ip module technical guide - az2controls.com

20
IP Module Technical Guide www.wattmaster.com

Upload: others

Post on 13-Jun-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

www.wattmaster.com

Page 2: IP Module Technical Guide - az2controls.com

TABLE OF CONTENTS

2 IP Module Technical Guide

WattMaster Controls, Inc.8500 NW River Park Drive · Parkville, MO 64152Toll Free Phone: 866-918-1100PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected] our web site at www.wattmaster.comForm: WM-IPM-TGD-01P Copyright February 2017 WattMaster Controls, Inc. Windows® 2000, Vista, 7, 8 & 10 are registered trademarks of Microsoft Corporation.WattMaster Controls, Inc. assumes no responsibility for errors or omissions.This document is subject to change without notice.

GENERAL INFORMATION ................................................................................................................ 3IP Module Overview ................................................................................................................................................. 3System Overview ..................................................................................................................................................... 3System Requirements .............................................................................................................................................. 3

QUICK START GUIDE ...................................................................................................................... 4

COMMLINK IV IP MODULE INSTALLATION .................................................................................... 5

COMMLINK 5 IP MODULE INSTALLATION ...................................................................................... 6

COMMLINK IV COMMUNICATIONS SETTING ................................................................................. 7

COMMLINK 5 COMMUNICATIONS SETTING .................................................................................. 8

COMMLINK 5 BAUD RATE SETTING ............................................................................................... 9

COMMLINK IV WITH IP MODULE CONNECTIONS AND WIRING .................................................. 10

COMMLINK 5 WITH IP MODULE CONNECTIONS AND WIRING .................................................... 11CommLink with IP Module Hardware Connection.................................................................................................. 12

CONFIGURATION .......................................................................................................................... 13Computer IP Address Set-up for Windows® XP, Vista, 7, or 8 ................................................................................ 13Changing the IP Address of the CommLink ........................................................................................................... 14

TROUBLESHOOTING ..................................................................................................................... 16Connecting the Network - Proxy and Firewall Compatibility .................................................................................. 16CommLink IV LED Descriptions ............................................................................................................................. 17CommLink 5 LED Descriptions .............................................................................................................................. 18Troubleshooting Procedures .................................................................................................................................. 19

Page 3: IP Module Technical Guide - az2controls.com

OVERVIEW

3IP Module Technical Guide

IP Module Overview

The OE415-02 IP Module installs into the CommLink IV or 5Communications Interface and provides a TCP/IP Port connection from the WattMaster control system to a building’s Ethernet LAN, providing communications with the control system through any computer (with Prism 2 software installed) connected to the LAN or the Internet (if confi gured for access through your LAN’s Internet fi rewall).

Using standard TCP/IP Protocol, with WattMaster’s Prism 2 software you are able to monitor and confi gure your controllers without a modem or a direct connection from a PC. Utilizing existing routers, proxies, or fi rewalls allows a PC running Prism 2 to connect to a controller in a remote accessible location orbuilding. Several IP connection profi les can be created to facilitate monitoring several sites.

System Overview

The IP Module is a stand-alone network appliance that connects to a 10BaseT or 10/100 network connection. The IP Module will require an IP address on the local network or a routable IP address provided by an ADSL or cable modem if it is to be accessed through the Internet. The PC will require a dialup or Ethernet network connection to the Internet or local network with routes to the CommLink. Check with your local IT Department in regards to your network routing needs.

The TCP/IP connection itself is a TCP connection made on a single port number and is static in nature. Firewall and proxy servers can be confi gured to allow traffi c to and from this device. The nature of the data is raw in form and comprised of packets native to Prism 2 software. The CommLink will respond to ICMP traffi c (PING) for verifi cation of proper confi guration, but Prism 2 software is required in order to send and receive data to the CommLink.

