manual monitoring and alarm system micromon -...

20
Monitoring and Alarm System Micromon Manual Refrigeration and Air Conditioning Controls REFRIGERATION AND AIR CONDITIONING

Upload: trinhdat

Post on 09-Apr-2018

238 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Monitoring and Alarm SystemMicromon

Manual

Refrigeration and Air Conditioning Controls

R E F R I G E R A T I O N A N D A I R C O N D I T I O N I N G

Page 2: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

2 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

Contents

Introduction 3

System Overview 4Printing 4Alarms 4Security 4Alarm Mute Key 5Left Arrow Key 5Menu Key 5

Key Operation 5Print Key 5Up Arrow Key 5Down Arrow Key 5Enter Key 6Operator/Equipment Safety 6Right Arrow Key 6Multiple Key Functions 6

Easy Setup 7

Extended Menu 8Installation Name 8Temperature Units 8Date Format 8Name 8Type 8Alarm Settings 9Printout Options 9Log Action 9Graph Action 9Units of Measurement 9

4-20mA Point Type 10Passcode Setup 10Log/Graph Setup 10Modem Dialout Setup 11Dialout 11Call Type 11Number 12Pager Info 12Send 12Modem Configuration 12Baud Rate 12Point Detail 13Point Overview 13

Operation via the Key Pad 13Dial 13Answer 13Daylight Saving 13Point Offset 14Graphics 14Single Point Log Printout 14Inhibiting a Point 14Point Overwiew 15

Main Menu 15Point Alarm List 15Event History 15Alarm Mode 15Muting and Clearing an Alarm 15

Alarm History 15Easy Setup 16Software Version 16Print Menu 16Alarm History 16Alarm Action 17Setup Information 17

Maintenance 18Cleaning 18Service 18

Full Character Set 18

Alphanumeric Character Set 18

Appendix A 19'AKM' Call Type 19

Page 3: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 3

Introduction

The Micromon has been developed to provide a comprehensive,yet simple-to-use means of monitoring and recording refrigera-tion temperatures and other aspects of refrigeration plantoperation. It is intended for use in small to medium food storageoperations (for example a small supermarket) where compliancewith the Food Hygiene Regulations is to be demonstrated.

Designed for operational simplicity, the system once configuredwill display the status of each input point. Further details on anyaspect of the operation of the installation are available via thekey pad. In addition there is the ability for authorised personnelto make adjustments to the monitoring settings. Historical data isstored within the system and may be viewed or printed on aregular basis. The data is accessible both on and off-site via theexternal modem connection and alarm calls can also be gener-ated if required.

The Micromon has been designed in such a way that programming of the system can easily be performed by untrainedpersonnel, in a matter of minutes. At power up, the programmer is prompted to make a few selections, all driven by easy menuoptions and icons.

The following sections provide a description of the Micromon, and the remainder of the manual provides further detail on theconfiguration, operation and maintenance of the system. It is recommended that the appropriate part(s) are studied before anyattempt is made to use the system.

Safety

To prevent accidents arising from improper handling, installation or operation, please read this manual carefully.

Validity

This document was made in October 2001 and applies to Danfoss Micromon with software version B2.2.

When the Micromon initially powers up the 'Easy Setup' procedure will start as follows.

Page 4: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

4 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

System Overview The Micromon consists ofa central monitoring unitwhich can monitor up to 16local sensors or inputswhich are usually locatedadjacent to the equipmentin question for examplespecific refrigerated areas(chiller cabinets, freezers,cold rooms or plantrooms). The precise layoutand configuration of thesesensors are specific toeach installation, and it isnot necessary for a typicaloperator to be familiar withthe operation of thesensors.

The Micromon provides audio and visual alarms whenever an input exceeds itspre-set alarm levels. The system can be pre-set to dial-out using a digital dialler orvia a modem whenever an alarm occurs (via "extended setup menu").

Security is provided by having passcode access to the protected settings. In thecase of mains failure, an alarm is triggered after a delay. The system can be pre-set to dial-out to an external telephone number if required.The Micromon will always FAIL SAFE (except for modem dailout).

If hard copy details of the monitor readings are required, a parallel printer port isprovided which can be connected to an ESC/P2 Epson compatible parallel printer.

Alarms

Security

Printing

Page 5: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 5

Key Operation

Alarm Mute Key

The functions of the keys on the front panel of the Micromon are described in thefollowing sections.

Main Functions

Use this key to acknowledge and mute the siren or reset the alarm. The red‘ALARM’ backlight will stop flashing and remain steady. Any ‘HIGH’ or ‘LOW’alarm indication will also stop scrolling and remain steady.

