Product Summary:The KE2 Compressor Sequencer OEM allows control of up to 8 stages of loading for a single suc-tion group, or up to 10 stages of loading (5 per suction group) for dual suction groups.
For dual suction groups, the controller is applicable to both racks with a shared common dis-charge, or independent discharge lines. Suction pressure can be controlled to either a fixed setpoint, or a floating suction pressure for maximum efficiency.
Each stage of loading can be set to: fixed speed compressor, variable speed compressor①, digi-tal compressor① ② or unloaders. The relays for the stages can alternatively be used to control a Master Liquid Line Solenoid, or as a Hot Gas Defrost Relay.
Communication:As is standard with many other KE2 Therm controllers, the KE2 Compressor Sequencer OEM has the simplest and easiest communication platform in the industry. The controller uses standard communication protocols and cables; no extra software is necessary, only an Ethernet connec-tion to the controller. E-mail and/or text alerts can be sent out right from the controller. Com-plete remote access is available during startup with one simple button press and an Internet connection.
① One per Suction Group
② Controller is designed to operate with a Copeland Scroll Digital Compressor, when Digital Compressor is selected.
Part Numbers - Controllers & Accessories
Part Number Description
KE2 Compressor Sequencer OEM21768 Controller only
Aux Relay Board21323 Auxiliary Relay Board
External Relays21304 Solid State Relay - Used to control digital compressor bypass valve
21032 Used to pilot contactor for 5th compressor stage, control master liquid line solenoid, hot gas solenoid or unloader valve with Aux Relay Board Relay #5.
Pressure Transducers20201③ Pressure Transducer 0 to 150 psia, 10 ft. lead - for suction pressure. 20204③ Pressure Transducer 0 to 150 psia, 40 ft. lead - for suction pressure.20202 Pressure Transducer 0 to 500 psig, 10 ft. lead - for discharge pressure.20712 Pressure Transducer 0 to 500 psig, 40 ft. lead - for discharge pressure.
Temperature Sensors21230 High temp sensor for discharge at condenser inlet, 15 ft.20199 Standard temp sensor for all other temp inputs, 10 ft. (black)20200 Standard temp sensor for all other temp inputs, 40 ft. (black)
Replacement Relays21374 Replacement Form C Relay for Main Board
Replacement Fuses21375 Replacement incoming power fuse for Main Board and Aux Relay Board21628 Replacement fuses for Aux Relay Board relays (5 pack)
③ Use transducers 20208 (10 ft.) or 20711 (40 ft.) for R-410A. Use 20202 (10 ft.) or 20712 (40 ft.) for R-744.
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60March 2019
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
This reference should remain on site with the installed KE2 Compressor Sequencer
Contents:Product Summary Pg. 1
Part Numbers - Controllers & Accessories Pg. 1
Dimensions & Specifications - Main Board Pg. 2
Dimensions & Specifications - Auxiliary Relay Board Pg. 3
Application Pg. 3
Setup Options Pg. 4 1 - Main Board Only Single Suction Group w. Common Discharge Pg. 52 - Main Board + 1 Aux Relay Board Single Suction Group w. Common Discharge Pg. 6-73 - Main Board + 2 Aux Relay Boards Single Suction Group w. Common Discharge Pg. 8-94 - Main Board + 2 Aux Relay Boards Dual Suction Groups w. Common Discharge Pg. 10-115 - Main Board + 2 Aux Relay Boards Dual Suction Groups w. Independant Disch. Pg. 12-13
Communication Setup Options Pg. 14
Setting Up Groups Pg. 15
Designating Relay Functions Pg. 16 - 18 ▪ Single Group - Main Board Only ▪ Single Group or Dual Group +Aux Boards
Running the System Pg. 18-19
Determining Compresor ON/OFF Order Pg. 20 ▪ Fixed Suction Pressure w. Digital Scroll or Variable Speed Compressors▪ Fixed Suction Pressure w. Fixed Speed Compressors▪ Floating Suction Pressure
Selectable Inputs Pg. 21
Descriptions of Selectable Input Mode Options Pg. 21
Remote Display Pg. 22 - 23 ▪ Variables Menu - Single Group▪ Setpoints Menu - Single Group ▪ Variables Menu - Dual Group▪ Setpoints Menu - Dual Group
Alarms Pg. 24 - 25 ▪ Critical & Cautionary Alarms - ALL Groups▪ Safety Alarms - ALL Groups
Webpage Setpoints - Main Board Pg. 26 - 27
Webpage Setpoints - Auxiliary Relay Boards Pg. 28
Webpage Screen Shots Pg. 29 - 37▪ Home Page▪ Status Page - Main Board▪ Status Page - Aux Relay Board▪ Settings Page ▪ Login Page▪ Network Page ▪ Setpoints Page - Main Board Only▪ Setpoints Page - Main Board + Aux Relay Board(s)▪ Graphs Page
Alphabetical List of Abbreviations Pg. 38 - 40
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 2
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Dimensions & Specifications KE2 Compressor Sequencer OEM - Main Board
NONC
COM
EARTH
11.20”
11.00”
5.70”
2.80”
3.25”
0.20”
0.20”
Ø0.150” Hole Thru (6 places)0.06”
1.60”
0.10”
ON
1 2 3 45 6 7 8
8.5”
3.25”
0.06”1.50”
KE2 Compressor Sequencer OEM – Main Board pn 21768
Input Voltage: 120/208/230 VAC
Ambient Temp: -40°F to 140°F (-40°C to 60°C)
Operating Temp: -40°F to 140°F (-40°C to 60°C)
Inputs: (2) temperature sensors
(2) pressure transducers
(3) selectable temperature / digital inputs
Outputs:(1) 0 to 10 VDC / 0 to 5 VDC - configurable for variable speed or 0V/10V for Digital Compressor Bypass Valve ①②
Relays: (3) 10A inductive
Relay Functions:Fixed speed, variable speed, digital com-pressor, hot gas defrost relay, master liquid line solenoid, unloader
Selectable Input Functions:
Internal compressor temp, room temp, monitor temp, hot gas defrost request, 2nd pressure, 2nd temp, compressor module alarm, high pressure safety alarm, oil pres-sure safety alarm, system off
Communication: Standard TCP/IP, API, XML, BACnet over IP③
① Digital Compressor Bypass Valve control requires PN 21304.② Controller is designed to operate with Copeland Scroll Digital Compressor.③ Requires KE2 Edge Manager PN 21634. Not available at release.
Digital Switch Relay– pn 21032
Operating Temp: -13°F to 131°F (-25°C to 55°C)
Relays: 10A inductive
Pressure Transducer – Suction Line pn 20201 (10ft.), 20204 (40 ft.)
Pressure Range: 0 to 150 psia
Proof Pressure 450 psi
Burst Pressure: 1,500 psi
Operating Temperature: -40°F to 275°F (-40°C to 135°C)
Pressure Transducer – Discharge Line, Suction & Discharge Line for R-744 pn 20202 (10ft.), 20712 (40 ft.)
Operating Range: 0 to 500 psig
Proof Pressure: 1,000 psi
Burst Pressure: 1,500 psi
Operating Temperature: -40°F to 275°F (-40°C to 135°C)
Standard Temperature Sensor pn 20199 (10ft.), 20200 (40 ft.)
Operating Temp: -60°F to 150°F (-51°C to 65°C)
High Temperature Sensor pn 21230 (15ft.)
Operating Range: -40°F to 302°F (-40°C to 150°C)
Q.2.60 March 2019Page 3
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Auxiliary Relay Board pn 21323 (When used with KE2 Compressor Sequencer OEM)
Input Voltage: 120/208/230 VAC
Ambient Temp: -40°F to 140°F (-40°C to 60°C)
Operating Temp: -40°F to 140°F (-40°C to 60°C)
Inputs: (2) temperature sensor / selectable inputs①
(1) pressure transducer
(1) selectable input
Outputs: (1) 0 to 10 VDC / 0 to 5VDC- configurable for variable speed or 0V/10V for Digital Compressor Bypass Valve②③
Relays: (4) 5A FLA inductive (1) 10A inductive external Digital Switch Relay - requires pn 21032
Relay Functions:Fixed speed, variable speed, digital compressor, hot gas defrost relay, master liquid line solenoid, unloader
Digital Input Functions:Internal compressor temp, room temp, monitor temp, hot gas defrost request, 2nd pressure, 2nd temp, compressor module alarm, high pressure safety alarm, oil pressure safety alarm, system off.
Dimensions & Specifications Auxiliary Relay Board
NONC
COM
EARTH
11.20”
11.00”
5.70”
2.80”
3.25”
0.20”
0.20”
Ø0.150” Hole Thru (6 places)0.06”
1.60”
0.10”
ON
1 2 3 45 6 7 8
8.5”
3.25”
0.06”1.50”
Application:The KE2 Compressor Sequencer OEM can be used on rack systems with up to 8 stages of loading for a single suction group, or up to 10 stages of loading (5 per suction group) for dual suction groups. For dual suction groups, the discharge line can be shared between the two groups, or independent. The relays can also be used to con-
Type of ControlTotal Number of Stages* (Compressor, Unloader)
1 2 3 4 5 6 7 8 9 10
Single Suction / Common Discharge KE2 Compressor Sequencer OEM
+1 Aux Relay Board +2 Aux Relay Boards
Dual Suction / Common Discharge KE2 Compressor Sequence OEM + 2 Aux Relay Boards (up to 5 stages per suction group)Dual Suction / Independent Discharge KE2 Compressor Sequence OEM + 2 Aux Relay Boards (up to 5 stages per suction group)
*Relays can also be used as a master liquid line solenoid valve relay and/or hot gas bypass relay.
Please refer to the point to point wiring diagrams for each specific application.
trol a Master Liquid Line Solenoid or act as a Hot Gas Defrost Relay. When more stages of loading are required than available on the main board, auxiliary relay boards can be added to increase the number of available relays. Please refer to the chart below for the number of required auxiliary boards for a specific application.
① Number of selectable inputs depends on application
② Digital Compressor Bypass Valve control requires PN 21304
③ Controller is designed to operate with a Copeland Scroll Digital Compressor.
