ELECTRICAL ABBREVIATIONS & NOTES A B C D E F G H I J K L M N O NOT USED Q R T U V W P X Y Z S AREA TYPE 12 AREA TYPE 1A AREA TYPE 7B AREA TYPE 7A AREA TYPE 4 THE SPECIAL AREA DESIGNATION BOXES, AS DEFINED BELOW, ARE LOCATED ON THE PLAN DRAWINGS TO DEFINE ELECTRICAL INSTALLATION REQUIREMENTS. DESIGNATION BOXES ARE LOCATED WITHIN ROOM OR BELOW ROOM NUMBER. ALL INDOOR AREAS NOT INDICATED OTHERWISE ARE AREA TYPE 1 AND MINIMUM NEMA TYPE 1 ENCLOSURES. CORROSIVE CHEMICAL FEED AND STORAGE ROOMS. CONDUIT SYSTEM SHALL BE EXPOSED SCHEDULE 80 PVC RIGID NON-METALLIC CONDUIT WITH PVC FITTINGS, BOXES AND ACCESSORIES. INDOOR WET LOCATIONS SUCH AS VAULTS, HOSEDOWN AREAS, BASEMENTS, ETC. MINIMUM NEMA TYPE 4 ENCLOSURE FOR EQUIPMENT AND GASKETED FITTINGS IN A CONDUIT SYSTEM. CLASS I, DIVISION 1 AREA AS DEFINED BY NEC. ALL EQUIPMENT AND CONDUIT SYSTEMS SHALL BE RATED FOR USE IN THIS AREA. CLASS I, DIVISION 2, GROUP C AND D (METHANE, GASOLINE) AS DEFINED BY NEC. EQUIPMENT AND CONDUITS SYSTEMS SHALL BE RATED FOR USE IN THIS AREA. INDOOR, DRY, DIRTY AREA. REQUIRES MINIMUM NEMA TYPE 12 GASKETED ENCLOSURES FOR ALL EQUIPMENT AND GASKETED FITTINGS IN CONDUIT SYSTEMS. AREA DESIGNATIONS GENERAL REQUIREMENTS ELECTRICAL ABBREVIATIONS ELECTRICAL GENERAL NOTES A AMBER, AMPERE, ALARM AC ALTERNATING CURRENT ACB AIR CIRCUIT BREAKER ACR ACCESS CARD READER AF AMPERE FRAME AFD ADJUSTABLE FREQUENCY DRIVE AFRD ARC-FLASH REDUCTION DEVICE AM AMMETER ANN ANNUNCIATOR AR ALARM RELAY AS AMMETER SWITCH, AMPERE SENSOR AT AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AUX AUXILIARY AWG AMERICAN WIRE GAUGE J,JB JUNCTION BOX ONE, SINGLE PAIR, TWISTED SHIELDED #16 CABLE THREE, SINGLE, SEVEN CONDUCTOR #14 MULTICONDUCTOR CONTROL CABLES 1-1PR#16S 3-7/C#14 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ROUTING ALL CONDUITS NOT SHOWN ON THE PLANS. THIS SHALL INCLUDE ALL CONDUITS SHOWN ON THE ONE-LINES AND HOME-RUNS SHOWN ON THE PLAN DRAWINGS. CONDUITS SHALL BE ROUTED AS DEFINED IN THE SPECIFICATION. 2. SPARE WIRES SHALL BE TAPED AND COILED AND LABELED TO INDICATE WHERE OTHER END OF SPARE WIRE IS LOCATED. 3. IF EQUIPMENT SUPPLIED BY MANUFACTURER HAS A LARGER LOAD THAN VALUE SHOWN, THE CABLE CONDUIT AND ELECTRICAL EQUIPMENT SHALL BE ENLARGED, AS REQUIRED, TO ACCOMMODATE THE HIGHER VALUE. 4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING PROPERLY SIZED STARTER OVERLOADS FOR EQUIPMENT FURNISHED. 5. LIGHTING AND RECEPTACLE CIRCUITS DESIGNATED ON THE FLOOR PLANS ARE NOT SHOWN ON THE ONE-LINES. CONDUCTORS FOR LIGHTING, RECEPTACLES, AND MISCELLANEOUS 120VAC CIRCUITS SHALL BE MINIMUM NO. 12AWG. CONDUIT FOR LIGHTING, RECEPTACLES, AND MISCELLANEOUS 120VAC CIRCUITS SHALL BE MINIMUM 3/4". 6. IN AREAS WHERE THERE ARE OVERHEAD BRIDGE CRANES, HOISTS, ETC. NO CONDUITS SHALL BE RUN OVERHEAD THAT WILL INTERFERE WITH THE OPERATION OF THE EQUIPMENT. 1. SOLID LINES ( ) INDICATE NEW WORK OR EQUIPMENT. 2. SCREENED LINES ( ) INDICATE EXISTING WORK OR EQUIPMENT. 3. DASHED LINES ( ) INDICATE FUTURE WORK OR EQUIPMENT. 4. REFER TO INDIVIDUAL DISCIPLINE CONTRACT DRAWINGS FOR ADDITIONAL ABBREVIATIONS, DETAILS, AND GENERAL DESIGN NOTES. 5. LEGEND SHEETS ARE GENERAL. SOME SYMBOLS AND ABBREVIATIONS MAY NOT BE UTILIZED ON THIS SPECIFIC PROJECT. 6. INFORMATION RELATED TO CIRCUIT IDENTIFICATION, WIRE & CONDUIT SIZES, AND ROUTING, IS ON THE FOLLOWING DRAWING TYPES. A. ONE-LINE DIAGRAMS SHOW CIRCUIT IDENTIFICATION, WIRE QUANTITY AND SIZES, AND CONDUIT SIZE WITHIN STRUCTURES. ONE-LINE DIAGRAMS ALSO INDICATE ORIGIN AND DESTINATION OF CIRCUITS, AND IDENTIFY CIRCUITS ROUTED UNDERGROUND. B. FOR CIRCUITS WITHOUT UNDERGROUND PORTIONS, BUILDING FLOOR PLANS SHOW LOCATION OF EQUIPMENT FOR DETERMINING CIRCUIT LENGTH WITHIN THE STRUCTURE. FOR CIRCUITS WITH UNDERGROUND PORTIONS, ANTICIPATED PENETRATION OF UNDERGROUND CONDUITS ARE SHOWN ON STRUCTURE PLANS FOR DETERMINING THE LENGTH OF THE IN-STRUCTURE PORTIONS OF CIRCUITS. BUILDING FLOOR PLANS MAY ALSO SHOW HOME RUNS FOR LIGHTING, RECEPTACLE, AND OTHER MISCELLANEOUS EQUIPMENT CIRCUITS. C. SITE PLANS INDICATE THE GENERAL ROUTING OF UNDERGROUND CONDUITS AND DUCT BANKS. CIRCUITS ROUTED IN UNDERGROUND CONDUITS OR DUCT BANKS ARE INDICATED IN DUCT BANK SECTIONS REFERENCED ON THE SITE PLAN. D. DUCT BANK SECTIONS AND SCHEDULES IDENTIFY CONDUIT SIZE, CONDUIT MATERIAL, ARRANGEMENT OF THE UNDERGROUND CONDUITS, AND CIRCUITS ROUTED IN EACH UNDERGROUND CONDUIT. B BUS BC BATTERY CHARGER BKR BREAKER BR BRAKE BT BEARING TEMPERATURE C CLOSE, COUNTER, CONTACTOR, CONTROL, CCTV CAMERA CAP CAPACITOR CB CIRCUIT BREAKER CB"A" CIRCUIT BREAKER AUXILIARY CONTACT (OPEN WHEN BREAKER IS OPEN) CB"B" CIRCUIT BREAKER AUXILIARY CONTACT (CLOSED WHEN BREAKER IS OPEN) CD CONTROL DAMPER CI CELL INTERLOCK CKT CIRCUIT CL2 CHLORINE COS CABLE OPERATED SWITCH CP CONTROL PANEL CPT CONTROL POWER TRANSFORMER CR CURRENT OF CONTROL RELAY, CARD READER CS CONTROL STATION CT CYCLE TIMER OR CURRENT TRANSFORMER CTC CYCLE TIMER CLUTCH CTM CYCLE TIMER MONITOR 2/C 2 CONDUCTOR 4"C 4" CONDUIT DC DIRECT CURRENT, DOOR CONTACT DI DOOR INTERLOCK DM DAMPER MOTOR, DEMAND METER, DIMMER SWITCH DPDT DOUBLE POLE DOUBLE THROW DPST DOUBLE POLE SINGLE THROW DPR DIFFERENTIAL PRESSURE REGULATOR DPS DIFFERENTIAL PRESSURE SWITCH DS DISCONNECT SWITCH, DOOR SWITCH, DESKTOP STATION DVLS DISCHARGE VALVE LIMIT SWITCH E ELECTRIC OPERATOR FOR CONTROL DAMPER OR VALVE EC EMPTY CONDUIT EDS ELECTRICAL DOOR STRIKE EL ELEVATION, EMERGENCY LIGHT EMH ELECTRICAL MANHOLE ER ELECTRODE RELAY ES END SWITCH, REQUEST TO EXIT SENSOR E-STOP EMERGENCY STOP ETM ELAPSED TIME METER EX EXISTING EXP EXPLOSION PROOF F FORWARD, FIELD FO FIBER OPTIC FPR FEEDER PROTECTION RELAY FS FLOW SWITCH G GREEN, GROUND, GENERATOR, GROUND FAULT GD GROUND DETECTOR GEN GENERATOR GFCI,GFI GROUND FAULT CURRENT INTERRUPTOR, GROUND FAULT INTERRUPTOR GLS GEARED LIMIT SWITCH GPR GENERATOR PROTECTION RELAY GND GROUND #8G #8 GROUND WIRE H HIGH, HUMIDISTAT HH HANDHOLE HMT HIGH MOTOR TEMPERATURE HOA HAND-OFF-AUTO HOR HAND-OFF-REMOTE HP HORSEPOWER HS HAND STATION HWCO HIGH WATER CUTOFF HZ HERTZ (CYCLE) I/O INPUT/OUTPUT I INSTANTANEOUS IJB INTERCOM JUNCTION BOX K KEY INTERLOCK KAIC THOUSAND AMPERES INTERRUPTING CURRENT KCMIL THOUSAND CIRCULAR MIL KO KEY OPERATED KV KILOVOLT KVA KILOVOLT AMPERE KVAR KILOVAR KW KILOWATT KWH KILOWATT HOUR L LOW, LEVEL, LONG-TIME LA LIGHTNING ARRESTER LAN LOCAL AREA NETWORK LC LIGHTING CONTRACTOR LCE LIGHTING CONTACTOR ENCLOSURE LIGHTING CONTROL ENCLOSURE LCP LOCAL CONTROL PANEL LCS LOCAL CONTROL STATION LOA LOCAL-OFF-AUTO LOR LOCAL-OFF-REMOTE LOS LOCK OUT STOP LP LIGHTING PANEL LS LIMIT OR LEVEL SWITCH LTG LIGHTING LWCO LOW WATER CUTOFF M MAGNETIC MOTOR STARTER MA MILLIAMPERE MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MCLU MOTOR CONTROL LINEUP MD MOISTURE DETECTOR, MOTION DETECTOR MDL MAGNETIC DOOR LOCK MFR MANUFACTURER MH MANHOLE, MOUNTING HEIGHT MOV MOTOR OPERATED VALVE MPR MOTOR PROTECTION RELAY MS MANUAL MOTOR STARTER MSH MOTOR SPACE HEATER MTS MANUAL TRANSFER SWITCH MV MILLIVOLT, MEDIUM VOLTAGE MVA MEGAVOLT AMPERE N NEUTRAL NGR NEUTRAL GROUNDING RESISTOR NGT NEUTRAL GROUNDING TRANSFORMER NC NORMALLY CLOSED NO NORMALLY OPEN, NUMBER O OPEN OL OVERLOAD OOA ON-OFF-AUTO OOR ON-OFF-REMOTE OS OCCUPANCY SENSOR O/U OVER/UNDER P PRIMARY, POWER, POLE PCS PLANT CONTROL SYSTEM PB PUSH BUTTON, PULL BOX PE PHOTOELECTRIC SENSOR, PHOTOCELL PF POWER FACTOR PFCC POWER FACTOR CORRECTION CAPACITOR PH PHASE PL PILOT LIGHT PLC PROGRAMMABLE LOGIC CONTROLLER PP POWER PANEL PR PAIR PRS PROXIMITY SWITCH PS PRESSURE SWITCH PT POTENTIAL TRANSFORMER, PROGRAM TIMER R RED, RAISE, RELAY, REVERSE RECP RECEPTACLE RES RESISTOR RH REMOTE HANDSET RT REPEATING TIMER RTD RESISTANCE TEMPERATURE DETECTOR RTU REMOTE TERMINAL UNIT RVSS REDUCED VOLTAGE SOLID STATE STARTER S SHORT-TIME, SHIELDED, STARTER SA SURGE ARRESTER, SPEAKER AMPLIFIER SCADA SUPERVISORY CONTROL AND DATA ACQUISITION SF6 SULFUR HEXAFLOURIDE SH SPACE HEATER SN SOLID NEUTRAL SO SOLENOID OILER SP SINGLE POLE SPD SURGE PROTECTION DEVICE SPDT SINGLE POLE DOUBLE THROW SPST SINGLE POLE SINGLE THROW SS SELECTOR SWITCH, START/STOP, STAINLESS STEEL SSM SOLID-STATE METERING SSS SOLID STATE STARTER SST SOLID-STATE TRIP SUPV SUPERVISORY CONTROL SV SOLENOID VALVE SWB,SWBD SWITCHBOARD SWG,SWGR SWITCHGEAR T THERMOSTAT, TIMER, TOTALIZER, TRANSFORMER TACH TACHOMETER TB TERMINAL BLOCK TC TIMER CLUTCH TD TIME DELAY RELAY TEMP TEMPERATURE TM TIMER MOTOR TQ TORQUE TR TIMER RELAY, TRIAD TS TEMPERATURE SWITCH TTB TELEPHONE TERMINAL BOARD UG UNDERGROUND UPS UNINTERRUPTIBLE POWER SUPPLY V VOLTS, VOLTAGE RESTRAINED VA VOLT AMPERE VAR VARMETER VFD VARIABLE FREQUENCY DRIVE VI VACUUM INTERRUPTER VLS VALVE LIMIT SWITCH VM VOLTMETER VPI VALVE POSITION INDICATOR VS VOLTMETER SWITCH W WHITE, WATTS WH WATTHOUR METER WM WATT METER WP WEATHERPROOF WPI WEATHERPROOF IN-USE WS WALL STATION X AUXILIARY RELAY XFMR TRANSFORMER XP EXPLOSION PROOF Z AUXILIARY RELAY, IMPEDANCE ZS POSITION SWITCH ZSS ZERO SPEED SWITCH Y YELLOW DRAWN: CHECKED: NO. DATE DESIGNED: SCALE REVISION PLANNING & ENGINEERING DIVISION 8560 ARLINGTON BOULEVARD FAIRFAX, VA 22031 Black & Veatch Corporation 106-4 039 -- - - -- - - -- - - J-E100_ELEC_ABBREV_NOTES.DWG -- CH MB -- - - -- - - -- - - -- - - ABBREVIATIONS AND NOTES ELECTRICAL 7-JUN-2021 P0215A SOFT STARTERS GRIFFITH FINISHED WATER PUMPING STATION FILE NAME: PROJECT DIVISION DATE: Fairfax Water BLACK &VEATCH DRAWING E100 SHEET Arlington, Virginia TAX MAP: FOR PURCHASE OF RVSS EQUIPMENT ONLY - NOT FOR CONSTRUCTION NONE C O M M O N W E A L T H O F V I R G I N I A P R O F E S S I O N A L E N G I N E E R SCOTT D. STOCKAM Lic . No . 0402032079 9/2/2021

