ke2 compressor sequencer oem · aux relay board 21323 auxiliary relay board external relays 21304...

40
Product Summary: The KE2 Compressor Sequencer OEM allows control of up to 8 stages of loading for a single suc- tion group, or up to 10 stages of loading (5 per suction group) for dual suction groups. For dual suction groups, the controller is applicable to both racks with a shared common dis- charge, or independent discharge lines. Suction pressure can be controlled to either a fixed setpoint, or a floating suction pressure for maximum efficiency. Each stage of loading can be set to: fixed speed compressor, variable speed compressor, digi- tal compressor① ② or unloaders. The relays for the stages can alternatively be used to control a Master Liquid Line Solenoid, or as a Hot Gas Defrost Relay. Communicaon: As is standard with many other KE2 Therm controllers, the KE2 Compressor Sequencer OEM has the simplest and easiest communication platform in the industry. The controller uses standard communication protocols and cables; no extra software is necessary, only an Ethernet connec- tion to the controller. E-mail and/or text alerts can be sent out right from the controller. Com- plete remote access is available during startup with one simple button press and an Internet connection. One per Sucon Group Controller is designed to operate with a Copeland Scroll Digital Compressor, when Digital Compressor is selected. Part Numbers - Controllers & Accessories Part Number Descripon KE2 Compressor Sequencer OEM 21768 Controller only Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to pilot contactor for 5th compressor stage, control master liquid line solenoid, hot gas solenoid or unloader valve with Aux Relay Board Relay #5. Pressure Transducers 20201Pressure Transducer 0 to 150 psia, 10 ſt. lead - for sucon pressure. 20204Pressure Transducer 0 to 150 psia, 40 ſt. lead - for sucon pressure. 20202 Pressure Transducer 0 to 500 psig, 10 ſt. lead - for discharge pressure. 20712 Pressure Transducer 0 to 500 psig, 40 ſt. lead - for discharge pressure. Temperature Sensors 21230 High temp sensor for discharge at condenser inlet, 15 ſt. 20199 Standard temp sensor for all other temp inputs, 10 ſt. (black) 20200 Standard temp sensor for all other temp inputs, 40 ſt. (black) Replacement Relays 21374 Replacement Form C Relay for Main Board Replacement Fuses 21375 Replacement incoming power fuse for Main Board and Aux Relay Board 21628 Replacement fuses for Aux Relay Board relays (5 pack) Use transducers 20208 (10 ſt.) or 20711 (40 ſt.) for R-410A. Use 20202 (10 ſt.) or 20712 (40 ſt.) for R-744. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090 Q.2.60 March 2019 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide This reference should remain on site with the installed KE2 Compressor Sequencer Contents: Product Summary Pg. 1 Part Numbers - Controllers & Accessories Pg. 1 Dimensions & Specifications - Main Board Pg. 2 Dimensions & Specifications - Auxiliary Relay Board Pg. 3 Application Pg. 3 Setup Options Pg. 4 1 - Main Board Only Single Suction Group w. Common Discharge Pg. 5 2 - Main Board + 1 Aux Relay Board Single Suction Group w. Common Discharge Pg. 6-7 3 - Main Board + 2 Aux Relay Boards Single Suction Group w. Common Discharge Pg. 8-9 4 - Main Board + 2 Aux Relay Boards Dual Suction Groups w. Common Discharge Pg. 10-11 5 - Main Board + 2 Aux Relay Boards Dual Suction Groups w. Independant Disch. Pg. 12-13 Communication Setup Options Pg. 14 Setting Up Groups Pg. 15 Designating Relay Functions Pg. 16 - 18 Single Group - Main Board Only Single Group or Dual Group +Aux Boards Running the System Pg. 18-19 Determining Compresor ON/OFF Order Pg. 20 Fixed Suction Pressure w. Digital Scroll or Variable Speed Compressors Fixed Suction Pressure w. Fixed Speed Compressors Floating Suction Pressure Selectable Inputs Pg. 21 Descriptions of Selectable Input Mode Options Pg. 21 Remote Display Pg. 22 - 23 Variables Menu - Single Group Setpoints Menu - Single Group Variables Menu - Dual Group Setpoints Menu - Dual Group Alarms Pg. 24 - 25 Critical & Cautionary Alarms - ALL Groups Safety Alarms - ALL Groups Webpage Setpoints - Main Board Pg. 26 - 27 Webpage Setpoints - Auxiliary Relay Boards Pg. 28 Webpage Screen Shots Pg. 29 - 37 Home Page Status Page - Main Board Status Page - Aux Relay Board Settings Page Login Page Network Page Setpoints Page - Main Board Only Setpoints Page - Main Board + Aux Relay Board(s) Graphs Page Alphabetical List of Abbreviations Pg. 38 - 40

Upload: others

Post on 16-Aug-2020

24 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Product Summary:The KE2 Compressor Sequencer OEM allows control of up to 8 stages of loading for a single suc-tion group, or up to 10 stages of loading (5 per suction group) for dual suction groups.

For dual suction groups, the controller is applicable to both racks with a shared common dis-charge, or independent discharge lines. Suction pressure can be controlled to either a fixed setpoint, or a floating suction pressure for maximum efficiency.

Each stage of loading can be set to: fixed speed compressor, variable speed compressor①, digi-tal compressor① ② or unloaders. The relays for the stages can alternatively be used to control a Master Liquid Line Solenoid, or as a Hot Gas Defrost Relay.

Communication:As is standard with many other KE2 Therm controllers, the KE2 Compressor Sequencer OEM has the simplest and easiest communication platform in the industry. The controller uses standard communication protocols and cables; no extra software is necessary, only an Ethernet connec-tion to the controller. E-mail and/or text alerts can be sent out right from the controller. Com-plete remote access is available during startup with one simple button press and an Internet connection.

① One per Suction Group

② Controller is designed to operate with a Copeland Scroll Digital Compressor, when Digital Compressor is selected.

Part Numbers - Controllers & Accessories

Part Number Description

KE2 Compressor Sequencer OEM21768 Controller only

Aux Relay Board21323 Auxiliary Relay Board

External Relays21304 Solid State Relay - Used to control digital compressor bypass valve

21032 Used to pilot contactor for 5th compressor stage, control master liquid line solenoid, hot gas solenoid or unloader valve with Aux Relay Board Relay #5.

Pressure Transducers20201③ Pressure Transducer 0 to 150 psia, 10 ft. lead - for suction pressure. 20204③ Pressure Transducer 0 to 150 psia, 40 ft. lead - for suction pressure.20202 Pressure Transducer 0 to 500 psig, 10 ft. lead - for discharge pressure.20712 Pressure Transducer 0 to 500 psig, 40 ft. lead - for discharge pressure.

Temperature Sensors21230 High temp sensor for discharge at condenser inlet, 15 ft.20199 Standard temp sensor for all other temp inputs, 10 ft. (black)20200 Standard temp sensor for all other temp inputs, 40 ft. (black)

Replacement Relays21374 Replacement Form C Relay for Main Board

Replacement Fuses21375 Replacement incoming power fuse for Main Board and Aux Relay Board21628 Replacement fuses for Aux Relay Board relays (5 pack)

③ Use transducers 20208 (10 ft.) or 20711 (40 ft.) for R-410A. Use 20202 (10 ft.) or 20712 (40 ft.) for R-744.

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60March 2019

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

This reference should remain on site with the installed KE2 Compressor Sequencer

Contents:Product Summary Pg. 1

Part Numbers - Controllers & Accessories Pg. 1

Dimensions & Specifications - Main Board Pg. 2

Dimensions & Specifications - Auxiliary Relay Board Pg. 3

Application Pg. 3

Setup Options Pg. 4 1 - Main Board Only Single Suction Group w. Common Discharge Pg. 52 - Main Board + 1 Aux Relay Board Single Suction Group w. Common Discharge Pg. 6-73 - Main Board + 2 Aux Relay Boards Single Suction Group w. Common Discharge Pg. 8-94 - Main Board + 2 Aux Relay Boards Dual Suction Groups w. Common Discharge Pg. 10-115 - Main Board + 2 Aux Relay Boards Dual Suction Groups w. Independant Disch. Pg. 12-13

Communication Setup Options Pg. 14

Setting Up Groups Pg. 15

Designating Relay Functions Pg. 16 - 18 ▪ Single Group - Main Board Only ▪ Single Group or Dual Group +Aux Boards

Running the System Pg. 18-19

Determining Compresor ON/OFF Order Pg. 20 ▪ Fixed Suction Pressure w. Digital Scroll or Variable Speed Compressors▪ Fixed Suction Pressure w. Fixed Speed Compressors▪ Floating Suction Pressure

Selectable Inputs Pg. 21

Descriptions of Selectable Input Mode Options Pg. 21

Remote Display Pg. 22 - 23 ▪ Variables Menu - Single Group▪ Setpoints Menu - Single Group ▪ Variables Menu - Dual Group▪ Setpoints Menu - Dual Group

Alarms Pg. 24 - 25 ▪ Critical & Cautionary Alarms - ALL Groups▪ Safety Alarms - ALL Groups

Webpage Setpoints - Main Board Pg. 26 - 27

Webpage Setpoints - Auxiliary Relay Boards Pg. 28

Webpage Screen Shots Pg. 29 - 37▪ Home Page▪ Status Page - Main Board▪ Status Page - Aux Relay Board▪ Settings Page ▪ Login Page▪ Network Page ▪ Setpoints Page - Main Board Only▪ Setpoints Page - Main Board + Aux Relay Board(s)▪ Graphs Page

Alphabetical List of Abbreviations Pg. 38 - 40

Page 2: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 2

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Dimensions & Specifications KE2 Compressor Sequencer OEM - Main Board

NONC

COM

EARTH

11.20”

11.00”

5.70”

2.80”

3.25”

0.20”

0.20”

Ø0.150” Hole Thru (6 places)0.06”

1.60”

0.10”

ON

1 2 3 45 6 7 8

8.5”

3.25”

0.06”1.50”

KE2 Compressor Sequencer OEM – Main Board pn 21768

Input Voltage: 120/208/230 VAC

Ambient Temp: -40°F to 140°F (-40°C to 60°C)

Operating Temp: -40°F to 140°F (-40°C to 60°C)

Inputs: (2) temperature sensors

(2) pressure transducers

(3) selectable temperature / digital inputs

Outputs:(1) 0 to 10 VDC / 0 to 5 VDC - configurable for variable speed or 0V/10V for Digital Compressor Bypass Valve ①②

Relays: (3) 10A inductive

Relay Functions:Fixed speed, variable speed, digital com-pressor, hot gas defrost relay, master liquid line solenoid, unloader

Selectable Input Functions:

Internal compressor temp, room temp, monitor temp, hot gas defrost request, 2nd pressure, 2nd temp, compressor module alarm, high pressure safety alarm, oil pres-sure safety alarm, system off

Communication: Standard TCP/IP, API, XML, BACnet over IP③

① Digital Compressor Bypass Valve control requires PN 21304.② Controller is designed to operate with Copeland Scroll Digital Compressor.③ Requires KE2 Edge Manager PN 21634. Not available at release.

Digital Switch Relay– pn 21032

Operating Temp: -13°F to 131°F (-25°C to 55°C)

Relays: 10A inductive

Pressure Transducer – Suction Line pn 20201 (10ft.), 20204 (40 ft.)

Pressure Range: 0 to 150 psia

Proof Pressure 450 psi

Burst Pressure: 1,500 psi

Operating Temperature: -40°F to 275°F (-40°C to 135°C)

Pressure Transducer – Discharge Line, Suction & Discharge Line for R-744 pn 20202 (10ft.), 20712 (40 ft.)

Operating Range: 0 to 500 psig

Proof Pressure: 1,000 psi

Burst Pressure: 1,500 psi

Operating Temperature: -40°F to 275°F (-40°C to 135°C)

Standard Temperature Sensor pn 20199 (10ft.), 20200 (40 ft.)

Operating Temp: -60°F to 150°F (-51°C to 65°C)

High Temperature Sensor pn 21230 (15ft.)