System Requirements

To program the IP Module to work with Prism 2, you will need:

• CommLink IV or CommLink 5 with power adapter

• IP Module

• Prism 2 software (can be downloaded from any of our websites)

• USB Drivers (can be downloaded from any of our websites)

• A PC with an Ethernet communications port (supplied by others)

• Ethernet RJ-45 Crossover CAT 5, 10 ft. long cable (supplied with the IP Module) and an available network port to connect the CommLink to your computer

• Microsoft Windows® 2000, Vista, 7, 8, or 10 (must be installed on the computer you are going to use)

• An IP Address, Subnet Mask, and Gateway Address for the CommLink’s IP Module. (Ask your Network Administrator for this information.)

• CommLink 5 ONLY - Baud rate of the control system that your CommLink 5 is connected to. See Figure 5, page 9 for further explanation.

General Information

Page 4: IP Module Technical Guide - az2controls.com

QUICK START GUIDE

IP Module Technical Guide4

Quick Start Guide

Quick Start Guide

NOTE: Please note, the R(+) and T(-) terminals on the communications terminal block are reversed from all previous versions of the CommLink.

WARNING: If you are replacing an earlier version of the CommLink with a CommLink 5, be aware that the polarity of the terminal block is reversed on the CommLink 5 from all previous models. You must always confi rm that the polarity is correct when wiring 24 VAC power to the CommLink power terminal block or serious damage to the product will result.

Follow the steps below to get your IP Module up and running in no time.

Step 1: Open your CommLink and snap in your IP Module. See Figure 1, page 5 for CommLink IV directions and Figure 2, page 6 for CommLink 5 directions.

Step 2: Set your CommLink’s communication switch to Multiple or Single. See Figure 3, page 7 for CommLink IV directions and Figure 4, page 8 for CommLink 5 directions.

Step 3: Set your CommLink 5’s Baud Rate switch to High or Low. See Figure 5, page 9.

Step 4: Wire your CommLink to the appropriate controller on your system and plug the CommLink into a power supply. See Figure 6, page 10 for CommLink IV directions and Figure 7, page 11 for CommLink 5 directions.

Step 5: Connect your CommLink to your PC via Ethernet cable. See Figures 8 & 9, page 12.

Step 6: Change your PC’s IP address. See page 13 for instructions.

Step 7: Change the IP address of your CommLink. See page 14 for instructions.

Step 8: Set the baud rate for your CommLink in the Confi guration Settings. See page 15 for instructions.

IMPORTANT NOTES:

Follow the included CommLink connection and wiring instructions sheet (See Figure 6, page 10 or Figure 7, page 11) to connect and confi gure the CommLink for an Ethernet connection.

Make sure you follow the appropriate directions for your Windows® version.

Familiarize yourself with all system components and review all documentation. Pay special attention to “Cautions,” “Notes,” and “Warnings” since these may keep you from experiencing unnecessary problems.

If you encounter any problems, please refer to the Troubleshooting section of this guide fi rst. If you can’t resolve the problem, please call WattMaster Technical Support at our toll free number— 1-866-918-1100.

Page 5: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

IP MODULE INSTALLATION

5

CommLink IV IP Module Installation

Figure 1: Installing the IP Module into the CommLink IV

Installing the OE415-02 IP Module into the CommLink IV

CommLink IV With OE415-02 IP Module Installed

LANTRONIXW

iPort

NR

00-20-4A-89-6B-EE

WP5001000-01

Rev.A

11

Pat. 4972,470

0

6W21

Made inTaiw

an

IP Module Installation Instructions:First Remove The Enclosure Screws That HoldThe Top And Bottom Of The CommLinkEnclosure Together. Remove The Top Half OfThe Enclosure To Access The Circuit Board AndIP Module Socket.

Insert The IP Module’s Guide Pins Into TheRound Pin Holes On The CommLink CircuitBoard As Shown. When The Pins Are ProperlyAligned, Press Down On The IP Module FirmlyTo Seat It Into Its Socket.

While The Top Of The Enclosure Is Removed,Make Sure That The SW1 DIP Switch Is SetCorrectly. See Figure 3.

After Making Sure The IP Module Is FirmlySeated, Replace The CommLink Cover AndSecure The Enclosure Halves Back TogetherWith The Enclosure Screws That WerePreviously Removed.

Follow The Instructions In This Guide ForInstalling The IP Module Software AndConfiguring The IP Module For Your ControlSystem.