Upload: others

Post on 01-Oct-2021

36 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: J-E100 ELEC ABBREV NOTES.DWG

ELECTRICAL ABBREVIATIONS & NOTES

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

NOT USED

Q

R

T

U

V

W

P

X

Y

Z

S

AREA TYPE 12

AREA TYPE 1A

AREA TYPE 7B

AREA TYPE 7A

AREA TYPE 4

THE SPECIAL AREA DESIGNATION BOXES, AS DEFINED BELOW, ARE LOCATED ON THE PLAN DRAWINGS TO DEFINE ELECTRICAL

INSTALLATION REQUIREMENTS. DESIGNATION BOXES ARE LOCATED WITHIN ROOM OR BELOW ROOM NUMBER. ALL INDOOR

AREAS NOT INDICATED OTHERWISE ARE AREA TYPE 1 AND MINIMUM NEMA TYPE 1 ENCLOSURES.

CORROSIVE CHEMICAL FEED AND STORAGE ROOMS. CONDUIT SYSTEM SHALL BE EXPOSED

SCHEDULE 80 PVC RIGID NON-METALLIC CONDUIT WITH PVC FITTINGS, BOXES AND ACCESSORIES.

INDOOR WET LOCATIONS SUCH AS VAULTS, HOSEDOWN AREAS, BASEMENTS, ETC. MINIMUM NEMA

TYPE 4 ENCLOSURE FOR EQUIPMENT AND GASKETED FITTINGS IN A CONDUIT SYSTEM.

CLASS I, DIVISION 1 AREA AS DEFINED BY NEC. ALL EQUIPMENT AND CONDUIT SYSTEMS SHALL BE

RATED FOR USE IN THIS AREA.

CLASS I, DIVISION 2, GROUP C AND D (METHANE, GASOLINE) AS DEFINED BY NEC. EQUIPMENT AND

CONDUITS SYSTEMS SHALL BE RATED FOR USE IN THIS AREA.

INDOOR, DRY, DIRTY AREA. REQUIRES MINIMUM NEMA TYPE 12 GASKETED ENCLOSURES FOR ALL

EQUIPMENT AND GASKETED FITTINGS IN CONDUIT SYSTEMS.

AREA DESIGNATIONS

GENERAL REQUIREMENTS

ELECTRICAL ABBREVIATIONSELECTRICAL GENERAL NOTES

A AMBER, AMPERE, ALARM

AC ALTERNATING CURRENT

ACB AIR CIRCUIT BREAKER

ACR ACCESS CARD READER

AF AMPERE FRAME

AFD ADJUSTABLE FREQUENCY DRIVE

AFRD ARC-FLASH REDUCTION DEVICE

AM AMMETER

ANN ANNUNCIATOR

AR ALARM RELAY

AS AMMETER SWITCH, AMPERE SENSOR

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

J,JB JUNCTION BOX

ONE, SINGLE PAIR, TWISTED

SHIELDED #16 CABLE

THREE, SINGLE, SEVEN CONDUCTOR #14

MULTICONDUCTOR CONTROL CABLES

1-1PR#16S

3-7/C#14

1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ROUTING ALL CONDUITS NOT SHOWN ON THE PLANS. THIS SHALL INCLUDE ALL

CONDUITS SHOWN ON THE ONE-LINES AND HOME-RUNS SHOWN ON THE PLAN DRAWINGS. CONDUITS SHALL BE ROUTED AS DEFINED

IN THE SPECIFICATION.

2. SPARE WIRES SHALL BE TAPED AND COILED AND LABELED TO INDICATE WHERE OTHER END OF SPARE WIRE IS LOCATED.

3. IF EQUIPMENT SUPPLIED BY MANUFACTURER HAS A LARGER LOAD THAN VALUE SHOWN, THE CABLE CONDUIT AND ELECTRICAL

EQUIPMENT SHALL BE ENLARGED, AS REQUIRED, TO ACCOMMODATE THE HIGHER VALUE.

4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING PROPERLY SIZED STARTER OVERLOADS FOR EQUIPMENT FURNISHED.

5. LIGHTING AND RECEPTACLE CIRCUITS DESIGNATED ON THE FLOOR PLANS ARE NOT SHOWN ON THE ONE-LINES. CONDUCTORS FOR

LIGHTING, RECEPTACLES, AND MISCELLANEOUS 120VAC CIRCUITS SHALL BE MINIMUM NO. 12AWG. CONDUIT FOR LIGHTING,

RECEPTACLES, AND MISCELLANEOUS 120VAC CIRCUITS SHALL BE MINIMUM 3/4".

6. IN AREAS WHERE THERE ARE OVERHEAD BRIDGE CRANES, HOISTS, ETC. NO CONDUITS SHALL BE RUN OVERHEAD THAT WILL

INTERFERE WITH THE OPERATION OF THE EQUIPMENT.

1. SOLID LINES ( ) INDICATE NEW WORK OR EQUIPMENT.

2. SCREENED LINES ( ) INDICATE EXISTING WORK OR EQUIPMENT.

3. DASHED LINES ( ) INDICATE FUTURE WORK OR EQUIPMENT.

4. REFER TO INDIVIDUAL DISCIPLINE CONTRACT DRAWINGS FOR ADDITIONAL ABBREVIATIONS, DETAILS, AND GENERAL DESIGN

NOTES.

5. LEGEND SHEETS ARE GENERAL. SOME SYMBOLS AND ABBREVIATIONS MAY NOT BE UTILIZED ON THIS SPECIFIC PROJECT.

6. INFORMATION RELATED TO CIRCUIT IDENTIFICATION, WIRE & CONDUIT SIZES, AND ROUTING, IS ON THE FOLLOWING DRAWING

TYPES.

A. ONE-LINE DIAGRAMS SHOW CIRCUIT IDENTIFICATION, WIRE QUANTITY AND SIZES, AND CONDUIT SIZE WITHIN

STRUCTURES. ONE-LINE DIAGRAMS ALSO INDICATE ORIGIN AND DESTINATION OF CIRCUITS, AND IDENTIFY CIRCUITS

ROUTED UNDERGROUND.