Secondary Function

Operates as a shift key to give extended functions with other keys.

Main Functions

Use this key to select the main or previous menu from any other screen.

Secondary Functions

Cancels input data without storing in edit fields ('ESC' key).

Main Functions

Use this key to select the Print Menu, except when in Alarm/Event history where itwill directly print out a list.

Secondary Functions

Changes the Case/Sign in edit fields.

Main Functions

Use this key to scroll the highlight upwards on a menu screen. If the highlight ispositioned on the first line of a menu, pressing this key will force the highlight tothe bottom of the menu. In addition, when a character entry field has beenselected, this key is used to increment the displayed value in the entry field.

Secondary Functions

Moves through the Point Detail screens, moves the cursor on the Overviewscreen and zooms in on the Graph screen.

Main Functions

Use this key to scroll the highlight downwards on a menu screen. If the highlightis positioned on the last line of a menu, pressing this key will force the highlight tothe top of the menu. In addition, when a character entry field has been selected,this key is used to decrement the displayed value in the entry field.

Secondary Functions

Moves through the Point Detail screens, moves the cursor on the Overviewscreen and zooms out on the Graph screen.

Main Functions

Use this key to move the cursor to the left when a character entry field has beenselected. In addition when an option has more than one screen associated with it(e.g. Point Detail), use this key to display the previous screen.

Secondary Functions

Moves the cursor on the Overview screen and moves the Graph Cursor.Main Functions

Menu Key

Print Key

Up Arrow Key

Down Arrow Key

Left Arrow Key

Page 6: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

6 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

Right Arrow Key Use this key to move the cursor to the right when a character entry field has beenselected. In addition when an option has more than one screen associated with it(e.g. Point Detail), use this key to display the next screen.

Secondary Functions

Moves the cursor on the Overview screen and moves the Graph cursor.

Main Functions

Use this key to select an item from a menu or to enter a value and move thecursor to the next entry field ('↵' key).

Secondary Functions

Inhibits points, adds the Graph cursor to the Graph screen and selects points onthe Overview screen.

Backspace in edit fields.

Adjusts Screen Contrast.

Accented/special characters editing mode.orSort and display alarms by point when in Point Detail Screen.

This equipment is safe to operate as long as the instructions in this manual arefollowed. High voltages are present inside the Micromon and the front accesspanel should not be opened while power is applied to the system.Ensure that mains power is disconnected before any maintenance is carried out.It is assumed that operators of the system will have adequate training on its use.Danfoss accept no liability for loss or damage caused by misuse of the equipment.

Enter Key

Multiple Key Functions

Operator/Equipment Safety

+

+

OR

+

Page 7: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 7

Easy Setup

Language

Clock

Site Name

Number Points Used

Application

To select a language, using the ' ', ' ', ' ' or ' ' keys move the selectionbox to the required language, then press the '↵↵↵↵↵' key to continue.

To modify the clock settings, using the ' 'and ' ' keys move the cursor to therequired field, then the ' ' and ' ' keys to modify the time and date, press the'↵↵↵↵↵' key to enter setting and the ' ' key to continue to the next screen.

To enter a site name, use the ' ' and ' ' keys to move the cursor, then the '' and ' ' keys to select the required characters. Press the ' ' key to continueto the next screen.

Use this screen to select the required number of points to be used. Use the ' 'and ' ' keys to increment up or down to the required number.

This screen is used select the application of those points that have just beenselected in the previous screen. Use the ' ' and ' ' keys to move the cursor tothe required point, then the ' ' and ' ' keys to move the 'tick' symbol to therequired application. Press the ' ' key to accept and continue to the nextscreen.

This screen is for setting the alarm parameters for the three different applications.These are "global" settings, e.g. the high, low and delay values entered for'Frozen' will apply to all points that have been set as 'Frozen' in the previousApplication setting screen.

Use the '↵↵↵↵↵' key to select each field and the ' or ' ' key to adjust each setting.Press the ' ' key to accept and continue to the next screen.

This screen is displayed giving a summary of all the points that have just beenset. Press the '↵↵↵↵↵' key to finally accept the setting or press the ' ' key to go

Alarm Parameters

Page 8: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

8 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

Summary back and modify setup. If a point's application settings are changed from thedefault (see Point Setup), then a 'dot' will be displayed above the 'tick' symbol as

shown .

If the ' ' key is pressed, then the 'Extended Setup Menu' will be displayed (seefurther for details).

