interior renovation project ac transit general office … · laminate cabinetry; and associated...

52
INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE BUILDING 1600 FRANKLIN STREET OAKLAND CONSTRUCTION BID SET SPECIFICATIONS 1-31-2005

Upload: others

Post on 17-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

INTERIOR RENOVATION PROJECT

AC TRANSIT GENERAL OFFICE BUILDING 1600 FRANKLIN STREET

OAKLAND

CONSTRUCTION BID SET

SPECIFICATIONS

1-31-2005

Page 2: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

AC TRANSIT GENERAL OFFICE BUILDING - INTERIOR RENOVATION

Section

No. Section Title

C&B AC Transit GO Bldg 00010 - 1

1/31/06 Construction Bid Set

BIDDING REQUIREMENTS

BY AC TRANSIT

DIVISION 1 - GENERAL REQUIREMENTS

01100 Summary

DIVISION 2 – SITEWORK THROUGH DIVISION 5 - METALS

Not Used

DIVISION 6 - WOOD AND PLASTICS

06400 Architectural Woodwork

DIVISION 7 – THERMAL AND MOISTURE PROTECTIOIN

07812 Applied Fireproofing Repair

DIVISION 8 – DOORS AND WINDOWS

Not Used

DIVISION 9 - FINISHES

09305 Tile Restoration and Cleaning

09510 Acoustical Ceilings

09650 Resilient Flooring and Base

09680 Carpeting

09720 Wall Coverings 09910 Paints

DIVISION 10 - SPECIALTIES

10440 Interior Signage

DIVISION 11 - EQUIPMENT

Not Used

DIVISION 12 - FURNISHINGS

12125 Picture Framing

12492 Vertical Louver Blinds

DIVISION 13 - SPECIAL CONSTRUCTION THROUGH DIVISION 16 - ELECTRICAL

Not Used

END OF TABLE OF CONTENTS

Page 3: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 01100 - 1

1/31/06 Construction Bid Set Summary

SECTION 01100

SUMMARY

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Contract description.

B. Definitions.

C. Preparatory work by AC Transit and Contractor.

D. Contractor's use of site and premises.

E. Work sequence and constraints.

1.2 CONTRACT DESCRIPTION

A. Work of the Project includes refurbishing selected finishes and related work at AC

Transit’s General Offices at 1600 Franklin, Oakland, California. Work includes

replacement of acoustical ceiling panels; providing new vinyl wall covering, carpet

tiles, sheet carpeting, resilient flooring and base, vertical blinds, and corner

guards; painting; refurbishing of upholstered and wood furnishing, repair of plastic

laminate cabinetry; and associated repair of surfaces and removal and disposal

of existing carpeting and other debris.

B. Refer to the Contract Drawings and Specifications for detailed requirements.

1.3 DEFINITIONS

A. District: In Divisions 1 through 16, the term “District” shall be understood to mean

AC Transit (District’s) Project Manager, except where it is used in the context of

District property, District policy, and similar contexts where it shall be understood

to mean AC Transit itself as the facility owner. In this Section, AC Transit shall be

used to distinguish between the District Project Manager and the District as

owner.

1.4 PREPARATORY WORK BY AC TRANSIT AND CONTRACTOR

A. AC Transit will prepare spaces where work is to be performed to the following

extent: Remove notices, artwork, and miscellaneous items from walls. Remove

or otherwise protect computers and other small office machines. Remove items

from desk and cabinet tops. Following work, AC Transit will replace computers

and other small office machines. This work will be performed in coordination with

the Contractor’s schedule. The Contractor shall make efforts to minimize

disruption of AC Transit operations.

Page 4: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 01100 - 2

1/31/06 Construction Bid Set Summary

B. The Contractor shall move and subsequently replace furniture and equipment as

necessary.

C. In order to replace carpeting, Contractor shall lift office systems furnishings

(cubicles) in a manner ensuring that these furnishings are not damaged.

1.5 CONTRACTOR'S USE OF SITE AND PREMISES

A. Limit use of site and premises to allow:

1. AC Transit’s continuing operations and occupancy of facility.

2. AC Transit’s operations including __ hours a day, 7 days a week

operations in the Telephone Information Center and adjacent offices.

B. The Contractor shall plan the Work carefully to work around unavoidable

obstacles in the execution of the Work. Coordinate with District Project Manager

and manager of the facility. Cooperate with building management and occupants

to minimize conflict, and to facilitate AC Transit’s operations.

C. The Contractor is responsible for safety and security precautions during the

project to minimize risk of injury and theft.

D. All required means of egress shall be maintained and unobstructed during all

phases of construction.

E. Work shall be completed during evenings, nights, and on weekends except as

otherwise required herein. Weekends shall be considered to start at 6 pm Friday

and end 6 am on Monday. Weekday evening / night work periods shall

commence at 6 pm and end at 6 am the following morning.

F. Obtain the District’s authorization of work during regular working hours Monday

through Friday between 6 a.m. to 6 p.m.

G. The Contractor shall not allow debris or waste materials to accumulate; regular

periodic removals shall be made to keep premises and building in orderly

appearance during the performance of work.

H. The Contractor, after completion of the work and prior to final inspection and

acceptance by the District, shall thoroughly clean all work from dirt, stains, soiling,

or defacement of any kind.

I. Reasonable access to restrooms, power, and water will be provided on–site by

AC Transit. The Contractor is responsible for security and protection from the

elements.

J. The Contractor shall provide its own parking and materials storage off-site.

K. The District will designate specific areas and times for delivery and unloading of

construction materials and equipment. The Contractor shall not park vehicles or

equipment, or unload materials, at any area other than area designated by the

District. On-site storage of materials will be limited and shall be coordinated with

Page 5: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 01100 - 3

1/31/06 Construction Bid Set Summary

the District. Material storage on-site shall be limited to materials needed for

immediate work and as permitted by the District.

1.6 WORK SEQUENCE AND CONSTRAINTS

A. Coordinate construction schedule and operations with District. Renovate floors in

this order:

1. 10, 2, and 4

2. 3, 5, and 6

3. 7, 8, and 9

4. 1st Floor: Schedule as proposed by the Contractor and accepted by

District Project Manager.

B. Contractor’s schedule shall take into account AC Transit’s preparation work prior

to carpet installation and painting.

1.7 BID ALTERNATE

A. Additive Bid Item (See Bid Schedule): Removing and furnishing and installing

new vertical louver blinds at First Floor Lobby Room 112:

1. Base Bid includes no new blinds at this room.

2. Additive Bid Item: Remove existing blinds and replace with new in

accordance with Section 12492, Vertical Louver Blinds.

PART 2 - PRODUCTS

Not used.

PART 3 - EXECUTION

Not used.

END OF SECTION

Page 6: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 06400 - 1

1/31/06 Construction Bid Set Architectural Woodwork

SECTION 06400

ARCHITECTURAL WOODWORK

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Refinishing, repair, and refurbishing of wood furnishings, millwork, and cabinetry,

where indicated.

1. Including replacing table edge with new edge, refinishing table top, and

finishing new edge of table at 10th floor conference room.

B. Coordination with District regarding electrical devices to be installed by District

personnel at wood furnishings. Including making cut-outs in 10th Floor

Conference Room Table.

1.2 RELATED SECTIONS

A. Section 09910 - Paints: Site finishing and refinishing of architectural woodwork.

1.3 REFERENCES

A. Woodwork Institute (WI) - Manual of Millwork Standards of the Woodwork

Industry.

1.4 SUBMITTALS

A. Shop Drawings: Indicate materials, component profiles and elevations where

woodwork to be repaired as indicated on the Contract Drawings

B. Product Data: Submit data for materials proposed for cleaning and re-furbishing

marred and discolored woodwork surfaces where refinishing is not required.

Indicate proposed materials for finishing and re-finishing architectural woodwork.

Highlight number of coats of each finish product.

C. Samples:

1. Plastic laminate color or colors proposed to match existing.

2. Wood edge for conference room table finished to match existing.

1.5 QUALITY ASSURANCE

A. Qualifications: Company specializing in performing Work of this section with

minimum three years documented experience.

1.6 PREPARATION MEETING

A. Convene minimum one week prior to commencing work of this section.

Demonstrate proposed cleaning and refurbishing methods.

Page 7: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 06400 - 2

1/31/06 Construction Bid Set Architectural Woodwork

1.7 DELIVERY, STORAGE, AND HANDLING

A. Protect units from moisture damage.

1.8 ENVIRONMENTAL REQUIREMENTS

A. During and after installation of Work of this section, coordinate with District to

ensure that temperature and humidity conditions in building spaces are

consistent and normal for the spaces in which wood work is performed.

1.9 FIELD MEASUREMENTS

A. Verify field measurements prior to fabrication.

PART 2 - PRODUCTS

2.1 COMPONENTS

A. Wood for Replacing Edge of 10th Floor Conference Table: Hardwood to match

existing table in appearance.

B. Plastic laminate edging: To match existing.

2.2 ACCESSORIES

A. Fasteners: Size and type to suit application.

2.3 FINISH

A. Stain and polyurethane to match existing.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Countersink anchorage devices at exposed locations. Conceal with solid wood

plugs of species to match surrounding wood; finish flush with surrounding

surfaces. Conceal small fasteners with wood filler to match surrounding wood.

