McKinley Avenue CNG Project
Columbus, OHIOMcKinley Avenue CNG StationRLBA 7962
03.07.2013CNG STATION OPTION E.2
Mechanical & Electrical Upgrades
HVAC Systems• Systemsaredesignedforcomfortcontrol,safetyoperation,
andareconstructedandcontrolledtobesafeforuseinafacilitywithnaturalgasstorage.
• Theoriginaltwoboilerheatinghotwatersystemhasbeenreplacedwithaneightboilersystemtoallowforhighefficiencyoperationthroughouttheheatingseason.Toimproveefficiencyduringtheshouldermonths,twocondensingboilersareincludedinthesystemallowingforuptoveryhighefficientoperation.
Gas Detection Monitoring• Anewgasdetectionmonitoringsystemhasbeenprovided
toallowfortheventilationrequirementstobeadjustedforenergysavingswhileprovidingdetectionnecessarytoventilateandexhaustshouldtherebeanaturalgasreleaseinsidethebuilding.
• Systemincludesapproximately360sensorslocatedthroughoutthegarageandmaintenancefacility.
• Sensorsareaninfraredtechnology.
Building Automation System• Abuildingautomationsystemhasbeenprovidedtoallow
forcompletecontrolandmonitoringofallequipment.
• Systemutilizesanopen(BACNet)protocolallowingforflexibilityandinteroperabilityinthefuture.
Electrical and Lighting• LightLevels:
• OriginalLightLevels10-15FCinthebusstorageareaand10-30FCinthebusmaintenancearea.
• NewLightLevels25FCinthebusstorageareaand50FCinthebusmaintenanceareas.
• ElectricalLoad:Approximately10.4W/SFfortheGarageandMaintenancefacility.
• Roughly1,200lightfixtures,Roughly30milesofconduit,andRoughly170milesofwiring
Featured LEED Credits• SustainableSites:Credit4.3AlternativeTransportation-
Low-EmittingandFuel-EfficientVehicles
• EnergyandAtmosphere:Credit1OptimizeEnergyPerformance
• Materials:Credit1.1BuildingReuse-Maintain50%ofInteriorNon-StructuralElements
• Materials:Credit2ConstructionWasteManagement
• Materials:Credit5RegionalMaterials
• IndoorEnvironmentalQuality:Credit7.1ThermalComfort-Design
Designing to Meet USGBC LEED Silver Requirements
LightingUpgradeAirHandlingUnit
RenovationandCompressedNaturalGas(CNG)FuelingProject
CNGStorageVessels
CompressorPlant
Schematic-CNGCompressing/FuelingStation
General Description of Facility COTA’sMcKinleyAvenuefacilityisa400,000squarefootfixed-routebusoperation,storageandmaintenancefacilityandhasindoorstoragecapacityfor240large40’buses.Inaddition,thefacilityhousesRadioroomoperations,theCustomerServicecallcenter,ITdatacenter,andadminis-trativeofficesforSecurity,Safety,VehicleMaintenanceandFacilityMaintenancesupportstaff.Thebuildingwascon-structedin1980andisinneedofsignificantupgradeandrenovationtobringthefacilityintoastateofgoodrepair.
Twoyearsago,COTAcommittedtoconvertingitsfleettocompressednaturalgas(CNG)vehicles.Thiscommitment,basedonbothenvironmentalandeconomicfactors,willre-sultinairqualityimprovementandsubstantialreductioninoperatingfuelcosts.Toadvancethisdecision,COTAwillconstructaCNGfuelingstation.TheMcKinleyAvenuefa-cilitywillbethesiteofCOTA’sinitialCNGfuelingstation.InadditiontoconstructingtheCNGstationCOTAwillberequiredtorenovatetheinterioroftheMcKinleyAvenuefacilitytoaccommodatethesevehicles.
Ultimately,thefacilitywillberenovatedto“likenew”con-ditionwithCNGcomplianceandanticipatedLeadershipinEnergyandEnvironmentalDesign(LEED)Silvercertifica-tion.LEEDdesignandconstructionwillresultinlowerlong-termoperatingcostsandanenvironmentallyfriendlybuilding.
InApril2013,COTAtookdeliveryofit’sfirstCNGcoach-es.Aspartofanewfive-yearcontractwithGilligCorpora-tion,COTAwillpurchaseupto30CNGbusesayear.Theaverageservicelifespanofatransitbusis12yearsanditisanticipatedthatCOTA’sentirefleetwillbeCNGbusesby2025.
