machine learning based classification of inrush, external ...cikitusi.com/gallery/2-aug-949.pdf ·...
TRANSCRIPT
Machine Learning Based Classification of Inrush,
External and Internal Faults in Differential
Protection of Power Transformer
Devshree Rana Neelesh Kumar
Electrical and Electronics Department Electrical and Electronics Department
M.Tech 4th
sem(ED&PS), DIMAT Assistant Professor, neelesh.patel27
Raipur, [email protected] @gmail.com
Abstract — This abstract illustrates differential protection
scheme for Power Transformer (PT) by using combined
Discrete Wavelet Transform (DWT), Principal Component
Analysis (PCA) and Support Vector Machines (SVMs)
methods. Discrimination between internal, external fault
and magnetizing inrush condition is a very challenging
task in PT differential protection scheme. Therefore,
discrete wavelet transform is used to extract the time and
frequency division information simultaneously from the
relaying signal (i.e. differential current) and then PCA is
used to reduce the dimensions of decomposed signals from
DWT. And then these reduced dimensional features of the
relaying signal is used to train and test the SVM to detect
internal fault. The PT is modelled in PSCAD/EMTDC
software to obtain the relaying under different operating
conditions. The proposed algorithm is evaluated in
MATLAB under different operating conditions of PT and
the tested data is simulated in PSCAD/EMTDC by varying
inception angle, fault location, fault resistances, loading
conditions of PT. Results show that the proposed
algorithm is stable, reliable and selective under different
operating conditions of PT
Keywords: - Power transformer (PT), Harmonic Restrained
(HR), Discrete wavelet transform (DWT), Principal
Component Analysis (PCA), Support vector machine (SVM).
1. INTRODUCTION
Medium and large power transformers are very important and
vital component of electric power systems. Due to its
importance and cost, its protection needs to be addressed
properly. The protection should be fast and reliable. Proper
continuous monitoring of power transformer can provide early
warning of electrical failure and can prevent catastrophic
losses. It can minimize damages and enhanced the reliability
of power supply. Accordingly, high expectations are imposed
on power transformer protective relays. Expectations from
protective relays include dependability (no missing
operations), security (no false tripping), speed of operation
(short fault clearing time) and stability [1]. Differential
protection scheme is generally used as the primary protection
of medium- and large-sized power transformers, in which the
value of differential current greater than no-load value
indicates an internal fault. A transformer is said to be a static
device as it contains two or more than two stationary electric
circuits which is interlinked with the common magnetic
circuits. Its purpose is to transfer the electrical energy from
one circuit to another circuit through magnetic core without
changing the frequency. It works on the principle of faradays
law of electromagnetic induction. There are two winding in
transformer the one who receives energy from the AC Mains
is called primary winding and the one who delivers energy to
the load is called the secondary winding. Power transformer is
also a kind of a transformer that is generally used in the
generating station (step-up) and at substation (step-down) to
transfer the large amount of power. These are used for
stepping up and stepping down the voltages. They are
designed in such a way that they deliver maximum efficiency
at full load.
There are different operating conditions of the power
transformer will be discussed briefly. Power transformer
operating conditions can be categorized in the following ways:
Normal operating mode is the one when power transformer
supplies the power to the load without interruption. It can be
said that the power system is in the healthy condition. In this
case rated or less than rated current flows in the transformer,
that means load could varies [1].Over-excitation is the one
when sudden removal of the large reactive load leads to the
increment in power systems terminal voltage [2].External fault
is the one they occur outside of the transformer and outside the
protection zone of the power transformer. It could be LG, LL,
LLG, LLL or LLLG fault. In this case huge amount of current
above rated current flows in the power system. Internal fault is
the one when winding of the power transformer gets short
circuited with each other and it could get grounded. The types
of internal fault are LG, LL, LLG, LLL, LLLG and TT fault.
In this case huge amount of current above rated current flows
in the power system. Magnetizing inrush is the one when
transformer gets connected from the source the huge amount
of current flows in the source side of the power transformer.
This is also called the energization of the transformer. The
magnitude of this current depends on switching angle between
0-360 degree and the residual flux presents in the transformer
core [1].The magnitude of the inrush current could be 10 times
greater than the rated current. Sympathetic inrush is the one
when any transformer gets energized in parallel with the
previous one than it affects the current in the previous
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/20
transformer. This condition is called sympathetic inrush [2].
