User's Manualser's Manual
BTC-4300Self-Tune Fuzzy / PIDProcess / Temperature Controller
BTC-4300
Self-Tune Fuzzy / PID
Process / Temperature Controller
UM43001E
-
8/10/2019 Manual BTC4300
2/142
2
UM43001B
Warning Symbolarning Symbol
Use the Manualse the Manual
The Symbol calls attention to an operating procedure, practice, or the like, which, if not correctly performed oradhered to, could result in personal injury or damage to or destruction of part or all of the product and system.Do not proceed beyond a warning symbol until the indicated conditions are fully understood and met.
The Symbol calls attention to an operating procedure, practice, or the like, which, if not correctly performed or
adhered to, could result in personal injury or damage to or destruction of part or all of the product and system.
Do not proceed beyond a warning symbol until the indicated conditions are fully understood and met.
Installers
Basic Function User
Enhanced Function User
System Designer
Expert User
Installers
Basic Function User
Enhanced Function User
System Designer
Expert User
Read Chapter 1, 2
Read Chapter 1, 3, 5
Read Chapter 1, 3, 4, 5
Read All Chapters
Read Page 11
Read Chapter 1, 2
Read Chapter 1, 3, 5
Read Chapter 1, 3, 4, 5
Read All Chapters
Read Page 11
-
8/10/2019 Manual BTC4300
3/142
3
M43001E
CONTENTS
Chapter 1 Overviewhapter 1 Overview
1-1 Features
1-2 Ordering Code
1-3 Programming Port & DIP Switch
1-4 Keys and Displays1-5 Menu Overview
1-6 System Modes
1-7 Parameter Description
1-1 Features
1-2 Ordering Code
1-3 Programming Port & DIP Switch
1-4 Keys and Displays
1-5 Menu Overview
1-6 System Modes
1-7 Parameter Description
Page Noage No Page Noage No
Chapter 2 Installationhapter 2 Installation2-1 Unpacking
2-2 Mounting
2-3 Wiring Precautions
2-4 Power Wiring
2-5 Sensor Installation Guidelines
2-6 Thermocouple Input Wiring
2-7 RTD Input Wiring
2-8 Linear DC Input Wiring
2-9 CT / Heater Current Input Wiring
2-10 Event Input wiring
2-11 Output 1 Wiring
2-12 Output 2 Wiring
2-13 Alarm 1 Wiring
2-14 Alarm 2 Wiring
2-15 RS-485
2-16 RS-2322-17 Analog Retransmission
2-18 Programming Port
2-1 Unpacking
2-2 Mounting
2-3 Wiring Precautions
2-4 Power Wiring
2-5 Sensor Installation Guidelines
2-6 Thermocouple Input Wiring
2-7 RTD Input Wiring
2-8 Linear DC Input Wiring
2-9 CT / Heater Current Input Wiring
2-10 Event Input wiring
2-11 Output 1 Wiring
2-12 Output 2 Wiring
2-13 Alarm 1 Wiring
2-14 Alarm 2 Wiring
2-15 RS-485
2-16 RS-232
2-17 Analog Retransmission
2-18 Programming Port
Chapter 3 Programming the Basic Functionhapter 3 Programming the Basic Function
3-1 Input 1
3-2 OUT1 & OUT2 Types
3-3 Rearrange User Menu
3-4 Heat Only Control
3-5 Cool Only Control
3-6 Heat - Cool Control
3-7 Dwell Timer
3-8 Process Alarms
3-9 Deviation Alarms
3-10 Deviation Band Alarms
3-11 Heater Break Alarm
3-12 Loop Break Alarm
3-13 Sensor Break Alarm
3-14 SP1 Range
3-15 PV1 Shift
3-16 Failure Transfer
3-17 Bumpless Transfer3-18 Self-tuning
3-19 Auto-tuning
3-20 Manual Tuning
3-1 Input 1
3-2 OUT1 & OUT2 Types
3-3 Rearrange User Menu
3-4 Heat Only Control
3-5 Cool Only Control
3-6 Heat - Cool Control
3-7 Dwell Timer
3-8 Process Alarms
3-9 Deviation Alarms
3-10 Deviation Band Alarms
3-11 Heater Break Alarm
3-12 Loop Break Alarm
3-13 Sensor Break Alarm
3-14 SP1 Range
3-15 PV1 Shift
3-16 Failure Transfer
3-17 Bumpless Transfer
3-18 Self-tuning
3-19 Auto-tuning
3-20 Manual Tuning
Chapter 4 Programming the Full Functionhapter 4 Programming the Full Function
4-1 Event Input
4-2 Second Set Point
4-3 Second PID Set
4-4 Ramp & Dwell
4-5 Remote Set Point
4-6 Differential Control
4-7 Output Power Limits
4-8 Data Communication
4-9 Analog Retransmission
4-10 Digital Filter
4-11 Sleep Mode
4-12 Pump Control
4-13 Remote Lockout
4-1 Event Input
4-2 Second Set Point
4-3 Second PID Set
4-4 Ramp & Dwell
4-5 Remote Set Point
4-6 Differential Control
4-7 Output Power Limits
4-8 Data Communication
4-9 Analog Retransmission
4-10 Digital Filter
4-11 Sleep Mode
4-12 Pump Control
4-13 Remote Lockout
Chapter 5 Applicationshapter 5 Applications
5-1 Pump / Pressure Control
5-2 Variable Period Full Wave SSR ( VPFW SSR )
5-3 Heat Only Control5-4 Cool Only Control
5-5 Heat - Cool Control
5-6 Ramp & Dwell
5-7 Remote Set Point
5-8 Differential Control
5-9 Dual Set Point / PID
5-10 RS-485
5-11 RS-232
5-12 Retransmit
5-1 Pump / Pressure Control
5-2 Variable Period Full Wave SSR ( VPFW SSR )
5-3 Heat Only Control
5-4 Cool Only Control
5-5 Heat - Cool Control
5-6 Ramp & Dwell
5-7 Remote Set Point
5-8 Differential Control
5-9 Dual Set Point / PID
5-10 RS-485
5-11 RS-232
5-12 Retransmit
Chapter 6 Calibrationhapter 6 Calibration
Appendix
Chapter 7 Error Codes & Troubleshootinghapter 7 Error Codes & Troubleshooting
Chapter 8 Specificationshapter 8 Specifications
A-1 Menu Existence Conditions
A-2 Factory Menu Description
A-3 Glossary
A-4 Index
A-5 Memo
A-6 Warranty
A-1 Menu Existence Conditions
A-2 Factory Menu Description
A-3 Glossary
A-4 Index
A-5 Memo
A-6 Warranty
3-21 Signal Conditioner DC Power Supply
3-22 Manual Control
3-23 Display Mode
3-24 Heater Current Monitoring3-25 Reload Default Values
3-21 Signal Conditioner DC Power Supply
3-22 Manual Control
3-23 Display Mode
3-24 Heater Current Monitoring
3-25 Reload Default Values
65
64
66
67
67
68
69
70
71
73
74
75
76
77
78
79
80
81
68
69
70
71
73
74
75
76
77
78
79
80
81
82
84
8687
88
90
92
93
94
96
98
99
82
84
86
87
88
90
92
93
94
96
98
99
100
104
107
124
127
129
136
139
141
124
127
129
136
139
141
4
7
8
911
12
13
4
7
8
9
11
12
13
21
21
22
23
24
25
26
26
28
29
30
32
34
35
36
3738
39
21
21
22
23
24
25
26
26
28
29
30
32
34
35
36
37
38
39
40
41
42
43
44
45
47
48
50
51
52
53
54
54
55
56
5758
59
61
40
41
42
43
44
45
47
48
50
51
52
53
54
54
55
56
57
58
59
61
Chapter 9 Modbus Communicationshapter 9 Modbus Communications110
-
8/10/2019 Manual BTC4300
4/142
Chapter 1 Overviewhapter 1 Overview
1 1 Features1 Features
BTC-4300 Fuzzy Logic plus PID microprocessor-based controller, incorporates a bright,easy to read 4-digit LED display, indicating process value. The technologyenables a process to reach a predetermined set point in the shortest time, with theminimum of overshoot during power-up or external load disturbance. The units arehoused in a 1/4 DIN case, measuring 96 mm x 96 mm with 53 mm behind panel depth.The units feature three touch keys to select the various control and input parameters.Using a unique function, you can put at most 5 parameters in front of user menu by using
contained in the setup menu. This is particularly useful to OEM's as it is easyto configure menuto suit the specific application.
Fuzzy Logic
SEL1 to SEL5
BTC-4300 Fuzzy Logic plus PID microprocessor-based controller, incorporates a bright,
easy to read 4-digit LED display, indicating process value. The technology
enables a process to reach a predetermined set point in the shortest time, with the
minimum of overshoot during power-up or external load disturbance. The units are
housed in a 1/4 DIN case, measuring 96 mm x 96 mm with 53 mm behind panel depth.
The units feature three touch keys to select the various control and input parameters.
Using a unique function, you can put atmost 5 parameters in front of usermenubyusing
contained in the setup menu.This isparticularlyuseful toOEM's as it iseasy
toconfiguremenuto suit thespecificapplication.
Fuzzy Logic
SEL1 toSEL5
BTC-4300 is powered by 11-26 VAC/VDC or 90 - 264 V AC supply, incorporating dual 2amp. control relays output and dual 2 amp. alarm relays output as standard. Alternativeoutput options include SSR drive, triac, 4 - 20 mA and 0 - 10 volts. BTC-4300 is fullyprogrammable for PT100, thermocouple types J, K, T, E, B, R, S, N, L, 0 - 20mA, 4 -20mAand voltage signal input, with no need to modify the unit. The input signals are digitized byusing a converter. Its allows the BTC-4300 to control fastprocesses such as pressure and flow. is incorporated. The self- tune can beused to optimize the control parameters as soon as undesired control result is observed.Unlike auto-tune, Self-tune will produce less disturbance to the process during tuning,andcanbeusedany time.
