james w. walcott

18
AN EVAPORATION/CRYSTALLIZA -I P3dF .I ROUTE TO ZERO DISCHARGE POWER GENERATION James W. Walcott Robert G. Gorgol of HPD Incorporated Naperville, Illinois PREPARED FOR PRESENTATION AT THE AlChE DENVER SUMMER NATIONAL MEETING, AUGUST, 1988

Upload: others

Post on 18-Dec-2021

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: James W. Walcott

"-6 2&0 L-7

AN EVAPORATION/CRYSTALLIZA - I P3dF .I

ROUTE TO ZERO DISCHARGE

POWER GENERATION

James W. Walcott

Robert G. Gorgol

of

HPD Incorporated

Naperville, Illinois

PREPARED FOR PRESENTATION AT THE AlChE DENVER SUMMER NATIONAL MEETING, AUGUST, 1988

Page 2: James W. Walcott

1

2

Table of Contents

Introduction . ..... .... ..................... ......... ... . ........... . .... . ....... .. ......... . .... . . ...... . . . ...... . 1

System Description .. ............. . . ... ... .. ... . .... . .......... . ............... ... . ... . . .. . . ...... . . . . . . . ... . . 2 2.1 Brine Concentrator ................................................................................... 4 2.2 Crystallizer/Centrige . .. ... ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 o 2.3 Control .............. . ...................... ..... .............. , ............................................ 12

3 Operation vs. Design .. ...................................................................................... 13

4 Conclusion .................................................................................. ........ ......... ... . 14

Page 3: James W. Walcott

1 Introduction

A new 425 MW, coal fired power generating plant recently went through a successful start-up

in the southeastern part of the United States. It was designed and is operating as a "zero

discharge" plant.

A natural draft cooling tower utilizes secondary treated municipal waste water as make-up

water. Residual organic and inorganic components are concentrated during cycles through

the cooling tower and a blowdown stream must be removed to prevent further build-up of

components that will affect the cooling tower efficiency and life. At design rate, a blowdown

stream of approximately 300 gpm is produced.

This paper presents the reliable and economical use of evaporation and crystallization to

recover clean, reusable water and to minimize disposal costs by producing a small volume

of dry solids from the large volume waste water stream. The installation of the cooling tower

blowdown system includes two 300 gpm trains, each consisting of a falling film evaporator

with mechanical vapor recompression as an energy source, a forced circulation crystallizer

constructed of high alloy material using mechanical vapor recompression as an energy

source, and a centrifuge to separate the crystallized waste for disposal.

-;L31;2,0~~

-1 -

Page 4: James W. Walcott

2 System Description

The Cooling Tower Blowdown Treatment (CTBT) System consists of two identical Trains

of equipment, the A and B Trains, with each train utilizing a Brine Concentrator System and

a Crystallizer System. The Brine Concentrator System uses an HPD Preheat Failing Film

(PF) Evaporator as the Brine Concentrator with ancillary operations including feed filtration,

feed preheat, feed deaeration and sludge (seed) recycle. The crystallizer system contains

an HPD crystallizer with entrainment separator and a centrifuge. Both the BC Evaporators

and the crystallizers utilize mechanical vapor recompression (MVR). In each train the

operation and control of the Evaporator and Crystallizer are totally independent of each

other.

The Cooling Tower Blowdown Treatment System (CTBT) has been designed for the feed

water conditions shown in Table 1.

-2-

Page 5: James W. Walcott

Table 1 : Feed Water Conditions

Variable Typical Minimum Maximum

Calcium, ppm as CaC03

Magnesium, ppm as CaCO3

Sodium, ppm as CaC03

Sulfate, ppm as CaCO3

Chloride, ppm as CaC03

Alkalinity, ppm as CaC03

Silica, ppm as Si02

Suspended Solids, ppm

Total Dissolved Solids, ppm

PH

836

275

1078

1 276

726

200

132

50

3Ooo

960

360

1380

2Ooo

960

300

150

150

3600

8.5

Page 6: James W. Walcott

2.1 Brine Concentrator

Each falling film cooling water blowdown evaporator system as depicted in Figure 1, is used

with mechanical vapor recompression to reduce the waste stream from 300 GPM to

approximately 6 GPM. V 4 q O GTD)

The waste water feed to the evaporator has a high scaling tendency due to the presence

of various carbonates, sulfates and silica.

The feed is pretreated by the addition of H2SO4 or NaOH for pH adjustment (5.5 - 7.5 range)

for better metal protection and to keep the metal hydroxides in solution. Anti-scaling agents

(organic phosphate or hexameta phosphate) and/or anti-foaming agents (high tempera-

ture formulated silicone based) are also added to the feed.