Operating Range: -40°F to 302°F (-40°C to 150°C)

Page 3: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 3

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Auxiliary Relay Board pn 21323 (When used with KE2 Compressor Sequencer OEM)

Input Voltage: 120/208/230 VAC

Ambient Temp: -40°F to 140°F (-40°C to 60°C)

Operating Temp: -40°F to 140°F (-40°C to 60°C)

Inputs: (2) temperature sensor / selectable inputs①

(1) pressure transducer

(1) selectable input

Outputs: (1) 0 to 10 VDC / 0 to 5VDC- configurable for variable speed or 0V/10V for Digital Compressor Bypass Valve②③

Relays: (4) 5A FLA inductive (1) 10A inductive external Digital Switch Relay - requires pn 21032

Relay Functions:Fixed speed, variable speed, digital compressor, hot gas defrost relay, master liquid line solenoid, unloader

Digital Input Functions:Internal compressor temp, room temp, monitor temp, hot gas defrost request, 2nd pressure, 2nd temp, compressor module alarm, high pressure safety alarm, oil pressure safety alarm, system off.

Dimensions & Specifications Auxiliary Relay Board

NONC

COM

EARTH

11.20”

11.00”

5.70”

2.80”

3.25”

0.20”

0.20”

Ø0.150” Hole Thru (6 places)0.06”

1.60”

0.10”

ON

1 2 3 45 6 7 8

8.5”

3.25”

0.06”1.50”

Application:The KE2 Compressor Sequencer OEM can be used on rack systems with up to 8 stages of loading for a single suction group, or up to 10 stages of loading (5 per suction group) for dual suction groups. For dual suction groups, the discharge line can be shared between the two groups, or independent. The relays can also be used to con-

Type of ControlTotal Number of Stages* (Compressor, Unloader)

1 2 3 4 5 6 7 8 9 10

Single Suction / Common Discharge KE2 Compressor Sequencer OEM

+1 Aux Relay Board +2 Aux Relay Boards

Dual Suction / Common Discharge KE2 Compressor Sequence OEM + 2 Aux Relay Boards (up to 5 stages per suction group)Dual Suction / Independent Discharge KE2 Compressor Sequence OEM + 2 Aux Relay Boards (up to 5 stages per suction group)

*Relays can also be used as a master liquid line solenoid valve relay and/or hot gas bypass relay.

Please refer to the point to point wiring diagrams for each specific application.

trol a Master Liquid Line Solenoid or act as a Hot Gas Defrost Relay. When more stages of loading are required than available on the main board, auxiliary relay boards can be added to increase the number of available relays. Please refer to the chart below for the number of required auxiliary boards for a specific application.

① Number of selectable inputs depends on application

② Digital Compressor Bypass Valve control requires PN 21304

③ Controller is designed to operate with a Copeland Scroll Digital Compressor.

Page 4: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 4

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Oil LineTo CondenserDischarge Header

Suction Header

Option 4:KE2 Compressor Sequencer OEM + 2 Aux Relay BoardsDual Suction Groups w. Common Discharge

Option 5:KE2 Compressor Sequencer OEM +2 Aux Relay BoardsDual Suction Groups w. Independent Discharge

Option 3:KE2 Compressor Sequencer OEM + 2 Aux Relay BoardsSingle Suction Group w. Common Discharge

Aux Relay Board 1 Aux Relay Board 2

To Condenser Oil Line

Suction Header

Discharge Header

Option 2: KE2 Compressor Sequencer OEM + 1 Aux Relay BoardsSingle Suction Group w. Common Discharge

Option 1:KE2 Compressor Sequencer OEMSingle Suction Group w. Common Discharge

To CondenserOil Line

Discharge HeaderSuction Header

To CondenserOil Line

Discharge Header

Suction Header Suction Header

Main Board Aux Relay Board 2

Up to 5 compressors

Aux Relay Board 1

Up to 5 compressors

Aux Relay Board 1

To Condenser Oil Line

Discharge HeaderSuction Header Suction Header

Discharge Header

Up to 5 compressorsUp to 5 compressors

Aux Relay Board 1 Aux Relay Board 2

Setup Options

Page 5: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 5

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT0 - 10VDC- Variable Speed (OV - 10V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY 3

RELAY 2RELAY 1

STEPPER MOTOR Not Used

RedBlack

GreenSuction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure TransducerGreen Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

* Use only chassis ground or spade connector ground

Option 1:Single Suction Group w. Common Discharge

To CondenserOil Line

Discharge HeaderSuction Header

Main Board

Page 6: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 6

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

ON

1 2 3 45 6 7 8

* Use only chassis ground or spade connector ground

**Function Options are the same as list shown for the Main Board Aux Inputs.

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT - Not Used0 - 10 VDC

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY - Not Used

RELAY - Not UsedRELAY - Not Used

STEPPER MOTOR Not Used

RedBlack

GreenSuction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure TransducerGreen Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304

**AUX 1 INPUT 3

ON

1 2 3 45 6 7 8

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def Req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

Shield - Not Used

**AUX 1 INPUT 2

AUX 1INPUT 1Not Used

RS485

1 - ON

2 - 8 OFF

B-

A+

ShieldNot Used

ADDRESS 1Address set to Address 1 only

Option 2: Main Board + 1 Aux Relay Board Single Suction Group w. Common Discharge

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

(pn 21323)To Condenser Oil Line

Suction Header

Discharge Header

Aux Relay Board 1

Page 7: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 7

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

ON

1 2 3 45 6 7 8

* Use only chassis ground or spade connector ground

**Function Options are the same as list shown for the Main Board Aux Inputs.

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT - Not Used0 - 10 VDC

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY - Not Used

RELAY - Not UsedRELAY - Not Used

STEPPER MOTOR Not Used

RedBlack

GreenSuction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure TransducerGreen Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304

**AUX 1 INPUT 3

ON

1 2 3 45 6 7 8

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def Req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

Shield - Not Used

**AUX 1 INPUT 2

AUX 1INPUT 1Not Used

RS485

1 - ON

2 - 8 OFF

B-

A+

ShieldNot Used

ADDRESS 1Address set to Address 1 only

Option 2: Main Board + 1 Aux Relay Board Single Suction Group w. Common Discharge

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

(pn 21323)To Condenser Oil Line

Suction Header

Discharge Header

Aux Relay Board 1

Page 8: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 8

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

ON

1 2 3 45 6 7 8

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT - Not Used0 - 10 VDC

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY - Not Used

RELAY - Not UsedRELAY - Not Used

STEPPER MOTOR Not Used

RedBlack

GreenSuction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure TransducerGreen Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5Not Used

0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

**AUX 1 INPUT 3

ON

1 2 3 45 6 7 8

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def Req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

Shield - Not Used

**AUX 1 INPUT 2

AUX 1 INPUT 1Not Used

RS485

1 - ON

2 - 8 OFF

B-

A+

ShieldNot Used

Aux Relay Board 1ADDRESS 1Address set to Address 1 only

B-

A+

* Use only chassis ground or spade connector ground

**Function Options are the same as list shown for the Main Board Aux Inputs.

ON

1 2 3 45 6 7 8

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5Not Used

0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

**AUX 2 INPUT 3

**AUX 2 INPUT 2

AUX 2 INPUT 1Not Used

ShieldNot Used

ON

1 2 3 45 6 7 8

Aux Relay Board 2ADDRESS 2Address set to Address 2 only

1- OFF

3 - 8 OFF

2 - ON

Option 3: Main Board + 2 Aux Relay BoardsSingle Suction Group w. Common Discharge

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

(pn 21323)

Aux Relay Board 1 Aux Relay Board 2

Oil LineTo CondenserDischarge Header

Suction Header

Page 9: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 9

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

ON

1 2 3 45 6 7 8

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT - Not Used0 - 10 VDC

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY - Not Used

RELAY - Not UsedRELAY - Not Used

STEPPER MOTOR Not Used

RedBlack

GreenSuction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure TransducerGreen Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5Not Used

0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

**AUX 1 INPUT 3

ON

1 2 3 45 6 7 8

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def Req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

Shield - Not Used

**AUX 1 INPUT 2

AUX 1 INPUT 1Not Used

RS485

1 - ON

2 - 8 OFF

B-

A+

ShieldNot Used

Aux Relay Board 1ADDRESS 1Address set to Address 1 only

B-

A+

* Use only chassis ground or spade connector ground

**Function Options are the same as list shown for the Main Board Aux Inputs.

ON

1 2 3 45 6 7 8

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5Not Used

0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

**AUX 2 INPUT 3

**AUX 2 INPUT 2

AUX 2 INPUT 1Not Used

ShieldNot Used

ON

1 2 3 45 6 7 8

Aux Relay Board 2ADDRESS 2Address set to Address 2 only

1- OFF

3 - 8 OFF

2 - ON

Option 3: Main Board + 2 Aux Relay BoardsSingle Suction Group w. Common Discharge

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

(pn 21323)

Aux Relay Board 1 Aux Relay Board 2

Oil LineTo CondenserDischarge Header

Suction Header

Page 10: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 10

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

ON

1 2 3 45 6 7 8

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT - Not Used0 - 10 VDC

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY - Not Used

RELAY - Not UsedRELAY - Not Used

STEPPER MOTOR Not Used

RedBlack

Green

Suction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure Transducer

Green Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

**AUX 1 INPUT 3

ON

1 2 3 45 6 7 8

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HGDef req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

Shield - Not Used

**AUX 1INPUT 2

AUX 1 INPUT 1Not Used

RS485

* Use only chassis ground or spade connector ground

**Function Options are the same as list shown for the Main Board Aux Inputs.

1 - ON

2 - 8 OFF

B-

A+

ShieldNot Used

B-

A+

Group 1 Relays

Group 2 Relays

Group 1Group 1Group 2

Group 2

Suction PressureAUX 2 INPUT 1

ON

1 2 3 45 6 7 8

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304

**AUX 2INPUT 3

ShieldNot Used

ON

1 2 3 45 6 7 8

1- OFF

3 - 8 OFF

2 - ON

Group 2

Suction TemperatureAUX 2 INPUT 2

Aux Relay Board 1ADDRESS 1Address set to Address 1 only

Aux Relay Board 2ADDRESS 2Address set to Address 2 only

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Option 4: Main Board + 2 Aux Relay Boards Dual Suction Groups w. Common Discharge

(pn 21323)To Condenser

Oil Line

Discharge Header

Suction Header Suction Header

Aux Relay Board 2

Up to 5 compressors

Aux Relay Board 1

Up to 5 compressors

Page 11: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 11

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

ON

1 2 3 45 6 7 8

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT - Not Used0 - 10 VDC

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY - Not Used

RELAY - Not UsedRELAY - Not Used

STEPPER MOTOR Not Used

RedBlack

Green

Suction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure Transducer

Green Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

**AUX 1 INPUT 3

ON

1 2 3 45 6 7 8

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HGDef req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

Shield - Not Used

**AUX 1INPUT 2

AUX 1 INPUT 1Not Used

RS485

* Use only chassis ground or spade connector ground

**Function Options are the same as list shown for the Main Board Aux Inputs.

1 - ON

2 - 8 OFF

B-

A+

ShieldNot Used

B-

A+

Group 1 Relays

Group 2 Relays

Group 1Group 1Group 2

Group 2

Suction PressureAUX 2 INPUT 1

ON

1 2 3 45 6 7 8

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304

**AUX 2INPUT 3

ShieldNot Used

ON

1 2 3 45 6 7 8

1- OFF

3 - 8 OFF

2 - ON

Group 2

Suction TemperatureAUX 2 INPUT 2

Aux Relay Board 1ADDRESS 1Address set to Address 1 only

Aux Relay Board 2ADDRESS 2Address set to Address 2 only

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Option 4: Main Board + 2 Aux Relay Boards Dual Suction Groups w. Common Discharge

