168

Page 16: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

16 | Unit Controls - UPM SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Each unit is factory provided with a Unit ProtectionModule (UPM) that controls the compressor operation and monitors the safety controls that protect the unit.

Safety controls include the following:• High pressure switch located in the refrigerant

discharge line and wired across the HPC terminals on the UPM

• Low pressure switch located in the unit refrigerant suction line and wired across terminals LPC1 and LPC2 on the UPM.

• Water side freeze protection sensor, mounted close to condensing water coil, monitors refrigerant temperature between condensing water coil and expansion valve or capillary tube. If temperature drops below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 30°F, however this can be changed to 15°F by cutting the R30 or Freeze1 resistor located on top of DIP switch SW1.

Figure # 9

• Evaporator freeze protection sensor, mounted after the thermal expansion device and the evaporator, monitors refrigerant temperature between the evaporator coil and thermal expansion valve. If temperature drops below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 30°F. (Figures #9 and #10)

Figure # 10 • The condensate overflow protection sensor is

located in the drain pan of the unit and connected to the ‘COND’ terminal on the UPM board. (Figure #11)

Figure # 11

If the thermostat is provided with a malfunction light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected directly to the (ALR) contact on the unit’s UPM board.

UPM Board Dry Contacts are Normally Open (NO)

NOTE: If unit is employing a fresh water system (no anti-freeze protection), it is extremely important to have the Freeze1 R30 resistor set to 30°F in order to shut down the unit at the appropriate leaving water temperature and protect your heat pump from freezing if a freeze sensor is included.

Page 17: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Unit Controls - UPM | 17Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

The UPM Board includes the following features:• ANTI-SHORT CYCLE TIMER: 5 minute delay on

break timer to prevent compressor short cycling.

• RANDOM START: Each controller has an unique random start delay ranging from 270 to 300 seconds on initial power up to reduce the chance of multiple unit simultaneously starting at the same time after power up or after a power interruption, thus avoiding creating large electrical spike.

• LOW PRESSURE BYPASS TIMER: If the compressor is running and the low pressure switch opens, the controller will keep the compressor ON for 120 seconds. After 120 seconds if the low pressure switch remains open, the controllers will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low pressure switch closes and the anti-short cycle time delay expires. If the low pressure switch opens 2-4 times in 1 hour, the unit will enter a hard lockout. In order to exit hard lockout power to the unit would need to be reset.

• BROWNOUT/SURGE/POWER INTERRUPTION PROTECTION: The brownout protection in the UPM board will shut does the compressor if the incoming power falls below 18 VAC. The compressor will remain OFF until the voltage is above 18 VAC and ANTI-SHORT CYCLE TIMER (300 seconds) times out. The unit will not go into a hard lockout.

• MALFUNCTION OUTPUT: Alarm output is Normally Open (NO) dry contact. If pulse is selected the alarm output will be pulsed. The fault output will depend on the dip switch setting for "ALARM". If it is set to "CONST", a constant signal will be produced to indicate a fault has occurred and the unit requires inspection to determine the type of fault. If it is set to "PULSE", a pulse signal is produced and a fault code is detected by a remote device indicating the fault. See L.E.D Fault Indication below for blink code explanation. The remote device must have a malfunction detection capability when the UPM board is set to "PULSE".

• DISPLAY OUTPUT: The Display output is a pulse output connected to the Unit Diagnostic Display (UDD) and it pulses 24VAC when the unit is in an lockout alarm condition.

UPM Board Factory Default Settings

TEMP 30°F

LOCKOUT 2

RESET Y

ALARM PULSE

TEST NO

UPM DIP SWITCH DEFAULT POSITION

lockout 4 2

reset R Y

alarm Cont pulse

test yes no

Table 3: UPM Fault Blink Codes

LED Blinks Fault Fault Criteria

None NoneAll fault conditions

nominal

1 High Pressure

Refrigerant discharge pressure has

exceeded 600 PSIG

2 Low Pressure

Refrigerant suction pressure has fallen

below 40 PSIG

3

Water Coil Freeze

Condition

Refrigerant temperature to the water coil has fallen below 30°F for 30

seconds

4Condensate

Overflow

Condensate levels in the unit drain pan are

too high

5Air Coil Freeze

Condition

Refrigerant temperature to the air coil has fallen below 30°F for 30 seconds

6 Brown OutControl voltage has fallen below 18 VAC

If 24 VAC output is needed R must be wired to ALR-COM terminal; 24 VAC will be available o the ALR-OUT terminal when the unit is in the alarm condition.

Page 18: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

18 | Unit Controls - UPM SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

• TEST DIP SWITCH: A test dip switch is provided to reduce all time delays settings to 10 seconds during troubleshooting or verification of unit operation.

• FREEZE SENSOR: The default setting for the freeze limit trip is 30°F (sensor number 1); however this can be changed to 15°F by cutting the R30 resistor located on top of the DIP switch SW1. The default setting for the freeze limit trip is 30°F (sensor number 2); however this can be changed to 15°F by cutting the R24 resistor located on top of the DIP switch SW1. Since freeze sensor 2 is dedicated to monitor the evaporator coil it is recommended to leave the factory default setting on the board. The UPM controller will constantly monitor the refrigerant temperature with the sensor mounted close to the condensing water coil between the thermal expansion valve and water coil. If temperature drops below or remains at the freeze limit trip for 30 seconds, the controller will shut the compressor down and enter into a soft lockout condition. Both the status LED and the Alarm contact will be active. The LED will flash (three (3) times) the code associated with this alarm condition. If this alarm occurs 2 times (or 4 if Dip switch is set to 4) within an hour the UPM controller controller will enter into a hard lockout condition. It will constantly monitor the refrigerant temperature with the sensor mounted close to the evaporator between the thermal expansion valve and evaporator coil as shown in Figure #10. If temperature drops below or remains at the freeze limit trip for 30 seconds, the controller will shut the compressor down and enter into a soft lockout condition. Both the status LED and the Alarm contact will be active. The LED will flash (three (6) times) the code associated with this alarm condition. If this alarm occurs 2 times (or 4 if Dip switch is set to 4) within an hour the controller will enter into a hard lockout condition.

• INTELLIGENT RESET: If a fault condition is initiated, the 5 minute delay on break time period is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition still exists or occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. A single condensate overflow fault will cause the unit to go into a hard lockout immediately, and will require a manual lockout reset.

• LOCKOUT RESET: A hard lockout can be reset by turning the unit thermostat off and then back on when the “RESET” dip switch is set to “Y” or by shutting off unit power at the circuit breaker when the “RESET” dip switch is set to “R”.

NOTE: Operation of unit in test mode can lead to accelerated wear and premature failure of components. The "TEST" switch must be set back to "NO" after troubleshooting/servicing.

It is recommended to have a flow switch to prevent the unit from running if water flow is lost.

The blower motor will remain active during a lockout condition. ECM Interface Board Thermostat Connections

Page 19: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Options | 19Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

OPTIONSExtended Range OptionSV heat pumps are supplied standard with capillary style expansion device tuned to typical boiler/tower system operating conditions. For applications that will experience more extreme fluid flow rates or temperatures (heating fluid temperatures below 50°F and/or cooling fluid temperatures below 60°F or above 100°F), an extended range option is required. The extended range option on the SV consists of a bi-flow, balanced port thermal expansion valve and an insulated water-to-refrigerant heat exchanger. With the extended range option installed SV units can provide heating with fluid temperatures as low as 40°F and as high as 120°F and cooling with fluid temperatures as low as 20°F and as high as 90°F.

Unit Mounted Non-Fused Disconnect SwitchSV heat pumps can be supplied with an optional unit mounted disconnect switch mounted to the electrical corner post of the unit. Field electrical wiring is connected to the switch and the switch then routes power to the heat pump electrical box. When the switch is in the “OFF” position, the heat pump electrical box is completely de-energized.

Hot Gas Reheat(Available on size 015 and larger)SV series heat pumps size 015 and larger can be provided with hot gas reheat for active dehumidification. In operation hot gas reheat dehumidifies space by cooling the air and removing moisture and then reheating the air back to a neutral temperature using waste heat from the compressor. The net effect is to decrease the relative humidity of the space without changing the sensible temperature. The major components of the hot gas reheat option are the hot gas reheat coil, the reheat solenoid valve and the control circuit. When the control circuit energizes the heat pump in reheat mode, the heat pump will operate in the cooling mode. The hot gas solenoid valve diverts the compressor discharge gas to the reheat coil which is mounted downstream of the unit evaporator. This hot gas re-heats the cooled air coming off of the evaporator.

To function, heat pumps with hot gas reheat must be controlled by both a thermostat and a humidistat (or a combination thermostat/humidistat). The humidistat must provide a dry contact closure on a rise in humidity above set point.

At water temperatures of 85° F, the reheat coil can recover 95% to 100% of the sensible capacity of the evaporator. At water temperatures below 60°F, the reheat coil can only recover 5% to 25% of the sensible capacity of the evaporator.Refer to the unit wiring diagram for control circuit details.

DDC ControlsFactory mounted DDC controls are available as an option on SV series heat pumps. Please refer to the DDC control manuals and literature for details on this option.

Internal 2-Way Water ValveIn many applications, including variable pumping and well water installations, a motorized water valve is required on the heat pump water circuit. On the SV series this water valve can be factory mounted and wired internally to the unit. The SV series internal water valve option features a 24VAC motorized water valve rated to 450 psig working pressure. This valve is wired to open on a thermostat call for compressor operation (heating or cooling) and will remain open as long as the thermostat calls. The valve can remain seated with up to 20 psi of back pressure on all sizes.The valve consists of two main parts: the valve body and the actuator. The valve body is brazed into the leaving water line of the heat pump and is a permanent part of the unit. The valve actuator can be easily removed from the valve body for service.Refer to the water side pressure drop table in the troubleshooting section of this manual to determine the appropriate pressure drop across the heat pump with and without the water valve option.

Note that the ability of the reheat coil to reheat cooled air back to a neutral temperature is affected by the water temperature of the system.

Note that the 2-Way Water Valve option will add additional pressure drop between the water in and water out connections of the heat pump.

Note that this water valve cannot be used as an isolation valve.

