Quietside Mini Splits

Technical Information “The 107”

Page 2: Mini Split Samsung

Quietside Mini Splits 107 Advisory note: An understanding of basic refrigeration, electricity and thermal dynamics is needed to fully understand this material If you do not have HVAC/R experience this training information will not be helpful Thank you for your attention. John Miles Denis Dumm Director of Engineering & Technical Support Technical Service N “Stu” Taylor Mike Steinke Technical Manager Technical Service Kevin Park Chris Dolan Technical Liaison Warranty 8750 Pioneer Blvd 6 Pine Hill Drive Santa Fe Springs CA 90670 Carlisle PA 17013 Tel : 1-888-699-6067 x 3 1-866-243-6498 Fax : 562-699-4351 717-243-7917

www.Quietside.comQUI-MS107-001 2

Page 3: Mini Split Samsung

3

Technical 107 Contents Page Number Title

4 Applications – Computer Rooms 5 Applications – Computer Rooms 6 Applications – Commercial Offices 7 Applications – Residential 8 Applications – Sun or 4 Season Rooms 9 Applications – Low Ambient Cooling 10 Low Ambient Wiring QSCE09-12 11 Low Ambient Wiring QSCE18-24 12 Low Ambient Wiring QSHE09-12 13 Low Ambient Wiring QSHE18-24 14 Applications – Heat Pump 15 Applications – Heat Pump 16 Applications – Heat Pump 17 Accessories 18 Accessories 19 Pre Installation Check List 20 Pre Installation Check List 21 Installation Tips 22 Installation Tips 23 Installation Tips 24 Installation Tips 25 Common Technical Questions 26 Unit Fault Codes 27 Unit Fault Codes (cont) 28 Unit Fault Codes (cont) 29 Maintenance 30 Warranty 31 Website, Manual Notes

Page 4: Mini Split Samsung

4

Applications Computer or Data Server Rooms Mini-splits are designed to primarily keep people comfortable. That means the typical range of temperatures for the zone is 70-72 DegF. Mini Splits were not specifically designed for cooling server rooms or other data rooms however due to their size and ease of installation this is a very common application, and also the #1 Technical Service issue. But FOLLOWING these guidelines can make for a reliable, profitable installation in this application Sizing Sizing of the Mini Split to the room is EXTREMELY IMPORTANT. Quietside recommends a 12,000 Btu/h capacity per 200 to 250 Sq Ft of room size. Do not exceed this sizing guideline.

Installing large capacity systems in small rooms will lead to short cycling of the compressor as the supply airflow from the unit to “bounces back” into the return air stream of the unit If using the larger capacity units, Supply air is discharged at a velocity of approximately 6ft per second. With a small room, where the opposite wall to the unit is less than 10ft away the supply air only circulates for approximately 4 seconds before returning to the unit. The room temperature sensor is located on the surface of the cooling coil, if the supply air quickly “bounces back” into the unit, it will satisfy the sensor and the compressor will be cycled off. All Quietside mini splits feature continuous fan operation, maintaining circulation in the room rapidly picking up the warmer return air from the room, causing the return air sensor to quickly sense a rise in temperature and call for compressor operation. This leads to short cycling of the unit, poor temperature control and a greatly reduced unit life span. Due to this scenario we recommend that you Do not install any capacity Quietside Mini Split in rooms of less than 100 Sq Ft in size

Page 5: Mini Split Samsung

5

Cont Unit Location Ensure that no obstacles to the air flow from the Indoor unit are within 10 feet of the unit, be especially aware that Computer server units create an airflow baffle and can have the same effect on airflow to and from the unit as a small room size. In Computer room application the Quietside Mini Split units must be installed a MINIMUM of 6ft from the floor so that the airflow from the unit is unimpeded. Sensible Heat and Humidity Quietside units are designed to provide an approximate SHR of 0.66. Be aware that low humidity conditions will further reduce unit performance, requiring either additional higher fan speeds to be programmed into the unit, or introduction of some latent load into the room, e.g. Use of a humidifier. Compressor Run Times To ensure compressor longevity it is paramount that the compressor run time be longer than 5 minutes at all times throughout the year. This will allow oil return to the compressor, and will ensure that the max number of starts per hour is not exceeded. If the compressor runtime is less than 5 minutes, especially at design ambient temperature it is very likely that the unit is oversized. Ambient The other major issue with Computer or Data rooms is that they are designed to operate 365 days 24/7. This means that the Outdoor unit will be exposed to temperatures below the minimum design ambient of 65 DegF Therefore for cooling below 65 DegF, Quietside insists on the following items to be installed on the system. 1. ICM 326H Fan Speed controller. 2. Crankcase Heater on ALL units If winter temperatures fall below 32 DegF a Wind Baffle on the Coil Inlet and the Exhaust of the condenser fan is required. This will isolate the unit from any wind that could cause the unit to over condense, slugging liquid refrigerant back to the Compressor, which can damage the valve plate, wash oil from the bearing services and eventually cause the Compressor to fail. A Wind Baffle will provide cooling operation down to an Ambient of 0 DegF Wind Baffles are field fabricated, drawings are available on request from Quietside

Page 6: Mini Split Samsung

6

Applications Commercial, Offices, Shops, Churches etc Sizing Again Sizing and Location of the Mini Split to the room is EXTREMELY IMPORTANT. Quietside recommends a 12,000 Btu/h capacity for each 350 to 450 Sq Ft of the Room Do not exceed this sizing guideline for the same reason as the computer room application information Again DO NOT install Quietside Mini Splits in rooms of less than 100 Sq Ft Ambient Check as to the lowest ambient temperature that will be required for cooling, the minimum design temperature for the Outdoor unit is 65 DegF, if cooling is required below that, down to 32 DegF, Quietside insists on an ICM 326H Fan Speed controller being installed on the Outdoor unit. On ALL units, a Crankcase Heater should also be installed. For cooling down to 0 DegF, the use of Wind Baffles is required, per the computer room application information. Filters Quietside Mini Splits, because of the constant operation of the fan require much more frequent filter cleanings or replacements than the standard “ducted US style” units which are generally used for commercial buildings. Quietside recommends that the filters are cleaned every 4 weeks of operation, more frequently in areas subject to dirtier conditions e.g. Warehouse offices etc Condensers located inside the Building Especially with Warehouse or additional office space the condensers can be installed inside the building, this provides two specific issues to address