18-bit A to D fast sampling rateSelf tune
BTC-4300 is powered by 11-26 VAC/VDC or 90 - 264 V AC supply, incorporating dual 2
amp. control relays output and dual 2 amp. alarm relays output as standard. Alternative
output options include SSR drive, triac, 4 - 20 mA and 0 - 10 volts. BTC-4300 is fully
programmable for PT100, thermocouple types J,K, T, E, B,R, S,N, L, 0 - 20mA, 4 -20mA
and voltage signal input,withnoneed tomodify the unit. The input signals are digitized by
using a converter. Its allows the BTC-4300 to control fast
processes such as pressure and flow. is incorporated. The self- tune can be
used tooptimize the control parametersas soon asundesired control result is observed.
Unlike auto-tune, Self-tune will produce less disturbance to the process during tuning,
and can beused any time.
18-bit A to D fast sampling rate
Self tune
High accuracy 18-bit input A DHigh accuracy 15-bit output D AFast input sample rate ( 5 times / second)
Two function complexity levelsUser menu configurablePump controlFuzzy + PID microprocessor-based controlAutomatic programmingDifferential controlAuto-tune functionSelf-tune functionSleep mode function" Soft-start " ramp and dwell timerProgrammable inputs( thermocouple, RTD, mA, VDC )
Analog input for remote set point and CTEvent input for changing function & set pointProgrammable digital filterHardware lockout + remote lockout protectionLoop break alarmHeater break alarmSensor break alarm + Bumpless transferRS-485, RS-232 communicationAnalog retransmissionSignal conditioner DC power supplyA wide variety of output modules available
Safety UL / CSA / IEC1010 1EMC / CE EN61326
High accuracy 18-bit input A D
High accuracy 15-bit output D A
Fast input sample rate ( 5 times / second)
Two function complexity levels
User menu configurable
Pump control
Fuzzy + PID microprocessor-based control
Automatic programming
Differential control
Auto-tune function
Self-tune function
Sleep mode function
Soft-start ramp and dwell timer
Programmable inputs( thermocouple, RTD, mA, VDC )
Analog input for remote set point and CT
Event input for changing function & set point
Programmable digital filter
Hardware lockout + remote lockout protection
Loop break alarm
Heater break alarm
Sensor break alarm + Bumpless transfer
RS-485, RS-232 communication
Analog retransmission
Signal conditioner DC power supply
A wide variety of output modules available
Safety UL / CSA / IEC1010 1
EMC / CE EN61326
UniqueValuableUnique
Valuable
4
UM43001B
-
8/10/2019 Manual BTC4300
5/142
-
8/10/2019 Manual BTC4300
6/142
Warm Up Load Disturbance
PID control with properly tuned
PID + Fuzzy control
Set point
Temperature
Time
Figure 1.2 Fuzzy PIDEnhances ControlStability
Figure 1.2 Fuzzy PID
Enhances Control
Stability
6
UM43001B
-
8/10/2019 Manual BTC4300
7/142
Accessories
CT94-1 = 0 - 50 Amp. AC Current TransformerOM95-3 = Isolated 4 - 20 mA / 0 - 20 mA Analog Output ModuleOM95-4 = Isolated 1 - 5V / 0 - 5V Analog Output Module
OM95-5 = Isolated 0 - 10V Analog Output ModuleOM94-6 = Isolated 1A / 240VAC Triac Output Module ( SSR )OM94-7 = 14V/40mA SSR Drive ModuleDC94-1 = Isolated 20V / 25mA DC Output Power SupplyDC94-2 = Isolated 12V / 40mA DC Output Power SupplyDC94-3 = Isolated 5V / 80mA DC Output Power SupplyCM94-1 = Isolated RS-485 Interface ModuleCM94-2 = Isolated RS-232 Interface ModuleCM94-3 = Isolated 4 - 20 mA / 0 - 20 mA Retransmission ModuleCM94-4 = Isolated 1 - 5V / 0 - 5V Retransmission ModuleCM94-5 = Isolated 0 - 10V Retransmission ModuleCC94-1 = RS-232 Interface Cable (2M)
CC91-3 = Programming Port Cable
CT94-1 = 0 - 50 Amp. AC Current Transformer
OM95-3 = Isolated 4 - 20 mA / 0 - 20 mA Analog Output Module
OM95-4 = Isolated 1 - 5V / 0 - 5V Analog Output Module
OM95-5 = Isolated 0 - 10V Analog Output Module
OM94-6 = Isolated 1A / 240VAC Triac Output Module SSR
OM94-7 = 14V/40mA SSR Drive Module
DC94-1 = Isolated 20V / 25mA DC Output Power Supply
DC94-2 = Isolated 12V / 40mA DC Output Power Supply
DC94-3 = Isolated 5V / 80mA DC Output Power Supply
CM94-1 = Isolated RS-485 Interface Module
CM94-2 = Isolated RS-232 Interface Module
CM94-3 = Isolated 4 - 20 mA / 0 - 20 mA Retransmission Module
CM94-4 = Isolated 1 - 5V / 0 - 5V Retransmission Module
CM94-5 = Isolated 0 - 10V Retransmission Module
CC94-1 = RS-232 Interface Cable 2M
CC91-3 = Programming Port Cable
Power Inputower Input
4: 90 - 264 VAC, 47-63 HZ5: 11 - 26 VAC or VDC,
SELV, Limited Energy
4: 90 - 264 VAC, 47-63 HZ
5: 11 - 26 VAC or VDC,
SELV, Limited Energy
1: Standard InputInput 1 - Universal Input
Thermocouple: J, K, T, E, B,R, S, N, L
RTD: PT100 DIN, PT100 JISCurrent: 4 - 20mA, 0 - 20 mA.
Voltage: 0 - 1V, 0 - 5V, 1 - 5V,
0 - 10VInput 2 - CT and Analog Input
CT: 0 - 50 Amp. AC CurrentTransformer
Analog Input: 4 - 20 mA,0 - 20mA, 0 - 1V, 0 - 5V,1 - 5V, 0 - 10V.
Input 3 - Event Input ( EI )9: Special Order
1: Standard Input
Input 1 - Universal Input
Thermocouple: J, K, T, E, B,
R, S, N, L
RTD: PT100 DIN, PT100 JIS
Current: 4 - 20mA, 0 - 20 mA.
Voltage: 0 - 1V, 0 - 5V, 1 - 5V,
0 - 10V
Input 2 - CT and Analog Input
CT: 0 - 50 Amp. AC Current
Transformer
Analog Input: 4 - 20 mA,
0 - 20mA, 0 - 1V, 0 - 5V,
1 - 5V, 0 - 10V.
Input 3 - Event Input EI
9: Special Order
Signal Inputignal Input
0: None1: Relay 2A/240VAC2: Pulsed voltage to
drive SSR, 5V/30mA3: Isolated
4 - 20mA / 0 - 20mA4: Isolated 1 - 5V / 0 - 5V5: Isolated 0 - 10V6: Triac Output
1A / 240VAC,SSRC: Pulsed voltage to
drive SSR, 14V/40mA9: Special order
0: None
1: Relay 2A/240VAC
2: Pulsed voltage to
drive SSR, 5V/30mA
3: Isolated
4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac Output
1A / 240VAC,SSR
C: Pulsed voltage to
drive SSR, 14V/40mA
9: Special order
Output 1utput
9: Special order: Special order
2A / 240VACA / 240VAC1: Form C Relay: Form C Relay0: None: None
Alarm 1larm
1 2
3 4
5
7
0: None1: Relay 2A/240VAC2: Pulsed voltage to
drive SSR, 5V / 30mA3: Isolated 4 - 20mA / 0 - 20mA4: Isolated 1 - 5V / 0 - 5V5: Isolated 0 - 10V6: Triac Output, 1A / 240VAC, SSR7: Isolated 20V / 25mA DC
Output Power Supply8: Isolated 12V / 40 mA DC
Output Power Supply9: Isolated 5V / 80mA DC
Output Power SupplyC: Pulsed voltage to
drive SSR, 14V/40mAA: Special order
0: None
1: Relay 2A/240VAC
2: Pulsed voltage to
drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac Output, 1A / 240VAC, SSR
7: Isolated 20V / 25mA DC
Output Power Supply
8: Isolated 12V / 40 mA DC
Output Power Supply
9: Isolated 5V / 80mA DC
Output Power Supply
C: Pulsed voltage to
drive SSR, 14V/40mA
A: Special order
Output 2utput
BTC-4300-
1 2 Ordering Code Ordering Code
BTC-4300-411110190 - 264 operating voltageInput: Standard InputOutput 1: RelayOutput 2: Relay
Alarm 1: Form C RelayRS- 485 Communication Interface
BTC-4300-4111101
90 - 264 operating voltage
Input: Standard Input
Output 1: Relay
Output 2: Relay
Alarm 1: Form C Relay
RS- 485 Communication Interface
BC-Set = Configuration SoftwareCommunicator = PC software to communicate
1024 tags
BC-Set = Configuration Software
Communicator = PC software to communicate
1024 tags
UM43001E
SNA10A = Smart Network Adaptor for Third
Party Software, Converts 255channels of RS-485 or RS-422 toRS-232 Network
SNA12A = Smart Network Adapter forprogramming port to RS-232interface
SNA10A = Smart Network Adaptor for Third
Party Software, Converts 255
channels of RS-485 or RS-422 to
RS-232 Network
SNA12A = Smart Network Adapter for
programming port to RS-232
interface
Example
7
Related Productselated Products
Range set by front keyboard
Need to order an accessory CT94-1 if
Heater Break detection is required.
Range set by front keyboard
Need to order an accessory CT94-1 if
Heater Break detection is required.
