  • 7/28/2019 Mitsubishi A500 Series VFD Brochure

    1/816

    A500 SeriesThe A500 Series delivers outstanding performance for a wide range of applications,

    including machinery that requires high motor torque production without encoder feedback,

    even at low RPM. A broad selection of standard settings, plus 3 plug-in option ports,

    enable the user to tailor the product to suit application requirements.

    Control Panel standard. Stores settings in non-volatile memoryfor copying to other drives.

    Low cost optional upgrade Parameter Unit, with 8 languages,back-light, 24 keys for direct numeric entry, non-volatilememory of all settings.

    RS-485 Multi-drop serial communication standard.

    Communications options:

    DeviceNet, Profibus DP, CC-Link, Modbus Plus

    Ease of maintenance:

    Removable control circuit terminal block

    Quick fan change-out

    Open loop magnetic flux vector control.

    Closed loop fluxvector speed control,including 0 RPM holding torque, withencoder feedback option.

    Sink / Source selectable control logic.POWER

    ALARM

    CONTROL PANEL

    HZ

    AV

    M O N E X T P U

    REV FWD

    POWER

    ALARM

    CONTROL PANEL

    HZAV

    M O N E X T P U

    REV FWD

    POWER

    ALARM

    CONTROLPANEL

    HZ

    A

    V

    M O N E X T P U

    REV FWD

    POWER

    ALARM

    CONTROLPANEL

    HZ

    A

    V

    M O N E X T P U

    REV FWD

    * CE mark is available on

    240V and 480V models only

    Constant Torque Variable TorqueModel Number

    hp Output Amps hp Output Amps

    3-Phase 240 VAC Input / Output

    0.5 3 1 3.6 FR-A520-0.4K-NA

    1 5 1.5 5 FR-A520-0.75K-NA

    2 8 3 9.6 FR-A520-1.5K-NA

    3 11 3 12 FR-A520-2.2K-NA

    5 17 5 18 FR-A520-3.7K-NA

    7.5 24 10 28 FR-A520-5.5K-NA

    10 33 10 37 FR-A520-7.5K-NA

    15 46 20 54 FR-A520-11K-NA20 61 25 68 FR-A520-15K-NA

    25 76 30 80 FR-A520-18.5K-NA

    30 90 40 104 FR-A520-22K-NA

    40 115 50 130 FR-A520-30K-NA

    50 145 60 154 FR-A520-37K-NA

    60 175 75 185 FR-A520-45K-NA

    75 215 100 248 FR-A520-55K-NA

    3-Phase 480 VAC Input / Output

    0.5 1.5 1 1.8 FR-A540-0.4K-NA

    1 2.5 1.5 3 FR-A540-0.75K-NA

    2 4 3 4.8 FR-A540-1.5K-NA

    3 6 3 6.7 FR-A540-2.2K-NA

    5 9 5 9 FR-A540-3.7K-NA

    7.5 12 10 14 FR-A540-5.5K-NA

    10 17 15 21 FR-A540-7.5K-NA

    15 23 20 27 FR-A540-11K-NA

    20 31 25 34 FR-A540-15K-NA

    25 38 30 40 FR-A540-18.5K-NA

    30 43 40 52 FR-A540-22K-NA

    40 57 50 65 FR-A540-30K-NA

    50 71 60 77 FR-A540-37K-NA

    60 86 75 96 FR-A540-45K-NA

    75 110 100 124 FR-A540-55K-NA

  • 7/28/2019 Mitsubishi A500 Series VFD Brochure

    2/8Mitsubishi Electric Automation | Variable Frequency Drives

    Constant Torque Variable Torque Light Variable TorqueModel Number

    hp Output Amps hp Output Amps hp Output Amps

    3-Phase 480 VAC Input / Output

    100 144 150 180 150 180 FR-A540L-G75K-NA

    150 180 150 216 200 260 FR-A540L-G90K-NA

    150 216 200 260 250 302 FR-A540L-G110K-NA

    200 260 300 361 350 432 FR-A540L-G132K-NA

    250 325 350 432 400 477 FR-A540L-G160K-NA

    350 432 450 547 500 610 FR-A540L-G220K-NA

    450 547 600 722 600 750 FR-A540L-G280K-NA