(pn 21323)To Condenser

Oil Line

Discharge Header

Suction Header Suction Header

Aux Relay Board 2

Up to 5 compressors

Aux Relay Board 1

Up to 5 compressors

Page 12: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 12

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

ON

1 2 3 45 6 7 8

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT - Not Used0 - 10 VDC

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY - Not Used

RELAY - Not UsedRELAY - Not Used

STEPPER MOTOR Not Used

RedBlack

Green

Suction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure Transducer

Green Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

**AUX 1 INPUT 3

ON

1 2 3 45 6 7 8

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

Shield - Not Used

DischargeTemperatureAUX 1 INPUT 2

DischargePressureAUX 1 INPUT 1

RS485

* Use only chassis ground or spade connector ground

**Function Options are the same as list shown for the Main Board Aux Inputs.

1 - ON

2 - 8 OFF

B-

A+

ShieldNot Used

B-

A+

Group 1 Relays

Group 2 RelaysGroup 1

Group 1Group 2

Suction PressureAUX 2 INPUT 1

ON

1 2 3 45 6 7 8

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V requires Solid State Relay pn 21304

**AUX 2 INPUT 3

ShieldNot Used

ON

1 2 3 45 6 7 8

1- OFF

3 - 8 OFF

2 - ON

Group 2

Suction TemperatureAUX 2INPUT 2

Option 5: Main Board + 2 Aux Relay Boards Dual Suction Group w. Independent Discharge

Aux Relay Board 1ADDRESS 1Address set to Address 1 only

Aux Relay Board 2ADDRESS 2Address set to Address 2 only

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Aux Relay Board 1 Aux Relay Board 2

To Condenser Oil Line

Discharge HeaderSuction Header Suction Header

Discharge Header

Up to 5 compressors

(pn 21323)

Page 13: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 13

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

ON

1 2 3 45 6 7 8

AUX 2

NO NCCOM

Suction Temp Sensor (black)

AUX 3

AUX 1

Discharge Temp Sensor (grey)

OUTPUT - Not Used0 - 10 VDC

Ethernet Port (RJ45) for remote communications

Display (RJ-11)

RELAY - Not Used

RELAY - Not UsedRELAY - Not Used

STEPPER MOTOR Not Used

RedBlack

Green

Suction Pressure Transducer

Line/L1

Neutral/L2

INCOMING POWER

120/208/230 VAC

GROUND*

EA

RTH

GROUND*(Chassis)

FUSE

Discharge Pressure Transducer

Green Black

Shared Red

T1AH250VP1A 250Vslow blow

5mm x 20mm

A + B –Sh

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)

requires Solid State Relay pn 21304

**AUX 1 INPUT 3

ON

1 2 3 45 6 7 8

Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off

Shield - Not Used

DischargeTemperatureAUX 1 INPUT 2

DischargePressureAUX 1 INPUT 1

RS485

* Use only chassis ground or spade connector ground

**Function Options are the same as list shown for the Main Board Aux Inputs.

1 - ON

2 - 8 OFF

B-

A+

ShieldNot Used

B-

A+

Group 1 Relays

Group 2 RelaysGroup 1

Group 1Group 2

Suction PressureAUX 2 INPUT 1

ON

1 2 3 45 6 7 8

INCOMING POWER

120/208/230VAC

GROUND

POWER FUSE

RELAY 5External Digital Switch - requires Relay pn 21032

0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V requires Solid State Relay pn 21304

**AUX 2 INPUT 3

ShieldNot Used

ON

1 2 3 45 6 7 8

1- OFF

3 - 8 OFF

2 - ON

Group 2

Suction TemperatureAUX 2INPUT 2

Option 5: Main Board + 2 Aux Relay Boards Dual Suction Group w. Independent Discharge

Aux Relay Board 1ADDRESS 1Address set to Address 1 only

Aux Relay Board 2ADDRESS 2Address set to Address 2 only

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Sh B– A+ – + + –+1

2S

igna

l - G

reen

B

lack

R

ed

– +5

FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2

COM NC NO COM NC NOCOM NC NO COM NC NO

Aux Relay Board 1 Aux Relay Board 2

To Condenser Oil Line

Discharge HeaderSuction Header Suction Header

Discharge Header

Up to 5 compressors

(pn 21323)

Page 14: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 14

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Communication SetupWhen powered up for the first time, the KE2 Compressor Sequencer OEM’s Remote Display will show CS (Compressor Sequencer), then SA (KE2 Smart Access). The controller is asking if remote access through KE2 Smart Access will be used. It will then blink diS (dis-abled).

Press and hold to disable KE2 Smart Access, or press the or arrow to reach EnA (enable). Press and hold to enable KE2

Smart Access.

On

Site

- Lo

cally

Rem

ote

Acce

ss

Joe’s C-Store & Gas

Joe’s C-Store & Gas

On the goXYZ Refrigeration

XYZ Refrigeration

At home At workOn siteAccess your

controllers:

Ways to connect:

Option 1: Directly ConnectedOption 2: Using the KE2 Smart GateOption 3: Using a KE2-LDA or KE2-EM35Option 4: Using the KE2 WiFi Service Tool Option 5: KE2 Smart Access PortalOption 6: KE2 Smart Access Portal w. Local DashboardOption 7: Customer VPN w. Local Dashboard

❶ Add KE2 Switch 8-port (pn 20166) or KE2 Switch 16-port (pn 21011) when connecting more than one controller.

❷ Typically DHCP should be enabled on the controllers when connecting directly to the customer network, unless directed by the customer’s IT department to set a static IP address.

Option 1: Directly Connected - Single Controller

Ethernet Cable

Computer

NOTE: Computer requires Static IP. See bulletin Q.5.11 or Video 124 at youtube.com/ke2therm

Option 4: Using the KE2 WiFi Service Tool (pn 20906)

thermsolutionsPWR WIFILANWAN 3G/4G

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

Ethernet Cable

KE2 WiFi Service Tool

KE2 Smart Gate

RB201 1UAS-2HND-IN

USB

SFP

POE GIGABIT ETHERNET

ETH1 ETH5ETH3 ETH4ETH2 ETH6 ETH10ETH8 ETH9ETH76 7 8 9 10

1 2 3 4 5FAST ETHERNET

Option 2: Using a KE2 Smart Gate (pn 20695) - Quick Multi-Controller Access

Ethernet Cable

Ethernet Cable

- or -

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

Option 3: Using a KE2-LDA (pn 21253) or KE2-EM35 (pn 21634)

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

WANLAN

Ethernet Cable

- or -❶ ❶ Ethernet Cable

- or -

Option 7: Customer VPN with Local Dashboard

Customer Network 1 2 3 654 7

Link/ACT

100/1000MbpsPOWER

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

WANLAN

- or -Internet

Customer VPN❶ ❶

Ethernet Cable

KE2-LDA KE2-EM35Ethernet Cable

- or -

1 2 3 654 7

Link/ACT

100/1000MbpsPOWER

Option 5: KE2 Smart Access Portal

InternetKE2 Smart Access

Customer NetworkEthernet Cable

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone❷

NO NCCOM

Ethernet Port

EARTH

IP-10.10.52.19MAC

00:04:A3:14:E5:92

IP-10.10.52.19MAC

00:04:A3:14:E5:92

Ethernet Cable

Option 6: KE2 SmartAccess Portal with Local Dashboard

1 2 3 654

7

Link/ACT

100/1000MbpsPOWER

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

WANLAN

- or -

Ethernet Cable

- or -Internet

KE2 Smart Access❶ ❶

KE2-LDA KE2-EM35Customer Network

Once connected to the Internet, the controller can be accessed at http://smartaccess.ke2therm.net

The initial login: Site - installer Password: Controller’s MAC address

The remainder of the setup is done via the browser interface. There are many ways to connect to the controller, in addition to KE2 Smart Access. Please refer to the options below, and chose the method that best suits the site and application.

Options

Page 15: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 15

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Setting Up Groups If using any Aux Relay Boards, the groups and Aux

Relay Boards must be setup before operation can begin.

Once connected to the controller either locally, using the IP address of the controller, or remotely through KE2 Smart Access, the home page will be displayed.

❶ Depending on the number of Aux Relay boards connected to the controller, one or two Unas-signed Aux Relay boards may appear on the screen.

❷ Click on the icon under Group 1.

❸ This will load the Setpoints page for Group 1.

❹ Next, click on the Settings page. Then click Login.

Enter the default username and password:

Username: ke2admin

Password: ke2admin

Click submit.

Once logged in, changes to the controller set-tings are now permitted.

❺ Instead of Login, the button in the lower right hand of the screen will now say Logout.

❻ Under Compressor Configuration, select the correct application from the list:

❼ Select the correct setup for the application and number of Aux Relay Boards,

❽ then click Save.

Page 16: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 16

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

If no Aux Relay Boards are being utilized, and Compressor Configuration is set to Single Group, relays can be designated from the Setpoints page of Group 1.

Otherwise, relays and any additional inputs are designated from the Aux Relay Board interface.

Single Group - Main Board Only

❶ Select the function of each relay,

❷ then click the Save button at the bottom of the page.

❸ Once saved, Comp HP will appear below any relays selected as a compressor. Enter the correct horsepower for each compressor, then click the Save button again.

Designating Relay Function: Compressors, Unloaders, LLS (Liquid Line Solenoid) or Hot Gas

❶❸

Page 17: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 17

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Single Group/ Dual Group + Aux BoardsWhen using Aux Relay Boards, the relays and any additional inputs can be assigned in the in-terface for the Aux Relay Board.

❶ From the Home Page click on the icon for the Aux Board:

❷ On the Aux Relay interface, Drivers (relays) are listed to the left.

❸ Inputs are listed to the right.

❷ ❸

Page 18: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 18

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

❹ Under the Mode drop down, assign the proper function to each relay and click Save.

NOTE: Do not enter the horsepower for the com-pressor before clicking Save.

❺ If prompted for a Login, the default is the same as the Main Board:

Username: ke2admin

Password: ke2admin

❻ After clicking Save, click on the relay again to change the horsepower.

❼ Enter the correct horsepower and click Save.

Continue until all relays have the proper function and horsepower.

❹❺

Running the SystemIMPORTANT: All of the settings on the Setpoints page should be reviewed before beginning operation (See pages 26 - 28 for detailed explanation of each Setpoint).

When the KE2 Compressor Sequencer OEM is started for the first time, or anytime a critical setpoint is changed, the controller enters System Off mode.

In System Off mode, the controller will not energize any relays until the user manually takes the controller out of System Off.

Once all setpoints have been reviewed, and the system is ready to be-gin operation, click the yellow button on the setpoints

page to begin running.

The button will change to and begin operation.

Clicking this button again will put the system back into System Off.

Note: When two suction groups are used, there will be two Setpoints pages, one for each group. Click the icon to go to the Setpoints page for that suction group. Each suction group is individually put into, and taken out of, System Off.

Please make sure to review the Setpoints page of BOTH suction groups.

Page 19: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 19

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Setpoints page for Group1

Setpoints page for Group 2

The Remote Display can also be used to put a suction group into, or take it out of, System Off mode.

Press and hold the button until SA is shown. Press the arrow un-

til SYS, SY1 or SY2 is shown. SYS indicates System Off when config-ured for Single Group. SY1 and SY2 indicate their respective groups when configured for Dual Group.

Press and the current status will be shown: oN, oN1, oN2 or oFF, oF1, oF2 depending on the configuration and suction group selected.

Press or to change the status.

Press and hold until the screen goes back to SYS, SY1 or SY2.

The suction group will now be in System Off, or running, depending on what was selected.

Page 20: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 20

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

When applying the controller to a system consisting of fixed speed compressors with or without unloading capabilities, the controller requires the user to assign a relay output for each compressor stage available using the controller’s browser interface.

When Fixed Suction Pressure and only Fixed Speed Compressors are selected the controller will stage the compressors by capacity in HP as defined on the Setpoints page or Aux Relay Board Setpoints page. Stages will be loaded and unloaded based on the smallest ca-pacity step available. If all available stages are equal, the controller will automatically select the option with the least amount of runtime.

The Suction Pressure Setpoint is the target pressure the controller works to achieve while running. The Suction Pressure Differential determines the pressure above and below the Suction Pressure Setpoint the controller will allow the suction pressure to vary before it makes an adjustment to capacity.

