Page 1: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

MAY 2004

Page 2: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

INDEX

SECTION 1 Page

Fig 1 - General Data & Dimensions 1Table 1 - Boiler Dimensions 1Table 2 - Combustion Chamber Data 1Table 3 - Technical Data 2

- Technical Data 3Fig 2 - Base Details 4

- Clearances/ Burner Information 4Fig 3 - Boiler Water Connections (6-7 Sect) 5Fig.4 - Boiler Water Connections (8-15 Sect) 5

SECTION 2

- General Information 6- Installation 7- Boiler Siting and Base 7

SECTION 3

- Ventilation 8- Flue 8- Flue Size Considerations 8- Water Circulation Systems 8- Boiler Protection 9- System Water Quality 9

SECTION 4

- Boiler Erection 10- Risk Assessment 10- C.O.S.H.H. 11- Erection/Assembly Check List 11- Waterway Sealing 12- Erection Procedure 12

Table 4 - Section Build Data/Boiler Sealant Details 13

Fig.5 - Waterway Sealing Details 13- Checking For Leaks 14- Boiler Dismantling 15- Fitting the Casing 15

Fig.7 - Boiler Insulation 15Fig.8 - Fitting Locknuts to Studs 15Fig.9 - Front Panel Fixing 15Fig.10 - Door Fixing 16Fig.11 - Door Micro Switch 16Fig.12 - Firing Door Casing & Insulation 16Fig.13 - Control Panel 17Fig.14 - Rear Casing 17Fig.15 - Boiler Side Rails 17Fig.16 - Boiler Side Panel Fixing 17Fig.17 - Side/Front Panel Fixing 18

- Fitting the Inserts 18- Insert Removal 18- Boiler Tool Storage 18- Cafco Blaze Preparation 19

Table 5 - Insert Dimensions 19Fig.18 - Insert Position 19

SECTION 5 Page

- Boiler Maintenance 20- Cleaning of Flue Surfaces 20- Class ‘D’ Fuel Oil 20- Classes ‘E’ and ‘F’ Fuel Oils and 20 Sludge Gas- Boiler Ancillaries 20- Boiler Controls 21- Commissioning 21- Additional Checks 22- Combustion Analysis (NG) 22- Burner Fan Rotation 22- Fault Finding 22- Overheat Operation 22- Burner Lockout 22

SECTION 6

Fig.20 - Control Panel Wiring 23Fig.21 - Pump Overrun Using Changeover 24

Pipe ThermostatFig.22 - Volt Free Connections 24

SECTION 7

- Casing Pack Details/Part Nos. 25-29

Page 3: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 1INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 1ISIS HE

Fig.1 - General Data & Dimensions (NOT TO SCALE - All measurements in millimetres)

T

N

T

D

1070 205 195

100

P

1405

690

373

200

830

210

70

1" BSPDrainConnection

ControlPanel

LSpecial flue adapterbox available for 6-9section boiler only

REAR SIDE

F

200

690

1050B

or P dimension refer to burner data sheet

able 1 – Boiler DimensionsNo of Sections 6 7 8 9 10 11 12 13 14 15

“L” mm 1255 1435 1615 1795 1975 2155 2335 2515 2695 2875“D” (Diameter) mm 250 350“B” (Diameter) mm 970 1150 1330 1550 1690 1870 2050 2230 2410 2590

OTE: Each boiler is supplied with 2 x 3”-4” extension turrets, 2 x 3” flanges, 1 x blank flange, 1 x 1” flange fordrain cock and 1 x flange for thermostat connections.

able 2 - Combustion Chamber DataNo of Sections 6 7 8 9 10 11 12 13 14 15

Mean Diameter mm 635Cross Sectional Area m² 0.343Length mm 920 1100 1280 1460 1640 1820 2000 2180 2360 2540Volume m3 0.291 0.349 0.407 0.465 0.522 0.581 0.639 0.697 0.754 0.811Surface Area m2 2.15 2.51 2.86 3.22 3.58 3.94 4.3 4.65 5.01 5.38Resistance mm 38 55 73 57 71 67 73 57 100Flue Gas Temperature(Gross) °C 180

Efficiency (Net) %(Gross) %

9082.2

Percentage CO2 Oil %Gas %

129

Heat Release kW/m² 249.3 250.6 244.1 253.7 259.5 259.9 262.3 262.2 254.3 265.6

Note: Base must notprotrude from rear of boiler.

Page 4: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 1 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 2ISIS HE

Table 3 – Technical DataNumber of Sections 6 7 8 9 10 11 12 13 14 15

CE Number BG/EC87/97/127

Output kW 440 516 586 670 762 840 925 1000 1070 1172

Input (Gross) GAS kWOIL kW

536514

629603

714685

817783

929891

1024982

11281082

12191169

13051251

14291370

Input (Net) GAS kW OIL kW

483482

567566

643642

736734

837836

922921

10161015

10981096

11751173

12871285

1 Fuel GAS m3/hrConsumption OIL lit/hr

5047.6

58.755.9

66.763.5

76.272.6

86.682.6

95.591

105.2100.3

113.7108.3

118.8115.9

133.3127

Maximum DesignPressure Bar 6 BAR ALL MODELS

2 Minimum Operating Pressure Bar 0.5 BAR ALL MODELS

3 Nominal Flue Connection Size 250mm DIAMETER 350mm DIAMETER

4 Flue Gas Volume m3/hr 656 770 874 999 1135 1252 1379 1491 1597 1748

Flue Draught Requirements 0 – 4 mm ALL MODELS

5 High Level NaturalVentilation to BS 6644 cm2 1342 1550 1742 1973 2225 2439 2673 2878 3070 3350

5 Low Ventilation NaturalVentilation to BS 6644 cm2 2684 3101 3485 3946 4451 4851 5346 5757 6141 6700

6 Mechanical Inlet to BS 6644 m3/sec 0.482 0.566 0.644 0.735 0.836 0.922 1.02 1.097 1.175 1.286

7 Water Connection Size(See Fig.3 & 4) BSP 3'' 4''

8 Water Flowat 11°C ∆ t lit/sec 9.5 11 12.6 14.5 16.5 18.2 20.1 21.7 23.2 25.4

8 Minimum Water Flowat 11oC ∆ t lit/sec 5.2 6.1 6.9 8.0 9.1 10 11 11.9 12.8 14

8 Hydraulic Resistanceat 11°C ∆ t kPa 2.8 4 5 6.5 8.2 11 13 14.5 15 21

9 Cold Feet Size to BS6644 Minimum Bore mm 38 50

9 Open Vent Size to BS6644 Minimum Bore mm 50 65 80

Safety Valve Size to BS 6644 Nominal Size mm 32 40 50 65 80

2 Maximum Flow Temperature °C 90°C ALL MODELS

10 Minimum Return Temperature °C 55°C ALL MODELS

11 Dry Weight kg 1460 1655 1850 2035 2230 2425 2620 2870 3065 3265

Water Content kg 285 330 375 420 465 510 555 600 645 690

Power Requirements 415V ALL MODELS

For metric to imperial conversions refer to chart inside back cover

Page 5: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 1INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 3ISIS HE

1. FUEL CONSUMPTIONGas fuel consumption is based on natural gas with a gross calorific value of 38.6 Mj/m3. The gas rateshould be corrected for the meter supply pressure particularly on high pressure supplies to preventoverfiring.

Oil fuel consumption is based on Class D (35 second) gas oil with a gross calorific value of45.5 Mj/kg. Kerosene has a gross calorific value of 46.5 Mj/lit.

2. MINIMUM OPERATING PRESSUREThis is the minimum operating pressure of the boiler with pumps operating (NOT static pressure). Therequirements of the Health & Safety Executive guidance note PM5 regarding maximum operatingtemperatures should be observed.

3. BOILER FLUE CONNECTIONThis is the nominal flue size of the flue connection spigot, for dimensional details of the flue connectionspigot see Fig.1. Actual flue size required to achieve correct draught and operation under all runningconditions may need to be increased.

4. FLUE GAS VOLUMEFlue gas volumes are given at STP (standard temperature and pressure 15°C and 1013.25 mbar). Typicalflue gas temperatures are 220°C at CO2 levels of 9% and 12% respectively on gas and oil

5. NATURAL VENTILATIONThe sizes indicated are free grille areas and are based on a single boiler installation.

6. MECHANICAL VENTILATIONThe volume given is for a single boiler installation.

7. WATER CONNECTION SIZESThe boiler connections are flanged with 3'' BSP screwed counter flanges provided. For further details onwater connections see Fig.3 and Fig.4 3'' – 4'' extension turrets are provided with 4” weldable flanges.

8. WATER FLOW RATESWater flow rates are given for boiler flow and return temperature differences of 11°C and 20°C.

9. COLD FEED/OPEN VENT/SAFETY VALVE SIZESSizes indicated are minimum sizes for single boiler installations.

10. MINIMUM RETURN TEMPERATUREIf system return temperatures below 55°C are required then contact the Potterton Commercial TechnicalDepartment.

11. WEIGHTThe dry weight is exclusive of the burner and gas train, see burner data table for relevant burner weights.Each section measures approximately 1.4m x 1m x 0.18m and weights 196kg (front), 185kg (intermediate)and 200kg (rear).

NOTE: ANY PERSON OR PERSONS MOVING OR LIFTING SHOULD BE TRAINED IN MANUALHANDLING TECHNIQUES AND IF NECESSARY USE SUITABLE LIFTING EQUIPMENT TO REDUCETHE RISK OF INJURY TO THEMSELVES OR OTHER PEOPLE.

12. Some burners may require higher than 17.0 mbar inlet pressure, please see relevant burner card fordetails, or contact the Commercial Technical Office.

Page 6: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 1 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 4ISIS HE

Fig.2 – Isis Base Details

Model Length (B)Of Plinth

6 9707 11508 13309 151010 169011 187012 205013 223014 241015 2590

CLEARANCES

The minimum boiler room clearances for access, erection and maintenance are as follows:-

REAR - 500mm (19.7 in) or sufficient to make flue and water connections.SIDES - 200mm (7.9 in) + burner projection on one side, 500mm on the other.FRONT - The length of the boiler to allow for cleaning, 1100mm minimum.