    600 722 700 866 FR-A540L-375K-NA

    700 866 800 1010 FR-A540L-450K-NA

    800 1010 900 1152 FR-A540L-530K-NA

    900 1152 1000 1296 FR-A540L-600K-NA

    1000 1296 1150 1440 FR-A540L-670K-NA

    1150 1440 1250 1534 FR-A540L-750K-NA

    1250 1584 1400 1728 FR-A540L-800K-NA

    3-Phase 600 VAC Input / Output

    1 1.7 1 1.8 FR-A560-0.75K-NA

    3 4 3 4.7 FR-A560-2.2K-NA

    5 6.1 5 7.3 FR-A560-3.7K-NA

    10 12 10 14.8 FR-A560-7.5K-NA

    20 22 25 27 FR-A560-15K-NA

    30 33 40 41 FR-A560-22K-NA

    50 55 60 62 FR-A560-37K-NA

    75 84 100 99 FR-A560-55K-NA

    100 104 100 104 FR-A560L-75K-NA

    125 131 150 152 FR-A560L-90K-NA

    150 152 215 221 FR-A560L-110K-NA

    200 202 250 255 FR-A560L-132K-NA

    250 255 300 304 FR-A560L-185K-NA

    300 304 400 402 FR-A560L-220K-NA

    400 402 500 496 FR-A560L-280K-NA

    550 552 650 663 FR-A560L-375K-NA

    650 663 750 773 FR-A560L-450K-NA

    750 773 800 800 FR-A560L-530K-NA

    800 800 900 900 FR-A560L-600K-NA

    900 880 1000 990 FR-A560L-670K-NA

    1000 990 1100 1100 FR-A560L-750K-NA

    1100 1100 1200 1210 FR-A560L-800K-NA

    1200 1210 1300 1320 FR-A560L-900K-NA

    Instruction Manuals

    Model Number Part Number

    A500 IB(NA)66790

    FR-A560 IB-0600012FR-A540L / A560L IB-T7273

    FR-A500 / E500Tech. Manual

    SH(NA)3193

  • 7/28/2019 Mitsubishi A500 Series VFD Brochure

    3/818

    Ratings 240V Class 0.4K 55KModel FR-A520-K-NA 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55

    Hp Rating *1Constant Torque 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75

    Variable Torque 1 1.5 3 3 5 10 10 20 25 30 40 50 60 75 100

    Rated Capacity Constant Torque 1.1 1.9 3.1 4.2 6.7 9.2 12.6 17.6 23.3 29 34 44 55 67 82

    (kVA) *2 Variable Torque 1.3 1.9 3.7 4.6 7.1 10.7 14.1 20.7 25.9 30.5 39.2 49.7 58.4 70.8 94.6

    Continuous Constant Torque 3 5 8 11 17 24 33 46 61 76 90 115 145 175 215

    Rating (A) Variable Torque 3.6 5 9.6 12 18 28 37 54 68 80 104 130 154 185 248

    Overload *3 Constant Torque 150% for 60 sec., 200% for 0.5 sec. (Inverse time characteristics)

    Current Rating Variable Torque 120% for 60 sec., 150% for 0.5 sec. (Inverse time characteristics)

    Voltage *4 3-Phase 200 - 220V 50Hz, 200 - 240V 60Hz 3-Phase 200 - 220V 50Hz, 200 - 230V 60Hz

    Regenerative Max. Value / Time 150% for 5 sec. 100% for 5 sec. 20% *5

    Braking Torque Tolerable Work. Rate 3%ED 2%ED Continuous *5

    Rated Input, AC Volt., Frequency 3-Phase 200 - 220V 50Hz, 200 - 240V 60Hz 3-Phase 200 - 220V 50Hz, 200 - 230V 60Hz

    Tolerable AC Voltage Fluctuation 170 - 242V 50Hz, 170 - 264V 60Hz 170 - 242V 50Hz, 170 - 253V 60Hz

    Tolerable Frequency Fluctuation 5%

    Supply (kVA) *7 1.5 2.5 4.5 5.5 9 12 17 20 28 34 41 52 66 80 100

    Protective Structure (JEM1030) Enclosed type (IP20) Open type (IP00)

    Cooling Method Self cooling Forced air cooling

    Approx.Weightkg 2.0 2.5 3.5 3.5 3.5 6.0 6.0 8.0 13.0 13.0 13.0 30.0 40.0 40.0 50.0

    lbs 4.4 5.5 7.7 7.7 7.7 13.2 13.2 17.6 28.7 28.7 28.7 66.1 88.2 88.2 110.2

    Height

    mm 260 260 260 260 260 260 260 300 400 400 400 550 550 550 700

    inches 10.2 10.2 10.2 10.2 10.2 10.2 10.2 11.8 15.8 15.8 15.8 21.6 21.6 21.6 27.6