Recovery inrush is the one when sever external fault gets
removed it affects the characteristics of the currents in the
power transformer.
Power transformers are devices that require continuous
monitoring and fast protection because they are essential to the
electrical power systems. About 10% of faults take place into
power transformers, in which 70% of these faults are caused
by short-circuits in its windings. In case of magnetizing inrush
and sympathetic inrush large current flows in the source side.
This large current from the source results in large differential
current, which in turn causes the relay to operate undesirably.
Owing to this reason, conventional differential relays are
blocked for few initial cycles of energization which makes the
relay operation delayed on switching-in of the transformer on
faults. And also in case of high amplitude current due to
external fault causes CTs to saturate this results in the high
amplitude differential current. Therefore, discrimination
between magnetizing inrush, external fault and internal fault
condition is the key to improve the security of the differential
protection scheme. Traditionally, two types of approaches are
used for the purpose of discrimination between inrush and
internal fault, that is, harmonic restraint (HR) and waveform
identification (WI) concepts [2].The HR is based on the fact
that the second harmonic (sometimes the fifth) component of
the magnetizing inrush current is considerably larger than that
in a typical fault current. The literature reveals the extensive
use of the HR method. However, the HR-based method fails to
prevent false tripping of relays because high second harmonic
components during internal faults and low second harmonic
components are generated during magnetizing inrush for
transformers having modern core material [1].Therefore, the
techniques based on detection of second/fifth harmonic
component are not useful to discriminate between the
magnetizing inrush and internal fault condition of modern
power transformers. The second method consists of
distinguishing magnetizing inrush and over-excitation
condition from internal fault condition on the basis of WI
concept. The development of advanced digital signal-
processing techniques and recently introduced artificial neural
network (ANN) provide an opportunity to improve the
conventional WI technique and facilitate faster, secured and
dependable protection for power transformers. However, a
large number of training data samples, slow convergence
during training, and a tendency to over-fit data are the
limitations of ANN-based schemes. The importance of the
protection and limitations of the existing techniques inspired
to do research in this area.
2. DIFFERENTIAL PROTECTION
Differential current relay is use to protect power transformer
in case of internal fault. It is mainly two types, Simple
differential relay and Percentage differential relay. Percentage
differential relay without restraining coil is considered as a
simple differential relay. Number of turns in restraining coil
and operating coil decides the slope of the differential relay.
Slope of the differential relay is in between differential current
vs. restraining current (biased current).
Figure.1. Percentage differential relay
The percentage differential relay can be made more immune to
mal-operation on 'external fault' by increasing the slope of the
characteristic. That‟s why the dual slope percentage
differential current relay is used. Where slope1 gives high
sensitivity for internal faults and slope2 gives high security for
external fault [3]. The magnitude of slope2 is greater than
slope1 to achieve proper sensitivity and security. Knee point
of dual slope differential current is decided where saturation of
CT is started.
Figure 2. Operating characteristics of percentage
differential relay
3. DISCRETE WAVELET TRANSFORM
Discrete signal is comprises by using scaling and wavelet
function is:
, -
√ ∑ , - , -
√ ∑∑ , - , -
(1)
Where,
, - is scaling function
, - is wavelet function
, - is approximate coefficient
, - is detailed coefficient
is shifting parameter
is shifting parameter
Approximate (2) and detailed (3) coefficients are:
, -
√ ∑ , - , -
(2)
, -
√ ∑ , - , -
(3)
In simple way it means that sampled input signal passes
through LPF and HPF simultaneously and then it gets down-
Equipment under
protection
CB CBCT
n:1
CT
n:1 ILIS
I2
I1
(I1 - I2)
Nr/2Nr/2
No
Restraining coil
Operating coilPercentage
differential
relay
Trip Trip
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/21
sampled by two. Output of the HPF is a convolution between
input signal and coefficients of HPF and then it gets down-
sampled by two. This is called detailed coefficient and it
contains upper half of the frequency present in the input
signals [8]. And Output of the LPF is also a convolution
between input signal and coefficients of LPF and then it gets
down-sampled by two. This is called approximate coefficient
and it contains lower half of the frequency present in the input
signals. And then again output of LPF goes to same kind of
LPF and HPF and gets down-sampled by two, and this process
goes on until goal will be reached.
