Islamic Republic of AfghanistanMinistry of Communication and IT (MCIT)

Amendment 1to

STANDARD BIDDING DOCUMENTS (SBD)

ForDesign, Equipment Supply and Installation of Disaster Recovery Site (DR site) for Ministry

of Communication and Information Technology (MCIT)

MCIT/96/ICB/G-02

1

Page 2: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Overview

Ministry of communication and IT is decided to bring some changes Based on announced project of Design, Equipment Supply and Installation of Disaster Recovery Site (DR site) for Ministry of Communication and Information Technology (MCIT) for better designing of the project and the infrastructure of mentioned site to fulfill the requirements discussed further by the expert team members of the MCIT. The changes will be adding and removing of some equipment along with its specification mentioned in the table below. it’s requested from all the bidders to follow the amendment and update themselves with new requirement.

Bellow items are changed and removed from the list of goods and equipment

Item 16: quantity of the racks changed from 5 to 1

Item 21: private cloud appliance is replaced to 8 compute node

Item 20: two servers removed from the list of goods and equipment

Item 7: Power cabling is changed from 25 to 4 rack and avr cable changed to 5x50 DB to UPS

item 1: quantity is one UPS of 90 kva

maintenance is required for one year.

below specification is new and complete to be followed.

Standard Data Center Component

S.No Product Description

1.00 UPS Power System - with 30 minutes backup at Full Load (Emerson/Vertiv ) 1

Capacity : 90 Kva MODULAR system

Input characteristics should include the following

Nominal voltage - 400 V three-phase + N (380/415 selectable)

2

Page 3: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

input voltage qualification windows @ 1.0 output PF without battery discharge - 478 to 305 V @ 100% load , 304 to 228 V @ 70 % load

Nominal frequency (Hz) - 50 (60 Hz selectable)

Tolerance on frequency (%) - 40 Hz to 70 Hz

Input P.F. @ nominal voltage and load > 33% (-) - > 0.99

Total harmonic distortion (THDi) @ full load (%) - < 5%

Inverter output characteristics should include

Nominal voltage - 400 V three-phase + N (380/415 selectable)

Nominal frequency (Hz) - 50 (60 Hz selectable)

Automatic adjustment of nominal output active power as a function of temperature

@ 30°C (%) -100

@ 35°C (%) - 90

@ 40°C (%) - 80

Output voltage stability in steady-state (5) - ± 1

Output stability in dynamic conditions for 100% load step variations (%) - Complies with IEC/EN 62040-3, Class 1

Load crest factor without derating (-) - 3:1

Output voltage distortion with 100% linear load (%) - <1

Output voltage distortion with non-linear load as specified by IEC/EN 62040-3 (%) - <4

Output frequency sync. window with bypass (%) - Nominal ± 10%

Output frequency stability with internal clock (%) - ± 0.02

Frequency slew rate (Hz/sec) - <1

Permitted overload:

. for 60 minutes (%) - 105 (APM 30-150 kW)

. for 60 minutes (%) - 110 (APM 120-300 kW)

. for 60 minutes (%) - 125

. for 60 minutes (%) - 150

Three phase short circuit current for 200 ms (%In) - 310% (APM 30-150 kW)

Three phase short circuit current for 200 ms (%In) - 340% (APM 120-300 kW)

UPS characteristics should include the following

Noise level @ 1 meter and @ 100% load according to ISO 3746 (dBA) - <62 dBA (APM 30-150 kW)

3

Page 4: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Noise level @ 1 meter and @ 100% load accoring to ISO 3746 (dBA) - <65 dBA (APM 120-300 kW)

Neutral current rating; (x nominal) - 1.7

AC/AC efficiency

– Double conversion mode @ 100% load (%) - 95.4

– Double conversion mode @ 66% load (%) - 95.7

– Double conversion mode @ 33% load (%) - 95.1

Maximum UPS cabinet dimensions WxHxD (mm) - 600x1996x1100 (APM 30-150 kW)

Maximum UPS cabinet dimensions WxHxD (mm) - 1200x2000x1100 (APM 120-300 kW)

