micom ieds for process bus_experts 2012
DESCRIPTION
Micom IEDTRANSCRIPT
GRID
MiCOM IEDs ForProcess Bus Applications
April 2009
Experts Training 2012
Stafford, United Kingdom
Scope
Digital Substations & Process Bus Overview Page 3
MiCOM IEDs for Process Bus Page 21
Px4x -9-2LE Interface Features Page 31
Process Bus Architectures Page 47
Testing, Conclusion Page 60
Presentation title - 01/01/2010 - P 3
Reference Digital SS Architecture across Grid
Proxy
Multiple Ethernet
IEC61850.8-1
Station Bus
C37.118 Phasor Data
Grid Control
Rooms
AMU
Primary Eqpt with
embedded sensors
for Condition Monitoring
Prot. Px40
DRUs
Switches
WAN
CMU
SCS HMI
Multiple Ethernet
IEC61850.9-2 &
IEC61850.8-1
Process Bus
Digital SS ComponentsIntegrated Substation Automation System with
1. Substation Control System (SCS)
2. Condition Monitoring System (CMS)
3. Smart Grid Applications (SG APPS – Cyber,
Intrusion,
Wide Area Management)
4. Substation Phasor Data Concentrator
Several IEDs
1. Protection / Measurement with 9-2 interface
2. Bay Controller Unit (BCU)
3. Condition Monitoring Unit (CMU)
4. Switches & Telecom
5. Proxy Server
6. Merging Units (AMU, DMU, NMU – for
NCIT)
7. Wide Area Control Unit (WACU)
8. Power Quality /Disturbance Record Unit
(DRU)
9. Energy Meters
DMU
SG APPSCMS PDC
WACU
BCU
Other
substations
sPDC
SG APPS
IEC 61850 Process Bus
Process Bus Elements� Ethernet Network, 100 Mb/s
� IEC 61850-9-2 LE for Sampled Values “SV”
� Current measurement (CT)
� Voltage measurement (VT)
� IEC 61850-8-1 GOOSE Service
� Status position of Circuit Breaker / Switches (CB)
� Trip signals from protections to CBs (Trip)
� Commands from Control Systems (Open/Close)
� Others (monitoring status reports, health, settings…)
� Time synchronisation
� Microsec accuracy required
IEC 61850 Process Bus
61850-9-261850-9-2
61850-8-1
61850-8-1
Bay Level
Protection Control
Station Level
Function A Function B
HV Equipment
Bay Level
Protection Control
HV Equipment
33
11
33
1166 66
99
44 55 44 55
88
77 Technical ServicesLogical View Of SA
IEC 61850 -9-2 Overview
� Sampled Value Transmission
� Unidirectional link (MU to IED)
� Physical layer : Optic fibre (copper optional)
� Data Link layer : Ethernet 100 Mbit/s
� Application Layer : IEC 61850-9-2 “Light Edition” guideline to aid implementation and interoperability
� Sampling rate : 80 or 256 samples per cycle
� Neutral current and/or voltage may be measured, or derived
� Sampled values are multicast on the LAN
� Defines Logical Device “MU”
� Synchronising of sampling
IEC 61850 -9-2 Overview
4V; 4I
4V; 4I
� IEC 61850-9-2LE Sampled Values
� Each SV message carries 4 voltages + 4 currents
� Primary values, quality info
� Current : 1mA to 2.14 MA, Voltage : 10mV to 21.4 MV
MU-L1
MU-L2
Protection
Bay 1Protection
Bay 2
(I1a, I1b, I1c, I1n, V1a, V1b, V1c, V1n)
(I2a, I2b, I2c, I2n, V2a, V2b, V2c, V2n)
HQ_IEC 61850 Process Bus_06/2011
IEC 61850 -9-2 Overview
� SV frames are multicast
� MAC Address range: 01-0C-CD-04-00-00 to 01-0C-CD-04-1F-FF
input on Merging Units
� Note the frame overhead : 24 bytes of ‘raw data’ (per 3-phase
voltage and current) in about 125 byte Ethernet frame
Ia x 1000
32 bit Int
Ia Quality
32 bits
Ib x 1000
32 bit Int
Ib Quality
32 bits
Ic x 1000
32 bit Int
Ic Quality
32 bits
In x 1000
32 bit Int
In Quality
32 bits
Va x 1000
32 bit Int
Va Quality
32 bits
Vb x 1000
32 bit Int
Vb Quality
32 bits
Vc x 1000
32 bit Int
Vc Quality
32 bits
Vn x 1000
32 bit Int
Vn Quality
32 bits
-9-2LE Sampled Value Frame
IEC 61850 Process Bus
Merging Unit – Typical Naming
� AMU : Analogue Merging Unit
� Interface with conventional instrument transformers