The frequency band of detailed and approximate coefficient
after m-level of decomposition are:
,
-
,
-
Figure. 3. Decomposition LPF and HPF
Figure (3) shows the decomposition LPF and HPF of
Daubichies6 (db6) mother wavelet family, where 6 represents
the order of the filter.
Figure. 4. Decomposition filtering block diagram
After the decomposition of sampled signals, these
approximate and details coefficient pass through thresholding
block.
4. PRINCIPAL COMPONENT ANALYSIS
Here the basic application of principal component analysis is
to reduce the dimension of the input vector that goes to the
SVM for classification purpose so that the classification
accuracy of the SVM increases.
PCA finds a new set of dimensions such that all the
dimensions are orthogonal and ranked according to the
variance of data among them [7]. It means more important
principle axis occurs first.
PCA works as follows:
It first calculates the covariance matrix of „n‟
dimensional input data sets.
Calculate Eigen vectors and corresponding Eigen
values.
Arrange the Eigen vectors according to their Eigen
values in decreasing order.
Select first „m‟ Eigen vectors and that will be the new
„m‟ dimensions.
Transform the original n-dimensional data points into
„m‟ dimensions.
Figure. 5. Mapping of data from two dimensional to one
dimensional in the red line axis
5. SUPPORT VECTOR MACHINES
Support vector machines are supervised learning model with
associated learning algorithm that analyses set of data for
classification or regression purposes. Here SVM is used for
classification purposes. SVM as a classifier takes training data
sets of two categories (class1 and class2) after that it builds the
model that assigns new data set into either class1 or class2.
SVMs are based on the idea of finding a hyper-plane that best
divides a dataset into two class, in case of two-dimensional
data points the hyper-plane would be a line (one dimension
less than the dimension of the input data). A good separation
is achieved by the hyper-plane that has the largest distance to
the nearest training-data point of any class (so-called
functional margin), since in general the larger the margin the
lower the generalization error of the classifier [15]. Figure
4.12 shows three hyper-plane H1, H2 and H3, where H1
clearly does not classify the input data sets, but H2 and H3
both are able to classify. Due to the fact that H3 has high
functional margin than the H2 hyper-plane, H3 would be the
LPF
HPF
LPF
HPF
LPF
HPF 2
2
2
2
2
2
f(n)
Detail 1
Detail 2
Detail n
Approximate n
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/22
best hyper-plane that would lead to the minimum
generalization error
Figure.6. Choosing proper hyper-plane to classify two
types of data sets
SVMs are a group of learning machines for solving pattern
recognition problems efficiently. SVMs try to find the hyper-
plane, which separates optimally the training patterns
according to their classes (i.e. hyper-plane with maximum
boundary margin). They have a good generalization
performance over traditional approaches, since their training is
based on the principle of structural risk minimization (SRM)
(i.e. minimizing the upper bound on the expected risk), while
the training traditional approaches is based on empirical risk
minimization (i.e. minimizing the number of the training
error). SVMs have a high computational efficiency in terms
of speed and complexity [11]. They are also more preferable
when dealing with high dimensional data as they are more
robust than traditional approaches which may over-fit the data.
The description of SVMs classification can be explained as
follows:
5.1 Linearly Separable Data:-
Let us consider a linear classification problem aiming to find
optimal separating hyper-plane with maximum margin [15].
Assuming that for the set of n training data:
*( ) * + + (4)
Where,
i=1, 2, 3….n;
is a d-dimensional input vector
indicate class 1 or -1 for the corresponding
For this it is possible to find a maximum margin hyper-
plane that linearly separates the appropriate class as shown in
the figure 4.5. In such case hyper-plane can be described by
the formula ; where is a weight vector and
is a bias. Additionally it is possible to find two hyper-planes
with no points between them one is 1 and another
one is , then a distance between these two
hyper-plane is called margin
‖ ‖ .
Figure.1. Hard margin classifier
Then class 1 (1) and class 2 (-1) for the input vector is
depicted by the following formulla.