Degree of protection - IP 20

Frame color - ZP-7021

Characteristics of electronic static changeover switch

Nominal voltage (V) - 400 (380/415 selectable)

Tolerance on voltage for qualification (%) - Nominal ±10%

Manufacturer authorization for the product supply and availability of trained resources on ground is a must

Nominal frequency (Hz) - 50 (60 Hz selectable)

Tolerance on frequency for qualification Permitted overload: (%) - Nominal ± 10 (± 20% selectable)

Continuous (%) - 110%

100ms (5) - 1000%

Classification according to IEC/EN 6062040-3 (N/A) - VFI-SS-111

EMC compatibility as per EN 62040-2 - Class C2

Certifications Safety : IEC60950-1, IEC 62040-1-1/AS62040-1-1,

1.10 Battery System : 40

  Battey Should support the load of UPS for 30minute at 80% load. 40 battery

Battery should be state of Art AGM VRLA type

Design life should be atleast 12 Years

4

Page 5: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

External battery bank without enclosure

Along with required circuit protection system

 

Nominal Voltage -12VRated Capacity- 125Ah (10 hour rate) to 1.80V/cell @25OC(77OF)

Internal resistance- Approx 5.7mΩTemperature range - Operation(maximum): -40C to 55C(-40F to 131C)

Operation (recommended): 15OC to 25OC(59F to 77F) Storage: -20C to 40C(-4F to 104F)

Float voltage- 2.25V/cell@25OC(77OF)Recommended Maximum charging current- 31 | 25A

Equalize and Cycle Service- 2.35V~2.40V/cell@25OC(77OF)Self Discharge- The residual capacity is above 90% after 90 days storage(25C/77F)

Temperature Ranges- M6 FemaleTerminal Hardware Torque- 10 ± 1.0Nm

Container Material -ABS (V0 optional)

 

2.00  Diesel Generator 1

The generator should having output power 125KVA/equivalent with frequency of 50 Cy/sec

KIRLOSKAR 125KVA / 100KW DG sets – Water Cooled Silent Diesel Generator SetPrime Rating at rated rpm ( as per ISO8528)1 kVA 125

kW 100Genset Model KG1- 125WS

Frequency Hz 50Power factor lagging 0.8

Voltage V 415 3ØGoverning class (As per ISO 8528 Part-V) G3

Noise level dBA < 75Fuel Consumption* At 100 % Load Ltrs/hr 27.4

At 75 % Load 20.2At 50 % Load 15.3

Fuel tank capacity Ltrs 230Overall dimensions of genset (L x W x H)^ mm 3200 x 1300 x 1795

Dry weight of genset with canopy (approx..)^ Kg 2090Wet weight of genset with canopy (approx..)^ Kg 2290

Electrical Battery starting voltage Volts-DC 12ENGINE

Engine Model 4K1080TA G2Rated output (Prime Continuous rating as per

) kW 114.7HP 156

5

Page 6: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

No. of cylinder Number 4Cubic capacity 2 Ltrs 4.32

Bore x Stroke mm 105 x 125Rated Speed RPM 1500Aspiration NA/TC/TA TA

Lube Oil change period hrs. 500Lube oil Sump Capacity Ltrs 18

Coolant Capacity Ltrs 21

ALTERNATOR Insulation Class - Class H

Alternator Efficiency (at 100% load) 0.8 pf** % 92.5Max Voltage Dip at Full Load 0.8 pf Lag sec < 20%

Max Time to build up rated voltage at Rated RPM- < 5 secprovided engine reach the rated speed < 5 sec

With Jacket water heater system

Digital Display based

Latest technology

3.00 FM 200 for the Datacentre - specification as follows ( L-11.8 x W-8.2 x 4.1) meter for Data Centre

1

3.10 FM 200 for the Power room -specification as follows L-5 x W-4 x H-4.1)Meter 1

The proposed system should have “double knock” control system for the discharge of gas in case of any emergency;

The FM200 cylinder should have its own built-in pressure safety relief valves and shall also be equipped with pressure gauge to indicate the pressure of its content.

The FM200 should protect individual zone. Each zone should cover the above false ceiling layer and under raised floor layer.

The proposed solutions should also have warning light and warning signs in case of any emergency.