**
**
*
*
*
0: None1: RS-4852: RS-2323: Retransmit 4-20mA
/0-20mA4: Retransmit 1 - 5V
/ 0 - 5V5: Retransmit 0 - 10V9: Special order
0: None
1: RS-485
2: RS-232
3: Retransmit 4-20mA
/0-20mA
4: Retransmit 1 - 5V
/ 0 - 5 V
5: Retransmit 0 - 10V
9: Special order
Communications
*
*
*
*
6
9: Special order: Special order
2A / 240VACA / 240VAC1: Relay: Relay0: None: None
Alarm 2larm
-
8/10/2019 Manual BTC4300
8/142
FrontPanel
RearTerminal
1 3 Programming Port and DIP Switch3 Programming Port and DIP Switch
Figure 1.3 Access Hole
Overview
Figure 1.3 Access Hole
Overview
Table 1.1 DIP SwitchConfiguration
Table 1.1 DIP Switch
Configuration
UM43001D
TC, RTD, mV
0-1V, 0-5V, 1- 5V, 0- 10V
0-20 mA, 4-20 mA
Input 1SelectInput 1
Select
All parameters are Unlocked
Only SP1, SEL1 SEL5 are unlocked
Only SP1 is unlocked
All Parameters are locked
Lockout
1 2 3 4
DIP SwitchIP Switch:ON :OFF
Factory Default Settingactory Default Setting
8
*
*
T he p ro gr am mi ng p or t i s u se d f or o ff -l in e a ut om at ic s et up a nd t es ti ngprocedures only. Don't attempt to make any connection to these pins when theunit is used fora normal control purpose.
The programming port is used for off-line automatic setup and testing
procedures only. Don't attempt to make any connection to these pins when the
unit isusedfora normalcontrol purpose.
When the unitleaves the factory, the DIP switch is set so that TC& RTD are selected for input1 and allparameters are unlocked.When the unitleaves the factory, the DIP switch isset so that TC& RTD are selected for input
1 andallparametersareunlocked.
Lockout function is used to disable the adjustment of parameters as well as operation ofcalibration mode. However, the menu can still be viewed even under lockout condition.Lockout function is used to disable the adjustment of parameters as well as operation of
calibration mode. However, the menu can still be viewed even under lockout condition.
SEL1- SEL5 represent those parameters which are selected by using SEL1, SEL2,...SEL5parameters contained in Setup menu. Parameters been selected are then allocated at thebeginningof theuser menu.
SEL1- SEL5 represent those parameters which are selected by using SEL1, SEL2,...SEL5
parameters contained in Setup menu. Parameters been selected are then allocated at the
beginningof theusermenu.
Access Hole
The programming port is used to connect toSNA12A for automatic programming, also canbe connected to ATE system for automatic testing& calibration.
The programming port is used to connect to
SNA12A for automatic programming, also can
be connected to ATE system for automatic testing
& calibration.
ON DIP
1 2 3 4
-
8/10/2019 Manual BTC4300
9/142
Process Unit Indicatorrocess Unit Indicator
Upper Display, to display process value,menu symbol and error code etc.Upper Display, to display process value,
menu symbol and error code etc.
Lower Display,to display set point value,parameter value or control
output value etc.
Lower Display,
to display set point value,
parameter value or control
output value etc.
3 Buttons for ease of controlsetup and set point adjustment.3 Buttons for ease of control
setup and set point adjustment.
Output 1 Indicatorutput 1 Indicator
Table 1.2 Keypad Operationable 1.2 Keypad Operation
For a number with decimal point thedisplay will be shifted one digit right:For a number with decimal point the
display will be shifted one digit right:
-19999 will be displayed by:19999 will be displayed by:
45536 will be displayed by:5536 will be displayed by:
-9999 will be displayed by:9999 will be displayed by:
The unit is programmed by using three keys on the front panel. The available key functions are listed in following table.he unit is programmed by using three keys on the front panel. The available key functions are listed in following table.
Press and release quickly to increase the value of parameter.Press and hold to accelerate increment speed.
Press and release quickly to decrease the value of parameter.Press and hold to accelerate decrement speed.
Select the parameter in a direct sequence.
Allow access to more parameters on user menu, also used to Enter manualmode, auto-tune mode, default setting mode and to save calibration dataduring calibration procedure.
Select the parameter in a reverse sequence during menu scrolling.
Select the operation Mode in sequence.
Reset the front panel display to a normal display mode, also used to leavethe specific Mode execution to end up the auto-tune and manual control
execution, and to quit the sleep mode.
The controller enters the sleep mode if the sleep function ( SLEP ) is enabled( select YES ).
By entering correct security code to allow execution of engineering programs.This function is used only at the factory to manage the diagnostic reports.The user should never attempt to operate this function.
Press
for at least 3 seconds
Press
for at least 6 seconds
Press
Press
Press
Press
Press
for at least 3 seconds
Up Key
Down Key
Scroll Key
Enter Key
Start Record Key
Reverse Scroll Key
Mode Key
Reset Key
Sleep Key
Factory Key
TOUCHKEYS FUNCTION DESCRIPTION
Reset historical values of PVHI and PVLO and start to record the peak process
value.
How to display a 5-digit number ?ow to display a 5-digit number ?
9
1 4 Keys and Displays4 Keys and Displays
: Confused CharacterConfused Character
Figure 1.4 Front Panel Descriptionigure 1.4 Front Panel Description
Table 1.3 Display Form of Charactersable 1.3 Display Form of Characters
-199.99 will be displayed by -199.94553.6 will be displayed by 4553-199.99 will be displayed by -199.9
4553.6 will be displayed by 4553
For a number without decimal pointthe display will be divided into twoalternating phases:
For a number without decimal point
the display will be divided into two
alternating phases:
A E I N S X
B F J O T Y
C G K P U Zc H L Q V ?
D h M R W =
UM43001B
BTC-4300
Output 2 Indicatorutput 2 Indicator
Alarm 1 Indicatorlarm 1 Indicator
Alarm 2 Indicatorlarm 2 Indicator
-
8/10/2019 Manual BTC4300
10/142
Power Onower On
All segments of display andindicators are left off for 0.5second.
All segments of display and
indicators are left off for 0.5
second.
All segments of display andindicators are lit for 2 seconds.All segments of display and
indicators are lit for 2 seconds.
Display program code of theproduct for 2.5 seconds.Display program code of the
product for 2.5 seconds.
The left diagram shows programno. 4 ( for BTC-4300 ) with version39.
The left diagram shows program
no. 4 ( for BTC-4300 ) with version
39.
Display Date Code and Serialnumber for 2.5 seconds.Display Date Code and Serial
number for 2.5 seconds.
Display the used hours for 2.5seconds.Display the used hours for 2.5
seconds.
The left diagram shows that the
unit has been used for 23456.2hours since production.
The left diagram shows that the
unit has been used for 23456.2
hours since production.
10
UM43001B
Figure 1.5 Display Sequence ofInitial Message
Figure 1.5 Display Sequence of
Initial Message
Program Coderogram Code
Program No.rogram No.
Program Versionrogram Version
Year (2001)ear (2001)
Month (December)onth (December)
Date (31'st)ate (31'st)
Date Codeate Code
The left diagram shows Year 2001,Month May ( 5 ), Date 22'st andSerial number 192. This means that
the product is the 192 'th unitproduced on May 22'st, 2001.Note that the month code stands for
stands for andstands for .
AOctober, B November C
December
The left diagram shows Year 2001,
Month May ( 5 ), Date 22'st and
Serial number 192. This means that
the product is the 192 'th unit
produced on May 22'st, 2001.
Note that the month code stands for
stands for and
stands for .
A
October, B November C
December
BTC-4300
BTC-4300
BTC-4300
BTC-4300
BTC-4300
-
8/10/2019 Manual BTC4300
11/142
PV Value
SV Value
UserMenuUser
Menu
SetupMenuSetup
Menu
Hand (Manual)Control
Mode
Hand (Manual)
Control
Mode
Auto-tuningModeAuto-tuning
Mode
DisplayModeDisplay
Mode
DefaultSettingMode
Default
Setting
Mode
CalibrationModeCalibration
Mode
Apply these modes will break the control loop and changesome of the previous setting data. Make sure that if the systemis allowable to use these modes.
Apply these modes will break the control loop and change
some of the previous setting data. Make sure that if the system
is allowable to use these modes.
RAMPA2DVA2SPA1DVA1SPTIME
PB1SHIF
CPB
REFC
TD1
OFST
TI1
TD2TI2
PB2SP2
PL2PL1
A2HYA1HYO1HY
SEL1
SEL5SEL4SEL3SEL2
FILE
To execute the
default settingprogram
PVHIPVLO
PV1PV2PB
TDTI
DV
CJCTPVR
PVRHPVRL
HC
SEL1
AOHI
IN1L
SP1HSP2F
AOLO
DP1
SP1L
AOFN
IN1U
SPMD
STOP
IN1
IN1H
IN2H
SLEP
PARI
IN2L
SELF
FILTPVMDEIFN
SEL2
DATA
DP2
BAUD
IN2U
ADDR
IN2
PROTCOMMFUNC
O1TY
O2TY
A1MD
A2FT
OUT1
OUT2
A1FN
A2MD
O1FT
O2FT
A2FN
CYC1
CYC2
A1FT
SEL5SEL4SEL3
HC
V2G
MA2G
MA1GSR1
REF1CJG
CJTLV1GADGAD0
for 3 seconds
for 3seconds
for3 seconds
Press for 3 seconds to enterthe auto-tuning mode
The flow chart shows a complete listing of all parameters.For actual application the number of available parametersdepends on setup conditions, and should be less
than that shown in the flow chart. See for theexistence conditions of each parameter.
Appendix A-1
The flow chart shows a complete listing of all parameters.
For actual application the number of available parameters
depends on setup conditions, and should be less
than that shown in the flow chart. See for the
existence conditions of each parameter.
