jci data sheet a4 template rev. 07 - ansul

4
One Stanton Street | Marinette, WI 54143-2542, USA | +1-715-735-7411 | www.ansul.com © 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. | Form No. F-2020130-00_A4 DATA SHEET ANSUL® Connected Fire Container Monitoring Description The ANSUL® Connected Fire Container Monitoring System is a remote monitoring solution for Fire Suppression Systems. Critical processes and business continuity are driving forces for the installation of clean agent fire suppression systems. System integrity is critical for those operations to continue running with the highest up-time possible. This solution prevents a loss in pressure from compromising the efficacy of the Fire Suppression System with remote visualization and early warning notification of changes in system pressure. This allows scheduled maintenance on the system before it reaches an alarm condition where the change in pressure could affect the functionality of the system. An electronic gauge is installed on each container and measures the pressure and temperature for that container. The readings are communicated via an encrypted LoRa communication protocol to the gateway. The allowable frequency range of the communication changes based on regional requirements, therefore a specific gateway must be used depending on the final installed location. The gateway collects the data and transmits it to the cloud via cellular network, SIM card, and is visible to authorized users on the dashboard or mobile application. Authorized users have a subscription based license with a user name and password to access their system information. Authorized users can be installers and service contractors as well as end-users. End-users are granted a license through their service contractor. Application The Connected Fire Container Monitoring System is installed on various clean agent fire suppression systems. It is particularly useful in remote location installations, smart buildings where critical processes are monitored 24/7, and applications where down-time of fire suppression systems could cause business down-time. 011461a Key Features n For use with Clean Agent Fire Suppression Systems n Remote monitoring of container pressure and temperature n Container data viewable by service contractor and end-user anywhere with access to internet or cellular network n Early warning of low pressure in container n Configurable microleak detection analysis and notification n Communication protocol to the cloud via cellular network or local network n Up to 2 year battery life operation with intelligent low battery operation, preventing connection interruption n Dashboard provides document storage for system design documentation along with system installation photos

Upload: others

Post on 05-Apr-2022

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: JCI Data Sheet A4 Template Rev. 07 - Ansul

One Stanton Street | Marinette, WI 54143-2542, USA | +1-715-735-7411 | www.ansul.com© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. | Form No. F-2020130-00_A4

DATA SHEET

ANSUL® Connected Fire Container Monitoring

DescriptionThe ANSUL® Connected Fire Container Monitoring System is a remote monitoring solution for Fire Suppression Systems. Critical processes and business continuity are driving forces for the installation of clean agent fire suppression systems. System integrity is critical for those operations to continue running with the highest up-time possible. This solution prevents a loss in pressure from compromising the efficacy of the Fire Suppression System with remote visualization and early warning notification of changes in system pressure. This allows scheduled maintenance on the system before it reaches an alarm condition where the change in pressure could affect the functionality of the system.

An electronic gauge is installed on each container and measures the pressure and temperature for that container. The readings are communicated via an encrypted LoRa communication protocol to the gateway. The allowable frequency range of the communication changes based on regional requirements, therefore a specific gateway must be used depending on the final installed location. The gateway collects the data and transmits it to the cloud via cellular network, SIM card, and is visible to authorized users on the dashboard or mobile application. Authorized users have a subscription based license with a user name and password to access their system information. Authorized users can be installers and service contractors as well as end-users. End-users are granted a license through their service contractor.

ApplicationThe Connected Fire Container Monitoring System is installed on various clean agent fire suppression systems. It is particularly useful in remote location installations, smart buildings where critical processes are monitored 24/7, and applications where down-time of fire suppression systems could cause business down-time.

011461a

Key Featuresn For use with Clean Agent Fire Suppression Systems

n Remote monitoring of container pressure and temperature

n Container data viewable by service contractor and end-useranywhere with access to internet or cellular network

n Early warning of low pressure in container

n Configurable microleak detection analysis and notification

n Communication protocol to the cloud via cellular networkor local network

n Up to 2 year battery life operation with intelligent lowbattery operation, preventing connection interruption

n Dashboard provides document storage for system designdocumentation along with system installation photos

Page 2: JCI Data Sheet A4 Template Rev. 07 - Ansul

Flowchart

011401a

Page 3: JCI Data Sheet A4 Template Rev. 07 - Ansul

Specifications - Electronic Sensorn One sensor per system container

n Electronic sensor connects the electronic display to the container valve

Model 451691 - M10 370 bar 451692 1/8 NPT 160 bar 451693 1/8 NPT 250 bar

System Usage iFLOW valve with INERT gases SAPPHIRE and FM-200 valves Pilot container with added thread adaptor (PN 452605)

CV-98 INERGEN valve

Max Pressure 370 bar (5366 psi) 160 bar (2321 psi) 250 bar (3626 psi)

Temperature Measurement

-30 °C to 100 °C (-22 °F to 212 °F)

Operating Temperature

-20 °C to 65 °C (-4 °F to 149 °F)

Storage Temperature

-40 °C to 85 °C (-40 °F to 185 °F)

Dimensions 56.2 mm x diameter 38 mm (2.2 in. x diameter 1.5 in.)