Page 20: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

20 | Application Considerations SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

APPLICATION CONSIDERATIONSBoiler/Cooling Tower SystemsTo assure adequate cooling and heating performance, the cooling tower and boiler water loop temperature should be maintained between 50°F to 75°F in the heating mode and 60°F to 110°F in the cooling mode. In the cooling mode, heat is rejected from the unit into the water loop. A cooling tower provides evaporative cooling to the loop fluid; thus, maintaining a constant supply temperature to the unit. When utilizing an open cooling tower, chemical water treatment is mandatory to ensure the water is free of corrosive materials.A secondary heat exchanger (plate frame between the unit and the open cooling tower) may also be used. In the heating mode, heat is absorbed from the water loop to the unit. A boiler can be utilized to maintain the loop within the proper temperature range.

No unit should be connected to the supply or return piping until the water system has been completely cleaned and flushed to remove dirt, piping chips or other foreign material. Supply and return hoses should be connected together during this process to ensure the entire system is properly flushed.After the cleaning and flushing has taken place the unit may be connected to the water loop and should have all valves wide open.See Figure #12

Figure # 12 Cooling/Boiler Application

NOTE: It is imperative that all air is eliminated from the closed loop side of the heat exchanger to prevent condenser fouling.

Note: See Figure #3 for Condensate Drain

Page 21: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Application Considerations | 21Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Geothermal Closed Loop SystemsOperation of an SV Series unit on a closed loop application requires the extended range option.

Utilizing Ground Loop Pumping Package (GLP), makes the installation easy. Anti-freeze solutions must be utilized when low loop temperatures are expected to occur. Refer to the installation manuals for more specific instructions. See Figure #13

Figure # 13 Earth Coupled Application

CAUTION: Closed loop and pond applications require specialized design knowledge. No attempt at these installations should be made unless the dealer has received specialized training.

Note: See Figure #3 for Condensate Drain

Page 22: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

22 | Certified Performance Table SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

CERTIFIED PERFORMANCE TABLETable 4: SV Series AHRI Ratings

MODELPSC Motor (Base)

WLHP GLHP

Cooling Capacity EER

Heating Capacity COP

Cooling Capacity EER

Heating Capacity COP

SV007 6,100 12.20 7,800 5.30 6,800 15.10 4,900 3.40

SV009 8,200 12.40 9,900 4.70 8,700 14.60 5,700 3.20

SV012 10,900 11.80 13,000 4.30 11,800 14.00 8,700 3.10

SV015 13,400 12.10 16,100 4.20 14,200 14.00 11,300 3.10

SV018 19,400 13.40 22,200 4.60 21,200 15.80 14,300 3.50

SV024 23,400 13.40 26,600 4.40 25,000 15.50 17,000 3.40

SV030 29,200 13.10 33,400 4.30 31,000 15.30 20,900 3.20

SV036 37,900 14.70 41,800 4.60 39,900 16.90 26,900 3.50

SV041 39,500 13.60 44,600 4.20 41,200 15.60 29,400 3.30

SV042 40,000 12.60 46,300 4.20 42,600 14.50 31,000 3.20

SV048 45,900 12.90 56,400 4.30 48,800 14.90 35,400 3.40

SV060 57,900 13.20 67,200 4.20 60,100 15.00 46,900 3.20

SV070 64,000 13.30 72,800 4.40 66,400 15.00 50,800 3.40

MODELECM Motor (Option)

WLHP GLHP

Cooling Capacity EER

Heating Capacity COP

Cooling Capacity EER

Heating Capacity COP

SV015 13,700 13.90 15,500 4.40 14,400 16.20 10,700 3.30

SV018 19,700 14.20 21,900 4.70 21,500 17.00 14,100 3.60

SV024 23,800 14.30 26,200 4.60 25,400 16.50 16,700 3.50

SV030 30,000 14.80 32,800 4.60 31,600 17.40 20,400 3.40

SV036 38,200 15.40 41,400 4.70 40,200 17.70 26,500 3.60

SV041 40,500 15.70 43,700 4.40 42,200 17.70 28,500 3.60

SV042 40,900 14.10 45,300 4.40 43,500 16.30 30,100 3.50

SV048 46,800 14.10 55,600 4.50 49,600 16.20 34,600 3.60

SV060 59,000 14.10 66,400 4.20 61,100 16.40 46,200 3.30

SV070 65,200 14.60 71,800 4.60 67,600 16.60 50,000 3.50

Notes:GLHP ratings require an extended range optionECM motors can be either constant torque or constant CFMRatings based upon AHRI/ANSI 13256-1 with 1" disposable filter

Page 23: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Fan Motor Options | 23Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

FAN MOTOR OPTIONSPermanent Split Capacitor Motors (PSC)The standard motor for all SV series heat pumps is a PSC motor. For all models the supplied motor is a three speed motor. If a speed change is required, follow the instructions below:1. Disconnect power to the heat pump.2. For units with leaded motors, remove the front

access cover.3. Remove the fan speed wire from the fan relay.

Clip the ¼” quick connect from the lead and cap the unused lead.

4. Uncap the desired fan speed wire and terminate with a ¼” quick connect. Connect to the fan relay.

5. If the motor is a 460 V motor and the speed is changed from high to medium or low, connect the high speed motor lead to the orange intermediate winding lead instead of simply capping it.

Refer to the PSC motor performance tables for heat pump blower performance with the PSC motor option.

Table 5: PSC Motor Performance Data

ModelFan

Speed

Rated Airflow 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20

SV-007 Low 370 340 295 250 - - - - - - - -

Med 300 390 360 330 300 260 - - - - - - -

Hi 410 380 350 315 280 210 - - - - - -

SV-009 Low 370 340 295 250 - - - - - - - -

Med 390 360 330 300 260 - - - - - - -

Hi 350 410 380 350 315 280 210 - - - - - -

SV-012 Low 300 290 290 300 - - - - - - - -

Med 380 380 360 330 290 - - - - - - -

Hi 400 420 400 380 360 340 320 - - - - - -

SV-015 Low 320 300 280 - - - - - - - - -

Med 380 370 360 340 330 - - - - - - -

Hi 500 520 500 480 460 430 400 340 - - - - -

SV-018 Low 720 710 700 - - - - - - - - -

Med 650 810 790 760 730 680 590 - - - - - -

Hi 1010 970 920 870 800 680 530 340 - - - -

SV-024 Low 750 740 710 670 620 - - - - - - -

Med 830 820 800 770 720 620 - - - - - -

Hi 850 1050 1000 950 910 840 710 570 490 - - - -

SV-030 Low 975 910 870 740 640 - - - - - - -

Med 1050 980 920 830 760 700 - - - - - -

Hi 950 1250 1170 1120 1070 940 830 740 650 - - - -

SV-036 Low 1290 1250 1200 1150 1080 1000 - - - - - -

Med 1410 1350 1290 1220 1150 1060 900 - - - - -

Hi 1200 1500 1440 1370 1290 1210 1120 1000 900 - - - -

Page 24: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

24 | Fan Motor Options SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

SV-041 Low 990 990 970 950 920 860 - - - - - -

Med 1220 1190 1150 1120 1080 1020 940 - - - - -

Hi 1200 1450 1380 1320 1250 1190 1120 1040 960 - - - -

SV-042 Low 1210 1210 1190 1160 1120 1080 - - - - - -

Med 1460 1450 1430 1390 1330 1250 1160 - - - - -

Hi 1400 1750 1710 1670 1620 1560 1460 1330 1210 1080 - - -

SV-048 Low 1450 1440 1420 1400 1360 1320 - - - - - -

Med 1700 1670 1630 1580 1530 1470 1400 - - - - -

Hi 1600 1930 1870 1810 1740 1670 1600 1520 1430 1340 - - -

SV-060 Low 1560 1550 1540 1530 1505 1475 1440 1400 - - - -

Med 1890 1880 1870 1860 1825 1790 1730 1670 1590 1500 - -

Hi 2000 2220 2200 2150 2100 2050 2000 1940 1870 1800 1700 1590 -

SV-070 Low 1570 1560 1550 1540 1530 1505 1475 1440 1400 - - -

Med 1900 1890 1880 1870 1860 1825 1790 1730 1670 1590 1500 -

Hi 2100 2240 2220 2200 2150 2100 2050 2000 1940 1870 1800 1700 1590

Table 5: PSC Motor Performance Data

Page 25: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Fan Motor Options | 25Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Constant Torque Motors (ECM)For installations where the efficiency of an electronically commutated brushless DC motor (ECM) motor is required, but the features of a constant airflow motor are not required, the SV series is offered with a constant torque ECM motor option. These motors feature up to 90% thermal efficiency combined with a flatter fan curve than a PSC motor and simple operation. These motors are provided with 5 speed taps to allow for a wide range of air flow and external static options. To change a speed tap follow the instructions below:

1. Disconnect power to the heat pump.2. Remove the blower access panel.3. Remove the speed tap wire from the terminal it

is currently connected to and connect it to the terminal desired.

Refer to the constant torque motor performance tables for heat pump blower performance with the constant torque motor option.