B. Obtain template from District and provide cutouts for electrical devices at 10th

Floor conference room table. Verify locations of cutouts from on-site dimensions.

Note, it shall be understood that the electrical devices themselves provide a

finished appearance at cut-out. Seal cut edges with polyurethane finish.

C. Install edge banding and table edge in accordance with WI standards

Page 8: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 06400 - 3

1/31/06 Construction Bid Set Architectural Woodwork

3.2 CLEANING, REFURBISHING, and FINISHING

A. Clean architectural woodwork including furnishings, casework, and wood trim,

hardware, fittings, and fixtures where indicated.

B. Where wood work is indicated to be refurbished, refurbish finish of woodwork to

eliminated discolorations such as water rings, lessen the appearance of

scratches, and to restore durable finish to match undamaged areas.

C. Where woodwork is indicated to be re-finished or finished, prepare and apply

finish in accordance with manufacturer’s installation instructions. Utilize stain

where required to achieve consistent finish replicating original finish. Apply the

number of coats recommended by manufacturer. Re-finish to restore finish to

like-new appearance. Finish new edge to match table.

END OF SECTION

Page 9: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 07812 - 1

1/31/06 Construction Bid Set Applied Fireproofing Repair

SECTION 07812

APPLIED FIREPROOFING REPAIR

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Repair of fireproofing of exposed structural steel at garage areas of building.

1.2 SYSTEM DESCRIPTION

A. Work consists of repairing damaged areas of fireproof coating at existing

structural steel in garage areas of the building. Contractor shall survey damage

and propose methods and extent of repair for District’s approval.

1.3 SUBMITTALS

A. Product Data: Submit data indicating product characteristics, performance

criteria, and limitations of use.

B. Repair Procedures: Provide written description of proposed repair procedures

including diagrams or photos, as appropriate.

C. Manufacturer's Installation Instructions: Submit information which includes any

special procedures, and conditions requiring special attention.

D. Manufacturer's Field Reports: Indicate compliance with manufacturer's

installation instructions and Contract Documents.

1.4 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing products

specified in this section, with minimum three years documented experience.

B. Applicator Qualifications: Company specializing in performing the Work of this

section, with minimum three years documented experience and approved by

manufacturer.

1.5 MOCK-UP

A. Repair sample area where directed by the District. After the sample area has

cured, Contractor shall meet with District and manufacturer’s representative to

evaluate success of the repair methods and decide on changes in application

method and repair materials, if necessary.

B. Where shrinkage and cracking are evident, adjust mixture and method of

application as necessary. Remove materials and re-construct mock-up.

Page 10: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 07812 - 2

1/31/06 Construction Bid Set Applied Fireproofing Repair

C. Mock-up may remain as part of the Work upon approval of the District.

1.6 PRE-INSTALLATION MEETING

A. Convene minimum one week prior to commencing Work of this section.

1.7 ENVIRONMENTAL REQUIREMENTS

A. Maintain environmental conditions necessary for successful repairs.

B. Provide ventilation in areas to receive fireproofing during application and

24 hours afterward, to dry applied material.

C. Provide temporary enclosure to prevent spray from contaminating air and from

damaging garage contents and surfaces.

PART 2 - PRODUCTS

2.1 APPLIED FIREPROOFING

A. Manufacturers:

1. Grace Construction Products.

2. Isolatek International.

3. Mandoval Vermiculite Products, Inc.

4. Pyroc.

B. Products: As proposed by Contractor and approved by District.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verify surfaces are ready to receive fireproofing.

3.2 PREPARATION

A. Perform tests as recommended by fireproofing manufacturer in situations where

adhesion of fireproofing to substrate is in question.

B. Remove incompatible materials that could affect bond by scraping, brushing,

scrubbing, or sandblasting.

C. Prepare substrates to receive fireproofing.

D. Protect surfaces not scheduled for fireproofing and equipment from damage by

overspray, fall-out, and dusting.

Page 11: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 07812 - 3

1/31/06 Construction Bid Set Applied Fireproofing Repair

3.3 MANUFACTURER'S FIELD SERVICES

A. Provide manufacturer’s field services including observation of site conditions,

conditions of surfaces and installation, quality of workmanship, and initial

instructions when necessary

B. Manufacturer's Field Reports: Document above observations; include

environmental conditions under which fireproofing materials were installed.

Submit observations.

3.4 CLEANING

A. Remove excess material, overspray, droppings, and debris.

B. Remove fireproofing from materials and surfaces not required to be fireproofed.

END OF SECTION

Page 12: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09305 - 1 1/31/06 Construction Bid Set Tile Restoration And Cleaning

SECTION 09305 TILE RESTORATION AND CLEANING PART 1 - GENERAL 1.1 SECTION INCLUDES

A. Cleaning of tile and grout surfaces, replacement of damaged units, and re-sealing.

1.2 SUBMITTALS

A. Provide product data on replacement tile, grout and setting materials; and cleaning and sealing products.

B. Submit samples of proposed tile units and non-slip strips.

C. Submit manufacturers' application instructions.

1.3 QUALITY ASSURANCE

A. Restorer Qualifications: Company with three years documented experience in tile maintenance and installation.

1.4 DELIVERY, STORAGE, AND HANDLING

A. Furnish cleaning, sealing, and setting materials in manufacturer's packaging, including instructions for use.

1.5 ENVIRONMENTAL REQUIREMENTS

A. Comply with product manufacturers’ recommended ventilation, temperature, and humidity requirements.

PART 2 - PRODUCTS 2.1 CLEANING AND SEALING PRODUCT MANUFACTURER

A. Aqua Mix, Inc. Products of another manufacturer may be submitted for approval as equals.

2.2 CLEANING AND SEALING MATERIALS

A. Cleaning Agent for Quarry Tile: Aqua Mix Sealer and Adhesive Remover.

B. Cleaning Agent: Aqua Mix Heavy Duty Tile and Grout Cleaner.

Page 13: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09305 - 2 1/31/06 Construction Bid Set Tile Restoration And Cleaning

C. Low Sheen Sealer for Quarry Tile: Aqua Mix Seal and Finish -- Low Sheen.

Minimum Performance Standards: 1. Coefficient of Friction: ASTM C1028. Static coefficient of friction greater

than 0.60 when applied to unglazed quarry tile. 2. Allows vapor transmission: ASTM E96. 3. Stain Resistant: ANSI Z124.3: Stain resistance rating lower than 40 on

selected surfaces.

D. Sealer for Toilet Room Tile: Aqua Mix Sealer’s Choice 15 Gold. 2.3 GROUT AND SETTING MATERIALS

A. In accordance with Tile Council of America Handbook. As proposed by Contractor and accepted by the District. Grout color and type to match existing.

2.4 TILE

A. Where tile or tile base is indicated to be replaced, tile to match existing as approved by the District.

PART 3 - EXECUTION 3.1 EXAMINATION

A. Verify that surfaces to be cleaned are ready for work of this Section.

B. Beginning installation means acceptance of existing surfaces and conditions. 3.2 PREPARATION

A. Protect elements surrounding the work of this Section from damage or disfiguration.

B. Remove fittings, finish hardware, escutcheons, and accessories.

3.3 CLEANING AND SEAL EXISTING FLOOR, BASE, AND WALL TILE

A. Clean tile with specified cleaning agent and remove existing soil and layers of sealer and wax in accordance with the cleaning agent manufacturer’s recommendation for the condition of tile. Utilize scrub machines on floors, if necessary.

B. Seal tile and grout using specified product in accordance with sealer

manufacturer’s written instructions. Apply three coats on quarry tile.

C. Sealing Quarry Tile: Apply three coats of specified sealer to quarry tile and rub each coat into surface. Apply within the manufacturer’s recommended coverage.

Page 14: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09305 - 3 1/31/06 Construction Bid Set Tile Restoration And Cleaning

Conduct test to determine if surface is completely sealed after 2 hours by applying water droplets to surface. If water is absorbed, thoroughly rub in an additional coat. Wait 2 hours and re-test.

D. Sealing Toilet Room Tile: Apply two coats of specified sealer to toilet room tile.

Polish dry. Apply within the manufacturer’s recommended coverage. Conduct test to determine if surface is completely sealed after 2 hours by applying water droplets to surface. If water is absorbed, thoroughly rub in an additional coat. Wait 2 hours and re-test.

E. Coordinate cleaning and sealing with tile repair and installation of non-slip strips

to ensure that new materials adhere to substrates.

F. Re-seal tile and grout surfaces as soon as possible after completion of cleaning to help ensure that surfaces are not contaminated prior to sealing.

G. Re-clean tile and grout surfaces prior to sealing if soiling has occurred.

3.4 TILE INSTALLATION

A. Remove entire existing tile where chipped or cracked. Where tiles are removed, remove setting material and surrounding grout. Prevent damage to surrounding tile and other surfaces. Prepare substrate as required for setting method.

B. Comply with applicable parts of ANSI A108 Series “Specifications for Installation

of Ceramic Tile” that apply to setting and grout materials.

