lecture 17 flat structures. aeration for flat structures ideally - uniform air flow – "dead...

8
Lecture 17 Flat Structures

Upload: michael-campbell

Post on 03-Jan-2016

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Lecture 17 Flat Structures. Aeration for Flat Structures Ideally - uniform air flow – "dead zones" –min. of.2 cfm design rate (this is double) –fines

Lecture 17

Flat Structures

Page 2: Lecture 17 Flat Structures. Aeration for Flat Structures Ideally - uniform air flow – "dead zones" –min. of.2 cfm design rate (this is double) –fines

Aeration for Flat Structures

• Ideally - uniform air flow –  "dead zones"  – min. of .2 cfm design rate (this is double) – fines concentrate under filling auger... – Duct pacing and storage –    less than or equal to grain depth –    longest air path should be less than or equal to 1.5

times the shortest path –  max. slope to grain = 10%

•  

Page 3: Lecture 17 Flat Structures. Aeration for Flat Structures Ideally - uniform air flow – "dead zones" –min. of.2 cfm design rate (this is double) –fines

Aeration for Flat Structures

• Duct Sizing – number of bushels – airflow rate – design velocity

• Positive vs Negative pressure – 2,500 fpm = positive – 1,500 fpm = negative

Page 4: Lecture 17 Flat Structures. Aeration for Flat Structures Ideally - uniform air flow – "dead zones" –min. of.2 cfm design rate (this is double) –fines

Grain Sampling and Inspection

•  Tell Tale signs –    leaking grain –    bulging walls –    snow melting off the roof

•  Prevention of dead zones... –    perforated flooring best –    when ducts are used: probe "dead zones

Page 5: Lecture 17 Flat Structures. Aeration for Flat Structures Ideally - uniform air flow – "dead zones" –min. of.2 cfm design rate (this is double) –fines

Preventing spoilage

• Preventing spoilage –   perforated floor best, but fines accumulate below the floor -

good spot for insects – checking "dead zones" – ducts can have fines accumulate, however cleaning and

treating is much easier. – "core" in center of bin (where grain unloads) prevents air

movement- spreader – probe areas where the probing is more difficult – filling and unloading leads to stagnant grain – Stirring devices – use of a vapor barrier – sealing bottom ring to concrete

Page 6: Lecture 17 Flat Structures. Aeration for Flat Structures Ideally - uniform air flow – "dead zones" –min. of.2 cfm design rate (this is double) –fines

Sampling equipment needed

• Moisture tester

• Sampling probe

• Temperature probe

• Measuring tape

• Grain dividers

• Scale to weigh foreign material

Page 7: Lecture 17 Flat Structures. Aeration for Flat Structures Ideally - uniform air flow – "dead zones" –min. of.2 cfm design rate (this is double) –fines

Getting a good sample

• Divide bin into 5 equal parts

• use probe

• Sample each section

Page 8: Lecture 17 Flat Structures. Aeration for Flat Structures Ideally - uniform air flow – "dead zones" –min. of.2 cfm design rate (this is double) –fines

Still concerned?

• Fan test... Musty odor?  

• Corrective Action –    Insects - fumigate –    Wet - dry –    Hot - aerate

• Note- Value of sampler greater than value of sample