Table 6: Constant Torque Blower Motor Data

ModelTap #

Rated Airflow 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20

SV-015

1 480 440 410 370 340 - - - - - - -

2 530 490 450 420 380 340 - - - - - -

3 500 600 560 510 470 440 410 370 - - - - -

4 650 600 560 520 500 480 440 380 - - - -

5 710 660 620 580 550 520 490 470 - - - -

SV-018

1 630 590 560 530 490 - - - - - - -

2 650 720 700 670 630 600 560 - - - - - -

3 790 770 750 710 670 620 560 - - - - -

4 910 890 850 810 740 670 590 520 - - - -

5 1010 970 920 860 810 750 660 530 - - - -

SV-024

1 650 610 580 560 520 - - - - - - -

2 740 720 690 660 620 570 - - - - - -

3 850 830 800 770 730 690 630 - - - - -

4 850 950 920 890 870 840 820 770 650 - - - -

5 1160 1110 1050 990 920 800 670 560 - - - -

SV-030

1 1020 1000 970 920 - - - - - - - -

2 1110 1060 1000 940 880 850 - - - - - -

3 950 1120 1070 1010 960 900 850 740 - - - - -

4 1160 1080 1010 950 880 840 750 550 - - - -

5 1150 1090 1020 960 890 850 760 540 - - - -

SV-036

1 1120 1090 1055 1030 1000 - - - - - - -

2 1260 1230 1200 1170 1140 1080 - - - - - -

3 1200 1330 1293 1253 1210 1167 1100 1030 - - - - -

4 1400 1357 1307 1250 1193 1120 1040 963 - - - -

5 1470 1420 1360 1290 1220 1140 1050 970 890 - - -

Page 26: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

26 | Fan Motor Options SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

SV-041

1 985 955 920 890 - - - - - - - -

2 1130 1100 1070 1030 1000 - - - - - - -

3 1200 1210 1180 1143 1100 1060 1010 - - - - - -

4 1290 1260 1217 1170 1120 1050 977 - - - - -

5 1370 1340 1290 1240 1180 1090 1000 920 - - - -

SV-042

1 1270 1250 1230 1210 - - - - - - - -

2 1440 1420 1410 1410 1400 1380 1340 - - - - -

3 1400 1540 1530 1510 1500 1490 1470 1430 1350 - - - -

4 1650 1630 1610 1600 1580 1530 1460 1360 1240 - - -

5 1730 1720 1700 1670 1620 1570 1490 1380 1260 1100 - -

SV-048

1 1390 1370 1350 1320 - - - - - - - -

2 1600 1580 1550 1530 1510 - - - - - - -

3 1600 1730 1700 1670 1650 1630 1600 1580 1540 - - - -

4 1830 1810 1780 1760 1740 1710 1670 1600 1520 - - -

5 1930 1910 1880 1860 1830 1780 1720 1640 1540 1420 - -

SV-060

1 1900 1880 1860 1820 - - - - - - - -

2 2000 1970 1950 1920 1890 1860 - - - - - -

3 2000 2110 2090 2060 2030 2010 1970 1940 1910 1880 - - -

4 2220 2200 2170 2140 2110 2080 2050 2060 2050 2000 1920 -

5 2340 2320 2290 2260 2230 2210 2180 2150 2110 2070 2000 1930

SV-070

1 2050 2010 1970 1930 - - - - - - - -

2 2150 2120 2080 2030 1990 1960 - - - - - -

3 2100 2270 2230 2200 2160 2120 2080 2040 2010 1980 - - -

4 2390 2350 2320 2280 2250 2200 2160 2130 2100 2070 2030 -

5 2520 2480 2450 2420 2380 2330 2290 2260 2220 2170 2100 2020

Table 6: Constant Torque Blower Motor Data

Page 27: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Fan Motor Options | 27Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Constant Airflow Motors (ECM)For installations where constant air delivery is critical or where external static pressure drop can vary greatly (such as with high MERV value filters) the SV series is offered with a constant air flow ECM motor option. This option provides ECM motor efficiency combined with a constant air delivery across a wide range of external static pressures. These motors dynamically adjust their power output to precisely match the desired air flow on a pre-programmed fan curve. Additionally these motors feature:1. A low CFM ventilation feature that circulates

air at 70% of full load when fan only is called. 2. A passive dehumidification mode that reduces

air flow during a cooling call when dehumidification is also required – this reduces the sensible heat ratio of the cooling coil and extends cooling run time to more effectively dehumidify. (refer to the ECM Interface Board section of this manual)

3. 3 speed settings per model. Units are factory set to “NORM” but can be field adjusted to “+” to increase CFM by 15% or to “-“ to reduce CFM by 15%. (refer to the ECM Interface Board section of this manual)

4. A “TEST” mode that operates the motor at a 70% torque setting. This setting can be used to diagnose programming problems in the motor itself. (refer to the ECM Interface Board section of this manual)

5. A CFM indicator light that provides a blink for each 100 CFM of air delivered (note that this blink code is approximate and should not replace test and balancing).

Refer to the constant air flow motor performance tables for heat pump blower performance with the constant air flow motor option.

Table 7: Constant Airflow Motor Performance Table

Model Fan Speed

Rated Airflow 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20

SV-015

A - Low 450 450 450 450 450 450 450 440 440 430 - -

A - Normal 500 500 500 500 500 500 500 500 480 470 460 - -

A - Hi 580 580 580 580 580 580 580 570 560 550 - -

SV-018

B - Low 550 540 540 540 540 540 540 530 520 500 - -

B - Normal 650 650 650 650 650 650 650 640 630 610 590 - -

B - Hi 750 750 750 750 750 750 740 730 710 690 - -

SV-024

C - Low 720 720 720 720 720 720 720 700 650 560 - -

C - Normal 850 850 850 850 850 850 850 850 850 800 700 - -

C - Hi 960 960 960 960 960 960 960 960 880 790 - -

SV-030

D - Low 810 810 810 810 810 810 810 810 810 810 - -

D - Normal 950 950 950 950 950 950 950 950 950 950 950 - -

D - Hi 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 - -

SV-036

A - Low 1020 1020 1020 1020 1020 1020 1020 1020 1020 1020 - -

A - Normal 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 - -

A - Hi 1380 1380 1380 1380 1380 1380 1380 1380 1380 1380 - -

SV-041

A - Low 1020 1020 1020 1020 1020 1020 1020 1020 1020 1020 - -

A - Normal 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 - -

A - Hi 1380 1380 1380 1380 1380 1380 1380 1380 1380 1380 - -

Page 28: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

28 | Fan Motor Options SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

SV-042

B - Low 1190 1190 1190 1190 1190 1190 1190 1190 1190 1190 - -

B - Normal 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 - -

B - Hi 1630 1630 1630 1630 1630 1630 1630 1630 1630 1630 - -

SV-048

A - Low 1360 1360 1360 1360 1360 1360 1360 1360 1360 1360 - -

A - Normal 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 - -

A - Hi 1840 1840 1840 1840 1840 1840 1840 1840 1840 1840 - -

SV-060

A - Low 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 -

A - Normal 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 -

A - Hi 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 -

SV-070

B - Low 1870 1870 1870 1870 1870 1870 1870 1870 1870 1870 1870 -

B - Normal 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 -

B - Hi 2330 2330 2330 2330 2330 2330 2330 2330 2330 2330 2330 -

Note: Air flow is 70% of tabulated values during fan only operation. Air flow is 80% of tabulated value during passive dehumidfication mode when enabled.

Table 7: Constant Airflow Motor Performance Table

Page 29: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Standard Blower Motor | 29Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

STANDARD BLOWER MOTOR

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Fan Motor

HP

Total Unit FLA

Min Circuit Amps

Max Fuse/ HACRQTY RLA LRA

SV0071 208-230/60/1 197/253 1 2.6 17.7 0.96 0.1 3.56 4.2 15

2 265/60/1 238/292 1 2.6 13.5 0.96 0.1 3.56 4.2 15

SV0091 208-230/60/1 197/253 1 3.4 22.2 0.96 0.1 4.36 5.2 15

2 265/60/1 238/292 1 2.9 18.8 0.85 0.1 3.75 4.5 15

SV0121 208-230/60/1 197/253 1 4.6 28 0.96 0.1 5.56 6.7 15

2 265/60/1 238/292 1 3.8 22.2 0.85 0.1 4.65 5.6 15

SV0151 208-230/60/1 197/253 1 5.6 29 0.96 0.1 6.56 8.0 15

2 265/60/1 238/292 1 4.6 20 0.85 0.1 5.45 6.6 15

SV0181 208-230/60/1 197/253 1 6.5 43 1.8 0.25 8.3 9.9 15

2 265/60/1 238/292 1 5.8 46 1.6 0.25 7.4 8.9 15

SV024

1 208-230/60/1 197/253 1 7.4 43 1.8 0.25 9.2 11.1 15

2 265/60/1 238/292 1 6.7 46 1.6 0.25 8.3 10.0 15

3 208-230/60/3 197/253 1 5.9 63 1.8 0.25 7.7 9.2 15

4 460/60/3 414/506 1 2.9 30 0.9 0.25 3.8 4.5 15

SV030

1 208-230/60/1 197/253 1 9.9 54 1.8 0.25 11.7 14.2 20

2 265/60/1 238/292 1 8.5 46 1.6 0.25 10.1 12.2 20

3 208-230/60/3 197/253 1 6.9 63 1.8 0.25 8.7 10.4 15

4 460/60/3 414/506 1 5.4 30 0.9 0.25 6.3 7.7 15

SV036

1 208-230/60/1 197/253 1 13 74 4.4 0.5 17.4 20.7 30

2 265/60/1 238/292 1 11.3 67 3.3 0.5 14.6 17.4 25

3 208-230/60/3 197/253 1 7.8 68 4.4 0.5 12.2 14.2 20

4 460/60/3 414/506 1 3.9 34 1.8 0.5 5.7 6.7 15

SV0411 208-230/60/1 197/253 1 13.6 88 4.4 0.5 18 21.4 35

3 208-230/60/3 197/253 1 8.8 68 4.4 0.5 13.2 15.4 20

4 460/60/3 414/506 1 4.4 34 1.8 0.5 6.2 7.3 15

SV0421 208-230/60/1 197/253 1 13.6 88 4.4 0.5 18 21.4 35

3 208-230/60/3 197/253 1 8.8 68 4.4 0.5 13.2 15.4 20

4 460/60/3 414/506 1 4.4 34 1.8 0.5 6.2 7.3 15

SV0481 208-230/60/1 197/253 1 15.7 84 4.4 0.75 20.1 24.0 35

3 208-230/60/3 197/253 1 11 88 4.4 0.75 15.4 18.2 25

4 460/60/3 414/506 1 5.4 44 2.8 0.75 8.2 9.6 15

SV0601 208-230/60/1 197/253 1 26.3 134 5.5 0.75 31.8 38.4 60

3 208-230/60/3 197/253 1 15.6 110 5.5 0.75 21.1 25.0 40

4 460/60/3 414/506 1 7.8 52 2.8 0.75 10.6 12.6 20

SV0701 208-230/60/1 197/253 1 28.3 178 5.5 0.75 33.8 40.9 60

3 208-230/60/3 197/253 1 19.2 136 5.5 0.75 24.7 29.5 45

4 460/60/3 414/506 1 8.7 66.1 2.8 0.75 11.5 13.7 20

Page 30: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

30 | Standard Blower Motor SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Constant Torque ECM Blower Motor