The 'Extended Menu' allows more detailed settings for the points and theremaining parameters.

The installation name is displayed on the Point Overview screen, the AlarmHistory screen, the Event History screen and on the various printouts.To set the installation name, select the Installation Name option from the SetupMenu.

Enter the installation name using the ‘ ’ or ‘ ’ keys to scroll through thecharacter list and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively.You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the

cursor and the ‘ ‘ and ‘ ‘ keys together to change the accents of certaincharacters, i.e, ë, ø, â, etc. When the installation name is complete, press ‘↵↵↵↵↵’, then' ' to return to the Setup Menu. Next time you display the Point Overviewscreen the installation name will appear at the top of the screen.

The Micromon's temperature unit of measurement can be set to either Fahrenheitor Centigrade. To select the temperature unit, press the '↵↵↵↵↵' key to move the activefield box around the 'temperature units' field, then use the ‘ ’ or ‘ ’ key to togglebetween Fahrenheit and Centigrade.

The date format of the Micromon unit can be set to either 'DD/MM' or 'MM/DD'. Toselect the date format required, press the '↵↵↵↵↵' key to move the active field boxaround the 'Date Format' field, then use the ‘ ’ or ‘ ’ key to toggle between 'DD/MM' and 'MM/DD'.

To select a different point number, use the ‘ ’ or ‘ ’ key. As each number isselected, the settings for the selected point are displayed.

To set the name of an individual point, ensure that the cursor is on the correctpoint number and press ‘↵↵↵↵↵’. The cursor will move to the Name field. Enter theinstallation name using the ‘ ’or ‘ ’ keys to scroll through the character list andthe ‘ ’ or ‘ ’ key to move the cursor left or right respectively. A maximum of 18characters can be entered into this field.You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the

cursor and ‘ ‘ to change case. When the installation name is complete, press‘↵↵↵↵↵’. The edit box will move onto the next field.

The point type can be modified from the default, set in the 'Easy Setup'. This canbe modified by using the ‘ ’ or ‘ ’ keys to scroll the point types. The point typesavailable to each point depend on which 'Alarm Parameter' settings have beenpreviously set in the 'Easy Setup', of which are defined as follows:

Frozen, ChillRTD PT1000 temperature probe (-100 to +100°C)

Extended Menu

Installation Name

Temperature Units

Date Format

Point Setup

Name

Type

Page 9: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 9

EKS EKS111 probe (-35 to +85°C)

DigitalNO Normally openNC Normally closed

To set the units of measurement, repeatedly press ‘↵↵↵↵↵’ to scroll through the fieldsuntil the Units field is highlighted.

Enter the units required using the ‘ ’ or ‘ ’ keys to scroll through the characterlist and the’ ' or ‘ ’ key to move the cursor left or right respectively.Note: This is a text field only and does not effect the operation of the system.

You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the

cursor and ‘ ‘ to change case. When the units have been set, press ‘↵↵↵↵↵’. Theedit box will move onto the next field.

Select the point as previously described. Repeatedly press ‘↵↵↵↵↵’ to scroll throughthe fields until the High field is highlighted. Set this field to set the value at orabove which an alarm will occur by using the ‘ ’ or ‘ ’ keys to scroll through thecharacter list and the ‘ ’ or ‘ ’ key to move the cursor left or right respectively.When the high temperature alarm point has been set, press ‘↵↵↵↵↵’. The edit box willmove onto the next field.Repeat the operation for the Low field, to set the value at or below which an alarmwill occur. Press ‘↵↵↵↵↵’ to move the edit box onto the next field.

Repeat the operation for the Delay field. Set the length of time (in minutes) that thefault must be present before an alarm is raised.

Log printouts are available for selected points on a timed or demand basis via theprint menu. 'Timed' means the Micromon is programmed to automatically print a

log at preselected intervals. A log printout can also be initiated via the ‘ ‘ key onthe keypad (manual). When a log is printed only points with the log action fieldappropriately set will be output. The available settings are:

Off Set this point to OFF if you do not want this point to beshown on any log printouts.

Timed The point will be included only in a 'Timed' log printout.

Manual The point will be included only in a 'Manual' log printout.

On Set this option to ON if you require this point to be included in alllog printouts.

Repeatedly press ‘↵↵↵↵↵’ to scroll through the fields until the Log field is highlighted.Use the ' ' or ' ' keys to set the required log action and press ‘↵↵↵↵↵’ to move thecursor onto the next field.

