laboratory fume hoods in accordance with title 8 ccr section 5154.1, ventilation requirements for...
TRANSCRIPT
Laboratory Fume Hoods
In accordance with Title 8 CCR Section 5154.1,
Ventilation Requirements for Laboratory-Type Hood Operations.
California State University Fresno
CSU Fresno, Environmental Health & Safety
(559) 278 - 7422
IntroductionPurpose of a Laboratory Fume Hood
Laboratory Fume Hoods help prevent exposure to fumes, vapors and particulate matter from hazardous substances.
IntroductionFunctions of a Laboratory Fume Hood
Fume hoods draw airflow inward, away from the worker.
Operator QualificationsTraining Requirements To operate a fume hood, one
must be trained to: Use the hood properly and
safely. Determine last performance test,
and if requirements are met. Understand the general hood
purpose, airflow characteristics, and potential for turbulent airflow and escape of hazardous substances from the hood.
Know where the quantitative airflow monitor or alarm system is located on the hood and how it is used to indicate an inward airflow during hood operation
8 CCR 5154.1(f)(3)
Pre-Use InspectionOverview
Check for last inspection date by EHS. Postings or signs should be present when a fume
hood is out of order and EHS is aware. If you suspect your hood is not working contact EHS immediately at 278-7422.
Check quantitative airflow monitoring device to ensure hood is working properly.
Use qualitative methods to ensure air is flowing in the proper direction.
Pre-Use InspectionDetermining last inspection Each fume hood must have
inspection record indicating: Last date of inspection. Initials of the last inspector
of the device. Whether the device passed
or failed inspection. This data sheet is normally
attached to the fume hood. Units that fail an inspection
are tagged with a “Do Not Use” sign with a date the unit was taken out of service.
Units must be re-inspected: Annually. After any repair. Following any addition of large
equipment to the unit.
Pre-Use InspectionQuantitative Monitoring Devices
A hood user must quantitatively identify whether their fume hood is working properly. The method must measure an exact or approximate rate of inward airflow.
Acceptable devices to determine quantitative airflow include: Inclined Manometers Diaphragm Pressure Gauges Vane Gauges An Airflow Alarm System is also acceptable, granted that the
“system provides an audible or visual alarm when the airflow decreases to less than 80% of the airflow required by subsection” 8 CCR 5154.1(e)(3)(A)
All values indicated on the device should be no less then those indicated on the certified“safe level” indicated by the label on the fumehood.
Pre-Use InspectionExamples of Quantitative Monitoring Devices
Vaneometer
Rare on campus, but acceptable.
Inclined Manometer
This device is very common on campus.
Diaphragm Pressure Gauge Rare on
campus, but acceptable.
Pre-Use InspectionExamples of Quantitative Monitoring Devices
Fume Hood Alarm Device
Alerts the user if there is inadequate inward airflow Visually Audibly
These units should have a visual aid of some sort indicating that the unit is functioning and is safe to use.
Pre-Use InspectionExamples of Quantitative Monitoring Devices
If you do not have a working qualitative method to assess if the fume hood is functioning properly, contact EHS at 278-7422.
Pre-Use InspectionQualitative Inspection Methods
Examples of Qualitative Devices include: Kimwipes / Delicate
Wipes Tape Mylar Strips
The device used must demonstrate airflow is flowing inward.
Pre-Use InspectionQualitative Inspection Methods
The material used (kimwipe, mylar or tape) should be pulled in by the fume hood to indicate there is inward airflow.
The material must be tested in multiple areas where the hood is open.
If you are having trouble or do not note the inward movement of air, make sure you have remembered to turn the unit on.
Using the Fume HoodWork Practices
The sash of the fume hood may be raised completely during usage, unless marked otherwise. If marked
the hood shall be opened no further then the safe operating level, indicated by the arrows, when in use.
Using the Fume HoodWork Practices
Store non-essential chemicals and other equipment outside of the fume hood.
Keep the hood free from obstruction of large equipment whenever possible.
Storage of hazardous waste containers not related to the wastes being generated within the hood is not advised. Incompatible wastes are required to be separated and closed
during storage, except when it is necessary to add waste Do not put your face inside the fume hood when
hazardous substances are present. Always keep your face and body outside the unit when in use.
Have Concerns?When should you contact EHS with any concerns?
Annual Inspection If you note that an
inspection was not completed within one year.
Maintenance Repairs Addition of Large
Equipment Newly Installed Hoods You suspect your fume
hood is not protecting you adequately for any reason.
Training Completion Acknowledgement form Please either print out a copy of this slide or request a hard copy from your Department
Safety Coordinator or Supervisor. Please sign/date in the spaces provided, and then forward it to your Department Safety Coordinator or Supervisor.
I have read the slides presented in the Laboratory Fume Hoods
Power Point presentation and have reviewed the associated department-specific plans.
Name (Print)_________________________________________________
Signature ___________________________________________________
Department _________________________________________________
Date _____________________________