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Fan Motor HP

Total Unit FLA

Min Circuit Amps

Max Fuse/ HACRQTY RLA LRA

SV0151 208-230/60/1 197/253 1 5.6 29 2.8 0.33 8.4 9.8 15

2 265/60/1 240/292 1 4.6 20 2.6 0.33 7.2 8.4 15

SV0181 208-230/60/1 197/253 1 6.5 43 2.8 0.33 9.3 10.9 15

2 265/60/1 240/292 1 5.8 46 2.6 0.33 8.4 9.9 15

SV024

1 208-230/60/1 197/253 1 7.4 43 2.8 0.33 10.2 12.1 15

2 265/60/1 240/292 1 6.7 46 2.6 0.33 9.3 11.0 15

3 208-230/60/3 197/253 1 5.9 63 2.8 0.33 8.7 10.2 15

4 460/60/3 414/506 1 2.9 30 2.1 0.5 5 5.7 15

SV030

1 208-230/60/1 197/253 1 9.9 54 2.8 0.33 12.7 15.2 25

2 265/60/1 240/292 1 8.5 46 2.6 0.33 11.1 13.2 20

3 208-230/60/3 197/253 1 6.9 63 2.8 0.33 9.7 11.4 15

4 460/60/3 414/506 1 5.4 30 2.1 0.5 7.5 8.9 15

SV036

1 208-230/60/1 197/253 1 13 74 4.1 0.5 17.1 20.4 30

2 265/60/1 240/292 1 11.3 67 3.9 0.5 15.2 18.0 25

3 208-230/60/3 197/253 1 7.8 68 4.1 0.5 11.9 13.9 20

4 460/60/3 414/506 1 3.9 34 2.1 0.5 6 7.0 15

SV0411 208-230/60/1 197/253 1 13.6 88 6 0.75 19.6 23.0 35

3 208-230/60/3 197/253 1 8.8 68 6 0.75 14.8 17.0 25

4 460/60/3 414/506 1 4.4 34 4.6 0.75 9 10.1 15

SV0421 208-230/60/1 197/253 1 13.6 88 6 0.75 19.6 23.0 35

3 208-230/60/3 197/253 1 8.8 68 6 0.75 14.8 17.0 25

4 460/60/3 414/506 1 4.4 34 4.6 0.75 9 10.1 15

SV0481 208-230/60/1 197/253 1 15.7 84 6 0.75 21.7 25.6 40

3 208-230/60/3 197/253 1 11 88 6 0.75 17 19.8 30

4 460/60/3 414/506 1 5.4 44 4.6 0.75 10 11.4 15

SV0601 208-230/60/1 197/253 1 26.3 145 7.6 1 33.9 40.5 60

3 208-230/60/3 197/253 1 15.6 123 7.6 1 23.2 27.1 40

4 460/60/3 414/506 1 7.8 70 4 1 11.8 13.8 20

SV0701 208-230/60/1 197/253 1 28.3 158 7.6 1 35.9 43.0 70

3 208-230/60/3 197/253 1 19.2 155 7.6 1 26.8 31.6 50

4 460/60/3 414/506 1 8.7 75 4 1 12.7 14.9 20

Page 31: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Standard Blower Motor | 31Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Constant CFM ECM Blower Motor

Model Voltage Code

Rated Voltage

Voltage Min/Max

Compressor Fan Motor FLA

Fan Motor HP

Total Unit FLA

Min Circuit Amps

Max Fuse/ HACRQTY RLA LRA

SV0151 208-230/60/1 197/253 1 5.6 29 2.8 0.33 8.4 9.8 15

2 265/60/1 240/292 1 4.6 20 2.6 0.33 7.2 8.4 15

SV0181 208-230/60/1 197/253 1 6.5 43 2.8 0.33 9.3 10.9 15

2 265/60/1 240/292 1 5.8 46 2.6 0.33 8.4 9.9 15

SV024

1 208-230/60/1 197/253 1 7.4 43 2.8 0.33 10.2 12.1 15

2 265/60/1 240/292 1 6.7 46 2.6 0.33 9.3 11.0 15

3 208-230/60/3 197/253 1 5.9 63 2.8 0.33 8.7 10.2 15

4 460/60/3 414/506 1 2.9 30 2.6 0.33 5.5 6.2 15

SV030

1 208-230/60/1 197/253 1 9.9 54 2.8 0.33 12.7 15.2 25

2 265/60/1 240/292 1 8.5 46 2.6 0.33 11.1 13.2 20

3 208-230/60/3 197/253 1 6.9 63 2.8 0.33 9.7 11.4 15

4 460/60/3 414/506 1 5.4 30 2.6 0.33 8 9.4 15

SV036

1 208-230/60/1 197/253 1 13 74 4.3 0.5 17.3 20.6 30

2 265/60/1 240/292 1 11.3 67 4.1 0.5 15.4 18.2 25

3 208-230/60/3 197/253 1 7.8 68 4.3 0.5 12.1 14.1 20

4 460/60/3 414/506 1 3.9 34 4.1 0.5 8 9.0 15

SV0411 208-230/60/1 197/253 1 13.6 88 6.8 0.75 20.4 23.8 35

3 208-230/60/3 197/253 1 8.8 68 6.8 0.75 15.6 17.8 25

4 460/60/3 414/506 1 4.4 34 5.5 0.75 9.9 11.0 15

SV0421 208-230/60/1 197/253 1 13.6 88 6.8 0.75 20.4 23.8 35

3 208-230/60/3 197/253 1 8.8 68 6.8 0.75 15.6 17.8 25

4 460/60/3 414/506 1 4.4 34 5.5 0.75 9.9 11.0 15

SV0481 208-230/60/1 197/253 1 15.7 84 6.8 0.75 22.5 26.4 40

3 208-230/60/3 197/253 1 11 88 6.8 0.75 17.8 20.6 30

4 460/60/3 414/506 1 5.4 44 5.5 0.75 10.9 12.3 15

SV0601 208-230/60/1 197/253 1 26.3 145 9.1 1 35.4 42.0 60

3 208-230/60/3 197/253 1 15.6 123 9.1 1 24.7 28.6 45

4 460/60/3 414/506 1 7.8 70 6.9 1 14.7 16.7 20

SV0701 208-230/60/1 197/253 1 28.3 158 9.1 1 37.4 44.5 70

3 208-230/60/3 197/253 1 19.2 155 9.1 1 28.3 33.1 50

4 460/60/3 414/506 1 8.7 75 6.9 1 15.6 17.8 25

Page 32: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

32 | Unit Start Up SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

UNIT START UP1. Set the thermostat to the highest setting.2. Set the thermostat system switch to “COOL”,

and the fan switch to the “AUTO” position. The reversing valve solenoid should energize. The compressor and fan should not run.

3. Reduce the thermostat setting approximately 5 degrees below the room temperature.

4. Verify the heat pump is operating in the cooling mode.

5. Turn the thermostat system switch to the “OFF” position. The unit should stop running and the reversing valve should de energize.

6. Leave the unit off for approximately (5) minutes to allow for system equalization.

7. Turn the thermostat to the lowest setting.8. Set the thermostat switch to “HEAT”.9. Increase the thermostat setting approximately

5 ° above the room temperature.10. Verify the heat pump is operating in the heating

mode.11. Set the thermostat to maintain the desired

space temperature.12. Check for vibrations, leaks, etc.

MAINTENANCE1. Filter changes or cleanings are required at

regular intervals. The time period between filter changes will depend upon type of environment the equipment is used in. In a single family home, that is not under construction, changing or cleaning the filter every 60 days is sufficient. In other applications such as motels, where daily vacuuming produces a large amount of lint, filter changes may be need to be as frequent as biweekly.

2. An annual “checkup” is recommended by a licensed refrigeration mechanic. Recording the performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. This data should be compared to the information on the unit’s data plate and the data taken at the original startup of the equipment.

3. Lubrication of the blower motor is not required, however may be performed on some motors to extend motor life. Use SAE-20 non-detergent electric motor oil.

4. The condensate drain should be checked annually by cleaning and flushing to insure proper drainage.

5. Periodic lockouts almost always are caused by air or water flow problems. The lockout (shutdown) of the unit is a normal protective measure in the design of the equipment. If continual lockouts occur call a mechanic immediately and have them check for: water flow problems, water temperature problems, air flow problems or air temperature problems. Use of the pressure and temperature charts for the unit may be required to properly determine the cause.

NOTE: Equipment should never be used during construction due to likelihood of wall board dust accumulation in the air coil of the equipment which permanently affects the performance and may shorten the life of the equipment.

Page 33: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Maintenance | 33Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Unit Check Out Sheet

Customer DataCustomer Name _____________________________________________ Date ___________________________________Address _____________________________________________________________________________________________________________________Phone _______________________________________________________ Unit Number ___________________________

Unit Nameplate DataUnit Make _________________________________________Model Number ____________________________________ Serial Number ____________________________________Refrigerant Charge (oz) __________________________Compressor: RLA ____________________ LRA ___________________________Blower Motor: FLA (or NPA) ___________ HP ____________________________Maximum Fuse Size (Amps) ____________Maximum Circuit Ampacity _____________

Operating ConditionsCooling Mode Heating Mode

Entering / Leaving Air Temp _______________ / _____________ _______________ / _____________

Entering Air Measured at: ______________________________ ______________________________

Leaving Air Measured at: ______________________________ ______________________________

Entering / Leaving Fluid Temp _______________ / _____________ _______________ / _____________

Fluid Flow (gpm) ______________________________ ______________________________

Compressor Volts / Amps _______________ / _____________ _______________ / _____________

Blower Motor Volts / Amps _______________ / _____________ _______________ / _____________

Source Fluid Type ______________________________ ______________________________

Fluid Flow (gpm)* ______________________________ ______________________________

Fluid Side Pressure Drop* ______________________________ ______________________________

Suction / Discharge Pressure (psig)* _______________ / _____________ _______________ / _____________Suction / Discharge Temp* _______________ / _____________ _______________ / _____________Suction Superheat* ______________________________ ______________________________Entering TXV / Cap Tube Temp* ______________________________ ______________________________Liquid Subcooling* ______________________________ ______________________________

* Required for Troubleshooting ONLY

Auxiliary HeatUnit Make __________________________________Model Number: ______________________________ Serial Number _____________________________ Max Fuse Size (Amps) _______________________Volts / Amps _______________________________Entering Air Temperature _____________________Leaving Air Temperature ______________________

Bosch Group601 NW 65th Court Fort Lauderdale, FL 33309 Phone: 866-642-3198 Fax: (800) 776-5529

MAIL TO: [email protected]

or scan the QR code and attach picture of this form with

the information requested.

