manul012r2v2 - tp series hmi

Upload: jose-luis-lopez

Post on 03-Jun-2018

235 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    1/116Doc Ref: LMAN012_R2V2

    4.7 inch Monochrom LCD, 240x128 Pixels

    5.7 inch, Colour TFT, 320x240 Pixels,

    with Powerful Data Dispose Function

    TP460-L

    TP560-T

    TP760-T

    5.7 inch Monochrome LCD, 320x240 Pixels,4MB FlashRom, 2KB SRAM

    7 inch, Colour Touch Screen Panel, Wide Screen Format

    7 inch, Colour Touch Screen Panel, Wide Screen Format,

    with 26 Function Keys, 256 ColourMP760-T

    TP560-L

    TP Series HMI MANUAL

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    2/116

    TouchWin User ManualIndex PageChapter 1 Summary

    1-1 Example of TP series touch screen 51-2 Function 61-3 Models 61-4 Dimensions and attributes 7

    1-4-1 Dimensions 71-4-2 Environment conditions 91-4-3 Image attribute 91-4-4 Configuration size 9

    1-5 Software 141-5-1 Software installation 141-5-2 Software screen components 15

    Chapter 2 Instructions2-1 Create new screens or windows 20

    2-1-1 Create new screen 222-1-2 Create a new window 23

    2-2 Set a title 242-3 Make a graph 26

    2-3-1 Draw a line, circle/oval and rectangle 262-3-2 Draw a polygon 272-3-3 Draw an arc 272-3-4 Change size 272-3-5 Moving objects 282-3-6 Cut, copy and paste 282-3-7 Global and unique unit 28

    Chapter 3 Components3-1 Text settings 323-2 Dynamic text 343-3 Lamp 363-4 Bit switch 383-5 Lamp button 393-6 Image conversion 423-7 Data display 433-8 Alarm data display 453-9 Text display 463-10 Input methods 47

    3-10-1 Data input 47

    3-10-2 Text input 483-10-3 Chinese input 493-10-4 Digital keyboard 503-10-5 ASCII keyboard 513-10-6 Data settings 523-10-7 User input 53

    3-11 Transfer window 543-12 Vertical bar 563-13 Horizontal bar 583-14 Dynamic image 603-15 Window button 623-16 Function button 633-17 Function field 65

    3-18 Real-time graph 673-19 Scatter column graph 703-20 Continuous column graph 72

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    3/116

    3-21 Data collect and save 743-22 Profile table 76

    Chapter 4 Alarm window4-1 Alarm setting 80

    Chapter 5 Print window5-1 Create new print window 845-2 Printer connection 86

    Chapter 6 System parameter6-1 System settings 88

    6-1-1 Setup screen and background 886-1-2 Order settings 886-1-3 Screen protection 88

    6-2 Control in turn 886-3 PLC type selection 88

    Chapter 7 Save and download7-1 Save a project 897-2 Download 90

    Chapter 8 Special funct ions8-1 Add a new function 91

    Chapter 9 PLC connection methods9-1 Application 97

    9-1-1 TP series online communication 979-1-2 TP series touch screen orders 97

    9-2 Xinje FC series 99

    9-2-1 Software setting 999-2-2 TP-FC-CAB0 connection diagram 1009-3 Mitsubishi FX series 101

    9-3-1 Software setting 1019-3-2 TP-FX-CAB0 connection diagram 1029-3-3 Communication units RS232BD 1029-3-4 Communication units RS485BD 102

    9-4 Siemens S7-200 series 1039-4-1 Software setting 1039-4-2 Operation address range 1039-4-3 TP-S7-CAB0 connection diagram 103

    9-5 OMROM C series 1049-5-1 Software setting 104

    9-5-2 Operation address range 1049-5-3 TP-CQM-CAB0 connection diagram 104

    9-6 Koyo S series 1059-6-1 Software setting 1059-6-2 Operation address range 1059-6-3 TP-SZ-CAB0 connection diagram 106

    9-7 Delta DVP series 1089-7-1 Software setting 1089-7-2 Operation address range 1089-7-3 TP-LG-CAB0 connection diagram 109

    9-8 LG Master-K series PLC 1109-8-1 Software setting 1109-8-2 Operation speed range 110

    9-8-3 TP-LG-CAB0 connection diagram 111

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    4/116

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    5/116

    1SummaryTP series touch screen is the first choice of medium size and small size control.

    Example of the model name

    TP-5 6 0-L

    1-1 Example of TP series touch screen

    1-3Models

    1-4Dimensions and attributes

    1-1Example of TP series touch screen

    1-5Software

    L:Monochrome;T:Colour

    60:means60series

    5:for

    5.7

    inch;

    4:

    for

    4.7

    inch

    A:for10.4inch

    TP:fortouchscreen

    1-2Function

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    6/116

    Visualize your plant using the features of the TP series touch screen.

    Here are the standard models in the following table:

    TP series Display materials Display size

    TP-460-L Black-white LCD 4.7 Inch

    TP-560-L Black-white LCD 5.7 InchTP-560-T 256 colour

    TP-A60-L Black-white LCD10.4 Inch

    TP-A60-T 256 colour

    The working voltage for the above table is DC24V.

    1-2 Function

    1-3 Model

    The series has the following advantages:1. Small size2. Easy to connect to the PLC3. Extensive icon library4. Extensive data memory5. Read and write PLC data functions6. Large image functions7. Modbus network connection