Graph printouts are available for selected points on a timed or demand basis viathe print menu. 'Timed' means the Micromon is programmed to automatically print

a graph at preselected intervals. A graph printout can also be initiated via the ‘ ‘key on the keypad (manual).When a graph is printed only points with the graphaction field appropriately set will be output. The available settings are:

Off Set this option to OFF if you do not want this pointgraph to be shown on any graph printouts.

Timed The graph for this point will be included only in a 'Timed' graphprintout.

Manual The graph for the point will be included only in a 'Manual' graphprintout.

Alarm Settings

Log Action

Graph Action

Printout Options

Units of Measurement

Page 10: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

10 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

On Set this option to ON if you require a graph for thispoint to be included in all graph printouts.

Repeatedly press ‘↵↵↵↵↵‘ to scroll through the fields until the Graph field is highlighted.Use the ' ' or ' ' keys to set the required graph action.

A point can be setup for 4-20mA application such as pressure, transducers, temp,flow, humidity, level etc. This can only be used on a point that had been previouslyset to 'Off'.Select a 'Off' point by scrolling through the point numbers, then select the typefield and set to '420'.

The default values for the 4-20mA are 0 to 100% (0 = 4mA and 100 = 20mA). Zeroand full scale can be modified via the second Point Detail screen.With the 'Type' field highlighted, press the ‘ ’ key to display the second PointDetail screen. The 4 and 20 values can be set. The value for the upper and lowerlimits can therefore represent % (RH), PPM, bar, psi etc, depending on themedium being measured. A numerical value for 4mA (lower limit) and 20mA(higher limit) is entered and the Micromon automatically scales the input for afigure proportional to the measurement.

This option allows you to change the three different levels of passcodes – Main,User and Local, also the Inhibit Protection and Point Offset protection can beactivated. The Main and Local Passcode provides access to all the setupscreens. The User Passcode only provides access to the Time/Date setup.The Micromon default setting are as displayed in the screen shown on the left.

From the Extended Menu, select the Passcode Setup option.

Use the ‘↵↵↵↵↵’ to highlight the passcode to be modified. Type in the passcode usingthe ‘ ’ or ‘ ’ keys to scroll through the character list and the ‘ ’ or ‘ ’ key tomove the cursor left or right respectively. N.B. Local passcode is numeric only.You can use the ‘ ‘ and ‘ ’ keys together to delete the character before the

cursor and ‘ ‘ to change case. When the passcode has been set, press ‘↵↵↵↵↵’ then

‘ ’ to return to the Setup Menu.

To set the Inhibit Protection, use the ‘↵↵↵↵↵’ key to highlight the 'Inhibit Protected' field,then using the ‘ ’ or ‘ ’ keys to select either 'Yes' or 'No'.

To set the Point Offset Disable, use the ‘↵↵↵↵↵’ key to highlight the 'Pt Offset Disable'field, then using the ‘ ’ or ‘ ’ keys to select either 'Yes' or 'No'.

The log print and graph print settings only apply if a printer is connected directly tothe Micromon. If no printer is used, only select the Sampling Rate if needed.To set the print frequencies, select the Log/Chart Frequency option from the SetupMenu.

Use the ‘↵↵↵↵↵’ to highlight the field to be modified. Type in the time required using the‘ ’and ‘ ’ keys to scroll through the character list and the ‘ ’ or ‘ ’ key to movethe cursor left or right respectively.

Set the values as follows:

Log Print Interval Set this value to determine the interval (i.e. frequency)between log prints (hours : minutes).

Start Print at Enter the time and day on which you require the firstprinting of the automatic log readings to start. (Only pointsthat have been set as Timed or ON will be included).

Graph Print Interval Set this value to determine the interval (i.e. frequency)between graph prints.

Start Print at Enter the time and day on which you require the firstautomatic graph to be printed. (Only points that have been

Log/Graph Setup

Passcode Setup

4-20mA Point Type

Page 11: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 11

set as Timed or ON will be included.)

Sampling Rate Set this field to the frequency of sampling required for thegraphs. The most commonly used value is 15 mins.

The Sampling Rate affects the amount of data that will be stored in the unitsmemory.

shtnoMnidoirePegarotS

)sniM(etaRgnilpmaS 1 3 01 51

)tniop8(4618Z080 7.1 2.5 3.71 8.52

)tniop61(5618Z080 1 3 01 9.41

Use this option to select the modem dialout settings. From the Extended Menu,select Modem Dialout Setup.