Page 34: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

34 | Troubleshooting SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

TROUBLESHOOTING

UNIT TROUBLESHOOTING

Problem Mode Check Possible Cause Action

Cooling Heating

No compressor operation but fan runs

X

Is fault LED Blinking 1 time?

High Pressure fault - no or low water flow

Check water valves and/or pumps for proper operation. Check for

water coil blockage.

High Pressure fault - high water temperature

Check water temperature - is it in range?

High Pressure fault - fouled or scaled water

coil

Check for proper flow rate and water temperature, but low water

side temp rise in cooling

X High Pressure fault - no or low air flow

Check fan motor for proper operation.

Check air filter

Inspect air coil for dirt/debris

Check duct work - are dampers closed or blocked?

X

Is fault LED Blinking 2 times?

Low Pressure fault - no or low air flow

Check fan motor for proper operation.

Check air filter

Inspect air coil for dirt/debris

Check duct work - are dampers closed or blocked?

Low Pressure fault - low refrigerant

Check refrigerant pressure with gauge set

X

Low Pressure fault - no or low water flow

Check water valves and/or pumps for proper operation. Check for

water coil blockage.

75Unit Check for proper flow rate and

water temperature, but low water side temp drop in heating.

Low Pressure fault - low refrigerant

Check refrigerant pressure with gauge set

X Is fault LED Blinking 3 times?

Freeze fault, water coil - no or low water flow

Check water valves and/or pumps for proper operation. Check for

water coil blockage.

Freeze fault - low water temperature

Check water temperature - is it below 40° entering? If heat pump is

connected to a closed loop with antifreeze check that the "FREEZE 1" resistor on the UPM board has

been cut to set the unit to antifreeze mode (see UPM features

on pages 15-17).

Freeze fault - low refrigerant

Check refrigerant pressure with gauge set

Page 35: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Troubleshooting | 35Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

No compressor operation but fan runs

X Is fault LED Blinking 4 times?

Condensate fault - poor drainage

Check condensate pan for high water level. Check drain line for

blockages, double trapping or inadequate trapping.

Condensate fault - blocked return air

Check condensate pan for high water level. Check air filter and

return air duct work for blockage. Check that there is adequate space between the return air opening and walls or other obstructions on free

return applications.

X X Is fault LED Blinking 5 times?

Brown out fault - low supply voltage

Check primary voltage - insure it is within the limits listed on the unit

data plate.

Brown out fault - overloaded control

circuit

Check control voltage - if it is below 18 V check accessories connected to the unit and insure that they do not exceed the VA draw shown on

page 11.

Brown out fault - bad thermostat connection

Check that thermostat wiring is proper gauge and length, that it is

not damaged and that all connections at the thermostat and

heat pump are secure.

X Is fault LED Blinking 6 times?

Freeze fault, air coil - no or low air flow

Check fan motor for proper operation.

Check air filter

Inspect air coil for dirt/debris

Check duct work - are dampers closed or blocked?

Freeze fault, air coil - blocked return air

Check that there is adequate space between the return air opening and walls or other obstructions on free

return applications.

Freeze fault, air coil - low refrigerant

Check refrigerant pressure with gauge set.

X XNo fault LED - contactor not

energized

Thermostat not calling for compressor

operation

Ensure that the thermostat is on and calling for "Y"

Bad thermostat connection

Check "Y" connection from thermostat. Insure that there is 24

VAC between "Y" and "C".

Loose wire to contactor coil

Check wiring - insure that there is 24 VAC across the contactor coil.

Burned out contactor coil

Test contactor with 24VAC (between "R" and "C"). Ohm

contactor coil - an open circuit indicates a burned coil.

UNIT TROUBLESHOOTING

Problem Mode Check Possible Cause Action

Page 36: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

36 | Troubleshooting SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

No compressor operation but fan runs X X No fault LED -

contactor energized

Open compressor overload

Check for supply voltage at the load side of the contactor. For 3 phase models check phase rotation and

voltage at all 3 phases.

Poor wiring connections

Look for signs of heat on the wiring insulation. Check that all wiring

connections are secure and properly torqued.

Burned out compressor

Does compressor hum when power is applied? If not check the

resistance of the compressor windings using the values shown in

the compressor characteristics chart. Note that the compressor

must be cool (70° F) when checking the windings.

No compressor or fan operation X X

Power LED onBad thermostat

connection / faulty thermostat

Check thermostat and wiring. Check unit terminal block for 24 VAC between "Y" and "C" and "G"

and "C".

Power LED off

Low or no supply powerInsure that the supply voltage to the unit is with in the range shown on

the unit data plate.

Faulty control transformer

Check for 24 VAC between "R" and "C" on the unit terminal block. For 75 and 100 VA transformers, check that the transformer circuit breaker has not tripped. Check low voltage

circuit for overload conditons or short circuits before replacing the

transformer.

No fan operation - PSC motor X X

Fan relay energized Faulty motor

check supply voltage from the fan relay to the motor. Check that all

motor wires are secure. With power off spin the motor shaft -

noise, resistance or uneven motion can be signs of motor failure.

Fan relay not energized

No fan operation signalCheck for 24 VAC across the fan

relay coil. Check all wiring connections.

Bad fan relay

If the relay coil is energized but the relay does not pull in, check the

resistance across the relay coil - an open circuit is an indicator of a

faulty relay.

No fan operation - constant torque motor X X

No fan operation signal Check for 24 VAC between "G" and "C". Check all wiring connections.

Loose wiring Check all wiring connections at motor and control box.

Faulty motor

Check supply voltage to the motor. Check that all motor wires are

secure. With power off spin the motor shaft - noise, resistance or

uneven motion can be signs of motor failure.

UNIT TROUBLESHOOTING

Problem Mode Check Possible Cause Action

Page 37: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Troubleshooting | 37Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

No fan operation - constant airflow motor X X

No fan operation signal

Check for 24 VAC between "G" and "C". Check all wiring connections.

Make sure that the thermostat connection plug is securely

connected.

Loose wiring

Check all wiring connections at motor and control box. Check that power and control harnesses are

securely connected.

Interface board problems

Make sure that the interface board is not damged and that all DIP

switches are in the proper configuration (refer to the blower

performance tables).

Faulty motor

Check supply voltage to the motor. Check that all motor wires are

secure. Move the "TEST" DIP switch to "ON" and the other switches to

"OFF" on the "ADJUST" switch block on the interface board - the motor should run at 70% torque whrn "G" is called. With power off spin the motor shaft - noise, resistance or

uneven motion can be signs of motor failure.

Unit not shifting into cooling X

Reversing valve solenoid energized Faulty solenoid

Check that the reversing valve solenoid is receiving 24 VAC. If so, check the resistance of the solenoid

- an open circuit may indicate a burned out solenoid.

Reversing valve solenoid not

energized

Miswired/faulty thermostat

Check that the reversing valve theromstat wire is connected to the

"O" terminal of the thermostat. Check for a contact closure

between "O" and "R".

Loose wire on "O" terminal

Check that the wires from the thermostat to the unit are securely connected and that the wires from the electrical box to the reversing

valve are connected.

Excessively cold supply air temperature in

cooling or excessively hot supply air

temperature in heating

X X Reduced air flow

Dirty Filter Replace filter.

Fan speed too low Consult blower performance table and increase fan speed if possible.

Excessive duct pressure drop

Consult blower performance table and increase fan speed if possible.

Excessively warm supply air temperature

in cooling and/or excessively cool air in

heating

X X

Air flow too high Fan speed setting too high

Consult blower performance table and reduce fan speed if possible.

High or low water temperature

Inlet water temperature out of range

Check unit capacity vs. water temperature.

Air leakage Leaky duct work Inspect duct work.

Loss of refrigeration capacity Low refrigerant Check refrigerant pressures with

gauge set.

UNIT TROUBLESHOOTING

Problem Mode Check Possible Cause Action

Page 38: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

38 | Troubleshooting SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

High humidity X

Air flow too high Fan speed setting too high

Consult blower performance table and reduce fan speed if possible.

Loss of refrigeration capacity Low refrigerant Check refrigerant pressures with

gauge set.

Short cycling

Unit oversized Check unit performance against building load calculations.

Poor thermostat location Make sure that thermostat is not located by a supply air duct .

Objectionable noise levels

X X

Air noise

Poor duct work/grille design

Insure duct work and grilles are properly sized for unit air flow.

Fan speed setting too high

Consult blower performance table and reduce fan speed if possible.

Structure bourne noise

Unit not mounted on full vibration pad

Mount unit on a vibration pad (see page 7).

Unit not connected with flexible conduit, water lines and/or duct work

Install unit in accordance with instructions on pages 6-8.

Unit cabinet touching wall or other building

component

Adjust unit location to avoid unit touching structure.

X

Compressor noise

High water temperature or low water flow rate

elevating head pressure

Increase water flow rate and/or reduce water temperature if

possible.

Scaled or fouled water coil elevating heat

pressureClean/descale water coil.

X Low air flow elevating head pressure

Check filter.

Increase fan speed.

X X Water hammer Fast closing valves installed change valves to slow-close type.