IP Module (Part Of OE415-02IP Module Kit). Used WhenTCP/IP LAN Or InternetCommunications With TheControl System Is Desired.

LocationPin - Typ.

Round Pin HoleIP ModuleSocket

IP ModuleSeated InSocket

ALTERA

EPM3032

WattMaster Controls Inc.

COMMLINK IP

YS102074

REV6 MADE IN USA

LANTRONIX WiPort NR

00-20-4A-89-6B-EEWP5001000-01 Rev.A11

Pat. 4972,470 06W21

Made in Taiwan

ALTERA

EPM3032

WattMaster Controls Inc.

COMMLINK IP

YS102074

REV6 MADE IN USA

Page 6: IP Module Technical Guide - az2controls.com

IP MODULE INSTALLATION

IP Module Technical Guide6

CommLink 5 IP Module Installation

Installing the OE415-02 IP Module into the CommLink 5

CommLink 5 with OE415-02 IP Module Installed

LANTRONIXW

iPort

NR

00-20-4A-89-6B-EE

WP5001000-01

Rev.A

11

Pat. 4972,470

0

6W21

Made inTaiw

an

IP Module Installation Instructions:First Remove The Enclosure Screws That HoldThe Top And Bottom Of The CommLinkEnclosure Together. Remove The Top Half OfThe Enclosure To Access The Circuit Board AndIP Module Socket.

Insert The IP Module’s Guide Pins Into TheRound Pin Holes On The CommLink CircuitBoard As Shown. When The Pins Are ProperlyAligned, Press Down On The IP Module FirmlyTo Seat It Into Its Socket.

After Making Sure The IP Module Is FirmlySeated, Replace The CommLink Cover AndSecure The Enclosure Halves Back TogetherWith The Enclosure Screws That WerePreviously Removed.

Follow The Instructions In This Guide ForInstalling The IP Module Software AndConfiguring The IP Module For Your ControlSystem.

IP Module (Part Of OE415-02IP Module Kit). Used WhenTCP/IP LAN Or InternetCommunications With TheControl System Is Desired.

LocationPin - Typ.

Round Pin Hole IP ModuleSocket

LANTRONIX WiPort NR

00-20-4A-89-6B-EEWP5001000-01 Rev.A11

Pat. 4972,470 06W21

Made in Taiwan

IP ModuleSeated InSocket

PIC32

24V

AC

GN

D

T SH

R

PIC32

24V

AC

GN

D

T SH

R

PIC32

24V

AC

GN

D

T SH

R

PIC32

24V

AC

GN

D

T SH

R

Figure 2: Installing the IP Module into the CommLink 5

Page 7: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

COMMUNICATION SETTINGS

7

CommLink IV Communications Setting

ALTERA

EPM3032

WattMaster Controls Inc.

COMMLINK IV

YS102074

REV6 MADE IN USA

The SW1 DIP Switch Located On The Circuit BoardInside The CommLink IV Housing Must Be SetCorrectly For Your Specific Application In Order ToFunction Properly.

To Check And/Or Set The SW1 Dip Switch, FirstRemove The (2) Enclosure Screws That Hold TheTop And Bottom Of The CommLink IV EnclosureTogether. Remove The Top Half Of The Enclosure ToAccess The Circuit Board And Dip Switches.

The DIP Switch Setting Be Set To“Multiple”

When There Is A MiniLink Wired To Your System.

The CommLink IV Is Factory SetFor Multiple Loop Applications.

SW1 MustIn The Following Situation:

The SW1 DIP Switch Setting Must Be Set To “Single”In The Following Situation:

When There IS NO MiniLink Wired To YourSystem.

Replace The CommLink IV Cover And Secure TheEnclosure Halves Back Together With The (2)Enclosure Screws That Were Previously Removed.