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    7/116

    1-4-1 Dimensions

    1. TP460-LTP460-L: real size (unit mm)163.2111.445

    Cut out size (unit mm)165113

    2. TP560-L/TP560-TTP560-L/T: Real size (unit mm) 180.413244

    Cut out size (unit mm)182.4134.4

    1-4 Dimensions and attributes

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    8/116

    3. TPA60-L/TPA60-TTPA60-L/TPA60-T: Real size (unit mm) 31123448

    Cut out sizeunit mm301224

    TP-A60-T TP-A60-L TP560-T TP560-L TP460-L

    Supply voltage 20 to 28V DC

    Current consumption 380mA 380mA 220mA 200mA 180mA

    Instantaneous powerdip

    Less than 20ms

    Overvoltage voltage AC1000V - 10MA one minutesignal and time

    Insulated resistance DC500V - about 10Mone minutesignal and time

    Communication port Support RS232/RS422/RS485

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    9/116

    1-4-2 Environment condition

    1-4-3 Image attribute

    TP-A60-T TP-A60-L TP-560-T TP-560-L TP-460-L

    TypeTFT ColourLCD

    4 rank greycolour

    TFT ColourLCD

    CCFLmonochrome

    monochrome

    Life cycle 50000 hours upwardsenvironment temperature 25 degrees24 hours run

    Display area 800*600 640*480 320*240 240*128

    Brightness AdjustableWord setting EnglishText size Variable sizevariable style

    Touch panelMatrix typetouch

    Matrix typetouch

    Matrix typetouch

    Screen 4MB 2KB 1KB

    1-4-4 Configuration s ize

    TP-A60-T TP-A60-L TP-560-T TP-560-L TP-460-L

    CONFIG

    Cooling Convection coolingExternalsize

    311*234*48mm 189.4*141.4*44.4mm173.2*121.4*45mm

    Panelmountaperturesize

    301*224mm 181*133mm 164*112mm

    TP-A60-T TP-A60-L TP560-T TP560-L TP460-L

    Operationtemperature

    0-50 0-60

    Storagetemperature

    -20 to 60

    Environmentalhumidity

    20 to 85%no condensation

    vibration 10 to 25HZXYZ direction each 30 minutes 2G

    Interference Voltage noise1000Vp-ppulse width 1usone minute

    Surroundingatmosphere

    No corrosive gas

    Protect

    configuration

    IP65

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    10/116

    TP460-L touch screen

    Front

    Back

    Touch screen

    Downloadport

    Communicationport

    Powerconnect

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    11/116

    5.7 inch touch screen

    Powerconnect

    Communicationport

    Downloadport

    Front

    Back

    Touch screen

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    12/116

    TP-A60-T/TP-A60-Ltouch screen

    Powerconnect

    Downloadport

    CommunicationPort

    Back

    Front

    Touch screen

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    13/116

    1-4 Interface details and download cable.

    TP touch screen series port communication plug pin number:

    TP touch screen download cable connection diagram

    Note:

    On the plug of download cablelink the eighth pin and fifth pin, then you can download TP

    with override.

    Pin number definition

    1 NC

    2 RXD2

    3 TXD2

    4 A2

    5 GND

    6 BUSY

    7 B2

    8 NC

    9 NC

    TP download port

    Pin number definition

    1

    2 RXD

    3 TXD

    4

    5 GND

    6

    7 RTS

    8

    9

    Computer COM port

    Pin number Definition

    1 TD+

    2 RXD1

    3 TXD1

    4 A1

    5 GND

    6 TD-

    7 B1

    8 RDD-

    9 RDD+

    TP communication port

    Pin number Definition

    1 NC

    2 RXD2

    3 TXD2

    4 A2

    5 GND

    6 BUSY

    7 B2

    8 NC

    9 NC

    TP download port

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    14/116

    This chapter describes the TP series softwares project screen and its components, and the

    components of the toolbox, template etc.

    1-5-1 Software installation

    Continued

    1-5 Software

    Findsetup.exeinthetouchscreensoftwareanddoubleclickit

    Click next or yes all along to enter user information dialogbox.

    Input user name, company name and serial number.

    The serial number is11111111111111 or Xinje TouchWin

    (note if the letter is in capital or not and the blank)

    Then click next

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    15/116

    1-5-2 Software screen components

    TP touch screens interface display contents name and function is described as follows

    Click next until finish installation and then click finish.

    If the installation is finished, therewill be an icon on the screen as

    shown.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    16/116

    Graphic toolbox

    1. 2. 3. 4. 5. 6. 7. 8

    1. Draw a line2. Draw an arc3. Draw a rectangle4. Draw a circle or oval5. Draw a polygon or multi-segment line6. Frame7. Bitmap8. Select unit

    Parts toolbox

    1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.12.13.14. 15.16.17. 18.19. 20. 21.22. 23.24. 25.26. 27.28

    1. Text 2. Dynamic text

    3. Variation text 4. Lamp

    5. Bit operate button 6. Lamp button

    7. Screen jump 8. Digital display

    9. Alarm display 10. Text display

    11. Data input 12. Text input

    13. Chinese input 14. Set data

    15. Digital keyboard 16. ASCkeyboard

    17. User input 18. Vertical bar

    19. Horizon bar 20. Dynamic image

    21. Call window 22. Window button

    23. Down scheme 24. Up scheme

    25. Function button 26. Real trend diagram

    27. Scatter column diagram 28. Continue column diagram

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    17/116

    Display toolbox

    1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15

    Operate toolbox

    1. 2. 3. 4. 5. 6

    Zoom toolbox

    1. 2. 3. 4.

    1. Date 2. Clock

    3. Buzzer 4. LCD light control

    5. Valve 6. Pipe

    7. Pump 8. Auto wind

    9. Convertor alarm information 10. Real time map

    11. History data map 12. Event button

    13. Display real time event 14. Display history event

    15. Sample save

    1. Global unit 2. Private unit

    3. New 4. Property

    5. Delete 6. Download

    1. Zoom out 2. Zoom ratio

    3. Zoom in 4. Menu grid

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    18/116

    Standard toolbox

    1. 2. 3. 4. 5. 6. 7.

    Graph adjustment toolbox

    1. 2. 3. 4. 5. 6

    1. New 2. Open

    3. Save 4. Cut

    5. Copy 6. Paste

    7. About

    1. Align left 2. Align centre

    3. Align right 4. Align top

    5. Align middle 6. Align bottom

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    19/116

    2InstructionsNote the model of your TP and also the make and model of your PLC and select the correctdownload cable and software.

    2-2Set a title

    2-3Make a graph

    2-1Create a new screen or window

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    20/116

    1. Click new icon in the standard tool column.

    New

    2. When you set up a new project, a dialog box as the following will appear, you should choosethe touch screens model, and then click next.

    2-1 Create a new screen and window

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    21/116

    3. Now choose the PLCs type, click setting to enter communicates parameter setting dialogbox.

    4. The default value is auto set when you choose the PLC model. If there is no specialrequirements please dont change it to avoid communication mistakes. When you finish setting,click OK and there will pop up a new project.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    22/116

    2-1-1 Create a new screen

    There are two ways to create a new screen:

    1. Left-clickscreen (see (1) below) in the project manager area on the left panel Right-clicknew (see (2) below)in the operate toolbox.

    2. Left-clickscreen in the project manager area then Right-clickinsert in the pop menu.(Insert a new screen in the console)

    3. There will pop up a new screen dialog box. Then input the screens ID and screen name,

    finally click OK and you will finish creating a new screen.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    23/116

    2-1-2 create a new window

    There is also two ways in creating windows.

    1. Left Clickwindow (see (1) below) in the project manager area on the left panel, Right-clicknew (see (2) below)in the operate toolbox.

    2. Left-clickwindow in the project manager areaRight-clickInsert

    (Insert a window in the console)

    3. There will pop up a new window dialog box, set the windows ID, name and size. Finally click

    OK and you will finish creating a new window.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    24/116

    There are two ways to give a project screen a different name.

    1. Click a certain screen or window in the console with the mouses right key, then chooseproperty in the pull down menu

    2. Click in the operate toolbox direct

    Use this pop-up

    2-2 Set a tit le

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    25/116

    Input a user-name in the name bar

    If you click the window property, you can also set its size in the pop up dialog box

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    26/116

    Using the Graphics bar

    2-3-1 Draw a line, circle and rectangle

    1. Click in the graphics bar.

    Draw a rectangle, click .