C. Comply with TCA Handbook for Ceramic Tile Installations for installation method proposed and accepted.

D. Match width, texture, and color of existing grout joint.

E. Clean and seal tile and grout upon completion of repair and restoration. Allow

grout to cure the number of hours required by sealer manufacturer’s written recommendations prior to sealing.

3.5 PROTECTION

A. Protect replacement tile from damage until completely cured and sealed. Protect tile from damage from construction.

B. Protect other surfaces from cleaning, sealing, and tile installation products.

END OF SECTION

Page 15: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09510 - 1 1/31/06 Construction Bid Set Acoustical Ceilings

SECTION 09510 ACOUSTICAL CEILINGS PART 1 - GENERAL 1.1 SECTION INCLUDES

A. Remove and salvage existing acoustical panels from the ceiling of rooms as shown on the Contract Drawings and replace with new acoustical panels. Remove existing and replace with new acoustical panels where indicated.

B. Replace damaged, sagging, non-matching, and discolored acoustical panels with

salvaged acoustical panels in all areas listed on the Finish Schedule.

1.2 RELATED SECTIONS

A. Invitation to Bid, Section 4, Scope of Work, or Section 01100, Summary of Work, “Work Sequence and Constraints”.

1.3 SUBMITTALS

A. Provide product data on acoustic units.

B. Submit two samples, 8 inches by 12 inches in size, illustrating material and finish of each acoustic unit.

C. Submit manufacturer's installation instructions.

1.4 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacture of ceiling suspension system and ceiling panels with ten years minimum experience.

B. Installer Qualifications: Company with three years minimum experience.

1.5 DELIVERY, STORAGE AND HANDLING

A. Store panel cartons open at each end to stabilize moisture content. 1.6 PROJECT CONDITIONS

A. Schedule installation of acoustic units after interior wet work is dry.

B. Ensure through coordination with District that temperature and humidity conditions required by the panel manufacturer as maintained prior to, during, and after installation.

Page 16: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09510 - 2 1/31/06 Construction Bid Set Acoustical Ceilings

1.7 EXTRA STOCK

A. Provide extra new panels equal to 1 percent of total for each type of new panels used. Label cartons with manufacturer and model number and contact information for manufacturer and local supplier.

B. Package undamaged remaining salvaged panels and label for District’s

information.

C. Store extra new and salvaged panels in designated location as directed by the District.

PART 2 - PRODUCTS 2.1 MANUFACTURERS - ACOUSTIC UNITS

A. U. S. Gypsum Company. USG product names are indicated as the design basis.

B. Armstrong World Industries.

C. BPB Celotex Corp.

D. Or equal. 2.2 MATERIALS - ACOUSTIC UNIT

A. Typical Panels: For locations of new ceiling panels, refer to Contract Drawings. Panels at typical floors. 1. Composition: Mineral Fiber, Wet-Formed. 2. Flame Spread: Class A per ASTM E1264. 3. Sag resistant. Treated for mold resistance 4. Surface Color: White. Factory-applied vinyl latex paint. 5. Noise Reduction Coefficient (NRC) Rating: 0.55. 6. Ceiling Attenuation Class (CAC) Rating: 35. 7. Light Reflectance: 0.82. 8. Size: 24 inches by 48 inches. 9. Thickness: 5/8 or 3/4 – inches, match existing. 10. Density: 0.92 pounds per square foot. 11. Edge: Beveled or Angled, Tegular. Similar to edge of existing panels and

to suit existing suspension system. Verify in field. 12. Surface Finish: Fine texture, non-perforated, non-fissured. 13. ASTM E1264 Classification: Type III, Form 1 or 2, Pattern G. 14. Pattern: USG, ClimaPlus.

B. 24 inch by 24 inch Panels: For locations of new ceiling panels, refer to Contract

Drawings. Panels at 10th floor and panels at lobby at 2nd floor. Verify in field. 1. Composition: Mineral Fiber, Wet-Formed. 2. Flame Spread: Class A per ASTM E1264.

Page 17: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09510 - 3 1/31/06 Construction Bid Set Acoustical Ceilings

3. Sag resistant. Treated for mold resistance 4. Surface Color: White. Factory-applied vinyl latex paint. 5. Noise Reduction Coefficient (NRC) Rating: 0.55. 6. Ceiling Attenuation Class (CAC) Rating: 35. 7. Light Reflectance: 0.82. 8. Size: 24 inches by 24 inches. 9. Thickness: 5/8 or 3/4 – inches, match existing. 10. Density: 0.92 pounds per square foot. 11. Edge: Beveled or Angled, Tegular. Similar to edge of existing panels and

to suit existing suspension system. Verify in field. 12. Surface Finish: Fine texture, non-perforated, non-fissured. 13. ASTM E1264 Classification: Type III, Form 1 or 2, Pattern G. 14. Pattern: USG, ClimaPlus.

PART 3 - EXECUTION 3.1 EXAMINATION

A. Verify that existing conditions are ready to receive work.

B. Beginning of installation means acceptance of existing conditions. 3.2 PREPARATION

A. Clean heating and air conditioning grilles and registers in rooms where existing ceiling panels are replaced with new panels and elsewhere as indicated.

B. Clean and paint existing suspended ceiling grid in rooms where existing ceiling

panels are replaced with new panels and elsewhere as indicated.

C. Clean heating and air conditioning grilles and registers in rooms where existing ceiling panels are replaced with new panels and elsewhere as indicated.

3.3 SALVAGING AND REPLACEMENT OF ACOUSTICAL UNITS -- GENERAL

A. Remove existing acoustical panels where designated for salvage. Prevent damage to units. Set aside and protect salvaged units for installation as part of the Work and for District’s extra stock.

B. Protect existing suspension system, lighting, HVAC registers and grilles, and

above ceiling items throughout removal and installation of panels.

C. Install new acoustical units in areas where existing were salvaged.

D. Remove damaged, sagging, non-matching, and discolored acoustical panels in areas where such removal and replacement is indicated and replace with salvaged undamaged panels. Resulting ceiling where panels have been

Page 18: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09510 - 4 1/31/06 Construction Bid Set Acoustical Ceilings

replaced with salvaged tile shall be uniform in color and pattern when work is complete.

E. Review with District the condition of salvaged panels which are not re-installed.

Take those panels which are selected by District for future use (extra stock) to storage location in the building as designated by District. Neatly stack panels. Dispose of panels which District does not select for future use.

3.4 INSTALLATION - ACOUSTICAL UNITS

A. Where existing acoustical panels are designated for removal but not salvage, remove existing panels.

B. Install acoustical units in accordance with manufacturer's instructions.

C. Fit acoustic units in place, free from damaged edges or other defects detrimental

to appearance and function.

D. Lay directional patterned units one way with pattern parallel to shortest room axis. Fit border neatly against abutting surfaces.

E. Install acoustic units level, in uniform plane, and free from twist, warp and dents.

F. Cut panels to fit irregular grid and perimeter edge trim. Field rabbet panel edge.

Double cut and field paint exposed edges of tegular units. 3.5 ADJUSTING, PATCHING, AND CLEANING

A. Replace members of suspension system where damaged in the course of the Work. Replace acoustical panels that are damaged, installed improperly, or shows visible signs of sagging.

B. Clean soiled areas of new ceiling material with mild soap and water in

accordance with pane manufacturer’s instructions. Replace ceiling panels damaged by improper cleaning. Clean areas of existing acoustical panels and suspension system soiled in the process of salvage, installation, and replacement.

END OF SECTION

Page 19: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09650 - 1

1/31/06 Construction Bid Set Resilient Flooring And Base

SECTION 09650

RESILIENT FLOORING AND BASE

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Resilient flooring and base.

1.2 REFERENCES

A. ASTM E 84 - Surface Burning Characteristics of Building Materials.

B. ASTM F1861 - Resilient Wall Base

1.3 SUBMITTALS

A. Provide product data on specified products, describing physical and performance

characteristics, sizes, patterns, and colors available.

B. Submit two samples of each product for each color and pattern selected. Submit

samples of Altro’s AQT CD colors.

C. Submit manufacturer's installation instructions.

D. Operation and Maintenance Data: Include maintenance procedures,

recommended maintenance materials.

E. Submit evidence that installer has completed manufacturer training.

1.4 QUALITY ASSURANCE

A. Installer: Installer shall have attended flooring manufacturer’s installation training.

B. Conform to applicable building code for flame/ fuel/smoke rating requirements in

accordance with ASTM E 84.

1.5 ENVIRONMENTAL REQUIREMENTS

A. Store materials for three days prior to installation in area of installation to achieve

temperature stability.

B. Maintain ambient temperature required by adhesive manufacturer three days

prior to, during, and 24 hours after installation of materials.

Page 20: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09650 - 2

1/31/06 Construction Bid Set Resilient Flooring And Base

C. Ensure through coordination with District that manufacturer’s required

temperature and humidity conditions are maintained prior to, during, and following

installation.

1.6 EXTRA MATERIALS

A. Provide 50 square feet of flooring and 20 lineal feet of base of each material,

color, and pattern utilized.

1.7 DELIVERY, STORAGE AND HANDLING

A. Store base materials in original containers in enclosed space at minimum of

70 degrees F for three days prior to installation.