, if =1
(5)
Or
, if =
(6)
For better SVM classifier this margin should be maximum, it
means the ‖w ‖ should be minimum. This finding w and
b can be done by several optimization techniques [12]. But
this optimization problem is solved by introducing Lagrange
multipliers and then class of the unknown data x may be
determined as follows:
( ) ( )
(7)
Where,
∑ ( )
Where,
is a input vector to be classify
is a support vector
is a class of given support vector
is a Lagrange multiplier
is a number of support vector
is a bias value (calculated during training process)
5.2 Linearly Non-separable Data:-
In case when training data can‟t be able to get separated by
linear hyper-plane then these input vector gets mapped into the
one higher dimension feature space in such a way so that the
mapped data gets separated by linear hyper-plane [15]. For
this purpose nonlinear function ø is used. Then the class of
unknown data may be expressed as follows:
X1
X2H1
H2
H3
X1
X2
w
w·x -
b = 0
w·x -
b= -1
w·x -
b = 1 ||w||
2
||w||b
Support
vectors
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/23
( ) (∑ ( ) ( )
) ( )
( ) ( ) ( ) ( )
Then the decision function of SVM is:
( ) (∑ ( )
) ( )
The most common kernel functions are:
Linear: ( ) ( )
Polynomial: ( ) ( )
Gaussian radial basis function: ( )
( ‖ ‖ ) , for
Hyperbolic tangent: ( ) ( ),
for some (not every) and
Figure.2. Non-linear based SVM classification
5.3 Soft margin:-
It may happen that even in new feature space it is impossible
to split this space into two classes. Then, soft margin method
may be employed to moderate optimization constraints. Soft
margin method allows the classifier to misclassify some
examples, what is illustrated in figure. This method introduces
two parameters (used in training process) [15].
is a slack variable that allow patterns to be in the margin
( , margin errors) or to be misclassified (
).
Figure.3. Soft margin classifier
5.4 General features
Support vector machine is considered as a promising method
for classification due to
solid mathematical foundations,
fast optimization algorithms,
no local optima, unlike in neural networks,
SVMs maximize the margin, which corresponds to
maximizing the generalization performance,
SVMs deal with nonlinear classification efficiently
(employing the kernel trick),
Good generalization performance even in case of
high-dimensional input vector and a small set of
training data.
The following algorithm provides the power transformer
protection
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/24
Figure.4. DWT and SVM based PT protection algorithm
6. MODELLING, SIMULATION AND RESULTS
Power transformer protection are performed in this thesis. To
achieve that first a power system is modelled in the
PSCAD/EMTDC where a source, power transformer,
transmission line and load is connected. Where ratings of
source is 400kV 50Hz, power transformer is 315 MVA
400kV/220kV 50Hz, transmission line is 220kv 100km and
the load is 285 MW, 137MVAR. The operation of Power
Transformer can be categorized into five categories which is
normal operating condition, internal fault, external fault, over
excitation, magnetizing inrush/ Sympathetic inrush. For these
operating conditions differential current is being generated in
the PSCAD/EMTDC software. In case of inrush three things
are considered first is the residual flux, second is the switching
angle and last is the loading conditions.
Figure.11. Power transformer internal fault model with
CTs
In this case switching angle is varied from 0° to 330° in the
interval of 10° and residual flux is varied from 10% to 80% of
rated flux. When generating internal fault current three things
are considered, fault percentage of winding, fault inception
angle (time of fault) and fault resistances (0.01 ohm to 20
ohm). And this differential currents are sampled at 10 kHz.
The different operating conditions model and the differential
current waveform are shown in the figures above and below.
Figure.12. Power transformer magnetizing inrush model
with residual flux and CTs
Apply Discrete Wavelet Transform
operating signal (differential current)
Start
NO
Yes
Idiff > Ithreshold
Principal Component Analysis
SVM (Support Vector Machine)
Trip signal
Inrush / external fault
Internal fault
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/25
Figure.13. Power transformer with external faults
Figure.14. Differential current during magnetizing inrush
of power transformer
Figure .14. is obtained by energizing the power transformer at
210 degree (inception angle), no load and residual flux with
75% of the rated flux. During these conditions differential
currents nature is peaky in some region and flat in another
region. That is due to the saturation of the transformer core.