� DMU : Digital Merging Unit
� Interface with CB / isolators / earth switches
� CMU : Condition Monitoring Merging Unit
� DMU with condition monitoring features
� NMU : Numerical Merging Unit
� Interface with digital instrument transformers
Presentation title - 01/01/2010 - P 10
IEC 61850 Process Bus
� Main 1, Main 2, BCU
� Individual CT cores per IED
� Independent tripping paths for Main 1 and Main 2 typically
CB
Status &
Trips
Conventional Bay Protection & Control – Example
Presentation title - 01/01/2010 - P 11
IEC 61850 Process Bus
DM
U#
1
-8-1 PRP
AM
U #
1
-9-2LE
DM
U#
2
-8-1 PRP
AM
U #
2
-9-2LE
AM
U #
3
-9-2LE Process Bus
(conceptual)
� Main 1, Main 2, BCU
� AMU, DMU
� Ethernet links and switches
� Time synch eqpt
Digital Bay Protection & Control – Example
HQ_IEC 61850 Process Bus_06/2011
IEC 61850 -9-2 Overview
� Sampling across multiple analogue MUs may need to be
synchronised � Protection functions/algorithms require all input quantities to be
supplied in ‘real time’
� Relay inputs may be from multiple MUs
o Substation layout
o Customer specifications
� Similar to synchrophasor measurements
Eg: Distance Protection (Voltage & Current)
� Both voltage & current could be supplied by one MU –
synchronisation integral to the MU
� Voltage from MU1 and current from MU2 - synchronisation
requires common time reference input to MUs
AMU - Sampling Synchronisation
Presentation title - 01/01/2010 - P 13
V˂0
I˂-36
V˂-18
I˂-81
1 ms delay
2.5 ms delay
IEC 61850 -9-2 Overview
→ SV frames from different MU may have uneven delays
→ Relay measurements will be incorrect unless the SV frames are time-aligned
IEC 61850 -9-2 Overview
� Techniques
� 1 PPS input on Merging Units
� Merging Units with capability for IEEE 1588 synchronisation
� Sampled Value frames carry synchronisation info
� Time tags (count) relative to the start of the ‘sec’
� Identifier for sync source – Global, Local or No Sync
Indicates if the SV
frame is synchronised
Sample Count0 – 3999 at 50 Hz
0 – 4799 at 60 Hz
Counter resets every sec when a
time sync signal is received
AMU - Sampling Synchronisation
Presentation title - 01/01/2010 - P 15
Relay - Sampled Values Alignment
IEC 61850 -9-2 Overview
� Time alignment of SV frames is necessary, and ensures correct operation of protection functions dependent on multiple MU’s� The number of MU’s may change depending on site
requirements and customer preferences
� Delays arise from
� Merging Units, due to their processing
� Network, depending on its configuration and switches
� Delays have a direct impact on the operating time of the scheme
� Time tags (count) relative to the start of the ‘sec’
� Identifier for sync source – Global, Local or No Sync
IEC 61850 -9-2 Overview
� Sampling Synchronisation Accuracy� Time source accuracy +/- 1µs
� Sampling across multiple MUs synchronised to within +/- 4µs
� MU should be capable of compensating network delays > 2µs
MiCOM P594
AMU - Sampling Synchronisation
IEC 61850 -9-2 Overview
� 1 Pulse Per Sec (1PPS) Signal� Transmitted by fibre as medium
� Rise and fall time < 20ns
� Clock source : Typically based on GPS
� Global 1PPS: 1PPS source is synced to GPS, pulse width between 5µs and 500 ms
� Local 1PPS : 1PPS source running on internal clock, pulse width between 0.9µs and 1.1µs
1PPS
P594 Merging Unit
AMU - Sampling Synchronisation
IEC 61850 -9-2 Overview
� Sync Flags in SV Frame
� Carried by the field smpSync
� Global 1PPS: Ideal, no impact on protection functions
� Local 1PPS : Some protections may have to be blocked
eg: Feeder differential
� No Sync : No 1PPS at AMU, running on AMU internal clock.
