lonworks adapter - rockwell automation · 2019. 8. 15. · lonworks adapter is transmitting control...
TRANSCRIPT
LonWorks Adapter
20-COMM-LFRN 1.xxx
User Manual
Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls” (Publication SGI-1.1) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will the Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
Attentions help you:
• identify a hazard• avoid the hazard• recognize the consequences
Important: Identifies information that is especially important for successful application and understanding of the product.
!ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Shock Hazard labels may be located on or inside the drive to alert people that dangerous voltage may be present.
Summary of Changes
This is the first release of the LonWorks adapter FRN1.xxx.
S-ii Summary of Changes
Table of Contents
Preface About This ManualRelated Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . P-1Rockwell Automation Support. . . . . . . . . . . . . . . . . . . . . . . . P-2
Chapter 1 Getting StartedComponents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Chapter 2 Installing the AdapterPreparing for the Installation . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Connecting the Adapter to the Network . . . . . . . . . . . . . . . . 2-1Connecting the Adapter to the Drive . . . . . . . . . . . . . . . . . . . 2-3Applying Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Chapter 3 Configuring the AdapterConfiguration Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Using the PowerFlex HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2Setting the I/O Configuration. . . . . . . . . . . . . . . . . . . . . . . . . 3-3Setting the Comm Fault Action . . . . . . . . . . . . . . . . . . . . . . . 3-4Setting the Idle Fault Action . . . . . . . . . . . . . . . . . . . . . . . . . 3-5Resetting the Adapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6Viewing the Adapter Configuration . . . . . . . . . . . . . . . . . . . . 3-7
Chapter 4 Configuring the LonWorks NetworkOverview of LonWorks Functionality . . . . . . . . . . . . . . . . . . 4-1Operating the Drive Using a LonMark Profile. . . . . . . . . . . . 4-2Node Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4Network Variable Inputs (NVIs) . . . . . . . . . . . . . . . . . . . . . . 4-5Network Variable Outputs (NVOs) . . . . . . . . . . . . . . . . . . . . 4-9Network Configuration Inputs (NCIs) . . . . . . . . . . . . . . . . . 4-13Conditions Required for Operation . . . . . . . . . . . . . . . . . . . 4-19Resource Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
ii Table of Contents
Chapter 5 TroubleshootingLocating the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . 5-1PORT Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2MOD Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3NET A Status Indicator (Service Indicator). . . . . . . . . . . . . . 5-4Viewing and Clearing Adapter Diagnostic Items. . . . . . . . . . 5-5Viewing and Clearing Events. . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Appendix A SpecificationsCommunications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Appendix B Adapter ParametersParameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Appendix C Logic Command/Status WordsPowerFlex 70 and PowerFlex 700 Drives . . . . . . . . . . . . . . . C-1
Glossary
Index
Preface
About This Manual
Documentation can be obtained online at http://www.ab.com/manuals.
The following conventions are used throughout this manual:
• Parameter names are shown in the following format Parameter xxx - [*]. The xxx represents the parameter number. The * represents the parameter name. For example Parameter 01 - [DPI Port].
• Menu commands are shown in bold type face and follow the format Menu > Command. For example, if you read “Select File > Open,” you should click the File menu and then click the Open command.
Topic PageRelated Documentation P-1Conventions Used in This Manual P-1Rockwell Automation Support P-2
Related Documentation
For: Refer to: PublicationDriveExplorer™ DriveExplorer Getting Started Manual
DriveExplorer Online Help 9306-GR001…
DriveTools 2000™ DriveTools 2000 Online Help HIM HIM Quick Reference 20HIM-QR001…PowerFlex™ 70 Drive PowerFlex 70 User Manual
PowerFlex 70/700 Reference Manual 20A-UM001…PFLEX-RM001…
PowerFlex 700 Drive PowerFlex 700 User Manual PowerFlex 70/700 Reference Manual
20B-UM001…PFLEX-RM001…
Network Cabling LonMark Layers 1-6 Interoperability Guidelines, Appendix A “Cable Requirements for the TP/FT-10 Channel.”
www.lonmark.org
Conventions Used in This Manual
P-2 About This Manual
• The firmware release is displayed as FRN X.xxx. The “FRN” signifies Firmware Release Number. The “X” is the major release number. The “xxx” is the minor update number. This manual is for Firmware release 1.xxx.
• This manual provides information about the LonWorks adapter and using it with PowerFlex 70 and 700 drives. Refer to the documentation for your product for specific information about how it works with the adapter.
Rockwell Automation offers support services worldwide, with over 75 sales/support offices, over 500 authorized distributors, and over 250 authorized systems integrators located through the United States alone. In addition, Rockwell Automation representatives are in every major country in the world.
Local Product Support
Contact your local Rockwell Automation representative for sales and order support, product technical training, warranty support, and support service agreements.
Technical Product Assistance
If you need to contact Rockwell Automation for technical assistance, please review the information in Chapter 5, Troubleshooting, first. If you still have problems, then call your local Rockwell Automation representative.
Rockwell Automation Support
U.S. Allen-Bradley Drives Technical Support:E-mail: [email protected]: (1) 262.512.8176Fax: (1) 262.512.2222Online: www.ab.com/support/abdrives
UK Customer Support Center:E-mail: [email protected]: +44 (0) 870 2411802Fax: +44 (0) 1908 838804
German Customer Service Center:E-mail: [email protected]: +49 (0) 2104 960-630Fax: +49 (0) 2104 960-501
Chapter 1
Getting Started
Chapter 1 provides information about the 20-COMM-L LonWorks adapter, an embedded communication option specifically for PowerFlex 70 and 700 (Standard) drives.
Figure 1.1 Components of the Adapter
Topic Page TopicComponents 1-1 Safety Precautions 1-3Features 1-2 Quick Start 1-5Compatible Products 1-2 Modes of Operation 1-6Required Equipment 1-3
Components
# Part Description� Status Indicators Three LEDs indicate the status of the connected drive, adapter,
and network. Refer to Chapter 5, Troubleshooting, for details.� DPI Connector A 20-pin, single-row shrouded male header. An Internal
Interface cable connects to this connector and one on the drive.� Terminal Block A 6-screw terminal block connects the adapter to the network.
�
�
�
1-2 Getting Started
The LonWorks adapter features the following:
• The adapter is mounted in the drive and receives its required power from the drive.
• Status indicators report the status of the drive communications, adapter, and network. They are visible both when the drive cover is opened and when it is closed.
• Based on the LonMark Functional Profile: “Variable Speed Motor Drive: 6010.”
• Send and receive Datalink data.
• Read/write access to parameters is available. You can configure and monitor parameter values over the networks.
• User-defined fault actions let you determine how the adapter and drive respond to communication disruptions on the network.
• LonMark conformance tested.
• Flash-upgradable.
DPI (Drive Peripheral Interface) is a second generation peripheral communication interface and a functional enhancement to SCANport. The LonWorks adapter is compatible with specific Allen-Bradley PowerFlex 7-Class drives. At the time of publication, compatible products include:
• PowerFlex 70 drives• PowerFlex 700 (Standard) drives
The PowerFlex 70/700 are used for examples in this manual. Refer to the respective user manuals for additional information.
Important: The LonWorks adapter will only work with the above specified products. It will NOT work with other products susch as PowerFlex 700S, PowerFlex 7000, and PowerFlex 700 Vector.
Features
Compatible Products
Getting Started 1-3
Equipment Shipped with the Adapter
When you unpack the adapter, verify that the package includes:
User-Supplied Equipment
To install and configure the LonWorks adapter, you must supply:
Please read the following safety precautions carefully.
Required Equipment
❑ One LonWorks adapter❑ A 2.54 cm (1 in.) and a 15.24 cm (6 in.) Internal Interface cable
(only one cable is needed to connect the adapter to the drive)❑ One grounding wrist strap❑ This manual❑ Diskette containing resource files
❑ A small flathead screwdriver❑ Network-specific cable to connect the adapter to the network. Refer
to the network-specific documentation for the cable recommendations and requirements.
❑ Configuration tools, such as:– PowerFlex HIM– DriveExplorer (version 2.01 or higher)– DriveExecutive (version 1.01 or higher)– LonMaker configuration software
Safety Precautions
!ATTENTION: Risk of injury or equipment damage exists. Only qualified electrical personnel familiar with drive and power products and the associated machinery should plan or implement the installation, start up, configuration, and subsequent maintenance of the product using a LonWorks adapter. Read and understand this manual in its entirety before proceeding. Failure to comply may result in injury and/ or equipment damage.
!ATTENTION: Risk of injury or death exists. The drive may contain high voltages that can cause injury or death. Remove all power from the drive, and then verify power has been removed before installing or removing a LonWorks adapter.
1-4 Getting Started
!ATTENTION: Risk of injury or equipment damage exists. DPI or SCANport host products must not be directly connected via 1202 cables. Unpredictable behavior due to timing and other internal procedures can result if two or more hosts are connected in this manner.
!ATTENTION: Risk of injury or equipment damage exists. If the LonWorks adapter is transmitting control I/O to the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting an adapter.
!ATTENTION: Risk of injury or equipment damage exists. Parameter 6 - [Comm Flt Action] lets you determine the action of the adapter and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a hazard of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
!ATTENTION: Risk of injury or equipment damage exists. Parameter 7 - [RcvHrtBeat Time] lets you determine how long it will take your adapter to detect network communication losses. By default, this parameter is set to 120 seconds. You can set it so that the duration is shorter, longer, or disabled. Take precautions to ensure that the setting does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
!ATTENTION: Risk of injury or equipment damage exists. When a system is configured for the first time, there may be unintended or incorrect machine motion. Disconnect the motor from the machine or process during initial system testing.
!ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for purposes of example. There are many variables and requirements with any application. Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication.
!ATTENTION: Risk of equipment damage exists. The adapter contains ESD (Electrostatic Discharge) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage, Publication 8000-4.5.2.
Getting Started 1-5
This section is designed to help experienced users start using the LonWorks adapter. If you are unsure how to complete a step, refer to the referenced chapter
Quick Start
Step Action Refer to 1 Review the safety precautions for the adapter. Throughout this
manual2 Verify that the drive is properly installed. Drive User
Manual3 Install the adapter.
Verify that the drive and the network are not powered. Then, connect the adapter to the network and to the drive. Use the captive screws to secure and ground the adapter to the drive.
Chapter 2, Installing the Adapter
4 Apply power to the adapter.Verify that the adapter and network are installed correctly and then apply power to them. The adapter receives power from the drive. The topmost status indicator should be solid green. Refer to Chapter 5, Troubleshooting, for a description of the other LEDs.
Chapter 2, Installing the Adapter
5 Configure the adapter for your application.Install and bind network variables. Set the parameters for the following features as required by your application:• I/O configuration• Fault actions
Chapter 3, Configuring the Adapter
6 Set up the network to communicate with the adapter.Use a network tool (such as LonMaker) to configure the adapter on the network.
Chapter 4, Configuring the LonWorks Network
1-6 Getting Started
The adapter uses four status indicators to report its operating status. They can be viewed on the adapter or through the drive cover.
Figure 1.2 Status Indicators (location on drive may vary)
If any other conditions occur, refer to Chapter 5, Troubleshooting.
Modes of Operation
# Status Indicator
Normal Status
Description
� PORT Flashing Green
Normal Operation. The adapter is establishing an I/O connection to the drive. It will turn solid green or red.