When connected to a modem, the Micromon is able to make telephone calls to upto five pre-programmed numbers whenever an alarm is detected (see AlarmActions section). Alternatively, individual alarms detected for a particular point canbe routed to a particular telephone number. It can also call a radio pager to alert aduty engineer. Three types of pager can be supported - Tone only, Numeric andAlphanumeric. The message that is sent can also be defined.Note: Support for the TAP pager protocol may vary from country to country.

Use the ‘ ’ or ‘ ’ keys to scroll through the dialout numbers and complete thefields for each device as described below:

Use this field to specify the type of device which is connected to the specifiedtelephone number. The options are as follows:

NO DIAL Indicates the Micromon will not dialout.

GSM SMS Indicates that a RS232/GSM modem device is connected. Sendstext messages to a GSM mobile phone and receives messages.

For information on this feature refer to document FunctionalDescription RC.8A.M.

DOWNLOAD Indicates that a computer is connected (directly or remotely)running Danfoss Central Station software. If the line is busy,the telephone number will be dialled up to four times (8 bit, No

Parity, 1 Stop Bit).

AKM Indicates that a computer is connected (directly or remotely)running Danfoss 'AKM' software. If remotely, dialout attempts willcontinue and after every 10 attempts the alarm relay will reset themodem.Note: Modem must be wired in conjunction with the alarm relay

(refer to appendix A).

BEEPER Indicates that a beeper type pager is connected. The systemdials the appropriate telephone number and then disconnects.

As there is no security associated with this option, the telephonenumber is always dialled twice unless the busy tone is received.

MESSAGE7 Indicates that a 7 bit modem is connected with a printer attached.(7 bit, Even Parity, 1 Stop Bit) (normally used in France).

MESSAGE8 Indicates that a 8 bit modem is connected with a printer attached.(8 bit, No Parity, 1 Stop Bit) (normally used in UK).

Modem Dialout Setup

Dialout

Call Type

Page 12: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

12 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

PAGER7S Indicates that a TAP 7 bit protocol pager is connected which candisplay a message. The message sent is defined on the Pager

Info line (7 bit, Even Parity, 1 Stop Bit).PAGER7M Identical to PAGER7S but sends message up to 4 times.

PAGER8S Indicates that a TAP 8 bit protocol pager is connected which candisplay a message. The message sent is defined on the Pager

Info line (8 bit, No Parity, 1 Stop Bit).

PAGER8M Identical to PAGER8S but sends message multiple times.

Enter the appropriate telephone numbers for each of the devices used. If acomma ‘,’ is inserted before the number, a delay of between 2 and 4 seconds willbe inserted between the modem picking up the line and dialling. If a ‘w’ is insertedbefore the number, the modem will wait for the secondary tone before dialling.

For a message to be sent to a pager, two items of information must be supplied inaddition to the TAP Pager server telephone number.

1. The pager I/D, this is normally marked on the pager.

2. The text message to be sent to the pager.

Text codes are available that add other information into the message. Thesecodes are as follows:

\S Sends the Store Name.\A Sends the Last Alarm Message\C Sends a count of alarms and muted alarms in the

format 2/4.\R Sends the Carriage Return (CR) character.\L Sends the Line Feed (LF) character.\\ Sends the \ character.// Sends the / character.\N Sends output name.

A typical text string will take the form:

123456\RAlarm at \S = \A\R

This page info string would cause pager '123456' to receive a message in the form"Alarm at Danfoss Superstore = 24 Fresh Fish 6.4 Hi>6.0"The pager info field is limited to a maximum of 30 characters

Use the ‘ ’ or ‘ ’ keys to select the option of the modem dialling out 'AlarmsOnly' or 'Alarms and Cleared Alarms'.

Finally, press ‘ ’ to return to the Setup Menu.

When connected to a modem, use this option to configure the modem settings.From the Setup Menu, select the Modem Configuration option.

Use the ‘ ’ or ‘ ’ keys to scroll through the valid baud rates to the required valueand press ‘↵↵↵↵↵’ to move onto the next field.

Enter the dial code you require. Use the ‘ ’and ‘ ’ keys to scroll through thecharacter list and the ‘‘and ‘‘ keys to move the cursor left or right respectively.

Enter the answer code you require. Use ‘ ’ or ‘ ’ keys to scroll through thecharacter list and the ‘ ‘ or ‘ ‘ key to move the cursor left or right respectively.

Note: Refer to your modem handbook for details of the valid modem commandsand answer codes.

Pager Info

Modem Configuration

Baud Rate

Send

Number

Page 13: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 13

When you have finished or to abandon the operation, press ‘ ’ once to return tothe Setup Menu and again to return to the Main Menu.