Figure.15. Differential current during L-G fault on the
primary side of PT
Figure .15. is obtained by creating a fault at phase A (with
ground) of the primary side of the power transformer at 180
degree (inception angle) of the sinusoidal voltage, 20% of the
winding A, 10 ohm fault resistance with full load conditions
Figure.16. Differential current during LL fault on the
primary side of PT
Figure .16. is obtained by creating a fault at phase A and B
(without ground) of the primary side of the power transformer
at 180 degree (inception angle) of the sinusoidal voltage, 20%
of the winding A and B with full load conditions.
Figure.17. Differential current during LL-G fault on the
primary side of PT
Figure .17. is obtained by creating a fault at phase A and B
(with ground) of the primary side of the power transformer at
180 degree (inception angle) of the sinusoidal voltage, 20% of
the winding A and B, 10 ohm fault resistance with full load
conditions.
Figure.18. Differential current during LLL fault on the
primary side of PT
Figure .18. is obtained by creating a fault at phase A, B and C
(without ground) of the primary side of the power transformer
at 180 degree (inception angle) of the sinusoidal voltage, 20%
of the winding A, B and C with full load conditions.
Figure.19. Differential current during LLL-G fault on the
primary side of PT
Figure .19. is obtained by creating a fault at phase A, B and C
(with ground) of the primary side of the power transformer at
180 degree (inception angle) of the sinusoidal voltage, 20% of
-15.00
-10.00
-5.00
0.00
5.00
10.000
.00
0.0
20
.03
0.0
50
.06
0.0
80
.09
0.1
10
.13
0.1
40
.16
0.1
70
.19
0.2
10
.22
0.2
40
.25
0.2
70
.28
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
transforme
-30.00
-20.00
-10.00
0.00
10.00
20.00
30.00
0.0
0
0.0
2
0.0
4
0.0
6
0.0
8
0.0
9
0.1
1
0.1
3
0.1
5
0.1
7
0.1
9
0.2
1
0.2
3
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
-30.00
-10.00
10.00
30.00
0.0
0
0.0
20
.04
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al
curr
ent
(A)
Time (second)
fault occurrence
-40.00
-20.00
0.00
20.00
40.00
0.0
0
0.0
2
0.0
4
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
-40.00
-20.00
0.00
20.00
40.00
0.0
0
0.0
2
0.0
4
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
-40.00
-20.00
0.00
20.00
40.00
0.0
0
0.0
2
0.0
4
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/26
the winding A, B and C, 10 ohm fault resistance with full load
conditions.
Figure.10. Differential current during L-G fault on the
secondary side of PT
Figure .20. is obtained by creating a fault at phase A (with
ground) of the secondary side of the power transformer at 180
degree (inception angle) of the sinusoidal voltage, 20% of the
winding A, 5 ohm fault resistance with full load conditions.
Figure.11. Differential current during LL fault on the
secondary side of PT
Figure .21. is obtained by creating a fault at phase A and B
(without ground) of the secondary side of the power
transformer at 180 degree (inception angle) of the sinusoidal
voltage, 20% of the winding A and B with full load
conditions.
Figure .212. Differential current during LL-G fault on the
secondary side of PT
Figure .22. is obtained by creating a fault at phase A and B
(with ground) of the secondary side of the power transformer
at 180 degree (inception angle) of the sinusoidal voltage, 20%
of the winding A and B, 5 ohm fault resistance with full load
conditions.
Figure.13. Differential current during LLL fault on the
secondary side of PT
Figure .23. is obtained by creating a fault at phase A, B and C
(without ground) of the secondary side of the power
transformer at 180 degree (inception angle) of the sinusoidal
voltage, 20% of the winding A, B and C with full load
conditions.
Figure.14. Differential current during LLL-G fault on the
secondary side of PT
Figure .24. is obtained by creating a fault at phase A, B and C
(with ground) of the secondary side of the power transformer
at 180 degree (inception angle) of the sinusoidal voltage, 20%
of the winding A, B and C, 5 ohm fault resistance with full
load conditions.
