Advanced Soft Starter

Presentation

January 2014

Page 2: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Range– 32 Models– 23 ~ 1600 A– 7.5 ~ 800 kW

• Voltage Ranges– 380 ~ 690 VAC

• Protection– IP20 LV-DS-0023B ~ LV-DS-0105B– IP00 LV-DS-0145B ~ LV-DS-1600C

Advanced Soft Starters

Page 3: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Control Voltages– 110 ~ 120 VAC

• Standard Approvals– CE: IEC 60947-4-2

– C-Tick

– RoHS: Compliant with EU Directive 2002/95/EC

Advanced Soft Starters

Page 4: LV Advanced Soft starter Familiarisation Presentation - SSUK

                              

 LV-DS-         –   –     –                                       

 

          

                  Control voltage         

 

                  C12 = 110 ~ 120 VAC         

 

                            

 

                  Mains voltage         

 

                  7 = 380 ~ 690 VAC                             

 

          

                  Bypass         

 

                  B = internally bypassedC = non-bypassed

                              

          

                  Nominal current rating

Model Range

Page 5: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Available for models: LV-DS-0145B ~ LV-DS-0220B

LV-DS-0255B ~ LV-DS-1000B

• Provide IP20 protection against accidental contact

Accessories: Fingerguards

Page 6: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Optional plug-in communication modules:– DeviceNet– Modbus– Profibus– USB– EtherNet/IP– Modbus TCP– Profinet

Accessories: Communication Modules

Page 7: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Operational control (start, stop, reset)

• Operating feedback (status, current and temperature)

• Maximum cable distance 100 m

Accessories: Remote Operator

Page 8: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Replicate functionality and contents of built-in display and interface

• Full graphical LCD display

• Parameter Upload/Download capability

• Operate in parallel to built-in interface

• Remote mountable up to 3m with cable supplied

• IP20 with mounting kit

Accessories: Remote Control Panel

Page 9: LV Advanced Soft starter Familiarisation Presentation - SSUK

• WinStart– Sales Engineer software

(not for end users)– Selects the right starter for the

application

• WinMaster– Control, monitor and program

starters remotely

Software Tools

Page 10: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Intuitive graphical user interface.

• Adaptive Control is the leading edge soft start technology.

• Bypassed up to 1000A as standard.

• Inside delta (6-wire) connection for the whole range.

• Adjustable bus bars 360C – 1600C.

• Comprehensive and customisable motor protection.

• Emergency Run.

• Shorted SCR Action.

• DC Braking – contactorless.

Key Selling Points

Page 11: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Display graphical LCD• 4 line text – real language feedback

messages• Real time graphs of motor operating

performance• Menus – standard, extended & quick

set• Logs

– 99 Events– Last 8 Trips

User Interface

Page 12: LV Advanced Soft starter Familiarisation Presentation - SSUK

Status LEDs

Metering screens

Trip diagnostics

Trip log

Event log

Local control pushbuttons

Navigationpushbuttons

Performance logs

Full text language display

Easy to Use

Page 13: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Standard Menu• Extended Menu• Quick Setup

Quick Setup

- Pump, centrifugal- Pump, submersible- Fan, damped- Fan, undamped- Compressor, screw- Compressor,

reciprocating- Conveyor- Crusher, rotary- Crusher, jaw

Pump, centrifugal

Parameter1-A Motor FLC2-A Start Mode2-J Adaptive Start Profile2-D Start Ramp Time2-H Stop Mode2-K Adaptive Stop Profile2-I Stop Time

Suggested ValueModel dependentAdaptive ControlEarly Acceleration10 secondsAdaptive ControlLate Deceleration15 seconds

Simple Programming Options

Page 14: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Cabling or bus-bar work for higher power installations can be costly and require significant panel space.

• LV-DS soft starters 360C ~ 1600C and 500B ~ 1000B reduce cable costs and panel space requirements because they allow top or bottom connection of both input and output cabling.