Appendix A-1
*1:
You can select at most 5 parameters put in front of the usermenu by using SEL1 to SEL5 contained at the bottom ofsetup menu.
You can select at most 5 parameters put in front of the user
menu by using SEL1 to SEL5 contained at the bottom of
setupmenu.
*2:
1 5 Menu Overview5 Menu Overview
UM43001B 11
*1
1
*2
Display Go Homeisplay Go HomeThe menu will revert toPV/SV display after keyboardis kept untouched for
exceptand
. However, themenu can revert to PV / SV
display at any time bypressing and .
2 minutes DisplayMode Menu ManualMode Menu
The menu will revert to
PV/SV display after keyboard
is kept untouched for
except
and
. However, the
menu can revert to PV / SV
display at any time by
pressing and .
2 minutes Display
Mode Menu Manual
Mode Menu
DB
-
8/10/2019 Manual BTC4300
12/142
1 6 System Modes6 System Modes
The controller performs close loop control under its normal control mode condition.The controller will maintain its normal control mode when you are operating user menu,setup menu or display mode, reloading default values or applying event input signal.
Under certain conditions the normal control mode will transfer to an .The exception modes include :
and All these modes perform in an open loop control exceptthe auto-tuning mode which performs ON-OFF plus PID close loop control. The modetransfer is governed by the priority conditions. A lower priority mode can not alter ahigher priority mode, as shown in Figure 1.6.
Exception ModeSleep Mode, Manual Mode, Failure Mode, Calibration
Mode Auto-tuning Mode.
The controller performs close loop control under its normal control mode condition.
The controller will maintain its normal control mode when you are operating user menu,
setup menu or display mode, reloading default values or applying event input signal.
Under certain conditions the normal control mode will transfer to an .
The exception modes include :
and All these modes perform in an open loop control except
the auto-tuning mode which performs ON-OFF plus PID close loop control. The mode
transfer is governed by the priority conditions. A lower priority mode can not alter a
higher priority mode, as shown in Figure 1.6.
Exception Mode
Sleep Mode, Manual Mode, Failure Mode, Calibration
Mode Auto-tuning Mode.
Figure 1.6System Mode PriorityFigure 1.6
System Mode Priority
? ModeMode
Sleep Mode?leep Mode?
Failure Mode?ailure Mode?
No
No
No
Yes
Yes
Yes
Manual Mode?anual Mode?
RequestNormalControlMode
Request
Normal
Control
Mode
RequestAuto-tuningMode
Request
Auto-tuning
Mode
RequestCalibrationMode
Request
Calibration
Mode
Priority
High
Low
The calibration mode, auto-tuning mode and normal control mode are in the samepriority level. The sleep mode is in the highest priority.The calibration mode, auto-tuning mode and normal control mode are in the same
priority level. The sleep mode is in the highest priority.
System Modes
Sleep Mode :
Manual Mode :
Failure Mode :
Calibration Mode :
Auto-tu nin g M ode :
Normal Control Mode :
See Section 4-11.
See Section 3-22.
See Section 3-16.
See Chapter 6.
See Section 3-19.
See Section 3-23, 3-25, 4-1
System Modes
Sleep Mode :
Manual Mode :
Failure Mode :
Calibration Mode :
Auto-tuning Mode :
Normal Control Mode :
See Section 4-11.
See Section 3-22.
See Section 3-16.
See Chapter 6.
See Section 3-19.
See Section 3-23, 3-25, 4-1
12
UM43001B
-
8/10/2019 Manual BTC4300
13/142
1 7 Parameter Description7 Parameter Description
Table 1.4 Parameter Descriptionable 1.4 Parameter Description
ParameterDescriptionParameter
Description
Range
DefaultValueDefault
Value
Containedin
Contained
in
BasicFunctionBasic
Function
ParameterNotation
Parameter
Notation
DisplayFormatDisplay
Format
SP1 Set point 1 SP1L SP1H 100.0 C(212.0 F)
TIME 0 6553.5 minutes 0.0Dwell Time
A1SP 100.0 C
(212.0 F)
Alarm 1 Set point
A1DV Alarm 1 Deviation Value -200.0 C
(-360.0 F)
10.0 C(18.0 F)
A2SP Alarm 2 Set point 100.0 C
(212.0 F)
A2DV Alarm 2 Deviation Value -200.0 C
(-360.0 F)
10.0 C(18.0 F)
RAMP Ramp Rate 0 0.0
OFST
REFC
SHIF
PB1
TI1UserMenu
SetupMenu
TD1
Offset Value for P control
PV1 Shift (offset) Value
Proportional Band 1 Value
Integral Time 1 Value
Derivative Time 1 Value
0
0
0
0
0
25.0
100
CPB Cooling Proportional Band
Value 1 100
25.0
-200.0 C(-360.0 F)
10.0 C(18.0 F)
0.0
Reference Constant forSpecific Function 2
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
Low:
High:
High:
Low:
200.0 C( 360.0 F)
500.0 C(900.0 F)
100.0 %
60
200.0 C( 360.0 F)
High:
High:
High:
High:
High:
SP2
PB2
TI2TD2
O1HY
A1HY
A2HY
PL1
PL2
COMM
PROT
Set point 2
Proportional Band 2 Value
Integral Time 2 Value
Derivative Time 2 Value
Output 1 ON-OFF ControlHysteresis
Hysteresis Control of Alarm 1
Hysteresis Control of Alarm 2
Output 1 Power Limit
Output 2 Power Limit
Function Complexity Level
Communication InterfaceType
COMM Protocol Selection
0
Low: 0
00
0.1
0.1
0.1
0
100
100
10025.0
37.8 C(100.0 F)
1000 sec
360.0 sec
255 %
500.0 C(900.0 F)
200.0 C( 360.0 F)
High:
High:
High:
High:
High:
High:
1000 sec
500.0 C(900.0 F)
High:
High:
High:
High:
High:
High:
High:
100 %
100 %
360.0 sec
55.6 C( 100.0 F)
10.0 C(18.0 F)
10.0 C(18.0 F)
10.0 C(18.0 F)
0.1
0.1
0.1
FUNC
UM43001B
0 Basic Function Mode:
Full Function Mode:1
0 : No communication function
:1 RS-485 interface
2 : RS-232 interface
:3 4 - 20 mA analog retransmissionoutput
4 : 0 - 20 mA analog retransmissionoutput
:5 0 - 1V analog retransmissionoutput
6 : 0 - 5V analog retransmissionoutput
:7 1 - 5V analog retransmissionoutput
8 :
:
0 - 10V analog retransmissionoutput
1
1
0
See Table 1.5, 1.6
See Table 1.5, 1.7
See Table 1.5, 1.8
0 Modbus protocol RTU mode
13
DB Heating-Cooling Dead Band
Negative Value= Overlap -36.0 0Low: 36.0%High:
-
8/10/2019 Manual BTC4300
14/142
ParameterDescriptionParameter
Description
Range
DefaultValueDefault
Value
Containedin
Contained
in
BasicFunctionBasic
Function
ParameterNotationParameter
Notation
DisplayFormatDisplay
Format
:
:
:
:
:
:
:
:
:
:
:
BAUD
DATA
PARI
STOP
AOFN
Baud Rate of Digital COMM
Data Bit count of DigitalCOMM
Parity Bit of Digital COMM
Stop Bit Count of DigitalCOMM
Analog Output Function
5
1
0
0
0
1(0)
AOLO
AOHI
Analog Output Low ScaleValueAnalog Output High ScaleValue
-19999
-19999
45536
45536
ADDR Address Assignment of DigitalCOMM Low:
Low:
Low:
High:
High:
High:
1 255
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
8
9
0.3 Kbits/s baud rate
0.6 Kbits/s baud rate
1.2 Kbits/s baud rate
2.4 Kbits/s baud rate
4.8 Kbits/s baud rate
9.6 Kbits/s baud rate
14.4 Kbits/s baud rate
19.2 Kbits/s baud rate
28.8 Kbits/s baud rate
38.4 Kbits/s baud rate
0 7 data bits
:
:
:
:
:
:
:
:
:
:
:
:
:
1 8 data bits
0
1
0
2
1
Even parity
Odd parity
No parity bit
One stop bit
Two stop bits
0 : Retransmit IN1 process value
1 : Retransmit IN2 process value
4 : Retransmit set point value
5 : Retransmit output 1 manipulationvalue
6 : Retransmit output 2 manipulationvalue
2 : Retransmit IN1 IN2 differenceprocess value
3 : Retransmit IN2 IN1 differenceprocess value
7 : Retransmit deviation(PV-SV)Value
0 C(32.0 F)
100.0 C(212.0 F)
IN1 IN1 Sensor Type Selection
T type thermocouple
E type thermocouple
B type thermocouple
R type thermocouple
S type thermocouple
J type thermocouple
K type thermocouple
Table 1.4 Parameter Description ( continued 2/7 )able 1.4 Parameter Description ( continued 2/7 )
SetupMenu
14
UM43001B
-
8/10/2019 Manual BTC4300
15/142
Low:
Low:
High:
High:
IN2U
DP2
IN2L
IN2H
IN2 Unit Selection
IN2 Decimal Point Selection
IN2 Low Scale Value
IN2 High Scale Value
-19999
-19999
45536
45536
Same as IN1U
Same as DP1
0
1000
2
1
ParameterDescriptionParameter
Description
Range
DefaultValue
Containedin
Contained
in
BasicFunctionBasic
Function
ParameterNotationParameter
Notation
DisplayFormatDisplay
Format
IN1U
IN1
DP1
IN1L
IN1H
IN1 Unit Selection
IN1 Sensor Type Selection
IN1 Decimal Point Selection
IN1 Low Scale Value
IN1 High Scale Value
-19999
-19999
45536
45536
7
13
4
8
14
5
9
0
15
6
10
1
16
7
11
2
17
12
3
0
0
1
1
2
2
3
N type thermocouple
L type thermocouple
PT 100 ohms DIN curve
PT 100 ohms JIS curve
4 - 20 mA linear current input
0 - 20 mA linear current input
0 - 1V linear Voltage input
0 - 5V linear Voltage input
1 - 5V linear Voltage input
0 - 10V linear Voltage input
Special defined sensor curve
Low:
Low:
High:
High:
0
1000
1
0(1)
1( 0 )
IN2 IN2 Signal Type Selection 1
IN2 no function
Current transformer input
4 - 20 mA linear current input
0 - 20 mA linear current input
0 - 1V linear voltage input
0 - 5V linear voltage input
1 - 5V linear voltage input
0 - 10V linear voltage input
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
Degree C unit
Degree F unit
Process unit
No decimal point
1 decimal digit
2 decimal digits
3 decimal digits
Output 1 Function 0
0
OUT1
O1TY
0
1
Reverse (heating ) control action
Direct (cooling) control action
:
:
0
1
2
3
Relay output
Solid state relay drive output
Solid state relay output
4 - 20 mA current module
:
:
:
:Output 1 Signal Type
Table 1.4 Parameter Description ( continued 3/7 )able 1.4 Parameter Description ( continued 3/7 )
SetupMenu
15
M43001B
-
8/10/2019 Manual BTC4300
16/142
ParameterDescriptionParameter
Description
Range
DefaultValueDefault
Value
Containedin
Contained
in
BasicFunctionBasic
Function
ParameterNotationParameter
Notation
DisplayFormatDisplay
Format
4
5
6
7
0 - 20 mA current module
0 - 1V voltage module
0 - 5V voltage module
1 - 5V voltage module
8 0 - 10V voltage module
:
:
:
:
:
CYC1
O1TY
Output 1 Cycle Time 100.0 sec 18.0
0
0.1Low: High:
O1FT Output 1 Failure Transfer
Mode
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0% to continue output 1 control function as the unitfails, power starts or manual mode starts.