o Protections dependent on multiple MUs for data may be blocked, eg: distance protection with two CT inputs)
o MU said to be in ‘Holdover Mode’
-9-2LE SAV
Merging Unit
AMU - Sampling Synchronisation
IEC 61850 -9-2 Overview
� IEEE 1588 Basics
� It is a high precision time synchronization (<1us) for
synchronising real-time clocks on an Ethernet LAN
� Also called PTP – Precision Time Protocol
� Current standard : IEEE 1588 version 2
� No need for separate cabling (IRIG-B, 1PPS)
� Fault tolerance using Redundant Clocks
AMU - Sampling Synchronisation
Scope
Digital Substations & Process Bus Overview Page 3
MiCOM IEDs for Process Bus Page 21
Px4x -9-2LE Interface Features Page 31
Process Bus Architectures Page 47
Testing, Conclusion Page 60
MiCOM Px4xProcess Bus Applications
� Range of IEDs with IEC 61850-9-2LE interface
� Covers major transmission applications –distance, current differential, transformer, backup / circuit breaker IED and busbarprotection
� Full IEC 61850 Process Bus integration in combination with existing IEC 61850-8-1 interface
� Tried and tested protection functionality
Now ready !
IEC 61850-9-2LE
Sampled Values
80 samples / cycle
MiCOM Px4xProcess Bus Applications
MiCOM Alstom
P446Distance protection, with integral teleprotection
and one / two breaker reclosing
MiCOM Alstom
P546Line differential for 2 or 3 terminal lines, with
distance and one / two breaker reclosing
MiCOM Alstom
P645Transformer differential for up to 5 ends, with
advanced loss-of-life thermal monitoring
MiCOM Alstom
P746Numerical busbar protection
MiCOM Alstom
P841Transmission line terminal IED, for backup,
reclose and breaker fail management
Relay Types Available
MiCOM Px4x Process Bus Applications
Process Bus Interface
Interface for -9-2LE
Sampled Values
Interface for -8-1 GOOSE
and Station Bus
HQ_IEC 61850 Process Bus_06/2011
MiCOM Px4xProcess Bus Applications
� Point to point connections
� Feasible when all the SV required by a relay are available from a single MU
� Simple network, minimum delay, minimal engineering effort
Interfacing SV to Px4x
-9-2LE
MiCOM Px4xProcess Bus Applications
Interfacing SV to Px4x – Transformer Protection
P645
HV+LV+TV
HV Current - 1
HV Current 2
TV Current - 1
TV Current - 2
LV Current
Point to point
connection
not possible
MiCOM Px4xProcess Bus Applications
� Networked connections
� Required if the SV required by a relay are from multiple MU, eg: transformer IED, busbar IED
� Ethernet switch(es) involved, possibility of additional delays and sample jitter; substation-hardened switches required, similar to Station Bus applications.
Interfacing SV to Px4x
-9-2LE
MiCOM Px4xProcess Bus Applications
� Networked connections - redundancy
� If required, network redundancy for SV may be achieved by external devices such as a RedBox.
