lecture on distribution system

Upload: imburais

Post on 02-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Lecture on Distribution System

    1/36

    DISTRIBUTION SYSTEM

  • 8/10/2019 Lecture on Distribution System

    2/36

    Distribution system typically starts here

  • 8/10/2019 Lecture on Distribution System

    3/36

  • 8/10/2019 Lecture on Distribution System

    4/36

    CIRCUIT BREAKERS

  • 8/10/2019 Lecture on Distribution System

    5/36

    Major Component of a Distribution Substation

    High-side and low-side switching

    In the figure high side switching is done with a simple switch

    Low-side switching is done with a relay-controlled circuit breaker.

    Reclosers can be used instead of circuit breakers.

    Transformer for voltage transformation.

    The figure has only one transformer

    Other designs make use of more than one transformers.

    Common voltages : 34.5 KV, 23.9 KV, 14.4 KV, 13.2 KV, 12.47 KV

    Voltage Regulation

    Maintains the users voltages to within acceptable levels.

    The voltage is regulated by a step-type regulator 10% plus or minuson the low-side bus

    Protection : In simple designs like in the diagram the automatic protection

    against short circuits is by way of the high-side fuse. In more complex

    designs, more extensive protection are employed.

  • 8/10/2019 Lecture on Distribution System

    6/36

  • 8/10/2019 Lecture on Distribution System

    7/36

    DISTRIBUTION FEEDER MAP

    Used to determine the existing operating conditions of a feeder and

    analysis can be performed. It contains most of the following information:

    Lines (overhead and underground)

    1.Where2.Distances

    3.Details

    a.Conductor sizes

    b.Phasing

    Distribution Transformers

    1.Location

    2.KVA rating

    3.Phase connection

    In-line transformers

    1.Location

    2.KVA rating

    3.Connection

    Shunt capacitors

    1.Location

    2.KVAR rating

    3.Phase connection

    Voltage regulators1.Location

    2.Phase connection

    3.Type

    a.Single-phase

    b.Three-phase

    Switches

    1.Location

    2.Normal open/close status

  • 8/10/2019 Lecture on Distribution System

    8/36

  • 8/10/2019 Lecture on Distribution System

    9/36

    DISTRIBUTION FEEDER ELECTRICAL CHARACTERISTICS

    The following data must be available :

    Overhead and underground spacingsConductor tables

    1.Geometric mean radius (GMR)

    2.Diameter

    3.Resistance

    Voltage regulators

    1.Potential transformer ratios2.Current transformer ratios

    3.Compensator settings

    a.Voltage level

    b.Bandwidth (range)

    c.R and X settings

    Transformers1.KVA rating

    2.Voltage ratings

    3.Impedance (R and X)

    4.No-load power loss

  • 8/10/2019 Lecture on Distribution System

    10/36

    NATURE OF LOADS

  • 8/10/2019 Lecture on Distribution System

    11/36

    NATURE OF LOADS

    The modeling and analysis of a power system depend upon the load.

    The load supplied by a distribution transformer is constantly changing.Every time a light bulb or an electrical appliance is switched on or off, the

    load seen by the distribution feeder changes

    LOAD GRAPHS

    A load graph, or load curve, is a graphic record showing the power

    demands for every instant during a certain time interval. The record may

    cover a period of

    one hour hourly load graph

    24 hours daily load graph

    one monthmonthly load graphone year yearly load graph

  • 8/10/2019 Lecture on Distribution System

    12/36

    The area under the load curve is equal to the energy in terms of

    kilowatt hours (or watt hours) delivered to the particular load. The power

    plant that supplies a particular load must have an aggregate (total)

    installed capacity at least equal to the maximum demand represented onthe load curve.

    One advantage of the load curve is that it can indicate at a glance the

    general character of the load that is being supplied by the plant (not

    readily obtained from tabulated figures)

    Less installed capacity of generating equipment is needed for the plant

    which has fewer number of valleys and peaks in each load graph. The

    more nearly the graph of a load approximates a horizontal line, the

    nearer the conditions will be ideal.