The proposed solutions should meet the requirement of international standard, manufacturer’s specification and also to meet the local law.

6

Page 7: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

HFC-227ea® CLEAN AGENT FIRE SUPPRESSION SYSTEM

AGENT STORAGE CONTAINER: HFC-227ea®

FEATURES• Pressure Vessel to hold agent until activated.

• Container Super – Pressurization Level360 psig at 70°F (24.8 bar at 21°C)

after filling with dry nitrogen• Container Rating

DOT 4BW500TC 4BWM534

• Container Actuation Methods*Electric / Pneumatic / Manual

IMPULSE VALVE

FEATURES• The 1” & 3” Impulse Valves are a rupture disc (metal

diaphragm), pressure operated device that allowsthe agent to be released from the container andinto the protected enclosure via the associated

piping network and discharge nozzle(s).• Agent Discharge Port allows agent release fromcontainer and also fulfills the pressure relief valverequirements in accordance with DOT regulations.• Agent Fill Port used to fill (refill) and pressurizethe container and also used for the Low Pressure

Switch.• Actuator Port used to connect an Impulse Valve

Operator (IVO) with Manual Strike Button forelectric and manual actuation of the container oran Impulse Valve Pneumatic Operator (IVPO) for

pneumatic operation.

IMPULSE RELEASE MODULE

FEATURES• The Impulse Releasing Module provides theprimary interface between the supervised releasingcircuit(s) of a NAFFCO fire suppression system andthe

Impulse Valve Operator (IVO); which is used torelease the fire suppressant agent from an impulsevalve container.

Impulse Release Module should be of the following specifications:

CURRENT CONSUMPTION - +24V Supervisory:20.0 ma (during capacitor charging), 3.0 ma (after capacitor is charged)

-24V Activated:

7

Page 8: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

-37.0 ma (LED active)

Temperature - 32°F to 130°F (0° to 54.4°C), 93% maximum humidity

COMPATIBLE ACTUATIONDEVICES - NF-02-12728, Impulse Valve Operator (IVO)

COMPATIBLE RELEASINGPANELS - NAFFCO Single Hazard Panel*

LOW PRESSURE SWITCH FEATURES and SPECIFICATIONS

• Continuously monitoring the container pressurefor a low-pressure condition. If the pressure inside

the container drops below 288 psig (1986 kPa),the switch contacts will transfer and invoke a“supervisory” indication on the control panel.

• Installed in the fill port on the container with anImpulse Valve.

• Can be installed when the container is chargedwithout the concern of agent/pressure loss

DISCHARGE NOZZLES

FEATURES• The discharge nozzle size refers to the size of

schedule 40 or 80 pipe that it can be connected to.• The discharge nozzle is mounted to allow the agent

to be discharge on a horizontal axis.• The nozzle orifice area is determined be

performing a hydraulic calculation using theNAFFCO Engineered Flow Calculation program.

• Nozzle should not be ordered until the clean agentsystem pipe network is installed and an “As Built”

hydraulic calculation is performed.• Nozzle orifice drilling must be done at NAFFCO

factory.

Single Hazard Panel 2⁄2

• Microprocessor-controlled.• Power-limited on all circuits except powerconnections (P1).• Four operational modes:• Local piezo with distinct event tones.• Reset switch.•

Audible silence switch.• Disable Mode for audible and release circuits, andrelays.

• Selection of 120, or 240VAC power input at 50 or 60hertz.

8

Page 9: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

• Re-settable and non-re-settable special applicationpower output

• Battery/Earth fault supervision.• 7 AH to 40 AH battery options, up to 90 hours

(Factory Mutual) standby.

ENCLOSURE• Steel enclosure 21” high by 14.35” wide by 4” deep

(Back-box dimensions)• Enclosure is equipped with a .50” wide lip to facilitate

flush mounting• Removable door for easy installation• Enclosure is available in Red or Gray.

INITIATING DEVICE CIRCUITS• Up to two Style B initiating device circuits capableof sequential alarm, cross-zone or single detector

release operation with an overall system capacity of50 detectors maximum.

• Three Style B initiating device circuits capable ofmonitoring closed contact devices.