LANTRONIX WiPort NR

00-20-4A-89-6B-EEWP5001000-01 Rev.A11

Pat. 4972,470 06W21

Made in Taiwan

DIP Switch 1 & 2 Off =Multiple Loop Communications

DIP Switch 1 On & 2 Off =Single Loop Communications

Setting the CommLink IV Communications Setting

CommLink IV Communications Setting

Figure 3: CommLink IV Communication Settings

Page 8: IP Module Technical Guide - az2controls.com

COMMUNICATION SETTINGS

IP Module Technical Guide8

CommLink 5 Communications Setting

Setting the CommLink 5 SettingCommunications

CommLink 5 Communications Setting

The Loop Switch Located On The Back Of TheCommLink 5 Housing Must Be Set Correctly ForYour Specific Application In Order For TheCommLink 5 To Function Properly.

The Switch Setting Should Be Set To“Multiple” In The Following Situation:

You Have A Single CommLink WithMiniLink(s) or MiniLink PD(s) Installed OnYour System.

The CommLink5 Is Factory Set For Multiple Loop Applications.

Loop

The Loop Switch Setting Should Be Set To“Single” In The Following Situation:

You Have A Single CommLink Without AnyMiniLinks Or MiniLink PDs Installed On YourSystem.

MU

LT

IPL

E

HIG

H

SIN

GL

E

LO

W

BAUDLOOP

R(+

)

24

VGN

D

SH

LD

T(-

)

SERIAL #

MU

LT

IPL

E

SIN

GL

E

LOOP

Switch Set To MultipleLoop Communications

MU

LT

IPL

E

SIN

GL

E

LOOP

Switch Set To SingleLoop Communications

Back of CommLink 5

Figure 4: Setting Loop Communications

Page 9: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

COMMUNICATION SETTINGS

9

CommLink 5 Baud Rate Setting

Setting the CommLink 5 Baud Rate

CommLink 5 Baud Rate Setting

The Baud Rate Switch Located On The Back OfThe CommLink 5 Housing Must Be Set CorrectlyFor Your Specific Application In Order For TheCommLink 5 To Function At Maximum Efficiency.

The Should Be Set To “High” In TheFollowing Situations:

You Are Using Only 2 Controllers, OnlyGPC-XP Controllers, or Only VCB-XControllers On Your System.

The CommLink 5 Is Factory Set For Low BaudRate Applications.

Baud Rate

The Baud Rate Should Be Set To “Low” In TheFollowing Situations:

You Are Using Orion Controllers Or AreUsing Orion Controllers In CombinationWith VCB-X or GPC-XP Controllers. ForExample, VCB-X or GPC-XP ControllersWith VCM-X or VCM Controllers.

AZ

MU

LT

IPL

E

HIG

H

SIN

GL

E

LO

W

BAUDLOOP

R(+

)

24

VGN

D

SH

LD

T(-

)

SERIAL #

Switch Set To High BaudRate (115,200)

Back of CommLink 5H

IGH

LO

W

BAUD

Switch Set To Low BaudRate (Anything Less Than115,200)

HIG

H

LO

W

BAUD

Figure 5: Setting the Baud Rate

Page 10: IP Module Technical Guide - az2controls.com

CONNECTIONS & WIRING

IP Module Technical Guide10

CommLink IV with IP Module Connections and Wiring

Figure 6: CommLink IV with IP Module Connection & Wiring

24 VAC Power

If Desired A 24 VAC Transformer(Not Included) Rated At 12 VAMinimum May Be Used InsteadOf The Supplied Power Pack.Use 18 Gauge Minimum2 Conductor Wire Between TheTransformer & CommLink IVTerminals.

120 to 24 VAC Power Pack(Included With CommLink IV)Connect To 120/1/60 DuplexReceptacle (By Others).

CommLink IV with IP Module

CommLink IV with IP Module Connection & Wiring

NOTES:1.) Use 18 Gauge Minimum 2 Conductor Twisted Pair With Shield Cable Belden #82760(Not Included) Or Equivalent To Connect The CommLink IV To A MiniLink Or MiniLink PDOn The Network Loop Or To Controllers On A Local Loop.

2.) The CommLink IV Cannot Communicate With The Control System Through ItsEthernet Port And USB Port At The Same Time.

3.) All Wiring Must Conform To Applicable Federal, State & Local Electrical Wiring Codes.