    METHODS OF OBTAINING A LOAD GRAPH IN A POWER PLANT1. Use of recording graphic meters such as graphic wattmeter

    2. Plotting values of power from indicating wattmeter readings at equal

    time interval

  • 8/10/2019 Lecture on Distribution System

    13/36

  • 8/10/2019 Lecture on Distribution System

    14/36

    Average demand

    The average of the demand over a specified period (day, week,

    month, )

    Must include demand interval, period, and unitsExample : the 15-minute average KW demand for the month was

    350 KW

    Diversified demand

    Sum of demands imposed by a group of loads over a particularperiod

    Must include demand interval, period and units

    Example : the 15-minute diversified KW demand in the period

    ending at 9:30 was 200 KW

    Maximum diversified demand

    Maximum of the sum of the demands imposed by a group of loads

    over a particular period

    Must include demand interval, period and units

    Example : the 15-minute maximum diversified KW demand for the

    week was 500 KW.

    http://d/EE%20SUBJECTS/1ST%20SEM%202009-2010/EE%20132%20-%20POWER%20SYSTEM/POWER%20SYSTEM/all%20demand%20curve.xlsxhttp://d/EE%20SUBJECTS/1ST%20SEM%202009-2010/EE%20132%20-%20POWER%20SYSTEM/POWER%20SYSTEM/all%20demand%20curve.xlsx
  • 8/10/2019 Lecture on Distribution System

    15/36

    Load duration curve

    The load duration curve plots the 15-minute KW demand vs. the

    percent of time the transformer operates at or above the specific KW

    demand.

    Example : the transformer operates with a 15-minute kw demand of 12

    kw or greater 22% of the time.

    Maximum noncoincident demand

    For a group of loads, the sum of the individual maximum demands

    without any restriction that they occur at the same

    Must include demand interval, period, and units

    Example : the maximum noncoincident 15-minute KW demand for the

    week was 700 KW

    http://d/EE%20SUBJECTS/1ST%20SEM%202009-2010/EE%20132%20-%20POWER%20SYSTEM/POWER%20SYSTEM/all%20demand%20curve.xlsx
  • 8/10/2019 Lecture on Distribution System

    16/36

    Demand factor

    The demand factor can be defined for an individual customer

    maximum demandDemand factor = -----------------------------

    connected load

    Load factor

    Ratio of the average demand of any individual customer or

    group of customer over a period to the maximum demand over

    the same period. It gives an indication of how well the utilitys

    facility is being utilized.

    Average demand

    Load factor = -----------------------------

    Maximum demand

  • 8/10/2019 Lecture on Distribution System

    17/36

    Utilization factor

    Ratio of the maximum demand to rated capacity. It gives an

    indication of how well the capacity of an electrical device isbeing utilized.

    Maximum demand

    Utilization Factor = ----------------------------------

    Transformer rating

    Diversity factor

    Ratio of the maximum noncoincident demand of a group of

    customers to the maximum diversified demand of the group.

    Maximum noncoincident demand

    Diversity Factor = ---------------------------------------------------

    Maximum diversified demand

  • 8/10/2019 Lecture on Distribution System

    18/36

    Load diversity

    Difference between maximum noncoincident demand and the

    maximum diversified demand.

    EXAMPLES .

  • 8/10/2019 Lecture on Distribution System

    19/36

  • 8/10/2019 Lecture on Distribution System

    20/36

    0

    1

    2

    3

    4

    5

    6

    7

    1 3 5 7 9 11131517192123252729313335373941434547495153555759616365676971737577798183858789919395

    0

    1

    2

    3

    4

    5

    6

    7

    8

    1 6 11 16 21 26 31 36 41 46 51 56 61 66 71 76 81 86 91 96

  • 8/10/2019 Lecture on Distribution System

    21/36

    0

    1

    23

    4

    5

    6

    7

    8

    1 6 11 16 21 26 31 36 41 46 51 56 61 66 71 76 81 86 91 96

    0

    1

    2

    3

    4

    5

    6

    7

    1 3 5 7 9 11131517192123252729313335373941434547495153555759616365676971737577798183858789919395

  • 8/10/2019 Lecture on Distribution System

    22/36

    0

    1

    2

    3

    4

    5

    6

    7

    8

    1 6 11 16 21 26 31 36 41 46 51 56 61 66 71 76 81 86 91 96

    ENERGY = 58.75 KW HRSAVERAGE DEMAND = 58.75/24 = 2.45 KW

    AVERAGE

  • 8/10/2019 Lecture on Distribution System

    23/36

    0

    1

    2

    3

    4

    5

    6

    7

    1 6 11 16 21 26 31 36 41 46 51 56 61 66 71 76 81 86 91 96

    LOAD DURATION CURVE

  • 8/10/2019 Lecture on Distribution System

    24/36

    FEEDER LOADS

    Load Allocation

    In the analysis of a distribution feeder load, data will

    have to be specified. The data provided will depend

    upon how detailed the feeder is to be modeled, andthe availability of customer load data.

    The most comprehensive model of a feeder will

    represent every distribution transformer. In this case,

    the load allocated to each transformer will have to be

    determined.

  • 8/10/2019 Lecture on Distribution System

    25/36

    Application of Diversity Factors

    The definition of the diversity factor (DF) is the ratio of the

    maximum noncoincident demand to the maximum

    diversified demand. When a diversity factor table is

    available, then it is possible to determine the maximum

    diversified demand of a group of customers served by a

    distribution transformer.Max. noncoincidental demand

    Max. diversified demand = ----------------------------------------

    DFn

    The maximum diversified demand becomes the allocated

    load for the transformer.