• Optional Class A module that converts all fiveinitiating device circuits to Style D wiring and

operation.

RELEASING CIRCUITS• One Agent Release circuit with maximum of 6

IRM’s• One Solenoid release circuit which can activate one

24V or two 12V solenoids• Model NF-10-063-1 provides option to use both

releasing circuits simultaneously.

RELAYS• General Alarm, Supervisory and Trouble relays• Two Optional CRM4 modules to add eight more

SPDT dry relay contact outputs

 

4.00 Raise Floor System for (130 sq meter). ( L-15.8 x W-8.2 ) with 20 perforated Tiles

The Proposed Raised Floor System panels should be manufactured to a high quality specification using rigidly applied production procedures. Mero Type 6

Flooring systems should independently tested and certified to meet the standards

The interested Bidder should have the site survey to know the exact dimension

Stringers should support each edge of panel.

The Bidder should provide the sample tiles for the verification and approval

Perforated Tiles

9

Page 10: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Dimensions - 600 x 600 mm

Panel thickness (without covering) - ~23 - 39 mm

Panel surface - without coating, galvanized steel sheet

Panel bottom - aluminium foil on request, galvanized steel sheet

System weight (without covering, floor height 1000mm) - ~43 -70 kg/m2

Panel weight - ~14.5 - 23 kg/unit

Panel material - fibre-reinforced calcium sulfate

Substructure

Module - 600 x 600 mm

Pedestal material - galvanized steel

Construction height (without covering) - ~ 55 - 1800 mm

Recommendation - Stringers should generally be used from a finished floor height of > 500 mm

Load values

Concentrated load:

acc. To DIN EN 12825 - Class 1 - 6

Nominal load - 2.000 - 6.000 N (higher loads on request)

Ultimate load - > 4.000 - 12.000 N

Electrostatic:

(independent from system and covering) - > 105 Ohm

Fire protection

Building material class acc to DIN 4102 T1: - A2

Building material class acc to DIN 13501 T1 - A1

Fire resistance class acc. To DIN 4102 T2 - F30 oder F60 (depending on system and covering)

Thermal conductivity

Base material - ~ 0, 44 W/mk

Acoustic values (New denomination acc. to DIN EN)

Sound reduction index R L,w,P - 52 - 58 dB (Normalized flank level difference D n,f,w,P)

Normalized impact sound pressure level L n,w,P - 63 - 40 dB (Normalized flank impact sound pressure level L n,f,w,P)

10

Page 11: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Improvement of sound pressure level red. Δ L w,P - 18 - 35 dB (Improvement of sound pressure level reduction Δ L w,P)

 

5.00

Automatic Voltage Regulator - 120 Kva 1

Power in Kva - 120 Kva

Input Voltage Correction Interval : 275-450VAC

Input Voltage Working Level : 155 to 490 VAC

Input Frequency : 47- 65 Hz

Line input Protection : Overcurrent, Low & High Voltage protection

Output Voltage : 380/400/415 VAC RMS +/- 2 %

Overloading : 10 Seconds for 200% load

Correction Speed : 90Volt Per Second

Output Protection : Should Protect Load by opening the circuit when overburden, short circuit occurs

Working Principle : Servo Motor, Microprocessor Controlled, Fully Automatic

Cooling System : Smart Fan System, Thermostate control based

Measure Value monitor : True RMS panel Voltmeter for output voltage and line voltage monitorization

Efficiency : 95%

Manual Bypass System : Unit should have manual bypass switch to turn ON/Off like Pako Switch

Protection Level : Indoor unit with IP 20 or IP 25

Working Temperature : -10 degree to 50 Degree

Relative Humidity : Less than 90%,DIN (40040)

Working Altitude : Less than 2000 meter

Acoustic Level : Less than 50 dB ( 1 Meter Square)

6.00

Automatic Transfer Switch 1

Automatic Transfer Switch for Dg Vs City Power

Ratings 250Amp

Fully automatic mains failure sensing and generator set start signal

Pre-programmed enabling the panel to run on installation

11

Page 12: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

with the ability to customise if necessary

Fast acting switches reduce transfer times between set andutility power

Automatic and manual operation

Automatically provides generator set start signal upon detection of mains failure, overvoltage or loss of phase