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0% to continue output 2 control function as the unitfails, power starts or manual mode starts.
BPLS
Output 2 FunctionOUT2 0
0
1
3
: PID cooling control
: Output 2 no function
: DC power supply moduleinstalled
O2TY
CYC2
O2FT
Output 2 Signal Type
Output 2 Cycle Time
Output 2 Failure TransferMode
100.0 sec
BPLS
18.0
0
0.1
Same as O1TY
Low: High:
A1FN Alarm 1 Function 2
6 IN1 process value high alarm:
9 IN2 process value low alarm:
0 No alarm function:
4 Deviation band out of band alarm:
1 Dwell timer action:
5 Deviation band in band alarm:
8 IN2 process value high alarm:
3 Deviation low alarm:
2 Deviation high alarm:
11 IN1 or IN2 process value lowalarm
:
7 IN1 process value low alarm:
10 IN1 or IN2 process value highalarm
:
12 IN1 IN2 difference process valuehigh alarm
:
13 IN1 IN2 difference process valuelow alarm
:
:
:
14 Loop break alarm
15 Sensor break or A-D fails
:
:
:
:
1
2
3
0 Normal alarm action
Latching alarm action
Hold alarm action
Latching & actionHold
A1MD Alarm 1 Operation Mode 0
Table 1.4 Parameter Description ( continued 4/7 )able 1.4 Parameter Description ( continued 4/7 )
SetupMenu
16
Output 1 Signal Type
UM43001B
-
8/10/2019 Manual BTC4300
17/142
ParameterDescriptionParameter
Description
Range
DefaultValueDefault
Value
Containedin
Contained
in
BasicFunctionBasic
Function
ParameterNotation
Parameter
Notation
DisplayFormatDisplay
Format
SELF Self Tuning Function
Selection
0
1
Self tune function disabled
Self tune function enabled
SLEP
Sleep mode Function
Selection
0 Sleep mode function disabled
Sleep mode function enabled1
0
0
:
:A1FT
A2FT
A2FN
Alarm 1 Failure TransferMode
Alarm 2 Failure TransferMode
Alarm 2 Function
1
2
0
1
Alarm output OFF as unit fails
Alarm output ON as unit fails
Same as A1FN
Same as A1MD
Same as A1FT
A2MD Alarm 2 Operation Mode 0
1
1EIFN Event Input Function
3
4
SP2, PB2, TI2, TD2 activated toreplace SP1, PB1, TI1, TD1
Reset alarm 1 output
9
10
Disable Output 1 & Output 2
Lock All Parameters
0 Event input no function:
1 SP2 activated to replace SP1:
2 PB2, TI2, TD2 activated to replacePB1, TI1, TD1
:
:
:
5 Reset alarm 2 output:
6 Reset alarm 1 & alarm 2:
7 Disable Output 1:
8 Disable Output 2:
:
:
PVMD PV Mode Selection
:
0
1
Use PV1 as process value
Use PV2 as process value
2 Use PV1 PV2 (difference) asprocess value
3 Use PV2 PV1 (difference) asprocess value
0
0
1
2
3
4
0 second time constant
0.2 second time constant
0.5 second time constant
1 second time constant
2 seconds time constant
5 seconds time constant
10 seconds time constant
20 seconds time constant
30 seconds time constant
60 seconds time constant
5
6
7
8
9
:
:
:
:
FILT Filter Damping TimeConstant of PV
2
Table 1.4 Parameter Description ( continued 5/7 )able 1.4 Parameter Description ( continued 5/7 )
SetupMenu
17
M43001B
-
8/10/2019 Manual BTC4300
18/142
SP2F Format of set point 2 Value
0
1
set point 2 (SP2) is an actual value
set point 2 (SP2) is a deviationvalue
0
ParameterDescriptionParameter
Description
Range
DefaultValueDefault
Value
Containedin
Contained
in
BasicFunctionBasic
Function
ParameterNotationParameter
Notation
DisplayFormatDisplay
Format
:
:
:
:
:
:
SPMD Set point Mode Selection
0
1
2
3
4
5
Use SP1 or SP2 (depends on EIFN)as set point
Use minute ramp rate as set point
Use hour ramp rate as set point
Use IN1 process value as set point
Use IN2 process value as set point
Selected for pump control
SEL1 Select 1'st Parameter
0
:
:
:
:
:
:
:
:
:16
17
18
Parameter PB2 put ahead
Parameter TI2 put ahead
Parameter TD2 put ahead
0
1
2
3
4
5
6
No parameter put ahead
Parameter TIME put ahead
Parameter A1SP put ahead
Parameter A1DV put ahead
Parameter A2SP put ahead
Parameter A2DV put ahead
Parameter RAMP put ahead
Parameter OFST put ahead
Parameter REFC put ahead
Parameter SHIF put ahead
Parameter PB1 put ahead
Parameter TI1 put ahead
Parameter TD1 put ahead
Parameter CPB put ahead
Parameter SP2 put ahead
7
8
9
10
11
12
13
14
15
0
SEL2
SEL3
SEL4
Same as SEL1
Same as SEL1
Same as SEL1
0
0
0
Low:
Low:
High:
High:
SP1L
SP1H
SP1 Low Scale Value
SP1 High Scale Value
-19999
-19999
45536
45536
0 C(32.0 F)
1000.0 C(1832.0 F)
Table 1.4 Parameter Description ( continued 6/7 )able 1.4 Parameter Description ( continued 6/7 )
Select 2'nd Parameter
Select 3'rd Parameter
Select 4'th Parameter
Select 5'th ParameterSEL5 Same as SEL1 0
AD0
ADG
V1G
A to D Zero CalibrationCoefficientA to D Gain CalibrationCoefficient
Voltage Input 1 GainCalibration Coefficient
-360 360
-199.9 199.9
-199.9 199.9
Low:
Low:
Low:
High:
High:
High:
Low: High:CJTLCold Junction LowTemperature CalibrationCoefficient
-5.00 C 40.00 C
CalibrationModeMenu
SetupMenu
18
UM43001BM43001B
Parameter DB put ahead
-
8/10/2019 Manual BTC4300
19/142
-
8/10/2019 Manual BTC4300
20/142
Table 1.5 Input ( IN1 or IN2 ) Rangeable 1.5 Input ( IN1 or IN2 ) Range
Table 1.6 Range Determination for A1SPable 1.6 Range Determination for A1SP
Table 1.8 Range Determination for SP2able 1.8 Range Determination for SP2
Table 1.7 Range Determination for A2SPable 1.7 Range Determination for A2SP
Range of A1SPsame as range of
Range of SP2same as range of
Range of A2SPsame as range of
If A1FN =
If PVMD =
If A2FN =
PV1.H, PV1.L
PV1
PV1.H, PV1.L
IN1
IN1
IN1
PV2.H,PV2.L
PV2
PV2.H,PV2.L
IN2
IN2
IN2
P1.2.H, P1.2.LD1.2.H, D1.2.L
P1.2.H, P1.2.LD1.2.H, D1.2.L
IN1, IN2
IN1, IN2
IN1, IN2
Input Type
Input Type
J_TC
N_TC
K_TC
L_TC
T_TC
PT.DN
E_TC
PT.JS
B_TC
CT
R_TC
Linear ( V, mA)or SPEC
S_TC
Range Low
Range Low
Range High
Range High
-120 C
(-184 F)
1000 C(1832 F)
1300 C(2372 F)
-200 C
(-328 F)
-200 C(-328 F)
-200 C(-328 F)
1370 C(2498 F)
-250 C
(-418 F)
-250 C(-418 F)
-210 C(-346 F)
400 C(752 F)
700 C(1292 F)
-100 C
(-148 F)
900 C(1652 F)
900 C(1652 F)
600 C(1112 F)
0 C
(32 F)
0 C
(32 F)
0 C
(32 F)
1820 C(3308 F)
1767.8 C(3214 F)
1767.8 C(3214 F)
0 Amp
90 Amp
-19999
45536
P1 2, P2 1
20
UM43001B
Exception: If any of A1SP, A2SP or SP2 is configured with respect toCT input, its adjustment range is unlimited.