1. Lower ambient, these units are rated at 95 DegF ambient, if the ambient in the building does not rise above 80 DegF, we can downsize the unit as it will produce more capacity and operate more efficiently

2. Cleaning the condenser coil, use soapy water and keep the condenser coil clean,

put it on the same schedule as the indoor unit filter cleaning

Page 7: Mini Split Samsung

7

Applications Residential Sizing Sizing and Location of the Mini Split to the room is still EXTREMELY IMPORTANT. Quietside recommends a 12,000 Btu/h capacity for each 500 to 600 Sq Ft of the Room for most applications inside the house The throw of the 9 or 12,000 Btu/h units is approximately 15 feet, and the 18 or 24,000 Btu/h units have a throw of approximately 25 feet. Therefore when applying these units in a residential application make sure that the units are not mounted at the top of the stairs blowing directly onto a wall or inside a niche or cutout in a room. Again the temperature sensor is designed to sense the returning air after it has been supplied to the room, extracted the heat and humidity and then returned to the unit, not when it has been bounced directly back off a wall or other obstacle. Ambient As standard the units are capable of cooling down to an ambient of 65 DegF, which is sufficient for the majority of residential applications Indoor unit Location For optimum unit operation the High Wall Indoor unit should be mounted a minimum of 6 feet from the floor. A minimum height of 4 feet must be maintained for correct unit operation. Ensure air flow is never directly straight onto areas where people may sit or congregate, as the temperature difference between Supply and Return air will be approximately 35 DegF. Outdoor unit location The Outdoor units are designed to operate with extremely low noise levels compared to the standard US condensing unit, this allows the outdoor units to located in areas closer to property lines, however when locating the Quietside Outdoor unit ensure that the spacing detailed in the Installation manual are observed, and that the maximum line length and lift restrictions are adhered to. Garages or FROG’s/Bonus Rooms Quietside Mini Splits are perfect for adding conditioning to Garages and FROG’s/Bonus Rooms Use a 400 sq per 12,000 Btu/h sizing guide and as always follow the location guidelines provided for the Indoor and Outdoor unit.

Page 8: Mini Split Samsung

8

Applications Sun Rooms or 4 Season Rooms Sizing Sizing and Location of the Mini Split to the room is still EXTREMELY IMPORTANT. Quietside recommends a 12,000 Btu/h capacity for each 325 to 350 Sq Ft of the Room The throw of the 9 or 12,000 Btu/h units is approximately 15 feet, and the 18 or 24,000 Btu/h units have a throw of approximately 25 feet. Sun Rooms are a great application for Quietside Mini Split units however there are several items that must be addressed to make the installation a success. Ambient Sun Rooms are different in their application as they by definition have a large solar gain and therefore can require cooling in cold ambient temperatures. Therefore as per Computer room and Commercial applications it is mandatory to install the ICM 326H low ambient control and a crankcase heater on the system. Indoor unit Location For optimum unit operation the High Wall Indoor unit should be mounted a minimum of 6 feet from the floor. A minimum height of 4 feet must be maintained for correct unit operation. Ensure air flow is never directly straight onto areas where people may sit or congregate, as the temperature difference between Supply and Return air will be approximately 35 DegF. Heat Pumps In order to use the Sun Room year round Heat Pumps are the recommended system, however it may be advisable to install some additional source of heat, such as electric baseboard if the Sun Room is to be used in temperatures below 24 DegF. Below 24 DegF the air temperature delivered from the unit will be close to body temperature making it feel uncomfortable, as when the Outdoor temperature falls the unit capacity and efficiency reduces, together with the unit requiring more frequent defrost cycles. This will assist in truly making the Sun Room a room to be enjoyed in comfort all year round

Page 9: Mini Split Samsung

9

Applications Low Ambient Cooling As stated in the Computer Room, Commercial and Sun Room application pages - ALL Quietside models as standard are capable of providing COOLING operation down to an ambient temperature of 65 DegF. Therefore to operate in Cooling down to an ambient temperature of 32 DegF, both an ICM326H Fan Speed Controller, plus a Crankcase Heater, either a Mars #32342 or Raychem #CCH-1 or 2 bellyband types MUST be installed. For cooling operation below 32 DegF, and down to a minimum of 0 DegF, Quietside recommends that Wind Baffles be installed on both the Coil Inlet and Fan Outlet of the Outdoor unit. Please contact Quietside directly for details of the design requirements for the Wind Baffles. We also recommend using these Wind Baffles in applications where the units may be exposed to prevailing winds blowing though the condenser coil. These winds may cause the unit to over condense and freeze the indoor unit, or allow liquid refrigerant to be inadvertently slugged back into the compressor. Installing the ICM326H Fan Speed Controller The controller should be located per the instructions provided, it is not weatherproof, therefore should be mounted inside the compressor compartment of the Outdoor unit Quietside Units have Ball Bearing Condenser Fan motors, set both the Hard Start and Cut Out speed setting dials to 1/3 off the MINIMUM position The Temperature sensing probe should be securely attached on or adjacent to a return bend on the condenser coil that measures 100 DegF in normal operation. In practice this works out to be the 3rd Return bend down from the top of the coil. Securely strap the probe to the bend or tube and insulate to ensure accurate temperature sensing. Wiring Wiring should be in accordance with the diagrams on the following pages, DO NOT deviate from the wiring shown, if in doubt please call Technical Support for assistance. Please note on Heat Pump units the bypass connection must be wired from the Reversing Valve to the ICM controller to ensure that the Outdoor fan operates at full speed in the Heat Pump Heating mode