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 4
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Oil LineTo CondenserDischarge Header
Suction Header
Option 4:KE2 Compressor Sequencer OEM + 2 Aux Relay BoardsDual Suction Groups w. Common Discharge
Option 5:KE2 Compressor Sequencer OEM +2 Aux Relay BoardsDual Suction Groups w. Independent Discharge
Option 3:KE2 Compressor Sequencer OEM + 2 Aux Relay BoardsSingle Suction Group w. Common Discharge
Aux Relay Board 1 Aux Relay Board 2
To Condenser Oil Line
Suction Header
Discharge Header
Option 2: KE2 Compressor Sequencer OEM + 1 Aux Relay BoardsSingle Suction Group w. Common Discharge
Option 1:KE2 Compressor Sequencer OEMSingle Suction Group w. Common Discharge
To CondenserOil Line
Discharge HeaderSuction Header
To CondenserOil Line
Discharge Header
Suction Header Suction Header
Main Board Aux Relay Board 2
Up to 5 compressors
Aux Relay Board 1
Up to 5 compressors
Aux Relay Board 1
To Condenser Oil Line
Discharge HeaderSuction Header Suction Header
Discharge Header
Up to 5 compressorsUp to 5 compressors
Aux Relay Board 1 Aux Relay Board 2
Setup Options
Q.2.60 March 2019Page 5
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT0 - 10VDC- Variable Speed (OV - 10V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY 3
RELAY 2RELAY 1
STEPPER MOTOR Not Used
RedBlack
GreenSuction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure TransducerGreen Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
* Use only chassis ground or spade connector ground
Option 1:Single Suction Group w. Common Discharge
To CondenserOil Line
Discharge HeaderSuction Header
Main Board
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 6
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
ON
1 2 3 45 6 7 8
* Use only chassis ground or spade connector ground
**Function Options are the same as list shown for the Main Board Aux Inputs.
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT - Not Used0 - 10 VDC
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY - Not Used
RELAY - Not UsedRELAY - Not Used
STEPPER MOTOR Not Used
RedBlack
GreenSuction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure TransducerGreen Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304
**AUX 1 INPUT 3
ON
1 2 3 45 6 7 8
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def Req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
Shield - Not Used
**AUX 1 INPUT 2
AUX 1INPUT 1Not Used
RS485
1 - ON
2 - 8 OFF
B-
A+
ShieldNot Used
ADDRESS 1Address set to Address 1 only
Option 2: Main Board + 1 Aux Relay Board Single Suction Group w. Common Discharge
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
(pn 21323)To Condenser Oil Line
Suction Header
Discharge Header
Aux Relay Board 1
Q.2.60 March 2019Page 7
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
ON
1 2 3 45 6 7 8
* Use only chassis ground or spade connector ground
**Function Options are the same as list shown for the Main Board Aux Inputs.
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT - Not Used0 - 10 VDC
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY - Not Used
RELAY - Not UsedRELAY - Not Used
STEPPER MOTOR Not Used
RedBlack
GreenSuction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure TransducerGreen Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304
**AUX 1 INPUT 3
ON
1 2 3 45 6 7 8
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def Req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
Shield - Not Used
**AUX 1 INPUT 2
AUX 1INPUT 1Not Used
RS485
1 - ON
2 - 8 OFF
B-
A+
ShieldNot Used
ADDRESS 1Address set to Address 1 only
Option 2: Main Board + 1 Aux Relay Board Single Suction Group w. Common Discharge
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
(pn 21323)To Condenser Oil Line
Suction Header
Discharge Header
Aux Relay Board 1
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 8
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
ON
1 2 3 45 6 7 8
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT - Not Used0 - 10 VDC
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY - Not Used
RELAY - Not UsedRELAY - Not Used
STEPPER MOTOR Not Used
RedBlack
GreenSuction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure TransducerGreen Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5Not Used
0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
**AUX 1 INPUT 3
ON
1 2 3 45 6 7 8
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def Req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
Shield - Not Used
**AUX 1 INPUT 2
AUX 1 INPUT 1Not Used
RS485
1 - ON
2 - 8 OFF
B-
A+
ShieldNot Used
Aux Relay Board 1ADDRESS 1Address set to Address 1 only
B-
A+
* Use only chassis ground or spade connector ground
**Function Options are the same as list shown for the Main Board Aux Inputs.
ON
1 2 3 45 6 7 8
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5Not Used
0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
**AUX 2 INPUT 3
**AUX 2 INPUT 2
AUX 2 INPUT 1Not Used
ShieldNot Used
ON
1 2 3 45 6 7 8
Aux Relay Board 2ADDRESS 2Address set to Address 2 only
1- OFF
3 - 8 OFF
2 - ON
Option 3: Main Board + 2 Aux Relay BoardsSingle Suction Group w. Common Discharge
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
(pn 21323)
Aux Relay Board 1 Aux Relay Board 2
Oil LineTo CondenserDischarge Header
Suction Header
Q.2.60 March 2019Page 9
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
ON
1 2 3 45 6 7 8
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT - Not Used0 - 10 VDC
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY - Not Used
RELAY - Not UsedRELAY - Not Used
STEPPER MOTOR Not Used
RedBlack
GreenSuction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure TransducerGreen Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5Not Used
0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
**AUX 1 INPUT 3
ON
1 2 3 45 6 7 8
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def Req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
Shield - Not Used
**AUX 1 INPUT 2
AUX 1 INPUT 1Not Used
RS485
1 - ON
2 - 8 OFF
B-
A+
ShieldNot Used
Aux Relay Board 1ADDRESS 1Address set to Address 1 only
B-
A+
* Use only chassis ground or spade connector ground
**Function Options are the same as list shown for the Main Board Aux Inputs.
ON
1 2 3 45 6 7 8
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5Not Used
0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
**AUX 2 INPUT 3
**AUX 2 INPUT 2
AUX 2 INPUT 1Not Used
ShieldNot Used
ON
1 2 3 45 6 7 8
Aux Relay Board 2ADDRESS 2Address set to Address 2 only
1- OFF
3 - 8 OFF
2 - ON
Option 3: Main Board + 2 Aux Relay BoardsSingle Suction Group w. Common Discharge
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
(pn 21323)
Aux Relay Board 1 Aux Relay Board 2
Oil LineTo CondenserDischarge Header
Suction Header
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 10
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
ON
1 2 3 45 6 7 8
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT - Not Used0 - 10 VDC
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY - Not Used
RELAY - Not UsedRELAY - Not Used
STEPPER MOTOR Not Used
RedBlack
Green
Suction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure Transducer
Green Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
**AUX 1 INPUT 3
ON
1 2 3 45 6 7 8
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HGDef req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
Shield - Not Used
**AUX 1INPUT 2
AUX 1 INPUT 1Not Used
RS485
* Use only chassis ground or spade connector ground
**Function Options are the same as list shown for the Main Board Aux Inputs.
1 - ON
2 - 8 OFF
B-
A+
ShieldNot Used
B-
A+
Group 1 Relays
Group 2 Relays
Group 1Group 1Group 2
Group 2
Suction PressureAUX 2 INPUT 1
ON
1 2 3 45 6 7 8
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304
**AUX 2INPUT 3
ShieldNot Used
ON
1 2 3 45 6 7 8
1- OFF
3 - 8 OFF
2 - ON
Group 2
Suction TemperatureAUX 2 INPUT 2
Aux Relay Board 1ADDRESS 1Address set to Address 1 only
Aux Relay Board 2ADDRESS 2Address set to Address 2 only
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Option 4: Main Board + 2 Aux Relay Boards Dual Suction Groups w. Common Discharge
(pn 21323)To Condenser
Oil Line
Discharge Header
Suction Header Suction Header
Aux Relay Board 2
Up to 5 compressors
Aux Relay Board 1
Up to 5 compressors
Q.2.60 March 2019Page 11
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
ON
1 2 3 45 6 7 8
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT - Not Used0 - 10 VDC
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY - Not Used
RELAY - Not UsedRELAY - Not Used
STEPPER MOTOR Not Used
RedBlack
Green
Suction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure Transducer
Green Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
**AUX 1 INPUT 3
ON
1 2 3 45 6 7 8
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HGDef req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
Shield - Not Used
**AUX 1INPUT 2
AUX 1 INPUT 1Not Used
RS485
* Use only chassis ground or spade connector ground
**Function Options are the same as list shown for the Main Board Aux Inputs.
1 - ON
2 - 8 OFF
B-
A+
ShieldNot Used
B-
A+
Group 1 Relays
Group 2 Relays
Group 1Group 1Group 2
Group 2
Suction PressureAUX 2 INPUT 1
ON
1 2 3 45 6 7 8
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V- Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304
**AUX 2INPUT 3
ShieldNot Used
ON
1 2 3 45 6 7 8
1- OFF
3 - 8 OFF
2 - ON
Group 2
Suction TemperatureAUX 2 INPUT 2
Aux Relay Board 1ADDRESS 1Address set to Address 1 only
Aux Relay Board 2ADDRESS 2Address set to Address 2 only
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Option 4: Main Board + 2 Aux Relay Boards Dual Suction Groups w. Common Discharge
(pn 21323)To Condenser
Oil Line
Discharge Header
Suction Header Suction Header
Aux Relay Board 2
Up to 5 compressors
Aux Relay Board 1
Up to 5 compressors
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 12
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
ON
1 2 3 45 6 7 8
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT - Not Used0 - 10 VDC
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY - Not Used
RELAY - Not UsedRELAY - Not Used
STEPPER MOTOR Not Used
RedBlack
Green
Suction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure Transducer
Green Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
**AUX 1 INPUT 3
ON
1 2 3 45 6 7 8
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
Shield - Not Used
DischargeTemperatureAUX 1 INPUT 2
DischargePressureAUX 1 INPUT 1
RS485
* Use only chassis ground or spade connector ground
**Function Options are the same as list shown for the Main Board Aux Inputs.
1 - ON
2 - 8 OFF
B-
A+
ShieldNot Used
B-
A+
Group 1 Relays
Group 2 RelaysGroup 1
Group 1Group 2
Suction PressureAUX 2 INPUT 1
ON
1 2 3 45 6 7 8
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V requires Solid State Relay pn 21304
**AUX 2 INPUT 3
ShieldNot Used
ON
1 2 3 45 6 7 8
1- OFF
3 - 8 OFF
2 - ON
Group 2
Suction TemperatureAUX 2INPUT 2
Option 5: Main Board + 2 Aux Relay Boards Dual Suction Group w. Independent Discharge
Aux Relay Board 1ADDRESS 1Address set to Address 1 only
Aux Relay Board 2ADDRESS 2Address set to Address 2 only
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Aux Relay Board 1 Aux Relay Board 2
To Condenser Oil Line
Discharge HeaderSuction Header Suction Header
Discharge Header
Up to 5 compressors
(pn 21323)
Q.2.60 March 2019Page 13
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
ON
1 2 3 45 6 7 8
AUX 2
NO NCCOM
Suction Temp Sensor (black)
AUX 3
AUX 1
Discharge Temp Sensor (grey)
OUTPUT - Not Used0 - 10 VDC
Ethernet Port (RJ45) for remote communications
Display (RJ-11)
RELAY - Not Used
RELAY - Not UsedRELAY - Not Used
STEPPER MOTOR Not Used
RedBlack
Green
Suction Pressure Transducer
Line/L1
Neutral/L2
INCOMING POWER
120/208/230 VAC
GROUND*
EA
RTH
GROUND*(Chassis)
FUSE
Discharge Pressure Transducer
Green Black
Shared Red
T1AH250VP1A 250Vslow blow
5mm x 20mm
A + B –Sh
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V)
requires Solid State Relay pn 21304
**AUX 1 INPUT 3
ON
1 2 3 45 6 7 8
Aux 1, 2 & 3 Function Options:- int comp temp- room temp- monitor temp- HG Def req- 2nd pres- 2nd temp- cmp module alarm- hi pres safety alarm- oil pres safety alarm- system off
Shield - Not Used
DischargeTemperatureAUX 1 INPUT 2
DischargePressureAUX 1 INPUT 1
RS485
* Use only chassis ground or spade connector ground
**Function Options are the same as list shown for the Main Board Aux Inputs.
1 - ON
2 - 8 OFF
B-
A+
ShieldNot Used
B-
A+
Group 1 Relays
Group 2 RelaysGroup 1
Group 1Group 2
Suction PressureAUX 2 INPUT 1
ON
1 2 3 45 6 7 8
INCOMING POWER
120/208/230VAC
GROUND
POWER FUSE
RELAY 5External Digital Switch - requires Relay pn 21032
0 - 10V - Variable Speed (OV - 10V) - or - (0V to 5V)- Digital Compressor Bypass Valve (OV/10V requires Solid State Relay pn 21304
**AUX 2 INPUT 3
ShieldNot Used
ON
1 2 3 45 6 7 8
1- OFF
3 - 8 OFF
2 - ON
Group 2
Suction TemperatureAUX 2INPUT 2
Option 5: Main Board + 2 Aux Relay Boards Dual Suction Group w. Independent Discharge
Aux Relay Board 1ADDRESS 1Address set to Address 1 only
Aux Relay Board 2ADDRESS 2Address set to Address 2 only
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Sh B– A+ – + + –+1
2S
igna
l - G
reen
B
lack
R
ed
– +5
FUSED RELAY 1 FUSED RELAY 3 FUSED RELAY 4FUSED RELAY 2
COM NC NO COM NC NOCOM NC NO COM NC NO
Aux Relay Board 1 Aux Relay Board 2
To Condenser Oil Line
Discharge HeaderSuction Header Suction Header
Discharge Header
Up to 5 compressors
(pn 21323)
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 14
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Communication SetupWhen powered up for the first time, the KE2 Compressor Sequencer OEM’s Remote Display will show CS (Compressor Sequencer), then SA (KE2 Smart Access). The controller is asking if remote access through KE2 Smart Access will be used. It will then blink diS (dis-abled).