Automatic mains re-transfer function

Manual switch operation possible via external handle

LED functions display showing generator set / mains availability and switch position

LCD display for voltage and timers

6.10

Earthing System

2 Dedicate earthing Pit - one for IT Equipment and one for Power Equipment

Earth resistance should not be more than 3 Ohm

EGB Plate for termination of all earthing point should also be inclusive in this

Provision at earth Pit to fill the water & Cover in case of soil dryness to maintain the resistivity

7.00

Power Cabling

All power cable should be original turkey or equivalent

Cable should not be used by bidder as under rating to the load / equipment requirement

Cable should be having BS standard

All earth cable should be Yellow+Green colour only

Should Be the Vender do cableing for 4 Rack Dual Sources for all Racks with Industrial Sockets

DG to ATS cable , 5x95mm Sq. Cu flexible cable

User's City power panel to ATS input cable, 4x150mm Sq. Cu flexible cable

AVR Input cable, 4x150mm Sq. Cu flexible cable from ATS

AVR Input earthing cable 1x50mm GY, Cu flexible Cable

AVR o/p Cable,4x120mm Sq. Cu flexible cable

ATS Earthing Cable 1x50mm GY, Cu Flexible Cable from earthing PIT

AVR O/p DB to UPS I/p, 5x50mm, Cu Flexible Cable

12

Page 13: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

AVR O/p DB to Stulz AC- 2 units- input Cable , 5x16mm Sq, Cu fleible unarmoud cable

AVR O/p DB to Comfort AC - Power Room, 5x4mm Cu Flexible unarmoud

Power Room Comfort AC outdoor Cable , 5x2.5mm Cu flexible unarmoud cable

UPS O/p DB to 8 no's IT rack in Data Centre, 5x6mm Cu Flexible unarmoud Cable

UPS O/p DB to 10 no's LED lighting , 3x1.5mm Cu flexible unarmoud cable

UPS O/p DB to FM 200, Biomatrix, EMS Sytem, 3x2.5mm Cu flexible Cable

FM200 Wiriing 2x0.75mm Sq. Fire proof, Hard Core Cable

IT Rack Chasis Ground cabling ,1x6mm GY, Cu Flexible unarmoud cable

Additoinal Cable

Battery Cable for UPS Systems, 1x50mm, Copper Flexible unarmoud, Original

Precision Aircondition Input cable, 5x25mm Sq. Copper Flexible unarmoud, Original

Smoke Sensor & FM200 Wire 2x0.75mm Sq., Fireproof, High quality

City Power Cable from the main DB to DC Power Room

8.00

Distribution Panel according to Site requirement

DB for UPS O/p Distribution to critical loads· One DB for AVR o/p to distribute for both UPS I/p, Air condition & other Raw

loads.· One DB with single breaker for AVR I/p supply. DB should be painted powder

paint and Non DC room.

All switchgear should be original one- Legrand or equivalent

All AC supply Panel should be having indication for Power availbility

Copper busbar should be used inside the DB to distribute the power to multiple branches from main incomer breaker in DB

 

9.00 Two Precision Aircondition (Emerson/Vertiv ) 2

AC should be microprocessor control base technology

Maximum cooling performance with minimum floor space

Model should be Air Cool

Specifications

Unit inlet air temperature - 24.0 °C

Unit inlet air relative humidity - 50.0 %

Unit airflow - 11682 m³/h

13

Page 14: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

ESP - 20 Pa

Air flow configuration - Downflow Up

Sea level - 0 m

Refrigerant - R410A

Unit power supply - 400 V/3 ph/50 Hz

Compressor type - Scroll

Expansion valve - EEV

Unit Performances

Gross total cooling capacity - 40.4 kW

Gross sensible cooling capacity - 40.4 kW

SHR - 1.00

Net total cooling capacity - 37.6 kW

Net sensible cooling capacity - 37.6 kW

Off coil air temperature - 13.4 °C

Off coil air relative humidity - 97.6 %

Room SPL (@ 2m, f.f) - 65.8 dB(A)