PART 2 - PRODUCTS

2.1 FLOORING MATERIALS

A. Manufacturers

1. Altro

2. Vortex Composites.

3. Or equal.

B. Resilient Flooring:

1. Quartz vinyl tile: Altro Quartz Tile, as manufactured by Altro North

America. Heavy duty commercial tile consisting of a minimum of 65

percent quartz particles. Meeting ASTM 10066 for chemical resistance.

Meeting slip resistance for level surfaces ASTM D2047. Indentation

resistance: 2100 psi when tested according to ASTM F970 (modified).

2. Colors: AQT CD-0211and AQT CD-0221, to be confirmed, upon review of

color samples. Up to two colors selected from Altro’s AQT CD Series.

2.2 BASE MATERIALS

A. Manufacturers

1. Allstate

2. Burke Flooring Products.

3. Flexco.

4. R.C. Musson Rubber Co.

5. Roppe.

6. Or equal.

B. Base:

1. ASTM F-1861, Type TS, Group 1, Styles A and B.

2. ASTM E-84, Class B rating with smoke density of 150-200.

3. Material: Rubber.

4. Size: 4 inches high, 1/8-inch thick.

5. Premolded external corners .

Page 21: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09650 - 3

1/31/06 Construction Bid Set Resilient Flooring And Base

6. End Stops: Pre-molded.

7. Toe Style: Coved.

8. Colors: Burke Mocha.

2.3 ACCESSORIES

A. Primers and Adhesives: Waterproof; types recommended by flooring

manufacturer.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verify that surfaces are smooth and flat with maximum variation of 1/4-inch in

10 feet, and are ready to receive Work.

B. Verify that concrete floors are dry to a maximum moisture content of 7 percent,

and exhibit negative alkalinity, carbonization, and dusting

C. Examine substrate for substances not compatible with adhesive.

D. Air temperature and surfaces in rooms to receive base shall be between

60 degrees to 90 degrees F unless otherwise recommended by manufacturer.

E. Beginning of installation means acceptance of existing substrate and site

conditions.

3.2 FLOORING PREPARATION

A. Remove sub-floor ridges and bumps. Fill low spots, cracks, joints, holes, and

other defects in flooring substrate accordance with base manufacturer’s

installation instructions.

B. Apply, trowel, and float filler to leave a smooth, flat hard surface.

C. Prohibit traffic from area until filler is cured.

D. Vacuum clean substrate.

E. Apply primer to surfaces as recommended by manufacturer.

3.3 FLOORING INSTALLATION

A. Install per manufacturer’s written instructions.

Page 22: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09650 - 4

1/31/06 Construction Bid Set Resilient Flooring And Base

3.4 BASE PREPARATION

A. Remove existing base. Fill low spots, cracks, joints, holes, and other defects in

accordance with base manufacturer’s installation instructions.

B. Vacuum clean substrate.

C. Apply primer to surfaces as recommended by manufacturer.

3.5 INSTALLATION - BASE MATERIAL

A. Fit joints tight and vertical. Maintain minimum measurement of 18 inches

between joints.

B. Miter internal corners. At external corners, use premolded units. At exposed

ends use premolded units.

C. Install base on solid backing. Bond tight to wall and floor surfaces.

D. Scribe and fit to door frames and other interruptions. Where existing resilient

base occurs at cabinets, remove and replace with new base. Install base on

cabinets where finished base is not present.

3.6 PROTECTION AND CLEANING

A. Repair or replace damaged surfaces that are soiled or scarred in a manner

acceptable to Owner.

B. Remove excess adhesive from floor, base, and wall surfaces without damage.

C. Clean and seal surfaces in accordance with manufacturer's instructions.

END OF SECTION

Page 23: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09680 - 1 1/31/06 Construction Bid Set Carpeting

SECTION 09680 CARPETING

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Carpet tile and sheet carpeting.

B. Carpet accessories.

1.2 SUBMITTALS

A. Product Data: Submit technical data for carpet tile material and accessory indicated.

1. Include information which specifically details physical properties and performance characteristics.

2. Include information which details installation methods for substrates indicated.

3. Include VOC content of each product used.

B. Verification Samples: Submit the following to serve as standards for judging the completed work:

1. For each distinct color and pattern indicated, submit two tiles samples.

2. Submit samples of edge guard.

C. Certification:

1. Submit manufacturer's certification that materials furnished comply with requirements indicated.

D. Qualifications:

1. Submit evidence of installer and office system furnishing mover experience including contact information from five facility owners for which each entity has performed work of similar character and scope within the last 18 months.

E. Procedures: Submit step by step procedures proposed for raising and lowering office systems furnishings (cubicles and attached shelving, bins, work surfaces, cabinets, and similar items). Include procedures to either maintain electrical and data wiring or to disconnect and re-connect. Include brief resume for personnel doing electrical and cabling work. (Upon District request, this personnel shall meet with District personnel during normal working hours to review procedures and precautions.)

Page 24: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09680 - 2 1/31/06 Construction Bid Set Carpeting

F. Maintenance Instructions: Submit manufacturer's instructions for maintaining appearance and condition of installed products. Include information on cleaning materials which could damage carpet tile.

G. Verification of Ordering: Within 5 days of receipt, submit a copy of carpet manufacturer's confirmation of order.

H. Results of Water Vapor Transmission Test performed on concrete slabs. Refer to Article 3.1 Examination.

1.3 QUALITY ASSURANCE

A. Installer's Qualifications: Firm regularly engaged in installation of products of the types and quantities required for this project, with a minimum of 5 years of satisfactory experience.

B. Qualifications of Entity Which Raises and Lowers Office Systems Furnishing (“Mover”): Firm regularly engaged in raising and lowering such furnishings of products of the types and quantities required for this project, with a minimum of 5 years of satisfactory experience.

C. Carpet systems shall meet or exceed the requirements of the Carpet and Rug Institute’s Green Label Indoor Air Quality Test Programs.

1.4 DELIVERY, STORAGE, AND HANDLING

A. Take measures as required to ensure materials are not damaged or deformed. Store products in flat position in properly ventilated, dry space. Use suitable means to prevent materials from lying in direct contact with the ground.

B. Allow carpet tile materials to reach temperature in area of installation or minimum temperature recommended by carpet tile manufacturer before installation.

C. Store materials in a temperature controlled room with a minimum temperature of 60 degrees F and a maximum temperature of 80 degrees F at least 3 days prior to and during installation.

1.5 WARRANTY

A. Submit a written warranty signed by the manufacturer, installer, and the Contractor, guaranteeing to correct failures in carpet tile which occur within 10 years after completion, without reducing or otherwise limiting any other rights to correction which the District may have under the contract documents. Failures are defined to include faulty workmanship or faulty materials. Correction may include repair or replacement.

Page 25: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09680 - 3 1/31/06 Construction Bid Set Carpeting

1.6 MAINTENANCE MATERIALS

A. After carpet tile installation has been completed, coordinate with the District for delivery of the following extra materials to a location designated by the District.

B. Carpet: A minimum of 5 percent for each carpet pattern, color and type installed, precisely matching carpet installed. Such materials shall be suitably protectively packaged and labeled as to contents and location of installation.

PART 2 - PRODUCTS

2.1 GENERAL

A. Interface Products are specified as the basis of design.

B. Single Source Responsibility: Obtain all of each different material from a single manufacturer.

C. Carpet systems shall meet or exceed the requirements of the carpet and Rug Institute’s Green Label Indoor Air Quality Test Program.

D. CPT-1 and CPT-2:

1. Radiant Panel: Class 1 (ASTM E648) 2. Smoke Density: Less than or equal to 450 (ASTM E662) 3. Lightfastness: Greater than or equal to 4.0 @ 60 AFU’s (AATCC 16 -

E) 4. Static: Less than 3 kV (AATCC-134)

2.2 CARPET TILE

A. CPT-1 (Field Tile) Typical Office Tile. 1. Pattern: Woodland Way 2. Modular, 50X50cm GlasBac Tile -1664302500 3. Color System: 100% Solution Dye 4. Soil/Stain Protection – Protekt with Dura Tech 5. Lifetime Antimicrobial – Intersept 6. Yarn Weight: 20oz. 7. Pile thickness: .122 in, 3.3 mm 8. Pile Density: 5,902 9. Color: Willow. Color to be verified. 10. Yarn System: Antron Lumena Solution Dyed nylon

A. CPT-2 (Border Tile to Compliment CPT-3) See Contract Drawings for Locations. 11. Pattern: Panorama 12. Modular, 50X50cm GlasBac Tile -1671402500 13. Color System: 100% Solution Dye 14. Soil/Stain Protection – Protekt with Zonyl 8779 Fluorochemical

Page 26: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09680 - 4 1/31/06 Construction Bid Set Carpeting

15. Lifetime Antimicrobial – Intersept 16. Yarn Weight: 20oz. 17. Pile thickness: .122 in, 3.3 mm 18. Pile Density: 5,902 19. Color: Color to be selected from full range of Panorama colors.. 20. Yarn System: Invista Type 6.6 Nylon

C. CPT-3 (Field Tile) See Contract Drawings for Locations. 1. Pattern: Frequency 2. Modular, 50X50cm GlasBac Tile -1662002500 3. Color System: 67% solution Dye, 33% Space Dye 4. Soil/Stain Protection – Protekt with Dura Tech 5. Yarn Weight: 20oz. 6. Pile thickness: .122 in., 3.1mm 7. Pile Density: 5,902 8. Color: Reflexion 9. Yarn System: 67% Antron Lumena Solution Dyed nylon

2.3 SHEET CARPETING

A. CPT-4: To match carpet tile CPT-2.

2.4 ACCESSORIES

A. Vinyl Edge Guard: BurkeMercer; Edge Guard or Reducer 700 Imperial, for 5/16” high carpet; or approved equal. Match color of resilient wall base at same room.

