manual tuxon-mc (bagging mode )

102
Tuxon-MC (bagging mode) USER’S MANUAL Ver. 1 / 2012 / 10

Upload: saconaconaca

Post on 18-Jul-2016

89 views

Category:

Documents


25 download

DESCRIPTION

Manual control de peso

TRANSCRIPT

Page 1: Manual Tuxon-MC (Bagging Mode )

Tuxon -M C

(bagging mode)

USER’S MANUAL

Ver. 1 / 2012 / 10

Page 2: Manual Tuxon-MC (Bagging Mode )

Table

1 General Information........................................................ 1

1.1 Function.................................................................... 1

1.2 Description................................................................ 2

1.3 Rear illustration......................................................... 3

1.4 Specification.............................................................. 4

1.5 Dimension................................................................. 5

2 Wiring.............................................................................. 6

2.1 Installation................................................................. 6

2.2 Power connection..................................................... 7

2.3 Load cell connection................................................. 7

2.3.1 Six wires........................................................... 7

2.3.2 Four wires........................................................ 8

2.4 I/O terminals............................................................. 9

2.5 Analog output connection....................................... 10

2.6 Serial port connection............................................. 11

3 Calibration.................................................................... 12

3.1 Instruction............................................................... 12

3.2 Flow chart............................................................... 12

3.3 Millivolt display........................................................ 15

3.4 Calibration without weights..................................... 16

3.5 Quick zero/gain calibration..................................... 18

3.6 Parameter table...................................................... 18

3.7 Parameter record................................................... 18

4 Parameter setting........................................................ 19

4.1 Defination............................................................... 19

4.2 Operation parameter table..................................... 21

Page 3: Manual Tuxon-MC (Bagging Mode )

5 Recipe setting............................................................. 24

5.1 Recipe number...................................................... 24

5.2 Recipe configuration............................................. 24

5.3 Recipe parameter table......................................... 25

6 Operation.................................................................... 33

6.1 Operating status.................................................... 33

6.2 Set batching times................................................. 33

6.3 Check and clear accumulative total....................... 34

6.4 Manual discharging............................................... 35

6.5 Manual zeroing...................................................... 36

6.6 Restore for broken power...................................... 36

6.7 Supplement........................................................... 36

6.8 Free fall Compensation......................................... 37

6.9 Filling level and control......................................... 37

6.10 I/O testing........................................................... 38

6.11 I/O defination...................................................... 39

6.12 Display testing.................................................... 43

6.13 Reset.................................................................. 44

6.14 Backup & restor................................................... 45

6.15 Analog calibration & self-definition...................... 46

6.15.1 Analog calibration........................................46

6.15.2 Analog self-definition...................................48

6.16 Password............................................................ 49

6.17 Set password...................................................... 49

6.18 Operation mode...................................................50

7 Automatical bagging................................................... 51

7.1 flow chart with hopper........................................... 51

7.2 flow chart without hopper ......................................51

Page 4: Manual Tuxon-MC (Bagging Mode )

7.3 Sketch map with hopper........................................52

7.4 Sketch map with hopper........................................53

7.5 Description............................................................ 53

8 Serial port communication.......................................... 55

8.1 RS protocol........................................................... 55

8.2 MODBUS protocol................................................ 77

9 Error and alarm message........................................... 98

.

Page 5: Manual Tuxon-MC (Bagging Mode )

- 1 -

1 General information

Tuxon-MC Bagging controller is a kind of

weight-increasing control instruments to control automatic

bagging machine at high accuracy and powerful function,

which widely used in various bagging systems for concrete,

bitumen, fertilizer, feeding stuff and so on.

1.1 Function

Small volume, unique design, easy operation;

Suit to all of load cells at bridge-type resistance strain

gauge;

14 I/O( 4 input / 10 output)

RS232/RS485 to ensure stable communication;

Fast, moderate and slow feeding with “Jog feeding” ;

Multi digital filter;

Automatical modify for free fall;

High precision 16bit DA analog output;

Automatical compensation

Digital calibration with or without weights;

Password for calibration, operation parameters etc.;

Automatic zeroing when power up;

Automatic zero tracking.

Three operation modes(optional).

Page 6: Manual Tuxon-MC (Bagging Mode )

- 2

1.2 Description

P 1-1

Keypad

:Zero/Exit key to exit present operation / return back.

:Parameters key to select parameters and set value.

:Function key to set parameters and select function.

:Confirmation key to enter or confirm parameters.

Status indication:

:Light in bagging process.

/ :Both SP1 and SP2 light in fast feeding;SP1

light in moderate feeding;SP2 light in slow feeding.

:Light in discharging process.

:Light for zero when weight is among 0±1/4d.

:Light for stability when weight is in stable range.

Display:

Main display:6digits, display weight and parameters.

Sub-display:6digits, display G.W. and parameters.

Page 7: Manual Tuxon-MC (Bagging Mode )

- 3 -

1.3 Rear illustration

P 1-2

① I/O input terminals

② I/O output terminals

③ Load cell terminals

④ Serial port / analog terminals

⑤ Power connection

⑥ Fuse socket

Page 8: Manual Tuxon-MC (Bagging Mode )

- 4

1.4 Specification

Common:

Power supply:AC90V~260V 50Hz (or 60Hz) ± 2%

Filter:Inside

Working temperature:-10~40℃

Max humidity:90%R.H without dew

Power consumption:About 10W

Dimension:105×151×57mm

Analog:

Load cell power:DC5V 300mA (Max)

Input impedance:10MΩ

Zero steady range:0.02~9mV

Input sensitivity:0.01uV/d

Gain input range:0.2~10mV

Transfer mode:Sigma - Delta

A/D conversion speed:120times/sec

Non-linearity:0.01%F.S

Gain drift:10PPM/℃

Display Precision:1/30000

Digital:

Weight display:6digits red high-brightness LED

Minus display:“-”

Overload display:“OFL”

Decimal point:5kinds (optional)

Page 9: Manual Tuxon-MC (Bagging Mode )

- 5 -

1.5 Dimension

Page 10: Manual Tuxon-MC (Bagging Mode )

- 6

2 Wiring

2.1 Installation

P 2-1

1. Cut hole as left size

in the suitable place of

control box.

2. Screw open in four

corners, then dismantle

mounting plates.

3. Install indicator in

the front of control box.

4. Insert mounting

plates on both sides

and then screw tightly.

Page 11: Manual Tuxon-MC (Bagging Mode )

- 7 -

2.2 Power connection

Tuxon-MC bagging controller connects power as follows:

P 2-2

2.3 Load cell connection

EX+: Excitation+ EX-: Excitation- SN+: Sense+ SN-: Sense- SIG+: Signal+ SIG-: Signal-

6 wires EX+ SN+ EX- SN- SIG+ SIG- Shield

4-wires EX+ EX- SIG+ SIG- Shield

1) 6 wires connection:

P 2-3

1. AC power must connect with ground;

2. Please do not connect indicator’s earth line

with other huge electronic equipment directly.

Page 12: Manual Tuxon-MC (Bagging Mode )

- 8

2) 4 wires connection

P 2-4

1. As load cell output sensitive analog signal,

please use shield cable to separate with other

cables, especially AC power;

2. 4 wires connection is suitable for short distance

and stable temperature or low precision field,

otherwise use 6 wires connection.

3. For more load cells parallel connection, their

sensitivity (mV/V) should be same.

Page 13: Manual Tuxon-MC (Bagging Mode )

- 9 -

2.4 I/O terminals

Tuxon-MC Bagging indicator transfer data by

optoelectronic isolation technology, thus need 24V DC

outside as power supply, which anode connect with indicator

24V+, and cathode with 24V- through the COM1 (DC+)

and the COM2 (DC-). The input signal is low level

effective, and the output is transistor open-collector output,

which driving current can reach 500mA.

I/O definition as follows:

P 2-5

Indicator input terminal connection:

P 2-6

Indicator output terminal connection:

P 2-7

Page 14: Manual Tuxon-MC (Bagging Mode )

- 10

I/O tolerant definition as follows:

Output Input

OUT1 Fast feeding IN1 Run

OUT2 Moderate feeding IN2 Nip bag

OUT3 Slow feeding IN3 Lower level

OUT4 Discharge IN4 Stop

OUT5 Over tolerance

OUT6 Run

OUT7 Pat bag

OUT8 Near-zero

OUT9 Nip bag

OUT10 Lack material

2.5 Analog output connection

Analog output two kinds: voltage and electric current.

For voltage output, 0-5V/0-10V/-5-5V/-10-10V is optional

for voltage output;4-20mA/0-20mA/0-24mA is optional for

electric current output. Define terminals as follows:

P 2-8

Note:Analog output is optional function, please declare if

need when place orders.

Page 15: Manual Tuxon-MC (Bagging Mode )

- 11 -

2.6 Serial port connection

Serial port(RS485 or RS232) connection as follows:

P 2-9

RS232 connection:

P 2-10

RS485 connection: C

on

troller 1

A

B

GND

Co

ntro

ller n

A

B

GND

Co

mp

uter

A

B

GND

GND is ground of RS485, it can very

much improve communica t ion

quality via connecting with GND by

low-resistance wire when there is a lot

of disturbance in working field.

.

.

.

P 2-11

Page 16: Manual Tuxon-MC (Bagging Mode )

- 12

3 Calibration

3.1 Instruction

Tuxon-MC bagging controller need calibrate at

beginning of operation or changing any parts on weighing

system or non-suitable application for user. The calibration

can define radix point, minimum scale division, maximum

scale capacity, zero and gain, etc.

User can press to enter next or press to

save setting to only change one parameter, and then

press to exit.

3.2 Flow chart

Press to display

CAL,and then press

to enter password.

Input correct

password , when

display “CAL ON” one

second, then enter to

set radix point

automatically.

Page 17: Manual Tuxon-MC (Bagging Mode )

- 13 -

1) Press set radix point

(0~0.0000 5 kinds optional),

press to save and enter mini division. 2) If not change radix point,

press directly to enter mini division.

1) Press to set mini

division(1~50 6kinds

optional ),press to save

and enter max. capacity.

2) If not change mini division,

press directly to enter

max. capacity.

1) Input max. capacity(≤mini

division × 30000),press

to save and enter millivolt display.

2) If not change, press to enter millivolt display directly.

1) Select suitable sensitivity based on load cell,

press to save and enter millivolt display. Otherwise to

press directly to enter millivolt display.

Page 18: Manual Tuxon-MC (Bagging Mode )

- 14

1) When load cell output

millivolt value, press to enter zero calibration directly. 2) The display value is similar with millivolt from SIG+/SIG- terminals. See Character 3.3 for details. 1) When scale platform is

stable, press to take

present weight as zero,and

enter gain calibration.

2 ) Press to reserve

original zero and enter gain calibration.

1) Gain calibration as the left chart. ▲When calibration with weights, please record zero millivolt, gain millivolt and weight value in list. If no weights, user will calibrate according to these data.

2) Press to enter password directly, no gain calibration.

1) See Character 5.11 to set

password, then press to

exit calibration and return.

2) If not set password,

press directly to return.

Normal working status.

Page 19: Manual Tuxon-MC (Bagging Mode )

- 15 -

3.3 Millivolt display

This function is mainly used to test weighing system,

four-corner position-error of force-transmitted equipment

and load cell’s linearity.