    Draw a circle/oval, click .

    2. Left-click at the start dot.

    3. Drag the cursor to the end dot.4. Let the mouses left key go to finish drawing a line.5. Set the property.

    Choose of the lines thickness (input value is an integer between 0~255)

    2-3 Make a graph

    When the object is selected, double Left-

    click the mouse or click in the operatetoolbox, then the property dialog box willappear.

    There are two options for the lines colour(At present the touch screen is monochrome)

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    27/116

    2-3-2 Draw a polygon

    1. Click in the toolbox.2. At the start dot of the polygon, press down your left key.3. Drag the cursor to the second apex position.4. Let the left key go to fix the second apex position.5. If you increase the apex number, please repeat doing this.6. Double click at the end apex and you will finish drawing a polygon.

    2-3-3 Draw an arc

    1. Click in the toolbox.2. At the start dot of the arc, press down your left key.3. Drag the cursor to the end, then let it go.

    2-3-4 Change size

    1. Hover the pointer over the required .2. The pointer will change to .3. Left-click and hold, then drag your mouse to the required size and release.

    Note:As before in the previous examples, the Properties window can also be used.

    In the properties box:

    1. Click on the Position tab.

    2. In the Position section, set the position of the

    object using X and Y.

    3. In the Size section, use width for horizontallength and height for vertical length.

    When you tick the lock, the lines position is fixed inthe screen.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    28/116

    2-3-5 Moving objects

    Using Drag and Drop.

    1. Select the object

    2. Leftclickandhold,thepointerwillthenchangeto ,thismeansthatyouhaveholdofthe

    image.

    3. Dragtheimagewhereyouwantittobeplacedandrelease.

    Note:As before in the previous examples, the Properties window can also be used.

    2-3-6 Cut, copy and paste

    1. Choose one that needs to be cut.

    2. Click the toolboxcut copy .3. Click in the toolbox.

    2-3-7 Global and unique unit

    In order to improve work efficiency, we offer global unit and unique unit operation. Global unit

    can be used by all the screensunique unit is the opposite, it can only be used by

    the current screen.

    Example:1. create 3 screens in all.

    In the first screen, we add a rectangle:

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    29/116

    2. When clicking the global unit button , the second and third screen now have the rectangleIn the same position.

    3. If we only want to keep the rectangle in the third screen, we will use unique unit. Choose therectangle in the third screen.

    4. Then click unique unit button we will find that only screen 3 has a rectangle.

    The rectangle will disappear in screen 2 and screen 1.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    30/116

    3Components

    3-7Data display

    3-8Alarm data display

    3-2Dynamic text

    3-3Lamp

    3-5Lamp button

    3-6Image conversion

    3-1Text settings

    3-2Bit switch

    3-9Text display

    3-10Input methods

    3-11Transfer window

    3-12Vertical bar

    3-13Horizontal bar

    3-14Dynamic bar

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    31/116

    3-15Window button

    3-16Function button

    3-17Function field

    3-18Real-time graph

    3-19Scatter column graph

    3-20Continuous scatter graph

    3-21Data collect and save

    3-22Profile table

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    32/116

    1. Click icon in the components toolbox

    2. Drag cursor into the screen, click the mouses left key to place the text (Right-click or pressthe ESC key to cancel your place).

    3. Double left-click or choose iconthere will pop up a text setting dialog box.

    3-1 Text settings

    Display the setting

    This contains content , frame andalignment mode.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    33/116

    4. Click when you have selected the text styles, size and colour you require.

    Clicking will present a file selectmap , choose a text frame from here.

    Choose font:

    To choose fonts, select thebutton under the Font tab.

    View the font setting dialog box

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    34/116

    In the industrial process control, a machines state may be multiple. By using dynamic text the

    machine can display these different states.

    1. Click the icon in the components toolbox

    2. Move cursor into the screen, Left-click to place it in the screen area (Right-click or press ESCkey, to cancel).

    3. When the text is been selected, you could choose property.

    4. Choose the dynamic texts object type.

    Note:PLC Registers define the ID on the display

    3-2 Dynamic Text

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    35/116

    Each register correspond to 16 states, eachparts corresponding value is 0~15.

    When the register value is 0the dynamic

    text will display the content of text 0.

    Others are the same. You can also choosealign type and text frame.

    Font Tab:Choose font and size

    Position Tab:Choose of texts position and sizeClick OK and you will finish propertyoperation.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    36/116

    In the process operation we can display clearly what state the machine is at, using color change

    of a lamp symbol.

    1. Click icon in the components toolbox

    2. Move cursor into the screen; click your left key to finish placing the lamp (Click your right keyor press ESC key to cancel placing).

    3. Click property and there will pop up a lamp dialog box

    continued

    3-3 Lamp

    Object Tab:Set station number to 1.

    Use the Object drop-down menu to selectPLC relay address.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    37/116

    Lamp config:

    Map Tab:

    You can set the relay bitmap ON or OFF.

    Click to change the lampappearance.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    38/116

    1. Click icon.

    2. Move cursor into the screen, click your left key to finish placing bit switch button (click yourright key or press ESC to cancel placing).

    3. Click property and there will pop up a bit switch button dialog box.

    SET ONWhen the button is pressed down, the selected middle relay will be set ON.

    SET OFFWhen the button is pressed down, the selected middle relay will be set OFF.

    REVERSEWhen the button is pressed down, the selected middle relay will be set the opposite logic.

    MOMENTARYWhen the button is pressed down, the selected middle relay will be set ON; when the button getsup, the selected middle relay will be set OFF.

    3-4 Bit swi tch

    Object Tab:Choose bit switch button in the objecttype

    Operate Tab:There are four states for bit switchbuttons.Here you can also choose key-presscontent and align mode.

    Press OK to finish property setting.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    39/116

    The lamp button has the function of lamp and button, but the lamp and the button could also be

    used separately for different relays.

    1. Place the lamp button in the screen

    2. Lamp button property setting (when not choosing the monitor object, the lamp button willbe only used as a button).

    Operate objectShows that the lamp button has the key-press function to some middle relay.

    Watch objectShows that the lamp button display some middle relays state (ON or OFF).

    3-5 Lamp but ton

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    40/116

    3. Operate setting

    Button operationThere are four states for the button operation:

    As a button, it has two statesButton ON and Button OFF.

    As a lamp, it has two statesState ON and State OFF.

    Change the style of the lamp buttonPress the Changing button under the Operate tab, then choose from the pop upfile select dialog box.

    continued

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    41/116

    Note:Dynamic object and passive object cant be set the same.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    42/116

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    43/116

    In an industrial process control application, we can display live data for live monitoring purposes.

    1. Click icon

    2. Move cursor into the screen to place it in the screenclick your right key or press ESC to

    cancel placing

    3. Click property and there will pop up a data display dialog box

    continued

    3-7 Data display

    Object Tab:Choose object type (register type, IDand if the data is single or doubleword).