B. Edge Guard Installation Adhesive: As recommended in writing by edge guard manufacturer.

C. Carpet Tile Installation Adhesive:

1. Carpet Tile, Floor Installation: Manufacturer's recommended water-resistant, release-type adhesive manufactured for use with type of carpet tile and substrate indicated.

PART 3 - EXECUTION

3.1 EXAMINATION

A. General: Verify that substrates are completely dry, free of harmful substances, and in satisfactory condition to receive carpet tile, as applicable. Examine substrates, with Installer present, for compliance with requirements for installation tolerances, moisture content, and other conditions affecting performance. Required conditions for concrete slabs include at least the following or stricter requirements of the carpet manufacturer:

1. Surface pH of 10 or higher when tested with distilled water and pH paper per ASTM D4262.

2. Concrete Surface Profile as defined by ICRI of 5, 6, 7, 8 or 9.

Page 27: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09680 - 5 1/31/06 Construction Bid Set Carpeting

3. Water vapor transmission rate of not more than 3 pounds of moisture per 1000 square feet per 24 hours when tested in accordance with ASTM F 1869 with three tests for the first 1,000 square feet and one test for each additional 1,000 square feet or fraction thereof.

B. Notify the District in writing of unsatisfactory conditions. Do not begin installation until these conditions have been satisfactorily corrected.

C. Start of installation work constitutes acceptance of substrate conditions and full responsibility for the completed work.

3.2 PREPARATION

A. Raise (and subsequently lower) office systems furnishings (cubicles and attached shelving, bins, work surfaces, cabinets, and similar items) using devices and techniques designed to ensure that furnishings are not twisted or otherwise damaged in the process of raising and lowering.

B. Move furniture and other objects sitting on floor or otherwise interfering with carpet installation. Utilize devices and techniques to ensure that furnishings are not twisted or otherwise damaged in the process of raising and lowering.

C. General: Follow carpet manufacturer's recommendations to ensure that each substrate is properly prepared to receive materials.

D. Remove existing carpeting, adhesive, and pad, if applicable.

E. Where carpet tile is scheduled to be installed over existing resilient flooring, repair and level floor as indicated prior to installing carpet tiles.

F. Fill cracks, gaps, and depressions using carpet tile manufacturer's recommended fast-setting and drying materials and methods.

G. Level off high spots and ridges.

H. Determine whether substrates are susceptible to dusting. Apply fast drying sealer where required to prevent formation of dust.

I. Vacuum-clean substrates thoroughly, just prior to beginning installation.

J. Properly prepared, smooth concrete and resilient flooring substrates may be left exposed for a maximum of 24 hours (except as noted), providing that adequate precautions are taken to prevent tripping hazard at exposed edges of carpeting. Re-clean substrate as necessary prior to installation of carpet tiles.

1. Exception: Preparation of substrates and installation of carpet at dispatch room shall be executed within the time restrictions specified in the scheduling and staging provisions of the General Requirements, but in no case shall the prepared substrate be left exposed for more than 24 hours within the approval of the District.

Page 28: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09680 - 6 1/31/06 Construction Bid Set Carpeting

3.3 INSTALLATION - GENERAL

A. Materials and methods shall enable use of carpet without detrimental effects immediately after installation.

C. Perform installation in accordance with manufacturer's instructions, except where more stringent requirements are shown or specified, and except where project conditions require extra precautions or provisions to ensure satisfactory performance of the work.

1. Maximize consistency of carpet appearance, particularly in terms of lay of pile and its direction.

2. Continue carpet into recessed spaces such as closets, and underneath obstacles with open bases.

3. Follow manufacturer's instructions for cutting carpet tiles, using tools designed to cut type of carpet materials being installed.

3.4 INSTALLATION - CARPET TILE

A. Minimum temperature throughout installation period: 60 degrees F. Do not install carpet tiles if temperature falls below minimum.

B. Layout:

1. Horizontal surfaces: Layout carpet tiles on floor surfaces as shown on the Contract Drawings. Carpet tile layout shall be parallel to building column lines depicted in the Contract Drawings.

2. Install carpet tile in quarter-turn pattern so that the linear pattern of the field and border tiles never align between adjacent tiles of any time.

C. Begin installation of carpet tiles at workpoint established by the installer.

D. Laying Carpet Tiles: Lay carpet tiles so that they firmly butt together.

1. Frequently verify that carpet tiles are correctly installed by measuring across ten carpet tiles.

2. If the gain over ten carpet tiles is more or less than 1/4 inch, installation is too loose or too tight.

3. Pull up carpet tiles and rework the area in accordance with carpet tile and adhesive manufacturers' instructions.

E. Cutting Carpet Tiles: Scribe carpet tiles to walls, columns, and other projections.

1. Verify proper fit by temporarily placing each dry cut carpet tile in precise location where it will be installed.

Page 29: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09680 - 7 1/31/06 Construction Bid Set Carpeting

2. Remove carpet tile and apply full spread of adhesive to back of carpet tiles.

3. Install carpet tile in place only after adhesive has set for period recommended by adhesive manufacturer.

F. Full Glue Spread Installation: Apply full spread of carpet tile manufacturer's recommended adhesive on carpet tiles. Do not install until adhesive has properly set for period recommended by adhesive manufacturer.

G. Immediately remove any adhesive from carpet tile surface by method which will not damage carpet tile.

3.5 INSTALLATION – SHEET CARPETING

A. Lay out rolls of carpet full for District approval.

B. Check matching of carpet before cutting and ensure there is no visible variation between dye lots.

C. Cut carpet, where required, in manner to allow proper seam and pattern

match. Ensure cuts are straight and true and unfrayed.

D. Seams: 1. Install in accordance with approved seam layout using a minimum of

seams. Where possible and practical, locate seams in areas of least amount of traffic.

2. Do not use small carpet fill strips. 3. Do not place seams perpendicular to doors or entries. 4. Cross joints necessary due to layout of areas shall be at absolute

minimum and shall be indicated on shop drawings. 5. Cross joins necessary due to length of rolls received shall be placed,

in the cutting, to avoid occurrence at conspicuous locations, near doors or at pivot points, and shall be approved prior to seaming.

6. Join seams in recommended manner so as not to detract from the appearance of the carpet installation and decrease its life expectancy. Ensure seams are straight, not overlapped or peaked and free of gaps.

E. Vacuum clean substrate. Spread adhesive in quantity recommended by

manufacturer after primer application to ensure proper adhesion over full area of installation. Apply only enough adhesive to permit proper adhesion of carpet before initial set.

F. Lay carpet on floors with the run of the pile in same direction of anticipated

traffic. Lay carpet on stairs with run of the pile in opposite direction of anticipated traffic to avoid peeking of backing at nosing.

G. Do not change run of pile in any one room or from one room to next where

continuous through a wall opening.

Page 30: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09680 - 8 1/31/06 Construction Bid Set Carpeting

H. Cut and fit carpet neatly around projections through floor and to walls and other vertical surfaces.

I. Fit carpet snugly to walls or other vertical surfaces where no base is

scheduled, leaving no gaps.

J. Do not place heavy objects such as furniture on carpeted surfaces for minimum of 24 hours or until adhesive is set.

K. Entire carpet installation is to be laid tight and flat to subfloor, well fastened at

edges, and present a uniform pleasing appearance. Ensure monolithic color, pattern, and texture match within any one area.

L. Install edging strips where carpet terminates at other floor coverings. Use

full length pieces only. Butt tight to vertical surfaces. Where splicing cannot be avoided, butt ends tight and flush.

M. Extend carpet as base finish up vertical surfaces to form base. Terminate

top of carpet with special liquid base gripper.

N. Install stair nosings full width of tread, in one continuous piece. Adhere over center surface and fit accurately and securely. Adhere carpet tight to treads and risers. Butt carpet on treads and risers tight to nosings.

O. Adhere carpet tight to treads and risers of stairs.

3.6 CLEANING - EACH DAY'S INSTALLATION

A. Remove carpet tile remnants which are not usable; comply with the District's instructions for final disposition of usable remnants.

B. Use commercial-quality vacuum cleaner to thoroughly clean installed carpet tile; trim loose yarns where required.

C. Eliminate stains; Contractor shall pay for and replace carpet tile from which stains cannot be eliminated using carpet tile manufacturer's recommended products and methods.