� The GOOSE / Station Bus interface does provide network redundancy (proprietary – SHP, DHP; open : RSTP, PRP)
Interfacing SV to Px4x
LAN A
LAN B
MiCOM Px4x Process Bus Applications
-9-2LE Interface Features: LN Assignment
� Upto 8 Logical Nodes available for flexible assignment of Sampled Values
� Number of MU’s may varydepending on substation layout and customer preferences
� Analogue input groups as in conventional relay
P446 Configuration
MiCOM Px4x Process Bus Applications
Interfacing SV to IED – Eg: Transformer Protection
P645
HV+LV+TV
Logical Node
HV Current 1
Logical Node
HV Current 2
Logical Node
LV Current
Logical Node
TV Current 2
Logical Node
TV Current 1
Scope
Digital Substations & Process Bus Overview Page 3
MiCOM IEDs for Process Bus Page 21
Px4x -9-2LE Interface Features Page 31
Process Bus Architectures Page 47
Testing, Conclusion Page 60
Presentation title - 01/01/2010 - P 31
Processing SV – Eg. P446
CT / VT
Input Module
IA, IB, IC
VA, VB, VC
Analog
Inputs48 samples /
cycle
IA (k), IB (k),
IC(k)
VA(k), VB(K),
VC(k)
80 samples /
cycle
Px4x with -9-2LE board
IEC 61850
Merging
Unit
-9-2LE
Interface
Board 48 samples /
cycle
IA, IB, IC
VA, VB, VC
Analog
Inputs
IA (n), IB (n),
IC(n)
VA(n), VB(n),
VC(n)
IA (n), IB (n),
IC(n)
VA(n), VB(n),
VC(n)
Relay CPU/
Co-processor
Relay CPU/
Co-processor
Px4x with analog inputs
MiCOM Px4x Process Bus Applications
The Px4x -9-2LE interface conditions the SV to enable reuse of
tried and tested protection algorithms
MiCOM Px4x Process Bus Applications
-9-2LE Interface Features: SV Synchronisation
� Setting for global/local synch for SV received� Adapt relay to functional requirements of the protection scheme� Common setting for all functions enables in the relay
Eg: P446 receiving SV from AMU1 (voltage) and AMU2 (current)
Case 1: Both AMU1 and AMU2 have common source of time sync, Local Sync setting is sufficient
Case 2: Time sync sources for AMU1 and AMU2 are different, Global Sync setting is required
AMU : Analogue Merging Unit
ESW : Ethernet switch
AMU 1
AMU 2
ESW
Presentation title - 01/01/2010 - P 33
MiCOM Px4xProcess Bus Applications
� Time alignment of SV frames is necessary, and ensures correct operation of protection functions dependent on multiple MU’s� The number of MU’s may change depending on site
requirements and customer preferences
� Delays arise from
� Merging Units, due to processing
� Network, depending on its configuration and switches
� SV alignment by MU Delay setting
AMU 1
AMU 2
AMU 3
ESW
AMU : Analogue Merging Unit
ESW : Ethernet switch
-9-2LE Interface Features: SV Alignment
Presentation title - 01/01/2010 - P 34
MiCOM Px4xProcess Bus Applications
Case 1: Relay with
1 MU
Case 2: Relay with
2 MU
Case 3: Relay with
2 MU
MU Delay: Relay setting,
indicates worst case relative
delay expected in receiving
SV from all MU’s linked to
the relay
In this case, no delay
between SV frames from
MU#1 and MU#2
In this case, there is a 1ms
delay between SV frames
from MU#1 and MU#2
-9-2LE Interface Features: SV Alignment
MiCOM Px4x Process Bus Applications
-9-2LE Interface Features
� Security against loss of SV
� Setting for SV Loss Rate� Loss rate evaluated per LN� Related protection functions blocked if Loss Rate exceeds the set value
� SV communication network statistics to facilitate commissioning, network monitoring and troubleshooting
� LNx Loss Rate Sec (x: 1….8)� LNx Frame Loss Cuml (x: 1….8)� LNx Error Sec (x: 1…..8)
MiCOM Px4x Process Bus Applications
-9-2LE Interface Features : Test Mode
� IEC 61850-9-2LE test mode aware
� Facilitates testing and commissioning� Common setting for all Logical Nodes
Test Blocked: All SV with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection
functions and issues a ‘9-2 Sample Alarm’.
Test Ignored: All SV received with an IEC 61850 Test flag are treated as good, protection functions remain active.
Test Only: All SV with an IEC 61850 Test flag are treated as good. Any channel data received without the Test flag
are treated as invalid. The IED blocks relevant protection
functions and issues a ‘9-2 Sample Alarm’.