Approvals EU declaration of Conformity

n CE Markings: Manufacturers Mark, Part No., Part Description, Serial No., CE0832

n EMC directive EN 61326 emmision (group 1, class B) and interference immunity

n EU directive 2011/65/EU (RoHS2)

Specifications - Electronic Displayn A digital serial interface connects the electronic sensor to the digital processor within the display

n Configurable for agent type, filling pressure, temperature, and density

n Communication frequency is determined by the location of the system installation

Model 451694 451695 451696 451697 451698

Model Description Display EU868 Display US915 Display AS923 Display AU915 Display IN865

Region/Country Europe North America Asia* Australia India

Communication LoRaWAN 1.0.2 compliant, Class A

Dimensions Approx 80 mm x 80 mm x 35 mm (3.2 in. x 3.2 in. x 1.4 in.)

Communication Frequency

868 MHz 915 MHz 915 MHz 915 MHz 868 MHz

Power Supply 2 x 1.5V AA non-rechargeable lithium batteries (ENERGIZER L91 AA 1.5V 3500mAH)

Menu Languages English, German, Italian, French, and Spanish

Operating Temperature

-20 °C to 55 °C (-4 °F to 131 °F)

Storage Temperature

-40 °C to 85 °C (-40 °F to 185 °F)

IP Rating IP 65

Approvals EU declaration of Conformity

n CE Markings: Manufacturers Mark, Part No., Part Description, Serial No., CE0832

n EMC directive EN 61326 emmision (group 1, class B) and interference immunity

n EU directive 2011/65/EU (RoHS2)

FCC Part 15 Class B Radiated and Conducted Emission

*Excludes China

Page 4: JCI Data Sheet A4 Template Rev. 07 - Ansul

Specifications - Gatewayn Communicates with the electronic gauge via LoRaWAN 1.0.2 compliant, Class A

n Communicates via 4G-LTE, 3G, 2G, or ethernet

n Single gateway can serve thousands of electronic display devices

Model 451957 451958 451963 452671

Region/Country See LoRa Regional Parameters in the user manual for a country by country list for which model must be used

Antennas Cellular, LoRa: female Sub-Miniature Version A (SMA) / LoRa: reverse polarity female SMA

Mobile Network Operator

European Network Operators

AT&T or Verizon Telstra GCF Certified Cell Module

SIM Card 2FF (25 mm x 15 mm) Mini SIM

Communication LoRaWAN 1.0.2 compliant, Class A

Communication Frequency

868 MHz 915 MHz 915 MHz 915 MHz

LoRa Channel Plan EU868/IN865 US915/AS915 AU915 US915/AS923

Dimensions Approx 161.3 mm x 107.4 mm x 42.8 mm (6.35 in. x 4.23 in. x 1.69 in.)

Operating Temperature -30 °C to 70 °C (-22 °F to 158 °F)

Storage Temperature -40 °C to 85 °C (-40 °F to 185 °F)

EMC Compliance EN 55023 Class B, EN 301 489-3 V2.1.1, EN 301 489-1 V2.2.0, EN 301-489-52 V1.1.0

US: FCC Part 15 Class B Canada: ICES-003 Class B

Australia: CISPR 32 EN 55023 Class B, EN 301 489-3 V2.1.1, EN 301 489-1 V2.2.0, EN 301-489-52 V1.1.0

System Compatibilityn 200 bar and 300 bar iFLOW

- INERGEN®

- IG-55

- IG-01

- IG-100

n INERGEN® 150 bar and 200 bar (CV-98 valve)

n N2 100 bar Pilot Container

n 25 bar FM-200

n 25 bar SAPPHIRE®

n 42 bar SAPPHIRE

n 70 bar SAPPHIRE PLUS

Dashboard OverviewThrough the Container Monitoring solution, there is an online dashboard and mobile application. The dashboard is available at https://www.connectedcontainers.johnsoncontrols.com/ and the container monitoring mobile application can be downloaded from the app store by searching Connected Fire Container Monitoring. Both remote access methods require a license to view and manage data access for the Container Monitoring products that are installed onto fire suppression systems.

Ordering InformationRetrofit hardware

451691 – Electronic Gauge Sensor M10 370 bar

451692 – Electronic Gauge Sensor 1-8 NPT 160 bar

451692 – Electronic Gauge Sensor 1-8 NPT 250 bar

452605 – Thread Adaptor M10 LPG 128 1-8 NPT

451694 – Electronic Gauge Display EU868

451695 – Electronic Gauge Display US915

451696 – Electronic Gauge Display AS923

451697 – Electronic Gauge Display AU915

451698 – Electronic Gauge Display IN865

Gateways

451957 – Gateway L4E1 LORA-868-EU-GB

451958 – Gateway L4N1 LORA-915-US

451963 – Gateway LAP3 LORA-915-AU

452671 – Gateway L4E1 LORA-915-EU-GB

Container AssembliesSee local price list for container assembly of the compatible systems for part numbers with the electronic gauge factory installed.