Green Normal Operation. The adapter is properly connected and communicating with the drive
� MOD Flashing Green
Normal Operation. The adapter is operating but is not transferring I/O data.
Green Normal Operation. The adapter is operating and transmitting I/O data.
� NET A Off Normal Operation. The adapter is configured.
PWR
STS
PORT
MOD
NET A
NET B
��
�
��
�
Chapter 2
Installing the Adapter
Chapter 2 provides instructions for installing the LonWorks adapter in a PowerFlex 70 or 700 drive.
Before installing the adapter, verify that you have all required equipment. Refer to Chapter 1, Getting Started.
1. Remove power from the drive.
2. Use static control precautions.
3. Open the drive cover.
Topic PagePreparing for the Installation 2-1Connecting the Adapter to the Network 2-1Connecting the Adapter to the Drive 2-3Applying Power 2-5
Preparing for the Installation
!ATTENTION: Risk of equipment damage exists. The adapter contains ESD (Electrostatic Discharge) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage, Publication 8000-4.5.2.
Connecting the Adapter to the Network
!ATTENTION: Risk of injury or death exists. The drive may contain high voltages that can cause injury or death. Remove all power from the drive, and then verify power has been removed before installing or removing an adapter.
2-2 Installing the Adapter
4. Connect a cable to the network, and route it through the bottom of the drive. (See Figure 2.3 on page 2-4. Refer to the LonMark Layers 1-6 Interoperability Guidelines, Appendix A “Cable Requirements for the TP/FT-10 Channel.”)
5. Connect a six-pin linear plug to the network cable. (See Figure 2.1 for the terminal definitions.)
Figure 2.1 Bus Topology with Shield Example
Terminal Name Function1 SHIELD(1)
(1) It is recommended to use shielded network cable. This shield must be grounded at one point on the network via a 470K ohm, 1/4 watt, ≤ 10% metal film resistor.
Noise mitigation(2)
(2) For noise mitigation, LON trunk lines should not be run in close proximity to drive or equipment power distribution feeds.
2 NET A Network connection, polarity insensitive3 NET B Network connection, polarity insensitive4 TERM BUS Connect to TERM COM for termination of Bus(3)
topology networks.
(3) To terminate a Bus Topology network (one termination at each end of the network), connect TERM COM to TERM BUS.
5 TERM COM Termination common6 TERM FT Connect to TERM COM for termination of Free(4)
topology networks.
(4) To terminate a Free Topology network (one termination per segment), connect TERM COM to TERM FT.
Node 1 Node 2 Node "n"
SHIELD
NET A
NET B
TERM B
US
TERM C
OM
TERM F
T
SHIELD
NET A
NET B
TERM B
US
TERM C
OM
TERM F
T
SHIELD
NET A
NET B
TERM B
US
TERM C
OM
TERM F
T
Installing the Adapter 2-3
1. Remove power from the drive and network.
2. Use static control precautions.
3. Connect the Internal Interface cable to the DPI port on the drive and then to the DPI connector on the adapter.
Figure 2.2 DPI Ports and Internal Interface Cables
Connecting the Adapter to the Drive
# Description # Description� 15.24 cm (6 in.) Internal Interface cable � Network cable� DPI Connector � 2.54 cm (1 in.) Internal Interface cable
�
�
�
�
LonWorks Adapter
PowerFlex 700 Drive0 – 1 Frame
PowerFlex 700 Drive2 Frame and Larger
PowerFlex 70 Drive
2-4 Installing the Adapter
4. Secure and ground the adapter to the drive by doing the following:
– On a PowerFlex 70, fold the Internal Interface cable behind the adapter and mount the adapter on the drive using the four captive screws.
– On a PowerFlex 700, just mount the adapter on the drive using the four captive screws.
Important: All screws must be tightened since the adapter is grounded through a screw. Recommended torque is 0.9 N-m (8.0 lb.-in.).
Figure 2.3 Mounting and Grounding the Adapter
PowerFlex 70 DriveAdapter mounts in drive.
Internal Interface cable folds behind adapter and in front of the drive.
Drive
Adapter
PowerFlex 700 Drive (0 and 1 Frames)Adapter mounts on door.
PowerFlex 700 Drive (2 & Larger Frames)Adapter mounts in drive.
Installing the Adapter 2-5
1. Close the door or reinstall the cover on the drive. The status indicators can be viewed on the front of the drive after power has been applied.
2. Apply power to the drive. The adapter receives its power from the connected drive. When you apply power to the drive for the first time, the topmost status indicator on the adapter should be solid green. If it is not green, refer to Chapter 5, Troubleshooting.
Applying Power
!ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable operation may occur if you fail to verify that parameter settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive.
2-6 Installing the Adapter
Notes:
Chapter 3
Configuring the Adapter
Chapter 3 provides instructions for setting the parameters in the adapter.
For a list of parameters, refer to Appendix B, Adapter Parameters. For definitions of terms in this chapter, refer to the Glossary.
The LonWorks adapter stores parameters and other information in its own non-volatile memory. You must, therefore, access the adapter to view and edit its parameters. The following tools can be used to access the adapter parameters:
Topic Page Topic PageConfiguration Tools 3-1 Setting the Idle Fault Action 3-5Using the PowerFlex HIM 3-2 Resetting the Adapter 3-6Setting the I/O Configuration 3-3 Viewing the Adapter Configuration 3-7Setting the Comm Fault Action 3-4
Configuration Tools
Tool Refer To:PowerFlex HIM page 3-2DriveExecutive Software (version 1.01 or higher)
DriveExecutive online help
DriveExplorer Software (version 2.01 or higher)
DriveExplorer Getting Results Manual, Publication 9306-GR001... (Download Only), or the online help
LonMaker configuration software www.echelon.com
3-2 Configuring the Adapter
If your drive has either an LED or LCD HIM (Human Interface Module), access parameters in the adapter as follows:
Using an LED HIM
Using an LCD HIM
Using the PowerFlex HIM
Step Key(s) Example Screens1. Press the ALT key and then the
Sel (Device) key to display the Device Screen.
2. Press the Up Arrow or Down Arrow to scroll to the 20-COMM-L adapter. Letters represent files in the drive, and numbers represent ports. The adapter is usually connected to port 5.
3. Press the Enter key to enter your selection.
4. Edit the parameters using the same techniques that you use to edit drive parameters.
Step Key(s) Example Screens1. In the main menu, press the Up
Arrow or Down Arrow to scroll to Device Select.
2. Press Enter to enter your selection.
3. Press the Up Arrow or Down Arrow to scroll to the 20-COMM-L (LonWorks) adapter.
4. Press Enter to select the LonWorks adapter. The main menu for the adapter is displayed.
5. Edit the parameters using the same techniques that you use to edit drive parameters.
ALT Sel
OR
Device
AND
OR
OR
F-> Stopped Auto
0.00 Hz
Main Menu:DiagnosticsParameterDevice Select
Port 5 Device
20-COMM-L
Main Menu:DiagnosticsParameterDevice Select
Configuring the Adapter 3-3
The I/O configuration determines the type of data sent to the drive. Logic Command/Status and Datalinks may be enabled or disabled.
1. Set the bits in Parameter 9 - [DPI I/O Cfg]. A “1” enables the I/O. A “0” disables it.
Figure 3.1 DPI I/O Configuration Screen
Bit 0 is the right-most bit. In Figure 3.1, it is highlighted and equals “1.”
2. If Logic Command/Reference is enabled, configure the parameters in the drive to accept the Logic Command from the adapter. For example, in a PowerFlex 70 or 700 drive, set Parameter 90 - [Speed Ref A Sel] to “Network” so that the drive uses the Reference from the adapter. For details, refer to the documentation for your drive.
3. If you enabled one or more Datalinks, configure parameters in the drive to determine the source and destination of data in the Datalink(s). For example, configure the Datalinks in a PowerFlex 70 or 700 drive by setting Parameters 300 - [Data In A1] to 317 - [Data Out D2]. Also, ensure that the LonWorks adapter is the only adapter using the enabled Datalink(s). Refer to Chapter 4, Datalink Ins and Chapter 4, Datalink Outs for additional information.
4. Reset the adapter. Refer to the Resetting the Adapter section in this chapter.
The adapter is ready to send and receive I/O.
Setting the I/O Configuration
Bit Description0 Logic Command/Reference (Default)1 Datalink A2 Datalink B3 Datalink C4 Datalink D5 - 15 Not Used
Port 5 Device
20-COMM-L
Parameter #: 09DPI I/O Cfgx x x x x x x x x x x 0 0 0 0 1Cmd/Ref b00
3-4 Configuring the Adapter
By default, when communications are disrupted (for example, a cable is disconnected), the drive will remain in its current state (e.g. a running drive will continue to run) until Parameter 7 - [RcvHrtBeat Time] has elapsed.
You can configure different responses to communications disruptions using Parameter 6 - [Comm Flt Action] and Parameter 7 - [RcvHrtBeat Time].
To change the Comm fault action
• Set the value of Parameter 6 - [Comm Flt Action] to the desired response action.
Figure 3.2 Comm Fault Action Screen on an LCD HIM
Setting the Comm Fault Action
!ATTENTION: Risk of injury or equipment damage exists. Parameter 6 - [Comm Flt Action] and Parameter 7 - [RcvHrtBeat Time] let you determine the action of the adapter and connected drive if communications are disrupted. Take precautions to ensure that the setting of these parameters does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
Value Action(1)
(1) Actual action taken requires Parameter 7 - [RcvHrtBeat Time] to have a value greater than “0.”
Description0 Fault The drive is faulted and stopped. (Default)1 Stop The drive is stopped, but not faulted.2 Zero Data The drive is sent 0 for output data. This does not
command a stop.3 Hold Last The drive continues in its present state.4 Send Flt Cfg The drive is sent the data that you set in the fault
configuration parameters (Parameters 11 - [Flt Cfg Logic] through 20 - [Flt Cfg D2 In]).
Port 5 Device
20-COMM-L
Parameter #: 06Comm Flt Action
0Fault
Configuring the Adapter 3-5
• Setting Parameter 7 - [RcvHrtBeat Time] to “0” disables the fault action, and a value greater than “0” enables the fault action. If nviDrvSpeedStpt is not received by the adapter within the Parameter 7 - [RcvHrtBeat Time] value, the fault action in Parameter 6 - [Comm Flt Action] will be taken.
Changes to these parameters take effect immediately. A reset is not required.
Parameter 8 - [Idle Flt Action] lets you determine the action of the adapter and connected drive when the node is taken offline.
To change the Idle fault action
• Set the value of Parameter 8 - [Idle Flt Action] to the desired response action:
Figure 3.3 Idle Fault Action Screen on an LCD HIM
Changes to this parameter take effect immediately. A reset is not required.
Setting the Idle Fault Action
Value Action Description0 Fault The drive is faulted and stopped. (Default)1 Stop The drive is stopped, but not faulted.2 Zero Data The drive is sent 0 for output data. This does not
command a stop.3 Hold Last The drive continues in its present state.4 Send Flt Cfg The drive is sent the data that you set in the fault
configuration parameters (Parameters 11 - [Flt Cfg Logic] through 20 - [Flt Cfg D2 In]).
Port 5 Device
20-COMM-L
Parameter #: 08Idle Flt Action
0Fault
3-6 Configuring the Adapter
To set the fault configuration parameters
If you set Parameter 6 - [Comm Flt Action] or Parameter 8 - [Idle Flt Action] to “Send Flt Cfg,” the values in the following parameters are sent to the drive after a communications fault occurs. You must set these parameters to values required by your application.