Supply air temperature - 14.1 °C

Supply air relative humidity - 93.5 %

Unit power input - 11.42 kW

Unit Net Sens EER - 3.30

System power input - 12.52 kW

Internal filter class (EN779 std) - F5

Internal filter air pressure drop - 121 Pa

Coil air pressure drop - 159 Pa

Unit air pressure drop - 477 Pa

Condensing temperature - 47.0 °C

FANS

Quantity - 1 n°

Power supply 400 V/3 ph/50 Hz

Power input - 1 x 2.75 kW

14

Page 15: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Operating Ampere - 1 x 4.53 A

Full load Ampere - 1 x 5.00 A

Locked rotor Amp. - 1 x 0.10 A

Room fan modulation (%) - 100 %

Fan speed - 1307 rpm

COMPRESSORS

Type - Scroll

Power supply - 400 V/3 ph/50 Hz

Power input - 1 x 8.64 kW

Compressors - COP 4.72

Operating Ampere - 1 x 15.68 A

Full load Ampere - 1 x 25.00 A

Locked rotor Amp. - 1 x 118.00 A

Relevant data for each CONDENSER

Condenser model - HCR59

Version - Standard

Air discharge - Vertical

Power supply - 230 V/1 ph/50 Hz

Variex - Yes

Heat load - 49.0 kW

Outdoor air temperature - 35.0 °C

Condenser airflow (@ max speed) - 15600 m³/h

Condenser actual airflow - 15600 m³/h

Max outdoor SPL (@ 5m,f.f.) - 53.0 dB(A)

Actual outdoor SPL (@ 5m,f.f.) - 53.0 dB(A)

Power input - 1.10 kW

Full load Ampere - 5.00 A

Locked rotor Amp. - 9.60 A

Width 2340 mm, Depth 1112 mm, Height 910 mm, Weight 102 kg

15

Page 16: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

10.00 Comfort AC 2

2 Ton Split Air-condition

One for Small Room of Data Centre

One for Power Room

General Features Type Split AC Capacity 2 Ton Functions Cooling Energy Rating 3 Star Dehumidification Yes Performance Features Air Circulation 585 / 1600 CFM

Compressor Rotary Moisture Removal Yes Noise Level (Indoor)(Low) 38 db Other Performance Features Fuzzy Logic, Chaos Logic Modes Dry Yes Cool Yes Auto Mode Yes Other Modes Sleep Mode Filters Anti-Bacteria Filter Yes Other Filters Triple Filter Convenience Features Auto Restart Yes Panel Display Digital On/Off Timer Yes Air

Swing Yes Other Convenience Features Remote Control Power Requirements Power Supply 230V / 50Hz Power Consumption(Cooling) 2100 Watts Running

Current(Cooling) 9.6 Amps Dimensions Indoor (W x H x D) 1090 x 300 x 218 mm Indoor Weight 13 Kg Outdoor (W x H x D) 870 x 655 x 322 mm Outdoor Weight 46 Kg

Additional Features Other Features Blue Evaporator Fin Type, Gold Condenser Fin Type, Jet Cool 

11.00

Camera (AXIS P3224-V MKII)

Continuous 360° pan

Manufacturer authorization for the product supply and availability of trained resources on ground is a must

Excellent light sensitivity

HDTV 720p and 23x optical zoom

Focus recall

Axis’ Zipstream technology

HDTV 720p 25/30 fps with WDR - forensic capture and Lightfinder:Color: 0.19 lux, F1.6:B/W: 0.04 lux, F1.6, 0 lux with IR illumination on HDTV 720p 50/60 fps:Color: 0.38

lux, F1.6B/W: 0.08 lux, F1.6, 0 lux with IR illumination on

IPv4/v6, HTTP, HTTPSa, SSL/TLSa, QoS Layer 3 DiffServ, FTP, CIFS/SMB, SMTP, Bonjour, UPnPTM, SNMP v1/v2c/v3(MIB-II), DNS, DynDNS, NTP, RTSP, RTP, SFTP,

