laboratory investigation on construction materials from kubwa extension building collapse site,...

Upload: emeso-ojo

Post on 03-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    1/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    1 | P a g e

    LABORATORY INVESTIGATION ON CONSTRUCTION

    MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    2/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    2 | P a g e

    CONTENTS

    1.0 INTRODUCTION

    2.0 BACKGROUND

    3.0 GEOTECHNICAL INVESTIGATIONS

    4.0 ANALYSIS OF TEST RESULTS

    5.0 DISCUSSIONS AND RECOMMENDATIONS

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    3/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    3 | P a g e

    TABLES AND FIGURES

    List of Tables

    Table 1 Allowable Bearing Capacity Values

    Table 2 Summary of Laboratory Test Results

    Appendices

    Appendix A Particle Size Distribution Graphs

    Appendix B Atterberg Limit Test

    Appendix C Direct Shear Test

    Appendix D Consolidation Test

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    4/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    4 | P a g e

    1.0 INTRODUCTION

    Construction materials comprises of any item consumed or used in a construction project and

    incorporated into the constructed building or structure. It covers a wide variety of materials

    ranging from aggregates (fine and coarse), reinforcement, cement, bricks, blocks e.t.c. To ensure

    the durability and stability of any structure, it is pertinent that a detailed engineering design is

    carried out to ensure that the proper construction material is recommended for the proposed

    work. Hence, construction material testing is a critical component in the design and construction

    of any civil engineering structure. Unfortunately, this is not the case as the use of poor

    construction materials has been attributed to be the major cause of building collapse in Nigeria

    (NBRRI Technical Reports No. 22 & 23). As a result, to ascertain the cause of any building collapse,

    the first step would be to conduct a thorough laboratory investigation of the construction

    materials used on the site.

    The report for the laboratory investigation conducted on the construction materials at the

    building collapsite site at Kubwa Extension is presented herein.

    1.1 Project Objectives and Scope of WorkThe purpose of the laboratory investigation was to determine the physical and engineering

    parameters of the construction materials used on the building collapse site. This will determine if

    the cause of the building collapse in question was as a result of poor quality of construction

    materials and identify which of the construction materials. To achieve this, the investigation

    comprised of the following:

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    5/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    5 | P a g e

    Laboratory testing of soil samples collected from the site to determine index andengineering properties of the subsoils. Tests conducted include:

    Particle size distribution Atterberg limits Direct shear test Consolidation test

    Compressive strength test on concrete rubbles and blocks collected from the site. Tensile strength test on reinforcement collected from the site Engineering analysis to determine suitability of materials used. Preparation of report including conclusions and findings.

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    6/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    6 | P a g e

    2.0 BACKGROUND

    The building collapse site was located at No 3 Ademola Awosika Road, close to the Living Faith

    Church, Kubwa Extension III, FCT. The collapsed Buildingwas an L-shaped framed structure

    and collapse occurred in the early hours of Wednesday 8th of August, 2012.

    The foundation of the building was completed and abandoned for over ten years. The structure

    was under construction with the second floor and its columns completed; while the roof beams

    were being formed when it collapsed. The framed structure collapsed and came down

    completely with the structural elements reduced to a heap of rubble; and concrete dissociating

    from element reinforcement. The mode of failure was not as expected for a framed structure

    still under construction. This is indicative of weak foundation and failure of structural

    elements.

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    7/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    7 | P a g e

    3.0GEOTECHNICAL INVESTIGATIONS3.1Collection of Samples

    Samples were collected from the building collapse site on the 27 th of September, 2012. Soil

    samples were collected at a depth of 1m below ground level from three different locations on the

    site. Two intact block samples (9 and 6)were collected from the site as well concrete debris.

    Reinforcement of diameters 12mm, 16mm and 20mm were also collected to test their tensile

    strength.

    3.2Laboratory Testing of Soil SamplesThe following tests were conducted on the samples collected from the site:

    Particle size distribution Atterberg limits Specific Gravity test Direct shear test Consolidation Test

    Particle Size Distribution:This test is performed to determine the percentage of different grain sizes contained within

    a soil. The mechanical or sieve analysis is performed to determine the distribution of the

    coarser, larger-sized particles, and the hydrometer method is used to determine the

    distribution of the finer particles. This test is performed in accordance with BS 1377: Part

    2: 1990. The distribution of different grain sizes affects the engineering properties of soil.

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    8/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    8 | P a g e

    Grain size analysis provides the grain size distribution, and it is required in classifying the

    soil.

    Atterberg LimitsThe Atterberg limits are based on the moisture content of the soil. This test is performed to

    determine the plastic and liquid limits of a fine grained soil. The liquid limit (LL) is

    arbitrarily defined as the water content, in percent, at which the soil changes from a plastic

    to a viscous fluid state The plastic limit is the moisture content that defines where the soil

    changes from a semi-solid to a plastic (flexible) state. The shrinkage limit is the moisture

    content that defines where the soil volume will not reduce further if the moisture content is

    reduced. A wide variety of soil engineering properties have been correlated to the liquid

    and plastic limits, and these Atterberg limits are also used to classify a fine-grained soil

    according to the Unified Soil Classification system or AASHTO system.

    This test was performed in accordance with BS 1377: Part 2: 1990.

    Direct Shear TestThe direct shear test is used for carrying out drained shear tests for the determination of

    effective shear strength parameters in cohesionless soils. The test was carried out using the

    small shearbox apparatus on undisturbed specimens obtained from the trial pit. This test

    was carried out in accordance with clause 4 of BS 1377: Part 7: 1990.

    Condolidation TestThe consolidation/oedometer test is performed to determine the rate of one-dimensional

    consolidation in clayey soil samples. This test is performed to determine the magnitude and

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    9/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    9 | P a g e

    rate of volume decrease that a laterally confined soil specimen undergoes when subjected

    to different vertical pressures. This test was carried out in accordance with clause 2 of BS

    1377: Part 5: 1990.