1. Test weighing system

(1) If the indicator display variational millivolt value

according to add weight, thus indicate load cells are

connected correctly and force-transmitted equipment is

operated normally.

(2) If the indicator display OFL (or –OFL), thus indicate

the weight is too heavy (or too light), then need unload (or

add) the weight. But if always display OFL (or –OFL) after

changing weight, maybe the following reason cause:

a. Please check force-transmitted equipment.

b. Please check the load cell’s connection.

c. Please check Load cells.

2. Test four-corner position-error of force-transmitted

equipment

Please load same weight on scale’s every corner and

record individual millivolt value. If the values are obviously

different, please adjust force-transmitted equipment.

3. Test load cell’s linearity

Please load several same weight values within the

weighing capacity and record relevant millivolt value after

zeroing every time; if the discrepancy is bigger among

millivolt values, thus indicate that the load cell’s linearity is

not good, need change new load cell or adjust

force-transmitted equipment.

Page 20: Manual Tuxon-MC (Bagging Mode )

- 16

3.4 Calibration without weights

Calibration without weights is only for urgency. If

change new load cells or indicator, or adjust weighing

system, calibration without weights is not correct.

Page 21: Manual Tuxon-MC (Bagging Mode )

- 17 -

Page 22: Manual Tuxon-MC (Bagging Mode )

- 18

3.5 Fast zero / gain calibration

In weighing status, press for long time, when display password input, then input password correctly and enter zero calibration. See Character 6.16 for details.

3.6 Calibration parameter table

Sign Parameter Type Division Initial value

Point Decimal

point 5

0,0.0,0.00,0.000, 0.0000

0

1d= Mini division 6 1,2,5,10,20,50 1

CP Max

capacity ≤mini division×30000 10000

St System millivolt

SE Sensitivity 2 2,3 2(mV/V)

E SCAL Zero

AddLd(d) Gain

PASS Set

password 000000

3.7 Calibration parameter record

Parameter Valued Date Remark

Decimal point position

Mini division

Max capacity

Load cell sensitivity

Password setting

List(calibration with weights):

Times

Zero millivolt

(mV)

Gain millivolt

(mV)

Weights

(Kg) Date Remark

1

2

3

Page 23: Manual Tuxon-MC (Bagging Mode )

- 19 -

4 Parameter setting

4.1 Defination

Press to select parameters, then press and

to set parameters, after that, press to save setting.

1)Optional parameter setting

Set“parameter 5 ”(ON)for example:

Note:Press to switch among

parameters;press to enter next

menu;press to return previous

menu.See Chapter 4.1 for details.

Page 24: Manual Tuxon-MC (Bagging Mode )

- 20

2)Numerical parameter setting

Set “parameter 7”(as 35)for example:

1. Press , then sub-display sparkle “OFF”.

2. Press , then sub-display show“ON”.

3. Press to save setting. If not need set other parameters,

press to return.

1. Press , sub-display sparkle “5” in the left.

2. Press till sub-display show “3”,

then press ,sparkle move to the

right one.

3. Press till sub-display show“5”,

then press to save and finish.

Page 25: Manual Tuxon-MC (Bagging Mode )

- 21 -

4.2 Operation parameter table

No. Para. Initial Description

1 01~99 01 Scale no.

2 1200~57

600 9600 Baud rate

3 Rs / Bus Rs

Communication mode: Rs: GM mode, including

Read and Cont mode;

Bus: MODBUS mode, including Rtu & AscII mode.

3.1 Read / Cont

Cont

Rs/Re mode:

READ:command;

CONT:continue

3.1.1 0~5 1

Serial port data-sent speed

for CONT at Rs/Re mode:

1-5:means 10,20,30,40 and

50ms;

0:means one character time.

3.1 Rtu/Asc Rtu MODBUS communication mode: Rtu or Asc

3.1.1 Hi Lo Lo Hi

Hi Lo

MODBUS dual-byte register storage turn for Rtu at

MODBUS:

Hi Lo:High byte in the front, low byte at back; Lo Hi:Low byte in the front, high byte at back.

Page 26: Manual Tuxon-MC (Bagging Mode )

- 22

4

18N2 18E1 18O1 18N1 17N2 17E1 17O1

18E1

Data format:

18N2:(R / C / B_r optional);

18E1:(R / C / B_r optional);

18O1:(R / C / B_r optional);

18N1:(R / C / B_r optional);

17N2:(R / C optional);

17E1:(R / C optional);

17O1:(R / C optional).

5 ON/OFF OFF Automatic zeroing when power on

6 00~99 01 Zero tacking range(00~99d

optional). If setting 0, not zero tracking.

7 01~99 50 Zeroing range(01%~99% of

full capacity).

8 01~99 01 Stability criterion range(01~99d optional).

9 0~9 5 AD digital filter parameter

0:no filter;9:strongest filter

10 0~9 0

Stability filter: Second filter

based on first one:

0:no filter;9:strongest filter

11 00~99 00

Automatic zeroing alternation when Bagging times finish .

Note:Not zero for first

bagging.(only effective in

binyES mode; 0 not to zero).

12 bin no/ binyES

binyES

Working mode:

bin no:Without weighing

hopper; binyES:With

weighing hopper.

Page 27: Manual Tuxon-MC (Bagging Mode )

- 23 -

12.1 GroSS /

nEt nEt

Gross/Net working mode for no weighing hopper: GroSS:Gross;nEt:Net

13 Co/Sin Co

Feeding mode: Co:Fast/Moderate/Slow combination;

Sin:Fast/Moderate/Slow single feeding.

14 ON / OFF

OFF

Switch to release bag automatically: ON:release automatically; OFF:release manually.

15 ON / OFF

OFF

Switch to count manual discharging into accumulative total: ON:yes;OFF:not.

16 ON / OFF

OFF

Switch to count over/under tolerance into accumulative total: ON:yes;OFF:not.

17 ON / OFF

OFF

Save when power off: ON:Restore after restart again when power off; OFF:not restore.

18

4-20 / 0-20 / 0-24 / 0-5 /

0-10 / -5-5 /

-10-10 / USEr

4-20

Analog output: 4-20:4-20mA 0-20:0-20 mA 0-24:0-24 mA 0-5 :0-5V 0-10:0-10V -5-5 :-5-5V -10-10 :-10-10V USEr: User self-definition

19 ON/OFF OFF Password switch

19.1 ****** Password setting. See Character 6.17 for details.

Page 28: Manual Tuxon-MC (Bagging Mode )

- 24

5 Recipe setting

5.1 Recipe number

Tuxon-MC can store 40pcs recipes related number

01~40, which can be configured by user.

5.2 Recipe configuring

1) Optional recipe parameters

Alternate between recipe parameters F1~F12 by ,

enter by and return by .

Page 29: Manual Tuxon-MC (Bagging Mode )

- 25 -

2) Configure recipe parameters

In recipe item, user can press to enter to check or change.

5.3 Recipe parameter table

No. Para. Initial Description

F1 U_LSet None Press to enter or press

to enter F2 directly.

F1.1 xxxxxx 000000 Target value.

F1.2 xxxxxx 000000

Leading quantity of fast feeding.

When fix value,if weight ≥

target value - leading

quantity of fast feeding,then

stop fast feeding.

F1.3 xxxxxx 000000

Leading quantity of moderate feeding.

When fix value,if weight ≥

target value - leading

quantity of fast feeding,then

stop moderate feeding.

F1.4 xxxxxx 000000

Free fall value. When fix value,if weight ≥ target value–free fall value, then stop slow feeding.

F1.5 xxxxxx 000000

Near-zone weight: When fix value, if present weight ≤ near-zone weight, then start timer to discharge after t5.

Page 30: Manual Tuxon-MC (Bagging Mode )

- 26

F1.6 xxxxxx 000000 Starting weight to pat bag.(Only display without weighing hopper mode)

F2 Ti set None Setting time: press to

enter, or press into item F3 directly.

F2.1 00.0~99. 9

(s) 00.5

Feeding delay time t1: With hopper mode:Zeroing at stability within zeroing alternation after time t1, otherwise feeding directly; Without hopper mode:reduce tare in stability after time t1 when nip bag.

F2.2 00.0~99. 9

(s) 00.9

No contrast time t2 in fast feeding: In time t2, the indicator don’t contrast present weight with the value (target value - leading quantity of fast feeding).

F2.3 00.0~99. 9

(s) 00.9

No contrast time t3 in moderate feeding: In time t3, the indicator don’t contrast present weight with the value (target value - leading quantity of moderate feeding).

F2.4 00.0~99. 9

(s) 00.9

No contrast time t4 in slow feeding: In time t4, the indicator don’t contrast present weight with the value (target value - free fall value).

Page 31: Manual Tuxon-MC (Bagging Mode )

- 27 -

F2.5 00.0~99. 9

(s) 00.5

Over tolerance checking time t5: Check over tolerance in stability after time t5.

F2.6 00.0~99. 9

(s) 00.5

Fix value within time t6 after time t5. With hopper mode: wait bag -nipped signal after time t6. Without hopper mode: begin to pat bag or release bag directly after time t6.

F2.7 00.0~99. 9

(s) 00.5

Discharging delay time t7: With hopper mode: when the weight is less than near-zero value, shut off discharging after time t7. Without hopper mode: when the weight is less than near-zero value,release bag automatically and return to G.W., so finish the bagging process once after timet7.

F2.8 00.0~99. 9

(s) 00.5

Bag-nipped delay time t8: Nipping bag within time t8.

F2.9 00.0~99. 9

(s) 00.5

Bag-released delay time t9: With hopper mode: Output signal to release bag after time t9 without discharging. Without hopper mode: Output signal to release bag after time t9 when fixing value finish or when patting bag finish.

Page 32: Manual Tuxon-MC (Bagging Mode )

- 28

F3 ON/OFF OFF

Over/under tolerance

alarm:

ON:press to enter

F3.1;press to enter F4;

OFF: press or to

enter F4 directly.

F3.1 0.0~9. 9 0.5

Over tolerance percent: When fix value,if weight ≥ target value + target value × over tolerance percent,so it is over tolerance.

F3.2 0.0~9. 9 0.5

Under tolerance percent: When fix value,if weight ≤ target value - target value x under tolerance percent,so it is under tolerance.

F3.3 ON/OFF OFF

Pause switch for Over/under tolerance: ON:pause and display present net weight at over or under tolerance, so user can press or input “clear alarm” effective signal, then go on;User also can input “stop” effective signal to stop . OFF:only output alarm message within time t, but not stop.

F3.4 00.0~99.9

(s) 00.5

Over/under tolerance alarm time t: output alarm within time t if above item is OFF.

Page 33: Manual Tuxon-MC (Bagging Mode )

- 29 -

F4 ON/OFF OFF

Free fall compensation:

ON:Press to enter

F4.1;Press to enter F5

directly.

OFF:Press or to

enter F5 directly.

F4.1 00~99 01

Free fall compensation times: The indicator will make the average of thus times as compensation value.

F4.2 00~99 02

Free fall compensation percent of target value: If free fall value is more than the percent of target value, the value will not be accounted to average.