D. Do not wet-clean carpet tile.

E. Ensure that carpet tile installed each day is clean and without damage at completion of installation.

END OF SECTION

Page 31: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09720 - 1

1/31/06 Construction Bid Set Wall Coverings

SECTION 09720

WALL COVERINGS

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Surface preparation and prime painting and vinyl faced wall covering, including

application materials and incidental services.

1.2 REFERENCES

A. ASTM D 2016 - Moisture Content of Wood.

B. NFPA 255 - Surface Burning Characteristics of Building Materials.

C. NFPA 286 - Methods for Fire Tests for Evaluating Contribution of Wall and

Ceiling Interior Finish to Room Fire Growth

1.3 SUBMITTALS

A. Provide product data on wall covering and adhesive.

B. Submit two samples of wall covering 12 inches by 12 inches in size illustrating

color, finish, and texture.

C. Submit manufacturer's installation instructions.

D. Submit manufacturer's certificate that products meet or exceed specified

requirements.

1.4 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing commercial

wall fabrics with five years documented experience.

B. Applicator Qualifications: Company specializing in installing wall fabrics with

three years documented experience.

1.5 REGULATORY REQUIREMENTS

A. Conform to applicable building code for flame spread/fuel contribution/smoke

development ratings. NFPA 255 Tunnel Test: Class A rating. NFPA 286 Corner

Burn Test: Meets requirements for Flame Spread, Smoke Developed and

Flashover.

Page 32: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09720 - 2

1/31/06 Construction Bid Set Wall Coverings

1.6 FIELD SAMPLE

A. Apply field sample panel, 96-inch by 96-inch square, illustrating installed covering

and joint seaming technique for each type wallcovering specified, application on

wall designated by the District.

B. Accepted field sample may or may not remain as part of the work, as determined

by the District.

1.7 ENVIRONMENTAL REQUIREMENTS

A. Provide continuous ventilation and heating facilities to maintain substrate surface

and ambient temperatures above 60 degrees F unless required otherwise by

manufacturer's instructions.

B. Do not apply adhesive when substrate surface temperature or ambient

temperature is below 60 degrees F or relative humidity is above 40 percent.

C. Maintain these conditions 24 hours before, during, and after installation of

adhesive wall covering.

D. Provide lighting level of 80 footcandles measured mid-height at substrate

surfaces.

1.8 EXTRA STOCK

A. Provide 25 lineal feet of each color of wall covering.

B. Package and label each roll by destination room number; store where directed.

1.9 DELIVERY, STORAGE, AND HANDLING

A. Inspect roll materials on site to verify acceptance.

B. Protect packaged adhesive from temperature cycling and cold temperatures.

C. Do not store roll goods on end.

PART 2 - PRODUCTS

2.1 MATERIALS

A. Wall Covering: Vinyl coated roll stock, in 54-inch wide rolls. Wall covering shall

be Regiment Pattern, White, as manufactured by Koroseal, to match existing wall

covering. To match existing, verify.

1. Gage: 30 mils.

2. Total Weight: 16.0 ounces per square yard.

3. Tensile Strength (Minimum): 50 x 50 Lb.

Page 33: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09720 - 3

1/31/06 Construction Bid Set Wall Coverings

4. Tear Strength (Minimum): 25 x 25.

5. Compliant with Federal Specifications CCC-2C408A, Type II. .

2.2 ACCESSORIES

A. Adhesive: Type recommended by wall covering manufacturer to suit application

to substrate.

B. Substrate Filler: As recommended by adhesive and wall covering manufacturers;

compatible with substrate.

C. Substrate Primer and Sealer: Type as recommended by wall covering

manufacturer.

D. Termination Trim: Extruded plastic of clear color.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Remove existing wall covering, clean, and prepare substrate surfaces as

required by wall covering manufacturer’s written instructions.

B. Verify that substrate surfaces are primed and ready to receive work, and conform

to requirements of the wall covering manufacturer.

C. Measure moisture content of surfaces using an electronic moisture meter. Do

not apply coverings unless moisture content of surfaces are below the following

maximums

1. Plaster and Gypsum Wall Board: 12 percent.

2. Masonry, Concrete, and Concrete Unit Masonry: 12 percent.

3. Wood Surfaces: 15 percent, measured in accordance with ASTM D

2016.

D. Notify District if flatness of existing wall surface varies more than 1/8-inch in 10

feet or more than 1/16-inch per foot.

E. Beginning of installation means acceptance of substrate.

3.2 PREPARATION

A. Examine substrate surfaces for conditions that would affect proper application of

wall covering. Surfaces shall be smooth, clean and dry. Correct defects.

B. Fill cracks and smooth irregularities with filler; sand smooth.

C. Wash impervious surfaces with trisodium phosphate, rinse and neutralize; wipe

dry.

Page 34: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09720 - 4

1/31/06 Construction Bid Set Wall Coverings

D. Sand glossy surfaces. Shellac marks which may bleed.

E. Remove electrical, telephone, and other wall plates and covers.

F. Vacuum clean surfaces free of loose particles.

G. Apply the number of coats of primer sealer to substrate surfaces as

recommended by wall covering manufacturer. Allow to dry. Lightly sand smooth.

Vacuum clean.

3.3 INSTALLATION

A. Apply adhesive and wall covering in accordance with manufacturer's instructions.

B. Apply adhesive immediately prior to application of wall covering. Apply to

substrate or fabric depending on manufacturer’s written instructions.

C. Use wall covering in roll number sequence or in pattern sequence, whichever is

applicable.

D. Razor trim edges on flat work table. Do not razor cut on gypsum board surfaces.

E. Apply wall covering smooth, without wrinkles, gaps or overlaps. Eliminate air

pockets and ensure full bond to substrate surface. Butt edges tight.

F. Horizontal seams are not acceptable.

G. Do not seam within 2 inches of internal corners or within 6 inches of external

corners.

H. Install wall covering before installation of bases, cabinets, hardware, or items

attached to or spaced slightly from wall surface. Do not install wall covering

more than 1/2-inch below top of resilient base. Run fabric behind cabinets and

splashes 2 inches.

I. Cover spaces above and below windows, above doors, in pattern or numerical

sequence from roll, whichever is applicable.

J. Where wall covering tucks into door frame reveals, or metal wallboard or plaster

stops, apply covering with contact adhesive within 6 inches of wall covering

termination. Ensure full contact bond.

K. Install termination trim where vinyl does not stop at a corner.

L. Remove excess wet adhesive from seam before proceeding to next wall covering

sheet. Wipe clean with dry cloth.

M. Continue wall covering through jambs and heads of drywall openings.

Page 35: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09720 - 5

1/31/06 Construction Bid Set Wall Coverings

3.4 CLEANING

A. Replace wall plates and accessories removed prior to work of this Section.

3.5 DEFECTS

A. Replace wall coverings applied to defective substrate surfaces. Correct defects

in completed wall coverings.

END OF SECTION

Page 36: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09910 - 1 1/31/06 Construction Bid Set Paints

SECTION 09910 PAINTS

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. The work includes the painting and finishing of interior and exterior exposed surfaces where indicated on the Contract Drawings.

B. The work includes restoration of existing surfaces as indicated. Existing surfaces include painted gypsum wallboard and vinyl wall covering. Work includes applying new vinyl wall covering prior to painting where indicated. Extent of restoration work involving existing painted surfaces is indicated on the Contract Drawings.

C. The term "paint" as used herein means all coating systems materials, and includes primers, emulsions, enamels, stain, sealers and fillers, and other applied materials whether used as prime, intermediate, or finish coats.

D. Paint exposed surfaces whether or not colors are designated in any schedule, except where the natural finish of the material is specifically indicated as a surface not to be painted. Where surfaces are not specifically identified, paint such surfaces the same as adjacent similar surfaces or as required by the District.

E. The paint systems specified indicate the basic painting systems. Deviations within the system, such as the use of two finish coats in lieu of undercoat and finish, will be permitted only where such procedure is recommended by the paint manufacturer and approved by the District.

1.2 WORK NOT INCLUDED IN THIS SECTION

A. Pre-Finished Items: Field finish does not include painting of pre-finished items such as such as acoustical panels and suspension systems, finished mechanical and electrical equipment, including light fixtures and distribution cabinets, except when specifically indicated to be painted.

B. Cabinets, wood veneer doors with natural finish, plastic laminate surfaces, lockers, and anodized aluminum shall not be painted unless when specifically indicated to be painted.

C. Concealed Surfaces: Painting is not required on wall or ceiling surfaces in concealed areas and generally inaccessible areas.

D. Nonferrous Metal Surfaces: Anodized aluminum, chrome-plated metal, stainless steel, copper, and similar nonferrous metal materials will not require finish painting unless otherwise indicated or specified.

Page 37: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09910 - 2 1/31/06 Construction Bid Set Paints

E. Operating Parts and Labels: 1. Moving parts of operating units, mechanical and electrical parts, such as

valve and damper operators, linkages, sensing devices, motor and fan shafts, and expansion joints, will not require finish painting unless otherwise indicated.

2. Do not paint over code-required labels, such as UL, FM, and WH, or equipment identification, performance rating, name, or nomenclature plates.

3. Do not paint automatic fire sprinkler heads. 4. Do not paint anodized window and door frames. 5. Do not paint fire extinguisher cabinets. 6. Do not paint natural finish wood trim and doors.