Page 10: Mini Split Samsung

Bla

ckN

Red

1N

2L

Ora

nge

GR

OU

ND

Fiel

d

Sup

plie

d W

ireN

1O

rang

e

L1

Bla

ck1

To C

ompr

esso

r

Not

esFi

eld

wire

from

Bla

ck to

Lin

e 1

115V

Con

nect

ion

on IC

M32

6HC

ut th

e O

rang

e w

ire a

nd w

ire a

s pe

r dia

gram

Loca

te T

empe

ratu

re P

robe

on

or a

d jac

ent t

o 10

0 D

egF

Ret

urn

bend

on

the

Con

dens

er C

oil

8750

Pio

neer

Blv

d, S

anta

Fe

Spr

ings

CA

906

70

Set

Cut

Out

Spe

ed to

1/3

off

MIN

in B

all B

earin

g R

ange

Tel :

562

699

606

6, F

ax :

562

699

4351

, Web

: w

ww

.Qui

etsi

de.c

om

Set

Har

d S

tart

to 1

/3 o

ff M

IN in

Bal

l Bea

ring

Ran

geTi

tle :

QS

CE

09/

12 C

oolin

g O

nly

ICM

326

H W

iring

Drg

# :

QS

CE

09-IC

MD

raw

n :

JLM

7/11

/200

6R

ev :

Zero

Orange

Black

FAN

MO

TOR

ICM

326

HH

EAD

PR

ESSU

RE

CO

NTR

OLL

ER

Line

2M

otor

Li

ne 1

115V

Line

124

0V Hea

t Pum

p

Page 11: Mini Split Samsung

Blu

e

Com

pres

sor

L2R

edC

onta

ctor

Black

L1

Ora

nge

Blu

eG

RO

UN

DFi

eld

Sup

plie

d W

ire

L4O

rang

e

Ora

nge

L3R

ed

1

Not

esFi

eld

wire

from

Bla

ck to

Lin

e 1

240V

Con

nect

ion

on IC

M32

6HC

ut th

e O

rang

e w

ire a

nd w

ire a

s pe

r dia

gram

Loca

te T

empe

ratu

re P

robe

on

or a

djac

ent t

o 10

0 D

egF

Ret

urn

bend

on

the

Con

dens

er C

oil

8750

Pio

neer

Blv

d, S

anta

Fe

Spr

ings

CA

906

70

Set

Cut

Out

Spe

ed to

1/3

off

MIN

in B

all B

earin

g R

ange

Tel :

562

699

606

6, F

ax :

562

699

4351

, Web

: w

ww

.Qui

etsi

de.c

om

Set

Har

d S

tart

to 1

/3 o

ff M

IN in

Bal

l Bea

ring

Ran

geTi

tle :

QS

CE

18A

/24A

Coo

ling

Onl

y IC

M 3

26H

Wiri

ngD

rg #

: Q

SC

E18

-ICM

Dra

wn

: JL

M9/

26/2

006

Rev

: Ze

ro

FAN

MO

TOR

ICM

326

HH

EAD

PR

ESSU

RE

CO

NTR

OLL

ER

Line

2M

otor

Li

ne 1

115V

Line

124

0V Hea

t Pum

p

CO

NT-

AC

TOR

CO

IL

Page 12: Mini Split Samsung

NR

ed

Bla

ckN

3N

2L

Ora

nge

Fiel

d S

uppl

ied

GR

OU

ND

Wire

N1

Ora

nge

Ora

nge

L1

Ora

nge

3 2Fi

eld

Sup

plie

dFi

eld

Wire

Sup

plie

d1

Wire

Not

esFi

eld

wire

from

Bla

ck to

Lin

e 1

115V

Con

nect

ion

on IC

M32

6HC

ut th

e O

rang

e w

ire a

nd w

ire a

s pe

r dia

gram

Fiel

d w

ire fr

om b

oth

side

s of

the

4 W

ay V

alve

to H

eat P

ump

8750

Pio

neer

Blv

d, S

anta

Fe

Spr

ings

CA

906

70

Set

Cut

Out

Spe

ed to

1/3

off

MIN

in B

all B

earin

g R

ange

Tel :

562

699

606

6, F

ax :

562

699

4351

, Web

: w

ww

.Qui

etsi

de.c

om

Set

Har

d S

tart

to 1

/3 o

ff M

IN in

Bal

l Bea

ring

Ran

geTi

tle :

QS

HE

09/

12 H

eat P

ump

ICM

326

H W

iring

Drg

# Q

SH

E9/

12-IC

MD

raw

n :

JLM

7/11

/200

6R

ev :

Zero

FAN

MO

TOR

ICM

326

HH

EAD

PR

ESSU

RE

CO

NTR

OLL

ER

Line

2M

otor

2Li

ne 1

115V

Line

124

0V

4 W

AY

VLV

Hea

t Pum

p

Page 13: Mini Split Samsung

Blu

e

Com

pres

sor

L2R

edC

onta

ctor

Black

L1

Ora

nge

Blu

eG

RO

UN

DFi

eld

Sup

plie

d W

ire

L4O

rang

e

Ora

nge

L3R

edR

ed

3 2

Fiel

d 1

Sup

plie

d W

ires

Not

esFi

eld

wire

from

Bla

ck to

Lin

e 1

240V

Con

nect

ion

on IC

M32

6HC

ut th

e O

rang

e w

ire a

nd w

ire a

s pe

r dia

gram

Fiel

d w

ire fr

om b

oth

side

s of

the

4 W

ay V

alve

to H

eat P

ump

Loca

te T

empe

ratu

re P

robe

on

or a

djac

ent t

o 10

0 D

egF

8750

Pio

neer

Blv

d, S

anta

Fe

Spr

ings

CA

906

70

Ret

urn

bend

on

the

Con

dens

er C

oil

Tel :