F4.3 0~3 2

Free fall compensation

range: 1 for 100%;2 for

50%;3 for 25%;0 for 0%.

F5 ON/OFF OFF

Under tolerance

supplement:

ON:Press to enter

F5.1;Press to enter F6.

OFF:Press or to

enter F6 directly.

F5.1 00~99 03

Jog-feeding supplement times: After that, if weight is still under tolerance, then sent out alarm signal .

Page 34: Manual Tuxon-MC (Bagging Mode )

- 30

F5.2 00.0~99.9

(s) 00.5

Jog-feeding supplement effective time.

F5.3 00.0~99.9

(s) 00.5

Jog-feeding supplement alternation time.

F6 ON/OFF OFF

Patting bag (Note:Not pat

bag with weighing hopper)

ON:Press to enter

F6.1; Press to enter F7.

OFF:Press or to

enter F7 directly.

F6.1 P_Add P_End P_AEn

P_End

P_Add : Only pat bag in

feeding;

P_End:Only pat bag after

fixed value;

P_AEn:Pat bag in feeding

and after fixed value. (Note: Not pat bag with

weighing hopper)

F6.2 000~999 0 Patting bag times in feeding.

F6.3 000~999 0 Patting bag times after fixed value.

F6.4 00.0~99.9

(s) 00.5

Patting bag delay time t10: With hopper mode: output signal to pat bag after time t10 when discharging finish. Without hopper mode: time t10 is ineffective.

Page 35: Manual Tuxon-MC (Bagging Mode )

- 31 -

F6.5 00.0~99.9

(s) 00.5

High-level lasting time for patting bag.

F6.6 00.0~99.9

(s) 00.5

Low-level lasting time for patting bag.

F6.7 ON/OFF OFF

Shake bag:begin to shake

bag after bag-patted last time when ON. (Note: Only display at no hopper mode)

F6.8 00.0~99.9

(s) 00.5

Shake bag delay time t: stop shaking bag after delay time t when bag release.

F7 ON/OFF OFF

Jog-feeding supplement:

ON:Press to enter

F7.1;Press to enter F8.

OFF:Press or to

enter F8 directly.

F7.1 d_S/d_d/

d_ds d_S

Jog-feeding supplement mode:

d_S:Slow jog-feeding;

d_d:Moderate Jog-feeding;

d_dS:slow and moderate

jog-feeding.

F7.2 00.00~

99.99(s) 0.05

Moderate feeding effective time ta at moderate jog feeding.

F7.3 00.00~

99.99(s) 0.05

Moderate feeding ineffective time tb at moderate jog feeding .

Page 36: Manual Tuxon-MC (Bagging Mode )

- 32

F7.4 00.00~

99.99(s) 0.05

Slow feeding effective time tc when slow jog feeding.

F7.5 00.00~

99.99 (s) 0.05

Slow feeding ineffective time td at slow jog feeding.

F8 0~9 1

Discharging times within one process. Release bag till discharging times finish at hopper mode. 0 to discharge directly, no need bag-nipped signal.

F9

sdp_DA / sdp_re / rdp_s1 / rdp_s3

dsp_re

In stop status,sub-display:

dsp_re:Recipe no.;

dsp_DA:Analog value;

rdp_s1:Accumulative total;

rdp_s3:Total bag quantity.

F10

rdp_fi rdp_s1 rdp_s2 rdp_s3

rdp_fi

In running status,under

display items:

rdp_fi:Display target value;

rdp_s1:Display

accumulative total value;

rdp_s2:Display target value

– feeding value;

rdp_s3:Display total bags.

F11 ON/OFF OFF

Display-locked function:

OFF:No display;

ON:display fixed value or

present weight when weight is less than near-zero value.

F12 ON/OFF OFF Recipe parameter password

Page 37: Manual Tuxon-MC (Bagging Mode )

- 33 -

F12.1 ****** Please refer Character 6.17 for details to set password.

6 Operation 6.1 Operation status

1. When power on, buzzer hoot, main and sub-display flash “8”,and instruction lights also sparkle.

2. After finished, main display

show “8806-b” , and sub-display

show “software no. ”.

3. (1)When operation parameter

no. 14=OFF or F14=ON power off in

stop status, bagging controller show

present weight after display working mode and software no.

within 3 seconds.

(2)When operation parameter

no.14=ON and power off in running

status, main display show gross

weight, sub-display show“Conti?” after display working

mode and software no. within 3 seconds. ID no. is material

no. before power off, such as right chart, material lno.3 is

batching when power off.

At this time, press to continue last bagging

process;press to begin new bagging process.

6.2 Set batching times

Batching times range is from 0~9999. When finished,

batching controller display “ERROR5” alarm and pause.

Page 38: Manual Tuxon-MC (Bagging Mode )

- 34

When user press or input “clear alarm” effective signal,

batching controller return stop status.

For example, set batching times “3” as follows:

6.3 Check and clear accumulative total

Accumulative total value display 9digits at most(main

display show 3digits and sub-display show 6digits), which

means main display show high 3digits and the sub-display

show low 6digits. Accumulative total times display 6digits on

main display. Please see following operation flow chart:

1. If batching times are zero, then enter stop status

directly after discharging.

2. If discharging one time when batching finish,

only when total batching finished, bagging controller

check if batching times are up.

1. In stop status, press (4times) till

main display show bAt.

2. Press to enter and sub-display

show“0000”and sparkle in hight digit.

3. Press to move sparkling digit to

the left, then press till sparkling digit

change to“3”.

4. Press to save and finish, then

press to return stop status.

Page 39: Manual Tuxon-MC (Bagging Mode )

- 35 -

6.4 Manual discharging

In stop status, when user input “manual discharging”

signal, the bagging controller output effective discharging

signal; input “manual discharging”signal again, then the

bagging controller output ineffective discharging signal.

In running status, after fixed value, the bagging

controller only output“discharging”effective signal to

discharge after received“discharging permit”effective signal.

1. In stop status, press (5times) till

main display show ”totAL”.

2. Press to enter accumulative total.

3. The present accumulative total value is

207356289, Press to enter accumulative total times.

4. The present accumulative total times

are 80307, press (2times) to return stop status.

1. When accumulative total disply, press for

sparkle value, then press to clear accumulative total value, and return stop status.

2. Not clear accumulative total value when running.

Page 40: Manual Tuxon-MC (Bagging Mode )

- 36

6.5 Manual zeroing

When stop, press or input “zeroing” signal to clear

gross weight value.

Note: Operation must be in stable status or gross

weight is in the zeroing range. Otherwise the indicator will

display ERROR3 or ERROR2 alarm message.

6.6 Save for broken power

When operation parameter 17 is ON, if the power

supply break, bagging controller can restore previous

working status after power restart again.

6.7 Supplement

When recipe parameter F3 is ON and present weight is

under tolerance, so bagging controller begin supplement if

recipe parameter F5 is ON. The bagging controller will

automatically check following supplement mode according

to present weight and target value:

(1)Present weight <target value – leading quantity of

fast feeding, restart fast, moderate and slow feeding again;

(2)Target value - leading quantity of fast feeding ≤

present weight ≤ target value – leading quantity of moderate

feeding, restart moderate and slow feeding again;

(3)Target value – leading quantity of moderate

feeding ≤ present weight ≤ target value – leading quantity of

slow feeding, restart jog feeding.

Page 41: Manual Tuxon-MC (Bagging Mode )

- 37 -

6.8 Free fall compensation

When recipe parameter F4 is ON, bagging controller

compensate free fall value automatically.

User need press long time to save the

compensation value in stop status.

Note: When supplement F5 is ON, the free fall value do

not compensate whether F4 is ON or OFF.

6.9 Filling level and control

There are three kinds of filling levels: dual levels

(upper and under levels), single level (under level) and no

filling levels. Please refer to following instruction:

1. Dual levels (upper and under levels): Define I12 and

I13 as input. When both upper and under levels input

ineffective, the filling output effective; When the upper level

input effective, the filling output ineffective. At same time, the

feeding won’t start till the under level input effective before

each feeding (fast, moderate or slow). But in feeding, it is no

use whether the under level input effective or not.

2. Single level (under level): Only define I13 as input.The

indicator won’t control to fill material. The feeding won’t start

till the under level input effective before each feeding (fast,

moderate or slow). But in feeding, it is no use whether the

under level input effective or not.

3. No filling levels:The indicator won’t control to fill

materials.

Page 42: Manual Tuxon-MC (Bagging Mode )

- 38

6.10 I/O testing

Press to switch among OUT1~OUT10 and

press to return. Please refer following flow chart:

Sub-display indicate F means IN1~IN4

from left to right,when input effectively, F change to O.

For example, F change to O indicates IN1 input effectively and connect correctly.

OUTPUT means testing. Main-display show output number, sub-display show status.

Press ,sub-display OFF change to ON indicates OUT1 output effectively and connect correctly.

Press to switch output numbers, such as from OUT1 to

OUT2.

Stop

Press 8 times till main-display show“tStio”.

Press ,main-display show“inPUt”

Press to enter I/O input testing.

Press ,main-display

show“oUtPUt”

Press to enter I/O output testing.

Page 43: Manual Tuxon-MC (Bagging Mode )

- 39 -

6.11 I/O definition

When stop, user can define I/O ports by and

to return.

The flow chart is to define OUT3 as O5(SP5) for

example:

Output code table:

Output

Code Definition Description

O0 None No def ini t ion

O1 Run Effective in running status

O2 Stop Effective in stop status

When stop, press 4times, main

display show“iodEF”.

Press to input correct calibration

password, the press to define. See Character 6.19 for details.

Main display shows output and

sub-display show code, press till

main display show OUT3.

Press till sub-display show 05, then

press to finish.

If not need define others, press to return.

When slow feeding ef fect, OUT3

ouput effectively.

Page 44: Manual Tuxon-MC (Bagging Mode )

- 40

O3 Pause Effective in pause status

O4 Fast feeding Begin fast feeding when weight <| target value – leading quantity of fast feeding.

O5 Moderate feeding

Begin moderate feeding when weight <| target value – leading quantity of moderate feeding.

O6 Slow feeding Begin slow feeding when present weight <| target value – free fall value.

O7 Fix value Fix value between slow feeding and discharging or patting bag.

O8 Over tolerance Effective in over tolerance.

O9 under tolerance Effective in under tolerance.

O10 Alarm Effective when over/under tolerance, batching times finished and so on.

O11 Nip bag Effective signal to nip bag and ineffective signal to release bag.

O12 Pat bag Control to pat bag.

O13 Discharging Discharge material after timeT6.

O14 Zero Effective when present net is less than near-zero value.

O15 Filling material

Control to fill material. When the under level input ineffective, the filling output effective;when the upper level input effective, the filling output ineffective.

O16 Batching times Finish batching times.

Page 45: Manual Tuxon-MC (Bagging Mode )

- 41 -

O17 Lacking material

When the under level input ineffective, the filling output effective.

O18 Stability Instruction light on for stability.

O19 Breaking output The signal output changed according to input signal.

O20 Stop-feeding

output

When fast, moderate and slow feeding, the signal is ineffective; others are effective.

Input

Code Definition Description

I1 Start Enter run status when impulse input is effective.

I2 Quick stop Return to stop status at once when impulse input is effective.