The falling film evaporator design encompasses parameters to minimize the scaling of heat

transfer surfaces and maximize energy efficiency. From the feed pretreatment tank and

prior to entering the evaporator, the waste stream passes through filters to remove solid

particles. This will minimize scaling and solid build-up of the plate type heat exchanger and

the stripper packing. After filtration, the feed passes through a plate type heat exchanger

where it is heated by the dean condensate returned from the evaporator. A plate type heat

exchanger will provide better heat transfer coefficients and better heat recovery than a shell

and tube type heat exchanger. The feed is further treated by deaeration in order to remove

air and gases contained in the feed, minimizing noncondensibles build-up in the evaporator

heat exchanger shell side.

The HPD PH falling film evaporator is shown in the attached diagram (Figure 2).

-4-

Page 7: James W. Walcott

PF EVAPORATOe

EXTERNAL* PLENUM

STEAM+

HEATER<

IJ "ENTI

* CONDENSATE&

VAPOR B O D Y

Figure 2

Page 8: James W. Walcott

The recirculated liquor is pumped from the bottom of the vapor body through the tube

bundle section to the top liquor box. The very low velocity gradient of the liquor at this point

helps in distributing evenly the liquor over the distribution tray located just above the top

tubesheet. A detail of the top liquor box is shown on Figure 3.

Page 9: James W. Walcott

D I S T R I B U T I O N P L A T E D E T A I L

DISTRIBUTION- PLATE HOLES

t FALLING LIQUOR

Figure 3

DISTRIBUTION PLATE

\TOP TUBE SHEET

t

The liquor is then distributed to the tubes in the falling film section and a liquor/vapor mixture

exists at the bottom of these tubes. Liquor and vapors are separated in the vapor body

with the liquor being collected in the lower portion while the vapors pass through the

entrainment separator prior to exiting the effect. The liquor is then recirculated via the

circulation pump for a subsequent cycle.

The advantage of this design is its simplicity, in terms of piping, control and maintenance.

The circulation piping is minimized as it consists of a downcomer from the vapor body to

the circulation pump and then a return pipe back to the vapor body. This is in direct contrast

Page 10: James W. Walcott

with other falling film designs where a large circulation pipe has to run externally up to the

top liquor box. Aside from reduced capital costs the PF evaporator minimizes radiation

losses and pump head requirements through the circulation piping.

Steam or vapor is distributed to the unit by way of an external plenum which wraps around

the heat exchange bundle. The vapors, thus introduced from all directions, sweep through

the heat exchanger bundle providing even distribution. Noncondensible gases are effi-

ciently removed from the system utilizing HPD’s special baffling.

Main plant steam is often utilized to provide heat for evaporation. Vapors from the evap-

orator are then condensed in a condenser by using cooling water. For the quantities of

water to be evaporated in most cooling tower blowdown process waste streams, the energy

costs required to produce the necessary steam cannot be justified. However, the use of

mechanical vapor recompression, utilizing approximately 88 KwHr/l ,OOO gallons feed,

makes evaporation a feasible solution to reduce the volume of waste.

The vapors generated by evaporation pass through an entrainment separation step before

going to the mechanical compressor. The risk of corrosion on erosion of the compressor

can be virtually eliminated by providing a properly sized vapor body that has both the proper

vapor release velocities and propre height for entrainment separation. A double stage

entrainment separator is provided that includes a Chevron type separator which remove

the bulk of liquid entrainment. This type of separator is rugged and not subject to plugging

with entrained solids. The second stage of entrainment separation is a mesh pad type

separator that further reduces entrainment levels to a minimum obtainable level. With this

combined entrainment separation design, the compressor is fully protected from liquid

carryover.

-8-

Page 11: James W. Walcott

The evaporated vapors are then compressed in the mechanical compressor to a pressure

that will provide a heat source on the shell side of the falling film evaporator a high enough

temperature to promote heat transfer. The required compression ratio is governmed by

the boiling point rise of the concentrated solution and by the driving force necessary to

transfer heat.

The falling film design is chosen for this application because of its ability to provide relatively

high heat transfer rates with low temperature driving forces of 8 - 10 degrees F.

A portion of the concentrated recirculation flow containing primarily sodium sulfate and

sodium chloride crystals (approximately 15% undissolved solids) to a hydrocyclone. The

cyclone underflow containing approximately 30% undissolved solids is mixed with the feed

solution in the feed tank. The purpose of adding solids to the feed is to provide crystal

seeding of the evaporator. Seeding the feed with undissolved solids provides a "sludge

recycle" that will assist in minimizing scaling of the heat transfer surfaces. Sufficient solids

are added by proper sizing of the hydrocyclone. This will ensure that any solids liberated

by supersaturation will deposit on the larger available crystal area of the seed crystals rather

than on the heat transfer surfaces.

During initial start-up of the system, seed crystals are provided from an external source.

A portion of the overftow from the cydone is sent back to the concentrated side, while the

other portion is mixed with the concentrated slurry overflow from the evaporator prior to

being sent to the waste slurry tank.

The MVR falling film evaporator recovers 97% of the waste stream as clean water.