Changes to these parameters take effect immediately. A reset is not required.
Changes to some adapter parameters require that you reset the adapter before the new settings take effect. You can reset the adapter by cycling power to the drive or by using the following parameter:
• Set Parameter 5 - [Reset Module] to Reset Module.
Figure 3.4 Reset Screen on an LCD HIM
When you enter 1 = Reset Module, the adapter will be immediately reset. When you enter 2 = Set Defaults, the adapter will set all adapter parameters to their factory-default settings. After performing a Set Defaults, enter 1 = Reset Module so that the new values take effect. The value of this parameter will be restored to 0 = Ready after performing the reset or setting the defaults.
Number Name Description11 Flt Cfg Logic A 16-bit value sent to the drive for Logic Command. 12 Flt Cfg Ref A 32-bit value (0 – 4294967295) sent to the drive as a
Reference or Datalink. Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most significant word of the value must be set to zero (0) or a fault will occur.
13 – 20 Flt Cfg x1 InFlt Cfg x2 In
Resetting the Adapter
!ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting control I/O to the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting a connected adapter.
Value Description0 Ready (Default)1 Reset Module2 Set Defaults
Port 5 Device
20-COMM-L
Parameter #: 05Reset Module
1Reset Module
Configuring the Adapter 3-7
The following parameters provide information about how the adapter is configured. You can view these parameters at any time.
Viewing the Adapter Configuration
Parameter No. Name and Description Details03 [Ref/Fdbk Size]
Displays the size of the reference and feedback as set in the ping message.
Default: 0 = 16-bitValues: 0 = 16-bit
1 = 32-bitType: Read Only
04 [Datalink Size]Displays the size of each Datalink word. The drive determines the size of the Datalinks.
Default: 0 = 16-bitValues: 0 = 16-bit
1 = 32-bitType: Read Only
06 [Comm Flt Action]Sets the action that the adapter will take if it detects that network communications have been disrupted (if Parameter 7 - [RcvHrtBeat Time] times out before nviDrvSpeedStpt is updated from the network).
Default: 0 = FaultValues: 0 = Fault
1 = Stop2 = Zero Data3 = Hold Last4 = Send Flt Cfg
Type: Read/WriteReset Required: No
07 [RcvHrtBeat Time]Sets the time used as a Receive Heartbeat timer and triggers the fault action in Parameter 6 - [Comm Flt Action].
Default: 120.0Minimum: 0.0 secondsMaximum: 3276.7 secondsType: Read/WriteReset Required: No
!ATTENTION: Risk of injury or equipment damage exists. Parameter 6 - [Comm Flt Action] and Parameter 7 - [RcvHrtBeat Time] let you determine the action of the adapter and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Take precautions to ensure that the setting of these parameters does not create a hazard of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
!ATTENTION: Risk of injury or equipment damage exists. Parameter 6 - [Comm Flt Action] and Parameter 7 - [RcvHrtBeat Time] let you determine the action of the adapter and connected drive if communications are disrupted. Take precautions to ensure that the setting of these parameters does not create a hazard of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
3-8 Configuring the Adapter
08 Idle Flt Action]Sets the action that the adapter will take during offline/disable occurrences.
Default: 0 = FaultValues: 0 = Fault
1 = Stop2 = Zero Data3 = Hold Last4 = Send Flt Cfg
Type: Read/WriteReset Required: No
10 [DPI I/O Active]Displays I/O that the adapter is set to transmit. The value of this parameter will usually be equal to the value of Parameter 9 - [DPI I/O Cfg].
Default: xxx0 0001Bit Values: 0 = I/O disabled
1 = I/O enabledType: Read OnlyBit Definitions0 = Cmd/Ref1 = Datalink A2 = Datalink B3 = Datalink C4 = Datalink D5 = Not Used6 = Not Used7 = Not Used
Parameter No. Name and Description Details
BitDefault 10000x xx
0123457 6
Chapter 4
Configuring the LonWorks Network
Chapter 4 provides information about configuring network variables to access a PowerFlex 70 or 700 drive when using a LonWorks adapter.
A network variable is a data item that a particular device application program expects to get from other devices on a network (an input network variable) or expects to make available to other devices on a network (an output network variable). Data exchange on a LonWorks network is handled with Standard Network Variable Types (SNVTs), which represent different types of standard data (e.g. temperature, pressure, voltage, etc.).
When a program writes into one of its output network variables, the new value of the network variable is propagated across the network to all nodes with input network variable connected to that output network variable. A network variable can only be bound to another network variable of the same type.
Specific network variables are described in sections Network Variable Inputs (NVIs), Network Variable Outputs (NVOs), and Network Configuration Inputs (NCIs).
Important: Any changes made via the LCD HIM to a parameter that is also updated by the network will be overwritten when the next network update occurs.
Topic PageOverview of LonWorks Functionality 4-1Operating the Drive Using a LonMark Profile 4-2Node Operations 4-4Network Variable Inputs (NVIs) 4-5Network Variable Outputs (NVOs) 4-9Network Configuration Inputs (NCIs) 4-13Conditions Required for Operation 4-19Resource Files 4-20
Overview of LonWorks Functionality
4-2 Configuring the LonWorks Network
A LonMark profile defines the functional profile for a node communicating with other nodes. The profile specifies which SNVTs (Standard Network Variable Types) and SCPTs (Standard Configuration Property Types) are used, and provides a semantic meaning about the information being communicated.
When a profile is implemented in a node, it’s called a LonMark object. One node can have several objects implemented. The LonWorks adapter has two objects: a node object and a drive object. The node object is used to control the other objects in a node. See Figure 4.1.
Figure 4.1 Node Object
The drive object is based on a specific LonMark functional profile (“Variable Speed Motor Drive: 6010”), as shown in Figure 4.2.
Operating the Drive Using a LonMark Profile
Node Object
MandatoryNetworkVariables
nv1 nviObjRequestSNVT_obj_request nv2 nvoObjStatus
SNVT_obj_status
Configuring the LonWorks Network 4-3
Figure 4.2 Drive Object
Variable Speed MotorDrive: 6010
MandatoryNetworkVariables
OptionalNetworkVariables
Manufacturer-DefinedNetworkVariables
nv1 nviDrvSpeedStptSNVT_switch
nv2nviDrvSpeedScaleSNVT_lev_percent
nv4nvoDrvCurntSNVT_amp
nv3nvoDrvSpeedSNVT_lev_percent
nv8nvoDrvStatusSNVT_state
nv9nvoFreqActSNVT_freq_hz
nv6nvoDrvPwrSNVT_power_kilo
nv7nvoDrvRunHoursSNVT_time_hour
nv5 nvoDrvVoltSNVT_volt
Configuration Propertiesnc50 - nciMaxSpeednc53 - nciMinSpeednc48 - nciRcvHrtBt nc49 - nciSndHrtBt nc52 - nciMinOutTm nc158 - nciNmlSpeednc159 - nciNmlFreqnc160 - nciRampUpTm nc161 nciRampDownTm nc162 nciDrvSpeedScale
nv18nvoDatalinkD1UNVT_DATALINK
nv17nvoDatalinkC2UNVT_DATALINK
nv16nvoDatalinkC1UNVT_DATALINK
nv19nvoDatalinkD2UNVT_DATALINK
nv27nviDatalinkD1UNVT_DATALINK
nv26nviDatalinkC2UNVT_DATALINK
nv25nviDatalinkC1UNVT_DATALINK
nv28nviDatalinkD2UNVT_DATALINK
nv10 nvoFB_configSNVT_count
nv14 nvoDatalinkB1UNVT_DATALINK
nv15nvoDatalinkB2UNVT_DATALINK
nv12nvoDatalinkA1UNVT_DATALINK
nv13nvoDatalinkA2UNVT_DATALINK
nv24nviDatalinkB2UNVT_DATALINK
nv23nviDatalinkB1UNVT_DATALINK
nv22nviDatalinkA2UNVT_DATALINK
nv21 nviDatalinkA1UNVT_DATALINK
nv20nviNV_configUNVT_DPI_CONFIG
nv11 nvoGenDataUNVT_DATALINK
Manufacturer- Defined Configuration Properties
ncRA1 nciParRdAdrncRA2 nciParWriAdrncRA3 nciParWriData
4-4 Configuring the LonWorks Network
The following sections describe the basics of node operation.
WINK (What is a WINK?)
WINK is a network command that verifies communication with a node. The NET A indicator will flash to indicate that a WINK was received. The LED will flash red according to the following sequence:
• 3 fast flashes
• OFF for 1 second
This sequence is repeated 10 times.
If the Node is Offline
If node is brought offline it will not accept any NVI (Network Variable Inputs) settings or update NVOs (Network Variable Outputs). The adapter uses the setting in Parameter 8 - [Idle Flt Action] and issues a command to the drive. NCI (Network Configuration Input) variable updates will be accepted but not forwarded to the drive until the node goes online and/or is reset.
If the Node is Online
The node accepts NCI and NVI settings and updates NVOs.
Node Operations
Configuring the LonWorks Network 4-5
This section provides descriptions of the Network Variable Inputs.
Variable: nviObjRequest
Format: SNVT_obj_request
Explanation:
This input enables control commands and updates from the network to specific objects in the node. The identification number for the node is 0 and for the drive object is 1. The request functionality is the same for both objects. The setting of nviObjRequest does not affect the ability of setting drive speed. The status of the node is reported in nvoObjStatus.
Valid range for object id:
0 and 1.
Valid range for request:
RQ_UPDATE_STATUS updates nvoObjStatus.
RQ_CLEAR_STATUS clears nvoObjStatus.
RQ_CLEAR_ALARM clears a fault in the drive.
RQ_REPORT_MASK reports supported requests in nvoObjStatus.
RQ_NORMAL and RQ_ENABLE are the normal requests when node function is normal.
All other requests are not supported, and any attempt to use them sets the invalid_request bit in nvoObjStatus.
Network Variable Inputs (NVIs)
Node Object Request
4-6 Configuring the LonWorks Network
Variable: nviDrvSpeedStpt
Format: SNVT_switch
Explanation:
This network variable input provides a speed reference setpoint. When nviDrvSpeedStpt.state is set to zero, the drive is stopped.
Valid range:
Default value:
Default value is AUTO (state = 0xFF). This value is adapted at power up. This network variable input uses Parameter 7 - [RcvHrtBeat Time] if this function is set up for use. The actual drive speed also depends on nviDrvSpeedScale.
Variable: nviDrvSpeedScale
Format: SNVT_lev_percent
Explanation:
This network variable input provides scaling for nviDrvSpdStpt. For example, if nviDrvSpeedStpt value is 100% and nviDrvSpeedScale value is -150%, then actual speed setpoint value is -150% (reverse direction at 1.5 times nominal speed).
Valid range:
-163.84 to +163.83%.
Default value:
Defined by nciDrvSpeedScale.