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    44/116

    Bit lengthDisplay or set the max number

    Decimal fraction

    Keep the efficient bits after the decimal

    DecimalizationDisplay the registers data in the form of algorithm (Mitsubishi and OMRONs PLC usethis form).

    Float numberDisplay the registers data in the form of floating decimal place

    Unsigned number

    The highest bit of register is 1it is not a sign bit. For exampleFFFF means 65535.

    Hex /BCDDisplay the data in the form of hex/BCD.

    In the display you can set datatype, length, align type and

    characters frame, colour andposition.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    45/116

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    46/116

    Text display is used to display the register data in the form of text in the touch screen.

    Please refer to data display for more details.

    3-9 Text Display

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    47/116

    3-10-1 Data input

    Data input is used to change a data word inside the PL When inputting data, there must be adigital keyboard.

    1. First, place data input component in the screen,

    2. Click data input component to make it the opposite colour (If password protected,

    you should input the password before modifying the data).

    3. When the data input frame turns to the opposite colour, there will appear a small digitalkeyboard as the following:

    4. After entering the number press ENT on the keyboard to finish the data input .The smallkeyboard will disappear at the same time.

    3-10 Input methods

    Please refer to Data display setting for

    setting data input.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    48/116

    3-10-2 Text input

    Just like data input, when inputting text there will be a text keyboard.

    1. First, place text input component in the screen, if the modify text is more, you could putmore text input components as the following:

    2. Click text input component. (If password protected, you should input the password beforemodifying the data).

    3. There will pop up a small text keyboard as the following:

    4. After entering the text, press ENT on the keyboard to finish text input.

    Please refer to text display setting in

    setting of text input.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    49/116

    3-10-3 Chinese input

    Chinese input is used to input Chinese characters into the register unit by touch screen.When inputting Chinese characters, a small keyboard and a character spell window is needed.

    1. First, place Chinese input component onto the screen. If more Chinese characters arerequired, put more Chinese input components as the following:

    2. Click text input component to make it the opposite colour (If password protected,you should input the password before modifying the data).

    3. When the Chinese input frame turns to the opposite colour, there will come out a small textkeyboard as the following:

    4. First, spell the character you want and input them on the keyboard. In the Chinese chosenarea, it will display five symbols. You can press UP or DOWN buttons to find the characteryou want. After selecting, press ENT to finish and the keyboard will disappear.When you want to modify, just press

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    50/116

    3-10-4 Digital keyboard

    1. The small digital keyboard must be used with data input.

    As before in the data input we can also modify the data input and the character input propertyat the same time. See the following diagram:

    Input tab:When pop-up keyboard is deselected, thekeyboard will no longer appear.

    So we need to add a digital keyboard or atext keyboard in the screen when we adddata input components or text input components.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    51/116

    3-10-5 ASCII keyboard

    The ASCII is similar to digital keyboard The ASCII keyboard must be used with text input .

    Please refer to digital keyboard.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    52/116

    3-10-6 Data settings

    1. Click icon

    2. Move cursor into the screen. Left-click to finish placing data setting button (Right-clickor press ESC button to cancel placing).

    3. Click property and there will pop up a data setting dialog box.

    Object Tab:Set register type and ID.

    Set data type.

    Operate Tab:Choosing arithmeticwill add 10 to theregisters data.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    53/116

    3-10-7 User input

    TheUser input key is used in the small keyboard. You can input letters at the same time. Butthe letters are in the format of ASC.

    Please refer to setup for the other settings.

    Operate Tab:Choosing constant, sets a value to acorresponding register.

    The example, it shows that after theoperation, the corresponding register will beset as 10. The former value in the registerwill be over written.

    Press OK to finish.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    54/116

    The following describes how to transfer the window.

    3-11 Transfer window

    Create a new window to be transferred.

    Set the windows size, name and otherinformation.

    Click in the components toolbox

    then place it onto the screen.

    Object tab:Click property button. Set the relays typeand address in the object.

    When the middle relay is ON, the windowto be transferred will pop out.

    When it is OFF, the window will be closed.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    55/116

    Window tab:Set the windows ID and the windowsposition.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    56/116

    Bar graphics is another format to display data.

    Vertical bar graph is used to display analog parameters such as temperature, pressure, ampsand so on. It displays data in the form of percent based on the max value and min value set inthe property .The height and width can also be set.

    1. Click , drag cursor into the screen, then Left-click.

    2. Double click the bar graphics or click property, a property dialog box will pop up.

    Object type

    Registers ID in the PLC.

    3-12 Vertical bar

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    57/116

    Stick Tab: Direction

    Direction when the bar increases.

    FormatSelect date.

    Max and minThe maximum and minimum value that the bar diagram shows

    Color tab:Set the bar diagrams bar colour and frame colour.

    Position tab:Set the position in the screen.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    58/116

    1. Click , drag cursor into the screen, then click your left key just as the following.

    2. Double click the bar graph or click property; a property dialog box will pop up.

    Object typeRegisters ID in the PLC.

    3-13 Horizontal bar

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    59/116

    Stick Tab: Direction:

    Direction when the bar increases.

    Format:Select date.

    Max and min:The maximum and minimum value that the bar diagram shows

    Color tab:Set the bar diagrams bar colour and frame colour.

    Position tab:Set the position in the screen.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    60/116

    Setting dynamic image is the same as dynamic text. If the registers value is different, they will

    all display different text (or image). The registers value range from 0 to 15 (16 states).

    1. Click , place it in the screen

    2. Set dynamic images property.

    Station numberWe default the Station number to.

    Object typeRegisters ID of the PLC.

    3-14 Dynamic image

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    61/116

    3. Setting dynamic picture in the Map tab:

    Picture 0 to Picture15:In the object, registers value 0-15 correspond picture 0picture 15.

    Changing button:Users self-defined picture.

    4. Click , there will pop up a dialog box, you can select a picture.

    Note:Picture format must be .bmp format.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    62/116

    Using the window Button:

    1. Create a new window.

    3-15 Window button

    Click button in the components toolboxand place it in the screen.

    Operate Tab:Open the property setting dialog box, fill thewindow IDto required value.

    If you want to select the current window, selectcurrent window.

    Then, the window ID colour will turn to grey.The Act drop-down list: open, close, hold .

    You could also set the window hide or show .

    Window Tab:In the display column, we can modifythe text content which will display on thebutton .If you want to close a window bythis button, you can change it to close.

    Click OK to finish setting the button

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    63/116

    The Function button can be programmed, allowing the button carry out different functions.

    1. Place in the screen.

    2. Double click the function button or click property.

    Function Tab:The function button has four types. They each stand for four states: released, pressed,

    releasing, and pressing. We can add different functions for the four states at one time.

    3-16 Function button

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    64/116

    Options:It shows that the buttons certain state can add the following function operation:Set coil, Reset coil, Reverse coil, Copy coil, Screen jump, Set data, Copy Register, Userinput, Open window, Close window, Decrease, Increase, Data block transmit, Arithmetic.