18 Gauge 2 ConductorWith Shield (Not Included)See Note 1.

Connect To AMiniLink PD, MiniLinkOr Other Controller AsRequired By YourSpecific SystemWiring Instructions.See Note 1.

MODEMRS-232

Serial #COMPUTER

USB

10/100ETHERNET

DIAG

24V

T G R GN

D

485 LOOP POWER

ResetDefaultValues

ACT LNKUSB

Co

nfi

g

No

rma

l

When Connecting Directly To YourComputer, Use The 10

CrossoverPrefabricated Ft.

Long CAT5 Ethernet Cable(Included).

Connect Directly To Your Computer(Crossover CAT 5) Or Connect To AnAvailable 10/100 BaseT Port On YourLAN (Standard CAT 5).

WARNING! Do Not Have Your Ethernet ConnectionAnd USB Connection Connected At The Same Time.This Could Cause Unreliable Communications.

Supplied With CommLinkBut Not Required For IPModule Installation. SeeNote 2.

Page 11: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

CONNECTIONS & WIRING

11

CommLink 5 with IP Module Connections and Wiring

Figure 7: CommLink 5 Connection & Wiring

24 VAC Power

If Desired A 24 VAC TransformerRated At 12 VA Minimum May Be

Used Instead Of The Supplied Power Pack.Use 18 Gauge Minimum 2 Conductor WireBetween The Transformer & CommLink 5Terminals.

(NotIncluded)

120 to 24 VAC Power Pack(Included) Connect To 120/1/60Duplex Receptacle (By Others).

USB Cable (Included).Connect This Cable ToYour Computer USB PortFor Direct Connection ToThe CommLink 5. AlsoUsed For AdvancedConfiguration of TheCommLink 5.

CommLink 5with IP Module

CommLink 5 with IP Module Connections & Wiring

NOTES:1) Use 18 Gauge Minimum 2 Conductor Twisted Pair With Shield Cable Belden #82760 Or Equivalent (Not Included) To ConnectThe CommLink 5 To A MiniLink Or MiniLink PD.

2) For Direct Connection Via USB, Your Computer Must Have An Unused USB Port Available. Drivers For Your USB Port AreProvided On A CD Supplied With The CommLink 5. Please Follow The Directions In The CommLink 5 USB Driver InstallationSection (Included) To Install And Configure The USB Drivers.

3) The CommLink 5 Cannot Communicate With The Control System Through Its Ethernet Port And USB Port At The Same Time.

4) All Wiring Must Conform To Applicable Federal, State & Local Electrical Wiring Codes.

18 Gauge 2 ConductorWith Shield (Not Included)See Note 1.

Connect To AMiniLink PD, MiniLinkOr Other Controller AsRequired By YourSpecific SystemWiring Instructions.See Note 1.

Serial #COMPUTER

USB

10/100ETHERNET

DIAG

485 LOOP POWERACT LNK

When UsingA MiniLink,Switch ShouldBe Set ToMultiple.

HIG

H

LO

W

BAUD

R(+

)

24

VGN

D

SH

LD

T(-

)

MU

LT

IPL

E

SIN

GL

E

LOOP

WARNING! Do Not Have Your EthernetConnection And USB ConnectionConnected At The Same Time. ThisCould Cause Unreliable Communications.

Optional - Prefabricated Ft. Long CAT5Ethernet Cable (Included With Optional OE415-02 IP Module Kit).

If A LongerEthernet Cable Is Required, You Will Need ToObtain (From Others) And Install An EthernetCable Of The Required Length For YourInstallation.

10

Connect To A 10/100 Base-TEthernet Router On Your LAN.

WARNING! If You Are Replacing An EarlierVersion Of The CommLink With A CommLink 5,Be Aware That The Polarity Of The TerminalBlock Is Reversed On The CommLink 5 FromAll Previous Models. You Must Always ConfirmThat The Polarity Is Correct When Wiring 24 VACPower To The CommLink Power Terminal BlockOr Serious Damage To The Product Will Result.

NOTE: Please Note, The R(+) And T(-)Terminals On The Communications TerminalBlock Are Reversed From All PreviousVersions Of The CommLink.