  • 8/10/2019 Lecture on Distribution System

    26/36

    Single-phase lateral.

  • 8/10/2019 Lecture on Distribution System

    27/36

    Example :

    A single-phase lateral provides service to three distribution

    transformers as shown above. The energy in kwh consumed by

    each customer during a month is known. A load survey hasbeen conducted for customers in this class, and it has been

    found that the customer 15-minute maximum kw demand is

    given by the equation :

    Max Kwdemand= 0.2+ 0.008 * kwh

    Customer#1 #2 #3 #4 #5

    Kwh 1523 1645 1984 1590 1456

    Max Kw 12.4 13.4 16.1 12.9 11.9

    Transformer 1

  • 8/10/2019 Lecture on Distribution System

    28/36

    Customer

    #12 #13 #14 #15 #16 #17 #18

    Kwh 2098 1856 2058 2265 2135 1985 2103

    Max Kw 17 15.1 16.7 18.3 17.3 16.1 17

    Customer

    #6 #7 #8 #9 #10 #11

    Kwh 1235 1587 1698 1745 2015 1765

    Max Kw 10.1 12.9 13.8 14.2 16.3 14.3

    Transformer 2

    Transformer 3

  • 8/10/2019 Lecture on Distribution System

    29/36

    N Div F N Div F N Div F

    1 1.1 26 3.00 51 3.15

    2 1.60 27 3.01 52 3.15

    3 1.80 28 3.02 53 3.16

    4 2.10 29 3.04 54 3.16

    5 2.20 30 3.05 55 3.16

    6 2.30 31 3.05 56 3.17

    7 2.40 32 3.06 57 3.17

    8 2.55 33 3.08 58 3.17

    9 2.60 34 3.09 59 3.18

    10 2.65 35 3.10 60 3.18

    11 2.67 36 3.10 61 3.18

    12 2.70 37 3.11 62 3.18

    13 2.74 38 3.12 63 3.18

    14 2.78 39 3.12 64 3.19

    15 2.80 40 3.13 65 3.19

    16 2.82 41 3.13 66 3.19

    17 2.84 42 3.13 67 3.19

    18 2.86 43 3.14 68 3.19

    19 2.88 44 3.14 69 3.20

    20 2.90 45 3.14 70 3.20

    21 2.90 46 3.14

    22 2.92 47 3.15

    23 2.94 48 3.15

    24 2.96 49 3.15

    25 2.98 50 3.15

    TYPICAL VULUES OF DIVERSITY FACTOR

  • 8/10/2019 Lecture on Distribution System

    30/36

    0

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61 64 67 70

    D

    iversityFactors

    Number of Customers

    Series1

  • 8/10/2019 Lecture on Distribution System

    31/36

    Determine for each transformer the non-coincident maximum kwdemand . Using the given diversity factor table, determine the

    maximum diversified kw demand.

    T1 : Noncoin. max = 12.4 + 13.4 + 16.1 + 12.9 + 11.9 = 66.7 kw

    Noncoin. Max 66.7

    Max. div. demand = -------------------- = ------- = 30.3 kw

    Div. fac. for 5 2.2

  • 8/10/2019 Lecture on Distribution System

    32/36

    T2 : Noncoin. max = 12.9 + 13.8 + 14.2 + 16.3 + 14.3 + 17 = 81.6 kw

    Noncoin. Max 81.6

    Max. div. demand = -------------------- = ------- = 35.5 kw

    Div. fac. for 6 2.3

    T3 : Noncoin. max = 17 + 15.1 + 16.7 + 18.3 + 17.3 +16.1 +17 = 117.5 kw

    Noncoin. Max 117.5

    Max. div. demand = -------------------- = ------- = 48.9 kw

    Div. fac. for 7 2.4

  • 8/10/2019 Lecture on Distribution System

    33/36

  • 8/10/2019 Lecture on Distribution System

    34/36

    0

    1

    2

    3

    4

    5

    6

    7

    1 6 11 16 21 26 31 36 41 46 51 56 61 66 71 76 81 86 91 96

    Series2

    LOAD CURVE FOR TRANSFORMER 1

  • 8/10/2019 Lecture on Distribution System

    35/36

    LOAD DURATION CURVE FOR TRANSFORMER 1

    0

    5

    10

    15

    20

    25

    30

    35

    1 6 11 16 21 26 31 36 41 46 51 56 61 66 71 76 81 86 91 96

    Series2

  • 8/10/2019 Lecture on Distribution System

    36/36