562

699

606

6, F

ax :

562

699

4351

, Web

: w

ww

.Qui

etsi

de.c

om

Set

Cut

Out

Spe

ed to

1/3

off

MIN

in B

all B

earin

g R

ange

Title

: Q

SH

E 1

8A/2

4A H

eat P

ump

ICM

326

H W

iring

Set

Har

d S

tart

to 1

/3 o

ff M

IN in

Bal

l Bea

ring

Ran

geD

rg #

: Q

SH

E18

-ICM

Dra

wn

: JL

M9/

26/2

006

Rev

: Ze

ro

FAN

MO

TOR

ICM

326

HH

EAD

PR

ESSU

RE

CO

NTR

OLL

ER

Line

2M

otor

Li

ne 1

115V

Line

124

0V Hea

t Pum

p

CO

NT-

AC

TOR

CO

IL4

WA

Y VA

LVE

Page 14: Mini Split Samsung

14

Applications Heat Pump Quietside Heat Pump units are NOT fitted with any type of auxiliary heating for back up heat during periods of time when the outdoor ambient is to cold to allow for full capacity operation. Basically the colder the air outside, the lower the capacity and supply air temperature provided by your Quietside Heat Pump. If the Outdoor Coil temperature is below 14 DegF, Heat Pump operation is stopped and the unit will shut down, until the coil temperature increases, when the unit will immediately go into a defrost. Therefore we recommend that the Quietside heat pump should NOT be used as the primary source of heating where Outdoor temperatures are regularly below 24 DegF for sustained periods of time. If a Heat Pump is used in these applications ensure that an additional source of heat (baseboard electric or hydronic, or other type) be used when the temperature falls below 24 DegF. Warm Start In Heat Pump operation the Indoor fan motor will only start operating, when the indoor coil temperature has reached 98 DegF. Then the fan will start operating in an ultra low speed mode, increasing in fan speed back to the selected speed on the remote control as the Indoor coil temperature increases. When the unit completes Defrost, the warm start feature will be used to allow the coil to warm up before restarting the Indoor fan. Warm start operation is indicated by a the run light on the display blinking once Heat Pump Heating on the Remote Control The symbol on the Remote Control for Heat Pump Heating is a little confusing The symbol that is a SUN is the correct symbol for Heat Pump Heating Press the mode button until the SUN is displayed, and then select the desired temperature and fan speed and the unit will operate in Heat Pump mode The symbol that looks like a FLAME is actually be a DRIP of water. This mode is the DRY mode, which is used to cool the room down at the lowest possible fan speed, which removes the most moisture from the room. Therefore if your customer complains that his heat pump is not operating in heating, first check that he has it in the correct mode on the remote control

Page 15: Mini Split Samsung

15

Cont Defrost Quietside units feature “Demand Defrost” which allows the unit to choose when to enter into defrost, not just every 30, 60 or 90 minutes as most heat pumps An Outdoor coil temperature sensor is located in the Outdoor unit, it MUST be connected back to the Indoor PCB, the sensor will assist in determining if defrost is required. (Not connecting the sensor will result in a fault code – see fault section) During Defrost the Indoor fan motor will stop so that cold air is not blown into the room. The Outdoor fan motor will also stop to speed up the defrost process. After defrost has finished the compressor will stop to equalize pressures. A single blink of the operating light shows that unit is in defrost. Defrost Initiation and Termination Defrost is initiated based on a combination of multiple sets of factors Factor A Total accumulated time for compressor operation in heating is greater

than 45 minutes Factor B Outdoor coil temperature is less than 23 DegF (16400Ω) for at least 1

minute Factor C Continuous Compressor operation for more than 3 minutes Factor D Unit has been on for at least 30 minutes, and then switched to Heat Pump

mode Factor E Unit is turned on in the Heat Pump mode Factor F Outdoor Coil temperature is below 28 DegF (14500Ω) Combinations required for defrost initiation A, B & C occurring together D & E occurring together E & F occurring together Terminating Defrost also has a combination of factors Factor G Outdoor Coil temperature sensor is above 59 DegF (7300Ω) Factor H Unit has been in the defrost mode for a maximum of 10 minutes Combinations required for defrost termination G OR H occurring independently

Page 16: Mini Split Samsung

16

Cont Reversing Valve The reversing or 4 way valve is energized for HEATING in a Quietside unit. If the unit does not produce heat when in the Heat Pump mode, check for line voltage starting at the Indoor unit terminal, and follow that voltage out via the interconnecting wire to the solenoid coil on the valve. Reversing valve coils are line voltage, again Quietside units do not use any 24V AC controls Overheat Protection Quietside units use a single speed compressor, so performance is dependant upon the ambient conditions (Indoor and Outdoor) Indoor fan speed, plus the flow of refrigerant through the unit. Quietside units measure the Indoor Coil temperature during Heat Pump operation, if the Indoor coil temperature becomes excessive the unit will protect itself. If the Indoor Coil temperature reaches 132 DegF (1800Ω), the Outdoor Fan will stop in an effort to reduce performance, it will not restart until the Indoor coil temperature has fallen to 126 DegF (2000Ω) If the Indoor coil temperature continues to rise, at 142 DegF (1500Ω) the unit will shut down the Compressor and the Outdoor Fan. Two minutes after shutting down the Compressor and Outdoor Fan, the Reversing Valve will switch back to the Cooling mode position. The Indoor fan speed will remain at the user set speed until the Indoor Coil temperature reaches 136 DegF (1600Ω), when it is forced into High Speed When the Indoor Coil has cooled down to 122 DegF (2100Ω), the unit will revert back to Heat Pump operation starting the Compressor, Outdoor Fan and re-energizing the Reversing Valve.