I3 Stop Return to stop status when impulse input is effective.

I4 Zero Zeroing for gross weight when impulse input is effective.

I5 Clear alarm Clear alarm when impulse input is effective.

I6 Recipe no. Recipe no. 1 to 40. If target value is 0, then go to next one.

I7 Nip bag /

release bag Change to nip bag or release bag.

I8 Manual

discharging

Discharge when level input is

effective;Stop to discharge when

level input is ineffective.

Page 46: Manual Tuxon-MC (Bagging Mode )

- 42

I9 Manual

discharging

Effective discharging output when impulse input is effective; ineffective when again more.

I10 Manual slow

feeding

Effective slow-feeding output when effective input one time; ineffective when again more. Note:Supplement in stop and run status.

I11 Keypad lock Only can press effectively.

I12 Upper level Level input for upper level of material hopper.

I13 Under level Level input for under level of material hopper.

I14 Discharging-val

ve closed completely

Effective input for discharging valve closed completely; contrarily not closed. With hopper mode:Not feeding until the input is effective. If ineffective input, then stop fast / moderate / slow feeding. Note: No definition, no use.

I15 Nip bag

completely

Effective input for nipping bag completely, contrarily not nip completely. With hopper mode : Not discharging until the input is effective. If ineffective input, then stop to discharge. Without hopper mode : Not feeding until the input is effective. If ineffective input, then stop fast / moderate / slow feeding. Note: No definition, no use.

Page 47: Manual Tuxon-MC (Bagging Mode )

- 43 -

I16 Pause Enter pause status when impulse input is effective.

I17 Start/Stop

When level input is effective, start to run;If ineffective, return to stop status after finish bagging when feeding, otherwise stop at once.

I18 Clear total Effective input to clear total times and weight.

I19 Breaking input Level input is effective, the breaking input is effective; Otherwise ineffective.

Note: Same input/output code can be defined as several

inputs/outputs, such as both IN1 and IN2 are defined as I4.

6.12 Display testing

The following flow chart is to test lights on main-display

and sub-display, status and instruction:

Press till all of main display, sub-display and status lights are bright.

Press till all of lights shine and sparkle at 2seconds/time.

Press 2times to exit testing and

return.

Press 7 times in stop status

till main display show “tStdip”.

Page 48: Manual Tuxon-MC (Bagging Mode )

- 44

6.13 Reset

Reset present parameters to initial setting.

Reset “I/O definition (io)” for example:

1. Suggestion: When reset, please backup first to be

used in the future.

1. In stop status, press till main display show “init”.

2. Press to input correct calibration password. See Character 6.19 for details.

3. Press till sub-display show“io

(I/O definition”).

Note: “SETUP”to backup operation parameters; “CAL”to backup calibration parameters; “rECiPE”to backup recipe parameters; “ALL”to reset all of parameters.

5. Press , sub-display show“SUCCES”to enter next

parameters. Press to return.

4. Press , sub-display show“YES?”.

Page 49: Manual Tuxon-MC (Bagging Mode )

- 45 -

6.14 Backup & Restore

User can make all of parameters backup.

Make“all of parameters (ALL)”backup for example:

Restore backup is similar with backup operation. When

main display show “rbAC”, press to enter and restore.

2. Press till sub-display show“ALL

(all of parameters)”

Note: “SETUP” operation parameters

backup; “CAL”calibration parameters

backup; “io”I/O definition backup.

“rECiPE”recipe parameters backup.

3. Press , sub-display

show“YES?”, then press to confirm and enter next parameters.

Otherwise press to exit and return stop status.

1. When stop,press till main

display show “bAC”. And then

press input calibration password,

sub-display show “SET UP”.

Page 50: Manual Tuxon-MC (Bagging Mode )

- 46

6.15 Analog calibration & self-definition

6.15.1 Analog calibration

Calibrate at 4 values:4mA、12mA、20mA and maximum

current.

1) 4mA:Main display shows CAL DA, sub-display 10923 ,

ID indicates 1;

2) 12mA:Main display shows CAL DA, sub-display 32768,

ID indicates 2;

3) 20mA:Main display shows CAL DA, sub-display 54613,

ID indicates 3;

maximum current:Main display shows CAL DA, sub-display

24.000.

For example: calibrate “12mA output” and “Max. current”:

1. In stop status, press till main

display show CALdA.

2.Press to input correct

calibration password, and then

press to enter analog self-

definition (sub-display show“SET”).

3.Press to set analog

self-definition parameters. Press

to switch analog calibration.

4.Press to set analog

calibration parameters.

Page 51: Manual Tuxon-MC (Bagging Mode )

- 47 -

Calibration method:

1. Please connect multi-meter with analog output terminals

correctly in calibration.

2.If the analog output value from multi-meter and terminals

are different, press , so sub-display sparkle, and then

press or to change DA digits and adjust analog

output value to be same as calibration value, after that,

press to finish.

3. If the analog output value from multi-meter and terminals

are same, press to next calibration item.

4.No need adjust DA digits to calibrate maximum analog,

only input analog value from multi-meter in the calibration.

6. Press to exit.

1. Press to calibrate 4mA.

2. Press to calibrate 12mA,

which ID indicate from 1 to 2;

Calibrate 20mA when ID indicate

3; If no ID indication, it calibrates

maximum current.

Note: Press long time in

calibration, sub-display value for all of

analog output restore to initial value.

Page 52: Manual Tuxon-MC (Bagging Mode )

- 48

6.15.2 Analog self-definition

Definition description:

1) minimum analog value is output analog value of minimum

analog. When the weight is less than zero,the linearity

between zero and maximum capacity is decreasing, then

stop to decrease at this value.

2) zero analog value is output analog value when the

indicator show zero. For example, SP0 define iout as 5.000,

so the analog value output 5.000mA when when the

indicator show zero.

3) maximum capacity analog value is output analog value

when the indicator show maximum capacity.

4) maximum analog value is output analog value when the

1. Press to define voltage and

current parameters.

2. Press , sub-display sparkle, and

then press to switch and

press to save. After that,

press to define analog value.

3. Analog self-definition: minimum

analog value, zero analog value,

maximum capacity analog value and

maximum analog value.

Main display show SP1、SP2、SP3、

SP4, which change by .

Note: Operation item 18 must set USEr.

Page 53: Manual Tuxon-MC (Bagging Mode )

- 49 -

weight is overflow.

6.16 Password

All initial passwords are :000000。 Note:Calibration password is same password as reset, backup, restore, I/O definition and analog calibration. When calibration password changed, others also changed.

Password operation as follows

6.17 Password setting

User can set password in parameters when F6.1 is“ON”.

Set operation parameters password for example:

2. Press to input password. Note: If input wrong,sub-display

show“Error”, then press again. If input wrong for three times, main display show“Error4”and self-lock, but user can operate again when power on again.

3. Input correct password, then

press to set parameters.

2. Press and in turn to input password. Note: User must input same new password twice to set password. If not, main display show“Error”one second and return to PASS again.

3. Once input same new password

twice, press to save and return

19.1.

1. Press to enter password.

1.When operation parameter 19 set

ON,press ,main display show

19.1,then press , main display

show PASS, enter password.

Page 54: Manual Tuxon-MC (Bagging Mode )

- 50

6.18 Operation mode

Tuxon-MC has three modes: weighing mode, bagging

mode and batching mode, which are optional for users.

Setting operation: When power on, press long

time in “8” sparkling till the indicator response two sonorants,

then the indicator show“PASS”without pressing . After

that, press to input password “880606” on

sub-display.

When password is correct, main display show “SELECT”

and sub-display show GM8806-A(Weighing mode)、

GM8806A-B(Bagging mode) or GM8806A-P(Batching

mode), which can change by pressing .

After selecting operation mode, press to confirm

and finish, then the indicator sparkle “8” to enter.

Note:After selecting operation mode, user need reset

the indicator to ensure parameters correct.

Page 55: Manual Tuxon-MC (Bagging Mode )

- 51 -

7 Automatical bagging process

7.1 Flow chart for bagging with weighing hopper

7.2 Flow chart for bagging without hopper

Page 56: Manual Tuxon-MC (Bagging Mode )

- 52

7.3 Sketch map for bagging process with

weighing hopper

Page 57: Manual Tuxon-MC (Bagging Mode )

- 53 -

7.4 Sketch map for bagging process without

weighing hopper

7.5 Description

1) With weighing hopper mode: Begin bagging process

when receive effective defined under level signal.

Without weighing hopper mode: Begin bagging process

when receive effective defined under level signal and

effective bag-nipped signal.

Ingredient weight ≥ target value - leading quantity of fast

feeding, shut fast feeding.

Ingredient weight ≥ target value - leading quantity of

moderate feeding, shut moderate feeding.

Page 58: Manual Tuxon-MC (Bagging Mode )

- 54

Ingredient weight ≥ target value - free fall value, shut

slow feeding.

2) t1: Begin bagging process after time delay t1(zeroing

first with weighing hopper or tare off without hopper).

The indicator show net weight instead of gross weight.

t2 / t3 / t4: No contrast time t2、 t3、 t4 in fast feeding,

moderate feeding and slow feeding to avoid feeding-

crushed weight.

T5: Over tolerance checking time t5.

T6: Fix value within time t6.

With weighing hopper mode: Discharge when receive

bag-nipped signal or wait.

Without weighing hopper mode: Pat bag or release bag.

T7:With weighing hopper mode: Shut off discharging after

time t7 when weight is less than near-zero value.

Without weighing hopper mode: Finish bagging after

time t7 when weight is less than near-zero value.

T8:Nip bag within t8 when receive effective signal.

T9: Release bag within t9 when receive effective signal.

3) Running status:Return stop status for effective stop input.

Stop feeding or discharging and return stop status for

effective urgent-stop input.

4) If recipe parameter F4=ON, check over / under tolerance

after every bagging finish. See Character 5.3 for details.

5) Pat bag: If F6 is ON, begin to pat bag after time t10(F6.4)

in discharging till finish, and then begin to release bag

after time t9. See Character 5.3 for details.

Page 59: Manual Tuxon-MC (Bagging Mode )

- 55 -

8 Serial port communication

Tuxon-MC has RS232/485 serial port to communicate with

host computer at two protocols: RS/ MODBUS.

8.1 RS protocol

Two modes:Continue(Cont) / Command(Read).

Data format:support all of data in operation parameter 4;

Baud rate: 1200/2400/4800/9600/19200/38400/57600

Code:ASCII

8.1.1 RS Continue (Cont)

When operation parameter 3=RS、3.1=Cont, indicator

send weighing data to host computer without command.

Data Format:

STX Scale

no. R S

Ingredient no.

State1

State2

G/N +/- Value CRC CR LF

Here:

STX —— 1bit,start character 02H

Scale no. —— 2bits,for example: 01 is 30H 31H

R —— 1bit,52H

S —— 1bit,53H

State 1 —— 1bit Bit

0 1 2 3 4 5 6 7

1 Run Pause Before feeding

Fast feeding

Moderate

feeding

Slow feeding

1

0 Stop Not

pause Not before

feeding

Page 60: Manual Tuxon-MC (Bagging Mode )

- 56

State 2 —— 1bit

Bit 0 1 2 3 4 5 6 7

1 Finish

feeding Fix

value Discharge

Finish batching

times Stable Overflow 1

0 Unstable

G/N —— (bit) , 0: net weight , 1~5: 0 , 6: 1

Bit 0 1 2 3 4 5 6 7

1 Net 0 0 0 0 0 1

0 Gross

+/- —— 1bit,sign:2BH(+)、2DH(-)

Value —— 7bit,including decimal point, if no, the highest bit

is space.