BURNER INFORMATION

For general dimensions and specifications see Potterton Isis burner data sheets. (NB: There is a separate datasheet for each burner type, eg. NuWay, Riello, EOGB.)

The burner should be fitted in accordance with the instructions in Section 4.

The burner unit should be commissioned in accordance with the manufacturers instructions and Potterton burnercard supplied with the burner to obtain the combustion figures detailed. Burner commissioning requires specialistknowledge and equipment. We therefore strongly recommend that the services of the Potterton ServiceDepartment should be used.

Feet details shown are from a 6section boiler. For larger modelsadditional intermediate section feetare added on 180mm spacing

160100

40

60

160

180

180

180

160

300

Rear of Plinth

1050

B

Front of Plinth

NOTE: Boiler base MUST NOTProtrude from rear of boiler

Page 7: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 1INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 5ISIS HE

Fig.3 – Boiler Water Connections (6 & 7 Section)

Fig.4 – Boiler Water Connections (8 – 15 Section)

A/B = Interconnected FloC = Return

= 3'' to 4'' Extension T

A = Flow B = Return AC

A = 3" B = 3"

C = 3"

A = 3" B = 3"

A/B = 2.5"

A = 3" B = 4"

A/B = 3"Flow = 4"

C = 4"

A

Flo

Flow Return

Return

Flow

Return

/B = Interconnected Flow = Return

w

urret

= 3" B = 4"

A/B = 4"w = 4"

C = 4"Return

Page 8: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 2 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 6ISIS HE

GENERAL

This Boiler is NOT SUITABLE for installation in anormally occupied area. (i.e. Kitchen).

A LIFETIME GAURANTEE is available on this boilerplease refer to our standard terms and conditions fordetails.

The Potterton Isis HE cast iron sectional boileravailable in outputs from 440 kW (6 section model) to1172 kw (15 section model). Specially designed andprewired control panels allow full boiler control. Table 3gives kW output and technical data for each model.

The boiler has a match tested package burners,available for Natural Gas, LPG, 35 Second & 28second Oil. Dual Fuel options are also available. Thepackage burner is supported on the front waterwaysection to which it is attached by hinges on one sideand locking nuts on the other. Hinge points areinterchangeable allowing for left or right hand dooropening by turning the door through 180° at theerection stage.

The Isis HE is suitable for use on fully pumped openvented or sealed systems with a maximum designpressure of 6-bar (87 p.s.i.) and up to a maximumoperating temperature of 90°C.

The Isis HE boiler is an overpressure type with threepass, reverse flame design. The first two passes in thecombustion chamber, the third in the convection tubeswhere the turbulence to achieve high heat transfer isgenerated by the extended surface area and insertsachieving operating efficiencies of up to 85.5% grossCV (91% nett CV).

The Isis HE is constructed with BS1452 Grade220 castiron heat exchanger, constructed in accordance withEN303.1 The boiler package meets Gas and Oilrequirements of M&E3 and burners EN767.

The waterway sections are joined with ‘O’ rings andsecured with tie rods with the final sealing of thecombustion chamber being made during assembly withboiler cement and silicone rubber.

The boilers are supplied unassembled and the largestindividual section is approximately 1.4m x 1m x 0.18mand weighs approximately 198 kg.

A 70mm thick insulating blanket encloses theassembled waterway sections and the complete unit isenclosed with pre-coated steel panels finished in red.

Standard Supply

• Unassembled cast iron sections (numberdependent on boiler output).

• Flue Spigot, insert tubes, combustion chamberdoor, burner adaptor plate, flanges, extensionturrets.

• Boiler wrap around insulation• Insulated casing• Cleaning tools• Control Panel

Controls

The Isis HE range are supplied as standard with anintegral control panel which is fitted with boiler on/offcontrol thermostat, high/low thermostat limitthermostat, boiler thermometer, water pressure gaugeand overheat indicator light.

A 240V single-phase supply is taken to the controlpanel. A 415V three-phase supply should be taken tothe burner motor connections.

Optional Extras

• Volt free contacts• Fully closing dampers

Shipping – Packaging

The boiler package is delivered unassembled ontwo/three pallets depending on size with the burnerseparately either in a carton or pallet.

It is recommended that the manufacturer’s trainedengineers should carry out erection andcommissioning, as will make valid the LIFETIMEGUARANTEE. See back page of this manual forservice office addresses.

Page 9: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 2INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 7ISIS HE

INSTALLATION

Before starting work a risk assessment should becarried out in the boiler and its access to determineand ensure a safe installation and workingenvironment.

Any person installing or working on the boiler must bequalified & competent, and in the case of gas firedboilers attention is drawn to the mandatoryrequirement of C.O.R.G.I Registration and qualified toA.C.O.P’s element 16. Also they must be electricallycompetent and adhere to the IEE regulations.

Manual Handling – Any person or persons moving orlifting the boiler or any part of it, should be trained inmanual handling techniques and if necessary usesuitable lifting equipment to reduce the risk of injury tothemselves or other people.

The installation should comply with relevant BritishStandard Specifications, Codes of Practice and currentBuilding Regulations, together with any specialregional requirements of the Local Authorities, GasUndertaking and Insurance Company. All electricalwiring must comply with the IEE Regulations for theElectrical Equipment of Buildings.

The installation of the boiler must be in accordancewith the relevant requirements of: -

• Health & Safety at Work Act 1974.• Building Regulations 1991• Electricity at Work Regulations 1989• Management of H&S at Work Regulations 1992• Manual Handling Regulations 1992• Model Water By-laws 1986• BS 7671: 1992 – Requirements for Electrical

Installations, IEE Wiring Regulations 16th Edition• BS 6644: 1991 – Installation of Gas Fired Hot

Water Boilers for Inputs between 60kW and 2MW• BS 7074: 1989 – Part 2 – Application Selection &

Installation of Expansion Vessels & AncillaryEquipment for Sealed Water Systems

• BS 6880: 1988 – Codes of Practice for LowTemperature Hot Water Systems

• BS 779: 1989 – Cast Iron Boiler for CentralHeating & Indirect Hot water Supply (Rated Output44kW and above)

• CP342.2 – Centralised Hot Water Supply• Gas Safety (Installation & Use) Regulations 1994• IM/11 Flues for Commercial and Industrial gas

Fired Boilers and Air Heaters• IGE/UP/1 – Soundness Testing & Purging

Procedure for Non-domestic Installations• IGE/UP/2 – Gas Installation Pipework, Boosters &

Compressors for Industrial & CommercialPremises.

• BS EN 303.1 & 303

In the event of a gas booster being necessary refer toIM/16 ‘Guidance Notes on the Installation of GasPipework, Boosters and Compressors in CustomersPremises’ and the Gas Act 1972, Schedule 4,Paragraph 18.

Manufacturers notes must not be taken in any way asoverriding statutory obligations.

In addition for oil fired appliances refer to thefollowing:-

BS 799 Oil Burning Equipment.

BOILER SITING AND BASE

The boiler should be sited in accordance with BS 6644:1991 with respect to protecting the boiler fromdamage, air for combustion and ventilation dischargeof products of combustion, clearances for service andaccess, temperatures, noise levels, the disposal ofboiler water and the effects of flooding of the boilerhouse or seepage from a roof top boiler house. Seesection 1 for required boiler clearances for service andaccess.

IMPORTANT: Boiler base must not protrude from rearof boiler otherwise difficulty will occur in fitting 3"- 4"extension turrets on rear return connections.

A level non-combustible floor capable of supporting theweight of the boiler filled with water, see technical data,together with any additional weight bearing down onthe base from connections, burner, etc, must beprovided. This will typically be a 50mm concrete plinthwith an area equal to that of the plan of the boiler.

Consideration should be given to fitting steel stripsbeneath the boiler feet for boiler base protection, seeFig.2 for base details.

The boiler has a water cooled base and no specialinsulation is required. When preparing a site,reference should be made to Local Authorities andBuilding Regulations 1992.

Before any work takes place Risk Assessments shouldbe carried out, to determine what possible risks areassociated with the work which is taking place.

L.P.G boilers should not be installed inbasements/below ground or in a well.

It is not recommended to install commercial boilers inkitchen or living areas.

For further advice on installations, refer toPotterton Technical Bulletins 1 –4.

Page 10: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 3 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 8ISIS HE

VENTILATION

Safe, efficient and trouble free operation ofconventionally flued boilers is vitally dependent onthe provision of an adequate supply of fresh air to theroom in which the appliance is installed. Accountmust also be taken of any other fuel burningappliance existing or to be fitted when designing theventilation and combustion air systems.IMPORTANT: The use of an extractor fan in thesame room as the boiler (or in an adjacent roomin communication) can, in certain conditions,adversely affect the safe operation of the boilerand therefore must be avoided.

Further guidance on ventilation for gas appliances isprovided by BS 6644: 1991. For oil see relevantStandard.

FLUE

To ensure safe and satisfactory operation thechimney system, which may be individual or commonin the case of modular boiler installations, shall becapable of the complete evacuation of combustionproducts at all times. The effective height of thechimney terminal(s) above the boiler(s) flue outlet(s)shall ensure sufficient buoyancy to overcome theresistance of the bends, tees and runs of the fluepipe involved and shall terminate in a down draughtfree zone. The number of bends used should bekept to a minimum and runs of flue pipe less than 45°to the horizontal should be avoided in order tocomply with the recommendations made in BS 6644:1991 and British Gas publication IM/11 "Flues forCommercial and Industrial Gas Fired Boilers and AirHeaters". The third edition of the 1956 Clean Air ActMemorandum and the Building Regulations shouldbe strictly observed and approval obtained whereapplicable, combustion chamber details are given insection 1.

The flue system must be designed to workspecifically to remove the products of combustion.IMPORTANT: 90° square bends must not be usedon the flue system, including the boiler fluespigot, a straight length followed by an "easysweep" or lobster back bend should be used.

FLUE SIZE CONSIDERATIONS

Nominal flue connection sizes are given in Table 3,these sizes refer to the boiler flue connection spigot.

The actual size of the flue system will depend onindividual site applications. Below are generalconsiderations on sizing flue systems.

Horizontal Flue Runs

Horizontal flue runs are not recommendedparticularly over 3m in length, where these areunavoidable advice should be sought from a fluesystem specialist.