Inviewoftheprojectedcostofnearly$75millionassociat-edwithacompleterenovationoftheMcKinleyfacilityandtheneedtosecurefunding,COTAhasdecidedtoapproachthisprojectinphases.InPhaseI,COTAfocusedmainlyonimprovementsofsafetyelementswhichincludedreplace-mentofall(32)busliftsandcriticalsupportequipmentinheavymaintenance.PhaseIIoftherenovationproject
beganin2012andisscheduledforcompletioninApril2013.Thetotalprojectedcostforthisphaseoftheprojectis$31,500,000.
PhaseIIrenovationsconsistofprovidingaCompressedNaturalGas(CNG)FuelingStationfortheeventualfleetconversiontoCNG-fueledbusesandnon-revenuevehicles.Therenovationelementscanbedividedintotwospecificcategories,(1)interiorrenovationstoupgradethefacilitytoreceiveCNGvehiclesand(2)CNGfuelingsystem.
The McKinley Avenue Renovation included the follow-ing:
• Additionoftheexteriorfuelingislandsthatincludesfourfuelinglanesandonebypasslane.
• AdditionofanewCNGbuildingforlineupofficeroom,futurecashroom,utilityroom,storageroom,restroomandMechanical/Electricalrooms.
• AdditionofanewCNGcompressorplant.• AdditionofanewGenerator.• Re-configuredparkingarea.• UpgradedmechanicalsystemsasrequiredbyNFPA.• Upgradedmaintenanceandbusstorageareastomeet
ClassIDivisionIIasrequiredintheNFPA30AChap-ter12andChapter8.
• Re-configuredbusrouteandadded/replacedallover-headdoors.
• Cleanedandpaintedtheroofofthemaintenanceandbusstorageareas.
• Replacedalllightinginthemaintenanceandbusstor-ageareas.
CNGFueling
CNG Compressor Plant• LargestCNGstationcurrentlyinuseinOhio.• Designedforamaturefleetofupto250buses.• Buseswillfuelin5to6minutesonaverage.
Mainstationcomponents:1. Onetwintowermanuallyregenerated
desiccantCNGdryer—manufacturedbyPSBinPennsylvania.
2. Four400Hp5stagereciprocatingcompressors.Oneofthefourcompressorsisprovidedtoensureredundancyintheeventofabreakdownononecompressor.Compressorsoperatewitha20psigsuctionpressureandamaximumdischargepressureof4500psig.CompressorsblocksaremanufacturedbyArielCorporationofMountVernon,OHandpackagesfabricatedbyANGIEnergyinWisconsin.
3. Twelve5500psigASMEstoragespherescontainingatotalvolumeofapproximately140,000standardcubicfeetofCNG.StoragemanufacturedbyJWinTexas.
4. ThreehighflowCNGdispenserswithlightandheavyvehiclehoses.Thesedispensersworkwith4valvepanels(oneateachcompressor)andonestoragemountedpaneltodirecttheflowofgastooptimizefillspeed.DispensersystemmanufacturedbyANGIEnergyinWisconsin.
5. ProgrammableLogicController(PLC)basedcontrolsystemandallmotorcontrolgearishousedinaprefabricatedcontrolroom.ThissystemmanufacturedbyANGIEnergyinWisconsin.
6. StandbygeneratorandAutomaticTransferSwitchtoprovidesufficientpowertopowertwocompressorsduringanoutage.
CNG Fueling Station• BypassLaneforcashdropandtirepressurecheck• 4fuelinglanes–ofwhichlane4willultimatelyhave
bothCNGanddiesel• Eachofthe4fuelinglanesalsohasvehiclefluids(en-
gineoil,transmissionoil,coolant,windshieldfluid)fortoppingoffduringfueling
• Canopyhasinfraredheatersforthewintermonths• Canopyareahasin-slabhotwaterheatingsystemto
eliminateiceandsnowduringwintermonths• CNGbuildinghasanofficeforthehostlers,arestroom,
storagerooms,aluberoomandmechanicalspaces
Natural Gas Line Upgrade• Servicewasupgradedfroma6”toa8”main.Medium
pressureservicehasanaveragepressureof25psi.Columbiagasguarantees10psi.
SitePlan