Figure.15. Differential current during external fault
Figure .25. is obtained by creating a fault at phase A, B and C
(with ground) at the end of secondary CT of the differential
-20.00
-10.00
0.00
10.00
20.00
0.0
0
0.0
20
.04
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
-40.00
-20.00
0.00
20.00
40.00
0.0
0
0.0
20
.04
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
-30.00
-20.00
-10.00
0.00
10.00
20.00
30.00
0.0
0
0.0
20
.04
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
-40.00
-20.00
0.00
20.00
40.00
0.0
0
0.0
2
0.0
4
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
-40.00
-20.00
0.00
20.00
40.00
0.0
0
0.0
2
0.0
4
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
-4
-2
0
2
4
0.0
0
0.0
2
0.0
4
0.0
6
0.0
8
0.0
9
0.1
1
0.1
3
0.1
5
0.1
7
0.1
9
0.2
1
0.2
3
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
external fault
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/27
relay / starting of a transmission line, inception angle of 210
degree of the sinusoidal voltage, 0.01 ohm fault resistance
with full load conditions.
Figure.16. Differential current during normal operating
condition
Figure .26. is obtained when transformer operates normally
with full load and no faults or any kind of a disturbances. The
nature of differential current in this case is sinusoidal with
extremely low magnitude.
Figure.17. Single phase differential current during
magnetizing inrush condition
Figure.18. Single phase view of differential current during
internal fault
After modelling of power transformer in PSCAD these
differential current are used in the MATLAB for DWT and
SVM based transformer protection. This differential current
first decomposed into different frequency band using db6
mother wavelet. The reconstructed decomposed signals for
internal fault, external fault and inrush are shown in the
following figures.
Figure.19. Different details and approximate signals of
internal fault current
Figure.20. Different details and approximate signals of
inrush current
-0.20
-0.10
0.00
0.10
0.200
.00
0.0
2
0.0
4
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al
curr
ent
(A)
Time (second)
-5.00
0.00
5.00
10.00
0.0
2
0.0
4
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
0.3
0Dif
fere
nti
al
curr
ent
(A)
Time(second)
-40.00
-20.00
0.00
20.00
40.00
0.0
0
0.0
20
.04
0.0
6
0.0
8
0.1
0
0.1
2
0.1
4
0.1
6
0.1
8
0.2
0
0.2
2
0.2
4
0.2
6
0.2
8
Dif
fere
nti
al c
urr
ent
(A)
Time (second)
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/28
Figure.21. Different details and approximate signals of
external fault current
From those DWT frequency band only fourth and fifth level
decomposed signal are passes through PCA for dimensions
reduction these reduced dimensional signals are called
features. This feature goes to the kernel based radial basis
function non-linear mapping SVM classifier for classification
purposes. Figure explains how each phase of the differential
currents samples passes through the protection algorithm. First
50 samples (1/4th
cycle) from pre fault and 200 samples (1
cycle) from post fault of differential current for each phase is
taken, then from these individual differential current, DWT
(db6 mother wavelet) decomposed detail4(25 samples) and
detail5( 18) computed.
That means for each individual differential current total
number of decomposed samples are 43 and 43 X 3 = 129 for
all the three phases. These decomposed samples goes to the
three different PCA for three types of classifications using
SVMs. The PCA1 reduces the dimensions from 129 to 10, the
PCA2 reduces the dimension from 129 to 8 and PCA3 reduces
the dimensions from 129 to 7. Using this algorithm the final
internal fault detection accuracy achieved is 99.16% on total
number of different 2486 testing samples that is illustrated in
the table 5. 1. Apart from the internal fault detection there
exist another two SVM. The second SVM identifies in which
side of the transformer windings, fault has occurred and the
third SVM discriminates between inrush and external fault.
Table 5.2 and table 5.3 shows their classification accuracy.
Figure.22. An Algorithm for power transformer protection
In this thesis 4030 training samples, 2486 testing samples, and
6516 total samples were generated. Training data is used to
create a differential power transformer protection model and
the testing samples is used to find the accuracy of that created
differential protection model. To do that it took only one cycle
data from occurrence time of inrush, internal and external
fault. The above algorithm is performed in this thesis.