Common Flue Systems

Where multiple boilers are installed on a commonflue system then the flue system should be designedto ensure the correct operation of the flue on varyingload conditions. In particular that the appliance fluedraught is within the operating parameter under fullload and partial load conditions. For safe andreliable operation of the boiler plant it isrecommended that the variance in flue draughtavailable at each appliance under full and part loadoperation is designed to a minimum.(It is essential that the services of a specialistflue system manufacturer are sought for thedesign of common flue systems).

For further information regarding ventilation andflueing see Potterton Technical Bulletin No.4, currentissue or see relevant British Standard publicationBS6644: 1991.THE ABOVE RECOMMENDATIONS ARE FORGENERAL GUIDANCE ONLY. POTTERTONCOMMERCIAL DIVISION CANNOT ACCEPTRESPONSIBILITY FOR FLUE SYSTEM DESIGNSBASED ON THE ABOVE RECOMMENDATIONS.

WATER CIRCULATION SYSTEMS

The water circulation system should be indirect andinstalled in accordance with the relevant parts ofBritish Standards Codes of Practice CP342.2 and BS6644: 1991.

The maximum and minimum design temperaturedifferential across the boiler should be 20°C and10°C and the boiler should be prevented fromoperating with flow rates giving a temperaturedifference across the boiler greater than 25°C basedon the full boiler output.

It is essential that all pipework connections to theboiler are self supporting, correctly aligned andallow for free expansion of both boiler andpipework.Care should be taken in the pipework design toprevent strain on the connections. Excessivestrain can lead to premature failure of the boiler,which is obviously outside the terms of ourwarranty.The use of expansion bellows to take up bothaxial and lateral movement is recommended.

Page 11: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 3INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 9ISIS HE

Page 12: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 3 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 10ISIS HE

Boilers operating under constant flow conditions canbe more accurately controlled and are not subject toexcessive temperature stresses.The boilers MUST NOT be fired under anycircumstances with less than the minimum waterflow.

On systems with variable flow rates due to flowreducing devices, ie. TRVs, zone valves, etc, orwhere the minimum heat demand, ie. summerdomestic hot water load, does not achieve theminimum boiler flow rate then consideration shall begiven to incorporating a primary loop system.

It is recommended that the system is designed togive a constant boiler flow rate. For furtherinformation on water circulation systems seePotterton Technical Bulletin No. 1 current issue.

BOILER PROTECTION

The provision of pump overrun by a time delay relayor a thermostat situated in the flow pipe close to theboiler is essential to remove residual heat from theboiler, see Fig.21, section 6.

Unions and isolating valves should be fitted to theflow and return manifolds so that the boiler can beisolated from the system if the need arises. Yourlegal obligations must be adhered to. (i.e. appropriatesafety valves must be fitted).

System Filling

The system must be clean, as debris regress willdamage the boiler.

IMPORTANT: The water level in the cistern orexpansion tank should be minimal on coldcharge to allow expansion without dischargefrom the overflow between cold and hotoperating conditions.

SYSTEM WATER QUALITY

High efficiency boiler systems require the waterquality of the system water to be controlled by theuse of inhibitors to maintain a neutral Ph and inhibitcorrosion. Additionally the water system should befree of leaks to prevent raw water make up which willdilute any inhibitors, promote corrosion and form limescale. Existing SystemsOn existing systems where boilers are beingreplaced due to failure then the cause should beinvestigated before installing new boilers. This cannormally be achieved by cutting open a failed boiler

section and examination for system debris orcontamination. Lime scale is a positive indicator of continuoussystem water make up due to water loss. Evidence ofmagnetite (black sludge) in the system and theformation of gas in radiators causing air locking is apositive indicator of corrosion.Where an old system shows evidence ofcontamination then system cleaning should becarried out before installation of new boilers. Theheating system should be chemically flushed toremove any lime scale or corrosion and a corrosionand lime scale inhibitor added. Lime scale descalersif incorrectly used could cause any remaining systemdebris to continue to breakdown and contaminate thenew boiler causing boiler failure. Advice on system cleaning and suitable productsshould be sought from specialist suppliers of systemcleaners such as Fernox or Sentinel. It is important to note that corrosion inhibitor can onlybe used in an attempt to prevent corrosion fromoccurring, where a system has an existing corrosionproblem, inhibitors will be ineffective and the systemrequires cleaning.

On existing systems where comprehensive descalingand desludging cannot be carried out thenconsideration should be given to separating the newboiler system from the existing system pipe work bythe use of plate heat exchangers. New SystemsNew pipe work systems should be thoroughly flushedwith a suitable cleaning agent to remove debris andflux residues before filling. The system water shouldbe dosed with a suitable corrosion and lime scaleinhibitor. System Water MonitoringThe system water should be monitored as part of amaintenance programme to ensure the following.Raw water make up is not occurring.Corrosion and lime scale Inhibitors are still activeWater Ph is below Ph 8.5 other wise on systems withaluminium content, component failures may occur.

SEALED SYSTEMS

GeneralPotterton Commercial boilers are suitable for use onsealed systems designed in accordance with BS6644: 1991 and BS 6880 Part 2. In addition,reference should be made to the Health & SafetyExecutive guidance note PM5 "AutomaticallyControlled Steam & Hot Water Boilers.

Page 13: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 4 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 10ISIS HE

BOILER ERECTION

A lifetime guarantee is available on this boiler whenerection and commissioning is carried out by thePotterton Commercial service department and thesystem meets with our recommendations. Pleaserefer to our standard terms and conditions for furtherdetails.

Risk Assessment

Before starting work a risk assessment should becarried out on the boiler house and its access todetermine and ensure a safe installation and workingenvironment.

Regardless of the type of activity being assessed, theprinciples of risk assessments are the same. Thebasic steps are: -

• Classify Activity• Identify Hazards• Identify Existing Control Measures• Determine Risk• Assess Acceptability of Risk• Prepare a Control Plan• Implement Plan• Review Plan• Record Results

Manual Handling

Any person or persons moving or lifting the boiler orany part of the boiler, should be trained in manualhandling techniques and if necessary use suitablelifting equipment to reduce the risk of injury tothemselves and other people.

Personal Protective Equipment

When undertaking any work you must comply withthe Personal Protective Equipment Regulations1992.

Confined Spaces

A “confined space” as defined in the Health & SafetyConfined Spaces Regulations 1997 ‘ means anyplace, including any chamber, tank, vat, silo, pit,trench, pipe, sewer, flue, well or other similar spacein which, by virtue of its enclosed nature, there arisesa reasonably foreseeable specified risk.

Precautions should be taken in all areas where byvirtue of its even partially enclosed nature, pose areasonably foreseeable specified risk.

Electrical Safety

Working on appliances can be broken down into twomain systems of work.

1) Safe systems of work are adapted for all boilermaintenance and repair work undertaken on site.

2) The work undertaken does not affect theelectrical safety of the appliance. In particular theearth connected to the buildings fixed electricalinstallation.

In the case of (1) above electrical work should onlybe undertaken once the boiler has been isolated fromthe electricity supply and confirmed electrically dead.If this is impractical then suitable precautions must beundertaken to prevent injury.

In the case of (2) above checks are specified toidentify any abnormality in the electricity supply to theboiler as well as to confirm that the boiler electricalconnections are reinstated correctly where it isnecessary to disconnect or reconnect any internalwiring within the boiler.

If it is necessary to disconnect and reconnect theappliance from the site electrical installation otherthan means of a plug and socket then additionalchecks shall be undertaken by an approved engineerto check the earth loop impedance in accordancewith IEE regulations.

Always carry out preliminary electrical safety checks.

All appliances and central heating systems must beprovided with their own means of isolation for safetypurposes especially during installation andmaintenance.

Packaging Details

A detailed breakdown of the contents of thepackages is given in section 7.

Preparation

Preparatory to installation of the boiler a check mustbe made to ensure that suitable facilities areavailable for off-loading of the individual waterwaysections and conveying them to the boiler room.Each waterway section weighs approximately 198 kgand measures 1400mm x 1000mm x 180mm. Ensureall manual handling techniques are followed.

Particular attention must be paid to ensuringcleanliness of the boiler room and waterway sections,dust or moisture may result in imperfect adhesion ofthe sealants which are applied during the erection ofthe waterways. All tapped holes should be degreasedbefore making connections.

Page 14: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 4INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 11ISIS HE

C.O.S.H.H

During the erection procedure there are a number ofitems which are subject to the Control Of SubstancesHazardous to Health (C.O.S.H.H) Regulations, andmay require specialist personal protective equipment(P.P.E) beyond what is normally required. Listedbelow are the items subject to the C.O.S.H.Hregulations and the recommended precautions thatshould be taken. For a full breakdown of anysubstances listed below, please contact theCommercial Technical Department.

1) Fire Putty 1000 – Wear gloves, overalls andsafety glasses. In the case of an irritation rinsethe affected area with water and wash gently. Inthe case of eye contact, flush abundantly withwater. If irritation persists seek medical advice.

2) Brandkitt 1000 – Wear gloves, overalls andsafety glasses. In the case of an irritation rinsethe affected area with water and wash gently. Inthe case of eye contact, flush abundantly withwater. If irritation persists seek medical advice.

3) Refractory Ceramic Fibre – Wear gloves andoveralls. In the case of an irritation rinse theaffected area with water and wash gently. In thecase of eye contact, flush abundantly with water.If irritation persists seek medical advice.

Potterton Commercial CustomerErection/Assembly Check List

The items listed below have been put together as aguide to what actions should be completed before theerection/assembly of a boiler takes place.

I. Site access available for persons carryingout the proposed work.

II. Site managers/personnel aware that workwill be taking place.

III. Risk assessments carried out on possiblerisks that may effect the persons carrying outthe proposed work.

IV. Sections and fittings boxes should bepositioned adjacent to the plinth(s) within theboiler house prior to persons carrying out theproposed work attending site. If this is unableto be done notice prior to attending siteshould be given.

V. When boilers are to be stripped and rebuilt,labour and transport should be provided formoving the sections from the delivery point to

the final erection point. If this is unable to beprovided notice prior to attending site shouldbe given.