    After you finish adding the function, you can modify the operation to obtain your users

    requirement. Set Coil

    Set1to certain relay or bit.

    Reset CoilSet0to certain relay or bit.

    Reverse CoilReverse certain relay or bit.

    Copy CoilCopy the source coils data to the destination coil.

    Screen JumpMake the screen jump to the predetermined screen.

    Set dataSet the appointed value to the an object.

    Copy registerCopy the registers value to the predetermined register.

    User inputInput button codes, the codes are in the form of ASC.

    Open windowOpen a predetermined window by the window ID.

    Close windowClose the window by the window ID.

    Download schematicDownload the schematic data (touch screen) to the device data (PLC).

    Upload schematicUpload the device data (PLC) to the schematic data.

    Data block transmitTransfer the source ID registers data to the target ID register.

    ArithmeticPerform an arithmetic function with the set registers data, then save the final value inthe target register.

    3. Property setting

    Pictures:

    There are two states as a buttonPressed and Released.

    Changing:

    When pressing the Changing button, the File select pop-up box will appear and a picturecan be selected.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    65/116

    The Function fields usage is similar to the Functionbutton, but they are not the same. The

    major difference is on the functions trigger action.The function button can set different operations to the four trigger actions. But the function fieldcan only have one trigger action selected to run the function.

    1. Place in the screen.

    2. Setting of function field property

    Act mode (You can only choose one trigger action):

    Start screenThe screen in which the function field is transferred, the function will be carried out.

    Coil springWhen the coil changes from 0 to1, the function fields function will be carried out.

    Time (seconds)The screen in which is the function field is transferred, the Function fields function willbe carried out. This function repeats wthin a certain time (can be manually set).

    ContinueThe screen in which the Function field is transferred, will carry out the function fieldcontinually.

    3-17 Function field

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    66/116

    3. Option card

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    67/116

    Real time graph can show a registers value changing in the form of graph. The trend graph will

    sample the PLC register and display its state versus time.. The display has the property of realtime.

    1. Place in the screen.

    2. Real time graph property setting

    Add:Add registers.

    ModifyModify the trend graph property of the user object.

    3-18 Real-time graph

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    68/116

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    69/116

    4. Trend property setting.

    Data

    CountShow the number real time graph can display. Pick period

    Show time space when real time graph pick data each time. It must be an integer. Range

    Show the range of real time graphs vertical change. The user can pre-set. Graph mode The graphs display mode is line, dot or column Display mode

    5. Save

    Object type

    Appoint the original ID after data sample is over and then save.As the data populates the table, the first four bytes are used to save the tables beginningaddress and end address. So, the datas real address is the objects address plus 4. Defaultedas PSW

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    70/116

    Scatter column graphs horizontal axis takes the scatter registers, and displays each registers

    value with a graph.

    1. Place scatter column graph in the screen.

    2. Set the scatter column graphs property.

    Note:The systems default is THREE display objects

    3-19 Scatter column graph

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    71/116

    3. Set the display property.

    PositionShows the real time graphs vertical display area

    FormatDecimal etc.

    PatternScatter column graphs display pattern, there are three choices: fold, dot, column

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    72/116

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    73/116

    Choose object type (Registers type, address and single word or double)Display property setting.

    NumberShow the number to display. Set the address. Here we default it to 5.

    FormatIn which format does the continue column graph change.

    PatternContinuous column graphs display pattern: fold, dot or column.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    74/116

    Data collect and save collects data in a certain cycle and saves it in the register ID.

    1. Place in the screen

    2. Set data collect and save property.

    Display object tableDisplay each registers object, you can add, modify, delete, move up or move down.

    3-21 Data col lect and save

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    75/116

    2. Collect setting

    CountTotal number of data to collect.

    PeriodCollect data in a certain time.

    MannerIf collecting data and time is at the same time.

    3. Save the settings

    ObjectThe start address for the data.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    76/116

    The profile table is used to display real-time and history alarm notes. It controls event

    Information and trigger times display with a bit. Meantime, history notes are saved in theTP series touch screens continuous register. The start address and number can be set by theuser.

    Profile table divides into History event display , Real-time event display and the

    First event control button . The difference is:

    The History event display saves the trigger event in order by the register, the user can affirm ordelete.Real-time event display so it can only display the spring event real time.

    History event description:

    1. Add in the screen, just as the following diagram:

    2. Set the propertyThe appearance option card is the first:

    3-22 Profile table

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    77/116

    ColumnYou can separately adjust three columns title, align mode and column width.

    You can appoint rows height and row number of each page.

    If selecting the events spring time will display as

    FFFF year FF month FF day FF hour FF minute FF second.

    Event capacity shows the max number of history data.

    Event option card:

    Click add button to add events. The serial number will be in order.

    Click modify button, modifies the coil corresponding to the columndisplay

    instead of . For example: the serial number is 1when M0

    coils rising edge happens, it will display temperature high.

    Click delete button to delete the event chosen at present.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    78/116

    Save the option card:

    In the object type column choose the registers type. Fix the address yourself.

    Note:The first four words save information is the first address and end address of history event.The real data starts from the set address plus 4.The other option cards are: font, colour and position etc. The user can refer to other controlsdescription.

    3. Add button and set its relative property, as the following:

    Choose the corresponding action in the key option. As follows:a) Previous page

    The profile table and display previous pages history notes.b) Next pageThe profile table and display the next pages notes.

    c) Previous itemMove to the up line from the current position.

    d) Next itemMove to the down line from the current position.

    e) ClearAll the history data in the profile table.

    f) AffirmAffirm of the current positions event.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    79/116

    4. The following example:

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    80/116

    4Alarm window Alarm window is used to display alarm messages when triggered. It controls messages displayedby a bit address of the PLC.

    1. Creating a new alarm window is similar to creating a new window, it has two ways.a) Left-click Alarm in the manage column to highlight.

    Or

    4-1 Alarm setting

    4-1Alarm setting

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    81/116

    b) Insert a window in the console.Left-click the window of the project manage area so it is highlighted then Right-clickand select Insert in the drop down menu.

    2. A new alarm window dialog will appear.a) Set the windows name, width and height.b) Set the objects type and pop-up period.c) Repeat means that when the alarm window will pop-up once only.d) 5 sec means pop up in the alarm window every 5 secondse) The alarm window can be set to appear every 5sec,

    10sec30sec1min5min10min30min.

    f) Press OK to finish setting

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    82/116

    3. Place a text in the corresponding position of the alarm window. The content is the relativealarm message i.e. temperature too high.

    The operator can then take action to solve the problem.

    4. Press OK to close the alarm window.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    83/116

    5Print window

    5-2Printer connection

    5-3

    Title

    5-1Create new print window

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    84/116

    It is a bit address message of the PLC to trigger print action. The windows content is the print

    content.