Drive Speed Setpoint
State Value Requested Speed0 n/a STOPPED1 0% 0%1 0.5 to 100.0% 0.5 to 100.0%1 100.0% 100.0%0xFF n/a AUTO (Default)
Speed Setpoint Scaling
Configuring the LonWorks Network 4-7
Variable: nviNV_config
Format: UNVT_DPI_CONFIG
Explanation:
This network variable input provides information on how parameters should be mapped to network variables. The NVI contains two fields:
• NV_index
• DPI_parameter
To check an already existing configuration, use the following procedures:
• To check which DPI parameter a network variable is connected to, use nviNV_config with the following data:
UNVT_DPI_CONF.NV_index = NV_index to checkUNVT_DPI_CONF.DPI_parameter = 65535 (decimal)
• To check which network variable a DPI parameter is connected to, use nviNV_config with the following data:
UNVT_DPI_CONF.NV_index = 255 (decimal)UNVT_DPI_CONF.DPI_parameter = DPI parameter to check
The result of the requests above are placed in nvoFB_config. If there is no configuration available, 0 (zero) is returned.
Valid range:
NV_index out: 14-20.
Module Configuration
LON SNVT NV_IndexDefault PowerFlex 70/700 Drive Parameter
nvoDrvSpeed 14 1nvoDrvCurnt 15 3nvoDrvPwr 17 7nvoDrvVolt 18 6nvoDrvRunHours 19 10nvoDrvFreqAct 20 1
4-8 Configuring the LonWorks Network
NV_index in: 31-36.
Default value:
This configuration is the default for PowerFlex 70/700 drives. For other future drives, the defaults are 0 and need to be configured prior to network commissioning. A value of 0 means the variable is disabled and cannot be used to send/receive data.
Note: It is necessary to configure nciNmlFreq and nciMaxSpeed to operate the drive from the network.
Variable: nviDatalinkA1nviDatalinkA2nviDatalinkB1nviDatalinkB2nviDatalinkC1nviDatalinkC2nviDatalinkD1nviDatalinkD2
Format: UNVT_DATALINK
Explanation:
These network variable inputs are used for generic parameter writes via Datalink Ins. To set up a Datalink, configure the adapter according to the drive manual. All data is sent in raw format; i.e., no scaling is performed.
Example:
If PowerFlex 70/700 Parameter 300 - [Data In A1] is set to “101,” it is pointing to Parameter 101 - [Preset Speed 1]. Any value written to nviDatalinkA1 will update Parameter 101 - [Preset Speed 1] with the value. A value of “100” equates to 10.0 Hz (note no scaling is performed).
LON SNVT NV_IndexDefault PowerFlex 70/700 Drive Parameter
nciNmlSpeed 31 44nciMinSpeed 32 81nciMaxSpeed 33 55nciRampUpTm 34 140nciRampDownTime 35 142nciNmlFreq 36 43
Datalink Ins
Configuring the LonWorks Network 4-9
This section describes the network variable outputs. No output values are sent over the network, unless they have changed (except nvoDrvSpeed, which is sent for the heartbeat functionality, and nvoObjStatus, if update status is requested).
Variable: nvoObjStatus
Format: SNVT_obj_status
Explanation:
This network variable output reports node object status and is updated every time its status changes (see page 4-5, Node Object Request).
Valid range:
Variable: nvoDrvStatus
Format: SNVT_state
Explanation:
This network variable output provides the status of the drive via the Logic Status word (see Appendix C, Logic Status Word).
Network Variable Outputs (NVOs)
Node Object Status
Invalid_ID The node has been asked for an invalid object ID.Invalid_IDrequest The node has been asked for an unsupported request.Report_mask Report supported fields.Comm_failure No contact with DPI.In_alarm The drive is faulted.Manual_control The drive is not controlled from the LonWorks peripheral.
Drive Status
4-10 Configuring the LonWorks Network
Variable: nvoDrvCurnt
Format: SNVT_amp
Explanation:
This network variable output provides the drive output current in amps.
Default PowerFlex 70/700 drive parameter mapping:
Parameter 3 - [Output Current].
Can be mapped using the nviNV_config variable.
Variable: nvoDrvSpeed
Format: SNVT_level_percent
Explanation:
This network variable output provides the speed of the drive as a percentage of the nominal speed. This network variable output is also used as a heartbeat to monitor the health of the LonWorks communication interface.
Default PowerFlex 70/700 drive parameter mapping:
Parameter 1 - [Output Freq].
Can be mapped using the nviNV_config variable.
Variable: nvoDrvPwr
Format: SNVT_power_kilo
Explanation:
This network variable output provides the drive power in kilowatts.
Default PowerFlex 70/700 drive parameter mapping:
Parameter 7 - [Output Power].
Can be mapped using the nviNV_config variable.
Drive Current
Drive Speed
Drive Power
Configuring the LonWorks Network 4-11
Variable: nvoDrvVolt
Format: SNVT_volt
Explanation:
This network variable output provides the drive voltage in volts.
Default PowerFlex 70/700 drive parameter mapping:
Parameter 6 - [Output Voltage].
Can be mapped using the nviNV_config variable.
Variable: nvoFreqAct
Format: SNVT_freq_hz
Explanation:
This network variable output provides the drive output frequency in Hz. This value is always positive (does not indicate the forward/reverse direction of revolution).
Default PowerFlex 70/700 drive parameter mapping:
Parameter 1 - [Output Freq].
Can be mapped using the nviNV_config variable or Parameter 28 - [DrvFreqActParam].
Variable: nvoDrvRunHours
Format: SNVT_time_hour
Explanation:
This network variable output provides the drive total running time in whole hours.
Default PowerFlex 70/700 drive parameter mapping:
Parameter 10 - [Elapsed Run Time].
Can be mapped using the nviNV_config variable or Parameter 27 - [DrvRunHoursParam].
Drive Voltage
Output Frequency
Operation Hour Counter
4-12 Configuring the LonWorks Network
Variable: nvoFB_config
Format: SNVT_count
Explanation:
This network variable output is used to verify that the configuration of the adapter is OK. When changing the configuration with the nviNV_config variable, nvoFB_config responds with the NV_index that was updated.
Variable: nvoDatalinkA1nvoDatalinkA2nvoDatalinkB1nvoDatalinkB2nvoDatalinkC1nvoDatalinkC2nvoDatalinkD1nvoDatalinkD2
Format: UNVT_DATALINK
Explanation:
These network variable outputs are used for generic parameter inputs via Datalink Outs. To set up a Datalink, configure the adapter according to the drive manual. All data is sent in raw format; i.e., no scaling is performed.
Example:
If PowerFlex 70/700 Parameter 310 - [Data Out A1] is set to “16,” it is pointing to Parameter 16 - [Analog In 1 Value]. The value in Parameter 16 - [Analog In 1 Value] will be read in nvoDatalinkA1. A value of “1000” equates to 1.000 mA or volt (note no scaling is performed).
Variable: nvoGenData
Format: SNVT_DATALINK
Explanation:
This network variable output provides data from the parameter number defined by nciParRdAdr. No scaling is performed and all data is presented in raw format.
Configuration Feedback
Datalink Outs
Generic Parameter Data
Configuring the LonWorks Network 4-13
The values of the NCIs change when written to and keep their values after a power cycle.
All NCIs, with a corresponding parameter in the drive, are read from the drive after reset and when going from offline to online. When the parameter is updated from the network, it is written to the drive.
NCI: nciSndHrtBt
Format: SNVT_time_sec
Explanation:
This network configuration input specifies the maximum send time for the variable nvoDrvSpeed.
Valid range:
The valid range is any value between 0.0 and 6,553.4 seconds.
Default value:
0.0 seconds (disabled)
NCI: nciRcvHrtBt
Format: SNVT_time_sec
Explanation:
This network configuration input specifies the maximum time that is allowed to elapse between updates of the network variable input nviDrvSpeedStpt. nciRcvHrtBt = 0 disables the Receive Heartbeat function. If a timeout occurs, the adapter will implement a fault action in Parameter 6 - [Comm Flt Action].
Valid range:
The valid range is any value between 0.0 and 6,553.4 seconds.
Default value:
120.0 seconds
Network Configuration Inputs (NCIs)
Send Heartbeat
Receive Heartbeat
4-14 Configuring the LonWorks Network
NCI: nciMinOutTm
Format: SNVT_time_sec
Explanation:
This network configuration input specifies the minimum period of time that expires before the network variable outputs can be re-sent. All variables are updated if they changed at each period end. This is good for limiting use of bandwidth on the LonWorks network. Setting nciMinOutTm = 0 disables transmission limiting.
Valid range:
The valid range is any value between 0.0 and 6,553.4 seconds.
Default value:
0.0 seconds (disabled)
NCI: nciNmlSpeed
Format: SNVT_rpm
Explanation:
This network configuration input sets the nominal speed of the motor in RPMs.
Default value:
1740 RPM
Default PowerFlex 70/700 drive parameter mapping:
Parameter 44 - [Motor NP RPM].
Can be adjusted using the nviNV_config variable or Parameter 30 - [NmlSpeedParam].
Minimum Send Time
Motor Nominal Speed
Configuring the LonWorks Network 4-15
NCI: nciNmlFreq
Format: SNVT_freq_hz
Explanation:
This network configuration input sets the nominal frequency of the motor.
Default value:
60 Hz.
Default PowerFlex 70/700 drive parameter mapping:
Parameter 43 - [Motor NP Hertz].
Can be adjusted using the nviNV_config variable or Parameter 29 - [NmlFreqParam].
NCI: nciMinSpeed
Format: SNVT_lev_percent
Explanation:
This network configuration input specifies the minimum speed of the motor. Its value is entered as a percentage of nominal frequency as defined by the Nominal frequency (nciNmlFreq) configuration value.
For example, if nciNmlFreq = 50 Hz. and nciMinSpeed = 10%, the minimum speed is 5 Hz.
Valid range:
The value of the minimum speed must be validated as follows:
-163.84% ≤ minimum speed ≤ maximum speed ≤ 163.83%
Default value:
0.0 Hz.
Default PowerFlex 70/700 drive parameter mapping:
Parameter 81 - [Minimum Speed].
Can be adjusted using the nviNV_config variable or Parameter 32 - [MinSpeedParam].
Nominal Frequency
Minimal Speed
4-16 Configuring the LonWorks Network
NCI: nciMaxSpeed
Format: SNVT_lev_percent
Explanation:
This network configuration input specifies the maximum speed of the motor. Its value is entered as a percentage of nominal frequency as defined by the Nominal Frequency (nciNmlFreq) configuration value.
For example, if nciNmlFreq = 50 Hz. and nciMaxSpeed = 125%, the maximum speed is 62.5 Hz.
Valid range:
The value of the maximum speed must be validated against the value of the minimum speed as follows:
-163.84% ≤ minimum speed ≤ maximum speed ≤ 163.83%
Default value:
130.0 Hz.
Default PowerFlex 70/700 drive parameter mapping:
Parameter 55 - [Maximum Freq].
Can be adjusted using the nviNV_config variable or Parameter 31 - [MaxSpeedParam].
NCI: nciRampUpTm
Format: SNVT_time_sec
Explanation:
This network configuration input sets the acceleration time. The value specifies the length of time it will take to bring the inverter from stop to maximum frequency.
Default value:
10.0 sec
Default PowerFlex 70/700 drive parameter mapping:
Parameter 140 - [Accel Time].
Can be adjusted using the nviNV_config variable or Parameter 33 - [RampUpTmParam].
Maximum Speed
Ramp Up Time
Configuring the LonWorks Network 4-17
NCI: nciRampDownTm
Format: SNVT_time_sec
Explanation:
This network configuration input sets the deceleration time. The value specifies the length of time it will take to bring the inverter to a stop when running at maximum frequency.