VI. Sections/casing, etc, should be kept in aclean and dry area prior toerection/assembly.

VII. Water should be available.

VIII. A drain off area should be available.

IX. Power should be available.

X. A site representative should be available atall times.

XI. Clear instructions supplied to the personscarrying out the proposed work regardingpositioning the boiler.

XII. Fire evacuation procedures, facilitiesavailability, specific health and safetyinformation, etc, should be provided.

Items VII to X are essential if boilers require pressuretesting.

Page 15: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 4 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 12ISIS HE

Boiler Erection

Waterway Sealing

The waterway sections are sealed at assembly withsilicone rubber compound (Flytande-Packning 260)and boiler sealing cement (Brandkitt-1000 Palokitti1000). The waterway sealing grooves must becleaned and primed with the primer liquid beforeapplying the sealant. The primer must be dry beforeapplying the sealant.

The silicone rubber compound and boiler sealingcement are supplied in cartridges which should beloaded into the sealant gun. The primer liquid issupplied in a bottle and is applied by hand (seeFig.4).

All sealing grooves must be primed and then filledwith the appropriate sealant to form a beadapproximately 5mm (1/4”) proud. This is obtained bycutting the correct size aperture in the cartridgenozzle.

If the nozzle is not cut to approximately 5mm (1/4”)diameter an incorrect amount of sealant will beapplied. When piercing the sealant tube direct thenozzle away from the face or hands to minimise therisk of skin contact.

Before commencing sealing operations sealant andprimer must be checked to ensure that there issufficient for the sections being erected (see table 4for specific quantities). It is advisable to keep sparecartridges to hand if these are available, particularlyfor the boiler cement as some cartridges may containa certain percentage of water, which should be safelydrained off before use.

The sealants and sealant gun, which are suppliedwith the boiler, are classified as consumables. Inaddition to this items standard boiler erection toolswill be required. These should include a crowbar,heavy duty adjustable wrench and a jack for raisingthe firing door.

Erection procedure

Waterway Sections

1. Check off all materials and parts against thedelivery document and boiler parts list (Section 7)ensuring that a sealant gun and adequate supplyof sealants and primer have been provided.

2. Using a clean rag and paraffin, clean the ‘O’ ringgrooves and sockets on the rear waterwaysection.

3. Clean all sealing grooves with a wire brush andapply the primer liquid using the applicator bottleprovided. Allow the primer to dry. This isimportant otherwise the sealant may not stick.

4. Apply a coating of silicone rubber compound5mm (1/4”) proud around each of the two outerboiler sealing grooves. See Fig.5

5. Apply a liberal coating of boiler sealing cementaround the inner sealing groove.

6. Support the rear section in its correct position onthe boiler base.

WARNING: THE SECTIONS ARE NOT SELF-SUPPORTING UNTIL SEVERAL SECTIONS HAVEBEEN ASSEMBLED TOGETHER. THEREFOREWHEN STARTING TO BUILD THE BOILER THEREAR SECTION AND ADJACENT INTERMEDIATESECTIONS SHOULD BE ADEQUATLEYSUPPORTED TO PREVENT INJURY OR DAMAGE.DUE TO THE WEIGHT OF THE SECTIONSASSEMBLY SHOULD BE PERFORMED BY NOLESS THAN TWO OPERATIVES.

Page 16: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 4INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 13ISIS HE

TABLE 4 – Section Build Data/Boiler Sealant Details (Giving quantities required per boiler size)

BoilerSize

OutputkW

Front SectionPt.No.92210102Weight 196kg*

IntermediateSection

Pt.No.92210202Weight 185kg*

Rear SectionPt.No.92210301

Weight 200kg

Boiler Cement(Brandkitt)

Pt.No.922120No. Rqd.

Silicone Sealant(Flytande)

Pt.No.922111No.Rqd.

SiliconePrimer

Pt.No.922119No. Rqd.

6 440 1 4 1 5 9 27 516 1 5 1 5 11 28 586 1 6 1 6 12 29 670 1 7 1 7 13 3

10 762 1 8 1 8 15 311 840 1 9 1 9 16 312 925 1 10 1 10 18 313 1000 1 11 1 10 19 314 1070 1 12 1 11 20 415 1172 1 13 1 12 21 4

• Weights are approximate

Fig.5 – Waterway Sealing Details

SMOOTH SEALANTINTO JOINTS AFTERTIGHTENING UPSECTIONS

SPRAY PRIMER ONALL SEALINGGROOVES, APPLYSEALANT WHENPRIMER IS DRY

“O” RING

“O” RINGGUIDE

BOILER SEALINGCEMENT INSINGLE INNERGROOVE

TIE BOLTS

SILICONE COMPOUND INTWO OUTER GROOVESENSURE BEAD IS 5mmPROUND

SEALANT GUNAND CARTRIDGE

5mm

Page 17: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 4 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 14ISIS HE

7. Fit a metal guide onto the top and bottom socketsin the rear section. These may require tappinginto position using a mallet. Care should be takento avoid damaging the guide rings. Fit an “O” ringover each guide ring.

8. Prepare one face of the first intermediate sectionas described in operations 2 – 5 and place inposition for assembly to the rear section. The twofaces that have been prepared utilising thesealants are now pulled together, this ensuresadequate sealant is throughout the boiler sealinggrooves.

Position the intermediate section directly in frontof the rear section and using a crowbar under thebottom of the intermediate section, gently lift theintermediate section slightly upwards andtowards the rear section engaging the two guiderings.

9. Insert tie bolts through the lower holes into theupper and lower securing lugs (Fig.6). Tightenthese in turn diagonally to ensure that pulling-upis equalised so giving an even pressure on both‘O’ rings. The bolts should be tightened until thetwo section faces are drawn together and toucharound the circumference. Ensure all bolts arefully tightened. A maximum torque of 80 N/mshould be applied.

10. Smooth over the sealing compound, which hassqueezed the section joint and drew to leave aclean bead, slightly proud. Repeat the procedureafter tightening each section.

11. At this stage, position the waterway sections sothat the flue outlet is aligned with the flue ducting,if this is already in position. Ensure that the boilerremains in alignment during assembly of thewaterways.

12. Prepare the sealing grooves and ‘O’ ring guidesof the forward face of the intermediate section(assembled in operation 8) and the rear face ofthe next intermediate section to be fitted.Proceed as previously described until allintermediate waterway sections and the frontwaterway section have been assembled. Thefront waterway section should be installed withthe chamfer pointing towards the front.

Fig.6 – Assembly Tie Bolts

13. Apply primer and silicone rubber compound tothe outer grooves in the rear face of the rearwaterway section and in the grooves on the faceof the flue cover. Offer up the flue cover to therear waterway section and secure with nuts andwashers.

Checking for Leaks

1. Fit blanking plates and gaskets to the boiler flowand return connections but leave a suitabletapping on top rear connection as it used as anair vent during filling and testing.

2. Fit a drain cock with a 1” BSP connection to theflange on the boiler lower front.

3. With all outlets blanked off except the air vent,connect a water supply to the drain cock and fillthe boiler. When this has been done all airexpelled blank off the boiler vent.

4. The maximum design pressure of the boiler mustnot exceed 6 bar and the maximum test pressuremust not exceed 9 bar.

The applied test pressure for assembled boilerfor use on a system designed to operate with aflow temperature not exceeding 100°C (or 17°Cbelow the saturated steam temperature at thedesign working pressure) shall be 1 ½ times thedesigned working pressure for a period of 30minutes. See BS 779: 1989 for further details.

5. Check carefully for leaks around the ‘O’ ringjoints and section interfaces.

RearSection

TieBolts

Page 18: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 4INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 15ISIS HE

6. Open the drain-cock and drain the boiler.Remove the blanking plates. Connect the flowand return 3” – 4” BSP extension turrets to theboiler (8 – 14 Section only).

Boiler Dismantling

IMPORTANT: THE BOILER SECTIONS ARE NOTSELF SUPPORTING PARTICULARLY WHENTHERE ARE ONLY TWO OR THREE SECTIONSLEFT IN SITU. THEREFORE DURINGDISMANTLING THE SECTIONS SHOULD BESUPPORTED TO PREVENT INJURY TOOPERATIVES.

Dismantling of the boiler is a reversal of the erectionprocedure as previously detailed. Care should betaken during dismantling due to the weight of thesections and should be carried out by two operatorsat a time.

Fitting the Casing

To allow fitting of the electrical and fuel services it willbe necessary to fit casing panels as detailed in theparagraphs 1 – 12 below, the flue spigot asparagraph 19 and the burner as detailed underrelevant section. However, the remaining casing andinsulation can, if required, be fitted after constructionhas ceased in the boiler house to minimise damageto the casing.

Fig.7 – Boiler Insulation

1. Fit the insulation strip to the front section asshown in Fig.7 and secure in position using theadhesive tape provided.

2. Fit firing door support brackets to the front face ofthe boiler, together with four studs and securingpins. Fit locknuts to the studs on the door hingeside, see Fig.8

Fig.8. – Fitting Locknuts to Studs

3. Fit the eight hexagonal spacers to the frontsection and fit the front boiler casing. This is atwo piece construction using eight machinescrews provided, see Fig.9.

Fig.9. – Front Panel Fixing

Front Door SupportBracket

Front Insulation StripBoiler BodyInsulation

FixingNut

SecuringPin

Firing DoorSupportBracket

Lock Nut

Hinge Stud

Fixing Spacer

Two PieceFront Casing

Page 19: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 4 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 16ISIS HE

4. Position the door for the required left or righthand opening. The two smaller of the four doorfixing holes should be positioned on the hingeside. Using a jack raise it into alignment with thedoor brackets and engage the door holes withthe appropriate hinge studs. Fit and tighten thefixing screws. See Fig.10.

Fig.10. – Door Fixing

Close the door and fasten it with the door securingnuts, open it and check the impression of the sealinggrooves in the braiding. There should be a uniformimpression approximately 2mm in depth. Adjust bymeans of the fixing nuts to obtain the requiredimpression. Tighten the fixing nuts and the doorsecuring nuts diagonally – as you would whentightening the nuts on a car wheel. This is importantas it ensures an even and adequate seal betweenthe door and front section. Make sure all locknuts arefully tightened and forming an adequate sealbetween the door and combustion chamber.

5. Fit the door micro switch using the bracketprovided. Close the door and adjust the switch sothat the plunger is depressed by the front panelwhen the door is closed. Slots in the bracketfacilitates adjustment, see Fig.11.