This option is to set the automatic clock change for winter/summer. Use the ‘ ’ or‘ ’ keys to scroll through the following options:

Mode - Off - Daylight saving switched off.Auto-US - American daylight saving time settings.Auto-EU - European daylight saving time settings.Manual - Times and offset can be manually set.

Start Day - Date for when time changes for summertime.

End Day - Date for when time changes back for wintertime.Time - The hour at which the change will take place.

Offset - The amount in hours the clock will change.

The Point Overview screen is the default screen and views the status of all thepoints at the same time, showing each activated point as one of the followingicons, depending on the point condition. This screen can also be selected from thePoint Overview option from the Main Menu.

- active point in normal condition - an inhibited point

- active point in an alarm condition

To select a point, the cursor box can be positioned around a point symbol by usingthe ‘ ‘ or ‘ ‘ keys. As each point is selected the point number and its currentstatus/temperature is displayed in the window on the right hand side of the screen.

To display more details of a particular point, position the cursor box around thepoint required and press ‘↵↵↵↵↵’. The Point Detail screen will be displayed.

Note: If a point has a local offset applied to it, this will be indicated by the

presence of the offset icon at the left of the Point Readout window.

To continuously view the status of a single point, either select the Point Detailoption from the Main Menu or select a point on the Point Overview and press ‘↵↵↵↵↵’.The Point Detail screen is displayed.Use the ‘ ’ key to select the next point or the ‘ ’ key to select the previous point.The point number is displayed in the upper left-hand corner of the screen and thecurrent status is displayed in large text in the centre of the screen.The text and symbols displayed in the window on the right hand side of the screenare as follows:

Indicates the upper alarm limit setting. When the of the

symbol is scrolling, it indicates that the upper alarm limit hasbeen exceeded.

Indicates the alarm delay in minutes. When the hand of the clock

rotates, it indicates that the point is in the alarm condition andthe delay has not yet expired.

Indicates the lower alarm limit setting. When the part of the

symbol is scrolling, it indicates that the lower alarm limit hasbeen exceeded.

Indicates the input point type.

The area adjacent the 'Input Point Type' also displays 'inhibit' and 'pulldown' icons.- an inhibited point.

Operation via the Key PadPoint Overview

Point Detail

Dial

Answer

Daylight Saving

Page 14: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

14 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

- a point in inhibit pulldown.

Press either the ‘ ’ key or the ‘ ’ key to return to the Main Menu or the ‘ ’key to display the historical graph data.

In the Point Detail screen, pressing the ' ' key displays the Print Range option

box. Use the ' ', ' ', ' ' and ' ' keys to enter the required value and the '↵' key

to move through each field. Press the ' ' key and the Printing in Operation screen

is displayed and the data is sent to the printer.

The format of the printout will be as shown:

To inhibit a point so that it cannot create an alarm, select the required Point Detailscreen and press ‘↵↵↵↵↵’. The Confirm Inhibit Yes/No message is displayed. Use the‘ ’ or ‘ ’ key to toggle the answer and press ‘↵↵↵↵↵’. When a point is inhibited a symbol is displayed alongside the point type. To uninhibit a point repeat theoperation.If the alarm condition is exceeded on an inhibited point (i.e. Pull-down), then theanimated pull-down arrows will be displayed next to the inhibit symbol .The inhibit function can be password protected. This can be configured byaccessing the 'Passcode Setup' screen.

Any point on the Micromon can have an offset applied to the displayed readings tocompensate for cable run losses etc. These offsets are point specific and mayonly be defined from the Micromon keypad, although their value is readable whenaccessing the unit remotely. Under normal circumstances these offsets (ifrequired) will be entered at installation and can only be modified by Danfoss

personnel. Any point which has an offset active will display the offset icon onboth the Point Detail and Point Overview screens.

To display an instant graph of the currently selected point, from the Point Detailscreen, press the ‘ ’ key. The chart is then displayed.The default time scale for the data displayed depends on the sample rate set. Forexample, a sample rate of 15 minutes will give a default time scale of 1 day.

To view historic data, press the ‘ ’ or ‘ ’ keys to page the graphic screens (withno overlap). Pressing the ‘ ’ or ' ' keys will scroll through each of the pointsdisplaying the data graphs.

Press the ‘↵’ to bring up the cursor, this can then be moved along left or rightdisplaying the reading and time for the cursor position in the top right hand cornerof the screen. In addition the screen will page left or right when the cursor reachesthe end of the display.