Once a stage has been loaded or unloaded, that stage must remain on or off as determined by the Min Comp Runtime and Min Comp Offtime. The controller will not load or unload more often than the time defined in the Min Compressor Switch Time.

If the system is maintaining the suction pressure within the normal operating range, which is defined as the Suction Pressure Setpoint +/- the Suction Pressure Differential, it will maintain the current capacity.

Mode of Control: Fixed Suction Pressure & Fixed Speed Compressors

Determining Compressor ON/OFF Order

Mode of Control: Fixed Suction Pressure with Digital Scroll or Variable Speed Compressors

When applying the controller to a system consisting of fixed speed compressors with or without unloading capabilities and one digital scroll or variable speed compressor, the controller requires the user to assign a relay output for each compressor stage available using the controller’s browser interface.

The Digital Scroll or variable speed compressor will serve as the pri-mary stage to provide the most consistent suction pressure possible. Initially, the Digital Scroll will start unloaded, or the variable speed compressor will run at the Min Speed setpoint.

If suction pressure rises above the Suction Pressure Setpoint, the Digital Scroll will be loaded by de-energizing the bypass solenoid or the variable speed compressor will be loaded by increasing the 0-10VDC output (0-5VDC also available). The rate at which the Digi-tal Scroll or variable speed is loaded is determined by the controller’s algorithm, and will improve as the controller learns the system. If the Digital Scroll or variable speed compressor is fully loaded, the next stage will be loaded based on the smallest capacity step available. If all available stages are equal, the controller will automatically select the option with the least amount of runtime. The compressors will continue to be loaded until all compressors are running at full load.

If suction pressure falls below the Suction Pressure Setpoint, the Digital Scroll will be unloaded by energizing the bypass solenoid, or the variable speed compressor will be unloaded by decreasing the 0-10VDC output. If the Digital Scroll or variable speed compressor is fully unloaded, the next stage will be unloaded based on the smallest step available. If all available stages are equal, the controller will au-tomatically select the option with the most amount of runtime. Suc-tion pressure will primarily be controlled by loading and unloading the Digital Scroll or variable speed compressor. If suction pressure is still low, and all other stages have been unloaded, the Digital Scroll’s compressor relay will be de-energized if minimum run, off and switch times have been met. For variable speed compressors, the 0-10VDC output will unload down to the Min Speed setpoint①.

① The Digital Scroll and variable speed compressor’s requirements for unloading follow their own rulesets and are not adjustable. It has been designed to be within the limits of the compressor manufacturer, and to ensure that specification is maintained the minimum times for transi-tioning are not adjustable.

The KE2 Compressor Sequencer OEM has the ability to float the tar-get suction pressure for maximum efficiency. When the Fixed/Float Suction setpoint is set to Float Suction, all Room Temperature sen-sors connected to a group will be compared to the Room Temp set-point on the controller. When the average of the Room Temperature sensors is below the Room Temp setpoint and above saturation tem-perature, the controller will raise the target suction pressure. When the average of the Room Temperature sensors is above the Room Temp setpoint, the controller will lower the target suction pressure.

While floating suction is enabled, the Suction Pressure setpoint be-comes the minimum suction pressure that the controller will work to maintain.

Mode of Control: Floating Suction Control

Page 21: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 21

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Selectable InputsThe digital inputs available depends on the application and number of Aux Relay Boards used. Please refer to the table below:

Application Hardware Number of Selectable Inputs Available

Single Suction / Common DischargeMain Board 3

Main +1 Aux Relay Board 5

Main + 2 Aux Relay Boards 7

Dual Suction / Common Discharge Main + 2 Aux Relay Boards 6

Dual Suction / Independent Discharge Main + 2 Aux Relay Boards 5

Selectable Input Mode: Sets the function of the Selectable Input (Complete Mode descriptions on the table below) Disabled In Cmp Temp Room Temp Monitor HG Defr Req 2nd Pres 2nd Tmp Comp Module Hi Pres Safety Oil Safety Sys Off

Input Active State: When a selectable input is set to one of the Digital Input Modes listed above, the Digital Input Active State determines whether the Digital Input performs the selected function (Digital Input Mode) when the input receives an open or shorted signal. Does not apply when Digital Input is used to receive a temperature sensor.

Descriptions of Selectable Input Mode OptionsInput Mode Designation

Disabled • Input performs no function.

In Cmp Temp(Internal Compressor Temperature)

• Monitors internal compressor temperature for Copeland Digital Scroll compressors. Triggers High Inter-nal Compressor Temperature Alarm, which turns off digital compressor until temperature lowers.

Room Temp • Used for floating suction pressure control.

Monitor • Used for monitoring a temperature. Does not affect control or alarming.

HG Defr Req (Hot Gas Defrost Request) • When active, energizes Hot Gas Defrost Relay. De-energizes relay when inactive.

2nd Pres (2nd Suction Pressure Setpoint) • When active, controller will operate using 2nd Suction Pressure setpoint as target suction pressure.

2nd Temp(2nd Room Temp Setpoint)

• When active, the controller will operate using 2nd Room Temp setpoint as target room temperature for suction float.

Comp Module (Compressor Module)

• Used for receiving an alarm from a compressor module. When active, will trigger Comp Mod Alarm.

Hi Pres Safety (High Pressure Safety Switch)

• Used for receiving an alarm from a high pressure safety switch. When active, will trigger Hi Pres Safety Alarm.

Oil Safety • Used for receiving an alarm from an oil pressure switch. When active, will trigger Oil Safety Alarm.

Sys Off(System Off)

• When active, begins to safely unload the suction group for pump down, and puts the group into System Off mode. In System Off mode, no relays will be energized, and a user must manually take the group out of System Off mode to resume operation.

Temperature Input Modes

Digital Input Modes

Page 22: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 22

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Remote Display - Variables Menu - Single GroupWhen not in a menu, press or to go through the Variables abbreviations.

Press to view a Variable in real time.

Press to return to the previous screen.

Abbrev. Full Name DescriptionPrs SuCTIOn PReSSuRe Suction Pressure as read by the controller.SUt SuCTIOn TemPeRaTuRe Suction Temperature as read by the controller.SAt SaTuRaTIOn TemPeRaTuRe Saturated Suction Temperature as calculated by the controller.SHt SUPERHEAT Suction Superheat as calculated by the controller.dPr DISCHaRGe PReSSuRe Discharge Pressure as read by the controller.dSt DISCHaRGe TemPeRaTuRe Discharge Temperature as read by the controller.dSA DISCHaRGe SaTuRaTIOn TemPeRaTuRe Discharge Saturation Temperature as calculated by the controller.dSH DISCHaRGe SuPeRHeaT Discharge Superheat as calculated by the controller.iP1 IP OCTeT 1 First three digits of the IP address.iP2 IP OCTeT 2 Second three digits of the IP address.iP3 IP OCTeT 3 Third three digits of the IP address.iP4 IP OCTeT 4 Fourth three digits of the IP address.FiR FIRmwaRe VeRSIOn Current firmware version on the controller.

Remote Display - Setpoints Menu - Single GroupWhen not in a menu, press and hold until SA is shown.

Press or to go through the setpoint abbreviations.

Press to view the current setpoint value. Press or to change the setpoint.Press and hold to save.For numerical setpoints, pressing once will change the digit that is being modified.

Press to return to the previous screen. When viewing a setpoint value, press to return to the previous screen without saving.

Abbrev. Full Name Min Max Default DescriptionSA KE2 SMART ACCESS diS EnA diS Turn KE2 Smart Access on or off: EnA to enable / diS to

disable KE2 Smart Access.

dHC DHCP mODe diS EnA diS Turn DHCP mode on or off: EnA to enable / diS to disable DHCP mode.

SyS SySTem On/OFF oFF on oFF Allow rack to run or put into system off: on to run / oFF to pump down rack and put into system off.

PSP TaRGeT SuCTIOn PRESSURE 0.0 psig 150.0 psig① 25.0 psig② Suction pressure the controller will work to maintain.

CLA CLEAR ALARMS Press and hold ENTER to clear all active alarms.

PAS weB PaSSwORD ReSeT Press and hold ENTER to reset browser password.

① R-410A = 300.0 psig, R-744 = 500.0 psig. ② R-744 =250.0 psig

Remote Display - Menus and ParametersWhen not in alarm or off, displays Group 1 Suction Pressure.

Abbreviation Full Name DescriptionoFF System Off All groups are in System Off mode.

oF1 System Off – Group 1 Group 1 is in System Off mode.

oF2 System Off – Group 2 Group 2 is in System Off mode.

Page 23: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 23

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Remote Display - Variables Menu - Dual Group When not in a menu, press or to go through the Variables abbreviations.

Press to view a Variable in real time.

Press to return to the previous screen.

Abbrev. Full Name DescriptionPr1 SuCTIOn PReSSuRe - GROuP1 Group 1 Suction Pressure as read by the controller.SU1 SuCTIOn TemPeRaTuRe - GROuP1 Group 1 Suction Temperature as read by the controller.SA1 SaTuRaTIOn TemPeRaTuRe - GROuP1 Group 1 Saturated Suction Temperature as calculated by the controller.SH1 SuPeRHeaT - GROuP1 Group 1 Suction Superheat as calculated by the controller.dP1 DISCHaRGe PReSSuRe - GROuP1 Group 1 Discharge Pressure as read by the controller.dt1 DISCHaRGe TemPeRaTuRe - GROuP1 Group 1 Discharge Temperature as read by the controller.

dS1 DISCHaRGe SaTuRaTIOn TemPeRaTuRe - GROUP1 Group 1 Discharge Saturation Temperature as calculated by the controller.

dH1 DISCHaRGe SuPeRHeaT - GROuP1 Group 1 Discharge Superheat as calculated by the controller.Pr2 SuCTIOn PReSSuRe - GROuP2 Group 2 Suction Pressure as read by the controller.SU2 SuCTIOn TemPeRaTuRe - GROuP2 Group 2 Suction Temperature as read by the controller.SA2 SaTuRaTIOn TemPeRaTuRe - GROuP2 Group 2 Saturated Suction Temperature as calculated by the controller.SH2 SuPeRHeaT - GROuP2 Group 2 Suction Superheat as calculated by the controller.dP2 DISCHaRGe PReSSuRe - GROuP2 Group 2 Discharge Pressure as read by the controller.dt2 DISCHaRGe TemPeRaTuRe - GROuP2 Group 2 Discharge Temperature as read by the controller.

dS2 DISCHaRGe SaTuRaTIOn TemPeRaTuRe - GROUP2 Group 2 Discharge Saturation Temperature as calculated by the controller.

dH2 DISCHaRGe SuPeRHeaT - GROuP2 Group 2 Discharge Superheat as calculated by the controller.iP1 IP OCTeT 1 First three digits of the IP address.iP2 IP OCTeT 2 Second three digits of the IP address.iP3 IP OCTeT 3 Third three digits of the IP address.iP4 IP OCTeT 4 Fourth three digits of the IP address.Fir FIRmwaRe VeRSIOn Current firmware version on the controller.

Remote Display - Setpoints Menu - Dual Group When not in a menu, press and hold until SA is shown.

Press or to go through the setpoint abbreviations.

Press to view the current setpoint value. Press or to change the setpoint.Press and hold to save.For numerical setpoints, pressing once will change the digit that is being modified.

Press to return to the previous screen. When viewing a setpoint value, press to return to the previous screen without saving.

Abbrev. Full Name Min Max Default DescriptionSA KE2 SMART ACCESS diS EnA diS Turn KE2 Smart Access on or off: EnA to enable / diS to disable

KE2 Smart Access.

dHC DHCP mODe diS EnA diS Turn DHCP mode on or off: EnA to enable / diS to disable DHCP mode.

Sy1 SySTem On/OFF - GROuP 1 oF1 on1 oF1 Allow group 1 to run or put into system off: on1 to run / oF1 to pump down group 1 and put into system off.

Sy2 SySTem On/OFF - GROuP 2 oF2 on2 oF2 Allow group 2 to run or put into system off: on2 to run / oF2 to pump down group 2 and put into system off.