6. Fit the firing door insulation panel, see Fig.12.

7. Fit the door casing using the four bolts, nuts andspacers provided, ensure that the top and bottom

side insulation pieces are placed in position, seeFig.12

Fig.11 – Door Micro Switch

Fit the firing door casing side panels using the sixscrews provided, see Fig.12. When fitting the doorcasing ensure that the two side insulation pieces areinserted.

Fig.12 – Firing Door Casing & Insulation

8. Fit the adaptor plate and gasket, see Fig.13, tothe front waterway section. Screw the thermostat,thermometer pockets and the pressure gaugeself isolating fittings into the tapings in theadaptor plate.

9. Fit the control panel housing to the front casingusing the four screws provided, see Fig.13.

Use Jack orWooden Props

MicroSwitch

MountingBracket

ControlPanel

FlexibleConduit

Page 20: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 4INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 17ISIS HE

10. Fit the control panel using the four screwsprovided ensuring that the thermostat andthermometer phials are connected into theirpockets and the pressure gauge sensing head tothe isolating fitting.

Fig.13 – Control Panel

11. Insulate the main boiler body ensuring that theinsulation is drawn down equally on both sides tothe base of the boiler. On larger boilers, wheretwo pieces of insulation are provided, tape theinsulation joint with the tape provided.

12. Insulate the rear section using the insulationpanels provided and mount the rear casingpanels using the three bolts and washers andsecure the two panels together using the screwsprovided, see Fig .14.

Fig.14 – Rear Casing

13. Mount the rear lower panels.

14. Mount the side rails, Fig.15. On 6 section boilersthese are omitted. On larger boilers there areeight rails provided (two for each corner) whichshould be drilled and fixed together to obtain thecorrect overall case dimension, (see Table 1.).

Fig.15 – Boiler Side Rails

15. Mount the side casing panels starting from therear of the boiler. Larger boilers will haveadditional side panels, see parts list. It will benecessary to drill fixing holes for these additionalpanels to compensate for erection tolerances.Ensure side case panels are level from front toback before drilling, see Fig.16.

Fig.16 – Boiler Side Panel Fixing

16. Drill and secure the side panel to the front panelusing the screws provided, see Fig.17.

17. Mount the top panels as shown in Fig.11. Drilland secure in position using the screws provided.

AdaptorPlatePressure

GaugeIsolatingFitting

ThermometerPocket

Data Plate

ControlPanelHousing

ControlPanel

ThermostatPocket

Rear Casing Panels

Flue Spigot

Rear Clean OutCovers

Position and secureusing a drill to suitboiler size

Side Rails

Position side casingand fasten inposition

Page 21: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 4 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 18ISIS HE

Fig.17 – Side/Front Panel Fixing

18. Fit the sight glass. The sight glass is placedbetween the two gaskets in the cast flange,which is then bolted onto the door.

19. Mount the rear cleaning doors and flueconnection spigot ensuring that the flue gasket isused, see Fig.14.

20. Mount the data plate on the front control panelhousing using the fixing screws provided, seeFig.13.

21. When the installation is complete and the boilersare ready to be commissioned, remove theprotective plastic film from the casing panels.

Fitting the Inserts

The Isis HE boiler utilises steel insert tubes in the flueway passes to extend the effective heat exchangersurface area thus increasing the operating efficiency.

WARNING THESE INSERTS MUST BEINSTALLED BEFORE THE BURNER IS FIREDOTHERWISE DAMAGE MAY OCCUR TO THEFLUE SYSTEM DUE TO HIGH EXHAUST GASTEMPERATURES.

1. The insert dimensions vary depending on theboiler size and the dimensions of the tubes to befitted should be checked against the sizes givenin the Parts List prior to fitting to ensure thecorrect inserts are installed.

2. The inserts should be installed with the pointedend, incorporating the removal ring, pointingtowards the front of the boiler and must bepushed fully back as shown in Fig.18.

IMPORTANT: If the inserts are not correctly installeddamage to the insert may occur.

3. The inserts should be positioned to ensure thatthey sit on the support feet as detailed in Fig.19.

Insert RemovalThe inserts should be removed using the insertremoval tool provided by hooking the insert removalring and withdrawing.

Boiler Tool Storage

Following completion of boiler assembly, the cleaningtools, insert removal tool and door access socket and“T” bar should be left in a safe and secure positionwithin the boiler room. It is recommended that a toolrack is incorporated within the boiler house for thispurpose.Fitting the Burner

1. Check that the burner which has been supplied isthe correct type for the boiler.

2. Fit the burner adaptor plates and boiler gasket tothe boiler using the M12 countersunk fixingscrews.

3. Place the burner gasket over the burner fixingstuds.

4. Insert the burner draught tube into the firing dooraperture with the gasket in position on themounting flange. Secure in position with the nutsand washers provided.

5. Prepare the “Cafco Blaze” insulating compoundas detailed below and pack it between thedraught tube and the firing door refractory. It isessential that the whole gap is filled and that thecompound be compressed and finished flush withthe inner face of the door refractory lining.

6. Connect the fuel supply to the burner. The fuelsupply pipes should be self-supporting and notapply undue pressure on the burner.

7. Connect the sight glass cooling tube. One endjoins the burner body, the other end with the sightglass nipple.

IMPORTANT: Failure to connect the cooling tubecan cause damage to the boiler if operated.

8. Connect the burner cable and plug to theAmphenol socket on the control panel.

9. Check the weight of the burner has not affectedthe sealing of the door to the front section,especially after the door has been opened andclosed several times.

Larger burners, especially dual fuel types, shouldbe supported independently with a suitabledevice whilst still allowing the door to be opened.

Drill andsecure frontside panelsusing screwsprovided

FrontCasing

Pre-DrilledRear FixingHoles

Page 22: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 4INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 19ISIS HE

Cafco Blaze Preparation

The Cafco Blaze compound is supplied in nominal 2kg packages. The compound should gradually be mixedwith water until pliable. The Cafco Blaze absorbs approximately 2 litres of water per kilogram.

Table. 5 – Insert Dimensions

No of Sections 6 7 8 9 10 11 12 13 14 15L = Overall Length 945 1125 1315 1315 1665 1665 2025 2025 2385 2385D = Major Diameter 60 60 55 55 60 60 55 55 50 50d = Minor Diameter 60 60 50 50 54 54 50 50 44.5 44.5A = Major Diameter Length 455 635 615 615 1165 1165 1325 1325 1685 1685B = Minor Diameter Length 490 490 700 700 500 500 700 700 700 700

Fig.18 – Insert Position Fig.19 – Insert Position

Dd

B A

L

INSERT LEGS

FLUEWAYINSERT

IMPORTANT The insert must be placedcentral in the flueway

IMPORTANT The insert must be inserted fullyto the rear of the flueway

INSERT

INSERT

COMBUSTIONCHAMBER FLUE

Page 23: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 5 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 20ISIS HE

BOILER MAINTENANCE

It is essential for efficient and trouble free operationthat the boiler plant is regularly maintained. This mustbe carried out by qualified and experiencedengineers and in the case of gas fired appliancesattention is drawn to the mandatory requirement ofCORGI (Confederation of Registered Gas Installers)registration of personnel undertaking work on theseappliances. This facility is available from PottertonCommercial Division, details are available fromregional offices listed on the back page back of thismanual.

Boilers should be serviced and re-commissioned as aminimum on an annual basis.

It is strongly advised that a maintenance contract beentered into with Potterton Commercial Division toensure that the boiler/burner unit is correctly andproperly maintained.

WARNING

Isolate the electrical and fuel supplies beforeattempting any maintenance work.

Cleaning of Flue Surfaces

The boilers are supplied with a set of cleaning toolscomprising flueway brushes and extension rods forroutine cleaning procedures as detailed in the partslist. Boilers may require periodic cleaning withspecialist mechanical equipment dependent on boilerconditions, fuel type, etc.

Cleaning of the boiler requires opening of the door,removal of the boiler inserts, these should beremoved and re-installed as detailed in Section 4.

Frequency of boiler cleaning varies and is dependenton site conditions, fuel type, heat load, design ofcontrols and running conditions.

For the maximum efficiency and economy in runningit is essential that the combustion chamber andflueway surfaces should be kept clean and free fromdeposits.

A layer of deposits 1/16" thick will reduce the heattransfer through the tube wall by up to 10%.

Not only does this waste fuel but the higher flue gastemperatures that result will increase the thermalstress within the boiler and may lead to joint leakageor in extreme cases section failure.

Natural gas, manufactured gas & LPG FiredBoilers

We recommend brushing out of the combustionchamber and flueways and the removal of the rearclean out covers to check for deposits in the flue boxtwice a year.

Class ‘D’ Fuel Oil

The boilers should be brushed out thoroughly at leastbi-monthly for 35 second and Class 2, 28 secondduring the heating season but more frequentattention may be necessary dependent on theoperating conditions to prevent the formation of hardadherent scale on the tube surfaces.

It is essential to ensure that cleaning is carried outthroughout the full length of the flue tube passes andthat the rear clean out covers are taken off to allowfor removal of deposits brushed through into the fluebox.

Should a heavy or tough adherent deposit becomeformed, which is too hard for the standard brush toremove, it may be necessary to either:-

1. Wash out the tubes with water followed by athorough brushing – this may have to berepeated several times.

Or

2. Use a flexible drive rotary tube scalingmachine.

Classes ‘E’ & ‘F’ Fuel Oils & Sludge Gas

Maintenance for boilers running on these fuels will berequired at more frequent intervals, possibly on aweekly basis or even a daily basis dependent on fueltype and quality.

Boiler Ancillaries

Check the sealing of the boiler door against the frontsection. There should be a uniform depression about3/32" (2mm) deep from the sealing grooves of thefront section in the braiding. If this is not uniform, thesealing may be adjusted by the locknuts on the hingepins – see Fig.8. Make sure the locknuts are fullytightened after adjustment is complete.

Keep a regular check on the condition of the doorrefractory and the infill around the burner draughttube. If there is any deterioration this must be madegood immediately to prevent damage to the boilerand burner.