Default value:
10.0 sec
Default PowerFlex 70/700 drive parameter mapping:
Parameter 142 - [Decel Time].
Can be adjusted using the nviNV_config variable or Parameter 34 - [RampDownTmParam].
NCI: nciDrvSpeedScale
Format: SNVT_lev_percent
Explanation:
This network configuration input sets a default value to nviDrvSpeedScale on every startup.
Default value:
0%
Valid range:
±163%
NCI: nciParRdAdr
Format: SNVT_count
Explanation:
This network configuration input is used to read any parameter in the drive. The data is read via the nvoGenData output.
Ramp Down Time
Speed Setpoint Scaling Default Value
Generic Parameter Read Address
4-18 Configuring the LonWorks Network
Default value:
0 (Not used)
Valid range:
Any valid drive parameter.
NCI: nciParWriAdr
Format: SNVT_count
Explanation:
This network configuration input is used to set the parameter number to which a write operation should be performed. The actual data value is collected from nciParWriData. The write operation is triggered only when nciParWriData is updated. The write operation is not triggered if nciParWriAdr is updated.
Important: Writing to a parameter via this method causes a Non-Volatile Storage (NVS) update (EEPROM write cycle). Do not write parameter data via this method frequently. Datalinks do not write to NVS and should be used for frequently changed parameters.
Default value:
0 (Not used)
Valid range:
Any valid drive parameter.
NCI: nciParWriData
Format: UNVT_DATALINK
Explanation:
This network configuration input is the raw data value that will be written to the drive parameter set in nciParWriAdr. The adapter will not scale the value.
Default value:
0
Valid range:
—
Generic Parameter Write Address
Generic Parameter Write Data
Configuring the LonWorks Network 4-19
This section will describe what conditions are required for performing some common actions and how the combination of SNVTs and SCPTs affects the operation of the drive.
Starting the Drive
The drive will RUN if nviDrvSpeedStpt.state is TRUE.
Stopping the Drive
The drive stops using the default stop mode if NviSpeedStpt.state is set to zero or if the node is brought offline or disabled, depending on the setting of adapter Parameter 8 - [Idle Flt Action].
Adjusting the Frequency Setting
Actual value written to drive =
nciNmlFreq * (nviDrvSpeedStpt / 100) * (nviDrvSpeedScale / 100)
Explanation:
Nominal frequency is the base for scale and setpoint percent values. See the Network Variable Inputs (NVIs) section for information about nviSpeedStpt and nviSpeedScale.
Resetting Faults
If an error occurs, the drive faults. After removing the cause of the fault and setting nviObjRequest to RQ_CLEAR_ALARM, the drive can be reset.
Conditions Required for Operation
nviSpeedScale
nviSpeedStpt.value
nviSpeedStpt.state Resulting Speed
0% 0% 1 0 Hz (RUN)100% 0% 1 0 Hz (RUN)0% 100% 1 0 Hz (RUN)150% 100% 0 (Normal) Stop150% 100% 1 1.5 * 1.0 * nciNmlFreq (RUN)-75% 100% 1 -0.75 * 1.00 * nciNmlFreq (RUN)150% 50% 1 1.5 * 0.50 * nciNmlFreq (RUN)
4-20 Configuring the LonWorks Network
nciMinOutTm vs. nciSendHrtBt
The nciMinOutTm has priority over nciSendHrtBt. This means that heartbeats will not be sent as often as specified in nciSendHrtBt if nciMinOutTm has a longer time set.
Error Handling
If nciRcvHrtBt is larger than zero, and heartbeats are not received within the nciRcvHrtBt time, then communication with the LonWorks network is considered down. The adapter response to loss of communication depends on the setting of Parameter 6 - [Comm Flt Action].
Refer to Chapter 5, Troubleshooting for more information on potential problems with the adapter and network.
LonMark resource files define the components of the external interface for a LonWorks device. These files allow installation tools and operator interface applications to interpret data produced by a device and to correctly format data sent to a device. They also help a system integrator or system operator to understand how to use a device and to control the LonMark objects on a device.
The LonWorks module uses three types of resource files:
• Type File (.TYP) - Defines network variable, configuration property, and enumerated types. LonMark standard network variable and configuration property types are defined in the STANDARD.TYP file. Type files have a .TYP extension.
• Functional Profile Template (.FPT) - Defines functional profiles that are used for describing LonMark objects. A functional profile specifies the mandatory and optional network variable and configuration property components of a LonMark object. LonMark standard functional profiles are defined in the STANDARD.FPT file. Functional profile templates have a .FPT extension.
• Format File (.FMT) - Defines display and input formats for network variable and configuration property types defined in a type file. Formats for the LonMark standard network variable and configuration property types are defined in the STANDARD.FMT file. Format files have a .FMT extension.
Resource Files
Configuring the LonWorks Network 4-21
In addition to the resource files, the following file types are also used:
• Language File - Defines language-dependent strings. There is a separate language file for each supported language. The supported language file determines the extension of a language file. Two language files are currently available for the LonMark standard type files; these are STANDARD.ENU for American English and STANDARD.ENG for British English.
• XIF File - Defines the external interface for a LonWorks device. This file contains self-documentation information, number of address table entries, number of message tags, and the number, types, and directions of network variables.
The resource files and XIF file are shipped with the LonWorks module on a floppy disk.
4-22 Configuring the LonWorks Network
Notes:
Chapter 5
Troubleshooting
Chapter 5 provides information for troubleshooting potential problems with the adapter and network.
The LonWorks adapter has three status indicators. They can be viewed on the adapter or through the drive cover.
Figure 5.1 Status Indicators (location on drive may vary)
Topic Page Topic PageLocating the Status Indicators 5-1 Viewing and Clearing Adapter
Diagnostic Items5-5
PORT Status Indicator 5-2MOD Status Indicator 5-3 Viewing and Clearing Events 5-8NET A Status Indicator (Service Indicator)
5-4
Locating the Status Indicators
# Status Indicator
Description Page
� PORT DPI Connection Status 5-2� MOD Adapter Status 5-3� NET A LonWorks Communication Status 5-4� NET B Not used for LonWorks N/A
PWR
STS
PORT
MOD
NET A
NET B
��
�
��
��
5-2 Troubleshooting
The PORT status indicator is the top LED on the drive. See Figure 5.1.
PORT Status Indicator
State Cause Corrective ActionsOff The adapter is not powered or
is not connected properly to the drive.
• Securely connect the adapter to the drive using the ribbon cable.
• Apply power to the drive.Flashing Red
The adapter is not receiving a ping message from the drive.
• Verify that cables are securely connected.
• Cycle power to the drive.Solid Red
The drive has refused an I/O connection from the adapter.Another DPI peripheral is using the same DPI port as the adapter.
Important: Cycle power to the product after making any of the following corrections.• Verify that all DPI cables on the drive
are securely connected and not damaged. Replace cables if necessary.
• Verify that the drive supports Datalinks.• Configure the adapter and drive to use
a Datalink that is not already being used by another peripheral.
Orange The adapter is connected to a product that is not supported by the firmware of the adapter.
• Connect the adapter to a product that is supported by the firmware of the adapter (PowerFlex 70 or 700 Standard drive).
Flashing Green
The adapter is establishing an I/O connection to the drive or I/O has been disabled.
• Verify the settings of Parameter 9 - [DPI I/O Cfg].
• Normal behavior if all I/O is disabled in Parameter 9 - [DPI I/O Cfg].
Solid Green
The adapter is properly connected and is communicating with the drive.
No action.
Troubleshooting 5-3
The MOD status indicator is the second LED from the top on the drive. See Figure 5.1.
MOD Status Indicator
State Cause Corrective ActionsOff The adapter is not powered. • Securely connect the adapter to the
drive using the ribbon cable.• Apply power to the drive.
Flashing Red: 2 Hz.
MinSendTime on the sending node is less than SendHeartBeatTime on that node.
Adjust the values of MinSendTime and SendHeartBeatTime to match each other.
3 Red Flashes...then Constant Red
The software has detected a RAM checksum error.
Cycle power to the drive.
6 Red Flashes...then Constant Red
The software has detected a Flash checksum error.
Reflash the adapter.
Flashing Red: 8 Hz.
The adapter CPU cannot communicate with the Neuron Chip.
Cycle power to the drive.
Solid Red
The adapter has failed the hardware test.
• Cycle power to the drive.• Replace the adapter.
Flashing Green
The adapter is operational, but is not transferring I/O data.
• Program the controller to recognize and transmit I/O to the adapter.
• Normal behavior if all I/O has been disabled in Parameter 9 - [DPI I/O Cfg].
Solid Green
The adapter is operational and transferring I/O data.
No action.
5-4 Troubleshooting
The NET A status indicator is the third LED from the top on the drive (see Figure 5.1) and is controlled by the Neuron Chip.
NET A Status Indicator (Service Indicator)
State Cause Corrective ActionsOff The node is configured. No action.Flashing Red
WINK command received. No action.
Flashing Green
The node is not configured. Configure the node.
Solid Green The node has no application program.
The Neuron Chip must be loaded with a new application program.
Troubleshooting 5-5
Adapter Diagnostic Items are viewable with DriveExplorer software (version 2.01 or higher), DriveExecutive software (version 1.01 or higher), or a HIM (version 2.001 or higher).
Viewing and Clearing Adapter Diagnostic Items
Step Keys Example ScreenViewing Diagnostic Items1. Access parameters in the adapter.
Refer to Using the PowerFlex HIM in Chapter 3.
2. Press the Up Arrow or Down Arrow to scroll to Diagnostics.
3. Press Enter to display the Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the Device Items option.
5. Press the Up Arrow or Down Arrow to scroll through the items.
Clearing Diagnostic Items1. Access parameters in the Adapter.
Refer to Using the PowerFlex HIM in Chapter 3.
2. Press the Up Arrow or Down Arrow to scroll to Parameter.
3. Press Enter to display the list of parameters in the adapter.
4. Repeat steps 2 and 3 to select Parameter 22 - [Clear Counters].
5. Set the value to 1 = Clear and then press Enter to clear the following diagnostic items: 26 and 27.
OR
OR
OR
Main Menu:DiagnosticsParameterDevice Select
Device Item # 6Feedback
1000
Parameter #: 22Clear Counters
1Clear
Main Menu:DiagnosticsParameterDevice Select
5-6 Troubleshooting
List of Diagnostic Items
If you encounter unexpected communications problems, diagnostic items can help you or Rockwell Automation personnel troubleshoot the problem.
# Name Description1 Common Logic
CmdCurrent value of the Common Logic Command being transmitted to the host by this peripheral.
2 Prod Logic Cmd Current value of the product-specific Logic Command being transmitted to the host by this peripheral.
3 Reference Current value of the product-specific Reference being transmitted to the host by this peripheral. Note that a 16-bit value will be sent as the most significant word of the 32-bit reference filed with the least significant word set to a value of zero.
4 Common Logic Sts Current value of the Common Logic Status being received from the host by this peripheral.
5 Prod Logic Sts Current value of the product-specific Logic Status being received from the host by this peripheral.
6 Feedback Current value of the product-specific Feedback being received from the host by this peripheral. Note that a 16-bit value will be sent as the most significant word of the 32-bit reference filed with the least significant word set to a value of zero.