B. FOR CIRCUITS WITHOUT UNDERGROUND PORTIONS, BUILDING FLOOR PLANS SHOW LOCATION OF EQUIPMENT FOR

DETERMINING CIRCUIT LENGTH WITHIN THE STRUCTURE. FOR CIRCUITS WITH UNDERGROUND PORTIONS, ANTICIPATED

PENETRATION OF UNDERGROUND CONDUITS ARE SHOWN ON STRUCTURE PLANS FOR DETERMINING THE LENGTH OF

THE IN-STRUCTURE PORTIONS OF CIRCUITS. BUILDING FLOOR PLANS MAY ALSO SHOW HOME RUNS FOR LIGHTING,

RECEPTACLE, AND OTHER MISCELLANEOUS EQUIPMENT CIRCUITS.

C. SITE PLANS INDICATE THE GENERAL ROUTING OF UNDERGROUND CONDUITS AND DUCT BANKS. CIRCUITS ROUTED IN

UNDERGROUND CONDUITS OR DUCT BANKS ARE INDICATED IN DUCT BANK SECTIONS REFERENCED ON THE SITE PLAN.

D. DUCT BANK SECTIONS AND SCHEDULES IDENTIFY CONDUIT SIZE, CONDUIT MATERIAL, ARRANGEMENT OF THE

UNDERGROUND CONDUITS, AND CIRCUITS ROUTED IN EACH UNDERGROUND CONDUIT.

B BUS

BC BATTERY CHARGER

BKR BREAKER

BR BRAKE

BT BEARING TEMPERATURE

C CLOSE, COUNTER, CONTACTOR, CONTROL,

CCTV CAMERA

CAP CAPACITOR

CB CIRCUIT BREAKER

CB"A" CIRCUIT BREAKER AUXILIARY CONTACT

(OPEN WHEN BREAKER IS OPEN)

CB"B" CIRCUIT BREAKER AUXILIARY CONTACT

(CLOSED WHEN BREAKER IS OPEN)

CD CONTROL DAMPER

CI CELL INTERLOCK

CKT CIRCUIT

CL2 CHLORINE

COS CABLE OPERATED SWITCH

CP CONTROL PANEL

CPT CONTROL POWER TRANSFORMER

CR CURRENT OF CONTROL RELAY, CARD READER

CS CONTROL STATION

CT CYCLE TIMER OR CURRENT TRANSFORMER

CTC CYCLE TIMER CLUTCH

CTM CYCLE TIMER MONITOR

2/C 2 CONDUCTOR

4"C 4" CONDUIT

DC DIRECT CURRENT, DOOR CONTACT

DI DOOR INTERLOCK

DM DAMPER MOTOR, DEMAND METER,

DIMMER SWITCH

DPDT DOUBLE POLE DOUBLE THROW

DPST DOUBLE POLE SINGLE THROW

DPR DIFFERENTIAL PRESSURE REGULATOR

DPS DIFFERENTIAL PRESSURE SWITCH

DS DISCONNECT SWITCH, DOOR SWITCH,

DESKTOP STATION

DVLS DISCHARGE VALVE LIMIT SWITCH

E ELECTRIC OPERATOR FOR CONTROL

DAMPER OR VALVE

EC EMPTY CONDUIT

EDS ELECTRICAL DOOR STRIKE

EL ELEVATION, EMERGENCY LIGHT

EMH ELECTRICAL MANHOLE

ER ELECTRODE RELAY

ES END SWITCH, REQUEST TO EXIT SENSOR

E-STOP EMERGENCY STOP

ETM ELAPSED TIME METER

EX EXISTING

EXP EXPLOSION PROOF

F FORWARD, FIELD

FO FIBER OPTIC

FPR FEEDER PROTECTION RELAY

FS FLOW SWITCH

G GREEN, GROUND, GENERATOR,

GROUND FAULT

GD GROUND DETECTOR

GEN GENERATOR

GFCI,GFI GROUND FAULT CURRENT INTERRUPTOR,

GROUND FAULT INTERRUPTOR

GLS GEARED LIMIT SWITCH

GPR GENERATOR PROTECTION RELAY

GND GROUND

#8G #8 GROUND WIRE

H HIGH, HUMIDISTAT

HH HANDHOLE

HMT HIGH MOTOR TEMPERATURE

HOA HAND-OFF-AUTO

HOR HAND-OFF-REMOTE

HP HORSEPOWER

HS HAND STATION

HWCO HIGH WATER CUTOFF

HZ HERTZ (CYCLE)

I/O INPUT/OUTPUT

I INSTANTANEOUS

IJB INTERCOM JUNCTION BOX

K KEY INTERLOCK

KAIC THOUSAND AMPERES INTERRUPTING CURRENT

KCMIL THOUSAND CIRCULAR MIL

KO KEY OPERATED

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAR KILOVAR

KW KILOWATT

KWH KILOWATT HOUR

L LOW, LEVEL, LONG-TIME

LA LIGHTNING ARRESTER

LAN LOCAL AREA NETWORK

LC LIGHTING CONTRACTOR

LCE LIGHTING CONTACTOR ENCLOSURE

LIGHTING CONTROL ENCLOSURE

LCP LOCAL CONTROL PANEL

LCS LOCAL CONTROL STATION

LOA LOCAL-OFF-AUTO

LOR LOCAL-OFF-REMOTE

LOS LOCK OUT STOP

LP LIGHTING PANEL

LS LIMIT OR LEVEL SWITCH

LTG LIGHTING

LWCO LOW WATER CUTOFF

M MAGNETIC MOTOR STARTER

MA MILLIAMPERE

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCLU MOTOR CONTROL LINEUP

MD MOISTURE DETECTOR, MOTION DETECTOR

MDL MAGNETIC DOOR LOCK

MFR MANUFACTURER

MH MANHOLE, MOUNTING HEIGHT

MOV MOTOR OPERATED VALVE

MPR MOTOR PROTECTION RELAY

MS MANUAL MOTOR STARTER

MSH MOTOR SPACE HEATER

MTS MANUAL TRANSFER SWITCH

MV MILLIVOLT, MEDIUM VOLTAGE

MVA MEGAVOLT AMPERE

N NEUTRAL

NGR NEUTRAL GROUNDING RESISTOR

NGT NEUTRAL GROUNDING TRANSFORMER

NC NORMALLY CLOSED

NO NORMALLY OPEN, NUMBER

O OPEN

OL OVERLOAD

OOA ON-OFF-AUTO

OOR ON-OFF-REMOTE

OS OCCUPANCY SENSOR

O/U OVER/UNDER

P PRIMARY, POWER, POLE

PCS PLANT CONTROL SYSTEM

PB PUSH BUTTON, PULL BOX

PE PHOTOELECTRIC SENSOR, PHOTOCELL

PF POWER FACTOR

PFCC POWER FACTOR CORRECTION CAPACITOR

PH PHASE

PL PILOT LIGHT

PLC PROGRAMMABLE LOGIC CONTROLLER

PP POWER PANEL

PR PAIR

PRS PROXIMITY SWITCH

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER, PROGRAM TIMER

R RED, RAISE, RELAY, REVERSE

RECP RECEPTACLE

RES RESISTOR

RH REMOTE HANDSET

RT REPEATING TIMER

RTD RESISTANCE TEMPERATURE DETECTOR

RTU REMOTE TERMINAL UNIT

RVSS REDUCED VOLTAGE SOLID STATE STARTER

S SHORT-TIME, SHIELDED, STARTER

SA SURGE ARRESTER, SPEAKER AMPLIFIER

SCADA SUPERVISORY CONTROL AND

DATA ACQUISITION

SF6 SULFUR HEXAFLOURIDE

SH SPACE HEATER

SN SOLID NEUTRAL

SO SOLENOID OILER

SP SINGLE POLE

SPD SURGE PROTECTION DEVICE

SPDT SINGLE POLE DOUBLE THROW

SPST SINGLE POLE SINGLE THROW

SS SELECTOR SWITCH, START/STOP, STAINLESS STEEL

SSM SOLID-STATE METERING

SSS SOLID STATE STARTER

SST SOLID-STATE TRIP

SUPV SUPERVISORY CONTROL

SV SOLENOID VALVE

SWB,SWBD SWITCHBOARD

SWG,SWGR SWITCHGEAR

T THERMOSTAT, TIMER, TOTALIZER,

TRANSFORMER

TACH TACHOMETER

TB TERMINAL BLOCK

TC TIMER CLUTCH

TD TIME DELAY RELAY

TEMP TEMPERATURE

TM TIMER MOTOR

TQ TORQUE

TR TIMER RELAY, TRIAD

TS TEMPERATURE SWITCH

TTB TELEPHONE TERMINAL BOARD

UG UNDERGROUND

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTS, VOLTAGE RESTRAINED

VA VOLT AMPERE

VAR VARMETER

VFD VARIABLE FREQUENCY DRIVE

VI VACUUM INTERRUPTER

VLS VALVE LIMIT SWITCH

VM VOLTMETER

VPI VALVE POSITION INDICATOR

VS VOLTMETER SWITCH

W WHITE, WATTS

WH WATTHOUR METER

WM WATT METER

WP WEATHERPROOF

WPI WEATHERPROOF IN-USE

WS WALL STATION

X AUXILIARY RELAY

XFMR TRANSFORMER

XP EXPLOSION PROOF

Z AUXILIARY RELAY, IMPEDANCE

ZS POSITION SWITCH

ZSS ZERO SPEED SWITCH

Y YELLOW

DRAWN:

CHECKED:

NO. DATE

DESIGNED:

SCALE

REVISION

FA

IR

FA

X W

AT

ER

PLANNING & ENGINEERING DIVISION

8560 ARLINGTON BOULEVARD

FAIRFAX, VA 22031

GR

IF

FIT

H F

IN

IS

HE

D W

AT

ER

P

UM

PIN

G S

TA

TIO

N

Black & Veatch Corporation

106-4

039

----

----

----

J-E100_ELEC_ABBREV_NOTES.DWG

--

CH

MB

----

----

----

----

ABBREVIATIONS AND NOTES

ELECTRICAL

7-JUN-2021

P0215A

NO

NE

S

OF

T S

TA

RT

ER

S

GR

IF

FIT

H F

IN

IS

HE

D W

AT

ER

P

UM

PIN

G S

TA

TIO

N

SOFT STARTERS

GRIFFITH FINISHED WATER PUMPING STATION FILE NAME:

PROJECT DIVISION DATE:Fairfax WaterBLACK &VEATCHDRAWING

E100SHEETArlington, Virginia

TAX MAP:

FOR PURCHASE OF RVSS EQUIPMENT ONLY - NOT FOR CONSTRUCTION

NONE CO

MM

ONWEALTH OF VIRGIN

IA

PRO

FESSIONAL ENGINEE

R

SCOTT D.STOCKAM

Lic .No.04020320799/2/2021

Page 2: J-E100 ELEC ABBREV NOTES.DWG

1500KVA2.4KV Δ - 480Y/277V

3%Z, 60HZ

3P-20

S4

S2

S1

K

59G

V

3P-5

0

MS

OL

P

V

V

SIZE 2 COMBINATION MAGNETIC MOTORSTARTER, REVERSING OR 2 SPEED

FUSE AND DISCONNECT SWITCH

MEDIUM VOLTAGE DRAWOUT CONTACTOR

LOW VOLTAGE DRAWOUT AIRCIRCUIT BREAKER

SIZE 4 COMBINATIONMAGNETIC MOTOR STARTER

LOW VOLTAGE AIR CIRCUITBREAKER, 3 POLE, 20 AMPERE

HIGH VOLTAGE DRAWOUT AIR ORVACUUM CIRCUIT BREAKER

CIRCUIT NO.22 WITH 3#8 INSULATEDCONDUCTORS AND 1#10 GROUND WIREFOR A 20HP MOTOR WITH 3 POLE,60A, MOTOR DISCONNECT SWITCH AND4#14 INSULATED CONDUCTORS FORAUXILIARY ITEM, AS FOR EXAMPLE ACONTROL STATION, ALL IN 2"CONDUIT.