UNIT TROUBLESHOOTING

Problem Mode Check Possible Cause Action

Page 39: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Temperature/Pressure Table | 39Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

TEMPERATURE/PRESSURE TABLE

OPERATING DATA

COOLING HEATING

MODEL ENTERING

WATER TEMP, ˚F

WATER FLOW GPM

SUCTION PRESSURE

PSIG

DISCHARGE PRESSURE

PSIG WATER TEMP

RISE, ˚F AIR TEMP DROP, ˚F

SUCTION PRESSURE

PSIG

DISCHARGE PRESSURE

PSIG

WATER TEMP DROP,

˚F AIR TEMP RISE, ˚F

SV007

30˚

1.4 65-80 282-344 6-7 14-17

1.9 73-89 294-359 3-4 15-18

40˚

1.4 106-129 146-178 17-21 18-22 80-98 299-365 7-9 16-20

1.9 102-124 133-162 10-13 19-23 89-108 311-380 4-5 17-21

50˚

1.4 115-141 180-220 17-20 17-21 95-116 315-385 9-11 19-23

1.9 111-135 163-200 10-12 18-23 105-128 329-402 5-7 20-24

60˚

1.4 124-152 213-261 16-19 17-21 109-133 332-406 11-13 21-26

1.9 120-146 194-237 10-12 18-22 121-148 346-423 6-8 22-27

70˚

1.4 134-163 247-302 15-19 17-20 124-151 349-427 12-15 23-28

1.9 128-157 225-275 9-11 18-21 138-168 364-444 7-9 25-30

80˚

1.4 143-175 281-343 14-18 16-20 138-169 366-447 14-17 26-31

1.9 137-168 255-312 9-11 17-21 154-188 381-466 8-10 27-33

90˚

1.4 152-186 315-385 14-17 16-19 153-187 383-468 16-19 28-34

1.9 146-179 286-350 8-10 17-20 170-208 399-487 9-12 29-36

100˚

1.4 161-197 349-426 13-16 15-19

1.9 155-190 317-387 8-10 16-20

SV009

30˚

1.8 91-111 251-307 5-6 21-25

2.4 95-116 256-313 3-4 22-26

40˚

1.8 112-137 144-176 14-17 22-27 107-130 267-327 6-7 24-29

2.4 106-130 137-167 10-12 23-28 112-137 273-333 4-5 25-30

50˚

1.8 116-142 177-217 13-16 21-26 123-150 284-347 7-9 27-33

2.4 111-135 169-206 9-12 22-27 129-158 289-353 5-6 28-34

60˚

1.8 121-148 211-258 13-16 21-26 139-170 300-366 8-10 30-37

2.4 115-140 200-245 9-11 22-27 146-179 306-374 6-7 32-39

70˚

1.8 126-154 245-299 13-15 20-25 156-190 316-386 9-12 33-41

2.4 119-146 232-284 9-11 21-26 163-200 322-394 7-8 35-43

80˚

1.8 130-159 278-340 12-15 20-24 172-210 332-406 11-13 36-44

2.4 124-151 264-323 9-11 21-26 180-220 339-414 8-9 38-47

90˚

1.8 135-165 312-381 12-15 19-24 188-230 349-426 12-15 39-48

2.4 128-157 296-362 9-10 20-25 197-241 355-434 8-10 41-51

100˚

1.8 140-171 345-422 12-14 19-23

2.4 133-162 328-401 8-10 20-24

Page 40: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

40 | Temperature/Pressure Table SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

SV012

30˚

2.6 73-89 266-325 5-6 15-18

3 77-94 272-333 3-4 16-19

40˚

2.6 117-143 189-231 14-17 18-22 86-105 279-341 6-7 17-21

3 112-137 178-217 8-9 19-24 90-110 286-350 4-5 18-22

50˚

2.6 126-154 221-270 14-17 18-21 162-198 293-358 7-8 20-24

3 121-148 207-253 8-9 19-23 170-208 300-366 5-6 21-25

60˚

2.6 131-160 252-308 13-16 17-21 110-134 306-374 8-10 22-27

3 125-153 237-290 8-9 18-22 115-141 314-383 6-7 23-29

70˚

2.6 135-165 284-347 13-16 17-20 122-150 320-391 9-11 24-30

3 130-158 266-326 7-9 18-22 129-157 327-400 6-8 26-32

80˚

2.6 140-171 320-391 13-16 16-20 134-164 333-407 11-13 27-33

3 134-164 300-367 7-9 17-21 141-172 341-417 7-9 28-35

90˚

2.6 144-176 360-440 13-16 16-19 147-179 347-424 12-14 29-36

3 138-169 338-414 7-9 17-21 154-188 355-434 8-10 31-38

100˚

2.6 149-182 405-495 13-15 15-19

3 143-174 381-465 7-9 16-20

SV015

30˚

2.8 74-90 244-299 3-4 13-15

3.8 78-95 251-306 2-3 13-16

40˚

2.8 122-149 183-224 14-18 19-23 87-106 257-314 4-5 15-18

3.8 117-143 172-210 8-10 20-24 91-111 263-322 3-3 16-19

50˚

2.8 131-160 214-261 14-18 18-22 164-201 269-329 5-6 17-20

3.8 126-154 201-245 8-10 19-24 173-211 276-337 3-4 18-22

60˚

2.8 136-166 244-298 14-17 18-22 111-136 282-344 6-7 19-23

3.8 131-160 230-281 8-10 19-23 117-143 289-353 4-5 20-24

70˚

2.8 141-172 275-336 14-17 17-21 124-152 294-360 7-8 21-25

3.8 135-165 258-316 8-10 18-22 131-160 302-369 5-6 22-27

80˚

2.8 145-178 310-378 14-17 17-20 136-166 307-375 8-9 23-28

3.8 140-171 291-356 8-10 18-22 143-175 314-384 5-6 24-30

90˚

2.8 150-183 349-426 14-17 16-20 149-182 319-390 8-10 25-30

3.8 144-176 328-401 8-9 17-21 156-191 327-400 6-7 26-32

100˚

2.8 155-189 392-480 13-16 16-19

3.8 149-182 369-451 8-9 17-21

SV018

30˚

3 65-80 282-344 6-7 14-17

5 73-89 294-359 3-4 15-18

40˚

3 121-148 184-225 17-21 18-22 80-98 299-365 7-9 16-20

5 117-143 167-204 10-13 19-23 89-108 311-380 4-5 17-21

50˚

3 123-151 222-271 17-20 17-21 95-116 315-385 9-11 19-23

5 119-145 202-247 10-12 18-23 105-128 329-402 5-7 20-24

60˚

3 125-153 260-318 16-19 17-21 109-133 332-406 11-13 21-26

5 120-147 237-289 10-12 18-22 121-148 346-423 6-8 22-27

70˚

3 127-155 298-365 15-19 17-20 124-151 349-427 12-15 23-28

5 122-149 271-331 9-11 18-21 138-168 364-444 7-9 25-30

80˚

3 129-158 336-411 14-18 16-20 138-169 366-447 14-17 26-31

5 124-152 306-374 9-11 17-21 154-188 381-466 8-10 27-33

90˚

3 131-160 374-458 14-17 16-19 153-187 383-468 16-16 28-34

5 126-154 340-416 8-10 17-20 170-208 399-487 9-12 29-36

100˚

3 133-162 413-504 13-16 15-19

5 128-156 375-458 8-10 16-20

Page 41: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Temperature/Pressure Table | 41Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

SV024

30˚

5 72-87 296-361 5-6 21-25

7 75-92 301-368 3-4 22-26

40˚

5 114-139 155-190 14-17 22-27 88-107 314-384 6-7 24-29

7 108-132 147-180 10-12 23-28 92-112 321-392 4-5 25-30

50˚

5 116-142 192-234 13-16 21-26 104-127 333-407 7-9 27-33

7 111-135 182-222 9-12 22-27 109-133 340-415 5-6 28-34

60˚

5 119-146 228-279 13-16 21-26 120-146 352-430 8-10 30-37

7 113-138 217-265 9-11 22-27 125-153 359-439 6-7 32-39

70˚

5 122-149 264-323 13-15 20-25 136-166 371-453 9-12 33-41

7 116-142 251-307 9-11 21-26 142-174 378-462 7-8 35-43

80˚

5 125-152 301-368 12-15 20-24 152-185 389-476 11-13 36-44

7 118-145 286-349 9-11 21-26 159-194 397-485 8-9 38-47

90˚

5 127-156 337-412 12-15 19-24 168-205 408-499 12-15 39-48

7 121-148 320-392 9-10 20-25 176-215 416-509 8-10 41-51

100˚

5 130-159 374-457 12-14 19-23

7 124-151 355-434 8-10 20-24

SV030

30˚

3.5 73-89 266-325 5-6 15-18

7.5 77-94 272-333 3-4 16-19

40˚

3.5 117-143 189-231 14-17 18-22 86-105 279-341 6-7 17-21

7.5 112-137 178-217 8-9 19-24 90-110 286-350 4-5 18-22

50˚

3.5 126-154 221-270 14-17 18-21 162-198 293-358 7-8 20-24

7.5 121-148 207-253 8-9 19-23 170-208 300-366 5-6 21-25

60˚

3.5 131-160 252-308 13-16 17-21 110-134 306-374 8-10 22-27

7.5 125-153 237-290 8-9 18-22 115-141 314-383 6-7 23-29

70˚

3.5 135-165 284-347 13-16 17-20 122-150 320-391 9-11 24-30

7.5 130-158 266-326 7-9 18-22 129-157 327-400 6-8 26-32

80˚

3.5 140-171 320-391 13-16 16-20 134-164 333-407 11-13 27-33

7.5 134-164 300-367 7-9 17-21 141-172 341-417 7-9 28-35

90˚

3.5 144-176 360-440 13-16 16-19 147-179 347-424 12-14 29-36

7.5 138-169 338-414 7-9 17-21 154-188 355-434 8-10 31-38

100˚

3.5 149-182 405-495 13-15 15-19

7.5 143-174 381-465 7-9 16-20

SV036

30˚

4.5 74-90 244-299 3-4 13-15

9 78-95 251-306 2-3 13-16

40˚

4.5 122-149 183-224 14-18 19-23 87-106 257-314 4-5 15-18

9 117-143 172-210 8-10 20-24 91-111 263-322 3-3 16-19

50˚

4.5 131-160 214-261 14-18 18-22 164-201 269-329 5-6 17-20

9 126-154 201-245 8-10 19-24 173-211 276-337 3-4 18-22

60˚

4.5 136-166 244-298 14-17 18-22 111-136 282-344 6-7 19-23

9 131-160 230-281 8-10 19-23 117-143 289-353 4-5 20-24

70˚

4.5 141-172 275-336 14-17 17-21 124-152 294-360 7-8 21-25

9 135-165 258-316 8-10 18-22 131-160 302-369 5-6 22-27

80˚

4.5 145-178 310-378 14-17 17-20 136-166 307-375 8-9 23-28

9 140-171 291-356 8-10 18-22 143-175 314-384 5-6 24-30

90˚

4.5 150-183 349-426 14-17 16-20 149-182 319-390 8-10 25-30

9 144-176 328-401 8-9 17-21 156-191 327-400 6-7 26-32

100˚

4.5 155-189 392-480 13-16 16-19

9 149-182 369-451 8-9 17-21

Page 42: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

42 | Temperature/Pressure Table SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