Page 12: IP Module Technical Guide - az2controls.com

CONNECTIONS & WIRING

IP Module Technical Guide12

CommLink with IP Module Hardware Connection

CommLink with IP Module Hardware Connection

You have two options for connecting the CommLink to your PC via Ethernet:

1.) You can connect the CommLink directly to your PC by using a crossover CAT 5 Ethernet cable (provided) as shown. See Figure 8 for details.

2.) You can connect both your PC and the CommLink to an Ethernet Hub with standard CAT5 cables (by others). See Figure 9 for details.

If using a hub or switch, connect a standard CAT 5 cable from the CommLink to the hub or switch. You will also need to connect your computer to the LAN via standard CAT 5 (by others).

If connecting directly to the CommLink without a hub or switch, use a crossover CAT 5 Ethernet cable. The LNK-LAN LED will light up once power is applied, indicating connection to the LAN.

Power up the CommLink by plugging in the power cable. The CommLink may take up to three minutes to power up completely. Once the CommLink is powered up, you should notice that the red “LOOP” LED light on the CommLink remains lit continuously and fl ickers during communication. See Figures 18 & 19, pages 17 & 18 for the LED location. Figure 8: Connecting with Crossover Ethernet

Cable (CommLink IV shown)

Figure 9: Connecting with Ethernet Cable and Hub(CommLink IV shown)

1 2 3 4

Page 13: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

CONFIGURATION

13

CommLink Confi guration

Computer IP Address Set-up forWindows® XP, Vista, 7, or 8

In order for the CommLink to communicate properly, you must set the IP address of the CommLink and computer to be within the same netmask. The following instructions explain how to change your computer’s IP address.

1.) Click <start>; then click <Control Panel>.

2.) Double-click <Network Connections> (XP), <Net-work & Sharing Center> (Vista), or <Network & Inter-net> (7), The Network Connections Window or Network & Sharing Center Window will appear (XP or Vista). Win-dows 7 & 8 users, click <Network and Sharing Center> for the Network & Sharing Center Window.

NOTE: If any wireless connections are listed, disable them by right-clicking the connection and selecting <Disable>.

3.) In the Network Connections Window, select theLocal Area Connections entry. (In Vista, fi nd the left panel and click on Manage Network Connections.) The Local Area Connection Status Window will appear.

Figure 10: Network Connections Window

4.) Click the <Properties> button. The Local Area Con-nection Properties Window will appear.

5). In the Connection Items List Box, be sure the InternetProtocol (TCP/IP) is checked (Figure 12). (In Vista, this will be TCP/IP v.4.) Click Internet Protocol (TCP/IP v.4) to highlight it and then click <Properties>. The Internet Protocol Properties Window will appear.

6). Type in the following information: a.) Make the IP address 192.168.1.5 b.) Make the Subnet mask 255.255.255.0 c.) Blank out the Default gateway setting (leave the setting blank as shown in Figure 13). d.) Blank out the Preferred DNS server setting and the Alternate DNS server setting (see Figure 13).

7.) Select <OK> until all of the above windows are closed. You may have to reboot the computer before the new values are valid.Figure 11: Local Area Connection Status Window

Figure 12: Local Area Connection Properties Window

Figure 13: Internet Protocol Properties Window

Page 14: IP Module Technical Guide - az2controls.com

CONFIGURATION

IP Module Technical Guide14

CommLink Confi guration

Changing the IP Address of the CommLink

Follow the instructions below to set your IP Module’s IP address. Be sure you have confi gured your PC’s IP address as described on page 13.

1.) Run the Prism 2 program, open the Job Sites Window, and type the default IP address 192.168.1.25 in the Node IP Address fi eld. See the Prism 2 Technical Guide if needed for further instructions. To access the IP Module web page, click on the <Communications> tab and then click <CommLink IP Web Settings> (see below).

2.) The CommLink IP Module Window, shown below, will appear if a connection is established.

3.) The Windows Security Window, shown in Figure 16, might pop up before you can have access to the CommLink IP Module Window, shown above. Click < OK> or < Cancel> to bypass the Windows Security Window.