TRANSFORMER WITH PRIMARY AND SECONDARYVOLTAGE, AND KVA RATING AS NOTED

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

SIZE 1 COMBINATION REDUCEDVOLTAGE AUTOTRANSFORMER

22:3#8,#10G,4#14,2"

15

GENERATOR

KIRK KEY INTERLOCK

RESISTOR

PROTECTION RELAY WITH IEEEDEVICE FUNCTION AS SHOWN

SINGLE-FUNCTION METER

SURGE OR LIGHTNING ARRESTER

GROUND CONNECTION

CURRENT OR POTENTIAL TEST SWITCH

INDICATES THAT ALL OR PART OFCIRCUIT MAY BE ROUTED IN DUCT BANKOR UNDERGROUND. CONDUIT SIZE SHOWNON ONE-LINE IS ABOVE GROUND AND/ORINSIDE OF STRUCTURE. SEE DUCT BANKSCHEDULE AND SECTIONS FOR CONDUITSIZE OF UNDERGROUND PORTION OFCIRCUIT.

ONE-LINE SHOWING POWER AND CONTROLTO A PACKAGE UNIT, AS FOR EXAMPLE ASTEAM GENERATOR OR AN AIR HANDLINGUNIT, SHALL IMPLY THAT ANY AND ALLASSOCIATED EQUIPMENT SHALL ALSO BEINSTALLED AND WIRED AS REQUIRED BYTHE EQUIPMENT FURNISHED.

CS 4#14,3/4"

CONDUCTORS FOR AUXILIARY ITEMSHALL NOT PASS THROUGH MOTORDISCONNECT SWITCH.22:3#8,#10G

4#14,2"

AUXILIARY ITEMS MAY NOTBE COMPLETELY SHOWN

AUXILIARY ITEMS MAYNOT BE COMPLETELYSHOWN

SURGE ARRESTER WITH SURGE CAPACITOR

G

ELECTRICAL INTERLOCKE

5KV1200A49KA

52A 5KV CLASS MEDIUM-VOLTAGE, DRAWOUT, VACUUM ORAIR INSULATED CIRCUIT BREAKER WITH A 1,200 AMPEREFRAME. BREAKER HAS A 49,000 AMPERE MAXIMUMFAULT CURRENT INTERRUPTING RATING.

A LOW VOLTAGE FIXED MOUNTED MOLDED CASE CIRCUITBREAKER WITH A 50 AMPERE TRIP RATING.TRIP UNIT IS NON-ADJUSTABLE THERMAL-MAGNETICTYPE.A LOW VOLTAGE FIXED MOUNTED MOLDED CASECIRCUIT BREAKER WITH A 1200 AMPERE FRAME ANDA 1000 AMPERE TRIP RATING.TRIP UNIT IS ADJUSTABLE SOLID-STATE TYPE WITHLONG-TIME, SHORT-TIME, INSTANTANEOUS, GROUNDFAULT AND ARC-FLASH REDUCTION PROTECTIONFEATURES.

A LOW VOLTAGE, DRAWOUT, POWER OR INSULATED CASECIRCUIT BREAKER WITH A 1600A FRAME AND SOLID-STATETRIP UNIT.TRIP UNIT HAS A SENSOR MODULE RATED FOR 1000AMPERES AND WITH A TRIP RATING OF 800 AMPERES ANDARC-FLASH REDUCTION PROTECTION FEATURES.

1000AT1200AFSSTLSIGAFRD

800AT1000AS1600AF

AFRD

DETAIL A

DETAIL B

DETAIL C

CONDUIT PLUGGED FLUSH. CONDUIT CAPPED.

UNDERGROUND CONCRETE ENCASEDELECTRICAL BANK ROUTED BENEATHSLAB-ON-GRADE

UNDERGROUND CONCRETE ENCASEDELECTRICAL DUCT BANK

WALL MOUNTED LIGHTING FIXTURE. REFER TONUMBER OR LETTER IN FIXTURE SCHEDULE.POWERED FROM LIGHTING PANEL LP1, CIRCUIT 1.CONTROLLED VIA FROM SWITCH A.

POLE OR STANCHION MOUNTED LIGHTING FIXTURE.REFER TO NUMBER OR LETTER IN FIXTURESCHEDULE. POWERED FROM LIGHTING PANEL LP1,CIRCUIT 1. CONTROLLED VIA FROM SWITCH A.

GROUND CONDUCTOR

DIRECT BURIED CONDUIT

CONDUIT TURNING UP. CONDUIT TURNING DOWN.

CONDUIT CONCEALED

CONDUIT EXPOSED

RECEPTACLE POWERED FROMLIGHTING PANEL LP1, CIRCUIT 1.LP1-1

CEILING, PENDANT, OR RECESSED LIGHTINGFIXTURE. REFER TO NUMBER OR LETTER INFIXTURE SCHEDULE. POWERED FROM LIGHTINGPANEL LP1, CIRCUIT 1. CONTROLLED VIA FROMSWITCH A.

1

LP1-1A

LINEAR LIGHTING FIXTURE. REFER TOFIXTURE NUMBER IN FIXTURE SCHEDULE.POWERED FROM LIGHTING PANEL LP1,CIRCUIT 1, VIA SWITCH A.

1LP1-1 A

UNDERGROUND ELECTRIC

OVERHEAD CIRCUIT

L2 - 5

TYPICAL FOR HOME RUN TO BE ROUTED TOLIGHTING PANEL L2 & CONNECTED TO CIRCUIT#5 (MINIMUM NO. 12 AWG CONDUCTORS AND3/4" CONDUIT)

OH OH

UE UE

HORN & STROBE

HORN

THERMOSTAT

JUNCTION BOX

GROUND ROD

GROUND ROD WITH TEST WELL

GROUND CONNECTION

DISCONNECT SWITCH

COMBINATION STARTER

POWER PANEL

LIGHTING PANEL

MISCELLANEOUS PANEL

LIGHTING CONTACTOR

T

J

STROBE

CAMERA

SINGLE POLE SWITCH

CX

60

30

TWO POLE SWITCH

THREE-WAY SWITCHCONTROLLING LIGHTS WITH "A" DESIGNATION

FOUR-WAY SWITCH

2

3A

4MOMENTARY SWITCHCONTROLLING CONTACTOR C1

C1M

DUPLEX RECEPTACLE 120 VOLT

SIMPLEX RECEPTACLE

TWISTLOCK RECEPTACLE

240V, 1Ø RECEPTACLE, TYPICALAMPERE RATING NOTED

DUPLEX FLOOR OUTLET

TELEPHONE OUTLET

480V, 3Ø WELDING RECEPTACLE, TYPICALAMPERE RATING NOTED120 VOLT DUPLEXRECEPTACLE (UPS)

TELEPHONE FLOOR OUTLET

COAXIAL CABLE OUTLET

RANGE RECEPTACLE

DATA NETWORK OUTLET

WIRE CONNECTION POINT

EXTERNAL CONNECTION POINT

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

STARTER, CONTACTOR OR RELAY COIL

NORMALLY OPEN PUSH BUTTON

NORMALLY CLOSED PUSH BUTTON

MAINTAINED PUSH BUTTON

NORMALLY CLOSED GEARED LIMIT SWITCH

NORMALLY OPEN GEARED LIMIT SWITCH

INDICATING LIGHT

FUSE

POTENTIOMETER

CAPACITOR

DIODE

RESISTOR

CONTROL POWER TRANSFORMER

SWITCH

MANUAL STARTER

OVERLOAD

OVERLOAD

ELECTRODE

FLOAT SWITCH(CLOSING ON RISING LEVEL)

FLOAT SWITCH(OPENING ON RISING LEVEL)

PRESSURE SWITCH(CLOSING ON RISING PRESSURE)

PRESSURE SWITCH(OPENING ON RISING PRESSURE)

VACUUM SWITCH(CLOSING ON INCREASING VACUUM)

VACUUM SWITCH(OPENING ON INCREASING VACUUM)

TEMPERATURE SWITCH(CLOSING ON RISING TEMPERATURE)

TEMPERATURE SWITCH(OPENING ON RISING TEMPERATURE)

FLOW ACTUATED SWITCH(CLOSING ON INCREASE IN FLOW)

FLOW ACTUATED SWITCH(OPENING ON INCREASE IN FLOW)

ON TIME DELAY CONTACT(NORMALLY OPEN, WHEN THE COIL IS ENERGIZEDTHE CONTACT WILL CLOSE AFTER A TIME DELAY)

ON TIME DELAY CONTACT(NORMALLY CLOSED, WHEN THE COIL IS ENERGIZEDTHE CONTACT WILL OPEN AFTER A TIME DELAY)

OFF TIME DELAY CONTACT(NORMALLY OPEN, WHEN THE COIL IS DE-ENERGIZEDTHE CONTACT WILL OPEN AFTER A TIME DELAY)

OFF TIME DELAY CONTACT(NORMALLY CLOSED, WHEN THE COIL IS DE-ENERGIZEDTHE CONTACT WILL CLOSE AFTER A TIME DELAY)

TORQUE SWITCH(NORMALLY OPEN)

TORQUE SWITCH(NORMALLY CLOSED)

LIMIT SWITCH(NORMALLY OPEN)

LIMIT SWITCH(NORMALLY OPEN, HELD CLOSED)

LIMIT SWITCH(NORMALLY CLOSED)

LIMIT SWITCH(NORMALLY CLOSED, HELD OPEN)

DIFFERENTIAL PRESSURE SWITCH(NORMALLY OPEN, CLOSING ON INCREASING DIFF.)

DIFFERENTIAL PRESSURE SWITCH(NORMALLY CLOSED, OPENING ON INCREASING DIFF.)