Exception: If any of A1SP A2SP or SP2 is configured with respect to
CT input, its adjustment range is unlimited.
-
8/10/2019 Manual BTC4300
21/142
Chapter 2 Installationhapter 2 Installation
2 2 Mounting2 Mounting
2 1 Unpacking1 Unpacking
Upon receipt of the shipment remove the unit from the carton and inspect theunit for shipping damage.If any damage due to transit , report and claim with the carrier.Write down the model number, serial number, and date code for future referencewhen corresponding with our s ervice center. The serial number (S/N) and datecode (D/C) are labeled on the box and the housing of control.
Upon receipt of the shipment remove the uni t f rom the carton and inspect the
unit for shipping damage.
I f any damage due to t ransit , report and cla im with the carrier.
Write down the model number, seria l number, and date code for future reference
when corresponding with our service center. The seria l number (S/N) and date
code (D/C) are labeled on the box and the housing of control .
Make panel cutout to dimension shown in Figure 2.1.ake panel cutout to dimension shown in Figure 2.1.Take both mounting clamps away and insert the controller into panel cutout.Install the mounting clamps back. Gently tighten the sc rews in the clamp till thecontroller front panels is fitted snugly in the cutout.
Take both mounting clamps away and insert the controller into panel cutout.
Install the mounting clamps back. Gently t ighten the screws in the clamp t il l the
controller front panels is f it ted snugly in the cutout.
Figure 2.1 Mounting Dimensionsigure 2.1 Mounting Dimensions
Dangerous voltages capable of causing death are sometimes presentin this instrument. Before installation or beginning any troubleshootingprocedures the power to all equipment must be switched off and isolated. Unitssuspected of being faulty must be disconnected and removed to a properlyequipped workshop for testing and r epair. Component replacement and internal
adjustments must be made by a qualified maintenance person only.
Dangerous vol tages capable of causing death are somet imes present
in this instrument. Before instal lat ion or beginn ing any t roubleshoot ing
procedures the power to all equipment must be switched off and isolated. Uni ts
suspected of being faulty must be disconnected and removed to a properly
equipped workshop for testing and repair. Component replacement and internal
adjustments must be made by a quali fied maintenance person only.
To minimize the possibility of fire or shock hazards, do not expose thisinstrument to rain or excessive moisture.
To minimize the possibility of fire or shock hazards, do not expose this
instrument to rain or excessive moisture.
Do not use this instrument in areas under hazardous conditions such asexcessive shock, vibration, dirt, moisture, corrosive gases or oil. The ambienttemperature of the areas should not exceed the maximum rating specified in Chapter 8.
Do not use this instrument in areas under hazardous conditions such as
excessive shock, vibration, dirt, moisture, corrosive gases or oil. The ambient
temperature of the areas should not exceed the maximum rating specified in Chapter 8.
UM43001B
21
92mm
92 mm
53 mm
Panel
Panel Cutout
-
8/10/2019 Manual BTC4300
22/142
2 3 Wiring Precautions3 Wiring PrecautionsBefore wiring, verify the label for correct model number and options. Switchoff the power while checking.
Care must be taken to ensur e that maximum voltage rating specified on the
label are not exceeded.
It is recommended that power of these units to be protected by fuses or circuitbreakers rated at the minimum value possible.
Al l u ni ts sh ou ld be inst al le d i ns id e a su it ably gr ou nd ed me tal e nc lo su re toprevent live parts being accessible from human hands and metal tools.
Al l w ir ing m us t c on fo rm to ap pr op ri at e s ta nd ar ds of go od pr ac ti ce an d l oc alcodes and regulations. Wiring must be suitable for voltage, current, andtemperature rating of the system.
Beware not to over-tighten the terminal screws.
Unused control terminals should not be used as jumper points as they maybe internally connected, causing damage to the unit.
Veri fy th at th e r at ings of th e o ut pu t d ev ices an d t he inpu ts as sp ec if ie d i nChapter 8 are not exceeded.
Electric power in industrial environments contains a certain amount of noise inthe form of transient voltage and spikes. This electrical noise can enter andadversely affect the operation of microprocessor-based controls. For thisreason we strongly recommend the use of shielded thermoc ouple extensionwire which connects the sensor to the controller. This wire is a twisted-pairconstruction with foil wrap and drain wire. T he drain wire is to be attached toground at one end only.
Before wir ing, veri fy the label for correct model number and opt ions. Switch
off the power whi le checking.
Care must be taken to ensure that maximum voltage rat ing speci fied on the
label are not exceeded.
I t is recommended that power of these uni ts to be protected by fuses or c ircu it
breakers rated at the minimum value possible.
All uni ts should be installed inside a sui tably grounded metal enclosure to
prevent l ive parts being accessible from human hands and metal tools.
All wir ing must conform to appropriate standards of good pract ice and local
codes and regulations. Wiring must be sui table for voltage, current, and
temperature rating of the system.
Beware not to over-t ighten the terminal screws.
Unused control termina ls should not be used as jumper points as they may
be internally connected, causing damage to the uni t.
Verify that the rat ings of the output devices and the inputs as specif ied in
Chapter 8 are not exceeded.
Electric power in industr ia l environments contains a certain amount of noise in
the form of t ransient voltage and spikes. This electrical noise can enter and
adversely affect the operation of microprocessor-based controls. For this
reason we strongly recommend the use of shielded thermocouple extension
wire which connects the sensor to the control ler. This wire is a twisted-pair
construct ion with foil wrap and drain wire. The drain wire is to be attached to
ground at one end only.
Figure 2.2 Lead Terminationigure 2.2 Lead Termination
Figure 2.3 Rear TerminalConnection Diagram
Figure 2.3 Rear Terminal
Connection Diagram
*
*
*
*
*
*
*
*
*
22
UM43001B
7.0mm max.3.2mm min.
Alarm 1
COMV
RTD
6
7
11
12
13
14
8
9
10 20
19
18
15
16
17
1
2
3
4
5
OP1
90-264 VAC
47-63 Hz15 VA
L
N
A
B
B
C
NO
OP2C
NO
C
NO NC
Alarm 2
AO+TX1
AOTX2
AI, CT+
EI
+
+ +
ALL RELAY CONTACTS:RESISTIVE 2A/240VAC
+
+
-
8/10/2019 Manual BTC4300
23/142
2 4 Power Wiring4 Power Wiring
The controller is supplied to operate at 11-26 VAC / VDC or 90-264VAC.Checkthat the installation voltage corresponds with the power rating indicated on theproduct label before connecting power to the controller.
The controller is suppl ied to operate at 11-26 VAC / VDC or 90-264VAC.Check
that the installat ion vol tage corresponds with the power rat ing indicated on the
product label before connecting power to the control ler.
90 264 VAC or11 26 VAC / VDC~
~
Fuse
Figure 2.4
Power Supply Connections
Figure 2.4
Power Supply Connections
This equipment is designed for installation in an enclosure which provides
adequate protection against electric shock. The enclosure must be connectedto earth ground.
Local requirements regarding electrical installation should be rigidly observed.Consideration should be given to prevent from unauthorized person access tothe power terminals.
This equipment is designed for installat ion in an enclosure which provides
adequate protection against electric shock. The enclosure must be connected
to earth ground.
Local requirements regarding electrical installation should be rigidly observed.
Consideration should be given to prevent from unauthorized person access to
the power terminals.
UM43001B
23
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
24/142
2 5 Sensor Installation Guidelines5 Sensor Installation Guidelines
Proper sensor installation can eliminate many problems in a control system. T heprobe should be placed so that i t can detect any temperature change with
minimal thermal lag. In a process that requires fairly constant heat output, theprobe shoul d be pl aced cl osed t o t he heat er. In a process w here t he heatd e m a n d i s v a r i a b l e , t h e p r o b e s h o u l d b e c l o s e d t o t h e w o r k a r e a . S o m eexperiments with probe location are often required to find this optimum position.
In a liquid process, addition of a stirrer will help to eliminate thermal lag. Sincethe thermocouple is basically a point measuring device, placing more than onethermocouple in paral lel can provide an average temperature readout andproduce better results in most air heated processes.
P r o p e r s e n s o r t y p e i s a l s o a v e r y i m p o r t a n t f a c t o r t o o b t a i n p r e c i s emeasurements. The sensor must have the correct temperature range to meetthe process requirements. In special processes the sensor might need to have
different requirements such as leak-proof, anti-vibration, antiseptic, etc.
Standard sensor l imits of error are 4degrees F ( 2degrees C ) or 0.75% ofsensed t emperat ure (hal f t hat for speci al ) pl us dr i f t caused by i mproperprotection or an over-temperature occurrence. This error is far greater thancontrol ler error and cannot be corrected on the sensor except by properselection and replacement.
Proper sensor installat ion can eliminate many problems in a control system. The
p robe should be pla ced so that i t c an detect an y temperatu re change wit h
min imal thermal lag. In a process that requi res fai rl y constant heat output, the
pr obe should be p laced clos ed to the heate r. In a pro ces s whe re the heat
d em and is var iable , the pr obe sh ould be clo sed to the wo rk are a. So me
experiments with probe locat ion are often required to f ind this opt imum posi tion.
In a l iquid process, addit ion of a sti rrer w il l help to eliminate thermal lag. Since
the thermocouple is basical ly a point measuring device, placing more than one
the rmocouple i n paral le l can p rovide an ave rage tempera tu re readout and
produce better resul ts in most ai r heated processes.
P ro pe r se nso r t y pe i s a l s o a v er y im po rt an t f ac to r t o ob ta i n p r ec ise
measurements. The sensor must have the correct temperature range to meet
the process requi rements. In special processes the sensor might need to have
different requirements such as leak-proof, anti-vibration, antiseptic, etc.