Figure 15: CommLink’s IP Module Home Page

Figure 17: CommLink’s IP Module Network Confi guration Settings

4.) Click <Network Confi guration> found in the menu bar on the left side of the web page.

Figure 14: CommLink IP Web Settings

Figure 16: Windows Security Window

WARNING: If you do enter a user name and password in this window and forget one or both of the items, you will be permanently locked out of the IP Module confi guration settings. WattMaster cannot reset those credentials back to the default, and as a result, you will need to purchase a new IP Module. Therefore, we highly recommend that you do not enter a username and password in this window.

Page 15: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

CONFIGURATION

15

Figure 18: CommLink Baud Rate Setting

CommLink Confi guration

5.) Under IP confi guration, select the radio buttonin front of the option <Use the following IPconfi guration> and type in the IP address, Subnet Mask, and Default Gateway as provided by the jobsite IT staff.

NOTE: Be sure all other settings are set to default as shown in Figure 17, page 14.

6.) Click <OK> at the bottom of the Network Settings Screen once the changes have been made.

7.) Click <CommLink Confi guration> found in the menu bar on the left side of the web page.

9.) Click <OK> at the bottom of the screen above once the changes have been made.

10.) After you are done modifying the IP settings, click<Apply Settings> in the menu bar to the left.

11). The following message will appear on the screen and the LNK-LAN LED will blink once:

12.) When the LNK-LAN LED fl ashes, it indicates that the new settings have been saved. To verify that the changes were successful, fi rst connect the IP Module to the building’s network using a standard Ethernet cable. Then make sure your PC has a connection to the Local Area Network and reopen the IP Module Setup Webpage by typing in the newly assigned IP Address.

13.) Be sure to set the IP address in Prism 2 to the new IP address set up for the CommLink.

Page 16: IP Module Technical Guide - az2controls.com

TROUBLESHOOTING

IP Module Technical Guide16

CommLink 5

Firewall //Proxy Router

Ethernet Cable To OtherNodes On Building LAN Or WAN

Ethernet Cable

Optional DirectComputer ConnectionTo CommLink 5 Via Crossover(Supplied with IP Module)

Personal Computer

Connecting the Network

Figure 19: Example Network Diagram of a Firewall or Proxy Confi guration

Proxy and Firewall Compatibility

Proxy and Firewall confi gurations may become necessary when the CommLink is connected to a LAN/WAN that is protected by a commercially available Firewall, Proxy, or NAT enabled router. Examples of these would include Cisco, NetGear, LinkSys, or WatchGuard Technologies. Also, some ISPs provide IP Address ranges that are already fi re-walled at the NOC or ISP Head-End. Make sure that your IT Department or ISP can create a mapped TCP port 39288 on your fi rewall/proxy to TCP port 39288 on the assigned IP Address of the CommLink.

Only with proper configuration of the Firewall/Proxy are connections to the CommLink from outside of the local area network going to be possible. Check that the Firewall/Proxy port is not set to time out or reset after a specifi ed amount of time when there is no traffi c from the remote PC.

Page 17: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

TROUBLESHOOTING

17

CommLink IV LED Descriptions

Figure 20: CommLink IV LED Display

STATUS

RX

-US

B

TX

-US

B

LO

OP

TX

-CP

U

RX

-CP

U

AC

T-L

AN

LN

K-L

AN

C O N T R O L S

CommLink IV

www.wattmaster.com

CommLink IV LED Descriptions

LOOP - Indicates communication activity on local controller network. This LED fl ickers off when data is exchanged with controller network.

TX-USB - Indicates transmitted data status of USBconnection. This LED only fl ashes if the CommLink IV is directly connected to a computer via a USB port. It will not fl ash when using the IP Module for LAN or WANconnections.

RX-USB - Indicates received data status of USB connection.This LED only fl ashes if the CommLink IV is directlyconnected to a computer via a USB port. It will not fl ash when using the IP Module for LAN or WAN connections.

TX-CPU - Indicates transmitted data status. This LED fl ashes when data is sent to Prism 2 from the CommLink IV using USB or Ethernet.