25 - SYNCHRONIZING OR SYNCHRONISM-CHECK DEVICE27 - UNDERVOLTAGE RELAY32 - DIRECTIONAL POWER RELAY37 - UNDERCURRENT OR UNDERPOWER RELAY46 - REV. PHASE OR PHASE-BAL. CURRENT RELAY47 - PHASE SEQ. OR PHASE BAL. VOLTAGE RELAY49 - MACHINE OR TRANSFORMER THERMAL RELAY50 - INSTANTANEOUS OVERCURRENT51 - AC TIME OVERCURRENT RELAY52 - AC CIRCUIT BREAKER59 - OVERVOLTAGE RELAY63 - PRESSURE SWITCH64 - GROUND DETECTOR RELAY67 - AC DIRECTIONAL OVERCURRENT RELAY71 - LIQUID OR GAS LEVEL RELAY81 - FREQUENCY RELAY83 - AUTOMATIC SELECTIVE CONTROL OR TRANSFER RELAY86 - LOCKOUT RELAY87 - DIFFERENTIAL PROTECTIVE RELAY

BREAKER DETAILSSCHEMATIC SYMBOLS

CONDUIT & WIRING INSTALLATION LEGEND

SWITCH & OUTLET SYMBOLS MISCELLANEOUS SYMBOLS

PROTECTION/RELAY DEVICE NUMBERS

HS

20 3P-60

P

PHOTOELECTRIC SENSOR,PHOTOCELLPE

CEILING MOUNTED OCCUPANCYSENSOROS

HORN SPEAKER

DUAL HORN SPEAKER

WALL MOUNTEDCONE SPEAKER

CEILING MOUNTEDCONE SPEAKER

SK

COMMUNICATION SYMBOLS

EX

EXIT LIGHTING FIXTURE. REFER TOFIXTURE NUMBER OR LETTERS IN FIXTURESCHEDULE. POWERED FROM LIGHTINGPANEL 1, CIRCUIT 1.

EM

EMERGENCY LIGHTING FIXTURE. REFERTO FIXTURE NUMBER OR LETTERS INFIXTURE SCHEDULE. POWERED FROMLIGHTING PANEL 1, CIRCUIT 1.

LP1-1A

LP1-1A

LP1-1

LP1-1

R

1

1

DIMMING WALL SWITCHCONTROLLING LIGHTS WITH "A" DESIGNATION

DMA

WALL SWITCH OCCUPANCY SENSORCONTROLLING LIGHTS WITH "A" DESIGNATION

OSA

OS WALL MOUNTED OCCUPANCYSENSOR

E

EE

ONE-LINE DIAGRAM LEGEND

ELECTRICAL LEGENDS

DRAWN:

CHECKED:

NO. DATE

DESIGNED:

SCALE

REVISION

PROJECT DIVISIONDRAWING

TAX MAP:SHEET

FAIRFAX WATERPLANNING & ENGINEERING DIVISION

8560 ARLINGTON BOULEVARDFAIRFAX, VA 22031

FILE NAME:

DATE:

Arlington, VirginiaBlack & Veatch Corporation

106-4

039

----

----

----

J-E101-ELEC_LEGENDS.DWG

--

CH

MB----

----

----

----LEGENDS

ELECTRICAL

7-JUN-2021

P0215A E101NONE

GR

IF

FIT

H F

IN

IS

HE

D W

AT

ER

P

UM

PIN

G S

TA

TIO

N

GR

IF

FIT

H F

IN

IS

HE

D W

AT

ER

P

UM

PIN

G S

TA

TIO

N

SOFT STARTERS

GRIFFITH FINISHED WATER PUMPING STATION

* olZI

o—-p-oH h

4lr o

u1£0 o oJp-bU

I o

0.Io o

o—r-oK

o

0 o

p oo

O^h

o

o ■#

CP0□ ----------0 -]

ocx®

07osjjHQ0 o

07

77

£7

S3 s

sPR­

'S

s □ss

J

J

■e

<§>

—O <>

u—<r

<1

FaM&ai WaterBLACK &VEATCH

FOR PURCHASE OF RVSS EQUIPMENT ONLY - NOT FOR CONSTRUCTION

CO

MM

ONWEALTH OF VIRGIN

IA

PRO

FESSIONAL ENGINEE

R

SCOTT D.STOCKAM

Lic .No.04020320799/2/2021

AutoCAD SHX Text
3P-60
AutoCAD SHX Text
20
Page 3: J-E100 ELEC ABBREV NOTES.DWG

8'-7 3/4"

3'-5"

6'-0

"

20'-1

1/2

"

5'-0"

DRAWN:

CHECKED:

NO. DATE

DESIGNED:

SCALE

REVISION

PROJECT DIVISIONDRAWING

TAX MAP:SHEET

FAIRFAX WATERPLANNING & ENGINEERING DIVISION

8560 ARLINGTON BOULEVARDFAIRFAX, VA 22031

FILE NAME:

DATE:

Arlington, VirginiaBlack & Veatch Corporation

106-4

039

----

----

----

J-E102-ELEC_RM_MEZZ_POWER_PLN.DWG

---

RC

MB----

----

----

----POWER PLAN

ELECTRICAL ROOM AND MEZZANINE

7-JUN-2021

P0215A E102

PMP-008-RVS

PMP-003-RVS

PMP-002-RVS

PMP-007-RVS

PMP-006-VFDPMP-009-VFD

PMP-004-VFD

MEZZANINE FLOOR PARTIAL PLAN EL 255.003/16" = 1'-0"

OPERATING FLOOR PARTIAL PLAN ELECTRICAL ROOM EL 255.003/16" = 1'-0"

NOTES:

1. REFER TO THE DRAWINGS E100 AND E101 FORELECTRICAL LEGEND & ABBREVIATION ANDGENERAL REQUIREMENTS.

2. CABLE TRAY SHALL BE MOUNTED AT 125"(BOTTOM OF THE TRAY). THE TRAYS NEED TOBE CENTERED BETWEEN THE MCLU AND THERVSS.

3. RVSS SHALL BE MOUNTED ON A GALVANIZEDSTEEL "C" CHANNEL MOUNTING FRAME ASSHOWN IN DETAIL D ON S102.

4. ALL THE MEDIUM VOLTAGE CABLE TO ANDFROM THE RVSS SHALL BE ROUTED VIA CABLETRAY.

FPS-MCLU01

FPS-SG01

FPS-MCLU02

FPS-MCC01RIGHT

FPS-MCC01LEFT

FPS-XFMR03

PLC CABINET

PMP-001-RVS(FUTURE)

PLC (MCLU01)

FPS-XFMR04

PLC (MCLU02)

PMP-005-RVS(FUTURE)12" CABLE TRAY(TYP OF 7)

18" CABLE TRAY(TYP OF 7)

36" CABLE TRAY

18" CABLETRAY

3/16"=1'-0"

2'4'6' 10'5'0

FPS-LP01XFMR FOR FPS-LP01

FPS-LP02XFMR FOR FPS-LP02

0 11/2

IF THIS BAR DOES NOTMEASURE 1" THEN DRAWING

IS NOT TO FULL SCALE

FUTURE FPS-VDP01

4/0 GROUNDCABLE TRAYGROUNDING

4/0 GROUNDCABLE TRAYGROUNDING

FOR

CO

NTI

NU

ATIO

N S

EE E

103

FLOOR EL 255.00

GR

IF

FIT

H F

IN

IS

HE

D W

AT

ER

P

UM

PIN

G S

TA

TIO

N

GR

IF

FIT

H F

IN

IS

HE

D W

AT

ER

P

UM

PIN

G S

TA

TIO

N

SOFT STARTERS

GRIFFITH FINISHED WATER PUMPING STATION

BA

B CA

T

c**

1 I

A-AA£i09 f A A

X

WH“1EFPS F'FOl /

F/--------------1

E I ( FPS-PF03 .) Ar +TH

FPS -PF02 - 44? All--------------1

E II ( FPS-PF04 )r--------------1

Eox

T082

I H F3 I■;

;

X-4FPS- GUH08 ■

M\

// /Q □□

ii ///A

FPS-EDHOI

AFPS-AHU01 A

FPS-CC01

'M

A770

y(DG) PDS01 yA

£ £ /it •I AA

y00 r n

.........T1-------------1 1-------------14 LTET TTT OQ|

4 (££ c’

Lm m. — * m.

Fa ax WaterBLACK &VEATCH

FOR PURCHASE OF RVSS EQUIPMENT ONLY - NOT FOR CONSTRUCTION

CO

MM

ONWEALTH OF VIRGIN

IA

PRO

FESSIONAL ENGINEE

R

SCOTT D.STOCKAM

Lic .No.04020320799/2/2021

AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
C
AutoCAD SHX Text
4
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
2
AutoCAD SHX Text
WH
AutoCAD SHX Text
G
AutoCAD SHX Text
WH
AutoCAD SHX Text
D
AutoCAD SHX Text
HF
AutoCAD SHX Text
HF
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
4
AutoCAD SHX Text
3
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
FPS-PF01
AutoCAD SHX Text
FPS-PF03
AutoCAD SHX Text
FPS-PF04
AutoCAD SHX Text
FPS-PF02
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
FPS-EDH01
AutoCAD SHX Text
FPS-AHU01
AutoCAD SHX Text
FPS-GUH08
AutoCAD SHX Text
T
AutoCAD SHX Text
08
AutoCAD SHX Text
T
AutoCAD SHX Text
09
AutoCAD SHX Text
DG
AutoCAD SHX Text
PDS
AutoCAD SHX Text
01
AutoCAD SHX Text
FPS-CC01
AutoCAD SHX Text
E
AutoCAD SHX Text
E
Page 4: J-E100 ELEC ABBREV NOTES.DWG

DRAWN:

CHECKED:

NO. DATE

DESIGNED:

SCALE

REVISION

GRIFFITH FINISHED WATER PUMPING STATION

Black & Veatch Corporation

106-4

039

----

----

----

J-E105-ELEC_RVSS_ONE_LIN_DIAG.DWG

--

CH

MB

----

----

----

----

RVSS ONE-LINE DIAGRAMS

7-JUN-2021

P0215A

NONE

NOTES:

1. REFER TO THE DRAWINGS E100 AND E101 FOR ELECTRICAL LEGEND & ABBREVIATION AND GENERAL REQUIREMENTS.

POWERMONITOR

POWERMONITOR

K NOTE 8 K NOTE 8LWCO LSLL-6200 (FROM SWGR)

LWCO LSLL-6700 (FROM SWGR)

1CT 1CTGFCT 1GFCT

NOTE 6 NOTE 650:5 50:5

C o oFPS-MCLU01-7D: 2#12,#12G, 3/4" NOTE 5

FPS-MCLU01-7E: 20#12, #12G, 1" NOTE 5

FPS-MCLU01-7F: 9-1TR#16S, #12G, 1-1/2" NOTE 5

O o oFPS-MCLU02-3D: 2#12,#12G, 3/4" NOTE 5

FPS-MCLU02-3E: 20#12, #12G, 1” NOTE 5

FPS-MCLU02-3F: 9-1TR#16S, #12G, 1-1/2” NOTE 5

c o oFPS-MCLU01-2D: 2#12,#12G, 3/4" NOTE 5

FPS-MCLU01-2E: 20#12, #12G, 1" NOTE 5

FPS-MCLU01-2F: 9-1TR#16S, #12G, 1-1/2" NOTE 5

2. NOT USED.MSH VS CS CS CS

ALL THE CONTROL SIGNALS FROM THE PUMPS TO THE RVSS WILL BE ROUTED IN THE EXISTING UNDERFLOOR CONDUITS IN THE SLAB THROUGH THE MCLU. THE CABLES WILL BE ROUTED VIA CONDUIT BETWEEN THE MCLU TO THE RVSS.