CRC —— 2bits,check sum,which add all of front digits and

transform decimal system, then take last two

digits to transform into ASCII.

CR —— 1bit,0DH

LF —— 1bit,0AH

The following data format for example:

02 30 31 52 53 79 54 41 2B 30 30 30 30 2E 38 36 32 35 0D 0A

Means present state at fast feeding,stable,bag-nipped, net

weight,display value +0.86 status.

8.1.2 Command mode (Read)

When operation parameters 3=RS、3.1=Read,the indicator

send present data to host computer only after received

command .

Page 61: Manual Tuxon-MC (Bagging Mode )

- 57 -

1) Host computer read“present status”

Read command:

STX Scale no. R S CRC CR LF

Correct response:Same as Cont mode(RS communication)

Wrong response:

STX Scale no. R S N O CRC CR LF

Here:

N —— 4E

O —— 4F

For example:02 30 31 52 53 36 34 0D 0A

Correct response:

02 30 31 52 53 79 54 41 2B 30 30 30 30 2E 38 36 32 35 0D 0A

Means present state at fast feeding,stable,bag-nipped, net

weight,display value +0.86 status.

Wrong response:02 30 31 52 53 4E 4F 32 31 0D 0A

2) Host computer read“present accumulative total”

Read command:

STX Scale no. R T CRC CR LF

Correct response:

STX Scale

no. R T

Total times

, Accumulative

total CRC CR LF

Wrong response:

STX Scale no. R T N O CRC CR LF

Here:

T —— 54H

,—— 2CH

Page 62: Manual Tuxon-MC (Bagging Mode )

- 58

Total times —— 4bits,0000~9999

Accumulative total —— 10bits,including decimal point

Read accumulative total command for example:

02 30 31 52 54 36 35 0D 0A

Correct response:

02 30 31 52 54 30 30 30 37 2C 30 30 30 30 30 34 32 2E 36

36 30 34 0D 0A

Means total times 7,accumulative value 42.660.

Wrong response: 02 30 31 52 54 4E 4F 32 32 0D 0A

3) Host computer read“recipes”

Read command:

STX Scale no. R R 00 Recipe

parameters CRC CR LF

Correct response:

STX

Scale no.

R R Ingredient

no. Recipe

parameters DDDD

DD CRC CR LF

Wrong response

STX Scale no. R R N O CRC CR LF

Here:

Ingredient no. —— fix 30 30

Recipe parameters —— 1bit,0:30H target value,1:31H

leading quantity of fast feeding,2:32H

leading quantity of moderate feeding,3:

33H free fall value, 4:34H near-zero value.

DDDDDD —— 6bits,recipe parameter values

For example, read target value command:

Page 63: Manual Tuxon-MC (Bagging Mode )

- 59 -

02 30 31 52 52 30 30 30 30 37 0D 0A

Correct response:

02 30 31 52 52 30 30 30 30 30 30 35 30 30 30 30 0D 0A

Means: Scale no. 1 target value is 500 .

Wrong response: 02 30 31 52 52 4E 4F 32 30 0D 0A

4) Host computer read“recipe parameters”

Read command:

STX Scale no. R F Parameters 0 CRC CR LF

Correct response:

STX Scale no. R F Parameters 0 DDDDDD CRC CR LF

Wrong response:

STX Scale no. R F N O CRC CR LF

Here:

F —— 46H

Parameters —— 3bits,such as feeding time delay F2.1 is

32H 31H 30H

DDDDDD —— 6bits,recipe parameter values

Read parameter F2.1 from scale no.1 command:

02 30 31 52 46 32 31 30 30 34 36 0D 0A

Correct response:

02 30 31 52 46 32 31 30 30 30 30 30 30 30 35 33 39 0D 0A

Means parameter F2.1 in scale no.1 is 0.5

Wrong response: 02 30 31 52 46 4E 4F 30 38 0D 0A

5) Host computer read“Bagging weight value”

Read command:

STX Scale no. R O 00 0 CRC CR LF

Page 64: Manual Tuxon-MC (Bagging Mode )

- 60

Correct response:

STX Scale no. R O 00 0 DDDDDD CRC CR LF

Wrong response:

STX Scale no. R O N O CRC CR LF

Here:

DDDDDD —— 6bits,batching value

For example: Read bagging weight value command:

02 30 31 52 4F 30 30 30 30 34 0D 0A

Correct response:

02 30 31 52 4F 30 30 30 30 30 30 35 30 30 39 37 0D 0A

Means scale no.1 bagging weight value is 500.

Wrong response: 02 30 31 52 4F 4E 4F 31 37 0D 0A

6) Host computer read“batching times”

Read command:

STX Scale no. R B CRC CR LF

Correct response:

STX Scale no. R B DDDDDD CRC CR LF

Wrong response:

STX Scale no. R B N O CRC CR LF

Here:

B —— 42H

DDDDDD —— 6bits,batching times

For example: Read batching times command:

Page 65: Manual Tuxon-MC (Bagging Mode )

- 61 -

02 30 31 52 42 34 37 0D 0A

Correct response:

02 30 31 52 42 30 30 30 31 30 30 33 36 0D 0A

Means scale no. 1 batching times are 100.

Wrong response: 02 30 31 52 42 4E 4F 30 34 0D 0A

7) Host computer read“decimal point”

Read command:

STX Scale no. R P CRC CR LF

Correct response:

STX Scale no. R P DDDDDD CRC CR LF

Wrong response:

STX Scale no. R P N O CRC CR LF

Here:

P —— 50H

DDDDDD —— 6bits,range at 0-4 (decimal point digits)

Read decimal point for example:

02 30 31 52 50 36 31 0D 0A

Correct response:

02 30 31 52 50 30 30 30 30 30 31 35 30 0D 0A

Means the decimal point of scale no.1 is 1bit.

Wrong response: 02 30 31 52 50 4E 4F 31 38 0D 0A

8) Host computer read“Recipe no.”

Read command:

STX Scale no. R N CRC CR LF

Page 66: Manual Tuxon-MC (Bagging Mode )

- 62

Correct response:

STX Scale no. R N DDDDDD CRC CR LF

Wrong response:

STX Scale no. R N N O CRC CR LF

Here:

DDDDDD —— 6bit,receipe no.

For example : Read recipe no. 02 30 31 52 4E 35 39 0D 0A

Correct response:

02 30 31 52 4E 30 30 30 30 30 31 34 38 0D 0A

Means scale no. 1 present recipe no. is 1 .

Wrong response: 02 30 31 52 4E 4E 4F 31 36 0D 0A

9) Host computer read “Operation parameters”

Read response:

STX Scale

no. R U

Operation parameters

0 CRC CR LF

Correct response:

STX Scale

no. R U

Operation parameters

0 DDDDDD CRC CR LF

Wrong response:

STX Scale no. R E N O CRC CR LF

Here:

U —— 55H

Operation parameters——3bits,such as zeroing range 7 is

37H 30H 30H

Page 67: Manual Tuxon-MC (Bagging Mode )

- 63 -

DDDDDD —— 6bits,operation parameter data.

For example:Read operation parameter 7 command

02 30 31 52 55 37 30 30 30 36 35 0D 0A

Correct response:

02 30 31 52 55 37 30 30 30 30 30 30 30 35 30 35 38 0D 0A

Meas Scale no. 1 operation parameter is 50。

Wrong response: 02 30 31 52 55 4E 4F 30 38 0D 0A

10) Host computer read“Restore for broken power”

Read command:

STX Scale no. R E CRC CR LF

Correct response:

STX Scale no. R E DDDDDD CRC CR LF

Wrong response:

STX Scale no. R E N O CRC CR LF

Here:

E —— 45H

DDDDDD —— 6bits,1 is “conti ?”status, 0 for not

“conti ?”status.

For examples: 02 30 31 52 45 35 30 0D 0A

Correct response:

02 30 31 52 45 30 30 30 30 30 31 34 38 0D 0A

Means scale no. 1 is in“conti?”status.

Wrong response: 02 30 31 52 4E 4E 4F 31 36 0D 0A

Page 68: Manual Tuxon-MC (Bagging Mode )

- 64

11) Host computer write“Recipe”

Write command:

STX Scale no. W R 00 Recipe

parameter DDDDDD CRC CR LF

Correct response:

STX Scale no. W R O K CRC CR LF

Wrong response:

STX Scale no. W R N O CRC CR LF

Here:

W —— 57H

K —— 4BH

Recipe parameter —— 1bit,0:30H target value,1:31H

leading quantity of fast feeding,2:32H

leading quantity of moderate,3:33H free

fall value; 4:34H near-zero value.

For example:Write target value=1500 in scale no.1

02 30 31 57 52 30 30 30 30 30 31 35 30 30 30 36 0D 0A

Correct response:

02 30 31 57 52 4F 4B 32 32 0D 0A

Means scale no. 1 has saved the weight value.

Wrong response: 02 30 31 57 52 4E 4F 32 35 0D 0A

12) Host computer write“Recipe parameter”

Write command:

STX Scale

no. W F

Set parameter

0 DDDDDD CRC CR LF

Page 69: Manual Tuxon-MC (Bagging Mode )

- 65 -

Correct response:

STX Scale no. W F O K CRC CR LF

Wrong response:

STX Scale no. W F N O CRC CR LF

Here:

F —— 46H

Set parameter —— 3bit,such as feeding time delay F2.1 is

32H 31H 30H

DDDDDD —— 6bit,set parameter value

For example:write parameter F2.1=3 to scale no.1

02 30 31 57 46 32 31 30 30 30 30 30 30 30 33 34 32 0D 0A

Correct response:

02 30 31 57 46 4F 4B 31 30 0D 0A

Means scale no. 1 has saved parameter F2.1=3.

Wrong response: 02 30 31 57 46 4E 4F 31 33 0D 0A

13) Host computer write operation parameter

Write command:

STX Scale

no. W U

operation parameter

0 DDDDDD CRC CR LF

Correct response:

STX Scale no. W U O K CRC CR LF

Wrong response:

STX Scale no. W U N O CRC CR LF

Here:

U —— 55H

Page 70: Manual Tuxon-MC (Bagging Mode )

- 66

Operation parameter —— 3bit,such as :zeroing range 7 is

37H 30H 30H

DDDDDD —— 6bit,operation parameter value

For example:Write 30 command on operation parameter 7

in scale no.1:

02 30 31 57 55 37 30 30 30 30 30 30 30 33 30 36 31 0D 0A

Correct response:

02 30 31 57 55 4F 4B 32 35 0D 0A

Means scale no. 1 has saved operation parameter 7.

Wrong response: 02 30 31 57 55 4E 4F 32 38 0D 0A

14) Host computer write“Recipe no.”