Press and hold to disable KE2 Smart Access, or press the or arrow to reach EnA (enable). Press and hold to enable KE2
Smart Access.
On
Site
- Lo
cally
Rem
ote
Acce
ss
Joe’s C-Store & Gas
Joe’s C-Store & Gas
On the goXYZ Refrigeration
XYZ Refrigeration
At home At workOn siteAccess your
controllers:
Ways to connect:
Option 1: Directly ConnectedOption 2: Using the KE2 Smart GateOption 3: Using a KE2-LDA or KE2-EM35Option 4: Using the KE2 WiFi Service Tool Option 5: KE2 Smart Access PortalOption 6: KE2 Smart Access Portal w. Local DashboardOption 7: Customer VPN w. Local Dashboard
❶ Add KE2 Switch 8-port (pn 20166) or KE2 Switch 16-port (pn 21011) when connecting more than one controller.
❷ Typically DHCP should be enabled on the controllers when connecting directly to the customer network, unless directed by the customer’s IT department to set a static IP address.
Option 1: Directly Connected - Single Controller
Ethernet Cable
Computer
NOTE: Computer requires Static IP. See bulletin Q.5.11 or Video 124 at youtube.com/ke2therm
Option 4: Using the KE2 WiFi Service Tool (pn 20906)
thermsolutionsPWR WIFILANWAN 3G/4G
Superheat0.0 F
Suct Pressure96.2 F
Suct Temp87.7 F
Computer, Tablet, or Smart Phone
Ethernet Cable
KE2 WiFi Service Tool
KE2 Smart Gate
RB201 1UAS-2HND-IN
USB
SFP
POE GIGABIT ETHERNET
ETH1 ETH5ETH3 ETH4ETH2 ETH6 ETH10ETH8 ETH9ETH76 7 8 9 10
1 2 3 4 5FAST ETHERNET
Option 2: Using a KE2 Smart Gate (pn 20695) - Quick Multi-Controller Access
Ethernet Cable
Ethernet Cable
- or -
Superheat0.0 F
Suct Pressure96.2 F
Suct Temp87.7 F
Computer, Tablet, or Smart Phone
Option 3: Using a KE2-LDA (pn 21253) or KE2-EM35 (pn 21634)
Superheat0.0 F
Suct Pressure96.2 F
Suct Temp87.7 F
Computer, Tablet, or Smart Phone
WANLAN
Ethernet Cable
- or -❶ ❶ Ethernet Cable
- or -
Option 7: Customer VPN with Local Dashboard
Customer Network 1 2 3 654 7
Link/ACT
100/1000MbpsPOWER
Superheat0.0 F
Suct Pressure96.2 F
Suct Temp87.7 F
Computer, Tablet, or Smart Phone
WANLAN
- or -Internet
Customer VPN❶ ❶
Ethernet Cable
KE2-LDA KE2-EM35Ethernet Cable
- or -
1 2 3 654 7
Link/ACT
100/1000MbpsPOWER
Option 5: KE2 Smart Access Portal
InternetKE2 Smart Access
Customer NetworkEthernet Cable
Superheat0.0 F
Suct Pressure96.2 F
Suct Temp87.7 F
Computer, Tablet, or Smart Phone❷
NO NCCOM
Ethernet Port
EARTH
IP-10.10.52.19MAC
00:04:A3:14:E5:92
IP-10.10.52.19MAC
00:04:A3:14:E5:92
Ethernet Cable
Option 6: KE2 SmartAccess Portal with Local Dashboard
1 2 3 654
7
Link/ACT
100/1000MbpsPOWER
Superheat0.0 F
Suct Pressure96.2 F
Suct Temp87.7 F
Computer, Tablet, or Smart Phone
WANLAN
- or -
Ethernet Cable
- or -Internet
KE2 Smart Access❶ ❶
KE2-LDA KE2-EM35Customer Network
Once connected to the Internet, the controller can be accessed at http://smartaccess.ke2therm.net
The initial login: Site - installer Password: Controller’s MAC address
The remainder of the setup is done via the browser interface. There are many ways to connect to the controller, in addition to KE2 Smart Access. Please refer to the options below, and chose the method that best suits the site and application.
Options
Q.2.60 March 2019Page 15
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Setting Up Groups If using any Aux Relay Boards, the groups and Aux
Relay Boards must be setup before operation can begin.
Once connected to the controller either locally, using the IP address of the controller, or remotely through KE2 Smart Access, the home page will be displayed.
❶ Depending on the number of Aux Relay boards connected to the controller, one or two Unas-signed Aux Relay boards may appear on the screen.
❷ Click on the icon under Group 1.
❸ This will load the Setpoints page for Group 1.
❹ Next, click on the Settings page. Then click Login.
Enter the default username and password:
Username: ke2admin
Password: ke2admin
Click submit.
Once logged in, changes to the controller set-tings are now permitted.
❺ Instead of Login, the button in the lower right hand of the screen will now say Logout.
❻ Under Compressor Configuration, select the correct application from the list:
❶
❷
❸
❹
❺
❻
❼ Select the correct setup for the application and number of Aux Relay Boards,
❽ then click Save.
❼
❽
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 16
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
If no Aux Relay Boards are being utilized, and Compressor Configuration is set to Single Group, relays can be designated from the Setpoints page of Group 1.
Otherwise, relays and any additional inputs are designated from the Aux Relay Board interface.
Single Group - Main Board Only
❶ Select the function of each relay,
❷ then click the Save button at the bottom of the page.
❸ Once saved, Comp HP will appear below any relays selected as a compressor. Enter the correct horsepower for each compressor, then click the Save button again.
Designating Relay Function: Compressors, Unloaders, LLS (Liquid Line Solenoid) or Hot Gas
❷
❶❸
Q.2.60 March 2019Page 17
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Single Group/ Dual Group + Aux BoardsWhen using Aux Relay Boards, the relays and any additional inputs can be assigned in the in-terface for the Aux Relay Board.
❶ From the Home Page click on the icon for the Aux Board:
❶
❷ On the Aux Relay interface, Drivers (relays) are listed to the left.
❸ Inputs are listed to the right.
❷ ❸
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 18
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
❹ Under the Mode drop down, assign the proper function to each relay and click Save.
NOTE: Do not enter the horsepower for the com-pressor before clicking Save.
❺ If prompted for a Login, the default is the same as the Main Board:
Username: ke2admin
Password: ke2admin
❻ After clicking Save, click on the relay again to change the horsepower.
❼ Enter the correct horsepower and click Save.
Continue until all relays have the proper function and horsepower.
❹❺
❻
❼
Running the SystemIMPORTANT: All of the settings on the Setpoints page should be reviewed before beginning operation (See pages 26 - 28 for detailed explanation of each Setpoint).
When the KE2 Compressor Sequencer OEM is started for the first time, or anytime a critical setpoint is changed, the controller enters System Off mode.
In System Off mode, the controller will not energize any relays until the user manually takes the controller out of System Off.
Once all setpoints have been reviewed, and the system is ready to be-gin operation, click the yellow button on the setpoints
page to begin running.
The button will change to and begin operation.
Clicking this button again will put the system back into System Off.
Note: When two suction groups are used, there will be two Setpoints pages, one for each group. Click the icon to go to the Setpoints page for that suction group. Each suction group is individually put into, and taken out of, System Off.
Please make sure to review the Setpoints page of BOTH suction groups.
Q.2.60 March 2019Page 19
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Setpoints page for Group1
Setpoints page for Group 2
The Remote Display can also be used to put a suction group into, or take it out of, System Off mode.
Press and hold the button until SA is shown. Press the arrow un-
til SYS, SY1 or SY2 is shown. SYS indicates System Off when config-ured for Single Group. SY1 and SY2 indicate their respective groups when configured for Dual Group.
Press and the current status will be shown: oN, oN1, oN2 or oFF, oF1, oF2 depending on the configuration and suction group selected.
Press or to change the status.
Press and hold until the screen goes back to SYS, SY1 or SY2.
The suction group will now be in System Off, or running, depending on what was selected.
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 20
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
When applying the controller to a system consisting of fixed speed compressors with or without unloading capabilities, the controller requires the user to assign a relay output for each compressor stage available using the controller’s browser interface.
When Fixed Suction Pressure and only Fixed Speed Compressors are selected the controller will stage the compressors by capacity in HP as defined on the Setpoints page or Aux Relay Board Setpoints page. Stages will be loaded and unloaded based on the smallest ca-pacity step available. If all available stages are equal, the controller will automatically select the option with the least amount of runtime.
The Suction Pressure Setpoint is the target pressure the controller works to achieve while running. The Suction Pressure Differential determines the pressure above and below the Suction Pressure Setpoint the controller will allow the suction pressure to vary before it makes an adjustment to capacity.
Once a stage has been loaded or unloaded, that stage must remain on or off as determined by the Min Comp Runtime and Min Comp Offtime. The controller will not load or unload more often than the time defined in the Min Compressor Switch Time.
If the system is maintaining the suction pressure within the normal operating range, which is defined as the Suction Pressure Setpoint +/- the Suction Pressure Differential, it will maintain the current capacity.
Mode of Control: Fixed Suction Pressure & Fixed Speed Compressors
Determining Compressor ON/OFF Order
Mode of Control: Fixed Suction Pressure with Digital Scroll or Variable Speed Compressors
When applying the controller to a system consisting of fixed speed compressors with or without unloading capabilities and one digital scroll or variable speed compressor, the controller requires the user to assign a relay output for each compressor stage available using the controller’s browser interface.
The Digital Scroll or variable speed compressor will serve as the pri-mary stage to provide the most consistent suction pressure possible. Initially, the Digital Scroll will start unloaded, or the variable speed compressor will run at the Min Speed setpoint.
If suction pressure rises above the Suction Pressure Setpoint, the Digital Scroll will be loaded by de-energizing the bypass solenoid or the variable speed compressor will be loaded by increasing the 0-10VDC output (0-5VDC also available). The rate at which the Digi-tal Scroll or variable speed is loaded is determined by the controller’s algorithm, and will improve as the controller learns the system. If the Digital Scroll or variable speed compressor is fully loaded, the next stage will be loaded based on the smallest capacity step available. If all available stages are equal, the controller will automatically select the option with the least amount of runtime. The compressors will continue to be loaded until all compressors are running at full load.
If suction pressure falls below the Suction Pressure Setpoint, the Digital Scroll will be unloaded by energizing the bypass solenoid, or the variable speed compressor will be unloaded by decreasing the 0-10VDC output. If the Digital Scroll or variable speed compressor is fully unloaded, the next stage will be unloaded based on the smallest step available. If all available stages are equal, the controller will au-tomatically select the option with the most amount of runtime. Suc-tion pressure will primarily be controlled by loading and unloading the Digital Scroll or variable speed compressor. If suction pressure is still low, and all other stages have been unloaded, the Digital Scroll’s compressor relay will be de-energized if minimum run, off and switch times have been met. For variable speed compressors, the 0-10VDC output will unload down to the Min Speed setpoint①.