3.

o c oFPS-MCLU02-8D: 2#12,#12G, 3/4" NOTE 5

FPS-MCLU02-8E: 20#12,12G, 1" NOTE 5

FPS-MCLU02-8F: 9-1TR#16S, #12G, 1-1/2' NOTE 5

4160V, 3PHASE, 3W, 60HZ, 2000A BUS, 50KAIC

FPS-MCLU02 2TOP FPS-MCLU02 2BTM

o

LU

I OCM

NOTE 9 NOTE 9 o

O

OQPOWER

MONITORPOWER

MONITORLU3

K NOTE 8 K NOTE 8LWCO LSLL-6300 (FROM SWGR)

LWCO LSLL-6800 (FROM SWGR)

O1CT 1CT OGFCT GFCTNOTE 6 NOTE 650:5 50:5

4. CABLE TRAY TO BE UTILIZED TO RUN THE MEDIUM VOLTAGE POWER CABLES FROM THE RVSS TO THE MCLU. POWER CABLES FROM RVSS TO MOTOR SHALL BE ROUTED VIA CABLE TRAY AND TO THE UNDERFLOOR CONDUITS THROUGH THE MCLU CUBICLE, AND SHALL BE CONTINUOUS.

ALL NEW CONTROL AND INSTRUMENTATION WIRE AND CABLE SHALL BE ROUTED FROM THE PUMP LOCATION TO THE RVSS VIA EXISTING UNDERFLOOR CONDUITS (UNDER THE SLAB) TO THE MCLU. CONTRACTOR TO PROVIDE OVERHEAD CONDUITS FROM THE MCLU TO THE RVSS FOR ALL THE CONTROL AND INSTRUMENTATION WIRING. CONTROL AND INSTRUMENTATION WIRING FROM RVSS TO PUMP SHALL BE CONTINUOUS, WITHOUT SPLICES .

5.

4160V, 3PHASE, 3W, 60HZ, 2000A BUS, 50KAIC

3CT100/5

NOTE 7

3CT400/5

NOTE 7

3CT100/5

NOTE 7

3CT400/5

NOTE 7

THE EXISTING CAPACITOR BANKS AND THEIR ENCLOSURES AND THE EXISTING MOTOR PROTECTION RELAYS AT THE MCLU WILL BE REMOVED AND TURNED OVER TO THE OWNER. ALL THE ASSOCIATED WIRINGS (DO/DI/CT/PT) AND COMPONENTS (PHASE CTS) WILL ALSO BE REMOVED AND TURNED OVER TO THE OWNER.

6.PARTIAL MCLU02 ONE-LINE DIAGRAMPARTIAL MCLU01 ONE-LINE DIAGRAM

CTS SHALL BE OF SPLIT CORE TYPE AND SHALL BE MOUNTED EXTERNAL TO THE MCLU IN A NEMA 12 ENCLOSURE

7.

8. POWER METER SHALL BE SCHNEIDER ELECTRIC PM8000.

NEW TIME DELAY FUSE SHALL BE PROVIDED UNDER THE MCLU MODIFICATION SCOPE OF WORK.

9.

FILE NAME:

PROJECT DIVISION DATE:Faorlfax rfaterBLACK &VEATCH FAIRFAX WATERPLANNING & ENGINEERING DIVISION

8560 ARLINGTON BOULEVARD FAIRFAX, VA 22031

DRAWING

E105SHEETArlington, Virginia

TAX MAP:

PMP-002-RVS PMP-007-RVS PMP-003-RVS PMP-008-RVSK K K K

MPR MPR MPR MPR

FPS-MCLU01 3TOP FPS-MCLU01 3BTM

NOTE 9 NOTE 9

1-1T

R#1

6S,3

/4'

1-1T

R#1

6S,3

/4'

CN

1-1T

R#1

6S,3

/4'

CD"0

6-1T

R#1

6S,3

/4"

FPS-

RVS

08-2

:9-1

TR#1

6S, 1

-1/2

'

6#14

,3/4

'

FPS-

RVS

08-5

:14#

14,1

coFP

S-R

VS08

-8:4

#14,

3/4'

CD

CL

FPS-

RVS

08-3

:2#1

2,#1

2G,3

/4

Jr

CO

NTI

NU

ED O

N M

CLU

02 O

N E

-104

CO

NTI

NU

ED O

N M

CLU

01 O

N E

-104

PDSH

-670

2 (D

IFFE

REN

TIAL

D

ISC

HAR

GE

VALV

E)2#

14,3

/4"

LEAK

DET

ECTI

ON

/VIB

RAT

ION

/C

OO

LIN

G W

ATER

VAL

VE P

OW

ER2#

14,3

/4"

DIS

CH

ARG

E VA

LVE

OPE

NZS

O-6

702(

LS1

-4)(L

S2-2

)

JAC

KET

LEAK

ALA

RM

YS-6

706

2#14

,3/4

"

6#14

,3/4

"

PSH

H-6

703

(PR

ESSU

RE

SWIT

CH

HIG

H-H

IGH

)

CD

2#14

,3/4

"

0

>

CLO

SED

ON

HIG

HPR

ESSU

RE

PSH

/PSL

-670

1D

ISC

HAR

GE

VALV

EPI

LOT

SOLE

NO

ID

Co

2#14

,3/4

"

2#14

,3/4

"

CO

OLI

NG

WAT

ER V

ALVE

SV-6

701

6#14

,3/4

"FP

S-M

CLU

01-7

G: 3

0#14

, #12

G, 1

-1/4

"

DIS

CH

ARG

E VA

LVE

CLO

SED

ZSC

-670

2 (L

S3-2

)(LS1

-1)

4#14

,3/4

"

-1TR

#16S

,3/4

"

-1TR

#16S

,3/4

"

CN

-1TR

#168

,3/4

"C

DCL

6-1T

R#1

6S,3

/4"

FPS-

RVS

07-2

:9-1

TR

#16S

, 1 -1

/2"

wowo6#

14,3

/4"

woFP

S-R

VS07

-:14#

14,1

"

C/3

CO

>

FPS-

RVS

07-8

:4#1

4,3/

4"

CD

CL

Xcn

FPS-

RVS

07-3

:2#1

2,#1

2G,3

/4"

-1TR

#16S

,3/4

"

-1TR

#16S

,3/4

"

IV3

-1TR

#16S

,3/4

"

CD-O

6-1T

R#1

6S,3

/4"

FPS-

RVS

03-2

:9-1

TR

#16S

, 1-1

/2"

a:O03o6#

14,3

/4"

03oFP

S-R

VS03

-5:1

4#14

,1

03co

>

FPS-

RVS

03-8

:4#1

4,3/

4"00

CL

X

03FP

S-R

VS03

-3:2

#12,

#12G

,3/4

"

FPS-

RVS

03-6

:14#

14,1

"

FPS-

RVS

03-4

:2#1

0,#1

OG

, 3/4

"

Ooa

CO

FPS-

RVS

03-1

:3-4

/0(8

KV),#

4G, 4

'N

OTE

4

-1TR

#16S

,3/4

"

-1TR

#16S

,3/4

"

CN

-1TR

#16S

,3/4

"C

DCL

6-1T

R#1

6S,3

/4"

FPS-

RVS

02-2

:9-1

TR

#16S

, 1 -1

/2"

03o03o6#

14,3

/4"

03oFP

S-R

VS02

-5:1

4#14

,1"

CO

CO

>

FPS-

RVS

02-8

:4#1

4,3/

4"

CD

CL

X

03FP

S-R

VS02

-3:2

#12,

#12G

,3/4

"

FPS-

RVS

02-6

:14#

14,1

FPS-

RVS

08-6

:14#

14,1

"

FPS-

RVS

08-4

:2#1

0,#1

OG

, 3/4

"

oa

o

FPS-

RVS

08-1

:3#1

/0(8

KV),#

6G, 3

" NO

TE 4

Ul

FPS-

RVS

07-6

:14#

14,1

FPS-

RVS

07-4

:2#1

0,#1

OG

, 3/4

"

oa

o

FPS-

RVS

07-1

:3#1

/0(8

KV),#

6G, 3

" NO

TE 4

LO

PDSH

-620

2 (D

IFFE

REN

TIAL

DIS

CH

ARG

E VA

LVE)

2#14

,3/4

'

LEAK

DET

ECTI

ON

/VIB

RAT

ION

/C

OO

LIN

G W

ATER

VAL

VE P

OW

ER2#

14,3

/4'

DIS

CH

ARG

E VA

LVE

OPE

NZS

O-6

802(

LS 1

-4)(L

S2-2

)

JAC

KET

LEAK

ALA

RM

YS-6

806

2#14

,3/4

'

6#14

,3/4

'

PSH

H-6

803

(PR

ESSU

RE

SWIT

CH

HIG

H-H

IGH

)2#

14,3

/4'

CD"D

>

CLO

SED

ON

HIG

HPR

ESSU

RE

PSH

/PSL

-680

1D

ISC

HAR

GE

VALV

EPI

LOT

SOLE

NO

ID

CO

2#14

,3/4

'

2#14

,3/4

'

DIS

CH

ARG

E VA

LVE

CLO

SED

ZSC

-680

2 (L

S3-2

)(LS1

-1)

CO

OLI

NG

WAT

ER V

ALVE

SV-6

801

6#14

,3/4

'FP

S-M

CLU

02-8

G: 3

0#14

, 12G

, 2'

4#14

,3/4

PDSH

-620

2 (D

IFFE

REN

TIAL

D

ISC

HAR

GE

VALV

E)2#

14,3

/4"

LEAK

DET

ECTI

ON

/VIB

RAT

ION

/ C

OO

LIN

G W

ATER

VAL

VE P

OW

ER2#

14,3

/4"

DIS

CH

ARG

E VA

LVE

OPE

N

ZSO

-620

2(LS

1 -4

)(LS2

-2)

JAC

KET

LEAK

ALA

RM

YS

-620

62#

14,3

/4"

6#14

,3/4

"

PSH

H-6

203

(PR

ESSU

RE

SWIT

CH

HIG

H-H

IGH

)C

D2#

14,3

/4"

0

>

CLO

SED

ON

HIG

H

PRES

SUR

E PS

H/P

SL-6

201

DIS

CH

ARG

E VA

LVE

PILO

T SO

LEN

OID

CO

2#14

,3/4

"