PS1 TaRGeT SuCTIOn PReSSuRe - GROUP1 0.0 psig 150.0

psig①25.0 psig②

Target Suction Pressure - Suction pressure the controller will work to maintain for group 1.

PS2 TaRGeT SuCTIOn PReSSuRe - GROUP2 0 psig 150.0

psig①25.0 psig②

Target Suction Pressure - Suction pressure the controller will work to maintain for group 2.

CLA CLEAR ALARMS Press and hold ENTER to clear all active alarms.PAS weB PaSSwORD ReSeT Press and hold ENTER to reset browser password.

① R-410A = 300.0 psig, R-744 = 500.0 psig. ② R-744 =250.0 psig

Page 24: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 24

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Critical Alarms & Cautionary Alarms

Abbre-viation Alarm Description Critical

A01 Suction Pres Sensor [Group 1] Alarm Group 1 suction pressure sensor is shorted, open or pressure out of range. ▪

A02 Disch Pres Sensor [Group 1] Alarm Group 1 discharge pressure sensor is shorted, open or pressure out of range. ▪

A03 Suction Temp Sensor [Group 1] Alarm Group 1 suction temperature sensor is shorted or open. ▪A04 Disch Temp Sensor [Group 1] Group 1 discharge temperature sensor is shorted or open. ▪A06 High Superheat [Group 1] Alarm Group 1 suction superheat is higher than Max Suction SH for longer

than Min/Max SH Del.

A07 Low Superheat [Group 1] Alarm Group 1 suction superheat is lower than Min Suction SH for longer than Min/Max SH Del. ▪

A08 High Disch Temp [Group 1] Alarm Group 1 discharge temperature is higher than Max Disch Temp for longer than Max Dis Tmp Del. ▪

A09 High Int Comp Temp [Group 1] Alarm Group 1 digital compressor internal temp high. Will turn off digital compressor until temp lowers.

A10 High Disch Pres [Group 1] Alarm Group 1 discharge pressure is higher than Max Disch Pres for longer than Max Dis Prs Del. ▪

A13 Comp Mod [Group 1] Alarm Group 1 Compressor Module digital input is active.A16 Oil Safety [Group 1] Alarm Group 1 Oil Safety digital input is active.A19 Hi Pres Safety [Group 1] Alarm Group 1 High Pressure Safety digital input is active.A22 Aux Brd Comms Alarm Main Board unable to communicate with the Aux Relay Board(s). ▪A25 Watchdog Alarm Contact KE2 Therm.

A26 Email Failure Alarm Email alert was not confirmed by email server provided after seven consecutive attempts.

A28 High Disch Temp [Group 2] Alarm Group 2 discharge temperature is higher than Max Disch Temp for longer than Max Dis Tmp Del. ▪

A29 Evap Comms [Group 1] Alarm Group 1 SiteView controllers not communicating.A30 Evap Comms [Group 2] Alarm Group 2 SiteView controllers not communicating.

A31 Disch Pres Sensor [Group 2] Alarm Group 2 discharge pressure sensor is shorted, open or pressure out of range. ▪

A32 Suction Temp Sensor [Group 2] Alarm Group 2 suction temperature sensor is shorted or open. ▪A34 High Superheat [Group 2] Alarm Group 2 suction superheat is higher than Max Suction SH for longer

than Min/Max SH Del.

A35 Low Superheat [Group 2] Alarm Group 2 suction superheat is lower than Min Suction SH for longer than Min/Max SH Del. ▪

A36 Disch Temp Sensor [Group 2] Alarm Group 2 discharge temperature sensor is shorted or open. ▪A37 High Int Comp Temp [Group 2] Alarm Group 2 digital compressor internal temp high. Will turn off digital

compressor until temp lowers.

A38 High Disch Pres [Group 2] Alarm Group 2 discharge pressure is higher than Max Disch Pres for longer than Max Dis Prs Del. ▪

Alarms - All GroupsAlarm Severity

Red LED - Critical Alarm: The controller will attempt to safely pump down the suction group. The group is unable to run safely with a critical alarm, and the controller will cease refrigeration for that group. The controller is attempting to prevent a catastrophic system failure, such as damage to the compressors. Critical alarms should be addressed immediately.

Yellow LED - Cautionary Alarm: The controller will continue to function to the best extent possible given the system conditions, but the alarm should be addressed as soon as possible.

Page 25: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 25

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Critical Alarms & Cautionary Alarms (continued)

Abbre-viation Alarm Description Critical

A41 Suction Pres Sensor [Group 2] Alarm Group 2 suction pressure sensor is shorted, open or pressure out of range. ▪

A44 Comp Mod [Group 2] Alarm Group 2 Compressor Module digital input is active.A47 Oil Safety [Group 2] Alarm Group 2 Oil Safety digital input is active.A50 Hi Pres Safety [Group 2] Alarm Group 2 High Pressure Safety digital input is active.

A53 Main: Aux Input 1 Sensor [Group 1] Alarm Main Board, Aux Input 1 Temp Sensor is shorted or open.

A54 Main: Aux Input 2 Sensor [Group 1] Alarm Main Board, Aux Input 2 Temp Sensor is shorted or open.

A55 Main: Aux Input 3 Sensor [Group 1] Alarm Main Board, Aux Input 3 Temp Sensor is shorted or open.

A56 Aux Addr 1: Input 2 Sensor [Group 1] or [Group 2] Alarm Aux Board 1, Input 2 Temp Sensor is shorted or open.

A57 Aux Addr 1: Input 3 Sensor [Group 1] or [Group 2] Alarm Aux Board 1, Input 3 Temp Sensor is shorted or open.

A58 Aux Addr 2: Input 2 Sensor [Group 1] or [Group 2] Alarm Aux Board 2, Input 2 Temp Sensor is shorted or open.

A59 Aux Addr 2: Input 3 Sensor [Group 1] or [Group 2] Alarm Aux Board 2, Input 3 Temp Sensor is shorted or open.

Safety Alarms (Preemptive Alarms)Safety alarms S01-03 and S11-13 are preemptive alarms and trigger before their respective critical alarms are triggered.

Abbre-viation Alarm Description Critical

S01 Low Safety SH 1 [Group 1] Alarm Group 1 suction superheat is below Min Safety Suc SH for more than 5 minutes.

S02 High Safety Suc Temp 1 [Group 1] Alarm

Group 1 suction temperature is above Max Safety Suc Tmp for more than 5 minutes.

S03 High Safety Disch Pres 1 [Group 1]Group 1 discharge pressure is above Max Safety Pressure. Control-ler will attempt to unload stages and not load anymore stages until pressure is well below Max Safety Pressure.

S11 Low Safety SH 2 [Group 2] Alarm Group 2 suction superheat is below Min Safety Suc SH for more than 5 minutes.

S12 High Safety Suc Temp 2 [Group 2] Alarm

Group 2 suction temperature is above Max Safety Suc Tmp for more than 5 minutes.

S13 High Safety Disch Pres 2 [Group 2] Alarm

Group 2 discharge pressure is above Max Safety Pressure. Control-ler will attempt to unload stages and not load anymore stages until pressure is well below Max Safety Pressure.

Page 26: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Webpage Setpoints - Main Board The following setpoints are available on the broswer interface of the Main Board.

Setpoint Description Range / Options Default

Rela

ys

RElAy#1 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp2, Unldr for Cmp3

Disabled

RElAy#2 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp3

Disabled

RElAy#3 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp2

Disabled

COMP HP Once compressor type is selected, the HP of each com-pressor can be set. 0.1 HP to 50.0 HP 5.0 HP

Varia

ble

Spee

d MIN SPEED Minimum speed for variable speed compressors. 6.0 Hz to 60.0 Hz 6.0 Hz

VOlTAgE Select output for variable speed compressors. 0 to 10VDC or 0 to 5VDC 0 to 10VDC

Def

rost

lo

ad MAx lOAD Maximum load, in BTU or AMPs, that the circuit can sustain at one time.②

0 Amps to 15,000 Amps0 BTU TO 6,000,000 BTU 80 Amps

UNITS Units for heater or refrigeration load during defrost. ② Amps/Btu Amps

Refr

iger

ation

FIxeD/FlOAT SuCTIOn Select whether target suction pressure can float accord-ing to room temperature. Fixed Suction, Float Suction Fixed

Suction

REFRIgERANT Referigerant used in the system.R-404A, R-507, R-407A, R-407C, R-422A, R-422D, R-134A, R-22, R-717, R-438A, R-408A, R-409A, R-407F, R-410A, R-744, R-448A, R-449A, R-450A, R-513A

R-404A

SUCTION PRESSURE Target suction pressure the controller works to maintain. 0 to 150 psig* *Max for R410A: 300 psig; R744: 500 psig

25 psig , 250 psig for R-744

ROOM TEMP Room temperature setpoint for suction float. -50.0°F to 90.0°F (-45.5°C to 32.2°C) -10.0°F

SUC PRESS DIFF

Suction Pressure Differential – when all compressor are set to fixed speed, controller will load and unload stages outside of this range. For digital and variable speed compressors, determines ideal range for suction pressure (target suction pressure ± the differential).

0.1 psi to 5.0 psi 2.0 psi

2ND ROOM TEMPWhen 2nd Temp Digital Input is active, this value be-comes the new room temperature setpoint for suction float.

-50.0°F to 90.0°F (-45.5°C to 32.2°C) -50.0°F (-45.5°C)

2ND SUCTION PRESSURE

When 2nd Pres Digital Input is active, this value becomes the new target suction pressure.

0 to 150 psig* *Max for R410A: 300 psig; R744: 500 psig 50.0 psig

MIN STAgE DElAy TIME Minimum time between switching stages. 2 sec to 240 sec 15 secMIN COMP RUNTIME Minimum time compressor must run before turning off. 0 sec to 240 sec 60 seconds

CUT OUT PRESSURE System turns completely off when suction pressure drops below this pressure.

0 to 150 psig* *Max for R410A: 300 psig; R744: 500 psig 5.0 psig

MIN COMP OFFTIME Minimum time compressor must be off before turning on. 0 sec to 240 sec 60 seconds

MAx PUMP OUT TIME Sets maximum time to reach cut-out pressure. 0 min to 240 min 2 minutes

TEMP UNITS Temperature Units Fahrenheit, Celsius Fahrenheit

Tem

p /

Dig

ital

Inpu

ts

INPUT 1 MODE Select function for Input 1 on the Main Board. Disabled, In Cmp Temp, Room Temp. Monitor, HG Defr Req, 2nd Pres, 2nd Temp, Comp Module, Hi Pres Safety, Oil Safety, Sys Off

Disabled

INPUT2 MODE Select function for Input 2 on the Main Board. Disabled

INPUT 3 MODE Select function for Input 3 on the Main Board. Disabled

INPUT 1 STATE Select active state for Input 1. Closed, Open Closed

INPUT2 STATE Select active state for Input 2. Closed, Open Closed

INPUT3 STATE Select active state for Input 3. Closed, Open Closed

Q.2.60 March 2019Page 26

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Page 27: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 27

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Webpage Setpoints - Main Board (continued) The following setpoints are available on the broswer interface of the Main Board.

Setpoint Description Range / Options Default

Sens

or O

ffset

s

SUCT PRESS OFFSET An offset added or subtracted from the suction pressure transducer reading, if needed. -5.0 psi to 5.0 psi 0 psi

SUCT TEMP OFFSET An offset added or subtracted from the suction tempera-ture sensor reading, if needed. -5.0 to 5.0 0

DISCH PRESS OFFSET An offset added or subtracted from the discharge pressure transducer reading, if needed. -5.0 psi to 5.0 psi 0 psi

DISCH TEMP OFFSET An offset added or subtracted from the discharge tem-perature sensor reading, if needed. -5.0 to 5.0 0

Aux 1 (MAIn BOARD InPuT 1) TeMP OFFSeT

An offset added or subtracted from the Input 1 tempera-ture sensor reading, if needed. -5.0 to 5.0 0

Aux 2 (MAIn BOARD InPuT 2) TeMP OFFSeT

An offset added or subtracted from the Input 2 tempera-ture sensor reading, if needed. -5.0 to 5.0 0

Aux 3 (MAIn BOARD InPuT 3) TeMP OFFSeT

An offset added or subtracted from the Input 3 tempera-ture sensor reading, if needed. -5.0 to 5.0 0

PID

PROPORTIONAl CMP

Should not be adjusted unless instructed to by KE2 Therm technical support.