F. Miscellaneous Surfaces: Rubber and elastomeric sealants, cementitious fireproofing, and machined surfaces of metal hardware and related fittings will not require finish painting.

1.3 REFERENCE STANDARDS

A. ASTM D4442 - Test Methods for Direct Moisture Content Measurement of Wood and Wood-Base Materials

B. Painting and Decorating Contractors of America (PDCA):

"Painting and Decorating Craftsman's Manual and Textbook"

C. SSPC Steel Structures Painting Manual, Volume 2, “Systems and Specifications

1.4 SUBMITTALS

A. Product Data: 1. Submit a complete list of all materials proposed for use, together with

manufacturers’ product specifications for such products. 2. Verify field conditions. No claim by the Contractor concerning the

unsuitability of any material specified, or the Contractor’s inability to produce first class work with such materials, will be considered unless such claim is made in writing to the District before Bids are submitted.

B. Colors and Samples: 1. Samples:

a. Before beginning work, prepare for approval a sample of each color, texture, and finish required. Such samples, when approved, shall constitute standards for color, texture, and finish of completed work.

b. Make samples 8 by 10 inches in size. c. When samples are rejected, a maximum of two additional modified

samples may be required, in each instance, to obtain approval. d. Approved samples shall be marked for identification and shall be

distributed to the District and A/E as required.

Page 38: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09910 - 3 1/31/06 Construction Bid Set Paints

e. Submit samples of vinyl wall covering proposed to match texture of existing vinyl wall covering.

C. Manufacturers' Review: Submit record of paint manufacturer’s review as specified in Article 1.5D.

1.5 QUALITY ASSURANCE

A. Regulatory Requirements: 1. Paint products and solvents shall comply with the latest regulations of the

Bay Area Air Quality Management District regarding regulations governing permissible content of volatile organic compounds (VOC).

2. Conform to applicable building code for flame spread/fuel contribution/smoke development rating requirements for finishes.

B. Quality Standards: 1. Preparation and painting work shall conform to the recommended

practices and quality standards of the “Painting and Decorating Craftsman’s Manual and Textbook,” latest edition, published by the Painting and Decorating Contractors of America.

2. Preparation and painting of steel surfaces shall conform to the quality standards of the SSPC Steel Structures Painting Manual, Volume 2.

3. Paints, enamels, stains, lacquers, and varnishes shall be applied in accordance with the manufacturers’ latest specifications, instructions, and recommendations.

C. Paint Coordination: 1. Ensure finish coats are fully compatible with the prime paints used.

Primers, intermediate (if any), and finish coats shall be products of the same manufacturer. If existing substrate is incompatible with or inadequate preparation for field coatings, provide barrier coats over incompatible substrate.

D. Paint Manufacturer’s Review: Before purchasing paint materials, review the proposed paint systems, materials, and substrates with qualified representatives of the proposed paint products manufacturer. Obtain manufacturer’s concurrence of the proposed paint systems, or any recommended changes thereto, before providing product data, samples, and mock-ups, as applicable.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver paint materials to the site in original, unopened packages and containers with labels intact and seals unbroken. 1. Container labeling to include manufacturer's name, type of paint, brand

name, brand code, coverage, surface preparation, drying time, cleanup, color designation, and instructions for mixing and reducing.

B. Store materials, tools, and equipment in a locked, properly ventilated, designated storage space on the site, assigned for this purpose. Receiving, opening, and mixing of paint materials shall be performed in this storage space. Keep storage

Page 39: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09910 - 4 1/31/06 Construction Bid Set Paints

space neat, clean, and accessible at all times. Protect areas from paint spillage. Do not store paints, etc. inside building. 1. Store paint materials at minimum ambient temperature of 45 degrees F

and a maximum of 90 degrees F, unless required otherwise by manufacturer's instructions.

C. Take all necessary measured measures to prevent fire hazards including spontaneous combustion. Including the following: Place paint-soaked or solvent-soaked rags, waste, and other materials which might constitute a fire hazard in closable metal containers and remove from the premises at the close of each day’s work.

1.7 PROJECT CONDITIONS

A. Do not apply materials when surface and ambient temperatures are outside the ranges required by paint manufacturer.

B. Surfaces shall be painted only when they are free from moisture.

C. No painting shall be performed when temperature is below 40 degrees F and above 90 degrees F or when the relative humidity is above 90 percent, unless recommended otherwise in writing by the paint manufacturer.

D. Coordinate with the District to ensure that ventilation, heating, and air conditioning is provided to maintain surface and ambient temperatures before, during, and 48 hours after application of finishes within the range required by manufacturer, and to provide required ventilation for installers and building occupants. If building ventilation facilities are not adequate, Contractor shall provide equipment and other devices to augment ventilation.

E. Provide lighting level of 80 footcandles measured mid-height at substrate surface. Building lighting may be utilized, however, Contractor shall provide additional fixtures to augment lighting levels where required.

F. Finish coats of paint shall not be applied on the interior of the building until dust-producing work is complete and dry.

1.8 EXTRA STOCK

A. Provide one-gallon container of each color and finish product to the District.

B. Label each container with color, color number, texture, and room locations, in addition to the manufacturer's label.

PART 2 - PRODUCTS

2.1 PAINT QUALITY STANDARDS

A. Provide primer paints produced by the same manufacturer as the intermediate and finish coats. Use thinners approved by the paint manufacturer which meet

Page 40: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09910 - 5 1/31/06 Construction Bid Set Paints

previously referenced regulatory requirements, and provide only to recommended limits.

B. Provide primers which are suitable for each surface to be painted and which are compatible with specified intermediate and finish paint coats.

C. Minimum dry film thicknesses (MDFT), in mils, and the number of coats required to obtain such thicknesses shall be in accordance with the paint manufacturer’s application instructions and recommendations.

2.2 PAINT MATERIALS

A. Refer to Paint Schedule at end of this Section.

B. Accessory Materials: 1. Shellac: ASTM D207, Type I, bleached, No. 4, cut with pure grain alcohol. 2. Thinner: As recommended by the manufacturer for the respective

product. 3. Spackle or Putty: Standard commercial product manufactured for the

purpose, thoroughly mixed to prevent the possibility of shrinkage. Spackle or putty shall be tinted toward finish color. Spackle or putty containing white lead will not be permitted for use on this Project.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verify that surfaces and substrate conditions are ready to receive work as instructed by manufacturer. Correct unsatisfactory conditions prior to commencement of work.

B. After completion of preparation, measure moisture content of surfaces using an electronic moisture meter. Do not apply finishes unless moisture content of surfaces are below the following maximums: 1. Plaster and Gypsum Wallboard: 12 percent. 2. Masonry, Concrete, and Concrete Unit Masonry: 12 percent. 3. Interior Located Wood: 15 percent, measured in accordance with

ASTM D 2016.

C. Test existing substrates for compatibility with subsequent cover materials.

D. Beginning of installation means acceptance of existing surfaces and substrate.

3.2 PREPARATION OF SURFACES

A. General: 1. Fix surfaces and prepare for painting. Painting or finishing shall not be

started until the surfaces to be painted or finished are in proper condition to accept, and assure the proper adhesion and functioning of, the specified painting system in accordance with the paint manufacturer’s

Page 41: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09910 - 6 1/31/06 Construction Bid Set Paints

installation instructions and recommendations. All surfaces to be painted shall be clean and dry.

2. Comply with coating manufacturer’s preparation instructions. Comply with manufacturer’s representative’s recommendations regarding preparation of unusual substrates such as mildew areas.

B. Existing Painted Surfaces to be Painted: 1. Wood Surfaces: All wood surfaces shall be power sanded as required to

remove all peeling, flaking, blistering, loose, or otherwise defective existing paint surfaces. In the case of edges of plastic laminate countertop splashes where plastic laminate edging is either partially or completely missing, remove existing plastic laminate and adhesive. Wood surfaces shall be sandpapered and dusted clean. Knots, pitch pockets, or sappy portions shall be sealed with clean shellac or knot sealer. Spackle or putty all nail holes, cracks, and other imperfections after first or prime coat with spackle or putty of color to match finish coat. a. Regarding edges of plastic laminate countertop splashes where

plastic laminate edging is either partially or completely missing, remove existing plastic laminate and adhesive. Prevent damage to other plastic laminate surfaces. Fill, sand, and prepare as specified for wood surfaces.

2. Metal Surfaces: Metal surfaces shall be power sanded as required to remove rusting, peeling, flaking, blistering, loose, or otherwise defective existing paint surfaces. Metal surfaces shall be dusted clean. Spackle or putt imperfections after prime coat. a. Where there is rusting of existing painted metal surfaces, power-

tool clean surfaces in accordance with SSPC-SP 3 to remove loose and defective paint surfaces, and then feathered smooth. Rust shall be completely removed. Then solvent clean surfaces in accordance with SSPC-SP 1 to remove dust, and apply prime coat of Ferrous Metal Primer, as applicable, to existing surfaces.

3. Gypsum Board and Plaster Surfaces: Latex fill minor defects. Spot prime after repair. For plaster, wash and neutralize high alkali surfaces.