7891011121314
Datalink A1 InDatalink A2 InDatalink B1 InDatalink B2 InDatalink C1 InDatalink C2 InDatalink D1 InDatalink D2 In
Current value of the specified Datalink In being transmitted to the host by the adapter. If the adapter has not enabled by the Datalink, the value is zero. Refer to Chapter 4, Configuring the LonWorks Network for information about Datalinks.
1516171819202122
Datalink A1 OutDatalink A2 OutDatalink B1 OutDatalink B2 OutDatalink C1 OutDatalink C2 OutDatalink D1 OutDatalink D2 Out
Current value of the specified Datalink Out being received from the host by the adapter. Refer to Chapter 4, Configuring the LonWorks Network for information about Datalinks.
23 Field Flash Cntr Current value of the Field Flash Counter (the number of times this device has been flash updated).
24 DPI Tx Err Cntr Current value of the DPI CAN Transmit Error Counter.25 DPI Rx Err Cntr Current value of the DPI CAN Receive Error Counter.26 LON Tx Err CRC errors detected during packet reception.27 LON Lost Msg Number of incoming packets that have been discarded due to
no available application buffers.
Troubleshooting 5-7
28 Last Reset Cause 0 = Power Up1 = External2 = Watchdog3 = Software4 = Cleared
29 Neuron State The state of the Neuron Chip:0 = appl_uncnfg1 = cnfg_online2 = unknown3 = cnfg_offline4 = soft_online
30 Neuron Chip ID The Neuron Chip ID number as an enumerated value.31 nviDrvSpdSp.val Last nviDrvSpdStpt.Value reported to adapter from the network.32 nviDrvSpdSp.st Last nviDrvSpdStpt.State reported to adapter from the network.33 nviDrvSpdSp.scale Last nviDrvSpdStpt.Scale reported to adapter from the network.34 nvoDrvSpeed Current Drive Speed propagated to the network nvoDrvSpeed
variable.
# Name Description
5-8 Troubleshooting
The adapter maintains an event queue that reports the history of its actions. You can view this using an LCD PowerFlex HIM, DriveExplorer software (2.01 or higher), or DriveExecutive software (1.01 or higher).
Viewing and Clearing Events
Step Keys Example ScreenViewing Events1. Access parameters in the adapter.
Refer to in Using the PowerFlex HIM Chapter 3.
2. Press the Up Arrow or Down Arrow to scroll to Diagnostics.
3. Press Enter to display the Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the Events option and then View Event Queue option.
5. Press the Up Arrow or Down Arrow to scroll through the events. The most recent event is Event 1.
Clearing Events1. Access parameters in the Adapter.
Refer to in Using the PowerFlex HIM Chapter 3.
2. Press the Up Arrow or Down Arrow to scroll to Diagnostics.
3. Press Enter to display the Diagnostics menu in the adapter.
4. Repeat steps 2 and 3 to enter the Events option and then the Clr Event option or Clear Event Queue option. A message will pop up to confirm that you want to clear the message or queue.
5. Press Enter to clear all events out of the event queue. All event queue entries will then display “No Event.”
OR
OR
OR
Main Menu:DiagnosticsParameterDevice Select
Event Q: 1 E3Ping Time Flt
Dgn: EventsView Event QueueClear EventClear Event Queue
Troubleshooting 5-9
Events
Many events in the Event queue occur under normal operation. If you encounter unexpected communications problems, the events can help you or Rockwell Automation personnel troubleshoot the problem. The following events may appear in the event queue:
Code Event Description1 No Event Empty event queue entry.2 DPI Bus Off Flt A bus off condition was detected on DPI. This event
may be caused by loose or broken cables or by noise.3 Ping Time Flt A ping message was not received on DPI within the
specified time.4 Port ID Flt The debounced DPI PIN ID was read as 0 or 7 after the
peripheral had completed start up.5 Port Change Flt The debounced DPI PIN ID has changed after the
peripheral had completed start up.6 Host Sent Reset The drive issued a reset event.7 EEPROM Sum Flt Start-up sequence detected corrupt EEPROM storage.8 Online @ 125 kbps The peripheral detects that the host is at 125 kbps.9 Online @ 500 kbps The peripheral detects that the host is at 500 kbps.10 Bad Host Flt The adapter was connected to an incompatible
product.11 Dup Port Flt Another peripheral with the same port number is
already in use.12 Type 0 Login The peripheral has logged in for Type 0 control.13 Type 0 Time Flt The peripheral has not received a Type 0 status message
within the specified time.14 DL Login The peripheral has logged into a Datalink.15 DL Reject Flt The host rejected an attempt to log in to a Datalink.16 DL Time Flt The adapter has not received a Datalink message
within the specified time.17 Control Disabled The peripheral has sent a “Soft Control Disable”
command to the DPI product.18 Control Enabled The peripheral has sent a “Soft Control Enable”
command to the host.19 Normal Startup The peripheral successfully started up.20 Message Timeout A client-server message sent by the peripheral was not
completed within 1 second.21 DPI Fault Msg The DPI Host has faulted.22 DPI Fault Clear The user cleared a fault in the adapter.23 Net Comm Flt The peripheral detected a communication fault on the
network. (Received heartbeat timeout.)24 Fault Cfg Error The peripheral detected a 32-bit fault configuration
reference when the host supports only a 16-bit reference; or detected a 32-bit fault configuration Datalink value when the host supports only 16-bit Datalinks.
25 LON Online The peripheral is on-line the LonWorks network.26 LON Offline The peripheral is off-line the LonWorks network.
5-10 Troubleshooting
27 LON Reset The peripheral has detected a reset of the Neuron Chip.28 LON Enabled The Node is enabled by RQ_ENABLE.29 LON Disabled The Node is disabled by RQ_DISABLE.30 Language CRC Bad The segment of flash holding the text translations has a
bad CRC.
Code Event Description
Appendix A
Specifications
Appendix A presents the specifications for the adapter.
Topic Page Topic PageCommunications A-1 Environmental A-2Electrical A-1 Regulatory Compliance A-2Mechanical A-1
Communications
Network ProtocolData Rates
LonWorks78 kbps
Electrical
Consumption 200 mA on DPI
Mechanical
DimensionsHeightLengthWidth
20 mm (0.79 in.)86 mm (3.33 in.)78.5 mm (3.09 in.)
Weight 85 g (3 oz.)
A-2 Specifications
Environmental
TemperatureOperatingStorage
-15 to 70° C (5 to 158° F)-40 to 85° C (-40 to 185° F)
Relative Humidity 5 to 95% non-condensing
Atmosphere Important: The adapter must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the adapter is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Regulatory Compliance
Certification SpecificationUL UL508C and cULCE EN50081-2 (1993) and EN61000-6-2
(1999)
Appendix B
Adapter Parameters
Appendix B presents information about the adapter parameters.
Topic PageParameter List B-1
Parameter List
Parameter No. Name and Description Details01 [DPI Port]
Displays the port to which the adapter is connected. This will usually be port 5.
Default: 0Minimum: 0Maximum: 7Type: Read Only
02 [DPI Data Rate]Displays the data rate used by the drive. This data rate is set in the drive, and the adapter detects it.
Default: 0 = 125 kbpsValues: 0 = 125 kbps
1 = 500 kbpsType: Read Only
03 [Ref / Fdbk Size]Displays the size of the reference and feedback. The drive determines the size of the reference and feedback.
Default: 0 = 16-bitValues: 0 = 16-bit
1 = 32-bitType: Read Only
04 [Datalink Size]Displays the size of each Datalink. The drive determines the size of Datalinks.
Default: 0 = 16-bitValues: 0 = 16-bit
1 = 32-bitType: Read Only
05 [Reset Module]No action if set to “Ready.” Resets the adapter if set to “Reset Module.” Restores the adapter to its factory default settings if set to “Set Defaults.” This parameter is a command. It will be reset to “0 = Ready” after the command has been performed.
Default: 0 = ReadyValues 0 = Ready
1 = Reset Module2 = Set Defaults
Type: Read/WriteReset Required: No
!ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting I/O that controls the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting a connected adapter.
B-2 Adapter Parameters
06 [Comm Flt Action]Sets the action that the adapter will take if it detects that network communications have been disrupted (if Parameter 7 - [RcvHrtBeat Time] times out before nviDrvSpeedStpt is updated from the network).
Default: 0 = FaultValues: 0 = Fault
1 = Stop2 = Zero Data3 = Hold Last4 = Send Flt Cfg
Type: Read/WriteReset Required: No
07 [RcvHrtBeat Time]Sets the time used as a Receive Heartbeat timer and triggers the fault action in Parameter 6 - [Comm Flt Action].
Default: 120.0Minimum: 0.0 secondsMaximum: 3276.7 secondsType: Read/WriteReset Required: No
08 [Idle Flt Action]Sets the action that the adapter will take during offline/disable occurrences.
Default: 0 = FaultValues: 0 = Fault
1 = Stop2 = Zero Data3 = Hold Last4 = Send Flt Cfg
Type: Read/WriteReset Required: No
Parameter No. Name and Description Details
!ATTENTION: Risk of injury or equipment damage exists. Parameter 6 - [Comm Flt Action] and Parameter 7 - [RcvHrtBeat Time] let you determine the action of the adapter and connected drive if communications are disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Take precautions to ensure that the setting of these parameters does not create a hazard of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
!ATTENTION: Risk of injury or equipment damage exists. Parameter 6 - [Comm Flt Action] and Parameter 7 - [RcvHrtBeat Time] let you determine the action of the adapter and connected drive if communications are disrupted. Take precautions to ensure that the setting of these parameters does not create a hazard of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
Adapter Parameters B-3
09 [DPI I/O Config]Configures the I/O to be transferred through the adapter.
Default: xxx0 0001Bit Values: 0 = I/O disabled
1 = I/O enabledType: Read/WriteReset Required: N/A
The Cmd/Ref bit must be set in order to control the drive via the network. The respective Datalink bit(s) must be set if the nvi/nvo Datalink variables are used.
Bit Definitions0 = Cmd/Ref1 = Datalink A2 = Datalink B3 = Datalink C4 = Datalink D5 = Not Used6 = Not Used7 = Not Used
10 [DPI I/O Active]Displays I/O that the adapter is actively transmitting. The value of this parameter will usually be equal to the value of Parameter 9 - [DPI I/O Config].
Default: xxx0 0001Bit Values: 0 = I/O disabled
1 = I/O enabledType: Read Only
Bit Definitions0 = Cmd/Ref1 = Datalink A2 = Datalink B3 = Datalink C4 = Datalink D5 = Not Used6 = Not Used7 = Not Used
11 [Flt Cfg Logic]Sets the Logic Command data that is sent to the drive if Parameter 6 - [Comm Flt Action] is set to Send Flt Cfg and communications are disrupted.
Refer to Appendix C, Logic Command Word for the bit definitions.
Default: 0000 0000 0000 0000Minimum: 0000 0000 0000 0000Maximum: 1111 1111 1111 1111Type: Read/WriteReset Required: No
12 [Flt Cfg Ref]Sets the Reference data that is sent to the drive if Parameter 6 - [Comm Flt Action] is set to Send Flt Cfg and communications are disrupted.
This is a linear engineering unit value where “0” equals 0 Hz. and “32,767” equals the Hz. value in the PowerFlex 70/700 Parameter 55 - [Maximum Freq].
Default: 0Minimum: 0Maximum: 4294967295Type: Read/WriteReset Required: No
Important: If the drive uses a 16-bit Reference, the most significant word of this value must be set to zero (0) or a fault will occur.