MiCOM Px4x Process Bus Applications
Enhanced GOOSE Capability
� The -9-2LE relay models have more configurable GOOSE inputs / outputs comparable to standard relays
� Facilitates full Process Bus implementation
Standard Px4x Px4x with -9-2LE
MiCOM Px4x Process Bus Applications
MiCOM P446 v72
� Distance protection with -9-2LE interface
� Configurable for single or double current (three-phase) inputs, thus covering P443 and P445 applications
� Enhanced -8-1 GOOSE count compared to P446 with analogue inputs, facilitates full Process Bus implementation
� Channel-aided schemes with standard distance relays at remote end – no need to retrofit -9-2LE at both line ends
MiCOM Px4x Process Bus Applications
MiCOM P841 v72
� Line terminal IED with -9-2LE interface
� Autoreclosing and circuit breaker failure for one or two breakers
� Configurable for single or double (three-phase) current inputs, covering P841A and P841B applications
� For backup overcurrent / earth fault applications where -9-2LE interface is called for
� Enhanced -8-1 GOOSE count compared to P841 with analogue inputs, facilitates full Process Bus implementation
A
B
C
LD1
LD2
BUS A
BUS B
MiCOM Px4x Process Bus Applications
MiCOM P546 v72
� Current differential protection with -9-2LE interface
� Functionally equivalent to P546 v57 (with CT/VT inputs)
� Configurable for single or double (three-phase) current inputs, covering majority of P543, P544 and P545 applications
� Application requires GPS synchronisation (1PPS) on all relays in the current differential scheme
� Enhanced -8-1 GOOSE count compared to P546 with analogeinputs, facilitates full Process Bus implementation
MiCOM Px4x Process Bus Applications
MiCOM P546 v72
� Current differential schemes in ‘mixed mode’ combining -9-2LE relays and those with analogue inputs
MiCOM Px4x Process Bus Applications
MiCOM P645 v11
� Transformer protection with -9-2LE interface
� Functionally equivalent to P645 v03 (with analogue inputs)
� Configurable for uptofive sets of (three-phase) current inputs, covering P642 (two-winding) and P643 (three-winding) applications
� Enhanced -8-1 GOOSE countcompared to P645 with analogue inputs
-9-2LE
-8-1
MiCOM Px4x Process Bus Applications
MiCOM P746 v11
� Centralised busbar protection with -9-2LE interface� Functionally equivalent to P746 v03 Note: Three-box mode is not available in the -9-2LE relay
� Enhanced -8-1 GOOSE count compared to P746 with analogue inputs, facilitates full Process Bus implementation
MiCOM Px4x Process Bus Applications
Common (platform) features
� Interoperable : Implementation of SV interface as per IEC 61850-9-2LE Guideline for 80 samples/cycle
� All the -9-2LE relays are built on the latest M-hardware (XCPU3)
� Ease of Configuration: -9-2LE parameters are part of the relay setting (.set) file
� Cybersecurity: Features as per current MiCOM implementation
� Redundancy: Option for -8-1 GOOSE , Parallel Redundancy Protocol implementation
MiCOM Px4x Process Bus Applications
Cortec/Ordering
� All -9-2LE relays are on M hardware only
� Option for -9-2LE in CORTEC for P446, P546, P645, P746, P841
� IEC 61850-8-1 port / protocol options are the same for relays analogue inputs or -9-2LE inputs
� Important: P594 is mandatory for ALL P546 relays in a current diff scheme
P594 version D
Scope
Digital Substations & Process Bus Overview Page 3
MiCOM IEDs for Process Bus Page 21
Px4x -9-2LE Interface Features Page 31
Process Bus Architectures Page 47
Testing, Conclusion Page 60
Presentation title - 01/01/2010 - P 47
IEC 61850 Process Bus
� Main 1, Main 2, BCU
� Individual CT cores per IED
� Independent tripping paths for Main 1 and Main 2 typically
CB
Status &
Trips
Conventional Bay Protection & Control – Example
Presentation title - 01/01/2010 - P 48
DM
U#
1
-8-1 PRP
AM
U #
1
-9-2LE
DM
U#
2
-8-1 PRP
AM
U #
2
-9-2LE
AM
U #
3
-9-2LE Process Bus
(conceptual)
Digital Bay - Typical� Main 1, Main 2, BCU
� AMU, DMU
� Ethernet links and switches
� Time synch eqpt
MiCOM Px4x Process Bus Applications
CB
H xxx
H xxx
P594
E
D
A
B
C
A
B
C
D
E
MiCOM Px4xProcess Bus Applications