    3.3Laboratory Testing of Concrete and ReinforcementIn the laboratory, the compressive strength test is carried out on concrete to determine the

    maximum strength at failure. A normal force is applied on the concrete element until it fails and

    this force is divided by the surface area to ascertain the compressive strength of the element. To

    obtain a represenative compressive strength, ten samples are usually crushed and the average is

    calculated as the compressive strenght. Unfortunately, an adequate number of samples from the

    salbs, beams or columns could not be obtained from the collapse site as most of the concrete

    elements had been broken up. Hence, the compressive strength test could not be performed.

    Similarly, the reinforcement obtained was deformed and rusted, hence could not be tested.

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    10/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    10 | P a g e

    4.0ANALYSIS OF TEST RESULTSThe purpose of the laboratory investigation was to determine the physical and engineering

    parameters of the construction materials used on the building collapse site. This will determine if

    the cause of the building collapse in question was as a result of poor quality of construction

    materials and identify which of the construction materials.

    4.1 Bearing Capacity Analysis

    The ultimate bearing capacity for foundations can be evaluated using shear strength parameters

    obtained from in situ or laboratory tests with suitable theoretical analysis. The Terzaghi equations

    which are applicable to foundations where the depth of foundation is less than the minimum

    width can be used as follows:

    For strip foundation,

    Qu = cNc + Z(Nq-1) + 0.5BN

    For square footing,

    Qu = 1.3cNc + Z(Nq-1) + 0.4BN

    For circular footing,

    Qu =1.3 cNc + Z(Nq-1) + 0.3BN

    Where: Qu Ultimate bearing capacity (kN/m2)

    c Cohesion (kN/m2)

    Unit weight (kN/m2)

    Z Depth of footing (m)

    B Width of footing (m)

    Nc, Nq, and Nare bearing capacity factors dependent on the angle of internal friction ()

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    11/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    11 | P a g e

    The allowable bearing capacity Qa, is the ultimate bearing capacity divided by a suitable factor of

    safety to limit settlements to 25mm and is usually in the range of 2 4. For foundations, a factor of

    safety of 3 is recommended.

    The table below presents the allowable bearing capacity for a square footing assuming a width of

    2m.

    Table 1: Allowable Bearing Capacity Values

    Allowable Bearing Pressure kN/m2

    Sample A Sample B Sample C

    DEPTH m

    1 126 133 154

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    12/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    12 | P a g e

    5.0DISCUSSION AND RECOMMENDATIONS5.1 Discussion

    a. SubsoilThe subsoil investigation at the collapsed site show that the subsoil consists basically of reddish to

    brwonish clayey sand. The grain size distribution of the soil showed more than 50% of the soils

    were retained on sieve No 200, indicating the soils are coarse grained. Since, 50% of these soils

    passed through sieve No 4, the soils are generally sandy soils. Also, the atterberg limits of two of

    the samples plotted below the line while the third plotted above the A-line on the Cassagrande

    plasticity chart. Based on the USCS soil classification system, these soils fall into the silty sands and

    clayey sands groups respectively. These soils generally have slight to medium expansion and

    compressibility with poor drainage characteristics.

    The results from the direct shear test further revealed the soil to be cohesive soils with an average

    internal friction of 180. Allowable bearing pressures ranged from 126 154 kN/m2. These values

    indicate that the soils bearing capacity was not exceeded. Hence, it can be deduced that the failure

    was not as a result of poor bearing capacity of the soil.

    b. ConcreteAs discussed in the previous section, compressive strength test could not be conducted due to

    insufficient number of samples. However, the following deductions were made based on visual

    observation of the concrete rubbles collected:

    Percentage of fine aggregates was more than the coarse aggregate Poor mix(voids observed in sample)

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    13/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    13 | P a g e

    Single sized aggregate(1 inch)was used Low cement content Aggregate Crushing Value(ACV) is over 37 Fine aggregate used did not pass the required envelope

    c. ReinforcementSimilarly, the tensile strength test could not be conducted due to insufficient number of

    samples. Also samples collected were bent and rusted which would reduce the tensile strength

    of the members.

    d. BlocksFrom visual observation, the blocks collected from the site appeared to be okay. As mentioned

    above, ten blocks are required to give a representative value of the blocks used on the site.

    5.2 Recommendation

    Details of laboratory investigation of construction materials collected from a building collapse site

    at Kubwa Extension are presented in this report. Building was an L-shaped framed structure still

    under construction. Laboratory investigation of the subsoil shows that the bearing capacity of the

    soil was satisfactory. However, the soils exhibited medium expansion and compressibility

    characteristics. Laboratory tests could not be performed on the other construction materials

    (concrete elements, blocks and reinforcement) due to the insufficient number of samples collected

    from the collapse site. It is recommended that ten samples of each material to be tested should be

    collected from building collapse sites to ensure that a representative value is obtained. However,

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    14/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    14 | P a g e

    visual observation of the concrete elements indicates a poor structural design was conducted

    prior to construction.

  • 7/28/2019 LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE SITE,

    15/15

    LABORATORY INVESTIGATION ON CONSTRUCTION MATERIALS FROM KUBWA EXTENSION BUILDING COLLAPSE

    SITE, ABUJA

    15 | P a g e

    REFERENCE

    NBRRI Technical Report No. 22: Collapse of Buildings in Nigeria (Technical Report on the Collapse

    of a 2-Storey Building at Mararaba. October 2011

    NBBRI Technical Report No. 23: Collapse of Buildings in Nigeria (Technical Report on the Collapse

    at Adenubi Close, Ikeja Lagos State. October 2011