Parameter No. Name and Description Details
BitDefault 10000x xx
0123457 6
BitDefault 10000x xx
0123457 6
B-4 Adapter Parameters
1314151617181920
[Flt Cfg A1 In][Flt Cfg A2 In][Flt Cfg B1 In][Flt Cfg B2 In][Flt Cfg C1 In][Flt Cfg C2 In][Flt Cfg D1 In][Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the drive if Parameter 6 - [Comm Flt Action] is set to Send Flt Cfg and communications are disrupted.
Note that these are 32-bit values. If 16-bit Datalinks are active, only the least significant word will be used. If the 32-bit value is out of range for a 16-bit Datalink, a configuration error will force a correction before I/O can be enabled.
Default: 0Default: 0Default: 0Default: 0Default: 0Default: 0Default: 0Default: 0Minimum: 0Maximum: 4294967295Type: Read/WriteReset Required: No
Important: If the drive uses 16-bit Datalinks, the most significant word of this value must be set to zero (0) or a fault will occur.
21 [Send Service Pin]Broadcasts a LON Service Pin Message from the Neuron Chip. This provides the Neuron ID.
An alternate method for providing the Neuron ID is enter the ID number manually. The Neuron ID can be viewed in Diagnostic Item #30 (see Chapter 5, List of Diagnostic Items).
Default: 0 = ReadyValues: 0 = Ready
1 = SendType: Read/WriteReset Required No
22 [Clear Counters]Clears the network diagnostic counters (Diagnostic Items #26 and #27).
Default: 0 = ReadyValues 0 = Ready
1 = ClearType: Read/WriteReset Required: No
23 [DrvSpeedParam]Sets the PowerFlex drive parameter number to be used with nvoDrvSpeed. See Chapter 4, Network Variable Outputs (NVOs).
Setting this parameter’s value to zero disables the firmware from fetching the corresponding parameter value from the drive.
Default: 1Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
24 [DrvCurntParam]Sets the PowerFlex drive parameter number to be used with nvoDrvCurnt. See Chapter 4, Network Variable Outputs (NVOs).
Setting this parameter’s value to zero disables the firmware from fetching the corresponding parameter value from the drive.
Default: 3Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
Parameter No. Name and Description Details
Adapter Parameters B-5
25 [DrvPwrParam]Sets the PowerFlex drive parameter number to be used with nvoDrvPwr. See Chapter 4, Network Variable Outputs (NVOs).
Setting this parameter’s value to zero disables the firmware from fetching the corresponding parameter value from the drive.
Default: 7Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
26 [DrvVoltParam]Sets the PowerFlex drive parameter number to be used with nvoDrvVolt. See Chapter 4, Network Variable Outputs (NVOs).
Setting this parameter’s value to zero disables the firmware from fetching the corresponding parameter value from the drive.
Default: 6Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
27 [DrvRunHoursParam]Sets the PowerFlex drive parameter number to be used with nvoDrvRunHours. See Chapter 4, Network Variable Outputs (NVOs).
Setting this parameter’s value to zero disables the firmware from fetching the corresponding parameter value from the drive.
Default: 10Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
28 [DrvFrqActParam]Sets the PowerFlex drive parameter number to be used with nvoDrvFreqAct. See Chapter 4, Network Variable Outputs (NVOs).
Setting this parameter’s value to zero disables the firmware from fetching the corresponding parameter value from the drive.
Default: 1Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
29 [NmlFreqParam]Sets the PowerFlex drive parameter number to be used with nciNmlFreq. See Chapter 4, Network Configuration Inputs (NCIs).
Default: 43Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
30 [NmlSpeedParam]Sets the PowerFlex drive parameter number to be used with nciNmlSpeed. See Chapter 4, Network Configuration Inputs (NCIs).
Default: 44Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
31 [MaxSpeedParam]Sets the PowerFlex drive parameter number to be used with nciMaxSpeed. See Chapter 4, Network Configuration Inputs (NCIs).
Default: 55Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
Parameter No. Name and Description Details
B-6 Adapter Parameters
32 [MinSpeedParam]Sets the PowerFlex drive parameter number to be used with nciMinSpeed. See Chapter 4, Network Configuration Inputs (NCIs).
Default: 81Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
33 [RampUpTmParam]Sets the PowerFlex drive parameter number to be used with nciRampUpTm. See Chapter 4, Network Configuration Inputs (NCIs).
Default: 140Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
34 [RampDownTmParam]Sets the PowerFlex drive parameter number to be used with nciRampDownTm. See Chapter 4, Network Configuration Inputs (NCIs).
Default: 142Values: PowerFlex drive
parameter numbers
Type: Read/WriteReset Required: Yes
Parameter No. Name and Description Details
Appendix C
Logic Command/Status WordsAppendix C provides the definitions of the Logic Command/Logic Status words that are used for some products that can be connected to the LonWorks adapter. If your product is not included here, refer to its documentation.
Logic Command Word
PowerFlex 70 and PowerFlex 700 Drives
Logic Bits15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description
x Stop 0 = Not Stop1 = Stop*
x Start(1) (2) 0 = Not Start1 = Start
x Jog 0 = Not Jog1 = Jog
x Clear Faults(2)
0 = Not Clear Faults1 = Clear Faults
x x Direction 00 = No Command01 = Forward Command10 = Reverse Command11 = Hold Direction Control
x Local Control
0 = No Local Control1 = Local Control
x MOP Increment
0 = Not Increment1 = Increment
x x Accel Rate 00 = No Command01 = Accel Rate 1 Command10 = Accel Rate 2 Command11 = Hold Accel Rate
x x Decel Rate 00 = No Command01 = Decel Rate 1 Command10 = Decel Rate 2 Command11 = Hold Decel Rate
x x x Reference Select
000 = No Command001 = Ref. 1 (Ref A Select)010 = Ref. 2 (Ref B Select)011 = Ref. 3 (Preset 3)100 = Ref. 4 (Preset 4)101 = Ref. 5 (Preset 5)110 = Ref. 6 (Preset 6)111 = Ref. 7 (Preset 7)
x MOP Decrement
0 = Not Decrement1 = Decrement
(1) A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.
(2) To perform this command, the value must change from “0” to “1.”
C-2 Logic Command/Status Words
Logic Status Word
PowerFlex 70 and PowerFlex 700 Drives
Logic Bits15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status Description
x Ready 0 = Not Ready1 = Ready
x Active 0 = Not Running1 = Running
x Command Direction
0 = Reverse1 = Forward
x Actual Direction
0 = Reverse1 = Forward
x Accel 0 = Not Accelerating1 = Accelerating
x Decel 0 = Not Decelerating1 = Decelerating
x Alarm 0 = No Alarm1 = Alarm
x Fault 0 = No Fault1 = Fault
x At Speed 0 = Not At Reference1 = At Reference
x x x Local Control
000 = Port 0 (TB)001 = Port 1010 = Port 2011 = Port 3100 = Port 4101 = Port 5110 = Port 6111 = No Local
x x x x Reference 0000 = Ref A Auto0001 = Ref B Auto0010 = Preset 2 Auto0011 = Preset 3 Auto0100 = Preset 4 Auto0101 = Preset 5 Auto0110 = Preset 6 Auto0111 = Preset 7 Auto1000 = Term Blk Manual1001 = DPI 1 Manual1010 = DPI 2 Manual1011 = DPI 3 Manual1100 = DPI 4 Manual1101 = DPI 5 Manual1110 = DPI 6 Manual1111 = Jog Ref
Glossary
B BindingA process whereby a network variable input and a network variable output are connected together. Binding a network variable tells the device which other devices it should talk to and what information it should share. Only network variables of the same SNVT type can be bound together. For example, a temperature type could not be bound to a pressure type.
Bus OffA condition that occurs when an abnormal rate of errors is detected in a device. The bus off device cannot receive or transmit messages on the network. This condition is often caused by corruption of the network data signals due to noise or data rate mismatch.
C ChannelThe transmission media that connect devices on the network such as twisted pair 78 kbps or power line carrier. Also called segment.
Configuration Property
A data value used to configure the application program in a device.
D Data RateThe speed at which data is transferred on the network. Each device on a network must be set for the same data rate.
Datalink
A type of pointer used by some drives to transfer data to and from the controller. Datalinks allow specified parameter value(s) to be accessed or changed without using Explicit Messages. The drive determines the size of Datalinks.
DPIA peripheral communication interface used by various Rockwell Automation drives and power products.
DPI Peripheral
A device that provides an interface between DPI and a network or user. Peripheral devices are also referred to as “adapters” and “modules.” The PowerFlex HIM is an example of a DPI peripheral.
G-2 Glossary
DPI Product
A device that uses the DPI communications interface to communicate with one or more peripheral devices. For example, a motor drive such as a PowerFlex drive is a DPI product. In this manual, a DPI product is also referred to as “product” or “host.”
DriveExplorer SoftwareDriveExplorer software is a tool for monitoring and configuring Allen-Bradley products and adapters. It can be run on computers running Microsoft Windows 95, Windows 98, Windows ME, Windows NT (version 4.0 or higher), Windows 2000, and Windows CE (version 2.01 or higher) operating systems. DriveExplorer (version 2.01 or higher) can be used to configure this adapter and PowerFlex drives. Information about DriveExplorer software and a free lite version can be accessed at http://www.ab.com/drives/driveexplorer.
DriveTools 2000 Software
A software suite designed for Microsoft Windows 98, Windows ME and Windows NT (4.0 or higher) and Windows 2000 operating systems. This software suite will provide a family of tools that you can use to program, monitor, control, troubleshoot, and maintain Allen-Bradley products. DriveExecutive (version 1.01 or higher) can be used with PowerFlex drives. Information about DriveTools 2000 can be accessed at http://www.ab.com/drives/drivetools_2000.
E Explicit Messaging
Explicit Messages are used to configure, monitor, and diagnose devices over the network.
F Fault ActionDetermines how the adapter and connected product act when a communications fault occurs (for example, a cable is disconnected).
Fault ConfigurationWhen communications are disrupted (for example, a cable is disconnected), the adapter and drive can respond with a user-defined fault configuration. The user sets the data that is sent to the drive in the fault configuration parameters: Parameters 11 - [Flt Cfg Logic] through 20 - [Flt Cfg D2 In]. When a fault action parameter is set to use the fault configuration and a fault occurs, the data from these parameters is sent as the Command Logic, Reference, and/or Datalink(s).
Glossary G-3
Flash Update
The process of updating firmware in the adapter. The adapter can be flash updated using the X-Modem protocol or Control FLASH, and a serial converter.
H Hold Last
When communications are disrupted (for example, a cable is disconnected), the adapter and drive can respond by holding last. Hold last results in the drive receiving the last data received via the network connection before the disruption. If the drive was running and using the reference from the adapter, it will continue to run at the same reference.
Human Interface Module (HIM)A device that can be used to configure and control a drive.
I Interoperability
The ability of systems from different manufacturers and of different types to share information with each other without losing any of their independent functional capabilities and without requiring complex programming by the integrator.
I/O Data
I/O data, sometimes called “implicit messages” or “input/output,” transmit time-critical data such as a Logic Command and Reference. The terms “input” and “output” are defined from the scanner’s point of view. Output is transmitted by the scanner and consumed by the adapter. Input is transmitted by the adapter and consumed by the scanner.
L LONAn acronym for local operating network. Consists of intelligent devices, or nodes, that are connected by one or more communications media and that communicate with one another using a common protocol.