Digital Bay – DetailedArchitecture
� Merging Units - AMU, DMU
� Time synch by 1PPS
� Redundancy for binary I/O
CB
AM
U #
1
-9-2LE
P594A
MU
#2
-9-2LE D
AM
U #
3
-9-2LE
A
B
C
BC
U
-9-2LE
I/O Card
Ma
in 2
-9-2LE
I/O Card
Ma
in 1
-9-2LE
I/O Card
A
B
C
D
MiCOM IEDs for Process Bus ApplicationsPossible migration strategy
Physical
Wiring
Retain all existing DC wiring
Change only CT / VT interface
Presentation title - 01/01/2010 - P 51
Process Bus ArchitecturesAdditional Info
SGCC China
Process Bus ArchitecturesAdditional Info
National Grid UK - Under Discussion
Concerns
- Reliability of Sampling Sync
- Inter-bay Process Bus
Process Bus ArchitecturesAdditional Info
Extracts from recent ‘Big Red’ paper*
� Five typical Process Bus architectures compared in relation to multiple criteria
� Criteria chosen� Reliability and availability � Cost : Initial investment + maintenance cost� Performance: Average network load, worst case transmission delay
* A Quantitative Evaluation of IEC61850 Process Bus Architectures
Jean-Charles Tournier & Thomas Werner,
ABB Corporate Research
Process Bus ArchitecturesAdditional Info
Extracts from recent ‘Big Red’ paper*
* A Quantitative Evaluation of IEC61850 Process Bus Architectures
Jean-Charles Tournier & Thomas Werner,
ABB Corporate Research
Main 1, Main 2, BCU
AMU x 1, DMU x 1
Switch x 1
Fibre links
Copper links
Main 1, Main 2, BCU
AMU x 2, DMU x 2
Switch x 2
PRP on all IEDs
Process Bus ArchitecturesAdditional Info
* A Quantitative Evaluation of IEC61850 Process Bus Architectures
Jean-Charles Tournier & Thomas Werner,
ABB Corporate Research
Extracts from recent ‘Big Red’ paper*
Fibre links
Copper links
Main 1 with BCU, Main 2 with BCU
AMU x 2, DMU x 2
Ring with RSTP on all IEDs
Alt. Ring with HSR on all IEDs
Main 1, Main 2, BCU
AMU x 2, DMU x 2
Ring with RSTP on all IEDs
Alt. Ring with HSR on all IEDs
Process Bus ArchitecturesAdditional Info
* A Quantitative Evaluation of IEC61850 Process Bus Architectures
Jean-Charles Tournier & Thomas Werner,
ABB Corporate Research
Extracts from recent ‘Big Red’ paper*
Main 1 with BCU per bay
Main 2 with BCU in common IED
AMU x 1, DMU x 2
RB: HSR Red Box
QB : HSR Quad Box
Extracts from recent ‘Big Red’ paper*
* A Quantitative Evaluation of IEC61850 Process Bus Architectures
Jean-Charles Tournier & Thomas Werner,
ABB Corporate Research
Process Bus ArchitecturesAdditional Info
Extracts from recent ‘Big Red’ paper*
* A Quantitative Evaluation of IEC61850 Process Bus Architectures
Jean-Charles Tournier & Thomas Werner,
ABB Corporate Research
Process Bus ArchitecturesAdditional Info
Notes: � Only component costs considered; engineering, testing and commissioning
may have significant impact. � Project specifications (eg: number of MUs per bay, protection operating
time) may become the deciding factor for architecture � Primary plant technology may lead to alternative conclusions
Scope
Digital Substations & Process Bus Overview Page 3
MiCOM IEDs for Process Bus Page 21
Px4x -9-2LE Interface Features Page 31
Process Bus Architectures Page 47
Testing, Conclusion Page 60
IED (SV
Interface)
V I
Ethernet
Switch
PC
Ethernet
GOOSE
and SV
GOOSE
and SV
Trip
IEC 61850
Test Kit
IED Conventional
Trip
� Testing of -9-2LE relays require test kits with capability for
� Send / receive GOOSE
� Generate SV– one or more logical nodes
� Display Sampled values
� Time synchronisation
� Testing may also call for Ethernet switches, Time sync source
Set-up for comparing performance of IEDs
- Standard vs -9-2LE
MiCOM Px4x Process Bus Applications
IED Testing
MiCOM Px4x Process Bus Applications
Customer Benefits
� Eliminate or reduce significantly the use of copper in secondary circuits
� Fibre optic replaces copper� Enhances operator safety� Eliminates EMI on secondary cabling
� Delinks data acquisition (currents, voltages) from signal processing / algorithms � Potential for reduced shut-downs for refurbishment� Relays (algorithms) may be upgraded independent of
acquisition
� Easier integration of sensors into smart grid solutions
GRID
http://www.alstom.com/grid/sas/