RX-CPU - Indicates received data status. This LED fl ashes when data is sent from Prism 2 to the CommLink IV using USB or Ethernet.

ACT-LAN - Indicates activity on the local area network.This LED fl ashes on when LAN is transmitting andreceiving data and only fl ashes if the IP Module isinstalled and operating.

LNK-LAN - Indicates local area network is connected. This LED is on when connected to LAN and only fl ashes if the IP Module is installed and operating.

Page 18: IP Module Technical Guide - az2controls.com

TROUBLESHOOTING

IP Module Technical Guide18

CommLink 5 LED Descriptions

Figure 21: CommLink 5 LED Display

CommLink 5 LED Descriptions

USB LEDs

LOOP - Indicates communication activity on local controller network. This LED fl ickers when data is exchanged with the controller network.

TX-USB - Indicates transmitted data status of USB connection. This LED only fl ashes when your CommLink 5 is connected to a computer and data is sent to Prism 2 from the CommLink 5 via USB.

RX-USB - Indicates received data status of USB connection.This LED only fl ashes when your CommLink 5 is connected to a computer and data is sent from Prism 2 to the CommLink 5 via USB.

COMP- Indicates connection to your computer. This LED will turn on solid once you plug the USB cable into your computer as long as the connection is not lost.

NETWORK LEDs

ACT-LAN - Indicates activity on the local area network. This LED fl ashes on when LAN is transmitting and receiving data and is only operational with an Ethernet connection.

LNK-LAN - Indicates local area network is connected. This LED is on when connected to LAN and is only operational with an Ethernet connection.

WLAN - Indicates wireless connection to the local area network. This LED fl ashes on when LAN is transmitting and receiving data and is only operational with an Ethernet connection.

Page 19: IP Module Technical Guide - az2controls.com

IP Module Technical Guide

TROUBLESHOOTING

19

Troubleshooting

Troubleshooting Procedures

Ethernet Connection When the device is connected to a hub, verify that the LINK LED is lit on the CommLink device and the ACT LED occasionally blinks. The ACT LED indicates network activity and may be refl ecting other network traffi c.

Ethernet Connection, Routing Verify the route is available to the CommLink and fi rewalls or proxies are confi gured to pass TCP network traffi c on port 39288 if necessary. This can be verifi ed by your Network Administrator.

IP Address Verify that the assigned IP Address is valid for the local network and that it is not in use by any other device. Try to PING the CommLink’s IP address to confi rm the address is correct and responding.

NOTE: Make sure that the CommLink is connected as shown in Figures 6 or 7 and all installation pro-cedures have been completed prior to using the “ping” command.

To do this, open a DOS session by opening a command prompt:

1. To open a command prompt, click <Start>, pointto <All Programs>, point to <Accessories>,and then click <Command Prompt>.

2. PING to the IP Address by typing: ping IP address

Example: ping 192.168.1.25

3. Press <Enter> on the keyboard.

4. If no reply is received, fi rst check your PC’s IPaddress and Ethernet connections. If problemspersist, consult your network administrator.

Prism 2 Software Verify that the IP address is correctly entered in the connection profi le for the CommLink. Also verify that the port is left blank in the profi le. This port area specifi es Comm port settings, not an IP address port.

TCP Port Address The TCP port address 39288 is hard coded into the EPROM of the CommLink and in Prism 2 software. It cannot be changed by the end user. The TCP port address needs to be set in your Prism 2 connection.

NOTE: WattMaster Controls Technical Support cannot troubleshoot internal PC and/or Windows®-based operating system problems.

NOTE: WattMaster Controls Technical Support cannot troubleshoot fi rewalls, routers, and/or problems on a customer’s internal or external network. An IT professional may need to be consulted.

Page 20: IP Module Technical Guide - az2controls.com

Form: WM-IPM-TGD-01P Printed in the USA February 2017 All rights reserved. Copyright 2017 WattMaster Controls, Inc. 8500 NW River Park Dr. Parkville, MO 64152 Phone (816) 505-1100 www.wattmaster.com Fax (816) 505-1101