• LV-DS soft starters 255B ~ 425B allow top or bottom inputs, outputs accessible from bottom

Adjustable/Flexible Busbar Configuration

Page 15: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Pluggable terminal blocks make wiring easy.

• Separate terminal blocks for control and I/O ensure tidier wiring.

Easy-Access Cabling

Page 16: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Full text interface with selectable language

– English, Chinese, German, Italian, French, Spanish, Brazilian Portuguese, Russian.

• Quick Setup function

• Advanced Menu offers specialised functions. These turn this superior soft starter into a powerful motor management system.

Intuitive Interface

Page 17: LV Advanced Soft starter Familiarisation Presentation - SSUK

• LV-DS soft starters deliver extensive monitoring information to support process improvement and maintenance. Feedback is available on-screen or via serial, analog and relay outputs.

• Programmable Screen

Metering and Monitoring

Page 18: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Time-stamped Trip and Event logs with full details of operating conditions.

• Counters record the starter’s operating

history:– Hours run, kWh, number of starts– User-resettable (password required), plus

lifetime

Logs and Counters

Page 19: LV Advanced Soft starter Familiarisation Presentation - SSUK

• The LV-DS soft starter can be programmed for two separate start scenarios. Typical application of this capability includes:– A single LV-DS soft starter to

control duty-standby pumps.– Different start performance for

varying load conditions.– Soft braking.

Dual-Parameter Sets

Page 20: LV Advanced Soft starter Familiarisation Presentation - SSUK

• DC brake is used to electrically brake high inertia loads. The brake cycle produces a motor brake torque which approximates the set motor torque.

• Increase productivity of machines such as band-saws and chippers by reducing the time needed to replace saw bands or cutting heads.

• The LV-DS soft starter pulses the DC over all three phases and does not require an external contactor.

DC Braking

Page 21: LV Advanced Soft starter Familiarisation Presentation - SSUK

• The LV-DS soft starter’s jog function allows the operator to run the motor at part speed in either the forward or reverse direction.

• Max torque is approx 50%~75% of motor FLT in forward and 25%~60% FLT in reverse.

• This is ideal for machine positioning of loads such as mixers or hopper bins ready for unloading.

Jog ForwardJog Reverse Normal Operation

1

2

3

Jog Operation

Page 22: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Uninterrupted operation of unmanned installations such as irrigators, flood pumps, remote pump stations is aided by the LV-DS soft starter’s Auto-Reset function.

Auto Reset

9-A Auto-Reset Action9-B Maximum Resets 9-C Reset Delay Groups A&B9-D Reset Delay Group C

9-A Auto-Reset Action

GroupA

B

C

TripsCurrent ImbalancePhase LossPower LossMains FrequencyUndercurrentInstantaneous OvercurrentInput A TripMotor OverloadMotor ThermistorStarter Overtemperature

Auto-Reset of Fault Conditions

Page 23: LV Advanced Soft starter Familiarisation Presentation - SSUK

• In the case of fire, equipment such as ventilation fans in high rise buildings can be required to run at all costs.

• Activation of the LV-DS’s Emergency Run mode initiates a start and deactivates all protections, enabling the motor to run as long as possible despite the deteriorating environment.

Emergency Run Mode

Page 24: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Not only does the LV-DS soft starter provide great starting and stopping, it is also a premium motor protection system.

• Motor overload protection is an important consideration for all applications. The LV-DS soft starter provides protection levels that are often only available from dedicated and expensive high-end motor protection relays.

• The LV-DS soft starter’s second order thermal model allows motors to be used to their full potential without fear of damage from overloading.

Premium Overload Protection

Page 25: LV Advanced Soft starter Familiarisation Presentation - SSUK

• SCR Shorted Action keeps your plant running even if one phase of the LV-DS soft starter is damaged.

• In the event that a damaged SCR is detected in one phase the LV-DS soft starter offers the option to continue operation using two phase control. This ensures continued operation while long term repair of the damage is initiated.