    Widthmm 110 110 150 150 150 220 220 220 250 250 250 340 450 450 480

    inches 4.3 4.3 5.9 5.9 5.9 8.7 8.7 8.7 9.8 9.8 9.8 13.4 17.7 17.7 18.9

    Depthmm 110 125 140 140 140 170 170 190 190 190 190 195 250 250 250

    inches 4.3 4.9 5.5 5.5 5.5 6.7 6.7 7.5 7.5 7.5 7.5 7.7 9.8 9.8 9.8

    Output

    PowerSupply

    Ratings 480V Class 0.4K 55KModel FR-A540-K-NA 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 1 5 18.5 22 30 3 7 45 5 5

    Hp Rating *1Constant Torque 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75

    Variable Torque 1 1.5 3 3 5 10 15 20 25 30 40 50 60 75 100

    Rated Capacity Constant Torque 1.1 1.9 3.1 4.2 6.9 9.1 13 17.5 23.6 29 32.8 43.4 54 65 84

    (kVA) *2 Variable Torque 1.3 2.3 3.6 5.1 6.9 10.6 16.0 20.5 25.9 30.5 39.7 49.5 58.6 72.6 94.7

    Continuous Constant Torque 1.5 2.5 4 6 9 12 17 23 31 38 43 57 71 86 110

    Rating (A) Variable Torque 1.8 3 4.8 6.7 9 14 21 27 34 40 52 65 77 96 124

    Overload *3 Constant Torque 150% for 60 sec., 200% for 0.5 sec. (Inverse time characteristics)

    Current Rating Variable Torque 120% for 60 sec., 150% for 0.5 sec. (Inverse time characteristics)

    Voltage *4 3-Phase 380 - 480V 50Hz / 60Hz

    Regenerative Max. Value / Time 100% for 5 sec. 20% *5

    Braking Torque Tolerable Work. Rate 2% ED Continuous *5

    Rated Input, AC Volt., Frequency 3-Phase 380 - 480V 50Hz / 60Hz

    Tolerable AC Voltage Fluctuation 323 - 528V 50Hz, / 60Hz

    Tolerable Frequency Fluctuation 5%

    Supply (kVA) *7 1.5 2.5 4.5 5.5 9 12 17 20 28 34 41 52 66 80 100

    Protective Structure (JEM1030) Enclosed type (IP20) Open type (IP00)

    Cooling Method Self cooling Forced air cooling

    Approx.Weightkg 3.5 3.5 3.5 3.5 3.5 6.0 6.0 13.0 13.0 13.0 13.0 24.0 35.0 35.0 36.0

    lbs 7.7 7.7 7.7 7.7 7.7 13.2 13.2 28.7 28.7 28.7 28.7 53.0 77.3 77.3 79.5

    Heightmm 260 260 260 260 260 260 260 400 400 400 400 550 550 550 550

    inches 10.2 10.2 10.2 10.2 10.2 10.2 10.2 15.8 15.8 15.8 15.8 21.6 21.6 21.6 21.6

    Widthmm 150 150 150 150 150 220 220 250 250 250 250 340 450 450 450

    inches 5.9 5.9 5.9 5.9 5.9 8.7 8.7 9.8 9.8 9.8 9.8 13.9 17.7 17.7 17.7

    Depthmm 140 140 140 140 140 170 170 190 190 190 190 195 250 250 250

    inches 5.5 5.5 5.5 5.5 5.5 6.7 6.7 7.5 7.5 7.5 7.5 7.7 9.8 9.8 9.8

    Output

    Power

    Supply

    Notes: See page 21.

    Notes: See page 21.

  • 7/28/2019 Mitsubishi A500 Series VFD Brochure

    4/8Mitsubishi Electric Automation | Variable Frequency Drives

    Ratings 480V Class 75K 280KModel FR-A540L-GK-NA 75 90 110 132 160 220 280

    Constant Torque 100 150 150 200 250 350 450

    Horsepower Rating *1 Variable Torque *6 150 150 200 300 350 450 600

    Light Variable Torque 150 200 250 350 400 500 600

    Rated Current (A)

    Constant Torque 144 180 216 260 325 432 547

    Variable Torque *6 180 216 260 361 432 547 722

    Light Variable Torque 180 260 302 432 477 610 750

    Overload Current Rating *3Constant Torque 150% 60 sec., 200% 0.5 sec @50C.(Inverse time characteristics)Variable Torque *6 120% 60 sec., 150% 0.5 sec. @50C. (Inverse time characteristics)

