mice hydrogen safety functions iec61508 compliance & emergency procedures mice safety review...

13
MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

Upload: leo-owens

Post on 12-Jan-2016

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

MICE Hydrogen Safety Functions

IEC61508 Compliance & Emergency Procedures

MICE Safety Review Meeting4th Oct 2011PJ Warburton - Daresbury Lab

Page 2: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

IEC 61508• Functional Safety of electrical / electronic /

programmable electronic safety – related systems• Functional safety is part of the overall safety that

depends on a system or equipment operating correctly in response to its inputs

• Neither safety nor functional safety can be determined without considering the systems as a whole and the environment with which they interact

• Safety – The freedom from unacceptable risk of harm

mh78
I've edited 3rd bullet - assume this is what you meant?
Page 3: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

SIL Rating• Tolerable Risk 10-5 Fatalities per

Year From RAL Safety• How Safe is H2 System

10-4 10-3 10-2

SIL 1PFD 10-1

SIL 2PFD 10-2

SIL 3PFD 10-3

Page 4: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

IEC 61508 Compliance Process

• LOPA Study conducted Nov 2010 based on HAZOP Report from Serco June 2006

• Panel consisted of representatives from FSC, MICE project at RAL & DL and RAL Safety

• Identified 2 Systems requiring SIL Functions

• Plus 2 to be considered but not requiring formal SIL Ratings

Page 5: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

SIL Rated Safety Functions• Following LOPA study the following events were

found to require SIL rated safety systems

• Buffer Tank Over Pressure• Leading to a release of hydrogen and ignition

leading to multiple deaths

• Build up of impurities in Cryostat (Ins Vac)

• Build up of impurities over a period of time, pressurisation and heating of hydrogen leading to a rupture & Explosion leading to multiple deaths

Page 6: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

Not Quite SIL Rated• Following LOPA study the following events were

found Not to require SIL rated safety systems

• Hydride Bed Over Pressure• Over heating of Metal Hydride Bed Leading to a

release of hydrogen and ignition leading to multiple deaths

• Temperature Rise in Absorber Volume• Causing pressurisation and heating of hydrogen

leading to a rupture & Explosion leading to multiple deaths

• Same outcome as Buffer Tank Over Pressure

Page 7: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

Buffer Tank Over Pressure

• Build up of pressure causing leaks in pipework and Hydrogen to escape

• SIL 1 Required PFD 1.00E-01 (1 out 10)• Solution detect the H2 before it reaches explosive

levels• Install a gas Detection System alarm 50% LEL• 2 Detectors / Beacons per location on separate loops• Detection system subject to annual checks• PFD Achieved 1.51E-02 (<2 out 100) = SIL 1• PFD = Probability of Failure on Demand• H2 LEL = 4%

Page 8: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

SIL Block Diagram

Page 9: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

Build up of impurities in Cryostat (Insulation

Vacuum)• Over time Cryostat insulation vacuum may build

up impurities. - O2 Leaking In – H2 Leaking Out • Depending on Temperature / Pressure an

Explosive atmosphere may form• Temp & Level Sensors are Ex i• Heaters are not so operation needs to be

prevented if vacuum is not good – below 10-3

Page 10: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

Build up of impurities in Cryostat (Insulation

Vacuum)• SIL 2 Required PFD 6.73E-03 (~7 out 1000)• Solution interlock heater power supply• Use 1 Set Point on existing Vac Gauge & Controller• Additional Set Point from new Vac Gauge &

Controller• Guard Line A & B Relays to turn of heater power

supply Hardwired I/L• Guard Line A & B inputs also into PLC for Software I/L• PFD Achieved 3.76E-03 (~4 out 1000) = SIL 2

Page 11: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

SIL Block Diagram

Page 12: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

Emergency Actions

• Return hydrogen to Bed if possible• Vent hydrogen to atmosphere via vent

line• IF PLC goes off

– Vacuum pumps stay on– Hydride Bed set to ‘chill’

Page 13: MICE Hydrogen Safety Functions IEC61508 Compliance & Emergency Procedures MICE Safety Review Meeting 4 th Oct 2011 PJ Warburton - Daresbury Lab

Questions