SV042

30˚

6 64-78 248-303 5-6 15-18

10 67-82 254-311 3-4 16-19

40˚

6 109-134 183-224 18-22 19-23 75-91 261-319 6-8 17-21

10 105-128 172-210 10-12 20-25 79-96 267-327 4-5 18-23

50˚

6 118-144 214-261 18-22 19-23 142-173 273-334 8-10 20-24

10 113-138 201-245 10-12 20-24 149-182 280-342 5-7 21-26

60˚

6 122-149 244-298 17-21 18-22 96-117 286-349 9-11 22-27

10 117-143 230-281 10-12 19-24 101-123 293-358 6-8 24-29

70˚

6 126-154 275-336 17-21 18-22 107-131 299-365 11-13 25-30

10 121-148 258-316 10-12 19-23 113-138 306-374 7-9 26-32

80˚

6 130-159 310-378 17-21 17-21 117-143 311-380 12-15 27-33

10 125-153 291-356 10-12 18-22 123-151 319-390 8-10 29-35

90˚

6 134-164 349-426 17-20 17-20 128-157 324-396 13-16 29-36

10 129-158 328-401 9-12 18-22 135-165 332-406 9-11 31-38

100˚

6 139-170 392-480 16-20 16-20

10 133-163 369-451 9-11 17-21

SV048

30˚

6 71-87 277-339 6-7 15-19

10 75-92 284-347 4-5 16-20

40˚

6 118-144 194-237 21-25 19-23 84-102 291-356 7-9 18-22

10 113-138 182-223 12-14 20-24 88-108 299-365 5-6 19-23

50˚

6 127-155 226-276 21-25 18-22 159-194 305-373 9-11 20-25

10 122-149 213-260 12-14 19-24 167-204 313-383 6-7 21-26

60˚

6 131-160 259-316 21-25 18-22 108-132 320-391 10-13 23-28

10 126-154 243-297 12-14 19-23 113-138 328-400 7-9 24-29

70˚

6 136-166 291-355 20-25 17-21 120-147 334-408 12-15 25-31

10 130-159 273-334 12-14 18-22 126-154 342-418 8-10 27-32

80˚

6 140-171 328-401 20-24 17-20 131-161 348-425 14-17 27-34

10 135-165 308-377 11-14 18-22 138-169 356-436 9-11 29-36

90˚

6 145-177 369-451 20-24 16-20 144-176 362-442 15-18 30-37

10 139-170 347-424 11-14 17-21 151-185 371-453 10-12 32-39

100˚

6 149-183 415-508 19-24 16-19

10 143-175 391-477 11-14 17-21

SV060

30˚

8 68-84 256-313 5-7 19-23

12 73-89 261-319 4-5 20-25

40˚

8 113-138 173-212 18-22 19-23 81-99 277-339 7-8 22-26

12 110-134 162-198 12-14 20-24 86-105 283-346 5-6 23-28

50˚

8 116-142 207-253 17-21 19-23 93-114 299-365 8-9 24-29

12 112-137 193-236 12-14 19-24 99-121 305-373 6-7 25-31

60˚

8 118-145 240-293 17-21 18-23 106-129 321-392 9-11 26-32

12 115-140 224-274 11-14 19-23 113-138 327-400 7-8 28-34

70˚

8 121-148 273-334 17-21 18-22 118-145 342-418 10-12 29-35

12 117-143 255-312 11-14 19-23 126-154 349-427 8-9 30-37

80˚

8 123-151 307-375 16-20 18-22 131-160 364-444 11-14 31-38

12 120-146 287-350 11-13 19-23 139-170 371-454 8-10 33-40

90˚

8 126-154 340-416 16-20 18-22 143-175 385-471 12-15 33-41

12 122-149 318-388 11-13 18-22 152-186 393-480 9-11 35-43

100˚

8 128-157 373-456 16-19 17-21

12 125-152 349-426 11-13 18-22

Page 43: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Temperature/Pressure Table | 43Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

SV070

30˚

12 68-84 256-313 5-7 19-23

16 73-89 261-319 4-5 20-25

40˚

12 117-143 182-222 15-19 21-26 81-99 277-339 7-8 22-26

16 114-139 170-208 11-14 22-27 86-105 283-346 5-6 23-28

50˚

12 120-147 215-263 15-18 20-25 93-114 299-365 8-9 24-29

16 117-143 201-246 11-14 21-26 99-121 305-373 6-7 25-31

60˚

12 123-150 248-304 14-17 20-24 106-129 321-392 9-11 26-32

16 119-146 232-284 11-13 21-25 113-138 327-400 7-8 28-34

70˚

12 126-154 282-344 14-17 19-24 118-145 342-418 10-12 29-35

16 122-149 263-322 10-13 20-25 126-154 349-427 8-9 30-37

80˚

12 129-157 315-385 13-16 19-23 131-160 364-444 11-14 31-38

16 125-153 294-360 10-12 19-24 139-170 371-454 8-10 33-40

90˚

12 132-161 348-426 13-16 18-22 143-175 385-471 12-15 33-41

16 128-156 326-398 10-12 19-23 152-186 393-480 9-11 35-43

100˚

12 134-164 382-466 12-15 17-21

16 131-160 357-436 9-11 18-22

Page 44: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

44 | Waterside Pressure Drop Table SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

WATERSIDE PRESSURE DROP TABLE WATER COIL VOLUME

Model

Water Flow Rate

(GPM)

Water Side Pressure Drop

(PSI)

Water Side Pressure Drop with Internal Valve (PSI)

SV0071.5 0.7 1.02 1.1 1.7

2.5 1.7 2.5

SV0092 1.7 2.2

2.5 2.5 3.33 3.5 4.6

SV0122.5 2.6 3.43 3.6 4.7

3.5 4.8 6.2

SV0153 3.9 5.04 6.5 8.35 9.8 12.5

SV0184 2.7 4.55 4.0 6.76 5.6 9.3

SV0244 2.8 3.36 5.8 6.88 9.7 11.4

SV0305 3.0 3.7

7.5 6.2 7.79 8.6 10.7

SV0366 2.6 3.69 5.4 7.512 9.1 12.6

SV0417 3.6 5.010 6.9 9.513 11.1 15.2

SV0427 3.6 5.010 6.9 9.413 11.1 15.1

SV0488 1.4 2.112 2.8 4.415 4.2 6.6

SV06010 2.3 3.515 4.8 7.218 6.7 10.0

SV07011 2.9 4.216 5.7 8.318 7.0 10.3

All values based upon pure water at 70° F.

SV Series Coaxial Coil Volume (gal)

007 0.04

009 0.06

012 0.08

015 0.09

018 0.14

024 0.14

030 0.24

036 0.27

041 0.27

042 0.27

048 0.49

060 0.62

070 0.62

Page 45: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Compressor Characteristics | 45Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