    Light Variable Torque 110% 60 sec., 150% 0.5 sec. @40C. (Inverse time characteristics)

    Voltage *4 3-Phase 380 - 480V 50Hz/ 60Hz

    Rated Input,AC Voltage, Frequency 3-Phase 380 - 480V 50Hz/ 60Hz

    Tolerable AC Voltage Fluctuation 323 - 528V 50Hz/ 60Hz

    Tolerable Frequency Fluctuation 5%

    Supply (kVA) *7Constant Torque 110 137 165 198 248 329 417

    Variable Torque *6 137 165 198 275 329 417 550

    Protective Structure (JEM1030) Open type (IP00)

    Cooling Method Forced air cooling

    Approximate Weight (kg (lbs)) 76 (167) 86 (189) 88 (194) 149 (328) 156 (343) 268 (590) 292 (642)

    Drive Height mm (in) 740 (29.1) 740 (29.1) 740 (29.1) 1010 (39.8) 1010 (39.8) 1010 (39.8) 1330 (52.4)

    Drive Width mm (in) 480 (18.9) 480 (18.9) 480 (18.9) 498 (19.6) 498 (19.6) 680 (26.8) 790 (31.1)

    Drive Depth mm (in) 360 (14.2) 360 (14.2) 360 (14.2) 380 (15.0) 380 (15.0) 380 (15.0) 440 (17.3)

    DC Reactor Height mm (in) 342 (13.5) 405 (15.9) 405 (15.9) 408 (16.1) 443 (17.4) 500 (19.7) 500 (19.7)DC Reactor Width mm (in) 150 (5.9) 175 (6.9) 175 (6.9) 175 (6.9) 190 (7.5) 210 (8.3) 220 (8.7)

    DC Reactor Depth mm (in) 185 (7.3) 190 (7.5) 195 (7.7) 230 (9.1) 230 (9.1) 260 (10.2) 255 (10.0)

    Output

    PowerSupply

    Notes: See page 21.

    Ratings 480V Class 375K 800KModel FR-A540L-K-NA 375 450 530 600 670 750 800

    Horsepower Rating *1Constant Torque 600 700 800 900 1000 1150 1250

    Variable Torque *6 700 800 900 1000 1150 1250 1400

    Rated Capacity (kVA) *2Constant Torque 550 660 770 878 988 1097 1169

    Variable Torque *6 660 770 878 988 1097 1169 1317

    Rated Current (A)Constant Torque 722 866 1010 1152 1296 1440 1584

    Variable Torque *6 866 1010 1152 1296 1440 1534 1728

    Constant Torque 150% 60 sec., 200% 0.5 secOverload Capacity *3

    (Inverse time characteristics) 150% 60 sec. (Inverse time characteristics)

    Variable Torque *6120% 60 sec., 150% 0.5 sec.(Inverse time characteristics)

    120% 60 sec. (Inverse time characteristics)

    Voltage *4 3-Phase 380 - 480V 50Hz/ 60Hz

    Rated Input,AC Voltage, Frequency 3-Phase 380 - 480V 50Hz/ 60Hz

    Tolerable AC Voltage Fluctuation 323 - 528V 50Hz/ 60Hz

    Tolerable Frequency Fluctuation 5%

    Supply (kVA) *7Constant Torque 550 660 770 878 988 1097 1210

    Variable Torque *6 660 770 878 988 1097 1210 1320

    Protective Structure (JEM1030) Open type (IP00) Enclosed type (IP20)

    Cooling Method Forced air cooling

    Approximate Weightkg 490 500 1060 1060 1100 1100 1200

    lbs 1078 1100 2332 2332 2420 2420 2640

    Drive Height mm (in) 1900 (74.8) 2900 (114.2)

    Drive Width mm (in) 1100 (43.3) 2300 (90.6)

    Drive Depth mm (in) 500 (19.7) 800 (31.5)

    Reactor Height mm (in) 330 (1 3.0)Internally mounted

    Reactor Width mm (in) 240 (9.5)

    Reactor Depth mm (in) 460 (1 8.4)and wired in cabinet

    Output

    PowerSupply

    Notes: See page 21.