TCP, UDP, IGMP, RTCP, ICMP, DHCP, ARP, SOCKS, SSH

12.00 NVR

AXIS Camera Station S1016 Mk II Recorder or Equivalent

CPU :Intel® Xeon® Processor E5-2609 v3 1.90 GHz, 15MB Cache

RAM :2 x 4GB (8192MB),Memory type: RDIMM 2133MT/s, Dual Rank, x8 Data Width

Number of Channels : 32 Channels Axis Camera Station included

16

Page 17: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Disk Storage : 24 TB (6x4 TB) Enterprise Class HDD (20 TB usable space after RAID) 7200rpm, SATA 6Gb/s , RAID 5. Possible to add 2 additionalHDDaRAID Controller:

PERC H730, 1GB NV Cache

Graphic Card : Matrox 200 eR

Operating System : Microsoft Windows 10 IoT Enterprise

Network Card : On-Board Broadcom 5720 Quad Port 1Gb/s LOM

Recording : Qualified for recording up to 64 video channels with a total recording rate up to 512 Mbit per second.

Power : Dual, Hot-plug, Redundant Power Supply, 495 W

Connectors : 4 x USB 2.0, 2 x VGA, Serial port (DB9), 4 x Ethernet (RJ45), 2 x Power inlet

Live view: Up to 25 camera split views or 1 x 4K camera view

Playback: 4 x 1080p camera split views or 1 x 4K camera view

13 Biometric System for Data Centre

Multi-Biometric Access Control TerminalCapacity Fingerprints 5,000 Faces 3,000 (1:N) / 4,000 (1:1) CardsAccess Control 600 LBS Electromagnetic Lock with LZ/U Bracketand Metallic Exit Push Button Switch

Specification

Main Biometric Fingerprint

IP Rating -

RF Options BEPL-OC 125 KHz

BEPM-OC 13.56MHz

MIFARE,MIFARE Plus DESFire/EV1 (CSN)

BEPH-OC 125kHz HID Prox

BEPI-OC 13.56MHz

FeliCa, iCLASS SR

BEPI(FE)-OC FeliCa

Multi-Controller Yes

Capacity

Max. User (1:1) 5,000

Max. User (1:N) 5,000

Max. Template (1:1) 10,000

17

Page 18: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Max. Template (1:N) 10,000

Max. Text Log 50,000

Max. Image Log-

Interface WiFi -

TCP/IP Yes

RS-485 1ch Host or 1ch Slave

(Selectable)

RS-232 -

Wiegand 1ch In or 1ch Out

(Selectable)

Input 2 Inputs

Relay 1 Relay

USB -

SD Card Slot -

Hardware

CPU 533MHz DSP

Memory 8MB RAM + 8MB Flash

LCD -

LED Indicator Multi-Color

Sound Multi-tone Buzzer

Operating Temp. -20° to 50°C

Tamper Yes

Power 12VDC

PoE -

Dimensions 50 x 160 x 37 (WxHxD mm)

Certificates

CE, FCC, KC, RoHS

Compatibility BioStar 1.x Yes

BioStar 2 Yes

14.00 DC/NOC/Electrical Room Room Lighting

Should Be Proper LED Lighting for the Whole DC/NOC Room(60X60)

18

Page 19: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Light will install in Ceiling Light

15.00NOC Room Furniture

Normal Furniture For 5 persons

False Ceiling for 130 Sq mtr

16.00

Ceiling tiles should be fire proof

17.10 Ramp for Data Centre

Minimum 8mm sheet metal based for ramp surface area

18.00

19.00

Network Cabling

All Networking cable should support - gigabyte in term of speed

All cabling have to be done in proper and systematic way with required Ducting etc.

Cable tray using for cabling should be constructed from sheetmetal steel

20.00

Environment monitoring Systems

Environment monitoring system for the Data centre with Alert SMS capabilities. The setup should include the following sensors integrated to the system ,Internal 3G

modem for SMS ( Dual-Band UMTS/HSPA+ 900/2100MHzQuad-Band GSM/GPRS/EDGE 850/900/1800/1900MHz) , Two Sensor

-Humidity/Temp, Two Sensor Rope -Water, Dry Contact , AC voltage sensor and Audio visual indicator outside the Door of the datacenter