    1. Creating a new alarm window is similar to creating a new window, it has two ways.

    a) Click Print in the manager textbox with your left key.

    b) Click new in the operate toolbox.

    5-1 Create a new print window

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    85/116

    2. A Print Window dialog box.a) Set its name, width, and height.b) Set its trigger object (a register bit of PLC. Take M0 for example, when M0=1, the

    print window pops, at the same time print the windows content. When you dontwant to print them, trigger objects value will be set 0).

    c) You can also set the print direction from left to right or from right to left.

    d) Press OK to finish setting.

    3. Add the print content you want in the print windows corresponding position setting.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    86/116

    Printer side TP series touch screen side

    9 pin D shape female

    Bus 2 RXD

    Data 3 TXD

    GND 5 GND

    6 DSR

    NOTEThe printer model we use to test is BRIGHTEK WH164Q0108A5you can refer to itsuser manual for printing.

    5-2 Printer connection

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    87/116

    6System parameter

    Choose system parameter in the file menu. See system setting dialog box.

    6-1 System sett ings

    6-2Control in turn

    6-3

    PLC type selection

    6-1System settings

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    88/116

    6-1-1 Start-up screen and setup background

    Its the first screen after power up. Usually we set this screen as the main menu screen or thescreen that will be used most often.

    Press set button and you can set the screens background colour (It can be set white or black.).

    6-1-2 Order setting

    In a project, all screens use a common order. If the password is used, we can hide screens anddata.

    6-1-3 Screen protection

    Set screen saver and background light delay time default as 3 minutes. When it is set to noscreen protection, it means the background light lights all the time.

    The PLC can switch the screen by modifying the registers value. Write the value n to registerD300. Example: TP560 will auto switch the display to the screen n?

    TP560 write the current screen numbers data to D301, so the PLC will know the displays state.

    Note:The designer can define the multi-control registers number.

    Select a PLC model. When the TP560 is down loading the screen, it transfers the screens dataalong with the PLCs communication protocol. So when the display is downloaded, it will pass theprotocol to communicate with the PLC.

    6-2 Control in turn

    6-3 PLC type selection

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    89/116

    7Save and download

    After finishing the screen edit, you can save the project file and download the screen project tothe TP series touch screen. It is now ready to debug online.

    1. Click buttonthe screen will pop up a save screen dialog box.

    2. Choose route and name to save it.

    3. The files extension name will auto defined as .twp

    4. Set the file name, choose the path, then click save to save the screen.

    7-2Download

    7-1Save a project

    7-1 Save a project

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    90/116

    1. Connect the computers 9 pin RS232 series port and TP series download 9 pin seriesport with a download cable.

    2. Make sure that TP series is connected to DC24V.

    3. Click button to download data.

    See download screen data prompt window.

    Note:In the process of downloading screen data, make sure the TP series power is not cut off orswitched off!

    After the screen transfer is over, there will be a pop up dialog box. It tells you that all projectscreens have transferred.

    4. Switch the displays power off, remove the screen transfer cable TP-SYS-CAB0,connect the TP to the PLC with the PLC communication cable.

    5. Power up the PLC and display. If communication is normal, they will carry out data monitorand other operation.

    Note:If communication fails because of wrong parameter or wrong cable connection, please check thefollowing:

    If the PLC model matches with the connection.

    If they have connected with communication cable

    If the communication cable is connected correctly.

    If PLCs communication parameter setting is correct

    If you have powered the PLC and display If you cant find the problem, please contact your supplier.

    7-2 Download

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    91/116

    8Special functions

    TP series touch screen not only has a terminal display function, it has its own memory area. Inthe different areas it has different definition and function.

    Identifier Definit ion Definition number Function

    PSB Bit

    0 Always ON

    1 Always OFF

    2 The first scan time is ON

    3 0.1 sec pulse

    4 1sec pulse

    5 1 min pulse

    PSW byte 1 Start screens ID

    2 Current screens ID

    The TP series touch screen can add a new function to communicate with an inverter on top of theoriginal function. See Mitsubishi FR series transducer for example to describe.

    8-1Save a project

    8-1 Add a new function

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    92/116

    1. First, open TouchWin edit tool, create a new project:

    2. Choose a corresponding display, click next:

    3. Choose Mitsubishi FR series inverter in the table, click setting as system default and clicknext:

    4. Input name, author, remark etc. press Finish to enter edit screen.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    93/116

    Here we will change the inverters parameters and input frequency mainly by the touch screen tocontrol the machine roll forward, roll back, and stop. At the same time we display the transducersstates of alarm code; output frequency output voltage and output circuit etc by the touch screen.(See the detailed presentation for the unit).

    5. Place digital display unit in the screen, open the property dialog box, default it as object

    option card. Choose the pull down menu of object

    Alarm codes will correspond to the alarm codes inside the inverter. Set the frequency tocorrespond to the inverters frequency.

    Output frequency corresponds to the output frequency of the inverter.

    Output current Corresponds to the output current of the inverter

    Output voltage Corresponds to the output voltage of the inverter Parameter Corresponds to the different parameter inside the inverter, the user can

    appoint a certain parameter in the inverter and display it on the touch screen.

    Order codes Corresponds to the different order codes inside the inverter, the user canappoint a certain order code to control the frequency for the corresponding action.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    94/116

    6. Click display option card according to the screens prompt and product demand, just as thefollowing diagram:

    7. Place Transducer Alarm Information in the screen. Just as the following:

    Inverter Alarm information units object option card is the same as a Digital display.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    95/116

    Description presentation:

    16 Over-circuit is cut off when speeding up

    17 Over-circuit is cut off when speed be determined

    18 Over-circuit is cut off when slowing down

    32 power up over-voltage is cut off when speeding up

    33 power up over-voltage is cut off when speed be determined

    34 power up over-voltage is cut off when slowing down or stop 48 Inverter over-load open circuit

    49 Electric machine over-load open circuit

    64 Radiator is over the temperature

    96 Loss of speed precaution

    112 Control-action transistor alarm

    128 Output side connect to the ground over-circuit protection

    129 Output wrap the phase protect

    144 External hot relay act

    160 Choose unit abnormal

    176 Parameter memory abnormal

    177 Parameter unit

    178 Retry times exceed 243 alarm unit abnormal

    246 CPU error

    247 CPU error

    0 No alarm information

    8. Place button unit in the screen, open the property dialog box as the following diagram:(Set option cards object type; you can refer to other units presentation for its option card)

    a) Roll forward/Stop as the transducers roll forward or stop state. ON is rolling forward,OFF is stop.

    b) Roll back/Stop as the transducers output roll back or stop state. ON is rolling back,OFF is stop.

    c) Rolling state as to the transducers output roll state. ON is rolling, OFF is not.d) Roll forward and back state as the transducers output roll forward and back state.

    e) ON means roll forward, OFF means roll back.

    f) Alarm Correspond to the transducers current alarm code.

    (Please refer to introduction before for other units relative property.)