Page 17: Mini Split Samsung

17

Accessories To make the installation process simpler Quietside is pleased to offer the following accessories for our range of Mini Splits Condensate pumps:

We recommend Aspen condensate pumps for our units. Several styles of pumps are available including those with covers to hide the piping and pump Remember all condensate pumps require maintenance and can be noisy during operation. These pumps must use the power supply provided at the indoor unit, 115V Pumps on the QSCE/HE 09-12 and 230V Pumps on the QSCE/HE 18-24. The Float switches/alarm must be wired into the system and Quietside provides wiring diagrams to ensure that the pumps are correctly wired in. For all other instructions refer to the instructions provided with the pump. Line Sets Quietside offer Line Sets for all of the High Wall and Multi Split units in both a 25ft and a 50ft length The advantages of these Line Sets are :

1. Both the Suction and “Expanded Gas” line are insulated with high efficiency 3/8” insulation. On all High Wall and Multi Split Quietside units both lines are required to be insulated as the Expansion Device for the system is located in the Outdoor unit

2. Electrical wire is included : As the Electrical Interconnect between the Indoor and

Outdoor units is line voltage, 14 AWG wire is required. The Line Sets are supplied complete with 7 conductor 14 AWG wire, sufficient to be able to connect all Quietside models – Check your local codes as to the ability to use this wire.

3. Factory made flare connections, these allow for complete confidence in the

connection at the Indoor and Outdoor units

Page 18: Mini Split Samsung

18

Cont Quietside Electrical Cables 14 Gauge wire is required in North America for all of the interconnect wiring 6 interconnecting wires are the most ever required between indoor and outdoor units, these are used on the QSHE systems Low Ambient Controller Refer to Page 7 for Low Ambient information and reference information Quietside recommends the ICM 326H Fan Speed Controller only Mounting Brackets Quietside offers wall-mounting brackets as an accessory. Mounting the condensing unit on the wall is common throughout the world keeping the Outdoor out of the way and as a method for keeping units inside the maximum line set runs. Gauge Adaptor In order to differentiate that the 13 SEER Quietside Mini Splits are now using R410A refrigerant to increase efficiency and protect the environment, the gauge connections are 5/16” instead of the standard ¼” used on most standard equipment. This prevents the use of an incorrect gauge set. To connect from the 5/16” Schrader to an R410A gauge set Quietside offer a single adaptor to attach to the Suction line Schrader, Quietside Part # R410-ADPT

Page 19: Mini Split Samsung

19

Pre Installation Requirements

1. Unit sized correctly and applied correctly Refer to Pages 3 through 10 for information on the sizing and additional requirements for the specific application required. If in doubt ask your Quietside authorized distributor or call Technical Service for advice

2. Electrical Requirements All the Quietside units require Line Voltage interconnect for both power for the Indoor unit and Control voltage for the Outdoor unit. There is NO 24V AC wiring on these units, therefore all the electrical wiring between the units MUST be a minimum of 14 AWG The Outdoor unit MUST be fed with power from a Breaker and/or Local Disconnect. The Outdoor unit MUST provide power for the Indoor unit. Do not install local disconnects or J boxes adjacent to the Indoor unit as this can cause mis-wiring and polarity issues for the system

3. Breaker Size Check the Breaker Size is correct for the system, Quietside units do not have start components for the compressor, and therefore they rely on the correct power and amperage supply to start Unit Power Supply Breaker Size QSCE/HE09 115V-1Ph-60Hz 15A QSCE/HE12 115V-1Ph-60Hz 15A QSCH/HE18 208/230V-1Ph-60Hz 20A QSCE/HE24 208/230V-1Ph-60Hz 25A

Page 20: Mini Split Samsung

20

Cont

4. Line Set Lengths and Sizes Ensure that the Maximum Line Set lengths are observed; the System will not operate correctly and will probably experience premature failure of its components. DO NOT upsize or alter the Line Set Sizes from those published, Quietside cannot guarantee operation with incorrectly sized or extended Line Sets DO NOT install Sight Glasses or Filter Driers in the Line Set Model Suction Expanded Gas Total Length Lift QSCE/HE09 ½” ¼” 50ft 20ft QSCE/HE12 ½” ¼” 50ft 20ft QSCE/HE18 5/8” 3/8” 50ft 20ft QSCE/HE24 5/8” 3/8” 50ft 20ft All of the units have the expansion device located in the Outdoor unit; therefore both the Suction and the “Liquid” line MUST be insulated (separately)

5. Indoor Unit Positioning High Wall units must be mounted high on the wall, use a height of 6 to 8 feet, with nothing that would restrict airflow in front of the indoor units. This will provide optimum operation. Minimum height from the floor is 4ft. The air returned to the indoor unit must be indicative of the true temperature of the entire space. When the unit is high on the wall, and the discharge air travels along the longest path possible to return to the unit (no blockage or reflected air returned) the system will operate properly. Wall units throw air approximately 15’ (9 & 12,000 Btu/h units) and 25’ (18 & 24,000 Btu/h units) Use the templates provided to locate the unit on the wall and to center the refrigerant connection hole – Quietside recommends a 3” wall penetration to ease mounting of the unit.

6. Outdoor Unit Positioning Ensure that a minimum distance of 6” behind the unit, and 24” in front of unit is maintained; otherwise the condenser airflow will be affected. Ensure adequate access for service and repair is provided. The easiest access to the unit can be obtained by removing the top cover to the condensing unit. All valve and electrical connections are on the RHS of the Outdoor unit when looking at the condenser fan

Page 21: Mini Split Samsung

21

Installation Tips Tools required for installing a Quietside Mini Split 10” or 12” Crescent wrenches (x 2) Small Electrical Screwdriver Tool to help knockout the cable entry holes Refrigerant Gauges and 5/16” Gauge Adaptor Vacuum Pump and Vacuum gauge Digital Refrigerant scale to weigh in extra R410A for long line set lengths Temperature measurement device Multi Meter

1. R410A Refrigerant

R410A refrigerant has similar temperatures to that of R22, however as well documented the pressures of R410A are approximately double that of R22. In addition to this the compressor oil used with R410A is extremely hydroscopic i.e. attracts water; therefore several precautions must be taken when installing R410A refrigerant units. These are :

1. Minimize the time that the system piping is open to the atmosphere. Avoid problems with a clean installation of refrigerant lines. Make sure that the flares are free of burrs and seat correctly.