Standard sensor limits of error are 4degrees F ( 2degrees C ) or 0.75% of
s en sed temp er atu re ( hal f th at f or s peci al ) p lu s d rif t c au sed b y i mpr ope r
pro tect ion or an over- temperature occur rence. This error i s far g reater than
controller error and cannot be corrected on the sensor except by proper
selection and replacement.
24
UM43001B
-
8/10/2019 Manual BTC4300
25/142
2 6 Thermocouple Input Wiring6 Thermocouple Input Wiring
+
Figure 2.5Thermocouple Input WiringFigure 2.5
Thermocouple Input Wiring
The colour codes used on the thermocouple extension leads are shown in Table 2.1.he colour codes used on the thermocouple extension leads are shown in Table 2.1.
ThermocoupleType
Thermocouple
Type
CableMaterialCable
Material
BritishBS
British
BS
Am er icanASTM
American
ASTM
GermanDI N
German
DIN
FrenchNF EFrench
NFE
T
J
Copper ( Cu )Constantan
( Cu-Ni )
Copper ( Cu )
Constantan
( Cu-Ni )
+ bluere d
* bl ue
+ blue
red
* blue
+ redbrown
* brown
+ red
brown
* brown
+ yellowblue
* blue
+ yel low
blue
* blue
Iron ( Fe )
Constantan( Cu- Ni )
I r on ( Fe )
Constantan
( C u - N i )
+ white
re d* black
+ white
red
* black
+ red
blue* blue
+ red
blue
* blue
+ yellow
black* black
+ yel low
black
* black
K
Nickel-Chromium( Ni-Cr )
Nickel-Aluminum( Ni-Al )
Nickel-Chromium
( Ni-Cr )
Nickel-Aluminum
( Ni-Al )
+ brownblue
* red
+ brown
blue
* red
+ yellowre d
* yellow
+ yellow
red
* ye llow
+ redgreen
* green
+ red
green
* green
+ yellowpurple
* yel low
+ yellow
purple
* yellow
RSR
S
Pt-13%Rh,PtPt-10%Rh,PtPt-13%Rh,Pt
Pt-10%Rh,Pt
+ whiteblue
* green
+ white
blue
* green
+ blackre d
* green
+ black
red
* green
+ redwhite
* white
+ red
white
* white
+ yellowgreen
* green
+ yel low
green
* green
B
Pt-30%RhPt-6%RhPt-30%Rh
Pt-6%Rh
+grey
re d* grey
+grey
red
* grey
Table 2.1 Thermocouple Cable Colour Codesable 2.1 Thermocouple Cable Colour Codes
* Colour of overall sheathColour of overal l sheath
+ whiteblue
* blue
+ white
blue
* blue
+ yellow
blue* black
+ yel low
blue
* black
DIP SwitchIP Switch
If the length of thermocouple plus the extension wire is too long, it may affect thetemperature measurement. A 400 ohms K type or a 500 ohms J type thermocouplelead resistance will produce 1 degree C temperature error approximately.
If the length of thermocouple plus the extension wire is too long, it may affect the
temperature measurement. A 400 ohms K type or a 500 ohms J type thermocouple
lead resistance will produce 1 degree C temperature error approximately.
Us eCopper WireUse
Copper Wire
Us eCopper WireUse
Copper Wire
+red
grey* grey
+red
grey
* grey
UM43001B
25
Thermocouple input connections are shown in Figure 2.5. The correct type ofthermocouple extension lead-wire or compensating cable must be used for the entiredistance between the controller and the thermocouple, ensuring that the correct
polarity is observed throughout. Joints in the cable should be avoided, if possible.
Thermocouple input connections are shown in F igure 2.5 . The cor rect type of
thermocouple extension lead-wire or compensating cable must be used for the entire
distance between the control ler and the thermocouple, ensuring that the correct
polarity is observed throughout. Joints in the cable should be avoided, if possible.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
26/142
2 7 RTD Input Wiring7 RTD Input Wiring
2 8 Linear DC Input Wiring8 Linear DC Input Wiring
Figure 2.6
RTD Input Wiring
Figure 2.6
RTD Input Wiring
DC linear voltage and linear current connections for input 1 are shown in Figure2.7 and Figure 2.8 .DC linear voltage and l inear current connect ions for input 1 are shown in Figure
2.7 and Figure 2.8 .
DC linear voltage and linear current connections for input 2 are shown in Figure2.9 and Figure 2.10 .DC linear voltage and l inear current connect ions for input 2 are shown in Figure
2.9 and Figure 2.10 .
Figure 2.7Input 1 Linear Voltage WiringFigure 2.7
Input 1 Linear Voltage Wiring
DIP SwitchIP Switch
DIP SwitchIP Switch
Two-wire RTD should be avoided, if possible, for the purpo se of accuracy. A 0.4ohm lead resistance of a two-wire RTD will produce 1 degree C temperatureerror.
Two-wire RTD should be avoided, i f possible, for the purpose of accuracy. A 0.4
ohm lead res is tance o f a two-wire RTD will produce 1 deg ree C temperature
error.
RTD
Three-wire RTDhree-wire RTD
RTD
Two-wire RTDwo-wire RTD
0~1V, 0~5V1~5V, 0~10V0~1V, 0~5V
1~5V, 0~10V
26
UM43001B
RTD connection are shown in Figure 2.6, with the compensating lead connected toterminal 19. For two-wire RTD inputs, terminals 19 and 20 should be linked. Thethree-wire RTD offers the capability of lead resistance compensation provided that the
three leads should be of same gauge and equal length.
RTD connection are shown in Figure 2.6, with the compensating lead connected to
terminal 19. For two-wire RTD inputs, terminals 19 and 20 should be linked. The
three-wire RTD offers the capability of lead resistance compensation provided that the
three leads should be of same gauge and equal length.
+
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
12
3
4
5
6
7
8
9
10
1112
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
27/142
Figure 2.9Input 2 Linear Voltage WiringFigure 2.9
Input 2 Linear Voltage Wiring
Figure 2.10Input 2 Linear Current WiringFigure 2.10
Input 2 Linear Current Wiring
0~1V, 0~5V1~5V, 0~10V0~1V, 0~5V
1~5V, 0~10V
0~20mA or4~20mA0~20mA or
4~20mA
Figure 2.8Input 1 Linear Current WiringFigure 2.8
Input 1 Linear Current Wiring0~20mA or4~20mA0~20mA or
4~20mA
DIP SwitchIP Switch
UM43001B
27
+
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
28/142
2 9 CT / Heater Current Input Wiring9 CT / Heater Current Input Wiring
CT94 1
1 2+
+
DIN RailIN Rail
Fuse
MainssupplyMains
supply
Heater 1eater 1
Heater 2eater 2
Heater 3eater 3
Figure 2.11CT Input Wiring forSingle Phase Heater
Figure 2.11
CT Input Wir ing for
Single Phase Heater
Heater Supplyeater Supply Current Transformerurrent TransformerContactor
CT Signal InputT Signal Input
CT94 1
1 2+
DIN RailIN Rail
Current Transformerurrent Transformer
+
Fuse
MainssupplyMains
supply
Figure 2.12
CT Input Wiring forThree Phase Heater
Figure 2.12
CT Input Wir ing for
Three Phase Heater
Contactor
CT Signal InputT Signal Input
Make sure that the total current through CT94-1 not exceed 50A rms.ake sure that the total current through CT94-1 not exceed 50A rms.
Three PhaseHeater PowerThree Phase
Heater Power
28
UM43001B
12
3
4
5
6
7
8
9
10
1112
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
29/142
2 10 Event Input wiring10 Event Input wiring
Open CollectorInputOpen Collector
Input
Switch Inputwitch Input
+
Figure 2.13Event Input WiringFigure 2.13
Event Input Wiring
The event input can accept a switch signal as well as an open collector signal. Theevent input function ( EIFN ) is activated as the switch is closed or an open collector (or a logic signal ) is pulled down.
Also refer to for event input function.Section 4-1
The event input can accept a switch signal as well as an open collector signal. The
event input function ( EIFN ) is activated as the switch is closed or an open collector (
or a logic signal ) is pulled down.