0 to 255 1

INTEgRAl CMP 0 to 255 1

DERIVATIVE CMP 0 to 255 0

PID TIME CMP 0 second to 255 seconds 1 second

Ala

rms

MIN SAFETy SUC SHMinimum Safety Suction Superheat. Provides a warning that suction line is low SH before triggering a critical low SH alarm.

0.0°F to 50.0°F (0.0°C to 27.8°C) 0.0°F

MIN SUCTION SHMinimum Suction Superheat. The lowest acceptable superheat for the suction line. Turns system off when exceeded longer than Min/Max SH Del.

5.0°F to 50.0° F (2.8°C to 27.8°C) 15.0°F

MAx SAFETy SUC TMP Max Safety Suction Temp. Provides a warning that suc-tion line temp is high. 5.0°F to 90.0°F (-15.0°C to 32.2°C) 90.0°F

MAx SUCTION SH Max Suction Superheat. Provides a warning that suction SH is high when exceeded longer than Min/Max SH Del. 25.0°F to 200.0°F (13.9°C to 111.1°C) 50.0°F

MAx SAFETy PRESSUREMax Safety Discharge Pressure. Discharge pressure above this value triggers High Safety Discharge Pressure alarm. Group will stop loading stages, and begin to unload.

0.0 psig to 500.0 psig 400.0 psig

MIn/MAx SH DelMin/Max Superheat Alarm Delay. Amount of time before a Min Suction SH or Max Suction SH alarm is triggered after exceeding the threshold.

0 to 254 minutes*Type 255 or ‘dis‘ and save to disable. Disabled

MAx DISCH TEMPMaximum Discharge Temp. Triggers alarm and turns system off when discharge temp exceeds this value longer than Max Dis Tmp Del.

25.0°F to 300.0°F (-3.9°C to 148.9°C) 268.0°F

MAx DIS TMP DEl Max Discharge Temp Delay. The amount of time before an alarm is initiated when Max Disch Temp is exceeded.

0 to 254 minutes*Type 255 or ‘dis‘ and save to disable. Disabled

MAx DISCH PRESMaximum Discharge Pressure. Triggers alarm and turns system off when discharge pressure exceeds this value longer than Max Dis Pres Del.

100.0 to 500.0 psig 450.0 psig

MAx DIS PRS DElMax Discharge Pressure Delay. The amount of time before an alarm is initiated when Max Disch Pres is exceeded.

0 to 254 minutes*Type 255 or ‘dis‘ and save to disable. Disabled

① Only one variable speed or digital scroll compressor can be selected per group.

② Function not currently implemented in most applications.

Page 28: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 28

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Webpage Setpoints - Auxiliary Relay BoardThe following setpoints are available on the broswer interface of the Auxiliary Relay Board.

Setpoint Description Range / Options Default

Rela

ys

RElAy#1 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp2, Unldr for Cmp3, Unldr for Cmp4, Unldr for Cmp5

Disabled

RElAy#2 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp3, Unldr for Cmp4, Unldr for Cmp5

Disabled

RElAy#3 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp2, Unldr for Cmp4, Unldr for Cmp5

Disabled

RElAy#4 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp2, Unldr for Cmp3, Unldr for Cmp5

Disabled

RElAy#5Not available on some setups Controls one stage or component.

Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp2, Unldr for Cmp3, Unldr for Cmp4

Disabled

COMP HP Once compressor type is selected, the HP of each compressor can be set. 0.1 HP to 50.0 HP 5.0 HP

Dig

ital I

nput

s INPUT2 MODE ②③ Select function for Input 2. Disabled, Int Cmp Temp, Room Temp, Monitor, HG Defr Req, 2nd Pres, 2nd Temp, Comp Module, Hi Pres Switch, Oil Safety Sw, Sys Off

Disabled

INPUT 3 MODE Select function for Input 3. Disabled

INPUT2 STATE Select active state for Input 2. Closed, Open Closed

INPUT3 STATE Select active state for Input 3. Closed, Open Closed

Aux

Inpu

ts

Aux InPuT1 (RelAy BOARD) OFFSeT

An offset added or subtracted from the Aux Input 1 pressure transducer reading on the Aux Relay Board, if needed.

-5.0 psi to 5.0 psi 0 psi

Aux InPuT2 (RelAy BOARD) OFFSeT

An offset added or subtracted from the Aux Input 2 temperature sensor reading on the Aux Relay Board, if needed.

-5.0 to 5.0 0

Aux InPuT3 (RelAy BOARD) OFFSeT

An offset added or subtracted from the Aux Input 3 temperature sensor reading on the Aux Relay Board, if needed.

-5.0 to 5.0 0

① Only one variable speed or digital scroll compressor can be selected per group.

② In dual suction group applications, Input 2 on Aux Relay Board 2 acts as suction temperature sensor for group 2.

③ In dual suction group applications with independent discharge, Input 2 on Aux Relay Board 1 acts as discharge temperature sensor for group 2.

Page 29: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 29

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Clic

k th

e ic

on t

o br

ing

up

a re

al t

ime

view

of t

he r

ack.

Clic

k th

e be

ll ic

on t

o vi

ew c

urre

nt a

larm

s.

Flas

hing

red

= C

ritic

al

Yel

low

= C

autio

nary

Clic

k to

dis

play

con

trol

ler

info

rmat

ion

(Loc

atio

n, IP

ad

dres

s, M

AC

add

ress

, Fi

rmw

are

vers

ion.

)

Exam

ple

of M

obile

Vie

w

Bri

ngs

up t

he

Sta

tus

page

fo

r th

at A

ux

Rel

ay B

oard

Bri

ngs

up t

he

Sta

tus

page

fo

r th

at A

ux

Rel

ay B

oard

Bri

ngs

up t

he

Set

poin

ts p

age

for

that

Suc

tion

Gro

up.

Bri

ngs

up t

he

Set

poin

ts p

age

for

that

Suc

tion

Gro

up.

KE2

The

rm c

onta

ct

info

rmat

ion

and

link

to w

ebsi

te

Des

crip

tion

:Fr

om th

e H

ome

page

, the

use

r can

acc

ess

the

Stat

us &

Set

poin

ts p

age

for t

he M

ain

Boar

d, a

s w

ell

as th

e St

atus

pag

e fo

r any

Aux

iliar

y Re

lay

Boar

ds.

Hom

e Pa

ge

Home Page

Page 30: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 30

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Ret

urns

to

the

Hom

e pa

ge.

Sta

tus

bar:

sho

ws

curr

ent

stat

us o

f gro

up,

and

seco

nds

to c

ount

dow

n to

the

nex

t st

age.

Clic

k to

go

to

Set

poin

ts p

age

for

that

su

ctio

n gr

oup.

Gro

up’s

nam

e an

d co

ntro

l met

hod.

Clic

k on

the

bar

to

expa

nd o

r co

llaps

e th

e vi

ew fo

r th

at s

uctio

n gr

oup

Sta

tus

of

each

rel

ay

Clic

k on

Suc

tion

Pre

ssur

e di

al t

o zo

om in

.

Tota

l % o

f co

mpr

esso

r ca

paci

ty u

sed

for

the

suct

ion

grou

p.

Scr

oll d

own

to v

iew

the

nex

t gr

oup.

Sen

sor

& D

igita

l In

put

valu

es

upda

ted

in r

ealti

me.

Sen

sor

& S

yste

m In

form

atio

nG

auge

col

or:

Gre

en =

Pre

ssur

e in

ran

geB

lue

= T

empe

ratu

re in

ran

geY

ello

w =

Out

of o

ptim

al r

ange

Red

= A

larm

ran

ge

Des

crip

tion

:Re

al ti

me

syst

em p

erfo

rman

ce in

form

atio

n fo

r the

Mai

n Bo

ard

and

any

Auxi

liary

Rel

ay B

oard

s.

Stat

us P

age

- Mai

n Bo

ard

Status Page - Main Board

Page 31: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 31

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Status Page- Auxiliary Board

Des

crip

tion

:Re

al t

ime

syst

em p

erfo

rman

ce in

form

atio

n fo

r th

e Au

xilia

ry R

elay

Boa

rd. T

he u

ser

also

des

igna

tes

rela

ys a

nd d

eter

min

es th

e fu

nctio

n of

sel

ecta

ble

inpu

ts fr

om th

is p

age.

Stat

us P

age

- Aux

iliar

y Bo

ard

Dis

play

the

sta

tus

of

each

Aux

Rel

ay B

oard

in

put.

Clic

k to

set

the

func

tion

of t

he in

put,

if av

aila

ble.

Dis

play

s st

atus

of e

ach

rela

y, a

nd a

nalo

g ou

tput

, fo

r va

riab

le s

peed

co

mpr

esso

rs.

Clic

k on

the

icon

to

set

the

fuct

ion

of e

ach

rela

y.

For

com

pres

sors

, sav

e th

e ty

pe o

f com

pres

sor

first

, the

n en

ter

the

HP

of

the

com

pres

sor,

and

cl

ick

save

aga

in

Page 32: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 32

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Bas

ic (P

ort

25

) K

E2 T

herm

Def

ault

Ser

ver

Upd

ate

firm

war

e.

Ref

er to

Q.5

.6 K

E2

Boo

tload

er G

uide

.

Sta

ndar

dS

iteV

iew

MA

NA

GER

Req

uire

d to

Log

in t

o m

ake

chan

ges

to S

ettin

gs p

age.

See

pag

e 3

3.

Rem

otel

y re

boot

s th

e co

ntro

ller.

Use

to v

erify

pro

per

e-m

ail

conf

igur

atio

n. C

lick

Save

bu

tton

(bot

tom

rig

ht o

f pag

e)

befo

re te

stin

g

Rem

oves

all

data

st

ored

by

cont

rolle

r. D

o no

t use

unl

ess

inst

ruct

ed to

by

KE2

Th

erm

.

Res

ets

cont

rolle

r’s

alar

ms

and

alar

m

cond

ition

s.

Cus

tom

er in

form

atio

n is

di

spla

yed

Use

to

veri

fy

prop

er A

PI

conf

igur

atio

n

Def

ines

the

con

trol

ler

loca

tion

for

KE2

Sm

art

Acc

ess

and

alar

m

notif

icat

ions

Cus

tom

er m

ay in

put

thei

r co

mpa

ny in

form

atio

n

Sel

ect

rack

con

figur

atio

n an

d re

nam

e gr

oups

(e

x. M

T S

uctio

n G

roup

, LT

Suc

tion

Gro

up e

tc.):

Sin

gle

Gro

upS

ingl

e G

roup

plu

s 1

Aux

Sin

gle

Gro

up p

lus

2 A

uxD

ual G

roup

Sha

red

Dis

char

ge p

lus

2 A

uxD

ual G

roup

Inde

pend

ent

plus

2 A

ux

Site

and

Pas

swor

d m

ay b

e ch

ange

d by

cus

tom

er t

o cr

eate

a

uniq

ue K

E2 S

mar

t A

cces

s lo

gin

for

acce

ssin

g th

e co

ntro

ller

rem

otel

y th

roug

h K

E2

Sm

artA

cces

s.

Use

to

cust

omiz

e th

e U

ser

Nam

e an

d P

assw

ord

from

the

def

ault

sett

ing.

The

cre

dent

ials

are

ne

cess

ary

to c

hang

e S

etpo

ints

, S

ettin

gs a

nd N

etw

ork

optio

ns fr

om

the

Mas

terV

iew

scr

eens

.