Write command:

STX Scale no. W N DD CRC CR LF

Correct response:

STX Scale no. W N O K CRC CR LF

Wrong response:

STX Scale no. W N N O CRC CR LF

Here:

DD —— 2bits,recipe no. range at 01-40.

For example: Write recipe no. 01 on scale no. 1 command:

02 30 31 57 4E 30 31 36 31 0D 0A

Correct response::

02 30 31 57 4E 4F 4B 31 38 0D 0A

Means scale no.1 has saved recipe no.

Wrong response: 02 30 31 57 4E 4E 4F 32 31 0D 0A

Page 71: Manual Tuxon-MC (Bagging Mode )

- 67 -

15) Host computer write“Batching times”

Write command:

STX Scale no. W B DDDDDD CRC CR LF

Correct response:

STX Scale no. W B O K CRC CR LF

Wrong response:

STX Scale no. W B N O CRC CR LF

Here:

B —— 42H

DDDDDD —— 6bits,range at 000000-009999.

For example:Write batching times 1000 on scale no.1:

02 30 31 57 42 30 30 31 30 30 30 34 31 0D 0A

Correct response:

02 30 31 57 42 4F 4B 30 36 0D 0A

Means scale no. 1 has saved batching times.

Wrong response: 02 30 31 57 42 4E 4F 30 39 0D 0A

16) Host computer write“Restor for broken power”

Write command:

STX Scale no. W E D CRC CR LF

Correct response:

STX Scale no. W E O K CRC CR LF

Wrong response:

STX Scale no. W E N O CRC CR LF

Page 72: Manual Tuxon-MC (Bagging Mode )

- 68

Here:

E —— 1bit,45H

D —— 1bit,range at 0 and 1,1 means to restore; 0

means not to restore.

For example:Write restore 01 command on scale no.1:

02 30 31 57 45 31 30 34 0D 0A

Correct response:

02 30 31 57 45 4F 4B 30 39 0D 0A

Means the command has been saved.

17) Host computer calibrate“decimal point”

Write command:

STX Scale no. C P Decimal

point CRC CR LF

Correct response:

STX Scale no. C P O K CRC CR LF

Wrong response:

STX Scale no. C P N O CRC CR LF

Here:

C —— 43H

P —— 50H

Decimal point ——1bit,range at 0~4

For example:Calibrate decimal point 3 on scale no.1:

02 30 31 43 50 33 39 37 0D 0A

Correct response:

02 30 31 43 50 4F 4B 30 30 0D 0A

Means scale no.1 has saved decimal point value.

Wrong response:02 30 31 43 50 4E 4F 30 33 0D 0A

Page 73: Manual Tuxon-MC (Bagging Mode )

- 69 -

18) Host computer“Add weights to calibrate zero”

Write command:

STX Scale no. C Z CRC CR LF

Correct response:

STX Scale no. C Z O K CRC CR LF

Wrong response:

STX Scale no. C Z N O CRC CR LF

Here:

Z —— 5AH

For example:Add weights to calibrate zero on scale no.1

02 30 31 43 5A 35 36 0D 0A

Correct response:02 30 31 43 5A 4F 4B 31 30 0D 0A

Means command has been performed.

Wrong response: 02 30 31 43 5A 4E 4F 31 33 0D 0A

19) Host computer“calibrate zero without weights”

Write command:

STX Scale no. C Y DDDDDD CRC CR LF

Correct response:

STX Scale no. C Y O K CRC CR LF

Wrong response:

STX Scale no. C Y N O CRC CR LF

Here:

C —— 43H

Y —— 59H

Page 74: Manual Tuxon-MC (Bagging Mode )

- 70

DDDDDD —— 6bits,which is millivolt value related zero.

For example:Write zero command on scale no.1

02 30 31 43 59 30 30 31 35 30 30 34 39 0D 0A

Correct response:02 30 31 43 59 4F 4B 30 39 0D 0A

Means scale no.1 has saved written data.

Wrong response: 02 30 31 43 59 4E 4F 31 32 0D 0A

20) Host computer calibrate“Minimum division and

maximum capacity”

Write command:

STX Scale no. C M DD DDDDDD CRC CR LF

Correct response:

STX Scale no. C M O K CRC CR LF

Wrong response:

STX Scale no. C M N O CRC CR LF

Here:

M —— 4DH

DD —— division value :1、2、5、10、20、50

DDDDDD —— 6bits,maximum capacity value

For example:Write division and maximum capacity

command on scale no.1

02 30 31 43 4D 30 31 30 31 30 30 30 30 32 39 0D 0A

Correct response:02 30 31 43 4D 4F 4B 39 37 0D 0A

Means scale no.1 has saved written value.

Wrong response: 02 30 31 43 4D 4E 4F 30 30 0D 0A

Page 75: Manual Tuxon-MC (Bagging Mode )

- 71 -

21) Host computer“Add weights to calibrate gain”

Write command:

STX Scale no. C G DDDDDD CRC CR LF

Correct response:

STX Scale no. C G O K CRC CR LF

Wrong response:

STX Scale no. C G N O CRC CR LF

Here:

G —— 47H

DDDDDD —— 6bit,gain value

For example:Calibrate gain command on scale no. 1

02 30 31 43 47 30 30 31 30 30 30 32 36 0D 0A

Correct response:02 30 31 43 47 4F 4B 39 31 0D 0A

Means scale no.1 has saved 10000.

Wrong response: 02 30 31 43 47 4E 4F 39 34 0D 0A

22) Host computer“calibrate gain without weights”

Write command:

STX Scale no. C L D1D1D1D1D1D1 D2D2D2D2D2D2 CRC CR LF

Correct response:

STX Scale no. C L O K CRC CR LF

Wrong response:

STX Scale no. C L N O CRC CR LF

Here:

Page 76: Manual Tuxon-MC (Bagging Mode )

- 72

L —— 4CH

D1D1D1D1D1D1 —— 6bits,gain millivolt value

D2D2D2D2D2D2 —— 6bits,gain weight value

For example:Calibrate gain without weights 4.110mV as

10000 on scale no. 1

02 30 31 43 4C 30 30 34 31 31 30 30 31 30 30 30 30 32 35

0D 0A

Correct response:02 30 31 43 4C 4F 4B 39 36 0D 0A

Means scale no. 1 has saved calibration value.

Wong response: 02 30 31 43 4C 4E 4F 39 39 0D 0A

23) Host computer“Manual discharging operation”

Write command:

STX Scale no. C D CRC CR LF

Correct response:

STX Scale no. C D O K CRC CR LF

Wrong response:

STX Scale no. C D N O CRC CR LF

Here:

D —— 44H

For example:Send discharging operation on scale no. 1

02 30 31 43 44 33 34 0D 0A

Correct response:02 30 31 43 44 4F 4B 38 38 0D 0A

Wrong response: 02 30 31 43 44 4E 4F 39 31 0D 0A

Page 77: Manual Tuxon-MC (Bagging Mode )

- 73 -

24) Host computer“Running operation”

Write command:

STX Scale no. C R CRC CR LF

Correct response:

STX Scale no. C R O K CRC CR LF

Wrong response:

STX Scale no. C R N O CRC CR LF

For example:Run scale no. 1 command

02 30 31 43 52 34 38 0D 0A

Correct response:02 30 31 43 52 4F 4B 30 32 0D 0A

Wrong response: 02 30 31 43 52 4E 4F 30 35 0D 0A

25) Host computer“Stop operation”

Write command:

STX Scale no. C T CRC CR LF

Correct response:

STX Scale no. C T O K CRC CR LF

Wrong response:

STX Scale no. C T N O CRC CR LF

For example:Stop scale no. 1 command

02 30 31 43 54 35 30 0D 0A

Correct response:02 30 31 43 54 4F 4B 30 34 0D 0A

Wrong response: 02 30 31 43 54 4E 4F 30 37 0D 0A

Page 78: Manual Tuxon-MC (Bagging Mode )

- 74

26) Host computer “Urgent-stop operation”

Write command:

STX Scale no. C J CRC CR LF

Correct response:

STX Scale no. C J O K CRC CR LF

Wrong response:

STX Scale no. C J N O CRC CR LF

Here:

J —— 4AH

For example:Urgent stop scale no. 1 command

02 30 31 43 4A 34 30 0D 0A

Correct response:02 30 31 43 4A 4F 4B 39 34 0D 0A

Wrong response: 02 30 31 43 4A 4E 4F 39 37 0D 0A

27) Host computer “Pause operation”

Write command:

STX Scale no. C S CRC CR LF

Correct response:

STX Scale no. C S O K CRC CR LF

Wrong response:

STX Scale no. C S N O CRC CR LF

For example:Pause scale no. 1

02 30 31 43 53 34 39 0D 0A

Correct response:02 30 31 43 53 4F 4B 30 33 0D 0A

Wrong response: 02 30 31 43 53 4E 4F 30 36 0D 0A

Page 79: Manual Tuxon-MC (Bagging Mode )

- 75 -

28) Host computer“Nip/release bag operation”

Write command:

STX Scale no. C Q CRC CR LF

Correct response:

STX Scale no. C Q O K CRC CR LF

Wrong response:

STX Scale no. C Q N O CRC CR LF

Here:

Q —— 51H

For example:Nip/release bag command on scale no. 1

02 30 31 43 51 34 37 0D 0A

Correct response:02 30 31 43 51 4F 4B 30 32 0D 0A

Wrong response: 02 30 31 43 51 4E 4F 30 34 0D 0A

29) Host computer“Manual slow feeding operation”

Write command:

STX Scale no. C O CRC CR LF

Correct response:

STX Scale no. C O O K CRC CR LF

Wrong response:

STX Scale no. C O N O CRC CR LF

For example:Manual slow feeding command on scale no.1

02 30 31 43 4F 34 35 0D 0A

Correct response:02 30 31 43 4F 4F 4B 39 39 0D 0A

Wrong response: 02 30 31 43 4F 4E 4F 30 32 0D 0A

Page 80: Manual Tuxon-MC (Bagging Mode )

- 76

30) Host computer“Clear alarm operation”

Write command:

STX Scale no. C B CRC CR LF

Correct response:

STX Scale no. C B O K CRC CR LF

Wrong response:

STX Scale no. C B N O CRC CR LF

For example:Clear alarm message on scale no. 1

02 30 31 43 42 33 32 0D 0A

Correct response:02 30 31 43 42 4F 4B 38 36 0D 0A

Wrong response: 02 30 31 43 42 4E 4F 38 39 0D 0A

31) Host computer“Zeroing operation”

Write command:

STX Scale no. C C CRC CR LF

Correct response:

STX Scale no. C C O K CRC CR LF

Wrong response:

STX Scale no. C C N O CRC CR LF

For example:Zeroing command on scale no.1

02 30 31 43 43 33 33 0D 0A

Correct response:02 30 31 43 43 4F 4B 38 37 0D 0A

Wrong response: 02 30 31 43 43 4E 4F 39 30 0D 0A

Page 81: Manual Tuxon-MC (Bagging Mode )

- 77 -

8.2 MODBUS protocol

8.2.1 Communication mode

1) Rtu: Every 8-bit byte in message are divided into 2pcs of

4-bit hexadecimal characters to transmit at binary code.