① The Digital Scroll and variable speed compressor’s requirements for unloading follow their own rulesets and are not adjustable. It has been designed to be within the limits of the compressor manufacturer, and to ensure that specification is maintained the minimum times for transi-tioning are not adjustable.
The KE2 Compressor Sequencer OEM has the ability to float the tar-get suction pressure for maximum efficiency. When the Fixed/Float Suction setpoint is set to Float Suction, all Room Temperature sen-sors connected to a group will be compared to the Room Temp set-point on the controller. When the average of the Room Temperature sensors is below the Room Temp setpoint and above saturation tem-perature, the controller will raise the target suction pressure. When the average of the Room Temperature sensors is above the Room Temp setpoint, the controller will lower the target suction pressure.
While floating suction is enabled, the Suction Pressure setpoint be-comes the minimum suction pressure that the controller will work to maintain.
Mode of Control: Floating Suction Control
Q.2.60 March 2019Page 21
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Selectable InputsThe digital inputs available depends on the application and number of Aux Relay Boards used. Please refer to the table below:
Application Hardware Number of Selectable Inputs Available
Single Suction / Common DischargeMain Board 3
Main +1 Aux Relay Board 5
Main + 2 Aux Relay Boards 7
Dual Suction / Common Discharge Main + 2 Aux Relay Boards 6
Dual Suction / Independent Discharge Main + 2 Aux Relay Boards 5
Selectable Input Mode: Sets the function of the Selectable Input (Complete Mode descriptions on the table below) Disabled In Cmp Temp Room Temp Monitor HG Defr Req 2nd Pres 2nd Tmp Comp Module Hi Pres Safety Oil Safety Sys Off
Input Active State: When a selectable input is set to one of the Digital Input Modes listed above, the Digital Input Active State determines whether the Digital Input performs the selected function (Digital Input Mode) when the input receives an open or shorted signal. Does not apply when Digital Input is used to receive a temperature sensor.
Descriptions of Selectable Input Mode OptionsInput Mode Designation
Disabled • Input performs no function.
In Cmp Temp(Internal Compressor Temperature)
• Monitors internal compressor temperature for Copeland Digital Scroll compressors. Triggers High Inter-nal Compressor Temperature Alarm, which turns off digital compressor until temperature lowers.
Room Temp • Used for floating suction pressure control.
Monitor • Used for monitoring a temperature. Does not affect control or alarming.
HG Defr Req (Hot Gas Defrost Request) • When active, energizes Hot Gas Defrost Relay. De-energizes relay when inactive.
2nd Pres (2nd Suction Pressure Setpoint) • When active, controller will operate using 2nd Suction Pressure setpoint as target suction pressure.
2nd Temp(2nd Room Temp Setpoint)
• When active, the controller will operate using 2nd Room Temp setpoint as target room temperature for suction float.
Comp Module (Compressor Module)
• Used for receiving an alarm from a compressor module. When active, will trigger Comp Mod Alarm.
Hi Pres Safety (High Pressure Safety Switch)
• Used for receiving an alarm from a high pressure safety switch. When active, will trigger Hi Pres Safety Alarm.
Oil Safety • Used for receiving an alarm from an oil pressure switch. When active, will trigger Oil Safety Alarm.
Sys Off(System Off)
• When active, begins to safely unload the suction group for pump down, and puts the group into System Off mode. In System Off mode, no relays will be energized, and a user must manually take the group out of System Off mode to resume operation.
Temperature Input Modes
Digital Input Modes
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 22
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Remote Display - Variables Menu - Single GroupWhen not in a menu, press or to go through the Variables abbreviations.
Press to view a Variable in real time.
Press to return to the previous screen.
Abbrev. Full Name DescriptionPrs SuCTIOn PReSSuRe Suction Pressure as read by the controller.SUt SuCTIOn TemPeRaTuRe Suction Temperature as read by the controller.SAt SaTuRaTIOn TemPeRaTuRe Saturated Suction Temperature as calculated by the controller.SHt SUPERHEAT Suction Superheat as calculated by the controller.dPr DISCHaRGe PReSSuRe Discharge Pressure as read by the controller.dSt DISCHaRGe TemPeRaTuRe Discharge Temperature as read by the controller.dSA DISCHaRGe SaTuRaTIOn TemPeRaTuRe Discharge Saturation Temperature as calculated by the controller.dSH DISCHaRGe SuPeRHeaT Discharge Superheat as calculated by the controller.iP1 IP OCTeT 1 First three digits of the IP address.iP2 IP OCTeT 2 Second three digits of the IP address.iP3 IP OCTeT 3 Third three digits of the IP address.iP4 IP OCTeT 4 Fourth three digits of the IP address.FiR FIRmwaRe VeRSIOn Current firmware version on the controller.
Remote Display - Setpoints Menu - Single GroupWhen not in a menu, press and hold until SA is shown.
Press or to go through the setpoint abbreviations.
Press to view the current setpoint value. Press or to change the setpoint.Press and hold to save.For numerical setpoints, pressing once will change the digit that is being modified.
Press to return to the previous screen. When viewing a setpoint value, press to return to the previous screen without saving.
Abbrev. Full Name Min Max Default DescriptionSA KE2 SMART ACCESS diS EnA diS Turn KE2 Smart Access on or off: EnA to enable / diS to
disable KE2 Smart Access.
dHC DHCP mODe diS EnA diS Turn DHCP mode on or off: EnA to enable / diS to disable DHCP mode.
SyS SySTem On/OFF oFF on oFF Allow rack to run or put into system off: on to run / oFF to pump down rack and put into system off.
PSP TaRGeT SuCTIOn PRESSURE 0.0 psig 150.0 psig① 25.0 psig② Suction pressure the controller will work to maintain.
CLA CLEAR ALARMS Press and hold ENTER to clear all active alarms.
PAS weB PaSSwORD ReSeT Press and hold ENTER to reset browser password.
① R-410A = 300.0 psig, R-744 = 500.0 psig. ② R-744 =250.0 psig
Remote Display - Menus and ParametersWhen not in alarm or off, displays Group 1 Suction Pressure.
Abbreviation Full Name DescriptionoFF System Off All groups are in System Off mode.
oF1 System Off – Group 1 Group 1 is in System Off mode.
oF2 System Off – Group 2 Group 2 is in System Off mode.
Q.2.60 March 2019Page 23
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Remote Display - Variables Menu - Dual Group When not in a menu, press or to go through the Variables abbreviations.
Press to view a Variable in real time.
Press to return to the previous screen.
Abbrev. Full Name DescriptionPr1 SuCTIOn PReSSuRe - GROuP1 Group 1 Suction Pressure as read by the controller.SU1 SuCTIOn TemPeRaTuRe - GROuP1 Group 1 Suction Temperature as read by the controller.SA1 SaTuRaTIOn TemPeRaTuRe - GROuP1 Group 1 Saturated Suction Temperature as calculated by the controller.SH1 SuPeRHeaT - GROuP1 Group 1 Suction Superheat as calculated by the controller.dP1 DISCHaRGe PReSSuRe - GROuP1 Group 1 Discharge Pressure as read by the controller.dt1 DISCHaRGe TemPeRaTuRe - GROuP1 Group 1 Discharge Temperature as read by the controller.
dS1 DISCHaRGe SaTuRaTIOn TemPeRaTuRe - GROUP1 Group 1 Discharge Saturation Temperature as calculated by the controller.
dH1 DISCHaRGe SuPeRHeaT - GROuP1 Group 1 Discharge Superheat as calculated by the controller.Pr2 SuCTIOn PReSSuRe - GROuP2 Group 2 Suction Pressure as read by the controller.SU2 SuCTIOn TemPeRaTuRe - GROuP2 Group 2 Suction Temperature as read by the controller.SA2 SaTuRaTIOn TemPeRaTuRe - GROuP2 Group 2 Saturated Suction Temperature as calculated by the controller.SH2 SuPeRHeaT - GROuP2 Group 2 Suction Superheat as calculated by the controller.dP2 DISCHaRGe PReSSuRe - GROuP2 Group 2 Discharge Pressure as read by the controller.dt2 DISCHaRGe TemPeRaTuRe - GROuP2 Group 2 Discharge Temperature as read by the controller.
dS2 DISCHaRGe SaTuRaTIOn TemPeRaTuRe - GROUP2 Group 2 Discharge Saturation Temperature as calculated by the controller.
dH2 DISCHaRGe SuPeRHeaT - GROuP2 Group 2 Discharge Superheat as calculated by the controller.iP1 IP OCTeT 1 First three digits of the IP address.iP2 IP OCTeT 2 Second three digits of the IP address.iP3 IP OCTeT 3 Third three digits of the IP address.iP4 IP OCTeT 4 Fourth three digits of the IP address.Fir FIRmwaRe VeRSIOn Current firmware version on the controller.
Remote Display - Setpoints Menu - Dual Group When not in a menu, press and hold until SA is shown.
Press or to go through the setpoint abbreviations.
Press to view the current setpoint value. Press or to change the setpoint.Press and hold to save.For numerical setpoints, pressing once will change the digit that is being modified.
Press to return to the previous screen. When viewing a setpoint value, press to return to the previous screen without saving.
Abbrev. Full Name Min Max Default DescriptionSA KE2 SMART ACCESS diS EnA diS Turn KE2 Smart Access on or off: EnA to enable / diS to disable
KE2 Smart Access.
dHC DHCP mODe diS EnA diS Turn DHCP mode on or off: EnA to enable / diS to disable DHCP mode.
Sy1 SySTem On/OFF - GROuP 1 oF1 on1 oF1 Allow group 1 to run or put into system off: on1 to run / oF1 to pump down group 1 and put into system off.
Sy2 SySTem On/OFF - GROuP 2 oF2 on2 oF2 Allow group 2 to run or put into system off: on2 to run / oF2 to pump down group 2 and put into system off.
PS1 TaRGeT SuCTIOn PReSSuRe - GROUP1 0.0 psig 150.0
psig①25.0 psig②
Target Suction Pressure - Suction pressure the controller will work to maintain for group 1.
PS2 TaRGeT SuCTIOn PReSSuRe - GROUP2 0 psig 150.0
psig①25.0 psig②
Target Suction Pressure - Suction pressure the controller will work to maintain for group 2.
CLA CLEAR ALARMS Press and hold ENTER to clear all active alarms.PAS weB PaSSwORD ReSeT Press and hold ENTER to reset browser password.
① R-410A = 300.0 psig, R-744 = 500.0 psig. ② R-744 =250.0 psig
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 24
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Critical Alarms & Cautionary Alarms
Abbre-viation Alarm Description Critical
A01 Suction Pres Sensor [Group 1] Alarm Group 1 suction pressure sensor is shorted, open or pressure out of range. ▪
A02 Disch Pres Sensor [Group 1] Alarm Group 1 discharge pressure sensor is shorted, open or pressure out of range. ▪
A03 Suction Temp Sensor [Group 1] Alarm Group 1 suction temperature sensor is shorted or open. ▪A04 Disch Temp Sensor [Group 1] Group 1 discharge temperature sensor is shorted or open. ▪A06 High Superheat [Group 1] Alarm Group 1 suction superheat is higher than Max Suction SH for longer
than Min/Max SH Del.