FAULT AND
INRUSH
TRAINING
SAMPLE
TESTING
SAMPLE
FALSE
DETECTION
Accuracy
Internal fault
(primary and secondary
winding fault)
3280 2000 12
99.16%
Inrush and
external fault 750 486 09
Total samples 4030 2486 21
Table.1. Classification accuracy table for internal fault,
inrush and external faults
Trip Signal
operating signal (differential current)
(Ida(250), Idb(250), Idc(250))
Start
NO
SVM 3SVM 2
SVM 1
INRUSH
AND
EXTERNAL
FAULT
INTERNAL
FAULT
Yes
PWF SWF INRUSH EXTERNAL
FAULT
Idiff > Ithreshold
Apply Discrete Wavelet Transform
(detail4(25), detail5(18))
PCA 3
129 X 7
PCA 2
129 X 8
PCA 1
129 X 10
[Ida(d4,d5) 43], [Idb(d4,d5) 43], [Idc(d4,d5) 43]
EnableEnable
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/29
FAULT UNIT
AND INRUSH
TRAINING
SAMPLE
TESTING
SAMPLE
FALSE
DETECTION
Accuracy
Primary winding fault
1640 1000 00
100% Secondary
winding faults
1640 1000 00
Total samples 3280 2000 00
Table .2. Classification accuracy table for primary and
secondary winding faults
FAULT UNIT
AND INRUSH
TRAINING
SAMPLE
TESTING
SAMPLE
FALSE
DETECTION
Accuracy
Inrush 350 226 00
100% External fault 400 260 00
Total samples 750 486 00
Table .3. Classification accuracy table for inrush and
external faults
7. CONCLUSION
The proposed protection based on combined wavelet, PCA
and SVM algorithm provides a differential protection for
Power Transformer. Which provides much more security than
the other existing ANN and conventional dual slope
percentage differential based protection. Here DWT extracted
the different time and frequency based information from
relaying signals then PCA is used to reduce the dimensions of
the detailed coefficients of DWT that passes through SVM
based classifier and then above protection algorithm achieved
an accuracy of 99.16% to detect the internal fault from
magnetizing inrush and external fault current. To achieve that
much accuracy it only took 1 cycle data from differential
current for the processing which leads to the fast power
transformer protection. Apart from fault detection this
algorithm also gives additional information on which side of
the transformer windings are damaged and also the external
fault and inrush conditions separately. This classify the
primary winding faults from secondary winding faults with
100% accuracy, and for the classification between inrush and
external fault it also achieved 100% accuracy.
In future the classification among all types of internal faults
(a-g, b-g, c-g, ab, bc, ca, ab-g, bc-g, ca-g, abc, abc-g) in each
side of the transformer windings will be performed with good
classification accuracy. And also to enhance the speed of
operation the data require for the processing would be reduce
and search for the new features so that SVM classify more
accurately. And this proposed algorithm can be implemented
in the real time.
8. REFERENCE
[1] M. Tripathy and R. P. Maheshwari, “Probabilistic neural-
network-based protection of power transformer,” IET
Electric Power Applications, vol. 1, no. 5, pp. 793 - 798,
Sept. 2007.
[2] M. Tripathy and R. P. Maheshwari, “Power
TransformerDifferential Protection Based On Optimal
Probabilistic Neural Network,” IEEE Transactions on
Power Delivery, vol. 25, no. 1, pp. 102 - 112, Jan. 2010.
[3] A. L. Orille-Fernandez and N. K. Ghonaim, “A FIRANN
as a differential relay for three phase power transformer
protection,” IEEE Transactions on Power Delivery, vol.
16, no. 2, pp. 215 - 218, Apr 2001.
[4] M. C. Shin and C. W. Park, “Fuzzy logic-based relaying
for large power transformer protection,” IEEE
Transactions on Power Delivery, vol. 18, no. 3, pp. 718 -
724, July 2003.
[5] S. A. Saleh and M. A. Rahman, “Real-time testing of a
WPT-based protection algorithm for three-phase power
transformers,” IEEE Transactions on Industry
Applications, vol. 41, no. 4, pp. 1125 - 1132, Aug. 2005.
[6] E. C. Segatto and D. V. Coury, “A differential relay for
power transformers using intelligent tools,” IEEE
Transactions on Power Systems, vol. 21, no. 3, pp. 1154 -
1162, Aug. 2006.