Page 24: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 5INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 21ISIS HE

Boiler Controls

The operation of boiler controls including controlthermostat, high/low thermostat and overheatthermostat should be checked on an annual basisand the burner recommissioned as detailed below.

Safety Interlocks

The operation of safety interlocks such as flowproving on mechanical flue/ventilation systemsshould be checked to ensure that operation of theboiler is prevented on a fault.

COMMISSIONING

IMPORTANT: The boiler must be commissionedfollowing completion of installation. Operation ofan uncommissioned appliance may cause injuryto personnel and damage to the boiler/burner unitand could invalidate the manufacturerswarranties.

Commissioning should only be carried out bypersonnel approved and competent to do so. Thisfacility is available from Potterton CommercialService Offices at the addresses as listed on theback page of this manual.

Commissioning of the burner unit should be carriedout in accordance with the burner manufacturershandbook provided with combustion adjustments inaccordance with the Potterton burner data sheet alsoprovided.

Before commencing to commission the burner checkthe following.

1. Electrical supply is of correct voltage and polarityand earthing is available.

2. Fuel supply is tested for leakage and purged ofair. Ensure the burner is suitable for theconnected fuel supply and pressure.

3. Boiler and system are fully flooded with waterand the operating pressure is within theappliance range.

4. Pumps are operational and any flow provinginterlocks are functional. The operation of thepump should be checked, particularly on sealedsystems, to ensure that operation does not causea reduction in pressure within the system belowthe minimum operating pressure. See section 3for further details on water circulation systems.

5. Ventilation is adequate and, in the case ofmechanical ventilation systems, operation of the

boiler is inhibited unless the ventilation fan isproved.

6. On mechanically assisted flue systems theoperation of the boiler plant should be inhibitedunless the mechanical flue system is operationaland flow proved.

7. The safety valve should be checked to ensurethat it is of the correct size and pressure. SeeSection 3 for further details.

8. The cold feed and open vent sizes should bechecked. See Section 3 for further details.

9. Ensure the burner fitted to the boiler is of thecorrect specification and size for the boiler andsuitable for the fuel supply available.

10. The burner blast tube has been sealed to thedoor refractory and the boiler door seal is correct.See Section 4 for further details.

11. The sight glass cooling tube is connectedbetween the boiler sight glass and burner body.

IMPORTANT: Operation of the burner without thecooling tube connected can lead to boiler damageand a hazardous condition occurring.

12. The boiler door micro switch prevents operationof the burner when door seal is broken.

13. The boiler inserts have been correctly fitted, seeSection 4.

Following completion of the above checks the burnershould be commissioned in accordance with theburner manufacturers handbook provided with theburner. The combustion figures, etc. should becompleted on the commissioning form provided atthe back of this manual and returned to PottertonCommercial at the address on the back page.

IMPORTANT: The boiler/burner units are suppliedin accordance with Potterton Commercial QualityAssurance plan registered to meet therequirements of BS 5750 Part 2. A condition ofthe supply of the appliance for compliance withthis Quality Assurance plan is the return of theappliance commissioning report.

Following/during commissioning of the burner unit thefollowing additional checks should be carried out.

14. Operation of the control, high/low and high limitthermostats should be checked for correctoperation.

Page 25: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 5 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 22ISIS HE

15. The flue draught available at the appliance flueoutlet should be checked under all operatingconditions (hot and cold) and should be withinthe boiler operating parameters, see Table 3

16. The fuel supply to the appliance should beisolated and the burner operated to ensure safetyshut down and lockout of the burner on flamefailure.

17. Shut down of the boiler plant by external controlsdoes not cause a hazardous condition and pumpoverrun is provided to remove residual heat fromthe boiler.

18. Following commissioning the boiler overheat andcontrol thermostats should be set tot he requiredoperating setting. See Section 3 for maximumoperating temperature.

19. Following completion of commissioning thesoundness of all automatic fuel valves should bechecked for leakage.

Additional Checks

Where possible the system should be checked toensure that following purging of air there is no rawwater make-up. In particular, when the system isoperated in the hot condition, there should be nodischarge of water from the safety valve, open ventor cold feed tank overflow that would otherwise leadto unregulated raw water make-up when the systemcools down.

COMBUSTION ANALYSIS (Natural Gas)

When commissioning the burner the combustionfigures must be within the following limits:-

CO2 9 – 9.5%CO 0 – 100ppmFlue Temp 160 220oC (nett)

BURNER FAN ROTATION

Prior to firing the burner check the rotation of theburner fan is correct by starting the burner whenswitching off and watching the fan slow down (referto burner manufacturers instructions for correctrotation direction).

FAULT FINDING

General fault finding for burner failure should be inaccordance with the burner manufactures handbook.Set out below are general guidance notes on systemfault finding.

Overheat Operation

a) The boiler/system pump is adequate for the duty.

b) Operation of flow reducing devices, ie, TRV’scompensated mixing valves, etc., do not reducethe water flow rate through the boiler below theminimum flow rates.

c) Pump overrun is incorporated to dissipateresidual heat from the boiler on system shutdown.

d) The operation of boiler back end valvesincorporate a time delay to allow for removal ofresidual heat from the boiler.

e) The boiler is operating at the correct rate and isnot overfired.

The use of a primary loop system is highlyrecommended to provide a constant boiler flow rateunder all operating conditions. For further informationrefer to Potterton Publication Technical Bulletin No.1Issue 3.

Burner Lockout

The package burners supplied with the boiler unithave an integral safety system to allow the safe andreliable operation of the burner. Failure of the burnerto operate correctly will cause the burner control boxto “lockout” and the lockout button on the burner willilluminate to indicate this.

The lockout condition can be manually reset bypushing the reset button and the control box shouldrestart it’s control sequence in an attempt to light theburner. If the control box lockout will not reset orgoes to lockout after being reset then the services ofa boiler repair/maintenance company should besought. This service is available from PottertonCommercial Division service offices at the addresseson the back page of this manual.

WARNING: The lockout reset button should notbe repeatedly operated otherwise a hazardoussituation may occur.

Should the boiler go to lockout, check the followingbefore attempting to relight the burner.

1. Fuel is available at the burner.

2. The electrical supply to the appliance is ofthe correct voltage and polarity.

The boiler control boxes in some instances haveindicator dials as an aid to fault finding on boilerlockout. In these instances refer to the control boxmanufacturers data sheet for fault finding details.

Page 26: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 6INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 23ISIS HE

Fig.20 – Control Panel Wiring

11

12

10

9

8

7

6

5

4

3

DoorMicroSwitch

Remote OverheatSignal

High/LowInterlock

Control Interlock

Remote BurnerLockout Signal

A

J

ControlStat

Limit Stat(ManualReset) 2

2 1

4

11

10

4

1

21 7

17

3

0

16

10

AM

Black

White Thin

Purple

Orange

Dark Blue ThinGrey

Red Thin

Light Blue Thin

White

Red Thick

Green & Yellow

Brown

Pink

K

2 G

1

N

L3

L2IncomingSupplies415V 50Hz

L

H

M

7

6

5

4

D

C

B

P

E

F

N

3

1

19

PHENOL SOCKET

LIMIT INDICATOR

High/LowStat

L1 3Ph + N

2

0

9

8

P

0

14 1

2

15

18

16

Denotes Site Wiring

Page 27: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 6 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 24

Fig.21 - Pump Overrun Using Changeover Pipe Thermostat

Fig.22 – Volt Free Connections

L1

L2

L3

N

ControlPanelTerminals

IncomingSupply

Pump

No

C

NcAuxillary Contact on boilertime control etc

PipeThermostatSet <55o

L

4 – WA

R1 N

240 VAC

NO14

NC12

COM11

1 9 6 4 N

VOLT-FREER1 – BURNER2 – 1ST STAR3 – 2ND STAR4 – OVERHN - NEUTRA

C

1

Y VOLT-F

R2

AC

NO14

NC12

C1

CONTACR LOCKOUGE RUN INGE RUN INEAT INDICL

REE C

N

240 V

OM1

N1

TST INDIDICATDICAT

ATION

ONNECTOR BOX

R4

AC

NO14

NC12

C1

R3 N

240 VAC

O4

NC12

COM11

CATIONIONION

ONTROL PANEL TERMINAL STRIP

N

240 V

OM1

Page 28: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 7INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 25ISIS HE

ISIS CASING PACK DETAILS (See Drawings)

ITEM DESCRIPTION PART NUMBER QTY/BOILERA Front Door Side Plates 922177 2B Front Door Casing (Not including side plates) 922176POT 1C Control Panel (Complete with Instruments) 922212POT 1D Control Panel Housing 922211 1E Front Left Hand Panel 922193 1F Front Right Hand Panel 922192POT 1G Side Panel (See Table Below)H Left Hand Rear Panel (4– 9 Section) 922196POT 1

Left Hand Rear Panel (10 – 14 Section) 922197 1J Right Hand Rear Panel (6 – 9 Section) 922194 1

Right Hand Rear Panel (10 – 14 Section) 922195 1K Rear Bottom Left Hand Panel 922200 1L Rear Bottom Right Hand Panel 922199 1M Control Panel Top Plate 922213 1N Top Front Panel 922210P Top Rear Intermediate Panel (See Table Below)

Top Intermediate panel *NOT SHOWN* (7 – 14 Section) 922209 1Q Top Rear Edge Panel 922198 1R Front Door Outer Insulation 922173 1S Front Door Top/Bottom Insulation Panels 922175 2T Front Door Side Insulation Panels 922174 2V Flue Hood Insulation (Left Hand) 922218 1W Flue Hood Insulation (Right Hand) 922218 1X Side Panel Support Rail (See Table Below)

Boiler Body Insulation 1.2m Roll *NOT SHOWN* (See Table Below)Boiler Body Insulation 0.6m Roll * NOT SHOWN* (See Table Below)Front Casing Insulation Strip * NOT SHOWN* 922217 2Insulation Sealing Tape *NOT SHOWN* 922214 2Cafco Blaze Burner Sealing Compound *NOT SHOWN* 923010POT 2 bags

Casing Pack Details

BoilerSections

SIDE PANELNo. Off x part No. x length

TOP REARINTERMEDIATE

PANELNo. Off x part No. x

Length

SUPPORT RAILNo. Off x Part No. x

Length

BOILER INSULATIONNo. Off x Pt. No x Width

6 2 x 922205 x 916mm 1 x 922208 x 799mm - x - x - 1 x 922215 x 1.2 m7 4 x 922203 x 556mm 1 x 922206 x 439mm 4 x 922201 x 1057mm 1 x 922215 x 1.2 m