  • 7/28/2019 Mitsubishi A500 Series VFD Brochure

    5/820

    Ratings 600V Class 75K 280K

    Model FR-A560L-K-NA 75 90 110 132 185 220 280

    Horsepower Rating *1Constant Torque 100 125 150 200 250 300 400

    Variable Torque *6 100 150 215 250 300 400 500

    Rated Capacity (kVA) *2Constant Torque 75 90 110 132 185 220 280

    Variable Torque *6 75 110 160 185 220 280 375

    Rated Current (A)

    Constant Torque 104 131 152 202 255 304 402

    Variable Torque *6 104 152 202 255 304 402 496

    Overload Current Rating *3Constant Torque 150% 60 sec., 200% 0.5 sec. (Inverse time characteristics)

    Variable Torque *6 120% 60 sec., 150% 0.5 sec. (Inverse time characteristics)

    Voltage *4 3-Phase 600V 60Hz

    Rated Input, AC Voltage, Frequency 3-Phase 600V 50Hz/ 60Hz

    Tolerable AC Voltage Fluctuation 488 - 632V 50Hz/ 60Hz

    Tolerable Frequency Fluctuation 5%

    Supply (kVA) *7Constant Torque 104 130 151 201 254 303 400

    Variable Torque *6 104 151 220 254 303 400 494

    Protective Structure (JEM1030) Open type (IP00)

    Cooling Method Forced air cooling

    Approx.Weight (kg (lbs)) 61 (135) 93 (205) 94 (207) 149 (328) 155 (341) 266 (586) 290 (638)

    Drive Heightmm 740 740 740 1010 1010 1010 1330

    inches 29.2 29.2 29.2 39.8 39.8 39.8 52.4

    Drive Widthmm 480 480 480 498 498 680 790

    inches 18.9 18.9 18.9 19.6 19.6 26.8 31.1

    Drive Depthmm 360 360 360 380 380 380 440

    inches 14.2 14.2 14.2 15.0 15.0 15.0 17.3

    DC Reactor Heightmm 320 337 400 400 438 495 495

    inches 12.6 13.3 15.8 15.8 17.3 19.5 19.5

    DC Reactor Widthmm 140 150 175 175 190 210 220

    inches 5.5 5.9 6.9 6.9 7.5 8.3 8.7

    DC Reactor Depthmm 170 180 200 215 220 235 265

    inches 6.7 7.1 7.8 8.5 8.7 9.3 10.4

    Output

    Power

    Supply

    Notes: See page 21.

    Ratings 600V Class 0.75K 55KModel FR-A560-K-NA 0.75 2.2 3.7 7.5 15 22 37 55

    Horsepower Rating *1Constant Torque 1 3 5 10 20 30 50 75

    Variable Torque *6 1 3 5 10 25 40 60 100

    Rated Capacity (kVA) *2Constant Torque 1.7 4 6.1 12 22 33 55 84

    Variable Torque 1.8 4.7 7.3 14.8 27 41 62 99

    Continuous Rating (A)Constant Torque 1.7 4 6.1 12 22 33 55 84

    Variable Torque *6 1.8 4.7 7.3 14.8 27 41 62 99

    Overload Current Rating *3Constant Torque 150% 60 sec., 200% 0.5 sec. (Inverse time characteristics)

    Variable Torque *6 120% 60 sec., 150% 0.5 sec. (Inverse time characteristics)

    Voltage *4 3-Phase 600V 60Hz

    Regenerative Braking TorqueMax. Value / Time 100% 5 sec 20% *5

    Tolerable Work.Rate 2% ED Continuous *5

    Rated Input, AC Voltage, Frequency 3-Phase 575V 60Hz

    Tolerable AC Voltage Fluctuation 490 - 632V 60Hz

    Tolerable Frequency Fluctuation 5%

    Supply (kVA) *7 2.5 5.5 9 17 28 41 66 100

    Protective Structure (JEM1030) Enclosed type (IP20)

    Cooling Method Forced air cooling

    Approximate Weight (kg (lbs)) 7 (15) 7 (15) 7 (15) 7 (15) 15 (32) 15 (32) 55 (120) 55 (120)

    Heightmm 260 260 260 260 400 400 807.5 807.5

    inches 10.2 10.2 10.2 10.2 15.7 15.7 31.8 31.8

    Widthmm 220 220 220 220 250 250 450 450

    inches 8.7 8.7 8.7 8.7 9.8 9.8 17.7 17.7

    Depthmm 170 170 170 170 190 190 250 250

    inches 6.7 6.7 6.7 6.7 7.5 7.5 9.8 9.8

    Output

    Power

    Supply

    Notes: See page 21.