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    96/116

    9PLC connection methods

    9-3Mitsubishi FX series

    9-2Xinje FC series

    9-5OMROM C series

    9-4Siemens S7-200 series

    9-7Delta DVP series

    9-6Koyo S series

    9-9Panasonic FP series PLC

    9-8LG master-K series PLC

    9-10.Schneider Electric PLC

    9-1Application

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    97/116

    9-1-1 TP series on line communication

    1. After downloading switch the power off and remove the screen transfer cable OP-SYS-CAB0.2. Connect the TP series DOWNLOAD port to the PLC communication port.3. Check if the PLCs communication parameter is correct.4. Resume power (TP series use DC 24V power),the display will now enter the run state.

    9-1-2 TP series touch screen orders

    In order to improve the machines safety, the data in the touch screen must be modified byprofessional people. So, this demands that the touch screen must have the function of dataprotection.

    1. First, set the systems parameter.Select file, then choose setting in the pull down menu.

    2. See the system setting dialog box, input the password and, press OK to finish.The order has three levels:

    Regular:Regular level can only carry out protection function of normal level.

    Advance:Advance level order can carry out protection functions of high level and regular level.

    SystemSystem level, you can carry out all level operations.

    9-1 Application

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    98/116

    3. Creating of project system. First, set screen jump button to make it jump to the page.

    4. Press user input button to switch to the screen.

    5. Press open order button to enter order input screen.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    99/116

    6 Press after setting the order. If the order is right, it will pop up 1or else it will pop up 2.

    7. Press Close orderto close the order dialog box, but if the operation is order protected it

    cannot be carried out.

    8. Press back button to return to the original screen.

    9-2-1 Software setting

    Parameter items Recommended setting

    PLC model Xinje FC series

    Communication port type RS232

    Data bit 8

    Stop bit 1

    Checksum bit Odd

    Baud rate 9600

    Bureau ID 1

    Address for operation:

    9-2 Xinje FC series

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    100/116

    PLC ID type Operation range Format Presentation

    M 0~383 DDD Assistant pointer

    W 0~2047 DDDD Data memory

    D means algorithm data

    9-2-2 TP-FC-CAB0 connection diagram

    2 RXD 4 RXD

    3 TXD 5 TXD

    5 GND 8 GND

    8 pin DIN round male pin column

    TP series touch screen side9 pin D shape female

    FC series PLC side8 pin round male

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    101/116

    9-3-1 Software setting

    Parameter items Recommended setting

    PLC model Mitsubishi FX series

    Data bit 7

    Stop bit 1

    Checksum bit Even

    Baud rate 9600

    Bureau ID 0

    PLC address range Operation range Format Presentation

    X 0~267 O External input bits

    Y 0~177 O External output bits

    M 0~1023 D Internal bits

    S 0~999 D Special bits

    T (as states) 0~255 D Timer state

    C 0~255 D Counter bits

    C16 0~199 D 16 bits count

    C32 200~255 32 bits count

    D 0~8255 D Data memory

    T (as registers) 0~255 Current value

    , X, Y, M andS all can extend as registers.

    9-3 Mitsubishi FX series

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    102/116

    9-3-2 TP-FX-CAB0 connection diagram

    1 TD+ 2 RD-

    6 TD- 1 RD+

    8 RD- 4 TD-

    9 RD+ 7 TD+

    5 GND 3 GND

    9-3-3 Communication units RS232BD

    2 TX 2 SD

    3 RX 3 RD

    5 GND 5 GND

    9-3-4 Communication units RS485BD

    RDA

    4 A SDA

    5 GND SG

    7 B RDB

    SDB

    TP series touch screen side9 pin D shape female

    FC series CPU RS422 port8 pin round shape female

    TP series touch screen side9 pin D shape female

    FX series PLC side8 pin D shape female

    TP series touch screen side9 pin D shape male

    FX series RS485BD unitRS485 port

    5 point connect port

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    103/116

    9-4-1 Software setting

    Parameter items Recommended setting

    PLC model S7-200

    Communication port type RS485

    Data bit 8

    Stop bit 1

    Checksum bit Even

    Baud rate 9600

    Bureau ID 2

    9-4-2 Operation address range

    PLC ID type Operation range Format Presentation

    VB 0~4095 DDDD Byte data register

    VW 0~4095 DDDD Word data register

    M 0~255.7 DDD.O Internal bits

    VD 0~4095 DDDD Double word data register

    D means algorithm data

    9-4-3 TP-S7-CAB0 connection diagram

    4 A 3 A

    7 B 8 B

    9-4 Siemens S7-200 series

    TP series touch screen side9 pin D shape female

    S7-200 series PLC side9 pin round shape female

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    104/116

    9-5-1 Software setting

    Parameter items Recommended setting

    PLC model OMROM

    Communication port type RS232

    Data bit 7

    Stop bit 2

    Checksum bit Even

    Baud rate 9600

    Bureau ID 0

    9-5-2 Operation address range

    PLC ID type Operation range Format Presentation

    IR 00000~24315 DDD (BB) As bits and register

    SR 24400~25515 DDD (BB) As bits and register

    HR 0000~9915 DD (BB) As bits and register

    AR 0000~2715 DD (BB) As bits and register

    LR 0000~6315 DD (BB0 As bits and register

    TC 0~512 DDD Timer /counter registers value

    DM 0~6655 DDDD Data register

    PV 0~512 DDD Time or counters current value

    9-5-3 TP-CQM-CAB0 connection diagram

    2 RXD 2 RXD

    3 TXD 3 TXD

    5 GND 5 GND

    9-5 OMRON C series

    TP series touch screen side9 pin D shape female

    OMROM PLC side9 pin D shape male

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    105/116

    9-6-1 Software setting

    Parameter items Recommended setting

    PLC model Koyo

    Communication port type RS232

    Data bit 8

    Stop bit 1

    Checksum bit Odd

    Baud rate 9600

    Bureau ID 1

    9-6-2 Operation address range

    PLC ID type Operation range Format Presentation

    I 0~477 OOO External input bits

    Q 0~477 OOO External output bits 0

    M 0~377 OOO Internal assistant bits

    T 0000~2715 OOO Timer bits

    C 0~177 OOO Counter bits

    S 0~177 OOO Step bits

    R 0~177 OOOOO Data register

    O means octal

    9-6 Koyo S series

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    106/116

    9-6-3 TP-SZ-CAB0 connection diagram

    1. CPU unit (DL05/DL105/DL230/DL250/DL350/DL450 RS232 Port

    2 RXD 4 TX

    3 TXD 3 RX

    75 GND 1 GND

    6 GND

    DL05 series port1&2, DL240s port1&2, DL250 port1, DL350s port1 and DL450s port2 are all

    hardware port of RJ-11, the connection line is the up diagram.