8 2 x 922203 x 556mm2 x 922204POT x 736mm

1 x 922207 x 619mm 4 x 922201 x 1057mm 1 x 922215 x 1.2 m1 x 922216POT x 0.6 m

9 2 x 922203 x 556mm 1 x 922208 x 799mm 8 x 922201 x 1057mm 2 x 922215 x 1.2 m

10 6 x 922203 x 556mm 1 x 922206 x 439mm 8 x 922202 x 1520mm 2 x 922215 x 1.2 m1 x 922216 x 0.6 m

11 4 x 922203 x 556mm2 x 922204POT x 736 mm 1 x 922207 x 619mm 8 x 922202 x 1520mm 2 x 922215 x 1.2 m

1 x 922216 x 0.6 m

12 4 x 922203 x 556mm 1 x 922208 x 799mm 8 x 922202 x 1520mm 2 x 922215 x 1.2 m1 x 922216 x 0.6 m

13 8 x 922203 x 556mm 1 x 922206 x 439mm 8 x 922202 x 1520mm 2 x 922215 x 1.2 m1 x 922216 x 0.6 m

14 6 x 922203 x 556mm2 x 922204POT x 736mm 1 x 922207 x 619mm 8 x 922202 x 1520mm 3 x 922215 x 1.2 m

15 4 x 922203 x 556mm4 x 922204POT x 736mm 1 x 922208 x 799mm 8 x 922202 x 1520mm 3 x 922215 x 1.2 m

Page 29: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 7 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 26ISIS HE

ITEM DESCRIPTION PART NUMBER QTY/BOILER1 Front Section 92210102 12 Intermediate Section 92210202 See Table3 Rear Section 92210301 14 Flue Hood – 250 mm Diameter (6 – 9 Section) 922132POT 15 Flue hood – 350 mm Diameter (10 – 15 Section) 922151 16 Guide Ring (Solid) 922044POT See Table7 "O" Ring (7.3 mm) 922048POT See Table8 Front Door (including refractory – 305 mm Diameter 922107 18a Front Door Rope Seal (Not shown) 922153 19 Inspection Glass (including gasket) 922109 110 Flange for Inspection Glass 922134 111 Cooling Tube 922089 112 Connector for Cooling Tube 922108POT 213 Front Door "T" Bar 922178 114 36 mm Socket for Item 13 922179 115 Hinge Bracket 922135 416 Hinge Bolt 922112POT 417 Retaining Pin 922141POT 418 Door Closing Nut – M24 x 55 922180POT 219 Door Micro Switch (excluding items 20-25 67&68) 922118 120 Bracket for Micro Switch 922165 121 Flexible Conduit 922181 122 Conduit Elbow (including nut) 922182 123 Conduit Coupling (excluding Nut) 922183 124 Coupling Nut 922184POT 125 Micro Switch Bracket Fixing Screw – M6 x 12mm 922005 226 Clean Out Door 3

Insulation Block 922125 1Screws Hex M6 x 30 mm` COM920060 1

27 Locking Handle (excluding item 28) 922015 628 M10 x 50mm Stud 922185 629 3” to 4” Extension Turret 922126 230 4” Counter Flange (Table D) 650115 231 4” Gasket 354697 232 M16 x 50mm Bolt including Nut 617610 833 Flange for Thermostat 922131 134 Flange for Drain (3/4”) 922127 135 Flange – 3” 921948POT 236 Flange Blank 922328POT 137 Gasket – 3” 920326 638 M12 x 40mm Screw (for 3 flanges) 920007 2439 Flue Spigot – 250mm Diameter (6 – 9 Section) 922147 140 Flue Spigot – 350mm Diameter (10 – 15 Section) 922046 141 Gasket for 250mm Diameter Flue Pipe (6 – 9 Section) 922148POT 142 Gasket for 350mm Diameter Flue Pipe (10 – 15 Section) 922047 143 M10 x 30mm Screw – Flue Spigot (6 – 9 Section) 920063POT 4

M10 x 30mm Screw – Flue Spigot (10 –15 Section) 920063POT 644 M10 Washer – Flue Spigot (6 – 9 Section) 617115 4

M10 Washer – Flue Spigot (10 – 15 Section) 617115 645 Boiler Cement (Brandkitt – 1000 Palokitti 1000) 922120POT See Table46 Silicone Sealant (Flytande-Packning 260) 922111 See Table47 Primer for Silicone 922119 See Table48 Applicator for Primer 92211901 149 Applicator for Items 45 & 46 922099 150 Flue Brush **NOT SHOWN** 922186 1

Page 30: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 7INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 27ISIS HE

51 Flue Brush Handle **NOT SHOWN** 922187 152 Flue Brush Extension (6 & 7 Section) **NOT SHOWN** 922188POT 153 Flue Brush Extension (8 – 10 Section) **NOT SHOWN** 922189 154 Flue Brush Extension (11 –13 Section) **NOT SHOWN** 922190 155 Flue Brush Extension (14 – 15 section) **NOT SHOWN** 922191 156a M12 Hexagon Nut 635406 156 Section Tie Bolts – M12 x 230mm 922122 See Table57 Flue Hood Tie Bolts – M12 x 160mm 922123 458 Data Plate 350464 159 M10 x 65mm Screw (Door Panel) 922219 460 M10 x 35mm Screw (Sight Glass) 922035 261 Spacer (for item 59) 922220POT 462 M10 Nut (for item 59) 635402 463 M24 Door Securing Nut 920052POT 464 M12 x 30mm Screw (Door Hinge) 922221 1265 M8 x 30mm Screw (Flue Hood) 635234 466 No.6 x 3.5mm Screw (Data Plate) 922223 467 M4 x 10mm Screw (Micro Switch) 633942 268 M4 Nut (Micro Switch) 635434 269 M4 Washer (Micro Switch) 617116 270 M8 Spacer (Front & Rear Lower) 922227 871 M8 Screw 922228POT 1272 M8 Washer 922229 1273 Self Tapping Screw (for casing) **NOT SHOWN** 922230 See Table74 M12 Countersunk Allen Screw (Burner) **NOT SHOWN** 633301 475 Optional Special Flue Box (6 – 9 Section) 922163 176 Amphenol Socket **NOT SHOWN** 922234 177 High Limit Thermostat 922139 178 Control Thermostat 922138 179 High/Low Thermostat 922138 180 Boiler Temperature Gauge 922144POT 181 Boiler Altitude Gauge 922158 182 Triple Thermostat Pocket 922142 183 Single Thermostat Pocket 922143 184 Pressure Gauge Non-Return Valve 925082 185 Terminal Strip (DIN Rail Mounting) 922001 186 DIN Rail 922002 187 DIN Rail Support Bracket 922003 190 Insert – 6 Section **NOT SHOWN** 922232POT 2291 Insert – 7 Section **NOT SHOWN** 922233 2292 Insert – 8 & 9 Section **NOT SHOWN** 922234 2293 Insert – 10 & 11 Section **NOT SHOWN** 922235 2294 Insert – 12 & 13 Section **NOT SHOWN** 922236POT 2295 Insert – 14 & 15 Section **NOT SHOWN** 922237 22

Quantity required Per Boiler SizeItem Description 6 7 8 9 10 11 12 13 14 152 Intermediate Section 4 5 6 7 8 9 10 11 12 136 Guide Ring (Solid) 10 12 14 16 18 20 22 24 26 287 “O” Ring (7.3mm) 10 12 14 16 18 20 22 24 26 28

45 Boiler Cement (Brandkitt – 1000Palokitti 1000) 5 5 6 7 8 9 10 10 11 11

46 Silicone Sealant (Flytande –Packning 260) 9 11 12 13 15 16 18 19 20 21

47 Primer for Silicone 2 2 2 2 2 2 2 2 2 256 Section Tie Bolts – M12 x 230mm 20 24 28 32 36 40 44 48 52 5673 Self Tapping Screw (for Casing) 70 110 110 110 130 130 130 150 150 150

Page 31: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

SECTION 7 POTTERTON COMMERCIAL PRODUCTS DIVISIONINSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 28ISIS HE

Isis Casing Details

AdaptorPlate

ThermometerPocket Thermostat

Pocket

C

8382

D

58 & 66

333738

A

B FIRINGDOOR

T

SR

35 - 38

61 & 6259

A

REARPANELS

262728

39-4465

L

K

J H

TOPPANELS W

Q

V

M

X

D

PN

910111260

343738

G

E

FSIDE PANELS

C

293031323738

75

67-69

D

2224

Page 32: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 7INSTALLATION, OPERATION & MAINTENANCE MANUAL

PAGE 29ISIS HE

Isis Boiler

Page 33: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

NAT GAS/L.P.G./OIL (KEROSENE & CLASS D) BOILER/BURNER SITE VISIT/COMMISSIONING REPORT IN ACCORDANCE WITH BS5750

REPORT SENT TOINSTALLER: YES NO

SITE VISIT COMMISSIONINGDate:.......................................................................Signature: ..............................................................

REPORT No: ..........................................................SITE ADDRESS: ...................................................................................................................................................................................................................................................................................................................................................................................

INSTALLER NAME & ADDRESS:......................................................................................................................................................................................................................................................................................................................................................COMMISSIONING DATE: .....................................