  • 7/28/2019 Mitsubishi A500 Series VFD Brochure

    6/8Mitsubishi Electric Automation | Variable Frequency Drives

    Ratings 600V Class 375K 900KModel FR-A560L-K-NA 375 450 530 600 670 750 800 900

    Horsepower Rating *1Constant Torque 550 650 750 800 900 1000 1100 1200

    Variable Torque *6 650 750 800 900 1000 1100 1200 1300

    Rated Capacity (kVA) *2Constant Torque 375 450 530 600 670 750 800 900

    Variable Torque *6 450 530 600 670 750 800 900 950

    Rated Current (A)Constant Torque 552 663 773 800 880 990 1100 1210

    Variable Torque *6 663 773 800 900 990 1100 1210 1320

    Constant Torque150% 60 sec., 200% 0.5 sec.

    Overload Capacity *3(Inverse time characteristics)

    150% 60 sec. (Inverse time characteristics)

    Variable Torque *6120% 60 sec. , 150% 0.5 sec.(Inverse time characteristics)

    120% 60 sec. (Inverse time characteristics)

    Voltage *4 3-Phase 600V 60H

    Rated Input, AC Voltage, Frequency 3-Phase 600V 50Hz/ 60Hz

    Tolerable AC Voltage Fluctuation 488 - 632V 50Hz/ 60Hz

    Tolerable Frequency Fluctuation 5%

    Supply (kVA) *7Constant Torque 550 660 770 797 896 986 1095 1205

    Variable Torque *6 660 770 797 896 986 1095 1205 1315

    Protective Structure (JEM1030) Open type (IP00) Enclosed type (IP20)

    Cooling Method Forced air cooling

    Approximate Drive Weight (kg (lbs)) 490 500 1060 1060 1100 1100 1200 1200(1078) (1100) (2332) (2332) (2420) (2420) (2640) (2640)

    Drive Height mm (inches) 1900 (74.8) 2900 (114.2)

    Drive Width mm (inches) 1100 (43.3) 2300 (90.6)

    Drive Depth mm (inches) 500 (19.7) 800 (31.5)

    Reactor Height mm (inches) 330 (13.0)

    Reactor Width mm (inches) 240 (9.5)Internally mounted

    Reactor Depth mm (inches) 460 (18.4)and wired in cabinet

    Output

    Power

    Supply

    Notes:

    1. The applicable motor capacity indicated is the maximum capacity applicable when Mitsubishi 4-pole standard motor is used.

    2. The rated output capacity indicated is based on the National Electric Code, 220V for 200V class, 440V for 400V class, 575V for 600V class.

    3. The overload capacity indicated in % i s the ratio of the overload current to the inverters rated current. For repeated duty, allow time for the inverter and motor to return to or

    below the temperatures under 100% load.

    4. The maximum output voltage cannot exceed the power supply voltage.The maximum output voltage may be set as desired below the power supply voltage.

    5. The torque indicated is the average value for deceleration from 60Hz to a stop and varies with motor loss.

    6. For use in Variable torque mode, refer to Pr.570.

    7. The power supply capacity changes with the values of the power supply side inverter impedance (including those of the i nput reactor and cables).

  • 7/28/2019 Mitsubishi A500 Series VFD Brochure

    7/822

    Control Method Soft-PWM control, high-carrier frequency PWM control (V/F control, advanced flux vector control selection)

    Carrier0.4K~55K, 230 & 480V 700Hz to 14.5K Hz. Maximum 5KHz for Soft PWM.

    Frequency0.75~55K, 600V 700Hz to 14.5K Hz. Maximum 8KHz for variable torque rating. Maximum 5Hz for Soft PWM.

    75K~280K, 480 & 600V 700Hz, 1K Hz, 2.5K Hz. Maximum 1KHz for Soft PWM. 2.5KHz setting permissible only with optional sine wave filter.

    Output Frequency Range 0.2 to 400 Hz

    Frequency Analog Input 0.015 Hz (Terminal No. 2 input: 12 bit/0 to 10V, 11 bit/0 to 5V;Terminal No.1 input: 12 bit/-10 to +10V, 11 bit/-5 to +5V)

    Control Resolution Digital Input 0.01 Hz

    Frequency Precision Within 0.2% of max.output frequency 25C 10C / (59F to 95F) during analog input:within 0.01% of set output frequency during digital input

    Voltage / Frequency Characteristics Any base frequency setting possible between 0 and 400 Hz; constant torque or variable torque pattern selection possible.Starting Torque 150% at 0.5 Hz (advanced flux vector control)

    Torque Boost Manual torque boost

    Acceleration / Deceleration Time Setting 0 to 3600 sec. (individual setting for acceleration/deceleration possible), linear or S-curve mode

    DC Braking Operation frequency (0 to 120 Hz), operation time (0 to 10 sec.), operation voltage (0 to 30%) variable

    Stall Prevention Operation Level Operation current level setting possible (0 to 200% variable), enable/disable selection

    Frequency Analog Input DC 0 to 5V, 0 to 10V, 4 to 20mA

    Setting Signal Digital Input Input from control panel, parameter unit; BCD 3-digit or 12-digit binary (using option FR-A5AX)

    Starting Signal Individual selection of forward run, reverse run; starting signal self-hold input (3-wire input) selective

    Multi-Speed Selection Up to 15 set speeds (each speed can be set between 0 and 4 00 Hz; speed can be changed via control panel or pa rameter unit during operation)

    2nd, 3rd Accel. / Decel.Time 0 to 3600 sec.(max. of three individual accelerations/decelerations can be set)

    JOG Operation Selection JOG operation mode selection terminal provided (*1)

    Current Input Selection Select input of frequency setting signal 4 to 20 mA DC (terminal No. 4)

    Output Stop Instant cutoff of inverter output (frequency, voltage)

    Error Reset Reset of protection operation hold state

    Upper/lower limit frequency setting, frequency jump operation, external thermal input selection, reverse polarity operation, instantaneous

    Operation Functions power failure restart operation, commercial power supply inverter switch-over function, forward run/reverse run prevention, slip compensation,

    operation mode selection, off-line auto tuning function, online auto tuning function, PID control, programmed operation, computer link operation (RS-485)

    Five types can be selected from:inver ter running, frequency reached, instantaneous power failure (undervoltage), frequency detection, 2nd

    frequency detection, 3rd frequency detection, in program mode operation, in PU operation, overload warning, regenerative brake pre-alarm,

    Operation Status electronic thermal relay pre-alarm, zero current detection, output current detection, PID lower limit, PID upper limit, PID forward run, PID

    reverse run, commercial power supply-inverter switchover MC 1, 2, 3, operation ready, brake release request, fan trouble, and fin overheat pre-alarm.

    Open collector output.

    Error (Inverter Trip) Relay output - contact rated (230 VAC, 0.3A / 30 VDC, 0.3A); open collector - alarm code (4-bit) output

    One type can be selected from: output frequency, motor current (constant or peak value), output voltage, frequency setting value, operation

    For Meter speed, motor torque, converter output voltage (constant or peak value), regenerative brake duty (*2), electronic thermal relay load rate,

    input power, output power, load meter and motor excitation current. Pulse train output (1,440 pulse/sec./full scale) or analo g output (0 to 10 VDC).

    Displayed on Select from output frequency, motor current (constant or peak value), output voltage, frequency setting value, operation speed, motor torque,

    FR-DU04 Control Operation Status overload, converter output voltage (constant or peak value), electronic thermal relay load rate, input power, output power, load meter, motor

    Panel or FR-PU04 excitation current, cumulative power ON time, actual operation time, cumulative power, regenerative brake duty and motor load rate.

    Parameter Unit Error Details Details of errors are displayed when the protective function activates. Details of up to eight errors are saved.(Only four errors are displayed on the control panel.)

    Additional Displays Operation Status Input terminal signal status, output terminal signal status, option mounting status, terminal assignment status.

    Only on FR-PU04 Error Deta ils Output voltage, current, frequency and cumulative power ON time before protective function activatesParameter Unit Interactive Operation guide and troubleshooting with help function

    Overcurrent cutoff (during acceleration, deceleration, constant speed), regenerative overvoltage cutoff, undervoltage, instantaneous power failure,

    Protective and Warning Functionsoverload cutoff (electronic thermal relay), brake transistor error (*2), ground fault overcurrent, output short circuit (*4), stall prevention,

    overload warning, brake resistor overheating (*2), fin overheating, fan trouble (*4), option error, parameter error, PU disconnected number of

    retries exceeded, output phase loss, CPU error, 24 VDC power output short circuit, control panel power short circuit, main circuit fault (*5).