Use

to

rece

ive

e-m

ail/

text

ale

rts

Sub

ject

for

e-m

ail/

text

ale

rts

Des

crip

tion

:Th

e Se

ttin

gs p

age

is w

here

com

pres

sor (

rack

) con

figur

atio

n is

save

d. T

his m

ust b

e se

t bef

ore

the

syst

em c

an ru

n. T

he S

ettin

gs p

age

also

co

ntai

ns c

ontr

olle

r con

figur

atio

n fo

r e-m

ail a

nd w

eb a

cces

s.

It al

so a

llow

s ins

talle

rs to

cus

tom

ize

the

Mas

terV

iew

with

thei

r com

pany

info

rmat

ion,

show

n un

der L

ocat

ion

Sett

ings

. The

Set

tings

pag

e in

clud

es th

e bu

tton

s to

upd

ate

the

cont

rolle

r, re

set p

ower

to th

e co

ntro

ller,

send

a te

st e

-mai

l, cl

ear d

ata

colle

cted

, and

cle

ar a

larm

s.

Settings Page

Setti

ngs P

age

Page 33: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 33

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

To m

ake

chan

ges

to t

he S

ettin

gs p

age,

Net

wor

k pa

ge a

nd S

etpo

ints

pa

ge t

he U

ser

Nam

e an

d P

assw

ord

mus

t be

pro

vide

d.

Def

ault

Use

r N

ame:

ke2

adm

in

D

efau

lt P

assw

ord:

ke2

adm

in

For

secu

rity

rea

sons

, the

Use

r N

ame

and

Pas

swor

d sh

ould

be

chan

ged

from

the

def

ault.

Onc

e yo

u ar

e lo

gged

in, g

o to

the

S

ettin

gs p

age

to c

hang

e th

e U

ser

Nam

e an

d P

assw

ord.

To m

ake

chan

ges

to t

he A

ux R

elay

B

oard

, th

e us

er w

ill b

e pr

ompt

ed

for

the

Use

r N

ame

and

Pas

swor

d if

not

alre

ady

logg

ed in

. The

def

ault

logi

n cr

eden

tials

are

the

sam

e as

th

e M

ain

Boa

rd.

U

ser

Nam

e: k

e2ad

min

Pas

swor

d: k

e2ad

min

Des

crip

tion

:Th

e Lo

gin

feat

ure

prev

ents

una

utho

rized

acc

ess

to th

e co

ntro

ller.

The

user

mus

t ent

er th

e U

ser N

ame

and

Pass

wor

d to

mak

e ch

ange

s to

the

Sett

ings

pag

e, N

etw

ork

page

, Se

tpoi

nts

page

, and

Aux

Rel

ay B

oard

s.

Login Page

Logi

n Pa

ge

Logi

n Pa

ge -

Aux

Rela

y Bo

ard

Page 34: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 34

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

IP A

ddre

ss m

ay b

e ch

ange

d to

mat

ch

the

onsi

te n

etw

ork.

Ty

pica

lly th

e su

bnet

m

ask,

gat

eway

and

pr

imar

y D

NS

shou

ld

also

be

chan

ged.

Net

wor

k se

ttin

gs m

ay b

e ch

ange

d to

mat

ch c

usto

mer

’s

envir

onm

ent.

DH

CP C

lient

Mod

e is

En

able

d or

Dis

able

dEn

able

d - I

P is

Dyn

amic

Dis

able

d - I

P is

Sta

tic

Show

s In

tern

et c

onne

ctio

n st

atus

:R

ed =

Una

ble

to r

each

Inte

rnet

Yello

w =

Som

e In

tern

et s

ervic

es

unav

aila

ble

Gre

en =

Goo

d In

erne

t con

nect

ion

NO

TE: D

o no

t m

odify

the

C

ontr

olle

r N

ame.

Ch

ange

“Loc

atio

n” o

n th

e Se

ttin

gs p

age

to e

asily

id

entif

y co

ntro

llers

.

Pre

vent

s un

auth

oriz

ed a

cces

s to

the

co

ntro

ller.

Use

r m

ust

ente

r U

ser

Nam

e an

d P

assw

ord

to m

ake

chan

ges

to t

he N

etw

ork

Set

up p

age.

Sav

es c

hang

es t

o th

e co

ntro

ller’

s ne

twor

k.

Des

crip

tion

:A

llow

s us

ers

to c

hang

e th

e co

ntro

ller’s

net

wor

k se

ttin

gs, i

n or

der t

o ad

d co

ntro

llers

to a

n ex

istin

g cu

stom

er n

etw

ork.

Net

wor

k Pa

ge

Network Page

Page 35: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 35

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Des

crip

tion

:A

llow

s th

e us

er to

set

up th

e co

ntro

ller,

and

to c

usto

miz

e th

e co

ntro

ller t

o m

eet s

peci

fic a

pplic

atio

n ne

eds.

The

KE2

Com

pres

sor S

eque

ncer

OEM

beg

ins

in S

yste

m O

ff M

ode.

The

use

r mus

t con

figur

e re

lays

and

refr

iger

atio

n se

tpoi

nts

to e

nsur

e th

e sy

stem

will

run

prop

erly

, the

n tu

rn th

e sy

stem

on.

The

scre

ensh

ot b

elow

sho

ws

the

Setp

oint

s pa

ge w

hen

no A

ux R

elay

Boa

rds

are

used

.

Setp

oint

s Pag

e -

mai

n Bo

ard

Onl

y - n

O a

ux R

elay

Boa

rds

Setpoints Page -Single Group - Main Board Only

Det

erm

ines

if t

he

Inpu

t is

act

ive

whe

n it

dete

cts

an O

pen

or

Clo

sed

circ

uit,

and

a D

igita

l Inp

ut is

as

sign

ed a

s th

e in

put

func

tion.

Inpu

t 1

, 2 o

r 3

Mod

e

Dis

able

dIn

Cm

p Te

mp

Roo

m T

emp

Mon

itor

HG

Def

r R

eq

2nd

Pre

s2

nd T

mp

Com

p M

odul

eH

i Pre

s S

afet

yO

il S

afet

y

Sys

Off

Sel

ecta

ble

Inpu

ts

Rel

ay 1

D

ropd

own

Opt

ions

Dis

able

dFi

xed

Spe

edV

aria

ble

Spe

edD

igita

lH

G D

efr

Rel

ayLL

SU

nldr

for

Com

p 2

Unl

dr fo

r C

omp

3

Rel

ay 2

- 3

Dro

pdow

n O

ptio

nsA

ll R

elay

Opt

ions

are

the

sa

me

as R

elay

1, e

xcep

t th

e lis

t of

Unl

oade

rs fo

r th

e co

mpr

esso

r ne

ver

incl

udes

th

e ac

tive

com

pres

sor.

Fixe

d S

uctio

n Fl

oat

Suc

tion

Fahr

enhe

it C

elsi

usB

tuA

mp

R-4

04

AR

-50

7R

-40

7A

R-4

07

CR

-42

2A

R-4

22

DR

-13

4a

R-2

2R

-71

7R

-43

8A

R-4

08

AR

-40

9A

R-4

07

FR

-41

0A

R-7

44

R-4

48

AR

-44

9A

R-4

50

R-5

13

A

Onc

e co

mpr

esso

rs a

re

sele

cted

and

sav

ed, H

P

shou

ld b

e en

tere

d fo

r ea

ch.

Indi

cate

s w

heth

er s

yste

m is

ru

nnin

g or

pum

ped

dow

n.

Clic

k to

put

sys

tem

into

pu

mpd

own

mod

e.

Sho

ws

whi

ch S

uctio

n G

roup

s se

tpoi

nts

are

bein

g di

spla

yed.

0 t

o 1

0 V

DC

0 t

o 5

VD

C

Sav

es c

hang

e to

the

S

etpo

ints

pag

e. M

ust

be lo

gged

in t

o sa

ve.

Page 36: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 36

KE2 Compressor Sequencer OEM pn 21768

Quick Start GuideD

escr

ipti

on:

Allo

ws

the

user

to s

etup

the

cont

rolle

r, an

d to

cus

tom

ize

the

cont

rolle

r to

mee

t spe

cific

app

licat

ion

need

s.

The

KE2

Com

pres

sor S

eque

ncer

OEM

beg

ins

in S

yste

m O

ff M

ode.

The

use

r mus

t con

figur

e re

lays

and

re

frig

erat

ion

setp

oint

s to

ens

ure

the

syst

em w

ill ru

n pr

oper

ly, t

hen

turn

the

syst

em o

n.

The

scre

ensh

ot b

elow

sho

ws

the

Setp

oint

s pa

ge w

hen

one

or tw

o Au

x Bo

ards

are

use

d. N

ote

whe

n tw

o su

ctio

n gr

oups

are

use

d, e

ach

suct

ion

grou

p w

ill h

ave

its o

wn

Setp

oint

s pa

ge

Setp

oint

s Pag

e -

Mai

n Bo

ard

+ Au

x Re

lay

Boar

d(s)

Inpu

t 1

, 2 o

r 3

Mod

e

Dis

able

dIn

Cm

p Te

mp

Roo

m T

emp

Mon

itor

HG

Def

r R

eq

2nd

Pre

s2

nd T

mp

Com

p M

odul

eH

i Pre

s S

afet

yO

il S

afet

y

Sys

Off

Sel

ecta

ble

Inpu

ts

Fahr

enhe

it C

elsi

us

0 t

o 1

0 V

DC

0 t

o 5

VD

C

R-4

04

AR

-50

7R

-40

7A

R-4

07

CR

-42

2A

R-4

22

DR

-13

4a

R-2

2R

-71

7R

-43

8A

R-4

08

AR

-40

9A

R-4

07

FR

-41

0A

R-7

44

R-4

48

AR

-44

9A

R-4

50

AR

-51

3A

Indi

cate

s w

heth

er s

yste

m is

ru

nnin

g or

pum

ped

dow

n.

Clic

k to

put

sys

tem

into

pu

mpd

own

mod

e.

Sho

ws

whi

ch S

uctio

n G

roup

s se

tpoi

nts

are

bein

g di

spla

yed.

Fixe

d S

uctio

n P

ress

ure

Floa

t S

uctio

n P

ress

ure

Det

erm

ines

if t

he

Inpu

t is

act

ive

whe

n it

dete

cts

an O

pen

or

Clo

sed

circ

uit,

and

a D

igita

l Inp

ut is

as

sign

ed a

s th

e in

put

func

tion.

Sav

es c

hang

es t

o th

e S

etpo

ints

pag

e.

Use

r m

ust

be

logg

ed in

to

save

.

Setpoints Page -Main Board + Aux Relay Board(s)

Page 37: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 37

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Exam

ple:

5.0

69

C

ap L

oad

44

.8

Suc

t P

res

22

Wee

kly

view

Mon

thly

vie

w

Cur

rent

act

ivity

Wri

tes

the

data

sto

red

on t

he

cont

rolle

r to

a C

SV

file

.

Dat

e an

d Ti

me

are

pulle

d fr

om t

he c

onne

cted

co

mpu

ter.

Day

s A

go, C

apac

ity L

oad,

and

S

uctio

n P

ress

ure

are

disp

laye

d w

hen

mov

ing

the

mou

se o

ver

the

data

.

Day

s ag

o

Des

crip

tion

:Th

e G

raph

ing

Snap

shot

sho

ws

the

past

sev

en d

ays

of C

apac

ity L

oad

and

Suct

ion

Pres

sure

re

adin

gs. I

t is

esse

ntia

l for

sys

tem

ana

lysi

s an

d tr

oubl

esho

otin

g.

The

expe

rts

at K

E2 Te

chni

cal S

uppo

rt c

an h

elp

trou

bles

hoot

you

r sys

tem

usi

ng th

is in

form

atio

n

Graphs Page

Gra

phs P

age

Page 38: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 38

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Alphabetical List of Abbreviations

Abbreviation Full Name Type Description

A01 A01 Suction Pres Sensor [Group 1] Alarm Alarm - Critical Group 1 suction pressure sensor is shorted, open or pressure

out of range.

A02 A02 Disch Pres Sensor [Group 1] Alarm Alarm - Critical Group 1 discharge pressure sensor is shorted, open or pres-sure out of range.