2#14

,3/4

"

CO

OLI

NG

WAT

ER V

ALVE

SV

-620

16#

14,3

/4"

FPS-

MC

LU01

-2G

: 30#

14, #

12G

, 1-1

/4"

DIS

CH

ARG

E VA

LVE

CLO

SED

ZS

C-6

202

(LS3

-2)(L

S1-1

)4#

14,3

/4"

THR

UST

RTD

UPP

ER B

EAR

ING

RTD

LOW

BEA

RIN

G R

TD

WIN

DIN

G R

TDS

RES

ET M

CLU

HS-

6801

C

HAN

D-O

FF-R

EMO

TEST

ART-

OFF

HS-

6801

AEM

ERG

ENC

Y ST

OP

HS-

6801

B

VIBR

ATIO

N S

WIT

CH

ES

MO

TOR

SPA

CE

HEA

TER

PLC

(MC

LU-0

2)

MC

LU-0

2

FPS-

VDP0

8

SUR

GE

ARR

ESTO

R

THR

UST

RTD

UPP

ER B

EAR

ING

RTD

LOW

BEA

RIN

G R

TD

WIN

DIN

G R

TDS

RES

ET M

CLU

H

S-63

01C

HAN

D-O

FF-R

EMO

TEST

ART-

OFF

HS-

6301

AEM

ERG

ENC

Y ST

OP

HS-

6301

B

VIBR

ATIO

N S

WIT

CH

ES

MO

TOR

SPA

CE

HEA

TER

PLC

(MC

LU-0

2)

MC

LU-0

2

FPS-

VDP0

3

SUR

GE

ARR

ESTO

R

THR

UST

RTD

UPP

ER B

EAR

ING

RTD

LOW

BEA

RIN

G R

TD

WIN

DIN

G R

TDS

RES

ET M

CLU

H

S-67

01C

HAN

D-O

FF-R

EMO

TEST

ART-

OFF

HS-

6701

AEM

ERG

ENC

Y ST

OP

HS-

6701

B

VIBR

ATIO

N S

WIT

CH

ES

MO

TOR

SPA

CE

HEA

TER

PLC

(MC

LU-O

I)

MC

LU-0

1

FPS-

VDP0

7

SUR

GE

ARR

ESTO

R

THR

UST

RTD

UPP

ER B

EAR

ING

RTD

LOW

BEA

RIN

G R

TD

WIN

DIN

G R

TDS

RES

ET M

CLU

H

S-62

01C

HAN

D-O

FF-R

EMO

TEST

ART-

OFF

HS-

6201

AEM

ERG

ENC

Y ST

OP

HS-

6201

B

VIBR

ATIO

N S

WIT

CH

ES

MO

TOR

SPA

CE

HEA

TER

PLC

(MC

LU-O

I)

MC

LU-0

1

FPS-

VDP0

2

SUR

GE

ARR

ESTO

R

FPS-

RVS

02-4

:2#1

0,#1

OG

, 3/4

"

oo-a

CO

FPS-

RVS

02-1

:3-4

/0(8

KV),#

4G, 4

" NO

TE 4

PDSH

-630

2 (D

IFFE

REN

TIAL

DIS

CH

ARG

E VA

LVE)

2#14

,3/4

"

LEAK

DET

ECTI

ON

/VIB

RAT

ION

/C

OO

LIN

G W

ATER

VAL

VE P

OW

ER2#

14,3

/4"

DIS

CH

ARG

E VA

LVE

OPE

NZS

O-6

302(

LS1

-4)(L

S2-2

)

JAC

KET

LEAK

ALA

RM

YS-6

306

2#14

,3/4

"

6#14

,3/4

"

PSH

H-6

303

(PR

ESSU

RE

SWIT

CH

HIG

H-H

IGH

)2#

14,3

/4"

03

0-

>

CLO

SED

ON

HIG

HPR

ESSU

RE

PSH

/PSL

-630

1D

ISC

HAR

GE

VALV

EPI

LOT

SOLE

NO

ID

CO

2#14

,3/4

"

2#14

,3/4

"

DIS

CH

ARG

E VA

LVE

CLO

SED

ZSC

-630

2 (L

S3-2

)(LS1

-1)

CO

OLI

NG

WAT

ER V

ALVE

SV-6

301

6#14

,3/4

"FP

S-M

CLU

02-3

G: 3

0#14

, #12

G, 1

-1/4

"

4#14

,3/4

"

FPS-

MC

LU02

-8C

:34#

14, 2

'

FPS-

MC

LU02

-8A:

3#6(

8KV)

,#8G

, CAB

LE T

RAY

FPS-

MC

LU02

-8B:

2-#1

2, 3

/4"

FPS-

RVS

08-1

:3-1

/0(8

KV),#

6G, C

ABLE

TR

AY

FPS-

MC

LU02

-3C

:34#

14, 2

"

FPS-

MC

LU02

-3A:

3-4/

0(8K

V),#

4G, C

ABLE

TR

AY

FPS-

MC

LU02

-3B:

2-#1

2, 3

/4"

FPS-

RVS

03-1

:3-4

/0(8

KV),#

4G, C

ABLE

TR

AY

FPS-

MC

LU01

-7C

:34#

14, 2

"

FPS-

MC

LU01

-7A:

3-#6

(8KV

),#8G

, CAB

LE T

RAY

FPS-

MC

LU01

-7B:

2-#1

2, 3

/4"

FPS-

RVS

07-1

:3-1

/0(8

KV),#

6G, C

ABLE

TR

AY

FPS-

MC

LU01

-2C

:34#

14, 2

"

FPS-

MC

LU01

-2A:

3-4/

0(8K

V),#

4G, C

ABLE

TR

AY

FPS-

MC

LU01

-2B:

2-#1

2, 3

/4"

FPS-

RVS

02-1

:3-4

/0(8

KV),#

4G, C

ABLE

TR

AY

CO

NTI

NU

ED O

N M

CLU

01 O

N E

-104

SOFT STARTERS

GRIFFITH FINISHED WATER PUMPING STATION

FOR PURCHASE OF RVSS EQUIPMENT ONLY - NOT FOR CONSTRUCTION

NONE CO

MM

ONWEALTH OF VIRGIN

IA

PRO

FESSIONAL ENGINEE

R

SCOTT D.STOCKAM

Lic .No.04020320799/2/2021

Page 5: J-E100 ELEC ABBREV NOTES.DWG

DRAWN:

CHECKED:

NO. DATE

DESIGNED:

SCALE

REVISION

GRIFFITH FINISHED WATER PUMPING STATION

Black & Veatch Corporation

106-4

039

----

----

----

J-E111-ELEC_RVSS_SCHEM_DIAG.DWG

---

SFR

MB

----

----

----

----

RVSS SCHEMATIC DIAGRAM

8-SEPT-2021

P0215A

NONE

4160V,30

MCLU 120V CPT SS1/SS2

POSITIONCRL CONTACTS OFF REMOTEHAND1-2

SS1 START 3-4STOPHAND 5-6o o -C11 2

CRL

SCHEMATIC SYMBOL LEGENDSS2 START STOPESTOPJ_Q--*

CRRHANDFFj h-o CRL LOCAL

START/STOPo— * —a

< AT OR NEAR DRIVEN EQUIPMENT

| AT MCLU

CD AT PLC

1 2

TRUN/STOPCRR CMD

i|CRR2 REMOTESTART/STOP

*:<

TD1 SET BETWEEN 0-10 SECONDS.TD2 SET BETWEEN 30-60 SECONDS.TD3 SET TIME IS ADJUSTABLE BASED ON DISCHARGE VALVE OPERATION SPEED. TD4 CONTACT SHALL BE CLOSED ALL THE TIME. CONTACT TO PULSE "OPEN" FOR 2 SECONDS TO OPEN MV CONTACTOR IN THE MCLU.

CRL CR2 CR10 TD1 MCLU-MFF FT CR1o- *:<

CRR2 CR1

CR1 CR2 CR10FF FT CR12<>► 4i

EXTERNAL RVSS CONNECTIONTD2 *:<

INTERNAL RVSS CONNECTION

CR1 TD2 CR13M1 START MOTORo- *:<

MOTORRUNNING

R *:<

TD3

RCCR1 TD3 MX

«----- t F--- *FT M2 STOP MOTOR«*■ o-

G MOTORSTOPPEDSS1 SS2

REMOTE REMOTECRR IN REMOTE*:<

5 65 6

TD1 OTO 10 SEC*:<

MOTOR PROTECTION RELAY

MOTOR WINDING HIGH TEMP DO-2

*:<

CR5 *:<

BEARING HIGH TEMP DO-3

CR6 *:<

VIBRATION HIGH DO-4CR3 VIBRATION

HIGH*:<

VIBRATION LOW DO-5CR4 VIBRATION

LOW*:<

NOTE 2,3T I LL BEARING RTD'S NOTE 4 VIBRATION - HIGH

TD4LWINDING RTD'S NOTE 5 VIBRATION - LOW OPEN MCLU-M (RX)

CR12LS2-2 CLOSE MCLU-M (RN)CR13«*■

CR6CR13 BEARING TEMP HIGH TO PLC

FT«*-CR4TD4CR1 VIBRATION ALARM TO PLCFF«*-CR10

TRIP 86 AT MCLUPUMP ^PRE-TRIP CR2 PUMP PRE­

TRIP FROM MCLURVS FAIL

*:<ESTOP

RVS FAIL CR11 ESTOP TO MCLU■o o-TF CR9— — *:< RESET

RESET MCLU ALARMSo aCR9A RVS FAIL*:< CRR

PUMP IN REMOTE TO MCLU (IN REMOTE)PUMP IN REMOTE TO MCLU (RESET ALARMS)

MPRR1 CRRICR10 COMMON FAIL— *:<

CR9CRR«*■

PUMP IN REMOTE TO PLCCR3 CR8 CR10TF CR7 WARNING— — *:< RVS COMMON FAIL TO PLCCR4 CR7

«*■ RVS WARNING TO PLCA RVS*:<CR5 M1WARNING

PUMP RUNNING TO PLCCR6 M2«*- PUMP STOP TO PLCCR7

RESET

NOTESCR11 RESETCOMMON FAIL

o a«»- *:<

RESETREFER TO THE DRAWINGS E100 AND E101 FOR ELECTRICAL LEGENDS, ABBREVIATIONS AND NOTES.

1.CR8 RESET

WARNINGALARM

«*■ o f>

M1 MPR GROUND CT ARE LOCATED IN THE MV CONTACTOR CUBICLE IN THE MCLU.

2.FF G«*■ ♦

SPACEHEATERENERGIZED

MPR PHASE CTS (3) AND PTS (3) SHALL BE MOUNTED INSIDE THE RVSS.

3.MOTOR SPACE HEATER

M1 • MODBUS TO PLC IN MCLU01/MCLU02* (FUTURE)ETM«*■ LOWER BEARING, UPPER BEARING AND THRUST RTDS INPUT TO

MPR (TOTAL OF 3).4.