Data format:8- E-1,8- O-1,8- n-1,8- n-2(optional)

Baud rate: 1200/ 2400/ 4800/ 9600/ 19200/ 38400/57600

(optional)

Code: binary system

2) ASCII: Every 8-bit byte in message is transmitted as 2pcs

ASCII characters at ASCII code.

Data format: List in parameter F4 (optional)

Baud rate: 1200/ 2400/ 4800/ 9600/ 19200/ 38400/57600

(optional)

Code: ASCII

8.2.2 MODBUS communication address

PLC address

Display address

Description

The following items are only-read register(code 0x03)

40001 0000

Preset state 1

Bit Meaning

.0 0: Stop; 1: Run

.1 0:Not pause; 1:Pause

.2 Before feeding

.3 Fast feeding

.4 Moderate feeding

.5 Slow feeding

.6 Fix value

.7 Over/under tolerance

Page 82: Manual Tuxon-MC (Bagging Mode )

- 78

.8 Alarm

.9 Nip bag

.10 Pat bag

.11 Discharge

.12 Near-zero value

.13 Filling

.14 Finish batching

times

.15 Lack material

40002 0001

Preset state 2

Bit Meaning

.0 0: Gross;1: Net.

.1 0:Unstable 1:Stable

.2 0:None zero 1:zero

.3 0:Not overflow 1:Overflow

.4 0:Not minus value 1:minus value

40003 0002 Present weight

When weight overflow,

indicator display OFL,return value 0xFFFFFFFF.

40004 0003

40005 0004 Accumulate total times

Only read,when write,return error data address. 40006 0005

40007 0006 Accumulate total weight

Only read,when write,return error data address. 40008 0007

Page 83: Manual Tuxon-MC (Bagging Mode )

- 79 -

40009 0008 Alarm

message

(bit form)0:Finish

batching times; 1:Over

zeroing range;2:Unstable

when zeroing;3: Over

tolerance signal;4: Under

tolerance signal;5:Target

value is 0 when start.

The following items are both of read and write(write function code 0x10,read function code 0x03)

40014 0013 Target value F1.1

Note:Write value

should less than or same as max.capacity.

40015 0014

40016 0015 Leading quantity of fast feeding

F1.2 40017 0016

40018 0017 Leading

quantity of moderate feeding

F1.3

40019 0018

40020 0019 Free fall value

F1.4 40021 0020

40022 0021 Near-zero value

F1.5 40023 0022

40024 0023 Start-patting weight

F1.6 40025 0024

40026 0025 Over weight value

F3.1 40027 0026

40028 0027 Under weight value

F3.2 40029 0028

40030 0029 Maximum capacity

Max.capacity ≤ minimum division×30000 40031 0030

Page 84: Manual Tuxon-MC (Bagging Mode )

- 80

40032 0031 Zero

calibration with weights

Write in 0001H to take

present weight as zero

when weighing plate is

steady;

Read to return present

millivolt data at zero .

( See Note 1)

40033 0032

40034 0033 Gain

calibration with weights

Write in present actual weight, indicator calibrate gain to write in weight value according to present millivolt value; Read to return millivolt value at present weight.

40035 0034

40036 0035 Zero

calibration without weights

Write in millivolt value calibrated at zero point; Read to return present millivolt data at zero point. 40037 0036

40038 0037 Gain

(millivolt) calibration

without weights

Write in millivolt value of gain weight, indicator save first; Read to return millivolt data of present weight.

40039 0038

40040 0039 Gain (weight)

calibration without weights

Write in weight value correlated with gain millivolt data after writing

in gain millivolt data,Gain

calibration proceeded by the two values when write

in the register;Read to

return 0000H.

40041 0040

Page 85: Manual Tuxon-MC (Bagging Mode )

- 81 -

The following items are two bytes and available to read and write(writing code 0x06,read code 0x03)

40042 0041 Decimal point

0000H:0bit;0001H:1bit;

0002H:2bit;0003H:3bit;0004H:4bit

40043 0042 Mini division 0001H:1;0002H:2;

0005H:5;000AH:10;

00014:20;0032H:50 40044 0043

Load cell sensitivity

0002H:2mV/V 0003H:3mV/V

40045 0044 Feeding time

delay t1 F2.1

0000H~03E7H

(00.0~99.9)

40046 0045 No contrast time

t2 of fast feeding

F2.2 0000H~03E7H

(00.0~99.9)

40047 0046

No contrast time

t3 of moderate

feeding

F2.3 0000H~03E7H

(00.0~99.9)

40048 0047

No contrast time

t4 of slow

feeding

F2.4 0000H~03E7H

(00.0~99.9)

40049 0048

Check

tolerance

time t5

F2.5 0000H~03E7H

(00.0~99.9)

40050 0049 Fix value time

t6 F2.6

0000H~03E7H

(00.0~99.9)

40051 0050 Discharging

time delay t7 F2.7

0000H~03E7H

(00.0~99.9)

Page 86: Manual Tuxon-MC (Bagging Mode )

- 82

40052 0051 Bag-nipped

time t8 F2.8

0000H~03E7H

(00.0~99.9)

40053 0052 Bag-released

time t9 F2.9

0000H~03E7H

(00.0~99.9)

40054 0053 Over/under tolerance alarm time

F3.4 0000H~03E7H

(00.0~99.9)

40055 0054 Free fall

compensation times

F4.1 0000H~0063H

(00~99)

40056 0055 Free fall

compensation range

F4.2 0000H~0063H

(00~99%)

40057 0056 Free fall

compensation percent

F4.3

0 for 0%;

1 for 100%;

2 for 50%;

3 for 25%.

40058 0057 Jog feeding

times F5.1

0000H~0063H

(00~99)

40059 0058 Jog feeding

effective time F5.2

0000H~03E7H

(00.0~99.9)

40060 0059 Jog feeding alternative

time F5.3

0000H~03E7H

(00.0~99.9)

40061 0060 Patting bag

mode F6.1

0:P_ADD;

1:P_End;

2:P_AEn

40062 0061 Patting bag

times in feeding

F6.2 0000H~03E7H

(000~999)

Page 87: Manual Tuxon-MC (Bagging Mode )

- 83 -

40063 0062 Patting bag times after fixed value

F6.3 0000H~03E7H

(000~999)

40064 0063 Delay time

before patting bag

F6.4 0000H~03E7H

(00.0~99.9)

40065 0064 High level

time in patting bag

F6.5 0000H~03E7H

(00.0~99.9)

40066 0065 Low level

time in patting bag

F6.6 0000H~03E7H

(00.0~99.9)

40067 0066 Shaking bag delay time

F6.8 0000H~03E7H

(00.0~99.9)

40068 0067

Control shaking switch

in moderate and slow feeding

F7.1

0:d_s;

1:d_d;

2:d_ds

40069 0068 Jog moderate

feeding effective time

F7.2 0000H~03E7H

(00.0~99.9)

40070 0069

Jog moderate feeding

ineffective time

F7.3 0000H~03E7H

(00.0~99.9)

40071 0070 Jog feeding of slow feeding effective time

F7.4 0000H~03E7H

(00.0~99.9)

40072 0071 Jog feeding of slow feeding

ineffective time F7.5

0000H~03E7H

(00.0~99.9)

Page 88: Manual Tuxon-MC (Bagging Mode )

- 84

40074 0073 Sub-display

data when stop F9

0:dsp_rE;

1:dsp_dA;

2:rdp_s2;

3:rdp_s3.

40075 0074 Sub-display

data when run F10

0:rdp_fi;

1:rdp_s1;

2:rdp_s2;

3:rdp_s3.

40076 0075 Recipe no. 1~40

40077 0076

Reserve Read zero from the

address. … …

40079 0078

40080 0079 Zero tracking

range 6

0000H~0063H

(00~99)

40081 0080 Zeroing range 7 0001H~0063H

(01~99)

40082 0081 Stability range

8 0001H~0063H

(01~99)

40083 0082 AD filter 9 0000H~0009H

(0~9)

40084 0083 Stability filter 10 0000H~0009H

(0~9)

40085 0084 Automatic

zeroing alternation

11 0000H~0063H

(00~99)

40086 0085 Analog mode 18 0000H~0007H

40087 0086

Reserve Read zero from the

address. … …

40089 0088

Page 89: Manual Tuxon-MC (Bagging Mode )

- 85 -

40090 0089 Batching

times 0000H~270FH

40091 0090

Back up / Restore initial

setting

Write:Initialization 8800 initialize all parameters; 8801 initialize calibration 8802 initialize operation parameters; 8803 initialize recipe parameters; 8804 initialize IO definition. Back up: (The highest bit change to 6); Restore: (The highest bit change to 7). Return 0 to read.

40092 0091 Start / Stop I/O testing

Write only in stop status. Write 1 to start I/O testing;Write 0 to exit. Read:1 for I/O testing status.0 for not I/O testing status.

40093 0092 Input testing

Write: not permit. ( Change only in stop) Read: Input IN1 ~ IN4 from low bit to high bit, 1 for effective input, 0 for ineffective input.

40094 0093 Output testing

Write: Output from OUT1 ~ OUT10 from low bit to high bit, 1 for effective output, 0 for ineffective output. Read: Return present output status.

Page 90: Manual Tuxon-MC (Bagging Mode )

- 86

40095 0094

I/O self- definition

IN1

Write: write

value related

with I/O

definition. For

example, if

define IN2 as

I3, user

should write 3

in IN2

register.

( Change only

in stop) Read: Return present I/O self-definition.

40096 0095 IN2

40097 0096 IN3

40098 0097 IN4

40099 0098 OUT1

40100 0099 OUT2

40101 0100 OUT3

40102 0101 OUT4

40103 0102 OUT5

40104 0103 OUT6

40105 0104 OUT7

40106 0105 OUT8

40107 0106 OUT9

40108 0107 OUT10

Following items are bits and available to read and write in loops (function code:0x01, 0x05)

00112 0111 Restore when

power off Write:FF00H = ON

0000H = OFF

Read:0001H = ON

0000H = OFF

Note:

Tare-off / zeroing

selection:

FF00H=b_tare;0000H=b_zero Restore for broken

power:

00113 0112 Auto- zeroing

when power on

00114 0113 Bagging mode

00115 0114 Gross/net

mode

00116 0115 Feeding mode

00117 0116 Auto /manual releasing bag

Page 91: Manual Tuxon-MC (Bagging Mode )

- 87 -

00118 0117 Manual

discharging counted in total

Write:FF00H=yes;000H=no

Read:conti?1 for

conti; 0 for not conti.

00119 0118 Over / under

tolerance recorded total

00120 0119 Save when power off

00121 0120 Over/under

tolerance alarm

00122 0121 Over/under tolerance

pause

00123 0122 Free fall

complement

00124 0123 Under

tolerance complement

00125 0124 Pat bag

00126 0125 Shake bag

00127 0126 Jog feeding

00128 0127 Display lock

00129 0128

Reserve Read zero from the

address. … …

00132 0131

00133 0132 Input state

Read:1 for effective,

0 for ineffective;

Write:Not permit.

00134 0133 Input state in2 not permit to write.

Page 92: Manual Tuxon-MC (Bagging Mode )

- 88

00135 0134 Input state In3 not permit to write.

00136 0135 Input state In4 not permit to write.