2. Quietside does not recommend any brazing of refrigerant line sets.

3. Do not install Sight Glasses or Filter Driers in the interconnecting Line Set. 4. Pressure test the system with dry Nitrogen or other dry gas. The system must be

put into a deep vacuum (200 Microns minimum), Quietside recommends a minimum of 45 minutes evacuation using the double evacuation process, breaking the original vacuum with dry Nitrogen, then re-evacuating prior to opening the service valves as the best method of ensuring a perfectly dry system.

5. In order to prevent confusion with what type of refrigerant is used in the system

Quietside uses a 5/16” Schrader connection on the Suction line to attach a gauge set to. Therefore an adaptor is required to connect to a standard US gauge set.

It is always a good practice to insulate the flare nuts to prevent loosening as the system operates; this is especially recommended for Heat Pump units due the changes in the temperatures seen at the service connections when the units operate in heating and then enter defrost.

Page 22: Mini Split Samsung

Cont

2. Electrical Wiring Connections Quietside systems are ALL POLARITY SENSITIVE to the power supply, even the 208/230V units, it is VITALLY IMPORTANT that the wiring from Outdoor to Indoor unit is point to point, with the wire leaving one terminal on the Outdoor units landing in the same numbered or lettered terminal on the Indoor unit This is a sample electrical interconnect for the following units, QCIH 09/12

Indoor Unit Outdoor Unit1 12 23 3

L1 L1N1 N1

(Ground) G GLN

SystemBreaker

115V Power is supplied from the Breaker on N & L 115V Power for the Indoor unit is provided on N1 & L1 Compressor signal is Terminal #1 4 Way Valve signal is Terminal #2 Condenser Fan signal is Terminal #3 G is Ground (or Earth as it is sometimes called) Electrical terminals at both the Indoor and Outdoor units require the use of a “small” bladed electrical screwdriver to access the terminal screws.

3. Number of Electrical Interconnect Wires If a question on the wiring occurs, the IOM manual contains the unit wiring diagrams Model Number of Interconnect Wires, including Ground QSCE 09/12 4 QSCE 18/24 4 QSHE 9/12 6 QSHE 18/24 6

22

Page 23: Mini Split Samsung

Cont

4. Service Valves

FLARE

FLARE

Quietside units manufactured in 2006/early 2007 do not have flare nuts supplied with them, Flare Nuts can be purchased at your Quietside wholesaler, they are standard. The refrigerant line set connections can be found under the GRAY plastic caps not the brass ones which cover the valve stems. DO NOT TRY TO PUT THE FLARE NUTS ON THE THREADS FOR THE SERVICE VALVE STEMS – THEY WILL NOT FIT Once the line set is connected, the system, it should be pressure tested and then evacuated to a minimum of 200 Microns, the charge for the system has to be released from the Outdoor unit. To do this, it is very important that the SUCTION SERVICE VALVE MUST BE OPENED FIRST This will allow the refrigerant to flood the system without passing through the capillary tube. If the Liquid service valve is opened first it is possible to log Oil in the capillary tube, especially if the outdoor temperature is low If this happens the unit will drop into a vacuum immediately on start up of the unit, to repair this either recover the refrigerant charge and start evacuation again or it is possible to clear the log by driving up the condenser head pressure by blocking off the outdoor coil or unwiring the condenser fan 23

Page 24: Mini Split Samsung

24

Cont

5. Adding Refrigerant Charge If the unit interconnect length exceeds the standard charge length of the system, additional refrigerant must be added to the system. Quietside systems are charged for a 25ft line set as standard. The additional refrigerant MUST BE WEIGHED INTO THE SYSTEM, as these are critically charged systems The additional amount of refrigerant required is calculated from the extra length of interconnect multiplied by the refrigerant quantity in oz/ft. All systems use R410A. QSCE/QSHE 09 & 12 Add 0.3 oz/ft of R410A over 25ft QSCE/QSHE 18 & 24 Add 0.5 oz/ft of R410A over 25ft Added Charge required for a line set of Unit 30ft 35ft 40ft 45ft 50ft QSCE 09 & 12 1.5oz 3.0oz 4.5oz 6.0oz 7.5oz QSCE 18 & 24 2.5oz 5.0oz 7.5oz 10.0oz 12.5oz QSHE 09 & 12 1.5oz 3.0oz 4.5oz 6.0oz 7.5oz QSHE 18 & 24 2.5oz 5.0oz 7.5oz 10.0oz 12.5oz Remember the Schrader connection for these R410A units is a 5/16” size, not the standard ¼”, this distinguishes the system from an R22 system, so that the incorrect gauges or refrigerant cannot be used by mistake.

6. Condensate Piping Follow installation instructions and remember water runs down hill. Installation diagram is in the Installation and Operation Manual To check the condensate piping system, all condensate should be completely drained from the system if the unit has not been in the cooling mode for at least 4 hours. To connect from the 18” condensate hose provided on the Indoor unit we recommend an ø 5/8” ID or ¾” OD clear flexible PVC hose, this will provide a tight interference fit on the unit connection and allow standard rigid copper or PVC piping (depending on local codes) to be used for the remainder of the drain.