Page 12: James W. Walcott

2.2 CrystaIlizer/Centrifuge

Further volume reduction is by utilizing a forced circulation type crystallizer as depicted in

Figure 4. This system consists basically of a vapor body, external heat exchanger, recir-

culation pump, recirculation and vapor piping, entrainment separator and condenser. This

type of system is specifically designed to concentrate waste streams to high percent solids

without significant scaling and operating disturbances.

The feed enters the suction side of the recirculation pump and passes through the heat

exchanger, prior to entering the vapor body where vapors are separated from the liquor

and supersaturation is released. The vapor leaving the crystallizer vessel passes through

an entrainment separator and compressor.

Concentrated liquor is recirculated from the vapor body retention chamber through a

two-pass, shell and tube heat exchanger and back to the vapor body. The heat that is

added to the recirculating liquor in the heater is released by vaporization of water in the

crystallizer vessel.

An important feature of this type of system that enhances it’s capability to prevent scaling

of the heat exchanger, isthe suppression of boiling in the two-pass heater. This suppression

is usually achieved by providing a static pressure above the heater equivalent to the steam

temperature in the heat exchanger shell. This design approach will eliminate bulk liquor

boiling due to temperature rise through the heat exchanger as well as film boiling at the

tube wall.

-1 0-

Page 13: James W. Walcott

' .

I

I

I

I

I

I

I

I

I

I

I

I I

I ! i I L---

I

I i I !

I I I

I

I I

I I

I I I I I I I I I

I I I I

Page 14: James W. Walcott

Generally, when concentrating waste streams to high percent solids, two inch diameter

tubes are utilized. The large diameter tubes provide turbulent flow at lower tube velocities

and minimize the possibility of plugging.

The shell side of the heat exchanger is vented continuously to avoid the build-up of non-

condensibles. This feature minimized the required steam pressure by allowing full use of

the available heat transfer surface. This will assist with the suppression of film boiling at

the heat exchanger tube walls.

The crystallizer vessel provides retention volume and time for the recirculating liquor. This

time is necessary to assure separation of vapors from the liquor and full release of super-

saturation. The recirculation rate is partially determined by the necessary tube velocities

to enhance heat transfer and prevent scaling.

A portion of the crystals are recirculated through the heat exchanger, thus, providing a

"sludge recycle". As in the brine concentrator, this provision will further minimize the ten-

dency of scaling on heat transfer surfaces.

The recirculation pump matches the crystallizer system in terms of rate and total dynamic

head. Normally, it is possible to include a low head, high volume pump that will operate at

relatively low speeds. This will provide long life for rotating parts and will minimize main-

tenance requirements.

The forced circulation crystallizer reduces the system waste from 6 GPM at a concentration

of 15% total solids to approximately 2.0 GPM, of final waste slurry at a concentration of 44%

total solids (CF = 2.9) and produces 5.8 GPM of reusable dean condensate. The overall

water removal is increased to approximately 98 - 99%.

4032

Page 15: James W. Walcott

Finally, the waste stream is further reduced by centrifuging the solids from the liquor that

is received back to the crystallizer. A Sharpies basket-type only is utilized with all wetted

parts constructed of 316L stainless steel materials. Final solids moisture content is slightly

higher than design. Diagram for 80% solids. Actual operation is providing 75% solids. This

is due primarily to the higher TOC level than expected that created a higher viscosity liquor

that makes separation more difficult.

2.3 Control

A unique feature of this waste brine concentration system or CTBT system is that it is totally

automatic, or computer controlled. After manual operation has been started, the system

may be converted over to the automatic mode, under which the computer (Gould Modicon

584L) will monitor and control the system. There is a separate Modican PC for Train A and

a separate Modicon for Train 6. Since the evaporator in each Train may be operated

independent of the crystallizer in each Train, it is therefore possible that the evaporator from

one Train can be operated with the Crystallizer of the other Train.

-1 2-

Page 16: James W. Walcott

3 Operation vs. Design

The cooling tower blowdown system has been operating for several months. The following

table provides a comparison of operation and design parameters.

Table 2: Operation and Design Parameters

Item Design Operation

Minimum Feed Flow 150 gpm 160/165 gpm

Condensate Quality < 10 mg/l <1/<1 mg/l

e 81 5 mg/l

(crystallizer)

Solid Product 80% ?4/69.6%

Recovery 9796 98.5/98%

Power 93.7 kwh/ 80.2/87.1 kwh/

lo00 gal feed lo00 gal feed

The solid product is not as dry as expected due to unexpected high TOC levels. However,

the solid product is easily handled.

Page 17: James W. Walcott

4 Conclusion

The combination of evaporation and crystallization successfully reduces the volume of

waste for landfill. Although capital and operating costs are high, it is proven technology

that is reliable and efficient. Future cooling tower blowdown systems may include other

membrane type technologies in combination with evaporation and crystallization that will

substantially reduce both initial capital and operating costs.

-14-

Page 18: James W. Walcott

' .. 9

B I I