    0.4K~55K, -10C (+14F) to +50C (+122F), no frost or condensation. -10C (+14F) to +40C (+104F) when either the variable torque rating or the FR-A5CV dirt protection

    240V & 480V attachment is used. -10C (+14F) to +30C (+86F) when both the variable torque rating and the FR-A5CV are used in combination.Ambient

    Temperature0.75K~55K, 600 V -10C (+14F) to +40C (+104F), no frost or condensation. -10C (+14F) to +30C (+86F) when the the FR-A5CV dirt protection attachment is used.

    75K~280K, 480 & 600V -10C (+14F) to +50C (+122F), no frost or condensation.

    375K~900K, 480 & 600V -10C (+14F) to +40C (+104F), no frost or condensation.

    Ambient Humidity 90% RH or less (no condensation)

    Storage Temperature *3 -20C to 65C / -4 to 149F

    Atmosphere Indoors (no corrosive gases, flammable gases, oil mist or dust)

    Altitude 1000m above sea level.Contact factory for higher altitude deratings.

    Vibration 5.9 m/s2 (0.6G max.) based on JIS C 0911

    Control

    Specifications

    OperationSpecifications

    Display

    Environment

    InputSignal

    OutputSignal

    Notes:1. JOG operation is possible with the control panel and parameter unit.

    2. Not provided for models FR-A520-11K and larger, or models FR-A540-11K and larger, which have no brake circuits.3. Temperatures to which the units can be exposed for a short time, such as during transportation.4. Only on ratings 55K and smaller.5. Only on ratings 75K and larger.

    General Specifications

  • 7/28/2019 Mitsubishi A500 Series VFD Brochure

    8/8Mitsubishi Electric Automation | Variable Frequency Drives

    B

    3 phaseAC powersupply

    NFBMC

    PU connector(RS-485)

    R

    S

    T

    R1

    S1

    PC

    STF

    STR

    STOP

    RH *5

    RM *5

    RL *5

    JOG *5

    RT *5MRS

    RES

    AU *5

    CS *5

    SD contactinput common

    Instantaneous powerfailure restart selection

    Current input selection

    Reset

    Output stop

    Second accel./decel.time selection

    JOG mode

    High speed

    Med. speed

    Low speed

    Multi-speedselection(Max. 15speeds)

    Start self-holdselection

    Reverse run start

    Forward run start

    24 VDC power supply andexternal transistor common *10

    Short bar

    U

    V

    W

    P1

    P

    PX*1

    N

    PR*1

    A

    CC

    RUN

    SU

    IPF

    OL

    FU

    SE

    FM

    SD

    AM

    5

    Grounding *8

    (-) (DC 0-10V)

    (+) (Analog signal output)

    (Moving coil type1mA full scale)

    Display meters(frequency meters, etc.)

    Running

    Frequency reached

    Instantaneous power failure

    Overload

    Frequency detection

    Open collector output common

    Scale calibrationresistor 1/2W *7

    Error output(Relay output)

    R

    Jumper*2

    Jumper*3

    External brake resistor

    DC reactor (Standard forratings 75K and larger.)

    Motor

    IM

    Grounding *8

    R

    Frequencypotentiometer1/2W1K*9

    3

    2

    1

    Common

    Auxiliary input

    Current input

    Frequency setting signal (analog)

    4 (DC4 - 20mA)

    2DC 0 - 5V orDC 0 - 10V

    *6

    5 (Analog common)

    10 (+5V)

    10E (+10V)

    Control input signal (not for voltage input)*10

    Main circuit terminal

    Input terminal for control circuit

    Output terminal for control circuit

    Open CollectorOutput *4 *10

    1DC 0 - 5V orDC 0 - 10V

    Notes:1. Terminals PR, PX, and the internal braking circuit are provided only on models FR-A520 - 0.4K through 7.5K, FR-A540 - 0.4K through 7.5K and FR-A560-0.75K through 7.5K.

    FR-A560-7.5K does not include the resi stor.

    2. Remove this jumper when using the FR-ABR external brake resistor.3. This jumper is provided only on models 55K and below. It must be removed when a DC reactor is installed.4. These output terminals can output error alarm codes, or 26 types of function can be individually assigned with Pr.190 through 195.5. This input terminal can be individually assigned 23 types of function with Pr. 180 through 186.6. The input signal can be changed with Pr. 73.7. Not required when the meter is calibrated with the control panel.8. Always ground the VFD, motor and DC reactor, if used.9. 2W1K is recommended when setting is changed often.10. Connections shown using sink logic; source logic connection is also supported.

    A500 Series Terminal Connection Diagram