SCR Shorted Action

Page 26: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Each LV-DS soft starter protection system is fully adjustable to site specific requirements.– Adjustable protection levels– Adjustable protection delays– Selectable protection actions

• By default each protection system will trip the LV-DS soft starter. However, to accommodate special circumstances, the action taken by a LV-DS soft starter protection system can also be set to Warn & Log or Log Only.

Fully Adjustable Protection

Page 27: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Constant current is the traditional form of soft starting, which raises the current from zero to a specified level and keeps the current stable at that level until the motor has accelerated.

• Constant current starting is ideal for applications where the start current must be kept below a particular level.

Initial current (parameter 2C)Current limit (parameter 2B)Full voltage current

1

2

3

Rotor speed (% full speed)

Cur

rent

(%

mot

or fu

ll lo

ad c

urre

nt)

Start Method: Constant Current

Page 28: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Current ramp soft starting raises the current from a specified starting level (1) to a maximum limit (3), over an extended period of time (2).

• Current ramp starting can be useful for applications where:– the load can vary between starts– the load breaks away easily, but starting time needs to be extended– the electricity supply is limited

4

Initial current (parameter 2C)Start ramp time (parameter 2D) Current limit (parameter 2B)Full voltage current

1

2

3

Time

Cur

rent

(%

mot

or fu

ll lo

ad c

urre

nt)

Start Method: Current Ramp

Page 29: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Kickstart provides a short boost of extra torque at the beginning of a start, and can be used in conjunction with current ramp or constant current starting.

• Kickstart can be useful to help start loads that require high breakaway torque but then accelerate easily (for example flywheel loads such as presses).

Kickstart level (parameter 2E)Kickstart time (parameter 2F)Initial current (parameter 2C)Start ramp time (parameter 2D) Current limit (parameter 2B)Full voltage current

4

1

2

3

5

6

Rotor speed (% full speed)

Cur

rent

(%

mot

or fu

ll lo

ad c

urre

nt)

Start Method: Kickstart

Page 30: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Adaptive Control is an intelligent motor control technique. In an Adaptive Control soft start, the LV-DS soft starter adjusts the current in order to start the motor within a specified time and using a selected acceleration profile.

Start Method: Adaptive Control Start

Page 31: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Examples:– Late acceleration on conveyors for a gentle start without belt flap

or chain couplings on milliscreens or belt couplings on fans.

– Early acceleration on submersible pumps where you need to be above minimum speed quickly.

– Constant acceleration and deceleration where they need linear response without need for tacho feedback.

Start Method: Adaptive Control Start

Page 32: LV Advanced Soft starter Familiarisation Presentation - SSUK

Stop Method Performance Result

Coast To Stop Natural load run down

TVR Soft Stop Extended run down time

Adaptive Control Extended run down time according to selected deceleration profile

Brake Reduced run down time

Soft starters are often used in pumping applications to eliminate the damaging effects of fluid hammer. Adaptive Control should be the preferred stop method for these applications.

Stop Methods

Page 33: LV Advanced Soft starter Familiarisation Presentation - SSUK

• During each start and stop, the soft starter compares the motor’s estimated speed with the selected profile.

• The soft starter then adjusts the power to the motor to achieve the selected profile (more power if the estimated speed is too low, less power if the speed is too high).

Adaptive Control

Page 34: LV Advanced Soft starter Familiarisation Presentation - SSUK

• The algorithm refines its model with data from every subsequent start and stop.

• The user can fine tune the adaptive control gain for smoother performance.

• Changing the gain or motor settings will restart the learning process, and the next start will use Constant Current.

Adaptive Control

Page 35: LV Advanced Soft starter Familiarisation Presentation - SSUK

• Controls acceleration/deceleration – is largely unaffected by changes in load.

• Provides choice of starting and stopping profiles – performance can be matched to load requirements.

• Ideal for pumping stopping: the varying needs of pump applications mean no single deceleration profile is ideal for all situations.

Adaptive Control