A03 A03 Suction Temp Sensor [Group 1] Alarm Alarm - Critical Group 1 suction temperature sensor is shorted or open.

A04 A04 Disch Temp Sensor [Group 1] Alarm - Critical Group 1 discharge temperature sensor is shorted or open.

A06 A06 High Superheat [Group 1] Alarm Alarm - Cautionary Group 1 suction superheat is higher than Max Suction SH for longer than Min/Max SH Del.

A07 A07 Low Superheat [Group 1] Alarm Alarm - Critical Group 1 suction superheat is lower than Min Suction SH for longer than Min/Max SH Del.

A08 A08 High Disch Temp [Group 1] Alarm Alarm - Critical Group 1 discharge temperature is higher than Max Disch Temp for longer than Max Dis Tmp Del.

A09 A09 High Int Comp Temp [Group 1] Alarm Alarm - Cautionary Group 1 digital compressor internal temp high. Will turn off

digital compressor until temp lowers.

A10 A10 High Disch Pres [Group 1] Alarm Alarm - Critical Group 1 discharge pressure is higher than Max Disch Pres for longer than Max Dis Prs Del.

A13 A13 Comp Mod [Group 1] Alarm Alarm - Cautionary Group 1 Compressor Module digital input is active.A16 A16 Oil Safety [Group 1] Alarm Alarm - Cautionary Group 1 Oil Safety digital input is active.A19 A19 Hi Pres Safety [Group 1] Alarm Alarm - Cautionary Group 1 High Pressure Safety digital input is active.A22 A22 Aux Brd Comms Alarm Alarm - Critical Main Board unable to communicate w. the Aux Relay Boards.A25 A25 Watchdog Alarm Alarm - Cautionary Contact KE2 Therm.

A26 A26 Email Failure Alarm Alarm - Cautionary Email alert was not confirmed by email server provided after seven consecutive attempts.

A28 A28 High Disch Temp [Group 2] Alarm Alarm - Critical Group 2 discharge temperature is higher than Max Disch Temp for longer than Max Dis Tmp Del.

A29 A29 Evap Comms [Group 1] Alarm Alarm - Cautionary Group 1 Siteview controllers not communicating.A30 A30 Evap Comms [Group 2] Alarm Alarm - Cautionary Group 2 Siteview controllers not communicating.

A31 A31 Disch Pres Sensor [Group 2] Alarm Alarm - Critical Group 2 discharge pressure sensor is shorted, open or pres-sure out of range.

A32 A32 Suction Temp Sensor [Group 2] Alarm Alarm - Critical Group 2 suction temperature sensor is shorted or open.

A34 A34 High Superheat [Group 2] Alarm Alarm - Cautionary Group 2 suction superheat is higher than Max Suction SH for longer than Min/Max SH Del.

A35 A35 Low Superheat [Group 2] Alarm Alarm - Critical Group 2 suction superheat is lower than Min Suction SH for longer than Min/Max SH Del.

A36 A36 Disch Temp Sensor [Group 2] Alarm Alarm - Critical Group 2 discharge temperature sensor is shorted or open.

A37 A37 High Int Comp Temp [Group 2] Alarm Alarm - Cautionary Group 2 digital compressor internal temp high. Will turn off

digital compressor until temp lowers.

A38 A38 High Disch Pres [Group 2] Alarm Alarm - Critical Group 2 discharge pressure is higher than Max Disch Pres for longer than Max Dis Prs Del.

A41 A41 Suction Pres Sensor [Group 2] Alarm Alarm - Critical Group 2 suction pressure sensor is shorted, open or pressure

out of range.A44 A44 Comp Mod [Group 2] Alarm Alarm - Cautionary Group 2 Compressor Module digital input is active.A47 A47 Oil Safety [Group 2] Alarm Alarm - Cautionary Group 2 Oil Safety digital input is active.A50 A50 Hi Pres Safety [Group 2] Alarm Alarm - Cautionary Group 2 High Pressure Safety digital input is active.

A53 A53 Main: Aux Input 1 Sensor [Group 1] Alarm Alarm - Cautionary Main Board, Aux Input 1 Sensor is shorted or open.

A54 A54 Main: Aux Input 2 Sensor [Group 1] Alarm Alarm - Cautionary Main Board, Aux Input 2 Sensor is shorted or open.

A55 A55 Main: Aux Input 3 Sensor [Group 1] Alarm Alarm - Cautionary Main Board, Aux Input 3 Sensor is shorted or open.

A56 A56 Aux Addr 1: Input 2 Sensor [Group 1] or [Group 2] Alarm Alarm - Cautionary Aux Board 1, Input 2 Sensor is shorted or open.

Page 39: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

Q.2.60 March 2019Page 39

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Alphabetical List of Abbreviations (continued)

Abbreviation Full Name Type Description

A57 A57 Aux Addr 1: Input 3 Sensor [Group 1] or [Group 2] Alarm Alarm - Cautionary Aux Board 1, Input 3 Sensor is shorted or open.

A58 A58 Aux Addr 2: Input 2 Sensor [Group 1] or [Group 2] Alarm Alarm - Cautionary Aux Board 2, Input 2 Sensor is shorted or open.

A59 A59 Aux Addr 2: Input 3 Sensor [Group 1] or [Group 2] Alarm Alarm - Cautionary Aux Board 2, Input 3 Sensor is shorted or open.

ClA CLA Clear Alarms Setpoints - Single Group, Setpoint - Dual Group Press and hold ENTER to clear all active alarms.

dH1 dH1 Discharge Superheat - Group1 Variables - Dual Group Group 1 Discharge Superheat as calculated by the controller.dH2 dH2 Discharge Superheat - Group1 Variables - Dual Group Group 2 Discharge Superheat as calculated by the controller.

dHC dHC DHCP mode Setpoints - Single Group, Setpoint - Dual Group

Turn DHCP mode on or off: EnA to enable / diS to disable DHCP mode.

dPr dPr Discharge Pressure Variables - Single group Discharge Pressure as read by the controller.dP1 dP1 Discharge Pressure - Group1 Variables - Dual Group Group 1 Discharge Pressure as read by the controller.dP2 dP2 Discharge Pressure - Group2 Variables - Dual Group Group 2 Discharge Pressure as read by the controller.

dS1 dS1 Discharge Saturation Temperature - Group1 Variables - Dual Group Group 1 Discharge Saturation Temperature as calculated by

the controller.

dS2 dS2 Discharge Saturation Temperature - Group2 Variables - Dual Group Group 2 Discharge Saturation Temperature as calculated by

the controller.

dSA dSA Discharge Saturation Temperature Variables - Single group Discharge Saturation Temperature as calculated by the controller.

dSH dSH Discharge Superheat Variables - Single group Discharge Superheat as calculated by the controller.dSt dSt Discharge Temperature Variables - Single group Discharge Temperature as read by the controller.dt1 dt1 Discharge Temperature - Group1 Variables - Dual Group Group 1 Discharge Temperature as read by the controller.dt2 dt2 Discharge Temperature - Group2 Variables - Dual Group Group 2 Discharge Temperature as read by the controller.

FiR Fir Firmware Version Variables - Single groupVariables - Dual Group Current firmware version on the controller.

iP1 iP1 IP Octet 1Variables - Dual GroupVariables - Single group

First three digits of the IP address.iP2 iP2 IP Octet 2 Second three digits of the IP address.iP3 iP3 IP Octet 3 Third three digits of the IP address.iP4 iP4 IP Octet 4 Fourth three digits of the IP address.oF1 oF1 System Off – Group 1 Default Display Group 1 is in System Off mode.

oF2 oF2 System Off – Group 2 Default Display Group 2 is in System Off mode.

PAS PAS web Password Reset Setpoints - Single Group Setpoint - Dual Group Press and hold ENTER to reset browser password.

Pr1 Pr1 Suction Pressure - Group1 Variables - Dual Group Group 1 Suction Pressure as read by the controller.Pr2 Pr2 Suction Pressure - Group2 Variables - Dual Group Group 2 Suction Pressure as read by the controller.PrS PrS Suction Pressure Variables - Single group Suction Pressure as read by the controller.

PS1 PS1 Target Suction Pressure - Group1 Setpoint - Dual Group Target Suction Pressure - Suction pressure the controller will work to maintain for group 1.

PS2 PS2 Target Suction Pressure - Group2 Setpoint - Dual Group Target Suction Pressure - Suction pressure the controller will work to maintain for group 2.

PSP PSP Target Suction Pressure Setpoints - Single Group Target Suction Pressure - Suction pressure the controller will work to maintain.

S01 S01 Low Safety SH 1 [Group 1] Alarm Alarms - Safety / Preemptive Group 1 suction superheat is below Min Safety Suc SH for more than 5 minutes.

S02 S02 High Safety Suc Temp 1 [Group 1] Alarm Alarms - Safety / Preemptive Group 1 suction temperature is above Max Safety Suc Tmp

for more than 5 minutes.

S03 S03 High Safety Disch Pres 1 [Group 1] Alarms - Safety / Preemptive

Group 1 discharge pressure is above Max Safety Pres-sure. Controller will attempt to unload stages and not load anymore stages until pressure is well below Max Safety Pressure.

Page 40: KE2 Compressor Sequencer OEM · Aux Relay Board 21323 Auxiliary Relay Board External Relays 21304 Solid State Relay - Used to control digital compressor bypass valve 21032 Used to

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.60 March 2019Page 40

KE2 Compressor Sequencer OEM pn 21768

Quick Start Guide

Alphabetical List of Abbreviations (continued)

Abbreviation Full Name Type Description

S11 S11 Low Safety SH 2 [Group 2] Alarm Alarms - Safety / Preemptive Group 2 suction superheat is below Min Safety Suc SH for more than 5 minutes.

S12 S12 High Safety Suc Temp 2 [Group 2] Alarm Alarms - Safety / Preemptive Group 2 suction temperature is above Max Safety Suc Tmp

for more than 5 minutes.

S13 S13 High Safety Disch Pres 2 [Group 2] Alarm Alarms - Safety / Preemptive

Group 2 discharge pressure is above Max Safety Pres-sure. Controller will attempt to unload stages and not load anymore stages until pressure is well below Max Safety Pressure.

SA SA KE2 Smart Access Setpoints - Single Group Setpoint - Dual Group

Turn KE2 Smart Access on or off: EnA to enable / diS to dis-able KE2 Smart Access.

SA1 SA1 Saturation Temperature - Group1 Variables - Dual Group Group 1 Saturated Suction Temperature as calculated by the controller.

SA2 SA2 Saturation Temperature - Group2 Variables - Dual Group Variables - Dual Group

Group 2 Saturated Suction Temperature as calculated by the controller.

SAt SAt Saturation Temperature Variables - Single group Saturated Suction Temperature as calculated by the controller.

SH1 SH1 Superheat - Group1 Variables - Dual Group Group 1 Suction Superheat as calculated by the controller.SH2 SH2 Superheat - Group2 Variables - Dual Group Group 2 Suction Superheat as calculated by the controller.SHt SHt Superheat Variables - Single group Suction Superheat as calculated by the controller.SU1 SU1 Suction Temperature - Group1 Variables - Dual Group Group 1 Suction Temperature as read by the controller.SU2 SU2 Suction Temperature - Group2 Variables - Dual Group Group 2 Suction Temperature as read by the controller.SUt SUt Suction Temperature Variables - Single group Suction Temperature as read by the controller.

Sy1 SY1

SY2

System On/Off - Group 1 Setpoint - Dual Group Allow group 1 to run or put into system off: on1 to run / oF1 to pump down group 1 and put into system off.

Sy2

SY1

SY2 System On/Off - Group 2 Setpoint - Dual Group Allow group 2 to run or put into system off: on2 to run / oF2 to pump down group 2 and put into system off.

SyS

SY1

SY2

System On/Off Setpoints - Single Group Allow rack to run or put into system off: on to run / oFF to pump down rack and put into system off.

KE2 Therm Solutions 12 Chamber Drive . Washington, MO 63090

1.888.337.3358 . www.ke2therm.com