Also refer to for event input function.ection 4-1
UM43001B
29
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
30/142
2 11 Output 1 Wiring11 Output 1 Wiring
120V/240V
Mains Supply
120V/240V
Mains Supply
Max. 2AResistiveMax. 2A
Resistive
Load
Relay Output Direct Driveelay Output Direct Drive
Relay or Triac (SSR)Output to DriveContactor
Relay or Triac (SSR)
Output to Drive
Contactor
Load
120V /240V
Mains Supply
120V /240V
Main s Supply
+
_
SSR
30mA / 5VPulsed
Volt ag e
30mA / 5V
Pulsed
Voltage
Internal Circuitnternal Circuit
5V
0V
3
4
33
33
Pulsed Voltage to Drive SSRulsed Voltage to Drive SSR
Figure 2.14Output 1 WiringFigure 2.14
Output 1 Wiring
120V /240VMains Supply120V /240V
Main s Supply
No FuseBreakerNo Fuse
Breaker
ThreePhaseHeaterPower
Three
Phase
Heater
Power
Three PhaseDeltaHeaterLoad
Three Phase
Delta
Heater
Load
Contactor
30
UM43001B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
45
6
7
8
9
10
11
12
13
1415
16
17
18
19
20
1
2
3
4
5
6
7
8
910
11
12
13
14
15
16
17
18
1920
-
8/10/2019 Manual BTC4300
31/142
0 - 1V, 0 - 5V1 - 5V, 0 - 10V0 - 1V, 0 - 5V
1 - 5V, 0 - 10V
Linear Voltageinear Voltage
Linear Currentinear Current
Maximum Load 500 ohmsaximum Load 500 ohms
Minimum Load 10 K ohmsinimum Load 10 K ohms
Max. 1A / 240Vax. 1A / 240V
Load
Triac (S SR) OutputDirect DriveTriac (SSR) Output
Direct Drive
+
+
0 - 20mA,4 - 20mA0 - 20mA,
4 - 20mA
Load
+
+
Load
120V /240V
Mains Supply
1 2 0V / 24 0 V
Mains Supply
UM43001B
31
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
32/142
2 12 Output 2 Wiring12 Output 2 Wiring
120V/240V
Mains Supply
120V/240V
Mains Supply
Max. 2AResistiveMax. 2A
Resistive
Load
Relay Output Direct Driveelay Output Direct Drive
Relay or Triac (SSR)Output to DriveContactor
Relay or Triac (SSR)
Output to Drive
Contactor
Load
120V /240V
Mains Supply
1 2 0V / 24 0 V
Main s Supply
+
_
SSR
30mA / 5VPulsed
Vol tage
30mA / 5V
Pulsed
Voltage
Internal Circuitnternal Circuit
5V
0V
5
6
33
33
Pulsed Voltage to Drive SSRulsed Voltage to Drive SSR
Figure 2.15Output 2 WiringFigure 2.15
Output 2 Wiring
120V /240VMains Supply120V /240V
Main s Supply
No FuseBreakerNo Fuse
Breaker
ThreePhaseHeaterPower
Three
Phase
Heater
Power
Three PhaseDeltaHeaterLoad
Three Phase
Delta
Heater
Load
Contactor
32
UM43001B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
33/142
Linear Voltageinear Voltage
Linear Currentinear Current
Maximum Load 500 ohmsaximum Load 500 ohms
Minimum Load 10 K ohmsinimum Load 10 K ohms
Max. 1A / 240Vax. 1A / 240V
Load
Triac (S SR) OutputDirect DriveTriac (SSR) Output
Direct Drive
+
+
0 - 20mA,
4 - 20mA
0 - 20mA,
4 - 20mA
Load
0 - 1V, 0 - 5V1 - 5V, 0 - 10V0 - 1V, 0 - 5V
1 - 5V, 0 - 10V
+
+
Load
120V /240V
Mains Supply
120V /240V
Main s Supply
UM43001B
33
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
34/142
2 13 Alarm 1 Wiring13 Alarm 1 Wiring
120V/240VMains Supply120V/240VMains Supply
Max. 2AResistiveMax. 2A
Resistive
Load
Relay Output Direct Driveelay Output Direct Drive
Relay Output toDrive ContactorRelay Output to
Drive Contactor
Figure 2.16Alarm 1 WiringFigure 2.16
Alarm 1 Wiring
120V /240VMains Supply120V /240V
Main s Supply
No FuseBreakerNo Fuse
Breaker
ThreePhaseHeaterPower
Three
Phase
Heater
Power
Three PhaseDeltaHeaterLoad
Three Phase
Delta
Heater
Load
Contactor
UM43001B
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
45
6
7
8
9
10
11
12
13
1415
16
17
18
19
20
-
8/10/2019 Manual BTC4300
35/142
2 14 Alarm 2 Wiring14 Alarm 2 Wiring
120V/240VMains Supply120V/240V
Mains Supply
Max. 2AResistiveMax. 2A
Resistive
Load
Relay Output Direct Driveelay Output Direct Drive
Figure 2.17Alarm 2 WiringFigure 2.17
Alarm 2 Wiring
Relay Output toDrive ContactorRelay Output to
Drive Contactor
120V /240VMains Supply120V /240V
Main s Supply
No FuseBreakerNo Fuse
Breaker
ThreePhaseHeaterPower
Three
Phase
Heater
Power
Three PhaseDeltaHeaterLoad
Three Phase
Delta
Heater
Load
Contactor
UM43001B
35
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
36/142
2 15 RS-48515 RS-485
TX1
TX1
TX1
TX1
TX2
TX2
TX2
TX2
Terminator220 ohms / 0.5WTerminator
220 ohms / 0.5W
Max. 247 units can be linkedax. 247 units can be linked
RS-232
PC
SNA10A orSNA10BSNA10A or
SNA10B
Figure 2.18RS-485 WiringFigure 2.18
RS-485 Wiring
RS-485 to RS-232network adaptorRS-485 to RS-232
network adaptor
UM43001B
Twisted-Pair Wirewisted-Pair Wire
36
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
37/142
2 16 RS-23216 RS-232
TX1
TX2
COM
PC
9-pinRS-232 port9-pin
RS-232 port
Figure 2.19RS-232 WiringFigure 2.19
RS-232 Wiring
UM43001B
CC94-1
37
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable mustbe modified according to the following circuit diagram.If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable must
be modified according to the following circuit diagram.
1
2
3
4
5
6
7
8
9
BTC-4300
TX1TX1 RD
13
14
10
TX2 TX2 TD
COM COM GND
Female DB-9emale DB-9
To DTE ( PC ) RS -232 Por to DTE( PC ) RS-232Por t
1 DCD2 RD3 TD4 DTR5 GND6 DSR7 RTS8 CTS9 RI
1 DCD
2 RD
3 TD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 RI
Figure 2.21Configuration of RS-232Cable
Figure 2.21
Configuration of RS-232
Cable
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
-
8/10/2019 Manual BTC4300
38/142
2 17 Analog Retransmission17 Analog Retransmission
Load
Load
Load
Load
Load
Load
0 - 20mA,4 - 20mA0 - 20mA,
4 - 20mA
1 - 5 V, 0 - 5V0 - 10V1 - 5 V, 0 - 5V
0 - 10V
The total effective resistance of serialloads can't exceed 500 ohms.The total effective resistance of serial
loads can't exceed 500 ohms.
Retransmit Currentetransmit Current
The total effective resistance of parallelloads should be greater than 10K Ohms.The total effective resistance of parallel
loads should be greater than 10K Ohms.
Retransmit Voltageetransmit Voltage
Figure 2.22 AnalogRetransmission WiringFigure 2.22 Analog
Retransmission Wiring
IndicatorsPLC'sRecordersData loggersInverters etc.
Indicators
PLC's
Recorders
Data loggers
Inverters etc.
IndicatorsPLC'sRecordersData loggersInverters etc.
Indicators
PLC's
Recorders
Data loggers
Inverters etc.
UM43001B
8
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
56
7
8
9
10
11
12
13
14
1516
17
18
19
20
-
8/10/2019 Manual BTC4300
39/142
2 18 Programming Port18 Programming Port
See Figure 1.3 in Section 1-3 to find the programming port location.ee Figure 1.3 in Section 1-3 to find the programming port location.
The programming port is used for off-line automatic setup and testing procedures only.Don't attempt to make any connection to these jumpers when the unit is used for anormal control purpose.
The programming port is used for off-line automatic setup and testing procedures only.
Don't attempt to make any connection to these jumpers when the unit is used for a
normal control purpose.
Switch Unit
DMM
Calibrator
SW6400
HP 34401AP 34401A
Fluke 5520Aluke 5520A
UM43001B
NOTE
39
Figure 2.23 ProgrammingPort Wiring
Figure 2.23 Programming
Port Wir ing
Programmerconnector and
ATE connectorinserted here
Programmer
connector and
ATE connector
inserted here
Access holeon thebottom view
Access hole
on the
bottom view
I N P T 1
ProgrammerP12AProgrammer
P12A
1 ON
DIP
2
3
4
-
8/10/2019 Manual BTC4300
40/142
This unit provides an useful parameter " FUNC " which can be used to selectthe function complexity level before setup. If the Basic Mode ( FUNC = BASC )is selected for a simple application, then the following functions are ignoredand deleted from the full function menu:RAMP, SP2, PB2, TI2, TD2, PL1, PL2, COMM, PROT, ADDR, BAUD, DATA,PARI, STOP, AOFN, AOLO, AOHI, IN2, IN2U, DP2, IN2L, IN2H, EIFN, PVMD,
FILT, SLEP, SPMD and SP2F.
This unit provides an useful parameter FUNC which can be used to select
the function complexity level before setup. If the Basic Mode ( FUNC = BASC )
is selected for a simple application, then the following functions are ignored
and deleted from the full function menu:
RAMP SP2, PB2, TI2, TD2, PL1, PL2, COMM, PROT, ADDR, BAUD, DATA,
PARI, STOP AOFN, AOLO, AOHI, IN2, IN2U, DP2, IN2L, IN2H, EIFN, PVMD,
FILT, SLEP SPMD and SP2F.
(1) Second setpoint(2) Second PID(3) Event input(4) Soft start (RAMP)(5) Remote set point
(6) Complex process value(7) Output power limit(8) Digital communication(9) Analog retransmission
(10) Power shut off (Sleep Mode)(11) Digital filter(12) Pump control(13) Remote lockout
(1) Second setpoint
(2) Second PID
(3) Event input
(4) Soft start (RAMP)
(5) Remote set point
(6) Complex process value
(7) Output power limit
(8) Digital communication
(9) Analog retransmission
(10) Power shut off (Sleep Mode)
(11) Digital filter
(12) Pump control
(13) Remote lockout
(1) Input 1: Thermocouple, RTD, Volt, mA(2) Input 2: CT for heater break detection(3) Output 1: Heating or Cooling ( Relay, SSR, SSRD, Volt, mA )(4) Output 2 : Cooling ( Relay, SSR, SSRD, Volt, mA ), DC Power supply.(5) Alarm 1: Relay for Deviation, Deviation Band, Process, Heater Break, Loop
Break, Sensor Break, Latch, Hold or Normal Alarm.(6) Alarm 2: Relay for Deviation, Deviation Band, Process, Heater Break, Loop
Break, Sensor Break, Latch, Hold or Normal Alarm.(7) Dwell Timer(8) Heater B