Measurement Range Celsius : -40°C to +75°C

Measurement Resolution Celsius : 1°CMeasurement Accuracy Celsius : Maximum ±2.3 at -40ºC, minimum ±0.4 at +25ºC and

±1.7 at +75ºCMeasurement Range Fahrenheit : -40°F to +167°F

Measurement Resolution Fahrenheit : 1°F incrementsMeasurement Accuracy Fahrenheit : Maximum ±4.1 at -40ºF, minimum ±0.9 at +25ºC

and ±4 at +167ºF

HumidityMeasurement range : 0 to 100% Relative humidity

Resolution : 1%Accuracy at : 25°C ±3%

Communications cable : UTP Cat 5 cablePower source : Powered by the sensorProbe. No additional power needed

Power Consumption : Typical 7.25 mWatt, 1.45mA

19

Page 20: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

Water sensor : Measurement RangeWet or Dry (-20 degrees C- +60 degrees C)

Measurement AccuracyAble to detect the presence or non-presence of water

Sensor TypePatent pending, capacitance measurement technology

Power ConsumptionTypical 125 mWatt, 25 mA

21.00 Civil Work & other miscellaneous work

removing of 2-3 walls between two moors and hall , reparing the hall in data center

22.00

Power Room seperation (Two walls need to add with esixting 2 walls available room to build the power room ) along with Distamper on wall

Windows Closing with Bricks along with removal of old window & delivring at ground outside along with Distamper on wall

Bullet Proof Door along with door frame - Total Sized 2.35 x 1.35 mtr

Additional civil work in Data Centre

Data Centre Wall painting

PVC Ductings for supporting cabling

GI Cable Tray for Data Centre & Power Room

Trenching work at ground for Cable laying from Dg to Building by RCC ground & Soft Soil alongwith civil work

23.00 Racks and accessories 1

Vertiv Knurr® Miracel or equivalent 2 server rack, made of stable, light weight aluminum profiles, connected withdie cast corner joints, rack completely assembled, demountable on site, completely grounded (EN 60950),heigth 2000 mm xwidth 800 mm xdepth 1200 mm,single sheet steel front-door 83% perforation,double sheet steel rear-door 83% perforation,19" server vertical extrusion incl. cable management,19" server vertical extrusion rear,top cover w/ lateral cable inlet closed,adjustable feed (0-25 mm) - load rating 8000 N static,side panel both sides,standard packaging with BRUSH STRIP and dual Door Locking set.jumpering space 150 mm, useful depth 740 mm,visible surface of covers RAL 7021 (dark gray).

20

Page 21: mcit.gov.afmcit.gov.af/Content/files/amendment RFP FOR DR.docx · Web viewto 8 compute node Item 20: two servers removed from the list of goods and equipment Item 7: Power cabling

23.10

19" Shelf QuickFix mounting without tools, 430x500, for installation depth 565-740 mm,RAL 7021 – Easy and fast fixation (one click) and pre-fixation– Suitable for all racks and enclosures with 19" mounting holes (9,0 x 9,0 square holes)– Depth-variable for the use at different useable depth and special depths– With perforation to optimize air supplyQ115932.3 4 / 8Load rating– 700 N static with equal load distributionMaterial/Finish– Sheet steel 1.0 mm, electroplated with zinc, powder-coated, texturedColor– Powder-coated texture RAL 7021 dark graySupply schedule1 19" QuickFix ShelfMounting hardware

24.00 10G Switches 2

X620 12 100Mb/1Gb/10GBASE-T ports with EEE, 4 100Mb/1Gb/10GBASE-T with EEE shared with 4 1Gb/10GBASE-X SFP+ ports, 2 x300W AC Power

power supply slots, 1 Fan Module slot, ExtremeXOS Edge license with 4x SR SFP+ modules

Power Cord,10A,BS1363,IEC320-C13

25.00Oracle Server X6-2 Compute Nodes: for oracle private cloud appliance 8

2(Twenty-Two-core Intel 2.2 GHz Xeon processors (Total 44 cores)

256 GB 2,400 MHz RAM

(2) 1.2 TB HDDs (RAID1)

(1) Dual-port QDR InfiniBand HCA (PCIe)

(1) GbE management port (BASE-T)

Redundant power supplies

21