1.0 BOILER1.1 Type:1.2 No of Sections:

1.3 BoilerNo/Position: RH LH Centre

1.4 Serial No:1.5 Fuel:2.0 BURNER2.1 Type:2.2 Serial Number:2.3 Spec Number:2.4 Control Box Type:2.5 Electrical Supply:2.6* Gas Train Type & Size:2.7* Gas Train Serial No:2.8* Gas Booster Type & Size:2.9* Gas Booster Serial No:3.0 BURNER SETTINGS3.1 Draught Tube Diameter mm3.2 Draught Tube Projection mm3.3 Diffuser Diameter mm

3.4 Diffuser Setting(Distance from end of draught tube) mm

Gas Nozzle: Side No of HolesDiameter mm

End No of Holes3.5*

Diameter mmOil Nozzles: High Fire Size

TypeLow Fire Size

3.5¶

Type

3.6 Electrode Settings?(to burner card/manufacturers instructions?)

3.7 Burner to Specification?(to burner card/manufacturers instructions?)

4.0 PRE-COMMISSIONING CHECKS (See Note)4.1 Is boiler house ventilation as per manual?

4.2 Electric supply fused, isolated & earth wireconnected?

4.3 Check external controls allow operation

4.4 Check boiler/system flooded and pumpsoperational and any isolation valves open

4.5* Check gas available at burner4.5¶ Check oil available at burner4.6* Check gas meter sizing adequate4.7 Check flue system clear5.0 COMBUSTION Pilot Low High Unit5.1* Gas rate m³/hr

5.2* Burner HeadPressure mmwg

5.3* Ionisation Probe/UVCell Current uA

5.4 Air Shutter Position -5.5¶ Oil Pump Pressure bar5.6 CO2 or O2 %5.7* CO ppm5.8¶ Smoke Number -

5.9 Gross Flue GasTemperature °C

5.10 Ambient Temperature °C5.11 Flue Draught mmwg

5.12*Inlet Gas Pressure (high fire). If multiboiler installation, inlet gas pressureall boilers high fire.

mmwg

5.13 Combustion Chamber Resistance mmwg5.14 Burner Fan Static Pressure mmwg

NOTE: Normally 5.13 and 5.14 only recorded when tappingsprovided. Position of measurement to be in accordance withboiler and/or burner manufacturers instructions.

* GAS FIRED INSTALLATIONS ONLY¶ OIL FIRED INSTALLATIONS ONLY

NOTE: It is the installers responsibility to ensure that the boiler is correctly commissioned by a competent engineer and that this report is completedand kept as a record. A commissioning service available from Potterton at the address listed on the back page of this manual. When a Pottertonengineer commissions, this completed report will be sent to the installer. it is the installers responsibility to action any points arising. Commissioningby Potterton engineers is restricted to equipment of our supply. No responsibility is accepted for the on site assembly or installation of the equipmentunless specifically carried out by Potterton. The installer must ensure that the boiler is installed in accordance with the manufacturers instructionsand all relevant BS Codes of Practice and Regulations (see manufacturers instructions for full details). Items 4.1 to 4.6 are related to the boilerinstallation and as such these pre-commissioning checks should be carried out in the presence of the installer.

Potterton is a Member of the Boiler & Radiator Manufacturers Association (BARMA), and the terms of this Commissioning Document follow thegenerally agreed conditions of the Association. Potterton, in line with it’s policy of continuous product development, reserves the right to alterand amend this Document as is deemed necessary at any time.

Brooks House, Coventry Road, Warwick CV34 4LLTel: 08706-050607 Fax: 08706-001516

Page 34: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

6.0 OPERATIONAL SAFETY CHECKS6.1 Check control stat operation6.2 Check limit stat operation6.3 Check high/low stat operation6.4* Check for gas leaks6.5* Check for gas leakage past valve assembly6.5¶ Check for oil leaks6.6 Check boiler locks out on loss of flame signal

6.7 Check boiler locks out on air pressure switchoperation

6.8 Check boiler locks out on all other safetyfunctions

6.9* Check gas booster interlocks operational

6.10Record INLET and OUTLET pressure switch settings:-

INLET ………………….. OUTLET …………………7.0 BOILER/SYSTEM CHECK LIST7.1 Control stat left at °C7.2 Limit stat left at °C7.3 High/low stat left at °C7.4 Maximum flow temperature recorded °C7.5 Maximum return temperature recorded °C7.6 Boiler water pressure7.7 Are pipework connections as per manual?

Is safety valve fitted?7.8 If so, SIZE _________________________

PRESSURE RATING ___________________7.9 Are water isolating valves fitted?7.10 Are water flow switches fitted?7.11 Are return water shut off or diverter valves fitted?7.12 Is shunt pump fitted?7.13 Is pump overrun fitted?

Flue type and diameter of connection to boiler:-

TYPE ………………………DIAMETER (mm) …………

Where appropriate and for multi boiler installationssketch details of flue system showing length of runsand diameters.Conventional Fan Assisted Flue Dilution

7.14

Approximate overall height ………………………….. mIs the fan interlocked with the boiler? YES / NO

7.15 Are flue dampers fitted? YES / NOIf so, interlocked? YES / NO

7.16 Fan assisted ventilation? YES / NO7.17 Any evidence of condensate formation? YES / NO7.18 Any evidence of water leakage? YES / NO7.19 Any evidence of flue gas leakage? YES / NO7.20 Has boiler been built and cased correctly? YES / NO

7.21* Is gas service cock installed? YES / NOIf so, accessible? YES / NO

7.22¶ Is oil filter fitted? YES / NO7.23¶ Is fire valve fitted? YES / NO

Oil supply: Single PipeTwo Pipe7.24¶Ring Main

8.0 COMMENTS ON ACCESSIBILITY FOR MAINTENANCE

9.0 NOTES & COMMENTS BY COMMISSIONINGENGINEER

FINDINGSYES NO

Is the installation safe for use?If the answer is NO, has a warning label beenraised?Is any remedial work required?Have warning labels been fitted?Has RIDDOR form been raised?

Customer Signature:

Print Name:

Date:

ENGINEER DETAILS

NAME

COMPANY

SIGNATURE

DATE

Baxi Heating Ltd.Reg.Office: Pentagon House, Sir Frank Whittle Road,Derby DE21 4XA – Registered in England 3879156

Document ID Ref: PCF/029/3

Page 35: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

CONVERSION TABLE

IMPERIAL TO METRIC METRIC TO IMPERIAL

HEAT1 Therm = 100,000 Btu/hr

1 Btu/hr = 0.2931 W 1 Btu = 1055 J 1 Btu/hr = 0.252 kcal/hr

1 kW = 3412 Btu/hr1 J = 0.0009478 Btu1 kcal/hr = 3.968 Btu/hr

FUEL CONSUMPTION1 dm3 = 1 LITRE1,000 dm3 = 1m3

1 ft3 = 28.317 dm3 (litre) 1 UK Gall = 4.546 litre 1 UK Gall = 1.2 U.S. Gallon

1 m3 = 35.3147 ft31 litre = 0.2199 Imp.Gallon

PRESSURE1 PSI = 2.307 FT1 kPa = 1000 Pa1 bar = 1000 mbar = 100 kPa

1 lb/in2 = 6895 Pa1 lb/in2 = 68.95 mbar1 in.w.g. = 249.1 Pa1 in.w.g. = 2.491 mbar1 in.w.g = 25.4 mm.w.g.

1 bar = 33.45 ft.w.g.1 kPa = 0.3345 ft.w.g.1 bar = 14.5 lb/in2

1 Pa = 0.3858 in.w.g.1 mm.w.g. = 0.0394 in.w.g.1 mm.w.g. = 9.8 Pa

LENGTH1m = 1000mm

1 inch = 25.4mm1 ft = 0.3048 m1 yard = 0.9144 m1 mile = 1.609 km

1 mm = 0.03937 in1 m = 3.281 ft1 m = 1.094 yard1 km = 0.6214 mile

VOLUME 1 ft3 = 0.02832 m3

1 ft3 = 28.32 litre1 m3 = 35.3147 ft31 litre = 0.03531 ft3

AREA 1 in2 = 645.2 mm2

1 in2 = 6.452 cm2

1 ft2 = 929 cm2

1 ft2 = 0.0929 m2

1 mm2 = 0.00155 in2

1 cm2 = 0.155 in2

1 m2 = 1550 in2

1 m2 = 10.76 ft2

FLOW RATE1 kg/sec = 1 lit/sec @0°C reference temperature

1 gall/min = 0.07577 lit/sec1 ft3/min = 0.4719 lit/sec1 ft3/min = 0.00047 m3/sec

1 lit/sec = 13.2 gall/min1 lit/sec = 2.119 ft3/min1 m3/sec = 2119 ft3/min

TEMPERATURE °F to °C = ("X"°F - 32) x 0.5556 °C to °F = ("X" °C x 1.8) + 32

TEMPERATURE DIFFERENCE1°C = 1oK

"X"°F x 0.5556 = °C "X" °C x 1.8 = °F

WEIGHT 1 lb = 0.4536 kg1 cwt = 50.8 kg1 ton = 1016 kg

1 kg = 2.205 lb1 tonne = 0.9842 ton1 tonne = 2204.6 lb

Page 36: Isis HE Installation Guide - pottertoncommercial.co.uk · The volume given is for a single boiler installation. 7. WATER CONNECTION SIZES ... The minimum boiler room clearances for

For further details on Potterton Commercial boiler products contact the following:-

Potterton Commercial Products Division Tel: (08706) 050607Brooks House Fax: (08706) 001516Coventry Road Sales Direct Line: (08706) 001991WARWICK Technical Direct Line: (08706) 002322CV34 4LL e-mail: [email protected]

Web Site: www.pottertoncommercial.co.uk

Our service organisation covers the whole of the U.K. to look after your needs for all PottertonCommercial Products. We are also able to offer our services for other manufacturers products.

SOUTHERN REGION NORTHERN REGIONPotterton Commercial Service Dept Potterton Commercial Service DeptUnit 2, Borehamwood Enterprise Centre Unit 102, Batley Enterprise CentreTheobald Street 513 Bradford RoadBOREHAMWOOD BATLEYHerts WD6 4RQ West Yorkshire WF17 8JYTel: (08702) 412759 Tel: (08702) 412759Fax: (02082) 072466 Fax: (01924) 420276

Our service offices offer a wide range of specialised services including:-

• Boiler Site Assembly• Burner Commissioning for all Fuels• Boiler Maintenance & Maintenance Contracts• Breakdown & Repair Services• Boiler Dismantling & Re-Jointing

• Burner & Boiler Replacement• Oil/Gas Conversions• System Conditioning• Water Treatment & Descaling• Packaged Units

Potterton Commercial spares are available nationwide through the Potterton Interpart network.Alternatively please contact:-

interpart

Brooks House, Coventry Road, Warwick CV34 4LL - Telephone: 08706 000454 Fax: 08706 000545

COMMERCIAL SALES & TECHNICAL ENQUIRIES