00137 0136 Output state

Read:From low to high

represent out1-out10,

which 1 for effective,0

for ineffective;

Write:Not permit

00138 0137 Output state out2 not permit to write

00139 0138 Output state out3 not permit to write

00140 0139 Output state out4 not permit to write

00141 0140 Output state out5 not permit to write

00142 0141 Output state out6 not permit to write

00143 0142 Output state out7 not permit to write

00144 0143 Output state out8 not permit to write

00145 0144 Output state out9 not permit to write

00146 0145 Output state out10 not permit to write

00147 0146 Start

Read:

Run = 1;

Not run= 0 Only

write

FF00H

= on

00148 0147 Urgent stop

Read:

Stop = 1;

Not stop=0

00149 0148 Stop

Read:

Stop = 1;

Not stop=0

Page 93: Manual Tuxon-MC (Bagging Mode )

- 89 -

00150 0149 Pause Read:Pause=1; Not pause = 0

00151 0150 Zeroing

Read:

Zeroing=1;

Not zeroing=0

00152 0151 Clear alarm

Read :

Cleared=1 ;

Not clear = 0

00153 0152 Select recipe Read : always

read OFF

00154 0153 Nip/release

bag

Read:

Nip bag=1;Release bag=0

Write

FF00=

on;

0000

=off

00155 0154 Manual

discharging

Read:Effective

discharging=1;ineffective discharging = 0

00156 0155 Manual slow

feeding

Read:effective

slow feeding=1 ineffective slow feeding = 0

00157 0156 Lock keypad

Read:

Locked = 1;

Not lock = 0

00158 0157 Upper filling

level

Read:

Effective = 1;Ineffective = 0

Page 94: Manual Tuxon-MC (Bagging Mode )

- 90

00159 0158 Under filling

level

Read:

Effective = 1;Ineffective = 0

Only

read 00160 0159

Discharging- closed

completely signal

Read:

Effective = 1;Ineffective = 0

00161 0160 Complete

nipping bag signal

Read:

Effective = 1;Ineffective = 0

00162 0161 Clear

accumulate total

Read:

Cleared = 1;Not clear = 0

Only

write

ON

00163 0162 Breaking input

Read:

Effective = 1;Ineffective = 0

Only

read

8.2.3 Function code

Above Modbus communication protocols have five function

codes:01 read coil、03 read register、05 force single coil、

06 preset single register、16( 10 Hex) preset several

registers.

◆ 01 read coil

Inquiry:Regulate coil start and quantities.

Response:

a) Every coil state in response message is corresponding

to every data in data area;1=ON;0=OFF。The LSB in

first byte is start address in inquiry. Other coils are in

seriation from lowest to highest in the byte till full of 8pcs,

next byte same seriation.

Page 95: Manual Tuxon-MC (Bagging Mode )

- 91 -

b) If they are not 8 multiples, the last byte is full of zero

from the remain to the highest,which byte sections

indicate all of byte quantities.

For example:Inquiry weighing indicator 01 to read 40- 43

coil (Coil 43- 40 related status:0- 0- 1- 0).

1) RTU communication mode:

Inquiry command:

Address Function

code Start

address Coil

quantity CRC parity

1byte 1byte 2byte 2byte 2byte

Correct response:

Address Function

code Account

byte Data area

CRC parity

1byte 1byte 1byte 1byte 2byte

Inquiry command:01 01 00 28 00 04 BD C1

Correct response:01 01 01 02 D0 49

2) ASCII communication mode:

Inquiry command:

Start Address Function

code Start

address Coil

quantities LRC parity

Stop

1byte 2byte 2byte 4byte 4byte 2byte 2byte

Correct response:

Start Address Function

code Account

byte Data area

LRC parity

Stop

1byte 2byte 2byte 2byte 2byte 2byte 2byte

Page 96: Manual Tuxon-MC (Bagging Mode )

- 92

Inquiry command: 3A 30 31 30 31 30 30 32 38 30 30 30 34

44 32 0D 0A

Correct response:3A 30 31 30 31 30 31 30 32 46 42 0D 0A

(Coil 43- 40 related status:0- 0- 1- 0)

03 read register

Inquiry:Regulate to read register start address and register

quantities.

Response:Regulate read register byte quantities, every

register relate 2bytes respectively;Message also has data

from every read register.

For example:read register 0007、0008(Register 0007、0008

respective data:0(Hex:0000H)、5(Hex:0005H)).

1) RTU communication mode:

Inquiry command:

Address Function

code Start

address

Inquiry register quantity

CRC parity

1byte 1byte 2byte 2byte 2byte

Correct response:

Address Function

code Account

byte Register

(0007) data Register

(0008) data CRC parity

1byte 1byte 1byte 2byte 2byte 2byte

Inquiry command:01 03 00 07 00 02 75 CA

Correct response:01 03 04 00 00 00 05 3A 30

Page 97: Manual Tuxon-MC (Bagging Mode )

- 93 -

2) ASCII communication mode:

Inquiry command:

Start Address Function

code Start

address

Inquiry register quantity

LRC parity

Stop

1byte 2byte 2byte 4byte 4byte 2byte 2byte

Correct response:

Start Address Function

code Account

byte

Register (0007) data

Register (0008) data

LRC parity

Stop

1byte 2byte 2byte 2byte 2byte 2byte 2byte 2byte

Inquiry command: 3A 30 31 30 33 30 30 30 37 30 30 30 32

46 33 0D 0A

Correct response:3A 30 31 30 33 30 34 30 30 30 30 30 30

30 35 46 33 0D 0A

◆ 05 force single coil

Force:Regulate force coil address;and one normal item in

force data area,regulate requested coil ON/ OFF state:

FF00 for ON,0000H for OFF,other data is ineffective to coil.

Response:Return normal response for force coil.

For example:Force 0056 coil is ON in weighing indicator 01.

1) RTU communication mode:

Force command:

Address Function

code Coil

address Force data

CRC parity

1byte 1byte 2byte 2byte 2byte

Page 98: Manual Tuxon-MC (Bagging Mode )

- 94

Correct response:

Address Function

code Coil

address Force data

CRC parity

1byte 1byte 2byte 2byte 2byte

Force command:01 05 00 38 FF 00 0D F7

Correct response:01 05 00 38 FF 00 0D F7

2) ASCII communication mode:

Force command:

Start Address Function

code Coil

address Force data

LRC parity

Stop

1byte 2byte 2byte 4byte 4byte 2byte 2byte

Correct response:

Start Address Function

code Coil

address Force data

LRC parity

Stop

1byte 2byte 2byte 4byte 4byte 2byte 2byte

Force command:3A 30 31 30 35 30 30 33 38 46 46 30 30

43 33 0D 0A

Correct response:3A 30 31 30 35 30 30 33 38 46 46 30 30

43 33 0D 0A

◆ 06 preset single register

Preset:Regulate to preset single register address and data.

Response:Return normal response after register is preset.

For example:Request 0009 register in weighing indicator 01

is preset 0005H(register 0009 data:5(Hex:0005H)).

Page 99: Manual Tuxon-MC (Bagging Mode )

- 95 -

1) RTU communication mode:

Preset command:

Address Function

code Preset register

address Preset data

CRC parity

1byte 1byte 2byte 2byte 2byte

Correct response:

Address Function

code Preset register

address Preset data

CRC parity

1byte 1byte 2byte 2byte 2byte

Preset command:01 06 00 09 00 05 99 CB

Correct response:01 06 00 09 00 05 99 CB

2) ASCII communication mode:

Preset command:

Start Address Function

code

Preset register address

Preset data

LRC parity

Stop

1byte 2byte 2byte 4byte 4byte 2byte 2byte

Correct response:

Start Address Function

code

Preset register address

Preset data

LRC parity

Stop

1byte 2byte 2byte 4byte 4byte 2byte 2byte

Preset command:3A 30 31 30 36 30 30 30 39 30 30 30 35

45 42 0D 0A

Correct response:3A 30 31 30 36 30 30 30 39 30 30 30 35

45 42 0D 0A

Page 100: Manual Tuxon-MC (Bagging Mode )

- 96

◆16(10 hex) Preset several registers

Preset start address in message and fixed value in data.

Response:Return address, function code, start address and

preset register quantity.

For example:Preset 2 registers in weighing indicator 01:

start register is 0030. Preset value is 0001H and 7318H

1) RTU communication mode:

Preset command:

Address Function

code Start

address Register quantity

Account byte

Preset data

CRC parity

1byte 1byte 2byte 2byte 1byte 4byte 2byte

Correct response:

Address Function

code Start

address Register quantity

CRC parity

1byte 1byte 2byte 2byte 2byte

Preset command:01 10 00 1E 00 02 04 00 01 73 18 07 D5

Correct response:01 10 00 1E 00 02 21 CE

2) ASCII communication mode:

Preset command:

Start Address Function

code Start

address Register quantity

Account byte

Preset data

LRC parity

Stop

1byte 2byte 2byte 4byte 4byte 2byte 8byte 2byte 2byte

Correct response:

Start Address Function

code Start

address Register quantity

LRC parity

Stop

1byte 2byte 2byte 4byte 4byte 2byte 2byte

Page 101: Manual Tuxon-MC (Bagging Mode )

- 97 -

Preset command:3A 30 31 31 30 30 30 31 45 30 30 30 32

30 34 30 30 30 31 31 43 39 36 31 38 0D 0A

Correctresponse: 3A 30 31 31 30 30 30 31 45 30 30 30 32

43 46 0D 0A

8.2.4 MODBUS communication error message

When weighing indicator check other error message

except parity code( CRC or LRC),indicator will send

message to host computer, the highest in function code is 1,

which means function code from weighing indicator to host

computer is added 128 based on function code from host

computer(For example: read register command 03H will be

changed to 83H).

Error code:

02: error data -received address, which is not permitted by

weighing indicator.

03: error inquiry data, which is not permitted by indicator.

Error message format:

1)RTU communication mode:

Address Function code Error code CRC parity

1byte 1byte 1byte 2byte

2)ASCII communication mode:

Start Address Function

code Error code

LRC parity

Stop

1byte 2byte 2byte 2byte 2byte 2byte

Page 102: Manual Tuxon-MC (Bagging Mode )

- 98

For example, host computer read coil(0040) by code 03.

1) RTU communication mode:

Inquiry command:01 03 00 28 00 01 04 02

Error response:01 83 02 C0 F1

2) ASCII communication mode:

Inquiry command:3A 30 31 30 33 30 30 32 38 30 30 30

31 44 33 0D 0A

Error response:3A 30 31 38 33 30 32 37 41 0D 0A

From response message, the present error code is 02,

which means the present received data address is error, not

permit by weighing indicator.

9 Error and alarm message

ERROR :Input wrong value; please refer to related

parameter range to input again.

ERROR2:The present weight value is out of zeroing range.

ERROR3:Scale platform is not stable in zeroing.

ERROR4:Input wrong password more than 3 times.

ERROR5:Alarm for batching times

ERROR6:Alarm for discharging monitor

ERROR7:Alarm for batching monitor

ERROR8:Alarm for total target value is over maximum

capacity or target value is 0.

ERROR9:Alarm for compensatory feeding

OVER :The load cell sign is too big in zero calibration.

UNDER :The load cell sign is too small in zero calibration.

OFL :Overflow