MK Series Remote Indicators For Line Isolation Monitors and Fault Location Technical Bulletin NAE2022020 / 09.2011 2

Upload: doancong

Post on 19-Feb-2019

224 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

MK SeriesRemote Indicators

For Line Isolation Monitors and Fault Location

Technical BulletinNAE2022020 / 09.2011

2

Page 2: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

2 Isolated Power System Equipment

Remote IndicatorsMK2000 Series

MK Series

Device features• LEDdisplayforlonglife

• Nointerferencewithmedicalequipment

• InterfaceswithallBENDERLineIsolation Monitors LIM2000 and LIM2010

• Useslowvoltagewiring(12VDCor12 VAC)

• Mountstostandardelectricalgangbox

• Connectionbyscrewterminalstrip

• Easy-to-clean,ruggedstainlesssteeland Lexandesign

• Optionsincludetestbutton,overload alarmLED,anddigitaldisplayshowing real-timeTHCreadings

Product DescriptionMKseriesremoteindicatorsaredesignedforusewiththeBENDERLIM2010LineIsolationMonitor.AremoteindicatorduplicatesaudibleandvisualalarmindicationsontheLIM.Allremoteindicatorsincludeagreen“SAFE”LED,ared“HAZARD”LED,anda“MUTE”buttonwithanintegralamberLED.The“MUTE”buttonisusedtosilencetheremoteau-diblealarm.Optionally,itcanalsobeusedtosilenceallaudiblealarmsinthesystem.

Standardfeaturesofallremoteindicatorsinclude:• Green“SAFE”LEDtoindicateanormalcondition• Red“HAZARD”LEDtoindicateanalarmcondition• MUTEpushbuttonwithintegratedamber“MUTE”LEDtosilencetheaudiblealarmModelswithadditionalfeaturesinclude:• MK2000P: Testbutton• MK2000C: Amber“OVERLOAD”alarmLED• MK2000CP: Amber“OVERLOAD”alarmLEDandtestbutton• MK2000CBM: Amber“OVERLOAD”alarmLED,testbutton,anddigital displaysshowingTHCreadingand%isolationtransformerloadinreal-timeMK2000seriesindicatorsareavailableinone-gangortwo-gangstainlesssteelfaceplatesforflushmountingintoapanelorwallboxwitha2”minimumdepth.TheMK2000CBMfeaturesadigitaldisplaywhichmimicstheLIMhazardcurrentdisplay.ThedisplayconsistsoftwosevensegmentredLEDsthatdisplaybetween0.1mAto9.9mA.The“CBM”versionisonlyavailableinatwo-gangconfiguration.

Operational InformationGeneral: Theremoteindicatorsarecontrolledbya12VDCsignalfromtheLIM.Agreen“SAFE”LEDstaysilluminatedwhilethesystemisinthenormalcondition.

WhentheLIMgoesintoalarm,thehazardlineisenergized.Thegreen“SAFE”LEDextin-guishesandthered“HAZARD”LEDilluminates.Whilein“HAZARD”mode,theaudiblealarmwillsound.Whendepressed,the“MUTE”buttonshallmutetheaudiblealarmsignal.ActuationofthisbuttonshallcausetheintegralamberLEDtoilluminate,indicatingthattheaudiblealarmhasbeensilenced.Whenthehazardcurrenthasreturnedtotheaccept-ablelevel,thealarmindicatorsshallautomaticallyreset.

Test Button: The“TEST”buttonwillputtheLIMthroughthetestcycle.Thisbuttonmustbeheldforapproximatelyfive(5)secondstocompletethetest.

Load Monitoring: Theloadmonitoringfeatureprovidestheabilitytomonitorthepercent-ageofloadusedonthesecondarysideoftheisolationtransformer.Thisisaccomplishedbyfeedingonelegofthesecondarywiresfromthetransformerthroughacurrenttrans-former,andsettingthesecondaryamperageoftheisolationtransformer.TheLIMcalcu-latesthepercentageofloadbeingused.Whentheisolationtransformerapproaches80%ofratedpower,aflashingamberLEDilluminates.When100%ofpowerisreached,aflash-ingamberLEDilluminatesaswellasanaudiblealarm.

Digital Display:The“CBM”optionfeaturesadigitaldisplayshowingboththetotalhazardcurrentandthepercentageoftransformerload.

Page 3: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

Isolated Power System Equipment 3

P

1 - Green“SAFE”LED

2 - Amber“OVERLOAD”LED(“C”optiononly)

3 - Red“HAZARD”LED

4 - “TEST”button(“P”optiononly)

5 - “MUTE”buttonwithamberLED

1

2

3

4

5

Operating and Display Elements Example: MK2000CP-G1 Operating and Display Elements Example: MK2000CBM

1

45

2

3

6

7

1 - Green“SAFE”LED

2 - Red“HAZARD”LED

3 - Amber“OVERLOAD”LED

4 - “TEST”button

5 - “MUTE”buttonwithamberLED

6 - DigitaldisplayshowingTotalHazardCurrent

7 - DigitaldisplayshowingTransformerLoad

Page 4: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicator

4 Isolated Power System Equipment

Dimensions: MK2000-G1 / MK2000P-G1 / MK2000C-G1 / MK2000CP-G1(Dimensionsininches)

Dimensions: MK2000CBM(Dimensionsininches)

Ordering Information

Product Type Mute Test Overload Digital Display Size Approval Article No.

MK2000-G1 Yes -- -- -- One-gang B 5213 00002

MK2000-G2 Yes -- -- -- Two-gang B 5213 00007

MK2000P-G1 Yes Yes -- -- One-gang B 5213 00188

MK2000C-G1 Yes -- Yes -- One-gang B 5213 00020

MK2000CP-G1 Yes Yes Yes -- One-gang B 5213 00021

MK2000CBM Yes Yes Yes Yes Two-gang B 5213 00022

MK2000-2G2 Yes -- -- -- Two-gang B 5213 00099

Technical Data: MK2000-G1 / MK2000-G2 / MK2000P-G1 / MK2000C-G1 / MK2000CP-G1 / MK2000CBMOperating voltage 12V DC or 12V ACMax. current 50 mA (MK2000CBM 100 mA)Operation class continuous operationAmbient temperature when operating +32º F to +122º F 0º C to +50º when stored -13º F to +158º F -25º C to +70º CConnection screw terminal blockConductor size AWG 30…12Tightening torque 5…7 lb-in.Mounting by screwsWeight MK2000-G1 / MK2000P-G1 / MK2000C-G1 / MK2000CP-G1 0.25 lb MK2000-G2 / MK2000CBM / MK2000-2G2 0.32 lb

Page 5: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

IsolatedPowerSystemEquipment 5

Remote Annunciator StationRAS Series

RAS Remote Annunciator Station

Device Features• Containsmultiplelineisolationmonitor remoteindicatorsforcentralizedmonito- ringofisolatedpowersystems

• Flushorsurfacemountedapplications

Digital system remote indicator

Product Description

RASseriesremoteannunciatorstationsutilizemultipleMKseriesremoteindicators,eachconnectedtoalineisolationmonitor.Includedremoteindicatorsmayfeatureabuilt-intestbuttonandatransformeroverloadLED.EachremoteindicatorispowereddirectlybytheLIM2010lineisolationmonitor,locatedattheisolatedpowerpanel.

Backbox

Forflushmountedapplications,thebackboxisfabricatedfromminimum16GAgalva-nizedsteel.Surfacemountedenclosuresarefinishedwithacoatofhospitalivoryepoxyenamelorequivalent.

Faceplate

Manufacturedfromminimum14GAtype304stainlesssteelwitha#4brushedfinish,thefaceplatesupportstheLIMremoteindicators.Thefaceplateforflushmountedunitsex-tends1”onallsidesofthebackbox.Forsurfacemountedmodules,thefaceplatematchesthedimensionsofthebackbox.

Remote Indicators

Refertothesection“RemoteIndicators,MK2000Series”inthisdocumentformoreinfor-mationonavailablemodels.

Page 6: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicator

6 Isolated Power System Equipment

1 - Stainless Steel Faceplate

2 -

3 - Remote Indicator

1.000"

3

1

2

MK2000

HAZARD

SAFE

MUTE

BENDER

MK2000

HAZARD

SAFE

MUTE

BENDER

MK2000

HAZARD

SAFE

MUTE

BENDER

MK2000

HAZARD

SAFE

MUTE

BENDER

BENDER

HAZARD

MK2000

SAFE

MUTE

BENDER

HAZARD

MK2000

MUTE

BENDER

SAFE

HAZARD

MK2000

SAFE

MK2000

MUTE MUTEHAZARD

BENDER

SAFE

Sample Outline: Remote Annunicator Station (Example Model: RAS-08B)

1 - Quantity of Remote Indicators 10: Ten

12: Twelve 14: Fourteen

16: Sixteen

2 - A: MK2000P

B: MK2000 C: MK2000C D: MK2000CP E: MK2000CBM

3 -

R A S1

0 8-2

B3

Ordering Information

* Refer to section “Remote Indicators, MK2000 Series” for information on remote indicators. See table below for information regarding available con�gurations and backbox sizes.Flush mounted modules shall have a face-plate that extends 1” on all sides from the backbox. Surface mounted modules shall have a faceplate that exactly matches the dimensions of the backbox.

Available Con�gurations and Backbox Sizes

Supported Remote IndicatorsSupported Quantites of

Remote IndicatorsBackbox Dimensions

(W x H x D) Backbox

Part Number

MK2000, MK2000P, MK2000C, MK2000CP 2, 3, 4, 5, 6, 7, 8 12” x 8” x 4” B120804

MK2000, MK2000P, MK2000C, MK2000CP 9, 10, 11, 12 12” x 12” x 4” B121204

MK2000, MK2000P, MK2000C, MK2000CP 13, 14, 15, 16 12” x 16” x 4” B121604

MK2000CBM 2, 3, 4 12” x 8” x 4” B120804

MK2000CBM 5, 6 12” x 12” x 4” B121204

MK2000CBM 7, 8, 9 16” x 12” x 4” B161204

MK2000CBM 10, 11, 12 18” x 12” x 4” B181204

MK2000CBM 13, 14, 15, 16 18” x 18” x 4” B181804

*Note: Backboxes are ordered separately

Backbox, Galvanized Steel

Type of Remote Indicators*

Mounting Type[]: Flush MountingS: Surface Mounting

02: Two04: Four06: Six08: Eight

Page 7: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

Isolated Power System Equipment 7

Remote Indicating StationMK2430

MK2430

Device Features• Displaysoperatingmessagesandalarmsforallconnecteddevices,includingmul-tiple,interconnectedLIM2010andEDSdevices

• BacklitLCDdisplay

• Predefinedtextsin20languages

• 200freelyprogrammablemessagetexts includinglocationlabels

• Audiblealarmwithmutebutton

• Settingschangedviaeasy-to-useon- boardmenu

• Flushandsurfacemountable

• 12digitalinputs(MK2430-11option)

• Storesupto250timestampedalarms

Digital system remote indicator

Product DescriptionTheuniversalremotealarmindicatorandoperatorpanelMK2430isintendedforvisualandaudibleindicationofoperatingstatusandalarmmessagesfromBENDERsystemsin-cludingtheLIM2010andEDSseriesgroundfaultlocationevaluators.TheMK2430dis-playsinformationregardingeachindividualdevice,system,orroomandcandefinecus-tomlabelsbasedoneachindividualapplication.Acompletesystemtestmayalsobedonefromthisdevice.

Alarm and Display Features:Statusandalarmsareviewedonaneasy-to-readLCDdisplay.Featuresinclude:

• Normaloperationindicator(greenLED)• Totalhazardcurrent• Overload• Overtemperature• LocationoffaultfromEDSdevices

• Connectionmonitoringalarms• Deviceerrors• Testresults• Measuredvalues• Audibleandvisualindication

Duringnormaloperation,theMK2430indicatestheoverallstatusofthesystem.TheMK2430-11features12digitalinputsallowingmessagesfromothertechnicalequipmenttoberecordedanddisplayed.

Display / Operating ElementsThebacklitdisplayfeaturesfourlinesof20characters.Itsuppliesmedicalandtechnicalper-sonnelwithclearinformationtoknowthestatusofthesystem.Everyalarmmessageutilizesthreelines.Thefourthlinecontainsstatusinformation(numberofmessages,testproce-dures,menuinformation).ThreeLEDsarelocatedabovethetextdisplay.Theyindicate:normaloperation(green),warnings(yellow)oralarms(red).Fivepushbuttonsareavailableforacknowledgingalarmsandwarnings,andforthemenusystem.

ProgrammingAlongwithcustomizablelabels,standardmessagesbuiltintotheMK2430arealsoavail-able.Thesemessagesareavailablein20differentlanguages.Deviceprogrammingcanbecompletedeitherthroughthedevice‘sbuilt-inmenuorthroughaPC.AnLEDandanaudiblesignalmaybeassignedtoeachindividualmessage.

Page 8: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicator

8 IsolatedPowerSystemEquipment

1- LED“NORMAL”:Normaloperatingmode

2- LED“WARNING”:Warningmessages

3- LED“ALARM”:Alarmmessages

4- LCD:Displayofoperatingandalarmmessages

5- “Mute”button Duringoperation:Mutesbuzzer Inmenumode:Movesbackastep

6- “TEST”button: Activatesself-testforinterconnecteddevices

7- “Menu”button: Duringoperation:Opensmenu Inmenumode:Enterkey(confirmchanges)

8- “Additionaltext”button: Duringoperation:Displaysadditionalinformation Inmenumode:Scrollsdown

9- “Scroll”button: Inoperatingmode:Scrollsthroughmessages Inmenumode:Scrollsup

Operating and Display Elements

History MemoryTimestampedwarningandalarmmessagesarestoredinthebuilt-inhistorymemoryautomatically.Upto250textmessagescanbesaved.MessagescanberetrievedthrouhtheMK2430‘sbuilt-inmenu.

MK2430-12TheMK2430-12isusedforvisualandaudibleindicationofalarmswhenusingBENDERLIM2010lineisolationmonitorsandEDSse-riesgroundfaultlocationevaluators.Thisindicatorisperfectfornursedesksthatoverseeseveraldifferentcriticalrooms.

MK2430-11TheMK2430-11additionallyfeatures12digitalinputscontrolledbyvoltagefree(dry)contacts.Theseinputsareidealformonitor-ingothermedicalequipment.

MK2430P-...TheMK2430P-…additionallyfeaturesstandardmessagesandfac-toryactivationofupto20alarmaddresses.

Customizablelabelsmaybeprogrammedindividuallyforeachalarmaddress.Theselabelswilldisplaywhenanalarmisactivetoensurepersonnelknowthelocationofaproblem.

1

56

7

23

4

98

Individualalarmtext (lines1…3)

Status line

Individualadditional text(lines5…7)

Status line

Sample alarm messages:

Page 9: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

Isolated Power System Equipment 9

MK2430-11RS

Remote Indicating Station Dimensions: Surface-mounted versionDimensionsininches

1 - StainlessSteelFaceplate,14”Wx10”H(T1410-MK2430)

2 - Backbox,GalvanizedSteel,12”Wx8”Hx4”D(B120804)

3 - RemoteIndicator(MK2430-11)

4 - PowerSupplyw/mountinghardware(CP-D24/0.24)

Remote Indicators Assembly

Product Type Description Article No.

MK2430-11RSRemote indicator with 12 programmable digital inputs,

preassembled with front trim, power supply and backboxB 5213 01095

MK2430-12RSRemote indicator preassembled with front trim, power supply

and backboxB 5213 01096

Remote Indicators Components and Accessories

Product Type Description Article No.

MK2430-11Remote indicator with 12 programmable digital inputs and a

BMS bus interface for flush mountingB 9510 0001NA

MK2430-12 Remote indicator with a BMS bus interface for flush mounting B 9510 0002NA

B120804Backbox for MK2430, 12” W x 8” H x 4” D

B 5213 00367

T1410-MK2430304SS front trim for MK2430

14” W x 10”HP 103 00195

CP-D 24/0.42Power supply with DIN rail

100-240 VAC inputP 138 00049

TMK-Set V3.xx Software for MK800/MK2430 (download or CD) B 9602 0087

Page 10: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicator

10 Isolated Power System Equipment

Remote StationMK800

MK800

Device Features• IndicationofsystemstatusandalarmsforacompleteBENDERsystem

• BacklitLCDdisplay

• Largegreen,yellow,andredLEDs

• 80predefinedstandardmessagesin 20languages

• 1000freelyprogrammablelabels

• Settingscarriedouteitherthroughon- boardmenuorviaaPC

• Historymemorystoringupto1000time-stampedalarmsandmessages

• 16digitalinputs/outputs(option)

• 1programmablerelay(option)

• Fivelargefunctionpushbuttons

• Availableforflushandsurfacemountingaswellasdoormounting

Product DescriptionTheMK800remotestationisafull-featuredremoteindicatingstationutilizedfor:

• indicationandvisualizationofoperatingstatusandalarmmessagesforcomplete BENDERsystems

• Centraloperationandparametersettingforallinterconnecteddevices

• Displayingmeasuredvaluesandsettingofresponsevaluesformonitoringpurposes

TheMK800monitorscompleteBENDERsystemsutilizingtheLIM2010lineisolationmoni-torandEDSseriesGroundFaultLocationEvaluator.Visualandaudibleindicationofalarmsarebuiltintothedevice.Thisdeviceisidealfornursestationsandtechnicalsta-tionsinchargeofmanydifferentcriticalareasofahospital.

Display / Operating ElementsTheMK800featuresalarge,backlitLCDdisplay.Itsuppliesmedicalandtechnicalpersonnelwithclearinformationtoknowthestatusofthesystem.Statusandalarmmessagesfromev-eryBENDERdeviceconnectedtotheBMSnetworkmaybedisplayedonthisdevice..Additionaltextcontainsstatusinformation,(suchasnumberofmessages),teststatus,ormenuinformation.Intheeventofanalarm,audibleindicationisalsoprovidedtoalertper-sonnelinatimelyfashion.AcentraltechnicalstationmayusetheMK800tocarryoutparam-etersettingsforallinterconnecteddevices.ThreeLEDs(green,yellow,red)givesimplevisualindicationofthesystem‘sstatus.Fivelarge,backlitpushbuttonsareprovidedforsimplemenuandmessagenavigation.Thepushbut-tonsprovidethefollowingfunctions:

• Visualandaudiblealarmtest

• Scrollingthroughalarmandwarningmessages

• Parametersettings

• Navigationthroughbuilt-inmenu

Digital remote indicating station

Page 11: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

Isolated Power System Equipment 11

Parameter SettingTheMK800provides80predefinedalarmmessagesavailablein20differentlanguages.Parametersettingmaybecarriedoutviatheonboardmenu.Additionally,theTMK-SetPCsoftwareallowsupto1000individualmessagestobeprogrammedandstoredontheMK800viaaUSBorRS-485connection.

History MemoryTimestampedwarningandalarmmessagesareautomaticallystoredintotheMK800‘sinternalmemory.Upto1000messagesmaybestored.EacheventcanbeeasilyaccesseddirectlyontheMK800.Additionally,thehistorymemorymaybeoutputtotheTMK-Historysoftwaretoprovidehistoryanalysis.

Digital Inputs / Relay Output (MK800-11 option)TheMK800-11additionallyfeatures16digitalinputscontrolledbyvoltagefree(dry)contacts.Theseinputsareidealformonitoringothermedicalequipment.

Fortestfunctionsorcommonalarms,aprogrammablerelayisalsoavailable.

Operating and Display Elements

1- LCD:Displayofoperating,warningandalarmmessages

2- LED“NORMAL”:Operationindicator

3- LED“WARNING”:Warningmessages

4- LED“ALARM”:Alarmmessages

5- Testbutton“TEST”:Activatesself-testforsupportingdevices

6- Buzzer“mute”:Duringoperation:Mutesbuzzer Inmenumode:Movesbackastep

7- “Scrollkey”:Duringoperation:Scrollsthroughmessages Inmenumode:Scrollsup

8- “Add.text”key:Duringoperation:Displaysadditionalinfo Inmenumode:Scrollsdown

9- “MENU”key:Duringoperation:Opensmenu Inmenumode:Enterkey(confirmchanges)

2 3 4

1

5 6 7 8 9

Page 12: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicator

12 Isolated Power System Equipment

Remote Indicating Station Dimensions MK800-11RS & MK800-12RS

Dimensions in inches

1 -

2 -

3 -

4 -

5 -

6 -

MK800-11RS

Remote Indicators Components and Accessories

Product Type Description Art. No.

MK800E-11Remote alarm indicator with 16 digital inputs built-in type w/

out enclosureB 9510 0106NA

MK800E-12 Remote alarm indicator built-in type w/out enclosure B 9510 0107NA

UP800 Mounting Shell B 951 00110

BR800-2 White bezel frame for MK800 B 951 00112

B120804Backbox for MK80012” W x 8” H x 4” D

B 5213 00367

T1410-MK800304SS front trim for MK800

14” W x 10”HP 103 00196

CP-D 24/0.42Power supply with DIN rail

100-240 VAC inputP 138 00049

TMK-Set V3.xx Software for MK800/MK2430 (download or CD) B 9602 0087

6

Remote Indicators Assembly

Product Type Description Art. No.

MK800-11RS Remote Alarm indicator with 16 digital inputs, preassembled with front trim, bezel frame, backbox and power supply B 5213 01093

MK800-12RS Remote Alarm indicator preassembled with front trim, bezel fra-me, backbox and power supply B 5213 01094

Stainless Steel Faceplate, 14”W x 10”H (T1410-MK800)

Backbox, Galvanized Steel, 12”W x 8”H x 4”D (B120804)

Remote Indicator (MK800E-11)

Power Supply with Mounting Hardware (CP-D 24/0.24)

Bezel Frame (BR800-2)

Mounting Shell (UP800)

Page 13: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

Isolated Power System Equipment 13

Technical Data: MK800 / MK2430 Remote Indicating Station

Insulation coordination acc. to IEC 60664-1Rated insulation voltage AC 250 VRated impulse voltage/pollution degree 4 kV/3

Supply voltageSupply voltage US AC/DC 24 VFrequency range US 0/40…60 HzOperating range US AC 18…28/DC 18…30 VPower consumption (MK800 / MK2430) < 5 VA / ≤ 3 VA

Displays and LEDsDisplay, characters four line, 4 x 20 charactersStandard message texts 20 languagesAlarm addresses (MK800 / MK2430) < 300 / < 150Programmable text messages (MK800 / MK2430) 1000 / 200History memory (messages) (MK800 / MK2430) 1000 / 250Standard text message 3 x 20 charactersAdditional text message (accessed via button) 3 x 20 charactersAlarm LEDs (three different colors) NORMAL (green) WARNING (yellow) ALARM (red)Menu texts English /SpanishButtons 5 (LIM test, buzzer mute, additional text, scroll, menu)

BuzzerBuzzer message configurableBuzzer interval configurableBuzzer frequency configurableBuzzer repetition configurable

Inputs (MK800-11 / MK2430-11) Only Digital inputs (MK800 / MK2430) 16 (IN1…IN16) / 12 (IN1....IN12)Galvanic separation yesControl of digital inputs via potential-free contacts/extraneous voltageOperating principle N/O or N/C operation / Off, can be selected for each inputFactory setting (MK800 / MK2430) Off / N/O OperationVoltage range (high) (MK800 / MK2430) AC/DC 10...30 V / AC/DC 15...30 VVoltage range (low) (MK800 / MK2430) AC/DC 0...5 V / AC/DC 0...2 V

Communication InterfaceInternalInterface/protocol RS-485/BMSBaud rate 9.6 kBit/sCable length ≤3900 ft (1200 m)Recommended cable (shielded, shield connected to PE on one side) min. J-Y(St)Y 2 x 0.6Terminating resistor 120 Ω (0.25 W) can be connected via DIP switchDevice address, BMS bus 1(…150)Factory setting device address 1 (master)External (MK800 Only)Baud rate (default setting) 57.6 kBit/sDevice address, BMS bus 1…99Factory setting device address 1 (master)

ProgrammingInterfaces RS-485 / BMS / USBSoftware TMK-Set V 3.0 and higherFactory setting password query activated

ColorsFront foil RAL 7035 (light grey) / RAL 7012 (basalt grey)Marking buttons RAL 5002 (ultramarine blue): RAL 7035 (light grey)Front plate RAL 7035 (light grey)

Switching elements (MK800 Only)Number of changeover contacts 1 (MK800-11 only)Operating principle N/C or N/O operation (programmable)Electrical service life, number of cycles 10.000Contact data acc. to IEC 60947-5-1 Utilization category AC-13 AC-14 DC-12 Rated operational voltage 24 V 24 V 24 V Rated operational current 5 A 3 A 1 AMinimum contact load 1 mA at AC/DC > 10 V

General dataEMC immunity acc. to EN 61000-6-2EMC emission acc. to EN 61000-6-4Operating temperature + 23 °F…+122°F (- 5 °C…+50°C)Classification of climatic conditions acc. to IEC 60721 Stationary use 3K5 Transport 2K3 Storage 1K4Classification of mechanical conditions acc. to IEC 60721 Stationary use 3M4 Transport 2M2 Long-time storage 1M3Operating mode continuous operationMounting any positionConnection plug-in terminalsConnection properties (supply voltage, BMS bus) rigid / flexible / conductor sizes 0.2…2.5/0.2…2.5 mm2/AWG 24-12 flexible with ferrule without/with plastic sleeve 0.25…2.5/0.25…2.5 mm2

Connection properties (inputs) rigid / flexible / conductor sizes 0.08…1.5/0.08…1.5 mm2/AWG 28-16 flexible with ferrule without / with plastic sleeve 0.25…1.5/0.25…0.5 mm2

Stripping length 0.25” (7 mm)Tightening torque 4.4…5.3 lb-in (0.5…0.6 Nm)Degree of protection, internal components (DIN EN 60529) IP50 (NEMA 1)Degree of protection, terminals (IEC 60529) IP20 (NEMA 1)Flammability class UL94V-0Product standards IEC 60364-7-710, UL 1022Operating manual (MK800 / MK2430) TGH1408 / TGH1389Weight (MK800 / MK2430) < 2.1 lb (950 g) / <0.46 lb (210 g)MK800-...RS / MK2430-...RSSupply voltage US AC 100-240 V Frequency range US 47-63 HzInrush current (115 V AC/ 230 V AC) < 15 A / < 30 AOperating range US AC 90...264/DC 120...370 VWeight (MK800 / MK2430) < 8.7 lb (3628.7 g) / 7.1 lb (3220.5 g)

Page 14: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicator

14 Isolated Power System Equipment

Wiring Diagram: Using MK2000

MK2000

LIM2010

SAFE

HAZARD

MUTEESC

TEST

RESET

MENU

L1L212VDC CMABRI1K1/NCK1/COMK1/NOSAFE

HAZARD

RI2

LIMGNDTEST1S1Z1/M+1S2Z2/M-K2/COMK2/NCK2/NO

GND2

F1, F2

To Load Center

Connector plateCP-LIM2010

Wiring Diagram: Using MK2000P

LIM2010

SAFE

HAZARD

MUTEESC

TEST

RESET

MENU

L1L212VDC CMABRI1K1/NCK1/COMK1/NOSAFE

HAZARD

RI2

LIMGNDTEST1S1Z1/M+1S2Z2/M-K2/COMK2/NCK2/NO

GND2

F1, F2

To Load Center

Connector plateCP-LIM2010

MK2000P

P

Page 15: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

IsolatedPowerSystemEquipment 15

Wiring Diagram: Using MK2000C

LIM2010

SAFE

HAZARD

MUTEESC

TEST

RESET

MENU

L1L212VDC CMABRI1K1/NCK1/COMK1/NOSAFE

HAZARD

RI2

LIMGNDTEST1S1Z1/M+1S2Z2/M-K2/COMK2/NCK2/NO

GND2

F1, F2

To Load Center

Connector plateCP-LIM2010

MK2000CCT

Wiring Diagram: Using MK2000CP

LIM2010

SAFE

HAZARD

MUTEESC

TEST

RESET

MENU

L1L212VDC CMABRI1K1/NCK1/COMK1/NOSAFE

HAZARD

RI2

LIMGNDTEST1S1Z1/M+1S2Z2/M-K2/COMK2/NCK2/NO

GND2

F1, F2

To Load Center

Connector plateCP-LIM2010

CT MK2000CP

P

Page 16: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicator

16 Isolated Power System Equipment

Wiring Diagram: Using MK2000CBM

LIM2010

SAFE

HAZARD

MUTEESC

TEST

RESET

MENU

L1L212VDC CMABRI1K1/NCK1/COMK1/NOSAFE

HAZARD

RI2

LIMGNDTEST1S1Z1/M+1S2Z2/M-K2/COMK2/NCK2/NO

GND2

F1, F2

To Load Center

Connector plateCP-LIM2010

CT

RS-4

85B A

Wiring Diagram: Using MK2430

LIM2010

SAFE

HAZARD

MUTEESC

TEST

RESET

MENU

L1L212VDC CMABRI1K1/NCK1/COMK1/NOSAFE

HAZARD

RI2

LIMGNDTEST1S1Z1/M+1S2Z2/M-K2/COMK2/NCK2/NO

GND2

F1, F2

To Load Center

Connector plateCP-LIM2010

CT

RS-4

85B A

U2U2V2V2

AC/DC 24 V3 VA

Page 17: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

Isolated Power System Equipment 17

Remote Indicator Comparison

Product Type Systems Monitored Mute Test Overload Digital Display Alarm History Refer to

MK2000-G1

One Yes -- -- -- -- Page 4

MK2000P-G1

One Yes Yes -- -- -- Page 4

MK2000C-G1

One Yes -- Yes -- -- Page 4

MK2000CP-G1

One Yes Yes Yes -- -- Page 4

MK2000CBM-G2

One Yes Yes Yes Yes -- Page 4

MK2000-2G2

Two Yes -- -- -- -- Page 4

MK2430

Multiple Yes Yes Yes Yes Yes Page 9

MK800

Multiple Yes Yes Yes Yes Yes Page 13

Page 18: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicator

18 Isolated Power System Equipment

A complete ground fault location system for hospitals

L1

L2

Power SupplyClass 2

Ground Fault Location EvaluatorEDS Series

MK2000 Series

>˚F

Line Isolation MonitorLIM2010

Complete system including LIM, EDS ground fault location, and remote indication

Advantages:• Groundfaultlocationwhilethesystemremainsonline

• Fastlocationoffaults

• Reducedmaintenancecosts

• IndicationoffaultycircuitshownonLCDdisplaysatboththe locationdeviceandremoteindicators

System functions:• Indicationoffaultybranchcircuits

• Modulardesignallowsforsimpleretrofitting/upgrading

• Currenttransformersforfaultdetectionavailableinmany

differentshapesandsizes

• Upto708subcircuitscanbemonitored

• Communicationviatwo-wireconnection

• Universallyapplicableformosttypesofungroundedsystems

FunctionTheEDSseriesworksinconjunctionwiththeLIM2010tocreateacompletegroundfaultlocationsystem.Afteranalarmisgen-eratedbytheLIM2010,theEDSseriessystemactivates(thiscanhappenautomaticallyorbemanuallycontrolled).Atestdevicegeneratesatestsignalforasetperiodoftime.Itsamplitudeanddurationarelimited.Thesignalflowsthroughthelocationofthegroundfault.Currenttransformersplacedaroundeachsubfeed-erorloadwillpickuponthistestsignal.TheEDSseriesdevicewillthenevaluatetheresults.Thelocationofthefaultisdis-playedontheEDSseriesviaeitheradigitaldisplayoranLEDbargraph.Specialremoteindicatorsconnectedtothesystemmayalsodisplaythelocationofthefault.

Ground fault location in isolated power systems with EDS series devicesBENDER‘scompletegroundfaultlocationsystemforhospitalshelpsincreasethere-liabilityofyoursystem,reducecosts,andcreatepredictivemaintanencebylocatinggroundfaultsquicklyandeasily.TheEDSseriesextendsthecapabilitiesoftheLIM2010 Line Isolation Monitor to not only knowthatthereisaproblem,buttofinditaswell.TheEDSseriesassistsinautomat-ingtheprocessoffindingfaultsbycon-nectingtosubfeedersorloadsandprodiv-ingnotificationwhenafaulthasbeenlo-cated.Remoteindicatorsalsoworkinconjunctionwiththissystemtonotifynurseandtechnicalstationsquicklywhenaproblemhasoccured.

Page 19: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Remote Indicators

Isolated Power System Equipment 19

Remote indication and communication solutions

Device communication

BENDER‘slineofcommunicationproductsallowforfastnotifica-tionofpersonnelwhenaproblemhasoccured.CriticalsystemsmonitoredbyBENDERequipmentmaybeconnectedtoavarietyofremoteindicatorstonotifypersonnelofthecurrentstatusofthesystem.Communicationgatewaysbringyourelectricalsafetynetworkintothe21stcenturybydisplayingsysteminformationviaseveralstandardprotocols,suchasEthernet,MODBUS,and

PROFIBUS.TheEthernetgatewaydeviceadditionallyfeaturesaneasy-to-usestatuspage,accessiblethroughawebbrowser.E-mailandSMSmessagingwhenanalarmhasoccuredisalsoavailable.Utilizingthiscommunicationsystemallowsfortimelyandcost-ef-fectivedeploymentofservicepersonnelandcanhelpavoidequipmentdamageorfailure.

Communication possibilities with BENDER systems and devices

1 - LIM2010 Line Isolation Monitor

2 - MK2430RemoteIndicatingStation

3 - BENDERcommunicationbus

4 - COM460IPEthernet/Modbus/TCPcommunicationgateway

5 - FTC470XMBModbus/RTUcommunicationgateway

6 - FTC470XDPProfibus/DPcommunicationgateway

7 - EthernetnetworkorModbus/TCPnetwork

8 - ConnectedPCwithwebbrowserorvisualizationsoftware

9 - OPCserverconnectivitycapabilities

10 -SCADA/BMSconnectivitycapabilities

11 -COM460IPcapability:E-mailnotification

12 -COM460IPcapability: WebbrowserbasednavigationviatheInternet

13 -COM460IPcapability: SMSnotification

COM460IP

XMBFTC470BENDER RS-485 Bus

EthernetModbus/TCP

OPC Modbus/TCP SCADA / BMS

TCP/IP/Ethernet

Modbus/TCP

TCP/IPModbus/TCP

Modbus RTU

Profibus DP

Modbus/TCP

WiFiRouter

OPC Server

XDP

1

3

2

4

5 6

8

7

9 10

11 12 13

Page 20: MK Series - benderinc.com · • Options include test button, overload alarm LED, and “SAFE”digital display showing real-time THC readings Product Description MK series remote

Canada • Brampton, ONToll-Free: 800-243-2438 • Fax: 905-799-3051

North American Headquarters • Coatesville, PAToll-Free: 800.833.6834 • Fax: 610.383.7100

www.bender.org • E-mail: [email protected]

Docum

entN

AE2

0220

20/10

.201

1/©

Ben

derInc

.