[7] E. Vazquez and I. I. Mijares, “Transformer Differential
Protection Using Principal Component Analysis,” IEEE
Transactions on Power Delivery, vol. 23, no. 1, pp. 67 -
72, Jan. 2008.
[8] A. M. Gaouda and M. M. Salama, “DSP Wavelet-Based
Tool for Monitoring Transformer Inrush Currents and
Internal Faults,” IEEE Transactions on Power Delivery,
vol. 25, no. 3, pp. 1258 - 1267, July 2010.
[9] D. Barbosa and U. C. Netto, “Power Transformer
Differential Protection Based on Clarke's Transform and
Fuzzy Systems,” IEEE Transactions on Power Delivery,
vol. 26, no. 2, pp. 1212 - 1220, April 2011.
[10] J. Yin and Y. Zhu, “Power transformer fault diagnosis
based on support vector machine with cross validation
and genetic algorithm,” International Conference on
Advanced Power System Automation and Protection, Oct.
2011.
[11] M. Elsamahy and M. Babiy, “An intelligent approach
using SVM to enhance turn-to-turn fault detection in
power transformers,” IEEE Electrical Power and Energy
Conference, Oct. 2012.
[12] A. M. Shah and B. R. Bhalja, “Discrimination Between
Internal Faults and Other Disturbances in Transformer
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/30
Using the Support Vector Machine-Based Protection
Scheme,” IEEE Transactions on Power Delivery, vol. 28,
no. 3, pp. 1508 - 1515, April 2013.
[13] H. Dashti and M. S. Pasand, “Power Transformer
Protection Using a Multiregion Adaptive Differential
Relay,” IEEE Transactions on Power Delivery, vol. 29,
no. 2, pp. 777 - 785, April 2014.
[14] A. Aktaibi and M. A. Rahman, “An Experimental
Implementation of the dq -Axis Wavelet Packet
Transform Hybrid Technique for Three-Phase Power
Transformer Protection,” IEEE Transactions on Industry
Applications, vol. 50, no. 4, pp. 2919 - 2927, Aug. 2014.
[15] D. Bejmert, “Analysis of potential use of the SVM
technique for transformer protection,” IEEE Power
Systems Computation Conference, February 2015.
[16] R. P. Medeiros and F. B. Costa, “Power Transformer
Differential Protection Using the Boundary Discrete
Wavelet Transform,” IEEE Transactions on Power
Delivery, vol. 31, no. 5, pp. 2083-2095, December 2015.
[17] A. M. Shah and B. R. Bhalja, “Power transformer
differential protection using S-transform and Support
Vector Machine,” National Power Systems Conference
(NPSC), Dec. 2016.
[18] S. Poornima and K. Ravindra, “Comparison of CWT &
DWT based algorithms in combination with ANN for
protection of power transformer,” International
Conference on Signal Processing, Communication,
Power and Embedded System, Oct. 2016.
[19] S. K. Murugan and S. P. Simon, “Power transformer
protection using chirplet transform,” IET Generation,
Transmission & Distribution, vol. 10, no. 10, pp. 2520 -
2530, July 2016.
[20] M. F. Abbas and L. Zhiyuan, “Inrush current
discrimination in power transformer differential
protection using wavelet packet transform based
technique,” IEEE PES Asia-Pacific Power and Energy
Engineering Conference, Oct. 2016.
[21] A. Ashrafian and M. Mirsalim, “Application of a
Recursive Phasor Estimation Method for Adaptive Fault
Component Based Differential Protection of Power
Transformers,” IEEE Transactions on Industrial
Informatics, vol. 13, no. 3, pp. 1381 - 1392, June 2017.
[22] L. Sevov and U. Khan, “Enhancing Power Transformer
Differential Protection to Improve Security and
Dependability,” IEEE Transactions on Industry
Applications, vol. 53, no. 3, pp. 2642 - 2649, June 2017.
[23] M. S. Deshmukh and V. T. Barhate, “Microcontroller
based differential relay using fuzzy logic for transformer
protection,” International Conference on Intelligent
Computing and Control Systems, June 2017.
CIKITUSI JOURNAL FOR MULTIDISCIPLINARY RESEARCH
Volume 6, Issue 8, August 2019
ISSN NO: 0975-6876
http://cikitusi.com/31