Page 25: Mini Split Samsung

25

Common Technical Problems These are a sample of the common Technical questions that are asked of our Technical Support staff. By having these available it may help diagnose a problem before calling

1. No operation Indoor Unit – No Indicator lights on the unit If the Indoor unit has power run to it, but it will not operate, first check the 6.3A Fuse that is mounted on the Indoor PCB (Microprocessor). This fuse is used to protect the PCB from spikes or changes in the power supply; therefore it is common to require this fuse after electrical storms or power outages Replacement fuses can most easily be obtained from Radio Shack, it is Radio Shack part # 270-1068. The fuse is a glass Buss type

2. No Compressor or Condenser Fan Operation on start up This is due to the polarity on the power supply being reversed, which allows the control relays to close on the same leg, giving 0V at the compressor. The reason that Quietside units have polarity even on 208/230V power is that they are built for the world marketplace. The rest of the world uses a 220V “Hot Leg” and a 0V Neutral leg. This means that the unit switches the “Hot Leg” via the PCB and sends it back to the Outdoor unit to start the compressor and condenser fan This can be alleviated by wiring the unit in multi colored wires (see the Quietside wire in the accessories section), or by making sure that the wiring is exactly point to point per the diagram – See the interconnect diagram on Page 20 of this manual or refer to the Quietside Basic Technical Guide for individual wiring interconnect diagrams. One method to check for this issue is to remove the interconnect wire from terminal #1, and them use a jumper wire between L1 and 1 on QSCE/QSHE 09/12 units L3 and 1 on QSCE/QSHE 18/24 units This should start the compressor and on Cooling only units the Outdoor fan also. If the compressor starts check the wiring between the Outdoor and Indoor units. If the wiring looks correct, then check the Indoor PCB for the correct outputs, at the Indoor remove the wires from terminals #1, 2 & 3. Turn on the unit in cooling and using a multi meter check from L1 or L3 to 1 for line voltage. If voltage is present check the wires for obvious damage, if no voltage is present it may be the Indoor PCB that is faulty.

Page 26: Mini Split Samsung

26

Unit Fault Codes The units have a self diagnostic capability should certain faults occur with the system. The Indoor unit will blink the run light a certain number of times to signify which fault has occurred These faults are : One Blink Unit is running in the Warm Start mode Two Blinks Room Temperature Sensor Error Three Blinks Coil Temperature Sensor Error Four Blinks Outdoor unit Error Five Blinks Freeze Protection Mode Six Blinks N/A Seven Blinks Outdoor Temperature Sensor Error – Heat Pumps only A constant blinking light indicates that the unit is running in the Defrost mode Warm Start Mode = 1 Blink This allows the Indoor coil to heat up on initial start of Heat Pump heating, Indoor fan will not operate until the coil temperature is 98 DegF Room Temperature Sensor Error = 2 Blinks Reason - If the Room Temperature sensor mounted on the front of the Indoor coil, either shorts out or the resistance value goes to infinity the unit will recognize this and shut down Remedy – Check sensor using a multi meter, if outside resistance range or shorted replace the sensor. If within normal range/not shorted replace PCB. This is the same thermistor as the Room Temperature and Heat Pump defrost temperature sensor. Temperature Resistance 50 DegF 8800 Ω 60 DegF 7100 Ω 70 DegF 5750 Ω 80 DegF 4650 Ω 90 DegF 3800 Ω

Page 27: Mini Split Samsung

27

Cont Coil Temperature Sensor Error = 3 Blinks Reason - If the Coil Temperature sensor mounted in a well on the RHS of the Indoor coil, either shorts out or the resistance value goes to infinity the unit will recognize this and shut down Remedy – Check sensor using a multi meter, if outside resistance range or shorted replace the sensor. If within normal range/not shorted replace PCB. This is the same thermistor as the Room Temperature and Heat Pump defrost temperature sensor. Temperature Resistance 20 DegF 17800 Ω 30 DegF 13800 Ω 40 DegF 11000 Ω 50 DegF 8800 Ω Outdoor Unit Error = 4 Blinks When the unit operates it continuously measures the Indoor coil temperature. If after 5 minutes of compressor operation the Indoor coil temperature is not below 77 DegF (5000Ω) for cooling operation, or above 86 DegF (4200Ω) in Heat Pump operation, the unit will display the 4 blinks. The unit will then operate for another 20 minutes with the error code blinking, if the Indoor coil temperature has still not fallen/risen below/above the requirements then the controller will shut down the unit This error code can have several causes Compressor problem – locked or other mechanical/electrical problem with the compressor – check the OLP located on top of the compressor, it should be normally closed, open circuit if the compressor is overheating or drawing locked rotor amperage. Check the compressor run capacitor, Quietside units do not use starting capacitors, in areas of low mains voltage a start component, e.g. “Kickstart” may be a good idea especially in a commercial application where multiple starts are often required. Refrigerant Loss or flow restriction – Check for a leak, if a leak is found, repair, evacuate and recharge to the nameplate charge, adding additional refrigerant if the line set is greater than 25ft. Check for a restriction in the system. The capillary tube expansion device(s) are located in the Outdoor unit. Check for clogged Filters, Indoor Fan or Coils – Ensure all parts are clean and free of debris