COMPRESSOR CHARACTERISTICS

Model Voltage Code Rated Voltage Compressor

Description

Compressor Data Plate Cold Winding Resistance Values (+/- 10%) Run

Capacitor (µF/V)Phase RLA LRA

Single Phase Three PhaseR-C S-C Line-Line

SV007 VT & CF 1 208-230/60/1 RGA5453BXD 1 2.6 17.7 4.08 6.63 - 15/370

2 265/60/1 RGA5453BXV 1 2.6 13.5 5.34 6.77 - 15/440

SV007 HZ 1 208-230/60/1 HGA5453BXD 1 2.6 17.7 4.08 6.63 - 15/370

2 265/60/1 HGA5453BXV 1 2.6 13.5 5.34 6.77 - 15/440

SV009 VT & CF 1 208-230/60/1 RGA5471BXD 1 3.4 22.2 2.95 7.35 - 15/370

2 265/60/1 RGA5471BXV 1 2.9 18.8 4.27 10.74 - 10/440

SV009 HZ 1 208-230/60/1 HGA5471BXD 1 3.4 22.2 2.95 7.35 - 15/370

2 265/60/1 HGA5471BXV 1 2.9 18.8 4.27 10.74 - 10/440

SV012 VT & CF1 208-230/60/1 RGA5494BXD 1 4.6 28 2.3 5.9 - 20/370

2 265/60/1 RGA5494BXV 1 3.8 22.2 3.47 8.7 - 15/440

SV012 HZ1 208-230/60/1 HGA5494BXD 1 4.6 27.9 2.3 5.9 - 20/370

2 265/60/1 HGA5494BXV 1 3.8 22.2 3.47 8.69 - 15/440

SV015 1 208-230/60/1 RGA5512BXD 1 5.6 29 2.31 5.45 - 25/440

2 265/60/1 RGA5512BXV 1 4.6 20 3.58 7.39 - 15/440

SV018 1 208-230/60/1 H82J153ABCA 1 6.5 43 1.431 2.383 - 30/370

2 265/60/1 H82J153ABHA 1 5.8 46 1.4 2.4 - 30/440

SV024 1 208-230/60/1 H82J183ABCA 1 7.4 43 1.431 2.383 - 35/370

2 265/60/1 H82J183ABHA 1 6.7 46 1.4 2.4 - 30/440

3 208-230/60/3 H82J183DBLA 3 5.9 63 - - 1.362 -

4 460/60/3 H82J183DBVA 3 2.9 30 - - 5.329 -

SV030 1 208-230/60/1 H82J223ABCA 1 9.9 54 0.982 1.729 - 35/370

2 265/60/1 H82J223ABHA 1 8.5 46 1.4 2.46 - 30/440

3 208-230/60/3 H82J223DBLA 3 6.9 63 - - 1.362 -

4 460/60/3 H82J223DBVA 3 3.6 30 - - 5.329 -

SV036 1 208-230/60/1 H82J283ABCA 1 13.0 74 0.819 1.634 - 40/370

2 265/60/1 H82J293ABHA 1 11.3 67 0.802 1.76 - 35/440

3 208-230/60/3 H82J283DBLA 3 7.8 68 - - 1.152 -

4 460/60/3 H82J283DBVA 3 3.9 34 - - 4.606 -

SV042 1 208-230/60/1 H82J323ABCA 1 13.6 88 0.656 1.558 - 45/370

3 208-230/60/3 H82J323DBLA 3 8.8 68 - - 1.152 -

4 460/60/3 H82J323DBVA 3 4.4 34 - - 4.606 -

SV048 1 208-230/60/1 H82J37MABCA 1 15.7 84 0.54 1.6 - 45/370

3 208-230/60/3 H82J37MDBLA 3 11.0 88 - - 0.928 -

4 460/60/3 H82J37MDBVA 3 5.4 44 - - 3.593 -

SV060 1 208-230/60/1 ZP54K5E-PFV-130 1 26.3 134 0.453 0.792 - 80/370

3 208-230/60/3 ZP54K5E-TF5-130 3 15.6 110 - - 0.68 -

4 460/60/3 ZP54K5E-TFD-130 3 7.8 52 - - 3.2 -

SV070 1 208-230/60/1 ZP57K5E-PFV-130 1 28.3 178 0.97 0.365 - 80/370

3 208-230/60/3 ZP57K5E-TF5-130 3 19.2 136 - - 0.6 -

4 460/60/3 ZP57K5E-TFD-130 3 8.7 67.1 - - 2.52 -

Page 46: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

46 | Corner Weights (HZ) SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

CORNER WEIGHTS (HZ)Configuration Left Hand Return Right Hand ReturnModel Total Left Front* Right Front* Left Back Right Back Left Front*Right Front* Left Back Right Back

SV007-HZ Lbs 98 28 21 25 24 21 28 24 25

kg 45 13 10 11 11 10 13 11 11SV009-HZ Lbs 103 29 23 26 25 23 29 25 26

kg 47 13 10 12 11 10 13 11 12SV012-HZ Lbs 105 29 24 26 26 24 29 26 26

kg 48 13 11 12 12 11 13 12 12SV015-HZ Lbs 127 36 28 34 29 28 36 29 34

kg 58 16 13 15 13 13 16 13 15SV018-HZ Lbs 177 57 36 48 37 36 57 37 48

kg 80 26 16 22 17 16 26 17 22SV024-HZ Lbs 181 58 37 48 38 37 58 38 48

kg 82 26 17 22 17 17 26 17 22SV030-HZ Lbs 194 61 41 52 41 41 61 41 52

kg 88 28 18 23 19 18 28 19 23SV036-HZ Lbs 237 71 49 66 52 49 71 52 66

kg 108 32 22 30 24 22 32 24 30SV042-HZ Lbs 231 70 47 64 50 47 70 50 64

kg 105 32 21 29 23 21 32 23 29SV048-HZ Lbs 268 87 60 62 60 60 87 60 62

kg 122 39 27 28 27 27 39 27 28SV060-HZ Lbs 288 88 65 69 66 65 88 66 69

kg 131 40 29 31 30 29 40 30 31SV070-HZ Lbs 316 98 72 76 70 72 98 70 76

kg 143 44 32 35 32 32 44 32 35*Front is control box end

Page 47: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Wiring Diagrams | 47Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

WIRING DIAGRAMS

Figure # 14 Dwg SV111000- Single Phase Base Unit, PSC Fan Motor

Page 48: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

48 | Wiring Diagrams SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Figure # 15 Dwg 311000

Page 49: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Wiring Diagrams | 49Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Figure # 16 Dwg SV111007- Single Phase Base Unit, Constant Torque ECM Fan Motor

Page 50: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

50 | Wiring Diagrams SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Figure # 17 Dwg SV111003 - Single Phase Base Unit, Constant Airflow ECM Fan Motor

Page 51: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Wiring Diagrams | 51Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Figure # 18 Dwg SV111001- Three Phase Base Unit, PSC Fan Motor

Page 52: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

52 | Wiring Diagrams SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Figure # 19 Dwg SV111002- Single Phase Unit with Waterside Economizer, PSC Fan Motor

Page 53: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Wiring Diagrams | 53Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Figure # 20 Dwg 311003- Three Phase Base Unit, Constant Airflow ECM Fan Motor

Page 54: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

54 | Dimensional Drawings SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

DIMENSIONAL DRAWINGSVertical

F

AB

CD

EF

GH

JK

MN

PQ

SV

007

1919

24.2

510

84.

59.

52.

449.

6813

.87

168

105.

63/

4" F

.P.T

.10

x16x

1S

V00

919

1924

.25

108

4.5

9.5

2.44

9.68

13.8

716

810

5.6

3/4"

F.P

.T.

10x1

6x1

SV

012

1919

24.2

510

84.

59.

52.

449.

6813

.87

168

105.

63/

4" F

.P.T

.10

x16x

1S

V01

521

.521

.532

.25

108

5.75

12.1

2.85

8.45

15.8

720

1416

8.1

3/4"

F.P

.T.

16x2

0x1

SV

018

21.5

21.5

32.2

514

143.

64.

82.

858.

4515

.87

2014

164.

83/

4" F

.P.T

.16

x20x

1S

V02

421

.521

.539

.25

1414

3.6

4.8

2.8

14.9

518

.87

2018

204.

83/

4" F

.P.T

.20

x20x

1S

V03

021

.521

.539

.25

1414

3.6

4.8

2.8

14.9

518

.87

2018

204.

83/

4" F

.P.T

.20

x20x

1S

V03

621

.526

43.2

515

.514

6.5

4.2

2.75

10.7

718

.87

2422

244.

23/

4" F

.P.T

.24

x24x

1S

V04

121

.521

.539

.25

15.5

142

4.2

2.8

14.9

518

.87

2018

204.

23/

4" F

.P.T

.20

x20x

1S

V04

221

.526

43.2

515

.514

6.5

4.2

2.75

10.7

718

.87

2422

244.

23/

4" F

.P.T

.24

x24x

1S

V04

824

32.5

45.2

518

1410

63.

2613

.220

.87

3022

246

1" F

.P.T

.24

x30x

1S

V06

024

32.5

45.2

518

1410

63.

2613

.220

.87

3022

246

1" F

.P.T

.24

x30x

1S

V07

026

33.2

558

.25

1815

.510

.87

2.92

13.3

625

.87

3030

327

1" F

.P.T

.16

x30x

1 (2

)

Wid

thD

epth

Hei

ght

MO

DE

LC

onde

nser

W

ater

C

onne

ctio

ns

Rec

omm

ende

d S

tand

ard

Rep

lace

men

t N

omin

al F

ilter

Siz

eR

/A D

uct

Flg

Wid

thR

/A D

uct

Flg

Hei

ght

Filte

r R

ack

Page 55: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Dimensional Drawings | 55Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Horizontal

Hor

izon

tal

AB

CD

EF

GH

JK

MN

PQ

RT

LV00

719

3311

.51.

516

.15

15.3

52.

389.

625

5.13

5.81

256.

223.

65.

131.

6614

.58.

63/

4" F

.P.T

.10

x16x

1LV

009

1933

11.5

1.5

16.1

515

.35

2.38

9.62

55.

135.

8125

6.22

3.6

5.13

1.66

14.5

8.6

3/4"

F.P

.T.

10x1

6x1

LV01

219

3311

.51.

516

.15

15.3

52.

389.

625

5.13

5.81

256.

223.

65.

131.

6614

.58.

63/

4" F

.P.T

.10

x16x

1LV

015

2243

171.

520

.15

21.3

52.

8615

.38

6.9

5.95

9.8

3.6

6.4

3.64

18.5

153/

4" F

.P.T

.16

x20x

1LV

018

2243

171.

520

.15

21.3

52.

8615

.38

5.7

8.6

6.3 6

9.15

5.2

1.5

18.5

153/

4" F

.P.T

.16

x20x

1LV

024

2243

171.

525

.15

16.3

52.

8614

.13

5.7

8.6

6.36

9.15

5.2

1.5

23.5

153/

4" F

.P.T

.16

x25x

1LV

030

2243

171.

525

.15

16.3

52.

8614

.13

5.7

8.6

6.36

9.15

5.2

1.5

23.5

153/

4" F

.P.T

.16

x25x

1LV

036

2254

.519

1.5

3023

2.85

16.1

36.

98.

637.

759.

86.

41.

4628

.517

3/4"

F.P

.T.

18x3

0x1

LV04

1 (N

/A)

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

LV04

222

54.5

191.

530

232.

8516

.13

6.9

8.63

7.75

9.8

6.4

1.46

28.5

173/

4" F

.P.T

.18

x30x

1LV

048

2554

.521

1.5

34.6

18.4

2.86

18.1

37.

510

7.7

10.8

67

2.4

3319

1" F

.P.T

.20

x34.

5x1

LV06

025

54.5

211.

534

.618

.42.

8618

.13

7.5

107.

710

.86

72.

433

191"

F.P

.T.

20x3

4.5x

1LV

070

2565

211.

548

.115

.42.

8618

.13

6.5

11.2

67

126

1.93

46.5

191"

F.P

.T.

20x2

4x1

(2)

Con

dens

er

Wat

er

Con

nect

ions

Rec

omm

ende

d S

tand

ard

Rep

lace

men

t N

omin

al F

ilter

Siz

eM

OD

EL

Wid

thD

epth

Hei

ght

R/A

Duc

t Fl

g W

idth

R/A

Duc

t Fl

g W

idth

R/A

Duc

t Fl

g H

eigh

t

Page 56: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

56 | Notes SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

NOTES

Page 57: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Notes | 57Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Page 58: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

58 | Notes SV Heat PumpSeries

SV Heat Pump Series8 733 914 818 (2013/08) Subject to change without prior notice

Page 59: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

Notes | 59Revised 08-13

8 733 914 818 (2013/08)SV Heat Pump Series

Page 60: Model SV - i Series Geothermal Heat Pump SV007 …ingramswaterandair.com/brochures/201309121821130.IOM_SV_201308...Model SV - i Series Geothermal Heat Pump 8 733 914 818 ... Cooling

601 N.W. 65th Court, Ft. Lauderdale, FL 33309Phone: 866-642-3198 | Fax: 954-776-5529www.boschtaxcredit.com | www.bosch-climate.usRevised 08-13

Made in FLORIDA