A07 Low Superheat [Group 1] Alarm Group 1 suction superheat is lower than Min Suction SH for longer than Min/Max SH Del. ▪
A08 High Disch Temp [Group 1] Alarm Group 1 discharge temperature is higher than Max Disch Temp for longer than Max Dis Tmp Del. ▪
A09 High Int Comp Temp [Group 1] Alarm Group 1 digital compressor internal temp high. Will turn off digital compressor until temp lowers.
A10 High Disch Pres [Group 1] Alarm Group 1 discharge pressure is higher than Max Disch Pres for longer than Max Dis Prs Del. ▪
A13 Comp Mod [Group 1] Alarm Group 1 Compressor Module digital input is active.A16 Oil Safety [Group 1] Alarm Group 1 Oil Safety digital input is active.A19 Hi Pres Safety [Group 1] Alarm Group 1 High Pressure Safety digital input is active.A22 Aux Brd Comms Alarm Main Board unable to communicate with the Aux Relay Board(s). ▪A25 Watchdog Alarm Contact KE2 Therm.
A26 Email Failure Alarm Email alert was not confirmed by email server provided after seven consecutive attempts.
A28 High Disch Temp [Group 2] Alarm Group 2 discharge temperature is higher than Max Disch Temp for longer than Max Dis Tmp Del. ▪
A29 Evap Comms [Group 1] Alarm Group 1 SiteView controllers not communicating.A30 Evap Comms [Group 2] Alarm Group 2 SiteView controllers not communicating.
A31 Disch Pres Sensor [Group 2] Alarm Group 2 discharge pressure sensor is shorted, open or pressure out of range. ▪
A32 Suction Temp Sensor [Group 2] Alarm Group 2 suction temperature sensor is shorted or open. ▪A34 High Superheat [Group 2] Alarm Group 2 suction superheat is higher than Max Suction SH for longer
than Min/Max SH Del.
A35 Low Superheat [Group 2] Alarm Group 2 suction superheat is lower than Min Suction SH for longer than Min/Max SH Del. ▪
A36 Disch Temp Sensor [Group 2] Alarm Group 2 discharge temperature sensor is shorted or open. ▪A37 High Int Comp Temp [Group 2] Alarm Group 2 digital compressor internal temp high. Will turn off digital
compressor until temp lowers.
A38 High Disch Pres [Group 2] Alarm Group 2 discharge pressure is higher than Max Disch Pres for longer than Max Dis Prs Del. ▪
Alarms - All GroupsAlarm Severity
Red LED - Critical Alarm: The controller will attempt to safely pump down the suction group. The group is unable to run safely with a critical alarm, and the controller will cease refrigeration for that group. The controller is attempting to prevent a catastrophic system failure, such as damage to the compressors. Critical alarms should be addressed immediately.
Yellow LED - Cautionary Alarm: The controller will continue to function to the best extent possible given the system conditions, but the alarm should be addressed as soon as possible.
Q.2.60 March 2019Page 25
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Critical Alarms & Cautionary Alarms (continued)
Abbre-viation Alarm Description Critical
A41 Suction Pres Sensor [Group 2] Alarm Group 2 suction pressure sensor is shorted, open or pressure out of range. ▪
A44 Comp Mod [Group 2] Alarm Group 2 Compressor Module digital input is active.A47 Oil Safety [Group 2] Alarm Group 2 Oil Safety digital input is active.A50 Hi Pres Safety [Group 2] Alarm Group 2 High Pressure Safety digital input is active.
A53 Main: Aux Input 1 Sensor [Group 1] Alarm Main Board, Aux Input 1 Temp Sensor is shorted or open.
A54 Main: Aux Input 2 Sensor [Group 1] Alarm Main Board, Aux Input 2 Temp Sensor is shorted or open.
A55 Main: Aux Input 3 Sensor [Group 1] Alarm Main Board, Aux Input 3 Temp Sensor is shorted or open.
A56 Aux Addr 1: Input 2 Sensor [Group 1] or [Group 2] Alarm Aux Board 1, Input 2 Temp Sensor is shorted or open.
A57 Aux Addr 1: Input 3 Sensor [Group 1] or [Group 2] Alarm Aux Board 1, Input 3 Temp Sensor is shorted or open.
A58 Aux Addr 2: Input 2 Sensor [Group 1] or [Group 2] Alarm Aux Board 2, Input 2 Temp Sensor is shorted or open.
A59 Aux Addr 2: Input 3 Sensor [Group 1] or [Group 2] Alarm Aux Board 2, Input 3 Temp Sensor is shorted or open.
Safety Alarms (Preemptive Alarms)Safety alarms S01-03 and S11-13 are preemptive alarms and trigger before their respective critical alarms are triggered.
Abbre-viation Alarm Description Critical
S01 Low Safety SH 1 [Group 1] Alarm Group 1 suction superheat is below Min Safety Suc SH for more than 5 minutes.
S02 High Safety Suc Temp 1 [Group 1] Alarm
Group 1 suction temperature is above Max Safety Suc Tmp for more than 5 minutes.
S03 High Safety Disch Pres 1 [Group 1]Group 1 discharge pressure is above Max Safety Pressure. Control-ler will attempt to unload stages and not load anymore stages until pressure is well below Max Safety Pressure.
S11 Low Safety SH 2 [Group 2] Alarm Group 2 suction superheat is below Min Safety Suc SH for more than 5 minutes.
S12 High Safety Suc Temp 2 [Group 2] Alarm
Group 2 suction temperature is above Max Safety Suc Tmp for more than 5 minutes.
S13 High Safety Disch Pres 2 [Group 2] Alarm
Group 2 discharge pressure is above Max Safety Pressure. Control-ler will attempt to unload stages and not load anymore stages until pressure is well below Max Safety Pressure.
Webpage Setpoints - Main Board The following setpoints are available on the broswer interface of the Main Board.
Setpoint Description Range / Options Default
Rela
ys
RElAy#1 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp2, Unldr for Cmp3
Disabled
RElAy#2 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp3
Disabled
RElAy#3 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp2
Disabled
COMP HP Once compressor type is selected, the HP of each com-pressor can be set. 0.1 HP to 50.0 HP 5.0 HP
Varia
ble
Spee
d MIN SPEED Minimum speed for variable speed compressors. 6.0 Hz to 60.0 Hz 6.0 Hz
VOlTAgE Select output for variable speed compressors. 0 to 10VDC or 0 to 5VDC 0 to 10VDC
Def
rost
lo
ad MAx lOAD Maximum load, in BTU or AMPs, that the circuit can sustain at one time.②
0 Amps to 15,000 Amps0 BTU TO 6,000,000 BTU 80 Amps
UNITS Units for heater or refrigeration load during defrost. ② Amps/Btu Amps
Refr
iger
ation
FIxeD/FlOAT SuCTIOn Select whether target suction pressure can float accord-ing to room temperature. Fixed Suction, Float Suction Fixed
Suction
REFRIgERANT Referigerant used in the system.R-404A, R-507, R-407A, R-407C, R-422A, R-422D, R-134A, R-22, R-717, R-438A, R-408A, R-409A, R-407F, R-410A, R-744, R-448A, R-449A, R-450A, R-513A
R-404A
SUCTION PRESSURE Target suction pressure the controller works to maintain. 0 to 150 psig* *Max for R410A: 300 psig; R744: 500 psig
25 psig , 250 psig for R-744
ROOM TEMP Room temperature setpoint for suction float. -50.0°F to 90.0°F (-45.5°C to 32.2°C) -10.0°F
SUC PRESS DIFF
Suction Pressure Differential – when all compressor are set to fixed speed, controller will load and unload stages outside of this range. For digital and variable speed compressors, determines ideal range for suction pressure (target suction pressure ± the differential).
0.1 psi to 5.0 psi 2.0 psi
2ND ROOM TEMPWhen 2nd Temp Digital Input is active, this value be-comes the new room temperature setpoint for suction float.
-50.0°F to 90.0°F (-45.5°C to 32.2°C) -50.0°F (-45.5°C)
2ND SUCTION PRESSURE
When 2nd Pres Digital Input is active, this value becomes the new target suction pressure.
0 to 150 psig* *Max for R410A: 300 psig; R744: 500 psig 50.0 psig
MIN STAgE DElAy TIME Minimum time between switching stages. 2 sec to 240 sec 15 secMIN COMP RUNTIME Minimum time compressor must run before turning off. 0 sec to 240 sec 60 seconds
CUT OUT PRESSURE System turns completely off when suction pressure drops below this pressure.
0 to 150 psig* *Max for R410A: 300 psig; R744: 500 psig 5.0 psig
MIN COMP OFFTIME Minimum time compressor must be off before turning on. 0 sec to 240 sec 60 seconds
MAx PUMP OUT TIME Sets maximum time to reach cut-out pressure. 0 min to 240 min 2 minutes
TEMP UNITS Temperature Units Fahrenheit, Celsius Fahrenheit
Tem
p /
Dig
ital
Inpu
ts
INPUT 1 MODE Select function for Input 1 on the Main Board. Disabled, In Cmp Temp, Room Temp. Monitor, HG Defr Req, 2nd Pres, 2nd Temp, Comp Module, Hi Pres Safety, Oil Safety, Sys Off
Disabled
INPUT2 MODE Select function for Input 2 on the Main Board. Disabled
INPUT 3 MODE Select function for Input 3 on the Main Board. Disabled
INPUT 1 STATE Select active state for Input 1. Closed, Open Closed
INPUT2 STATE Select active state for Input 2. Closed, Open Closed
INPUT3 STATE Select active state for Input 3. Closed, Open Closed
Q.2.60 March 2019Page 26
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Q.2.60 March 2019Page 27
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Webpage Setpoints - Main Board (continued) The following setpoints are available on the broswer interface of the Main Board.
Setpoint Description Range / Options Default
Sens
or O
ffset
s
SUCT PRESS OFFSET An offset added or subtracted from the suction pressure transducer reading, if needed. -5.0 psi to 5.0 psi 0 psi
SUCT TEMP OFFSET An offset added or subtracted from the suction tempera-ture sensor reading, if needed. -5.0 to 5.0 0
DISCH PRESS OFFSET An offset added or subtracted from the discharge pressure transducer reading, if needed. -5.0 psi to 5.0 psi 0 psi
DISCH TEMP OFFSET An offset added or subtracted from the discharge tem-perature sensor reading, if needed. -5.0 to 5.0 0
Aux 1 (MAIn BOARD InPuT 1) TeMP OFFSeT
An offset added or subtracted from the Input 1 tempera-ture sensor reading, if needed. -5.0 to 5.0 0
Aux 2 (MAIn BOARD InPuT 2) TeMP OFFSeT
An offset added or subtracted from the Input 2 tempera-ture sensor reading, if needed. -5.0 to 5.0 0
Aux 3 (MAIn BOARD InPuT 3) TeMP OFFSeT
An offset added or subtracted from the Input 3 tempera-ture sensor reading, if needed. -5.0 to 5.0 0
PID
PROPORTIONAl CMP
Should not be adjusted unless instructed to by KE2 Therm technical support.
0 to 255 1
INTEgRAl CMP 0 to 255 1
DERIVATIVE CMP 0 to 255 0
PID TIME CMP 0 second to 255 seconds 1 second
Ala
rms
MIN SAFETy SUC SHMinimum Safety Suction Superheat. Provides a warning that suction line is low SH before triggering a critical low SH alarm.
0.0°F to 50.0°F (0.0°C to 27.8°C) 0.0°F
MIN SUCTION SHMinimum Suction Superheat. The lowest acceptable superheat for the suction line. Turns system off when exceeded longer than Min/Max SH Del.
5.0°F to 50.0° F (2.8°C to 27.8°C) 15.0°F
MAx SAFETy SUC TMP Max Safety Suction Temp. Provides a warning that suc-tion line temp is high. 5.0°F to 90.0°F (-15.0°C to 32.2°C) 90.0°F
MAx SUCTION SH Max Suction Superheat. Provides a warning that suction SH is high when exceeded longer than Min/Max SH Del. 25.0°F to 200.0°F (13.9°C to 111.1°C) 50.0°F
MAx SAFETy PRESSUREMax Safety Discharge Pressure. Discharge pressure above this value triggers High Safety Discharge Pressure alarm. Group will stop loading stages, and begin to unload.
0.0 psig to 500.0 psig 400.0 psig
MIn/MAx SH DelMin/Max Superheat Alarm Delay. Amount of time before a Min Suction SH or Max Suction SH alarm is triggered after exceeding the threshold.
0 to 254 minutes*Type 255 or ‘dis‘ and save to disable. Disabled
MAx DISCH TEMPMaximum Discharge Temp. Triggers alarm and turns system off when discharge temp exceeds this value longer than Max Dis Tmp Del.
25.0°F to 300.0°F (-3.9°C to 148.9°C) 268.0°F
MAx DIS TMP DEl Max Discharge Temp Delay. The amount of time before an alarm is initiated when Max Disch Temp is exceeded.
0 to 254 minutes*Type 255 or ‘dis‘ and save to disable. Disabled
MAx DISCH PRESMaximum Discharge Pressure. Triggers alarm and turns system off when discharge pressure exceeds this value longer than Max Dis Pres Del.
100.0 to 500.0 psig 450.0 psig
MAx DIS PRS DElMax Discharge Pressure Delay. The amount of time before an alarm is initiated when Max Disch Pres is exceeded.
0 to 254 minutes*Type 255 or ‘dis‘ and save to disable. Disabled
① Only one variable speed or digital scroll compressor can be selected per group.
② Function not currently implemented in most applications.
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 28
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Webpage Setpoints - Auxiliary Relay BoardThe following setpoints are available on the broswer interface of the Auxiliary Relay Board.
Setpoint Description Range / Options Default
Rela
ys
RElAy#1 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp2, Unldr for Cmp3, Unldr for Cmp4, Unldr for Cmp5
Disabled
RElAy#2 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp3, Unldr for Cmp4, Unldr for Cmp5
Disabled
RElAy#3 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp2, Unldr for Cmp4, Unldr for Cmp5
Disabled
RElAy#4 Controls one stage or component.Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp2, Unldr for Cmp3, Unldr for Cmp5
Disabled
RElAy#5Not available on some setups Controls one stage or component.
Disabled, Fixed Speed, Variable Speed①, Digital①, HG Defr Relay, LLS, Unldr for Cmp1, Unldr for Cmp2, Unldr for Cmp3, Unldr for Cmp4
Disabled
COMP HP Once compressor type is selected, the HP of each compressor can be set. 0.1 HP to 50.0 HP 5.0 HP
Dig
ital I
nput
s INPUT2 MODE ②③ Select function for Input 2. Disabled, Int Cmp Temp, Room Temp, Monitor, HG Defr Req, 2nd Pres, 2nd Temp, Comp Module, Hi Pres Switch, Oil Safety Sw, Sys Off
Disabled
INPUT 3 MODE Select function for Input 3. Disabled
INPUT2 STATE Select active state for Input 2. Closed, Open Closed
INPUT3 STATE Select active state for Input 3. Closed, Open Closed
Aux
Inpu
ts
Aux InPuT1 (RelAy BOARD) OFFSeT
An offset added or subtracted from the Aux Input 1 pressure transducer reading on the Aux Relay Board, if needed.
-5.0 psi to 5.0 psi 0 psi
Aux InPuT2 (RelAy BOARD) OFFSeT
An offset added or subtracted from the Aux Input 2 temperature sensor reading on the Aux Relay Board, if needed.
-5.0 to 5.0 0
Aux InPuT3 (RelAy BOARD) OFFSeT
An offset added or subtracted from the Aux Input 3 temperature sensor reading on the Aux Relay Board, if needed.
-5.0 to 5.0 0
① Only one variable speed or digital scroll compressor can be selected per group.
② In dual suction group applications, Input 2 on Aux Relay Board 2 acts as suction temperature sensor for group 2.
③ In dual suction group applications with independent discharge, Input 2 on Aux Relay Board 1 acts as discharge temperature sensor for group 2.
Q.2.60 March 2019Page 29
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Clic
k th
e ic
on t
o br
ing
up
a re
al t
ime
view
of t
he r
ack.
Clic
k th
e be
ll ic
on t
o vi
ew c
urre
nt a
larm
s.
Flas
hing
red
= C
ritic
al
Yel
low
= C
autio
nary
Clic
k to
dis
play
con
trol
ler
info
rmat
ion
(Loc
atio
n, IP
ad
dres
s, M
AC
add
ress
, Fi
rmw
are
vers
ion.
)
Exam
ple
of M
obile
Vie
w
Bri
ngs
up t
he
Sta
tus
page
fo
r th
at A
ux
Rel
ay B
oard
Bri
ngs
up t
he
Sta
tus
page
fo
r th
at A
ux
Rel
ay B
oard
Bri
ngs
up t
he
Set
poin
ts p
age
for
that
Suc
tion
Gro
up.
Bri
ngs
up t
he
Set
poin
ts p
age
for
that
Suc
tion
Gro
up.
KE2
The
rm c
onta
ct
info
rmat
ion
and
link
to w
ebsi
te
Des
crip
tion
:Fr
om th
e H
ome
page
, the
use
r can
acc
ess
the
Stat
us &
Set
poin
ts p
age
for t
he M
ain
Boar
d, a
s w
ell
as th
e St
atus
pag
e fo
r any
Aux
iliar
y Re
lay
Boar
ds.
Hom
e Pa
ge
Home Page
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 30
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Ret
urns
to
the
Hom
e pa
ge.
Sta
tus
bar:
sho
ws
curr
ent
stat
us o
f gro
up,
and
seco
nds
to c
ount
dow
n to
the
nex
t st
age.
Clic
k to
go
to
Set
poin
ts p
age
for
that
su
ctio
n gr
oup.
Gro
up’s
nam
e an
d co
ntro
l met
hod.
Clic
k on
the
bar
to
expa
nd o
r co
llaps
e th
e vi
ew fo
r th
at s
uctio
n gr
oup
Sta
tus
of
each
rel
ay
Clic
k on
Suc
tion
Pre
ssur
e di
al t
o zo
om in
.
Tota
l % o
f co
mpr
esso
r ca
paci
ty u
sed
for
the
suct
ion
grou
p.
Scr
oll d
own
to v
iew
the
nex
t gr
oup.
Sen
sor
& D
igita
l In
put
valu
es
upda
ted
in r
ealti
me.
Sen
sor
& S
yste
m In
form
atio
nG
auge
col
or:
Gre
en =
Pre
ssur
e in
ran
geB
lue
= T
empe
ratu
re in
ran
geY
ello
w =
Out
of o
ptim
al r
ange
Red
= A
larm
ran
ge
Des
crip
tion
:Re
al ti
me
syst
em p
erfo
rman
ce in
form
atio
n fo
r the
Mai
n Bo
ard
and
any
Auxi
liary
Rel
ay B
oard
s.
Stat
us P
age
- Mai
n Bo
ard
Status Page - Main Board
Q.2.60 March 2019Page 31
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Status Page- Auxiliary Board
Des
crip
tion
:Re
al t
ime
syst
em p
erfo
rman
ce in
form
atio
n fo
r th
e Au
xilia
ry R
elay
Boa
rd. T
he u
ser
also
des
igna
tes
rela
ys a
nd d
eter
min
es th
e fu
nctio
n of
sel
ecta
ble
inpu
ts fr
om th
is p
age.
Stat
us P
age
- Aux
iliar
y Bo
ard
Dis
play
the
sta
tus
of
each
Aux
Rel
ay B
oard
in
put.
Clic
k to
set
the
func
tion
of t
he in
put,
if av
aila
ble.
Dis
play
s st
atus
of e
ach
rela
y, a
nd a
nalo
g ou
tput
, fo
r va
riab
le s
peed
co
mpr
esso
rs.
Clic
k on
the
icon
to
set
the
fuct
ion
of e
ach
rela
y.
For
com
pres
sors
, sav
e th
e ty
pe o
f com
pres
sor
first
, the
n en
ter
the
HP
of
the
com
pres
sor,
and
cl
ick
save
aga
in
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 32
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Bas
ic (P
ort
25
) K
E2 T
herm
Def
ault
Ser
ver
Upd
ate
firm
war
e.
Ref
er to
Q.5
.6 K
E2
Boo
tload
er G
uide
.
Sta
ndar
dS
iteV
iew
MA
NA
GER
Req
uire
d to
Log
in t
o m
ake
chan
ges
to S
ettin
gs p
age.
See
pag
e 3
3.
Rem
otel
y re
boot
s th
e co
ntro
ller.
Use
to v
erify
pro
per
e-m
ail
conf
igur
atio
n. C
lick
Save
bu
tton
(bot
tom
rig
ht o
f pag
e)
befo
re te
stin
g
Rem
oves
all
data
st
ored
by
cont
rolle
r. D
o no
t use
unl
ess
inst
ruct
ed to
by
KE2
Th
erm
.
Res
ets
cont
rolle
r’s
alar
ms
and
alar
m
cond
ition
s.
Cus
tom
er in
form
atio
n is
di
spla
yed
Use
to
veri
fy
prop
er A
PI
conf
igur
atio
n
Def
ines
the
con
trol
ler
loca
tion
for
KE2
Sm
art
Acc
ess
and
alar
m
notif
icat
ions
Cus
tom
er m
ay in
put
thei
r co
mpa
ny in
form
atio
n
Sel
ect
rack
con
figur
atio
n an
d re
nam
e gr
oups
(e
x. M
T S
uctio
n G
roup
, LT
Suc
tion
Gro
up e
tc.):
Sin
gle
Gro
upS
ingl
e G
roup
plu
s 1
Aux
Sin
gle
Gro
up p
lus
2 A
uxD
ual G
roup
Sha
red
Dis
char
ge p
lus
2 A
uxD
ual G
roup
Inde
pend
ent
plus
2 A
ux
Site
and
Pas
swor
d m
ay b
e ch
ange
d by
cus
tom
er t
o cr
eate
a
uniq
ue K
E2 S
mar
t A
cces
s lo
gin
for
acce
ssin
g th
e co
ntro
ller
rem
otel
y th
roug
h K
E2
Sm
artA
cces
s.
Use
to
cust
omiz
e th
e U
ser
Nam
e an
d P
assw
ord
from
the
def
ault
sett
ing.
The
cre
dent
ials
are
ne
cess
ary
to c
hang
e S
etpo
ints
, S
ettin
gs a
nd N
etw
ork
optio
ns fr
om
the
Mas
terV
iew
scr
eens
.
Use
to
rece
ive
e-m
ail/
text
ale
rts
Sub
ject
for
e-m
ail/
text
ale
rts
Des
crip
tion
:Th
e Se
ttin
gs p
age
is w
here
com
pres
sor (
rack
) con
figur
atio
n is
save
d. T
his m
ust b
e se
t bef
ore
the
syst
em c
an ru
n. T
he S
ettin
gs p
age
also
co
ntai
ns c
ontr
olle
r con
figur
atio
n fo
r e-m
ail a
nd w
eb a
cces
s.
It al
so a
llow
s ins
talle
rs to
cus
tom
ize
the
Mas
terV
iew
with
thei
r com
pany
info
rmat
ion,
show
n un
der L
ocat
ion
Sett
ings
. The
Set
tings
pag
e in
clud
es th
e bu
tton
s to
upd
ate
the
cont
rolle
r, re
set p
ower
to th
e co
ntro
ller,
send
a te
st e
-mai
l, cl
ear d
ata
colle
cted
, and
cle
ar a
larm
s.
Settings Page
Setti
ngs P
age
Q.2.60 March 2019Page 33
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
To m
ake
chan
ges
to t
he S
ettin
gs p
age,
Net
wor
k pa
ge a
nd S
etpo
ints
pa
ge t
he U
ser
Nam
e an
d P
assw
ord
mus
t be
pro
vide
d.
Def
ault
Use
r N
ame:
ke2
adm
in
D
efau
lt P
assw
ord:
ke2
adm
in
For
secu
rity
rea
sons
, the
Use
r N
ame
and
Pas
swor
d sh
ould
be
chan
ged
from
the
def
ault.
Onc
e yo
u ar
e lo
gged
in, g
o to
the
S
ettin
gs p
age
to c
hang
e th
e U
ser
Nam
e an
d P
assw
ord.
To m
ake
chan
ges
to t
he A
ux R
elay
B
oard
, th
e us
er w
ill b
e pr
ompt
ed
for
the
Use
r N
ame
and
Pas
swor
d if
not
alre
ady
logg
ed in
. The
def
ault
logi
n cr
eden
tials
are
the
sam
e as
th
e M
ain
Boa
rd.
U
ser
Nam
e: k
e2ad
min
Pas
swor
d: k
e2ad
min
Des
crip
tion
:Th
e Lo
gin
feat
ure
prev
ents
una
utho
rized
acc
ess
to th
e co
ntro
ller.
The
user
mus
t ent
er th
e U
ser N
ame
and
Pass
wor
d to
mak
e ch
ange
s to
the
Sett
ings
pag
e, N
etw
ork
page
, Se
tpoi
nts
page
, and
Aux
Rel
ay B
oard
s.
Login Page
Logi
n Pa
ge
Logi
n Pa
ge -
Aux
Rela
y Bo
ard
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 34
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
IP A
ddre
ss m
ay b
e ch
ange
d to
mat
ch
the
onsi
te n
etw
ork.
Ty
pica
lly th
e su
bnet
m
ask,
gat
eway
and
pr
imar
y D
NS
shou
ld
also
be
chan
ged.
Net
wor
k se
ttin
gs m
ay b
e ch
ange
d to
mat
ch c
usto
mer
’s
envir
onm
ent.
DH
CP C
lient
Mod
e is
En
able
d or
Dis
able
dEn
able
d - I
P is
Dyn
amic
Dis
able
d - I
P is
Sta
tic
Show
s In
tern
et c
onne
ctio
n st
atus
:R
ed =
Una
ble
to r
each
Inte
rnet
Yello
w =
Som
e In
tern
et s
ervic
es
unav
aila
ble
Gre
en =
Goo
d In
erne
t con
nect
ion
NO
TE: D
o no
t m
odify
the
C
ontr
olle
r N
ame.
Ch
ange
“Loc
atio
n” o
n th
e Se
ttin
gs p
age
to e
asily
id
entif
y co
ntro
llers
.
Pre
vent
s un
auth
oriz
ed a
cces
s to
the
co
ntro
ller.
Use
r m
ust
ente
r U
ser
Nam
e an
d P
assw
ord
to m
ake
chan
ges
to t
he N
etw
ork
Set
up p
age.
Sav
es c
hang
es t
o th
e co
ntro
ller’
s ne
twor
k.
Des
crip
tion
:A
llow
s us
ers
to c
hang
e th
e co
ntro
ller’s
net
wor
k se
ttin
gs, i
n or
der t
o ad
d co
ntro
llers
to a
n ex
istin
g cu
stom
er n
etw
ork.
Net
wor
k Pa
ge
Network Page
Q.2.60 March 2019Page 35
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Des
crip
tion
:A
llow
s th
e us
er to
set
up th
e co
ntro
ller,
and
to c
usto
miz
e th
e co
ntro
ller t
o m
eet s
peci
fic a
pplic
atio
n ne
eds.
The
KE2
Com
pres
sor S
eque
ncer
OEM
beg
ins
in S
yste
m O
ff M
ode.
The
use
r mus
t con
figur
e re
lays
and
refr
iger
atio
n se
tpoi
nts
to e
nsur
e th
e sy
stem
will
run
prop
erly
, the
n tu
rn th
e sy
stem
on.
The
scre
ensh
ot b
elow
sho
ws
the
Setp
oint
s pa
ge w
hen
no A
ux R
elay
Boa
rds
are
used
.
Setp
oint
s Pag
e -
mai
n Bo
ard
Onl
y - n
O a
ux R
elay
Boa
rds
Setpoints Page -Single Group - Main Board Only
Det
erm
ines
if t
he
Inpu
t is
act
ive
whe
n it
dete
cts
an O
pen
or
Clo
sed
circ
uit,
and
a D
igita
l Inp
ut is
as
sign
ed a
s th
e in
put
func
tion.
Inpu
t 1
, 2 o
r 3
Mod
e
Dis
able
dIn
Cm
p Te
mp
Roo
m T
emp
Mon
itor
HG
Def
r R
eq
2nd
Pre
s2
nd T
mp
Com
p M
odul
eH
i Pre
s S
afet
yO
il S
afet
y
Sys
Off
Sel
ecta
ble
Inpu
ts
Rel
ay 1
D
ropd
own
Opt
ions
Dis
able
dFi
xed
Spe
edV
aria
ble
Spe
edD
igita
lH
G D
efr
Rel
ayLL
SU
nldr
for
Com
p 2
Unl
dr fo
r C
omp
3
Rel
ay 2
- 3
Dro
pdow
n O
ptio
nsA
ll R
elay
Opt
ions
are
the
sa
me
as R
elay
1, e
xcep
t th
e lis
t of
Unl
oade
rs fo
r th
e co
mpr
esso
r ne
ver
incl
udes
th
e ac
tive
com
pres
sor.
Fixe
d S
uctio
n Fl
oat
Suc
tion
Fahr
enhe
it C
elsi
usB
tuA
mp
R-4
04
AR
-50
7R
-40
7A
R-4
07
CR
-42
2A
R-4
22
DR
-13
4a
R-2
2R
-71
7R
-43
8A
R-4
08
AR
-40
9A
R-4
07
FR
-41
0A
R-7
44
R-4
48
AR
-44
9A
R-4
50
R-5
13
A
Onc
e co
mpr
esso
rs a
re
sele
cted
and
sav
ed, H
P
shou
ld b
e en
tere
d fo
r ea
ch.
Indi
cate
s w
heth
er s
yste
m is
ru
nnin
g or
pum
ped
dow
n.
Clic
k to
put
sys
tem
into
pu
mpd
own
mod
e.
Sho
ws
whi
ch S
uctio
n G
roup
s se
tpoi
nts
are
bein
g di
spla
yed.
0 t
o 1
0 V
DC
0 t
o 5
VD
C
Sav
es c
hang
e to
the
S
etpo
ints
pag
e. M
ust
be lo
gged
in t
o sa
ve.
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 36
KE2 Compressor Sequencer OEM pn 21768
Quick Start GuideD
escr
ipti
on:
Allo
ws
the
user
to s
etup
the
cont
rolle
r, an
d to
cus
tom
ize
the
cont
rolle
r to
mee
t spe
cific
app
licat
ion
need
s.
The
KE2
Com
pres
sor S
eque
ncer
OEM
beg
ins
in S
yste
m O
ff M
ode.
The
use
r mus
t con
figur
e re
lays
and
re
frig
erat
ion
setp
oint
s to
ens
ure
the
syst
em w
ill ru
n pr
oper
ly, t
hen
turn
the
syst
em o
n.
The
scre
ensh
ot b
elow
sho
ws
the
Setp
oint
s pa
ge w
hen
one
or tw
o Au
x Bo
ards
are
use
d. N
ote
whe
n tw
o su
ctio
n gr
oups
are
use
d, e
ach
suct
ion
grou
p w
ill h
ave
its o
wn
Setp
oint
s pa
ge
Setp
oint
s Pag
e -
Mai
n Bo
ard
+ Au
x Re
lay
Boar
d(s)
Inpu
t 1
, 2 o
r 3
Mod
e
Dis
able
dIn
Cm
p Te
mp
Roo
m T
emp
Mon
itor
HG
Def
r R
eq
2nd
Pre
s2
nd T
mp
Com
p M
odul
eH
i Pre
s S
afet
yO
il S
afet
y
Sys
Off
Sel
ecta
ble
Inpu
ts
Fahr
enhe
it C
elsi
us
0 t
o 1
0 V
DC
0 t
o 5
VD
C
R-4
04
AR
-50
7R
-40
7A
R-4
07
CR
-42
2A
R-4
22
DR
-13
4a
R-2
2R
-71
7R
-43
8A
R-4
08
AR
-40
9A
R-4
07
FR
-41
0A
R-7
44
R-4
48
AR
-44
9A
R-4
50
AR
-51
3A
Indi
cate
s w
heth
er s
yste
m is
ru
nnin
g or
pum
ped
dow
n.
Clic
k to
put
sys
tem
into
pu
mpd
own
mod
e.
Sho
ws
whi
ch S
uctio
n G
roup
s se
tpoi
nts
are
bein
g di
spla
yed.
Fixe
d S
uctio
n P
ress
ure
Floa
t S
uctio
n P
ress
ure
Det
erm
ines
if t
he
Inpu
t is
act
ive
whe
n it
dete
cts
an O
pen
or
Clo
sed
circ
uit,
and
a D
igita
l Inp
ut is
as
sign
ed a
s th
e in
put
func
tion.
Sav
es c
hang
es t
o th
e S
etpo
ints
pag
e.
Use
r m
ust
be
logg
ed in
to
save
.
Setpoints Page -Main Board + Aux Relay Board(s)
Q.2.60 March 2019Page 37
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Exam
ple:
5.0
69
C
ap L
oad
44
.8
Suc
t P
res
22
Wee
kly
view
Mon
thly
vie
w
Cur
rent
act
ivity
Wri
tes
the
data
sto
red
on t
he
cont
rolle
r to
a C
SV
file
.
Dat
e an
d Ti
me
are
pulle
d fr
om t
he c
onne
cted
co
mpu
ter.
Day
s A
go, C
apac
ity L
oad,
and
S
uctio
n P
ress
ure
are
disp
laye
d w
hen
mov
ing
the
mou
se o
ver
the
data
.
Day
s ag
o
Des
crip
tion
:Th
e G
raph
ing
Snap
shot
sho
ws
the
past
sev
en d
ays
of C
apac
ity L
oad
and
Suct
ion
Pres
sure
re
adin
gs. I
t is
esse
ntia
l for
sys
tem
ana
lysi
s an
d tr
oubl
esho
otin
g.
The
expe
rts
at K
E2 Te
chni
cal S
uppo
rt c
an h
elp
trou
bles
hoot
you
r sys
tem
usi
ng th
is in
form
atio
n
Graphs Page
Gra
phs P
age
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 38
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Alphabetical List of Abbreviations
Abbreviation Full Name Type Description
A01 A01 Suction Pres Sensor [Group 1] Alarm Alarm - Critical Group 1 suction pressure sensor is shorted, open or pressure
out of range.
A02 A02 Disch Pres Sensor [Group 1] Alarm Alarm - Critical Group 1 discharge pressure sensor is shorted, open or pres-sure out of range.
A03 A03 Suction Temp Sensor [Group 1] Alarm Alarm - Critical Group 1 suction temperature sensor is shorted or open.
A04 A04 Disch Temp Sensor [Group 1] Alarm - Critical Group 1 discharge temperature sensor is shorted or open.
A06 A06 High Superheat [Group 1] Alarm Alarm - Cautionary Group 1 suction superheat is higher than Max Suction SH for longer than Min/Max SH Del.
A07 A07 Low Superheat [Group 1] Alarm Alarm - Critical Group 1 suction superheat is lower than Min Suction SH for longer than Min/Max SH Del.
A08 A08 High Disch Temp [Group 1] Alarm Alarm - Critical Group 1 discharge temperature is higher than Max Disch Temp for longer than Max Dis Tmp Del.
A09 A09 High Int Comp Temp [Group 1] Alarm Alarm - Cautionary Group 1 digital compressor internal temp high. Will turn off
digital compressor until temp lowers.
A10 A10 High Disch Pres [Group 1] Alarm Alarm - Critical Group 1 discharge pressure is higher than Max Disch Pres for longer than Max Dis Prs Del.
A13 A13 Comp Mod [Group 1] Alarm Alarm - Cautionary Group 1 Compressor Module digital input is active.A16 A16 Oil Safety [Group 1] Alarm Alarm - Cautionary Group 1 Oil Safety digital input is active.A19 A19 Hi Pres Safety [Group 1] Alarm Alarm - Cautionary Group 1 High Pressure Safety digital input is active.A22 A22 Aux Brd Comms Alarm Alarm - Critical Main Board unable to communicate w. the Aux Relay Boards.A25 A25 Watchdog Alarm Alarm - Cautionary Contact KE2 Therm.
A26 A26 Email Failure Alarm Alarm - Cautionary Email alert was not confirmed by email server provided after seven consecutive attempts.
A28 A28 High Disch Temp [Group 2] Alarm Alarm - Critical Group 2 discharge temperature is higher than Max Disch Temp for longer than Max Dis Tmp Del.
A29 A29 Evap Comms [Group 1] Alarm Alarm - Cautionary Group 1 Siteview controllers not communicating.A30 A30 Evap Comms [Group 2] Alarm Alarm - Cautionary Group 2 Siteview controllers not communicating.
A31 A31 Disch Pres Sensor [Group 2] Alarm Alarm - Critical Group 2 discharge pressure sensor is shorted, open or pres-sure out of range.
A32 A32 Suction Temp Sensor [Group 2] Alarm Alarm - Critical Group 2 suction temperature sensor is shorted or open.
A34 A34 High Superheat [Group 2] Alarm Alarm - Cautionary Group 2 suction superheat is higher than Max Suction SH for longer than Min/Max SH Del.
A35 A35 Low Superheat [Group 2] Alarm Alarm - Critical Group 2 suction superheat is lower than Min Suction SH for longer than Min/Max SH Del.
A36 A36 Disch Temp Sensor [Group 2] Alarm Alarm - Critical Group 2 discharge temperature sensor is shorted or open.
A37 A37 High Int Comp Temp [Group 2] Alarm Alarm - Cautionary Group 2 digital compressor internal temp high. Will turn off
digital compressor until temp lowers.
A38 A38 High Disch Pres [Group 2] Alarm Alarm - Critical Group 2 discharge pressure is higher than Max Disch Pres for longer than Max Dis Prs Del.
A41 A41 Suction Pres Sensor [Group 2] Alarm Alarm - Critical Group 2 suction pressure sensor is shorted, open or pressure
out of range.A44 A44 Comp Mod [Group 2] Alarm Alarm - Cautionary Group 2 Compressor Module digital input is active.A47 A47 Oil Safety [Group 2] Alarm Alarm - Cautionary Group 2 Oil Safety digital input is active.A50 A50 Hi Pres Safety [Group 2] Alarm Alarm - Cautionary Group 2 High Pressure Safety digital input is active.
A53 A53 Main: Aux Input 1 Sensor [Group 1] Alarm Alarm - Cautionary Main Board, Aux Input 1 Sensor is shorted or open.
A54 A54 Main: Aux Input 2 Sensor [Group 1] Alarm Alarm - Cautionary Main Board, Aux Input 2 Sensor is shorted or open.
A55 A55 Main: Aux Input 3 Sensor [Group 1] Alarm Alarm - Cautionary Main Board, Aux Input 3 Sensor is shorted or open.
A56 A56 Aux Addr 1: Input 2 Sensor [Group 1] or [Group 2] Alarm Alarm - Cautionary Aux Board 1, Input 2 Sensor is shorted or open.
Q.2.60 March 2019Page 39
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Alphabetical List of Abbreviations (continued)
Abbreviation Full Name Type Description
A57 A57 Aux Addr 1: Input 3 Sensor [Group 1] or [Group 2] Alarm Alarm - Cautionary Aux Board 1, Input 3 Sensor is shorted or open.
A58 A58 Aux Addr 2: Input 2 Sensor [Group 1] or [Group 2] Alarm Alarm - Cautionary Aux Board 2, Input 2 Sensor is shorted or open.
A59 A59 Aux Addr 2: Input 3 Sensor [Group 1] or [Group 2] Alarm Alarm - Cautionary Aux Board 2, Input 3 Sensor is shorted or open.
ClA CLA Clear Alarms Setpoints - Single Group, Setpoint - Dual Group Press and hold ENTER to clear all active alarms.
dH1 dH1 Discharge Superheat - Group1 Variables - Dual Group Group 1 Discharge Superheat as calculated by the controller.dH2 dH2 Discharge Superheat - Group1 Variables - Dual Group Group 2 Discharge Superheat as calculated by the controller.
dHC dHC DHCP mode Setpoints - Single Group, Setpoint - Dual Group
Turn DHCP mode on or off: EnA to enable / diS to disable DHCP mode.
dPr dPr Discharge Pressure Variables - Single group Discharge Pressure as read by the controller.dP1 dP1 Discharge Pressure - Group1 Variables - Dual Group Group 1 Discharge Pressure as read by the controller.dP2 dP2 Discharge Pressure - Group2 Variables - Dual Group Group 2 Discharge Pressure as read by the controller.
dS1 dS1 Discharge Saturation Temperature - Group1 Variables - Dual Group Group 1 Discharge Saturation Temperature as calculated by
the controller.
dS2 dS2 Discharge Saturation Temperature - Group2 Variables - Dual Group Group 2 Discharge Saturation Temperature as calculated by
the controller.
dSA dSA Discharge Saturation Temperature Variables - Single group Discharge Saturation Temperature as calculated by the controller.
dSH dSH Discharge Superheat Variables - Single group Discharge Superheat as calculated by the controller.dSt dSt Discharge Temperature Variables - Single group Discharge Temperature as read by the controller.dt1 dt1 Discharge Temperature - Group1 Variables - Dual Group Group 1 Discharge Temperature as read by the controller.dt2 dt2 Discharge Temperature - Group2 Variables - Dual Group Group 2 Discharge Temperature as read by the controller.
FiR Fir Firmware Version Variables - Single groupVariables - Dual Group Current firmware version on the controller.
iP1 iP1 IP Octet 1Variables - Dual GroupVariables - Single group
First three digits of the IP address.iP2 iP2 IP Octet 2 Second three digits of the IP address.iP3 iP3 IP Octet 3 Third three digits of the IP address.iP4 iP4 IP Octet 4 Fourth three digits of the IP address.oF1 oF1 System Off – Group 1 Default Display Group 1 is in System Off mode.
oF2 oF2 System Off – Group 2 Default Display Group 2 is in System Off mode.
PAS PAS web Password Reset Setpoints - Single Group Setpoint - Dual Group Press and hold ENTER to reset browser password.
Pr1 Pr1 Suction Pressure - Group1 Variables - Dual Group Group 1 Suction Pressure as read by the controller.Pr2 Pr2 Suction Pressure - Group2 Variables - Dual Group Group 2 Suction Pressure as read by the controller.PrS PrS Suction Pressure Variables - Single group Suction Pressure as read by the controller.
PS1 PS1 Target Suction Pressure - Group1 Setpoint - Dual Group Target Suction Pressure - Suction pressure the controller will work to maintain for group 1.
PS2 PS2 Target Suction Pressure - Group2 Setpoint - Dual Group Target Suction Pressure - Suction pressure the controller will work to maintain for group 2.
PSP PSP Target Suction Pressure Setpoints - Single Group Target Suction Pressure - Suction pressure the controller will work to maintain.
S01 S01 Low Safety SH 1 [Group 1] Alarm Alarms - Safety / Preemptive Group 1 suction superheat is below Min Safety Suc SH for more than 5 minutes.
S02 S02 High Safety Suc Temp 1 [Group 1] Alarm Alarms - Safety / Preemptive Group 1 suction temperature is above Max Safety Suc Tmp
for more than 5 minutes.
S03 S03 High Safety Disch Pres 1 [Group 1] Alarms - Safety / Preemptive
Group 1 discharge pressure is above Max Safety Pres-sure. Controller will attempt to unload stages and not load anymore stages until pressure is well below Max Safety Pressure.
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.60 March 2019Page 40
KE2 Compressor Sequencer OEM pn 21768
Quick Start Guide
Alphabetical List of Abbreviations (continued)
Abbreviation Full Name Type Description
S11 S11 Low Safety SH 2 [Group 2] Alarm Alarms - Safety / Preemptive Group 2 suction superheat is below Min Safety Suc SH for more than 5 minutes.
S12 S12 High Safety Suc Temp 2 [Group 2] Alarm Alarms - Safety / Preemptive Group 2 suction temperature is above Max Safety Suc Tmp
for more than 5 minutes.
S13 S13 High Safety Disch Pres 2 [Group 2] Alarm Alarms - Safety / Preemptive
Group 2 discharge pressure is above Max Safety Pres-sure. Controller will attempt to unload stages and not load anymore stages until pressure is well below Max Safety Pressure.
SA SA KE2 Smart Access Setpoints - Single Group Setpoint - Dual Group
Turn KE2 Smart Access on or off: EnA to enable / diS to dis-able KE2 Smart Access.
SA1 SA1 Saturation Temperature - Group1 Variables - Dual Group Group 1 Saturated Suction Temperature as calculated by the controller.
SA2 SA2 Saturation Temperature - Group2 Variables - Dual Group Variables - Dual Group
Group 2 Saturated Suction Temperature as calculated by the controller.
SAt SAt Saturation Temperature Variables - Single group Saturated Suction Temperature as calculated by the controller.
SH1 SH1 Superheat - Group1 Variables - Dual Group Group 1 Suction Superheat as calculated by the controller.SH2 SH2 Superheat - Group2 Variables - Dual Group Group 2 Suction Superheat as calculated by the controller.SHt SHt Superheat Variables - Single group Suction Superheat as calculated by the controller.SU1 SU1 Suction Temperature - Group1 Variables - Dual Group Group 1 Suction Temperature as read by the controller.SU2 SU2 Suction Temperature - Group2 Variables - Dual Group Group 2 Suction Temperature as read by the controller.SUt SUt Suction Temperature Variables - Single group Suction Temperature as read by the controller.
Sy1 SY1
SY2
System On/Off - Group 1 Setpoint - Dual Group Allow group 1 to run or put into system off: on1 to run / oF1 to pump down group 1 and put into system off.
Sy2
SY1
SY2 System On/Off - Group 2 Setpoint - Dual Group Allow group 2 to run or put into system off: on2 to run / oF2 to pump down group 2 and put into system off.
SyS
SY1
SY2
System On/Off Setpoints - Single Group Allow rack to run or put into system off: on to run / oFF to pump down rack and put into system off.
KE2 Therm Solutions 12 Chamber Drive . Washington, MO 63090