LonMaker SoftwareWindows-based software package for designing, documenting, installing, and maintaining multi-vendor, open, interoperable LonWorks networks.
LonWorks DeviceHardware and software than runs an application and communicates with other devices using the LonWorks protocol. May optionally interface with input/output hardware. Includes at least one processor and a LonWorks transceiver. Typically includes a Neuron Chip.
G-4 Glossary
LonWorks Network
Intelligent devices that communicate with each other using the LonWorks protocol over one or more communications channels.
LonWorks ProtocolThe open control networking protocol designed for applications involving sense, monitor, control, and identification functions. Also known as EIA 709.1 Control Networking Standard and as LonTalk protocol.
Logic Command/Status
The Logic Command is used to control the drive (e.g., start, stop, direction). It consists of one 16-bit word of input to the adapter from the network. The definitions of the bits in this word depend on the drive.
The Logic Status is used to monitor the drive (for example, operating state, motor direction). It consists of one 16-bit word of output from the adapter to the network. The definitions of the bits in this word depend on the drive.
N Network VariableA data item that a particular device application program expects to get from other devices on a network (a network variable input) or expects to make available to other devices on a network (a network variable output). Examples are a temperature, switch value, and actuator position setting.
Neuron Chip
A microprocessor usually contained in each LonWorks node which processes all LonTalk protocol messages, senses inputs, manipulates outputs, implements application-specific functions, and stores installation-specific parameters.
NodeAn intelligent device connected to the network. Nodes are programmed to send messages to one another in response to changes in various conditions, and to take action in response to messages they receive.
Non-Volatile Storage (NVS)The permanent memory of a device. Devices such as the adapter and drive store parameters and other information in NVS so that they are not lost when the device loses power. NVS is sometimes called “EEPROM.”
Glossary G-5
P ProtocolsRules that order how information is transmitted and presented. An “open protocol” is one in which the manufacturer has made the language “translation” available to anyone who wishes to use it.
R Reference/FeedbackThe Reference is used to send a reference (for example, speed, frequency, torque) to the product. It consists of one word of input to the adapter from the network. The size of the word (either a 16-bit word or 32-bit word) is determined by the drive.
The Feedback is used to monitor the speed of a product. It consists of one word of output from the adapter to the network. The size of the word (either a 16-bit word or 32-bit word) is determined by the drive.
S SCPT
An acronym for Standard Configuration Property Type. SCPTs are standardized definitions of the units, scaling, encoding, and meaning of the contents of configuration properties.
SNVT
An acronym for Standard Network Variable Type. SNVTs are a set of predefined types of network variables with associated units, such as degrees, centigrade, etc. SNVTs promote interoperability of products from different manufacturers by standardizing the names given to output and input network variables.
Status IndicatorsLEDs that are used to report the status of the adapter, network, and drive. They are on the adapter and can be viewed on the front cover of the drive when the drive is powered.
T TransceiverA device that is both a transmitter and a receiver for a communications channel.
Type 0/Type 1/Type 2 Control
When transmitting I/O, the adapter can use different types of messages for control. The Type 0, Type 1, and Type 2 events help Rockwell Automation personnel identify the type of messages that is used.
G-6 Glossary
Z Zero DataWhen communications are disrupted (for example, a cable is disconnected), the adapter and drive can respond with zero data. Zero data results in the drive receiving zero as values for command data. If the drive was running and using the reference from the adapter, it will stay running but at zero reference.
Index
Aadapter
applying power, 2-5compatible products, 1-2components, 1-1configuring I/O for, 3-3connecting to a drive, 2-3connecting to a network, 2-1features, 1-2grounding, 2-4installation, 2-1 to 2-5mounting on a drive, 2-4parameters, B-1 to B-6resetting, 3-6specifications, A-1viewing its configuration, 3-7
applying power to the adapter, 2-5
attentions, 1-3
Bbaud rate, see data rate
binding, definition of, G-1
bit definitions for Logic Command/Status word, C-1
bus off, definition of, G-1
Ccables
Internal Interface cables, 2-3network, 2-2required for installation, 1-3
channel, definition of, G-1
Clear Counters parameter, B-4
Comm Flt Action parameter, B-2
communications specifications, A-1
compatible products, 1-2
components of adapter, 1-1
Configuration Feedback (NVO), 4-12
configuration property, definition of, G-1
configuration tools, 3-1
configuring parameters, 3-1 to 3-8
configuring the LonWorks network, 4-1 to 4-21
connecting an adapter to a drive, 2-3
connecting an adapter to a network, 2-1
Ddata rate, definition of, G-1
Datalink Size parameter, B-1
Datalinks (NVI), 4-8
Datalinks (NVO), 4-12
Datalinks, definition of, G-1
diagnostic itemslist of, 5-6viewing and clearing, 5-5
dimensions, A-1
DPIadapter uses, 1-2definition of, G-1peripheral, G-1ports on adapter and drives, 2-3products, 1-2, G-2
DPI Data Rate parameter, B-1
DPI I/O Active parameter, B-3
DPI I/O Config parameter, B-3
DPI Port parameter, B-1
Drive Current (NVO), 4-10
Drive Power (NVO), 4-10
Drive Speed (NVO), 4-10
Drive Speed Setpoint (NVI), 4-6
Drive Status (NVO), 4-9
Drive Voltage (NVO), 4-11
drive, see DPI products
DriveExploreraccessing parameters with, 3-1definition of, G-2free lite version, G-2
DriveTools 2000accessing parameters with, 3-1definition of, G-2
DrvCurntParam parameter, B-4
DrvFrqActParam parameter, B-5
DrvPwrParam parameter, B-5
I-2 Index
DrvRunHoursParam parameter, B-5
DrvSpeedParam parameter, B-4
DrvVoltParam parameter, B-5
EEEPROM, see Non-Volatile Storage
(NVS)
electrical specifications, A-1
environmental specifications, A-2
equipment, 1-3
eventslist of, 5-9viewing and clearing, 5-8
Explicit Messaging, G-2
Ffactory-default settings, 3-6
fault actionconfiguring an adapter for, 3-5definition of, G-2
fault configurationconfiguring an adapter for, 3-5 to 3-6definition of, G-2
features of the adapter, 1-2
firmware release, P-2
flash update, G-3
Flt Cfg A1 - D2 In parameters, B-4
Flt Cfg Logic parameter, B-3
Flt Cfg Ref parameter, B-3
GGeneric Parameter Data (NVO), 4-12
grounding an adapter, 2-4
HHIM (Human Interface Module)
accessing parameters with, 3-1definition of, G-3LCD model, 3-2LED model, 3-2
hold lastconfiguring an adapter for, 3-5definition of, G-3
II/O
configuring an adapter for, 3-3definition of, G-3
Idle Flt Action parameter, B-2
installationapplying power to the adapter, 2-5connecting to the drive, 2-3connecting to the network, 2-1preparing for, 2-1
Internal Interface cablesconnecting to adapter and drive, 2-3shipped with adapter, 1-3
interoperability, definition of, G-3
LLCD HIM, 3-2
LED HIM, 3-2
Logic Command/Statusbit definitions, C-1definition of, G-4
LON, definition of, G-3
LonMaker Software, definition of, G-3
LonMark profile, operating the drive using, 4-2
LonWorks device, definition of, G-3
LonWorks networkconfiguring, 4-1 to 4-21definition of, G-4
LonWorks protocol, definition of, G-4
Mmanual
conventions, P-1related documentation, P-1
MaxSpeedParam parameter, B-5
mechanical dimensions, A-1
MinSpeedParam parameter, B-6
Index I-3
MOD status indicatorlocating, 5-1troubleshooting with, 5-3
modes of operation, 1-6
Module Configuration (NVI), 4-7
mounting an adapter on a drive, 2-4
NNCIs (Network Configuration Inputs), 4-13
NET A status indicatorlocating, 5-1troubleshooting with, 5-4
NET B status indicatorlocating, 5-1
network cableconnecting to 6-pin plug, 2-2selecting, 2-2
Network Configuration Inputs (NCIs), 4-13
Network Variable Inputs (NVIs), 4-5
Network Variable Outputs (NVOs), 4-9
network variable, definition of, G-4
Neuron Chip, definition of, G-4
NmlFreqParam parameter, B-5
NmlSpeedParam parameter, B-5
nodedefinition of, G-4operations, 4-4
Node Object Request (NVI), 4-5
Node Object Status (NVO), 4-9
Non-Volatile Storage (NVS)accessing parameters in, 3-1definition of, G-4
NVIs (Network Variable Inputs), 4-5
NVOs (Network Variable Outputs), 4-9
OOperation Hour Counter (NVO), 4-11
Output Frequency (NVO), 4-11
Pparameters
accessing, 3-1configuring, 3-1 to 3-8factory-default settings, 3-6list of, B-1 to B-6
plug for network cable, 2-2
PORT status indicatorlocating, 5-1troubleshooting with, 5-2
power consumption, A-1
PowerFlex drives70/700 Logic Command/Status, C-1compatible with adapter, 1-2
preparing for installation, 2-1
products, see DPI products
protocols, definition of, G-5
Qquick start, 1-5
RRampDownTmParam parameter, B-6
RampUpTmParam parameter, B-6
RcvHrtBeat Time parameter, 3-7, B-2
Ref/Fdbk Size parameter, B-1
reference/feedback, definition of, G-5
regulatory compliance, A-2
related documentation, P-1
required equipment, 1-3
Reset Module parameter, B-1
resetting an adapter, 3-6
Ssafety precautions, 1-3
SCPT (Standard Configuration Property Type), definition of, G-5
Send Service Pin parameter, B-4
six-pin linear plug, 2-2
SNVT (Standard Network Variable Type), definition of, G-5
specifications for adapter, A-1
I-4 Index
Speed Setpoint Scaling (NVI), 4-6
status indicatorsdefinition of, G-5MOD, 5-3NET A, 5-4normal operation, 1-6PORT, 5-2troubleshooting with, 5-1
Ttechnical support, P-2
tools, 1-3
transceiver, definition of, G-5
troubleshooting, 5-1 to 5-10
Uupdate, see flash update
Vviewing adapter configuration, 3-7
WWeb page
for DriveExplorer software, G-2for DriveTools 2000 software, G-2for manuals, P-1
Zzero data
configuring an adapter for, 3-5definition of, G-6
Allen-Bradley, ControlFLASH, DPI, DriveExplorer, DriveTools 2000, DriveExecutive, PowerFlex, and SCANport are trademarks of Rockwell Automation.
LONWORKS, LonMaker, LonTalk, Neuron, and LON are trademarks of Echelon Corporation.
Windows, Windows NT, and Microsoft are trademarks of Microsoft Corporation.
www.rockwellautomation.com
Corporate HeadquartersRockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201
Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing SolutionsAmericas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444Europe/Middle East/Africa: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640Asia Pacific: Rockwell Automation, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Headquarters for Dodge and Reliance Electric ProductsAmericas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433Europe/Middle East/Africa: Rockwell Automation, Brühlstraße 22, D-74834 Elztal-Dallau, Germany, Tel: (49) 6261 9410, Fax: (49) 6261 17741Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 6356-9077, Fax: (65) 6356-9011
U.S. Allen-Bradley Drives Technical SupportTel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives
Publication 20COMM-UM008A-EN-P – January, 2003 P/N 308875-P01Copyright © 2003 Rockwell Automation, Inc. All rights reserved. Printed in USA.