    RJ-11 6 foot female pin feet arrange

    2. CPU unitDL250 CPU unit Port2 RS422

    TP series touch screen side9 pin D shape female

    DL250 CPU unitRS422 port

    15 port SVGA port female

    8 RD-10 TX-

    9 RD+ 9 TX+

    5 GND 7 GND

    6 TD- 6 RX-

    1 TD+ 13 RX+

    11 RTS+

    14 CTS+

    12 RTS-

    15 CTS-

    DL250 units Port2 combines RS232 and RS422 these two electric ports, when using, please payattention to their type setting.

    TP series touch screen side

    9 pin D shape female

    Direct Logic seriesRS232 port

    6 feet RJ-11 male

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    107/116

    3. CPU unit (DL430/DL440/DL450 CPU unit Port1&DL350 CPU unit Port2 RS232)

    TP series touch screen side9 pin D shape female

    DL350/405 series CPU RS232 port

    25 pin D shape female

    3 TXD 2 TX

    2 RXD 3 RX

    5 GND 7 GND

    4 RTS

    5 CTS

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    108/116

    9-7-1 Software setting

    Parameter items Recommended setting

    PLC model Delta DVP

    Communication port type RS232

    Data bit 7

    Stop bit 1

    Checksum bit Even

    Baud rate 9600

    Bureau ID 1

    9-7-2 Operation address range

    PLC addressrange

    Operationrange

    Format Presentation

    X 0~377 OOO External input bits

    Y 0~377 OOO External output bits

    M 0~1279 DDDD Internal bits

    S 0~1023 DDDD Special bits

    T 0~255 DDD Timer state

    C 0~255 DDD Counter bits

    D 0~1279 DDDD 16 bits count

    TD 0~255 DDD 32 bits count

    CD 0~255 DDD Data memory

    PresentationD means algorithm numberO means octal number

    , X, Y, M andS all can extend as registers.

    9-7 Delta DVP series

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    109/116

    9-7-3 TP-LG-CAB0 connection diagram

    TP series touch screen side

    9 pin D shape female

    Delta DVP series

    8 pin round shape male

    2 TXD 4 TX

    3 RXD 5 RX

    5 GND 8 GND

    Delta DVP series PLC contain DVP-14/24/32/60ES00 and DVP-XXESO1 etc. modelall can

    connected with TP touch screen by program communication port on CPU unit.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    110/116

    9-8-1 Software setting

    Parameter items Recommended setting

    PLC model LG Master-K

    Communication port type Port2 Port1

    ProtocolModbusSlave PRG

    Data bit 8 8

    Stop bit 1 1

    Checksum bit Even check No check

    Baud rate 9600 34800

    Bureau ID 1 1

    9-8-2 Operation address range

    PLC address

    range

    Operation

    range Format Presentation

    P 0~127F DDDH Input/output bits

    K 0~31F DDH Keep relay bits

    M 0~191F DDDH Internal bits

    L 0~63F DDH Connect relay bits

    F 0~63F DDH Read only

    T 0~255 DDD Timer bits

    C 0~255 DDD Counter bits

    TD 0~255 DDD Current value of timer

    CD 0~255 DDD Current value of counter

    D 0~5119 DDDD Data register

    SD 0~100 DDD Step bits

    , Can be used as a register

    Extend to use as a register

    9-8 LG Master-K series PLC

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    111/116

    9-8-3 TP-LG-CAB0 connection diagram

    Port 1

    TP series touch screen side

    9 pin D shape female

    Master k series CPU

    9 pin D shape female

    2 RXD2 RXD

    3 TXD3 TXD

    5 GND 5 GND

    Port 2

    TP series touch screen side

    9 pin D shape female

    Master k series CPU

    RS232 port9 pin D shape female

    2 RXD4 RXD

    3 TXD7 TXD

    5 GND 5 GND

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    112/116

    9-9-1 Software setting

    Parameter items Recommended setting

    PLC model Panasonic FP

    Communication port type RS232

    Data bit 8

    Stop bit 1

    Checksum bit No

    Baud rate 9600

    Bureau ID 1

    Note:

    Usually we default FP series PLCs station number as 1but if FP3 has a special controlthe

    station number must be 0. Please check to communication setting of PLC when connecting.

    9-9-2 Operation address range

    PLC addressrange

    Operationrange

    Format Presentation

    X 0~12F DDH External input bits

    WX 0~12 DD As a register

    Y 0~12F DDH External output bits

    WY 0~12 DDDH As a register

    R 0~62F, 90~903F Internal assistant bits

    WR 0~62, 900~903 DD As a register

    T 0~99 DD Timer bits

    C 100~143 DDD Counter bits

    SV 0~143 DDD Set value of timer or counter

    EV 0~143 DDDD Current value of timer or counter

    DT 0~9999 Data register

    9-9 Panasonic FP series PLC

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    113/116

    9-9-3 TF-FP-CAB0 connection diagram

    NAIS FP series PLC contains FP0/1/2/3/2SF/10SH etc. series, all of them can connect to TPtouch screen by the program port on the CPU or communication port.

    CPU unit RS232

    TP series touch screen side9 pin D shape female

    FP0/FP2/FP2SH/FPM CPU5 pin DIN round shape female

    2 RXD3 RXD

    3 TXD2 TXD

    5 GND 1 GND

    TP series touch screen side9 pin D shape female

    FP1/FP2/GP2SH/FP10SH CPURS232 port

    9 pin D shape female

    2 RXD3 TXD

    3 TXD2 RXD

    5 GND5 GND

    1 CD

    7 RTS

    8 CTS

    4 DTR

    6 DSR

    5 pin female plug type

    Diagram:In FP0 series only FP0-CXXCXX model has RS232 communication port.

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    114/116

    9-10-1 Software setting

    Parameter items Recommended setting

    PLC model Schneider Electric

    Communication port type RS485

    Protocol MODBUS

    Data bit 8

    Stop bit 1

    Checksum bit Even

    Baud rate 9600

    Bureau ID 1

    9-10-2 Operation address range

    9-10-3 TP-NEZA-CAB0 connection diagram

    TP series touch screen side

    9 pin D shape female

    Schneider Electric PLC side

    8 pin D shape male

    4 A1 A

    7 B 2 B

    5

    7

    PLC address type Operation type Format Presentation

    M 0~2047 DDDD Internal bits

    MW 0~2047 DDDD Register bits

    9-10 Schneider Electric PLC

  • 8/12/2019 Manul012r2v2 - Tp Series Hmi

    115/116

    DocumentationReference

    DocumentNumber RevisionDate

    LMAN 012 R2 V2 18/07/2012

    XINJEISAREGISTEREDTRADEMARKOFXINJEELECTRICALCO.LTD. REPLICATIONOFTHE

    INFORMATIONCONTAINEDWITHINTHISDOCUMENTWITHOUTPRIORNOTIFICATION

    ANDAGREEMENTISPROHIBITED.

    ForhelpandsupportregardingyourXINJEproductsvisittheonline

    SupportCentreorcontactuson:[email protected].

    www.listoltd.com

    www.xinjesupport

    centre

    listo.com

    Internationalpartnerswith: