—JULIO OLIVEIRA, ABB POWER GRIDS – GRID AUTOMATION, DECEMBER 01ST
ABB Ability - Digital SubstationsFISE 7a Edición
—Current challenges and changes facing utilities
December 11, 2017 Slide 2
Aging infrastructureLegecy systems with static or
eletromechanical relays, and evenfirst microprocessor based relays
Workforce in transitionMaintenance and operationengineering groups memberselegible for retirement in next fewyears.
ReliabilityThere´s increasing pressure to
continually improve reliabilityand customer satisfaction.
Spending justificationRevenue challenges and regulatoryinspection will drive thecosts/expenditure.
Cyber segurançaAttacks on critical infrastructure areincreasing in terms of regularity andsophistication.
Disruptive technologiesDigitalization techniques for
substation automation via IEC61850, concerns about cyber security
and asset management demandsattention by the utilities part.
Changes in business modelNew players are entering in energy
market, and among them are investorswho are non-utilities companies. This
group will be responsible by 20% oftransmission and distribution around the
world until 2020.
TrainingNetwork computers and itsprotocols, topologies andcommunication redundancy.
CostsMinimizeàOptimize
PerformanceExceedàMeet or beat
RisksAvoidàManage
$
—
Digital substations concepts
Protocols and Ethernet allocation
Communication network topologies
Cyber security approaches
Reference cases
Atlas Juazeiro: First full digital substation in South America
December 11, 2017 Slide 3
Iniciativa EletrobrasAgenda
—
Intelligentsubstation
HMI
SDM600Data
manager
How the digitalization is understood by the utilitiesDigital substation concepts and scenarios
December 11, 2017 Slide 4
Station bus
Process bus
Mobile workforcemanagement
CALMPlatformSCADA NCCDisturbanc
e records
Operation
Network control center
Super PDCPMUs
SCADA Level 2
RTU Gateway Level2
Cyber security
Mergingunits
Ability
Primary apparatus sensing
Control room perimeter
Teleprotection overMPLS with FOX615
1
2
3
4
7
xOpportunities to explore with digital substations- Process bus- Cyber security- MPLS/TP teleprotection- PMUs- Asset management- MESH industrial Wifi communication- Primary apparatus sensing
“A digitalized substation (no digital substation) doesn´t considers thegray areas!”
Asset Management
PMU and PDCs
WiFi Industrial
6
5
—A full Digital Substation
December 11, 2017 Slide 5
The resources available on an IEC 61850 station and process bus application with ABB Ability
AB
BA
bili
tyo
nd
igit
alsu
bst
atio
njo
urn
ey
• All the control copper cables from VTs, CTsand apparatus (circuit breaker anddisconnectors) to the control room arereplaced by optical fibers
• The SAM600 MUs converts the analog data from theswitchyard (voltage and current) in digital signalsprovided by the SMV protocol. The binaries inputsand output are, as well, encoded in GOOSE messagesover the Ethernet network and carried out togheterSMV data.
• The RELION protection and control IEDs offers 4redundant communication networks with zerolatency and switchover, avoiding loss ofinformation in this critical mission system incase of failures N-1
• The MicroSCADA supervisory system get data from theIEDs and show the real time status of the substationvia the single line diagrams, event and alarm lists. Thearchitecture of such system contains 2 GPS clocks tooffers a 1 microsecond synch time to the entirenetwork architecture
LEVEL 0The substationswichyard
LEVEL 0The SAM600 merging unitsIEC 61850-9-2 standard
LEVEL 1Control roomProtection and control IEDs
LEVEL 2Control roomMicroSCADA supervisorysystem
1
2
3
4
ABB AbilityTM
On Prem or Cloud
—A full Digital Substation
December 11, 2017 Slide 6
The benefits overview
Sceneries: From conventional to digital What happen inside the control room? The direct impacts of a digital substation
—
IEC 61850-8-1 and 9-2 togheterProtocols and Ethernet allocation
December 11, 2017 Sources: ABBSlide 7
The station and process bus togheter offers thefollowing services. using the 7 OSI layers:
Vertical communication over MMS: Data exchangeamong IEDs and supervisory system;Horizontal communication with GSE messages:Information between the IEDs;Process communication: GSE for binary signalsbetween the IEDs and the merging units, SMVmessages for analogs such as currents and voltages;IEEE 1588 (PTP) for devices synchronism, accuracyaround 1 µs;Network redundancy in IEC 62439-3 standard (PRPand HSR).
Protocols and services
1
2
3
GOOSE
SV,GOOSE
Bay 1
Processbus
Station bus
MergingUnit
Prot &CtrlDevices
StationComputer
Gateway
Bay n
SAM600SAM6004
—
The sampled values in process busProtocols and Ethernet allocation
December 11, 2017 Sources: ABBSlide 8
Which signals are transmitted in a SMV frame?Four currents, four voltages and their qualityinformation.
Merging units and SMV according IEC 61850-9-2LE
1
984 bitsThis is the size of atypical SMV frame
4800It´s the numberof samples in onesecond in a 60Hzfrequency rate
5Mb/sIt´s the Ethernetnetworkbandwidthallocated for asingle SMV frame
SMV frame captured with the IEC61850 State of art testing toolITT600
—Usage of PRP and HSE according IEC 62439-3Communication network topologies
December 11, 2017 Slide 9
PRP
HSR
Recommended to stationbus
Recommended toprocess bus
—
Unauthorized access or attackCyber security approaches
December 11, 2017 Slide 10
—
How to deal to cyber hazards & standardsCyber security approaches
December 11, 2017 Slide 11
IEC 62443*IEEE 1686 IEC62351* NERCCIP
There´s different standards to deal to sensitive data protection in a substation. These mechanisms are aligned to the digitalsubstation philosophy once the data and network communications were expanded with the introduction of process bus. Anyway, more
attention is requited from utilities regarding this issue
—
ABB’s IEC 61850 digital substation experienceReference cases
December 11, 2017 Slide 12
Pilot installationBraemar, AUGIS NCIT,670series
Pilot installationLaufenburg, CHGIS NCIT,670series, REB500
Pilot installationSvK, SEDCB with FOCS,670series
Pilot installationCHGIS NCIT,670series, 3rd party
Pilotinstallation UKGIS NCIT,670 series
Pilot installationNehden, DE3rd party NCIT,REB500
Real installationLoganlea, AUGIS NCIT,670series, REB500
Real installationMillmerran, AUGIS NCIT,670series, REB500
Pilot installationTPC, TWSAM600670series, 3rd party
Real installationBulli Creek, AU*GIS NCIT,670series, REB500
2009 2010 2011 2012 2013 2014 2015 2016 2017
Real installationUKSAM600, FOCS670series, 3rd party
Pilot installationCN (several)DCB with FOCS3rd party
Pilot installationVattenfall, SEAIS 3rd party NCIT,670, 630, 615series
Pilot installationUSDTB with FOCS,SAM600, 670 series
* 3 more projects under commissioning by utilityPilot projects are installations to verify technology and compare to traditional systemsReal projects are installations without traditional backup
Pilot installationNLGIS NCITL+G revenue meter
Pilot installationTPC, TWSAM600670series, 3rd party
Pilot installationBRSAM600670series
Real installationINSAM600670, 615 series
—
Stand-alone merging units pilot projects executed by ABB Brazil: ISA/Brazil and ICE/Costa RicaReference cases
December 11, 2017 Slide 13
Project description
- SAM600 installation in existing line transmission
Pilot experience
- Equipment installed and successfully commissioned inJune 2017
Stand-alone merging unit in Brazil
Project description
- SAM600 installation in existing capacitor bank 34,5kV
Pilot experience
- Equipment installed and successfully commissioned in July 2017
Stand-alone merging unit in CostaRica
—
First full digital substation in South AmericaAtlas Juazeiro
December 11, 2017 Slide 14
- A 230kV substation composed by 2 transmission lineand 1 power transformer;
- The solution applies all resources of IEC 61850-8-1 and9-2:
§ PRP network redundancy for station bus using Relion IEDsand MicroSCADA;
§ HSR network redundancy for process bus applying SAM600merging units;
§ PTP synchronization concerning about 1 us of accuracy;
§ Network traffic optimization for better performance;
§ SMV and GSE available in the process bus network;
§ Independent busbar voltages process bus network;
§ No switches (failure points) in process bus application, in amore robust solution including cyber security approach;
§ Flexible naming for Logical nodes and data objects;
§ Totally IEC 61850 Edition 2 compliant.
Atlas Juazeiro substation