5. MOTOR WINDING RTDS INPUT TO MPR (TOTAL OF 6).

6. MPR SHALL BE PROVIDED WITH A SPARE OF 6 DIGITAL OUTPUTS FOR CLIENT CONFIGURATIONS, ALL SPARE DO’S WILL BE PRE-WIRED TO TERMINAL BLOCKS INSIDE THE RVSS.

TYPICAL FOR PMP-002-RVS, PMP-003-RVS j

PMP-007-RVS, PMP-008-RVS

FILE NAME:

PROJECT DIVISION DATE:FaBrlfax WaterBLACK &VEATCH FAIRFAX WATERPLANNING & ENGINEERING DIVISION

8560 ARLINGTON BOULEVARD FAIRFAX, VA 22031

DRAWING

E111SHEETArlington, Virginia

TAX MAP:

SOFT STARTERS

GRIFFITH FINISHED WATER PUMPING STATION FOR PURCHASE OF RVSS EQUIPMENT ONLY - NOT FOR CONSTRUCTION

NONE CO

MM

ONWEALTH OF VIRGIN

IA

PRO

FESSIONAL ENGINEE

R

SCOTT D.STOCKAM

Lic .No.04020320799/2/2021

Page 6: J-E100 ELEC ABBREV NOTES.DWG

ELECTRICAL EQUIPMENT

BOLTS TO ELECTRICAL EQUIPMENT(BY MANUFACTURER)

MC6x12 (GALV) COORDINATE LENGTH ANDLOCATION WITH ELECTRICAL EQUIPMENTSUPPORTS

1/2 " DIA ADHESIVE ANCHOR (EMBED 5")WITH 1 1/2" PROJECTION (GALV)SPACED AT 2'-0" OC (MAX) AND2" MIN FROM END OF CHANNEL

EXISTING 8" THICKCONCRETE SLAB

EQ EQ

1" MIN

TYPICAL EXTRA REINFORCEMENT AT OPENINGS 12" TO < = 54"

CONCRETE COVER FOR REINFORCEMENT

BEAMS & COLUMNS WALLS & SLABS

TYPICAL EXTRA REINFORCEMENTAT ISOLATED RE-ENTRANT CORNERS

LENGTH OF LAPPED SPLICESFOR REINFORCEMENT (INCHES)

**TOP BARS OTHERS **TOP BARS OTHERS

LOCATION SPECIFIED COVER

BARSIZE

*

TYPICAL REQUIRED UNLESS ADDITIONAL REINFORCEMENT SPECIFICALLY INDICATED AT OPENINGS ON DRAWINGS

UNLESS NOTED OTHERWISE ON THE DRAWINGS

4255#7

122#11

#8

#9

#10

69

84

103

94

53

65

79

#3 16

#4

#5

#6

19

33

24

16

16

26

18

3748

108

60

74

91

83

46

57

70

16

19

29

24

16

16

22

18

#7

#11

#8

#9

#10

#3

#4

#6

#5

#5 BAR x 4'-0" LONGEACH CORNER IN CENTERFOR CONCRETE THICKNESS 12"OR LESS EACH FACE FORCONCRETE THICKNESS > 12"

* LAP SPLICE LENGTH FOR BARS OF DIFFERENT SIZES SHALL BE THE GREATER OF THE SMALL BAR LAP LENGTH OR 0.75x THE LARGER BAR LAP LENGTH.

** TOP BARS ARE HORIZONTAL BARS SO PLACED THAT MORE THAN 12" OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR. HORIZONTAL BARS IN WALLS ARE TO BE PROVIDED WITH LAP LENGTHS AS REQUIRED FOR TOP BARS. VERTICAL BARS MAY BE CONSIDERED AS OTHER BARS.

UNFORMED SURFACES ADJACENT TO EXCAVATION................... 3"

SURFACES INSIDE OF OZONE CONTACTORS EXPOSEDTO OZONE IN WATER OR AIR.......................................................... 3"

FORMED SURFACES THAT ARE SUBMERGED, AND FORMEDOR TOP SURFACES EXPOSED TO WEATHER, SATURATEDAIR, OR EARTH................,................................................................. 2"

OTHER LOCATIONS:

BEAMS AND GIRDERS................................................................... 1 1/2"

SLABS, WALLS AND JOISTS: #6 AND LARGER.......................................................................... 1 1/2"

#5 AND SMALLER......................................................................... 1"

NOTES:

1. COVER IS MEASURED TO NEAREST BAR, STIRRUP, TIE, OR SPIRAL, AS APPLICABLE.

2. TOLERANCES FOR CONCRETE COVER AND THE FABRICATION AND PLACING OF REINFORCEMENT SHALL CONFORM TO ACI 117.

EXTRA BARS EQUAL IN TOTAL AREA TO REGULAR REINFORCEMENTCUT BY OPENING. PLACE ONE HALF TOTAL AREA TO EACH SIDE OFOPENING AND IN THE SAME TRANSVERSE POSITION AS REGULARREINFORCEMENT

ONE EXTRA BAR EACH CORNER PER LAYER OFREGULAR REINFORCEMENT (SEE TABLE BELOW)

THICKNESSOF CONCRETE

DIAGONALBAR SIZE

RECTANGULAROPENING

CIRCULAROPENING

DIAGONAL BAR LENGTH

B = THE REQUIRED LENGTH FOR LAPPEDSPLICE FOR TOP BARS AS SHOWN ON THIS SHEET

< 12"12" TO 18"

> 18"

#4#5#6

3'-0"3'-0"3'-0"

D+12"D+12"D+12"

NOTE:TYPICAL REQUIRED UNLESS ADDITIONAL REINFORCEMENTSPECIFICALLY INDICATED AT OPENINGS ON DRAWINGS

#5 BAR x 4'-0" LONGEACH CORNER IN CENTER

B

D B

B

D B

D

FOR CIRCULAR OPENINGS21" < D < = 54"

FOR OPENINGS12" < = D < = 21"

FOR RECTANGULAR OPENINGS21" < D < = 54"

TOP SURFACES OF SLABS THAT ARE SUBMERGED.................... 3"

NO SCALE

NO SCALE

UNLESS NOTED OTHERWISE ON THE DRAWINGS

BARSIZE

*

#5 BAR CONTINUOUSTYPICAL

#5@12" EACH WAYTOP AND BOTTOM

NOTE:FOUNDATION DIMENSIONS DETERMINED BY EQUIPMENT FURNISHEDAND EQUIPMENT ANCHORAGE EDGE DISTANCE REQUIREMENTS.

11 #5@12"

TYPICAL

FINAL GRADE

11

4"

1'-0

"

1'-0

"TY

PIC

AL(4

) SID

ES

1'-0"TYPICAL

3/4"CHAMFERTYPICAL

STANDARDHOOK TOPAND BOTTOMTYPICAL

1'-0"

TYPICAL

SLAB

TH

ICKN

ESS

MIN

US

2"

STANDARD HOOKTYPICAL

LEAVE ROUGHNEW CONSTRUCTION

#4 U-BAR @12"(4) BARS MINIMUM#4 U-BAR @12"

(4) BARS MINIMUM

1 1/2" MINIMUMTO FRONT EDGEOF ENCLOSURE

ADHESIVE ANCHOR INTOCONCRETE FOR EXISTINGCONSTRUCTIONTYPICAL

SLAB THICKNESSMINUS 2"6" MAXIMUM

TOP LAYER REINFORCEMENT

REPLACE OR REMOVE EXIST FLOORCOVERING AS REQUIRED FOR REHABCONSTRUCTION3/4" CHAMFER

TYPICAL

6" MIN

TYP

SEE NOTE 3TYPICAL

NOTES:

1. UNLESS OTHERWISE NOTED, ALL INDOOR FLOOR MOUNTED ELECTRICALEQUIPMENT, INCLUDING SWITCHGEAR, SWITCHBOARDS, MOTORCONTROL CENTERS, ADJUSTABLE FREQUENCY DRIVES, INSTRUMENTCABINETS, ECT., SHALL BE PROVIDED WITH EQUIPMENT BASES.

2. CONTRACTOR AND SUPPLIER SHALL COORDINATE FINAL LOCATION ANDSIZE OF PADS WITH EQUIPMENT FURNISHED. COORDINATE ANCHORBOLT REQUIREMENTS FOR REQUIRED EMBEDMENT DEPTHS ANDCONCRETE EDGE DISTANCES.

3. WHERE THE DESIGN ANCHOR BOLT EMBEDMENT IS GREATER THAN THECONCRETE EQUIPMENT BASE THICKNESS, THEN THE REQUIRED DEPTHOF EMBEDMENT SHALL BE MEASURED FROM THE TOP OF STRUCTURALSLAB AND NOT THE TOP OF THE EQUIPMENT BASE.

4. EQUIPMENT BASE SHALL USE STRUCTURAL CONCRETE AS INDICATED INTHE CAST-IN-PLACE CONCRETE SPECIFICATION.

5. ANCHOR BOLTS AND REINFORCING WILL BE INSPECTED INACCORDANCE WITH THE CODE REQUIRED SPECIAL INSPECTIONS ANDPROCEDURES SPECIFICATION.

..

EXISTING FLOOR.

NEW FLOOR

4"

MANUFACTURERS RECOMMENDEDWALL CLEARANCE

CONDUITS TO BE PLACED INACCORDANCE WITH CONDUITPLACING DETAILS

ANCHOR BOLT AS REQUIRED BY EQUIPMENTFURNISHED. SEE METEOROLOGICAL ANDSEISMIC DESIGN CRITERIA SPECIFICATIONSFOR ADDITIONAL REQUIREMENTS

SEE NOTES 2 AND 4

DRAWN:

CHECKED:

NO. DATE

DESIGNED:

SCALE

REVISION

PROJECT DIVISIONDRAWING

TAX MAP:SHEET

FAIRFAX WATERPLANNING & ENGINEERING DIVISION

8560 ARLINGTON BOULEVARDFAIRFAX, VA 22031

FILE NAME:

DATE:

Arlington, VirginiaBlack & Veatch Corporation

106-4

039

----

----

----

J-S102.DWG

KC

NA

MT----

----

----

----SECTIONS AND DETAILS

STRUCTURAL

11-AUG-2021

P0215A S102NONE

EXTERIOR EQUIPMENT FOUNDATIONC- NO SCALE

STANDARD CONCRETE REINFORCEMENT DETAILSA- NO SCALE 03-S300_USA

03-S340_USA

ELECTRICAL EQUIPMENT BASEB- NO SCALE 03-S360_USA

ELECTRICAL EQUIPMENT SUPPORT CHANNELD- NO SCALE

SOFT STARTERS

GRIFFITH FINISHED WATER PUMPING STATION

:x,i

4-

Iz \\\

Li

\tr—^i lWLxd

[ Vx // E/V /

V/•:X<

^aoFlfax WaterBLACK &VEATCHi®

FOR PURCHASE OF RVSS EQUIPMENT ONLY - NOT FOR CONSTRUCTION