Page 28: Mini Split Samsung

28

Cont Freeze Protection Mode = 5 Blinks If the Indoor coil temperature sensor reads a temperature of 32 DegF (13300Ω), and the compressor has been running continuously for 10 minutes, the Compressor and the Outdoor fan will shut down, and the Indoor fan speed will be set to low. When the Indoor coil temperature rises to 45 DegF (9900Ω), and the compressor has been off for a minimum of 3 minutes, the compressor and the Outdoor fan will restart. If the Indoor coil temperature sensor reads a temperature of 5 DegF (25600Ω), and the compressor has been running for 3 minutes continuously, the Compressor, Outdoor fan, Indoor fan and the Air Vane will be shut down. The unit will be restarted after a 6 minute off period, if the coil temperature sensor again senses a temperature of 5 DegF within a six minute period the unit will again shut down and the unit will indicate that it is in the Freeze Protection mode. Check Refrigerant charge, Indoor Fan & Filters, is unit cooling below 65 DegF Ambient? Defrost Temperature Sensor = 7 Blinks On Heat Pump systems there is a sensor in the Outdoor Coil which measures the temperature of that coil. It is connected via the factory supplied (or field supplied) 18 AWG to the Indoor unit. If the sensor shorts out or the resistance is out of range or if it is not connected to the Indoor unit, it will display the error code when turned into the Heat Pump mode. The system can operated in the cooling mode without the sensor being connected, however if the heating mode is selected the unit will display the error code. Temperature Resistance 20 DegF 17800 Ω 30 DegF 13800 Ω 40 DegF 11000 Ω 50 DegF 8800 Ω 60 DegF 7100 Ω 70 DegF 5750 Ω 80 DegF 4650 Ω 90 DegF 3800 Ω The sensor uses a 2 pin electrical connector, check this to ensure that the electrical connection is made correctly. Pull apart the connector and check on the wire from the Indoor unit, the voltage provided from the Indoor Microprocessor to the sensor, it should be 5VDC. If no voltage is found the Indoor PCB is faulty.

Page 29: Mini Split Samsung

29

Maintenance Mini Splits are very easy to maintain, in reality they are not very different to the maintenance on a Central A/C or Heat Pump system, and can be placed on a similar maintenance schedule with one major exception. Filters & the Continuous Fan All Mini Splits feature continuous Indoor fan operation when the unit is powered and turned on, the Indoor fan does not cycle with the compressor as is common with the standard “US style” systems The reason for this is : While the system is on, the fan slowly moves air throughout the conditioned space, monitoring the temperature of the air returning to the fan coil. This action provides accurate temperature control and eliminates temperature and air stratification inside the room. The system will quickly react to changes in temperature in the conditioned space, allowing a minimal temperature fluctuation and a more comfortable environment. The energy use and wear on a constantly moving fan is less than a fan constantly starting and stopping. The additional cost per year is negligible. It can be compared to a 40-watt light bulb being used all year (approximate cost per day of less than a quarter) to a 1/3 to ½ (500 to 750 watts) hp motor. (Which is started and stopped 4 to 6 times in an hour, consuming far more energy and costing more : 500W x 20minutes = 166W consumed per hour versus 40W for the Quietside unit But the constant fan operation does have one drawback, the unit air filters work harder and therefore clog up faster than on a regular central unit Therefore Quietside recommends that in ALL applications the 2 large Air Filters be cleaned MONTHLY. This is very important, especially with the lower airflows of the Quietside units any loss of airflow due to dirty or clogged filters can cause the unit to possibly freeze up the indoor coil or to cycle on the freeze protection thermostat

Page 30: Mini Split Samsung

30

Warranty Information THE CURRENT QUIETSIDE WARRANTY IS : 5 YEARS ON THE COMPRESSOR ONE YEAR ON ALL FUNCTIONAL PARTS 90 DAYS LIMITED LABOR WARRANTY Warranty support first starts with the Quietside Distributor. Initially they should be able to advise on the correct application, shipping and handling procedures for the product and general installation advice. Always check the product packaging prior to leaving the Distributor, note any damage and return the product to the Distributor if necessary – DO NOT INSTALL DAMAGED UNITS AND THEN TRY TO CLAIM A WARRANTY PART. Should a problem occur with the product, again the Distributor will be the first point of contact in the warranty process. The Distributor should either have a Quietside Warranty claim form or a replacement part available to the contractor. Following proper procedures will expedite warranties. A warranty claim form must be filled out completely and legibly. Include the name and a contact person at both the Contractor and Wholesaler Send the completed claim form to Quietside via the fax number on the form or email to [email protected] If it is not filled out correctly it will be returned to the Wholesaler or the Contractor to be corrected. Typical turnaround for a warranty is 2 to 3 business days. Typically parts will not be required to be returned unless requested by the factory Quietside may contact the contractor or technician to review the installation if required, or to verify a labor claim In the unexpected event of a problem occurring within the first 90 Days of operation Quietside will require the additional labor claim paperwork to be completed; your Quietside distributor can assist with this. When approved, the labor warranty payment will be credited back to the Quietside distributor referencing the contractor involved. Remember: “No Claim Form, or an incorrectly filled out form = No Action”

Page 31: Mini Split Samsung

31

Website The Quietside website has been designed to further assist you in obtaining information on all of our products. The address is

www.Quietside.com

The website is organized into several sections, products, installation tips and support. All of the published documents from Quietside are available on the website for printing or downloading as necessary. Email addresses for Sales, Customer Support, Warranty and Technical Support are available to contact us.

Manual Notes

THANK YOU FOR READING THIS MANUAL, WE HOPE IT HAS BEEN INFORMATIVE.

PLEASE NOTE THAT ALL QUIETSIDE UNITS ARE SUBJECT TO CONTINOUS IMPROVEMENT AND SPECIFICATIONS CAN CHANGE WITHOUT NOTICE PLEASE CHECK THE INFORMATION SUPPLIED WITH THE UNIT BEFORE INSTALLATION

ALL SIZING GUIDES CONTAINED IN THIS MANUAL ARE SUGGESTIONS ONLY BASED ON OUR EXPERIENCE AND KNOWLEDGE, HOWEVER PLEASE PERFORM AN ACCURATE HEAT LOAD ANALYSIS PRIOR TO SELECTING AND INSTALLING YOUR QUIETSIDE MINI SPLIT

John Stu Denis Mike Kevin Chris

Page 32: Mini Split Samsung

Quietside West Tel : 562-699-6066, Fax : 562 699 4351 Quietside East Tel : 717-243-2535, Fax : 717 243 7917