To zoom in or out press the ' ' or ' ' keys, this will display the following timespans:

45 mins 12 hours 4 weeks1.5 hours 1 day 12 weeks3 hours 3.5 days 11 months6 hours 1 week

Point Offset

Graphics

Inhibiting a Point

Single Point Log Printout

Page 15: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 15

To exit the zoom facility, remove the graph cursor by pressing '↵' again. Pressingthe ' ' key will then take you back to the Point Detail screen.

When a graph is displayed on the screen, pressing the ' ' key dumps the graph

to a directly connected printer (cursor must be removed first).

When one or more alarms have been raised, the built-in siren will sound, thebacklight will flash red and the point(s) in alarm will pulse. If a parallel printer isconnected, the time, status and point details of the alarm can be printed.If the ‘ ’ key is not pressed within the programmed time setting, the dial-out relaycan be programmed to automatically activate, sending a signal to the dial-outequipment/security system if it is connected.

To stop the siren sounding and the red backlight flashing, press the ‘ ’ key.

Check what the problem is by selecting the Point Detail screen for the point inalarm and noting its present status and alarm settings. The fault will need to befound and rectified before the alarm can be successfully cleared.If there appears to be no problem, it could be that the fault has ‘cleared itself’ (e.g.the temperature has since returned to an acceptable level). In this case, the pointwill stop pulsing.If there are no further faults on other points, the alarm status will be cleared.

To display the Main Menu, press the ‘ ’ key (repeat if necessary). To select anoption from the Main Menu, use the ‘ ’ or ‘ ’ key to position the highlight over therequired option and press ‘↵↵↵↵↵’ or ‘ ’.

Note: Options which have a symbol alongside them are password protected.

Use this option to display the default Point Overview screen as previouslydescribed.

To display the alarm history, select the Alarm History option from the Main Menu.The Alarm List screen is displayed with the most recent alarm heading the list.

Up to 999 latest alarms can be viewed.

Each alarm is given a number from 1 to 999 (restarting at 1 after the 999th) and istime and date stamped. The description shows the information relevant to eachpoint. The two ‘ ’ symbols at the bottom of the screen indicate that the listcontinues. The list can be scrolled up and down using the ‘ ’ or ‘ ’ keys. Press‘↵↵↵↵↵’ to display events with the alarms.

To display the alarm history for a particular point, select the Point Detail screen,

then press the and keys together. The Alarm List screen is displayed listingall alarms for the selected point only.

To display the event history, select the Event History option from the Main Menu.The Event List screen is displayed with the most recent event heading the list.The latest 100 events stored are viewed. The list can be scrolled up and downusing the ‘ ’ or ‘ ’ keys.

This option starts up the easy setup that is used on initial Micromon setup, aspreviously described.

Use this option to display the unit's software and hardware details for reference.To return to the Main Menu, either wait 1 minute or press any key.

This facility only applies if a parallel printer is directly connected. A series ofprintouts can be initiated in condensed mode. To perform a print operation press

the ‘ ’ key to display the Print Menu.

Alarm History

Point Alarm List

Point Overwiew

Main Menu

Muting and Clearing an Alarm

Alarm Mode

Event History

Page 16: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

16 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

Use this option to print the current status of all points.Note: Only those points which have their log action set to ON or Manual will beprinted.

Use this option to print an individual graph of each of the points in turn. From thePrint Menu, select the Graph of Selected Points option. The Select Period screenwill then appear. Use the ' ', ' ', ' ' and ' ' keys to enter the required value andthe '↵' key to move through each field. The Printing in Operation screen isdisplayed and the data is sent to the printer.

Note: Only those points which have their graph action set to ON or Manual will beprinted.

Use this option to print a list of all the alarms and events. The Alarm/Event List isprinted showing the Alarm List followed by the Event List.

From the Print Menu, select the Alarm List option. The Select Period screen willthen appear. Use the ' ', ' ', ' ' and ' ' keys to enter the required value andthe '↵' key to move through each field. The Printing In Operation screen is thendisplayed and the data is sent to the printer.

Each alarm is given a number from 1 to 999 (restarting at 1 after the 999th) and istime and date stamped. The description shows the information relevant to eachpoint.Similarly, each event is time and date stamped and the description shows theinformation relevant to each event.

Note: This operation may take considerable time and paper.The various codes printed in the status (St) column are defined as follows:ok No fault presentHi High alarmInh InhibitLow Low alarmOff The input is offOC Signal over rangeSC Signal under range

The various codes displayed in the printout Reason column are defined as follows:Fault probe fault> High value alarm greater than high alarm limit< Low value alarm less than low alarm limit.

Use this option to print the current setup of the Micromon unit.

When the Micromon generates a new alarm, the following alarm outputs areactivated.

Log of All Points

Graph of Selected Points

Alarm History

Easy Setup

Software Version

Print Menu

Page 17: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 17

Setup Information

Alarm Action

tuptuO noitpircseD noitcA

)TUOLAID(1YALERrofnoitcennoctuolaiDdeyaleR

tinurellaidlatigidehtlitnumralawenhcaenoevitcA

desserpsiyek'ETUM'

)mralApeR(2YALERarofnoitcennocdeyaleR

tinumralAtaepeRllitserasmralaelihwevitcA

.tneserp

NERIS rednuoslanretnI 1yaleRsaemaS

PMAL yalpsiDdeR 2yaleRsaemaS

HSALF yalpsiDgnihsalFdeR 1yaleRsaemaS

5-1smedoM smedoM mralanotuolaidoT

Page 18: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

18 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

Maintenance

Cleaning To keep the Micromon free from dust, periodically wipe the outside surface with asoft dry cloth. DO NOT use any abrasive cleaners, wax or solvents. Stubbornmarks may be removed by using a soft cloth dampened with a mild detergent.

This Micromon unit should be serviced only by qualified service personnel andshould ensure that replacement parts match the original safety characteristics.

CAUTION: This unit is fitted with rechargeable batteries, use only manufacturersreplacements.

Service

Full Character Set Alphanumeric Character Set

A a )ecaps(

B b !

C c "

D d #

E e $

F f %

G g &

H h '

I i (

J j )

K k *

L l +

M m ,

N n -

O o .

P p /

Q q 0

R r 1

S s 2

T t 3

U u 4

V v 5

W w 6

X x 7

Y y 8

Z z 9

[ { ;

\ | <

] } =

^ ~ >

` º

0 V

1 W

2 X

3 Y

4 X

5 a

6 b

7 c

8 d

9 e

A f

B g

C h

D i

E j

F k

G l

H m

I n

J o

K p

L q

M r

N s

O t

P u

Q v

R w

S x

T y

U z

Page 19: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

Micromon Micromon RS.8A.Y3.02 © Danfoss 01-2003 19

Appendix A

'AKM' Call Type

Background The Danfoss AKM has been updated to allow it to receive alarms from m2units. However the m2 alarm dialout procedure differs from the DanfossGateway in that it is not as tolerant of faulty telecommunication equipment.The m2 would make repeated calls to try to transmit the alarm message upto a maximum of 8. This conformed to the current telecommunicationregulations when the procedure as defined.AKM will continue to try to transmit the alarm indefinitely. It can also controlthe power to the modem using one of it relays. It does this after ten failedattempts to dial-out and every 6 hours.The 'AKM' call type has been created to mimmic the same dialout as theAKM.

The m2 has two relays that are normally used for alarm indication. TheRelay 2 (REP ALARM) can be used to control the modem power. TheRelay is rated at 24V 1A max, so the low voltage power after the mainstransformer must be switched. Mains voltage MUST NOT be connected tothis relay.

Modem to m2 Wiring

Dial Out Settings

Alarm Action Setup

:eciveD sgnitteS noitpircseD

:2yaleR 000000000:reggirT lortnocrewopmedomselbanE

nmedoM :reggirT deriuqersAceS0:yaleDceS0:noitaruD

emiT:nOraelC

.thgindnayadNOmedomspeek,111111111yllausU.tuolaidtsrifdnamralaneewtebyaleD

.llactaeperhcaeneewtebyaleD.sseccuslitnutuolaideunitnoC

Modem Dial Out Setup

:tuolaiD sgnitteS noitpircseD

:5-1 MKA:epyTllaC:rebmuN deriuqersA

:ofnIregaP

.stpmettaseunitnoctpecxe'daolnwoD'saemaS.rebmunenohpeletMKAehT

.deriuqertoN

Page 20: Manual Monitoring and Alarm System Micromon - Danfossfiles.danfoss.com/TechnicalInfo/Dila/01/RS8AY302.pdf · Monitoring and Alarm System Micromon ... Point Alarm List 15 Event History

20 Manual RS.8A.Y3.02 © Danfoss 01-2003 Micromon

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This alsoapplies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

List of Literature

Technical RC.8A.ULeaflet Provides technical information on the Micromon unit.

Instructions RI.8G.AProvides full instructions on how to mount the Micromon

unit and connection AKS12 sensors.