C. Areas with Possible Mildew: Use cleaner recommended by paint manufacturer for application, such as cleaners containing household bleach to kill mildew.

D. Vinyl Wall Covering to be Painted: Verify that existing wall covering is soundly adhered. Re-adhere areas which have separated from substrate using materials recommended for application. Clean substrate of mildew prior to re-adhering vinyl wall covering. Clean vinyl wall covering prior to priming as required by paint manufacturer. 1. Where portion of existing vinyl wall cover is missing or where painted new

vinyl wall covering is designated, apply new vinyl wall covering to match the texture of the adjacent existing vinyl wall covering and paint.

Page 42: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09910 - 7 1/31/06 Construction Bid Set Paints

E. Architectural Woodwork to be Re-Finished and New Architectural Woodwork to be Finished: Refer to Section 06400, Architectural Woodwork.

F. Hardware and Fixtures: 1. Hardware, hardware accessories, plates, lighting fixtures, and similar

items in place shall be removed prior to painting and replaced upon completion of each space.

2. Heating and other equipment adjacent to walls shall be disconnected, using workers skilled in appropriate trades, and moved to permit wall surfaces to be painted. Following completion of painting, they shall be expertly replaced and reconnected.

G. Exposed Plumbing, Mechanical, and Electrical Items, Designated to be Painted: 1. Wash exposed metal with solvent, prime, and paint as scheduled.

3.3 PAINT PERFORMANCE AND FIELD QUALITY ASSURANCE

A. Painting shall be performed by skilled and experienced painters, working under the supervision of a capable supervisor. Materials shall be thinned only for proper workability and in compliance with the manufacturer’s specifications.

B. Paint material shall be evenly brushed or smoothly flowed on without runs or sagging, and free from drops, ridges, laps, and brush marks. Ensure that all coats are thoroughly dry before applying succeeding coats. Sand surfaces between coats as necessary to produce a smooth finish and as may be required for adhesion of succeeding coats.

C. Putty, caulking, or spackle shall be applied after surface is primed and primer is dry.

3.4 FINISHING MECHANICAL AND ELECTRICAL EQUIPMENT

A. Where wall and ceiling surfaces are scheduled to be painted, paint grilles, registers, diffusers, and speaker grilles to match adjacent wall and ceiling surfaces with the following exception: Factory pre-finished items need not be painted if installed in a suspended acoustical ceiling system where the acoustical panels match the mechanical or electrical item color.

B. In finished spaces, prime and paint exposed pipes, conduit, boxes, ducts, hangers, brackets, collars, and supports. Paint to match adjacent surfaces.

C. Repair or replace identification markings on mechanical or electrical equipment when painted accidentally.

3.5 PROTECTION AND CLEANING

A. Protection floors, adjacent surfaces, prefinished materials, building fixtures, furnishings, equipment, and similar surfaces.

B. Painted and finished surfaces, including furnishings, subject to damage or defacement due to work in the building or vicinity shall be protected and covered.

Page 43: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 09910 - 8 1/31/06 Construction Bid Set Paints

The Contractor shall be responsible for damage to finishes, furnishings, painted work and to that of other work caused by painting operations until final acceptance.

C. Clean and retouch the work as necessary for a first-class job. Building surfaces and building contents shall be left clean and neat in all respects, free from any paint spots, smears, smudges, or stain.

3.6 PAINT SCHEDULE

A. Provide a minimum of two coats (unless otherwise specified), consisting of prime coat and finish coat, in texture and color as selected and approved by the District. Provide intermediate coat where necessary to cover existing color or pattern. Provide a minimum of three coats at exterior.

B. Materials List: Products of ICI/Dulux Paints have been listed to establish a standard of quality. Products specified contain no volatile organic compounds (VOC). Interior products shall be odor-free. Products of Sherwin Williams, Benjamin Moore, Kelly Moore, Frazee, or equal may be submitted for the District’s approval. 1. 9116, Lifemaster Primer. 2. 9200, Lifemaster, Semi-gloss. 3. 9300, Lifemaster, Eggshell. 4. 4020, Devflex, Waterborne Exterior Primer 5. 4208, Devflex, Waterborne Acrylic Gloss Enamel.

C. Schedule:

Interior

Substrate Finish Filler/

Primer

Inter-

mediate

Finish Remarks

GWB, plaster, and vinyl wall covering designated to be painted: Typical.

Eggshell 9116 9300

GWB and vinyl wall covering designated to be painted: Lunch rooms, coffee rooms

Semi-gloss 9116 9200

Ferrous metal, typical. Semi-gloss 9116 9200 Existing painted wood. Semi-gloss 9116 9200

Exterior

Substrate Finish Filler/

Primer

Inter-

mediate

Finish Remarks

Ferrous metal, typical. Gloss 4020 4208 4208 END OF SECTION

Page 44: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 10440 - 1

1/31/06 Construction Bid Set Interior Signage

SECTION 10440

INTERIOR SIGNAGE

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Removal of existing logo from glass doors, where indicated.

B. Translucent AC Transit logo signs for glass doors. District will provide logo

artwork.

1.2 SUBMITTALS

A. Shop Drawings: Submit artwork enlarged to actual size and submit diagram

indicating locations and overall dimensions of each sign.

B. Signage Removal: Submit written description of signage removal techniques.

C. Samples: Submit sample of signage material, 6 inch by 6 inch.

D. Manufacturer's Installation and Maintenance Instructions: Submit instructions for

signage material.

1.3 QUALITY ASSURANCE

A. Fabricator/Installer Qualifications: Company specializing in signage work

specified in this section with minimum three years documented experience.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Avery Graphics.

2.2 COMPONENTS

A. Translucent Vinyl Film: High performance film designed for window graphics.

Avery Graphics A9-Pantone Translucent Colors. Outdoor durability equal to 9

years, vertical exposure, unprinted.

1. Color: White translucent film designed to resemble sandblast graphics.

2. Total Thickness: 2.3 mils.

Page 45: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 10440 - 2

1/31/06 Construction Bid Set Interior Signage

PART 3 - EXECUTION

3.1 PREPARATION

A. Remove existing logo from each door using methods which will not scratch or

discolor glass. .

3.2 INSTALLATION

A. Install signs at locations indicated.

END OF SECTION

Page 46: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 12125 - 1 1/31/06 Construction Bid Set Picture Framing

SECTION 12125 PICTURE FRAMING PART 1 - GENERAL 1.1 SECTION INCLUDES

A. Remove existing framed photographs, other portraits, and artwork (referred to as “artwork” herein) and re-frame them in new frames with mats.

B. Old frames and accessories shall be turned over to the District after artwork is

removed.

1.2 UNIT PRICE - MEASUREMENT AND PAYMENT

A. Framed Picture: Quantity on Bid Schedule is approximate and includes 10 complete picture frames, glazing, mat, backing, and hanging hardware delivered to the District as extra stock for future artwork.

B. Basis of Measurement: By each photograph, other portrait, or artwork framed

and installed, complete.

C. Basis of Payment: Includes removing artwork from existing frame and all other work described in this Section.

1.3 SUBMITTALS

A. Shop Drawings: Show frame and mat sizes for typical artwork.

B. Product Data: Submit frame manufacturer’s product data. Submit product data on mat material.

C. Samples:

1. Submit corner of specified frame (6 inches by 6 inches). 2. Submit mat color samples for selection. 3. After approval of corner sample and mat color, submit prototype frame

and mat for approval. Fabricate using actual materials proposed for the work, including hanging hardware. If the District provides sample photograph, incorporate sample in prototype.

1.4 QUALITY ASSURANCE

A. Qualifications: Company specializing in performing Work of this section with minimum three years documented experience.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Protect units from moisture damage.

Page 47: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 12125 - 2 1/31/06 Construction Bid Set Picture Framing

B. It is anticipated that the Contractor will remove artwork from the site and install artwork in frames at an off-site workshop. Prior to removing artwork, Contractor shall photograph each item and prepare a list with brief description of each item. Contractor shall obtain sign-off from the District acknowledging that the Contractor has accurately listed removed artwork. Contractor shall sign same documentation accepting responsibility for said artwork. Contractor shall take responsibility for artwork and ensure that artwork is located at a secure location.

C. Protect artwork and assembled framed units from damage and soiling.

1.6 FIELD MEASUREMENTS

A. Verify artwork measurements prior to fabrication. 1.7 EXTRA STOCK

A. Quantity on Bid Schedule includes 10 complete picture frames with glazing, cut mat, backing, assembly hardware, and hanging hardware, protected by packaging such as bubble wrap and cartons, and delivered to the District as extra stock for future artwork.

PART 2 - PRODUCTS 2.1 COMPONENTS

A. Prefinished Wood Frame: To match Gibraltar 52149, Mahogany, 2 1/2 inch side frame, as manufactured by American Frame, Corporation, or equal. www.americanframe.com.

B. Mat Board: Crescent Brand, white core, acid-free core and back, 1/16 inch thick,

bright white bevel. Custom cut with bevel. Color: One color as selected from manufacturer’s standard colors.

C. Glazing: Standard acrylic glazing.

2.2 ACCESSORIES

A. Picture Hanging Hardware: Size and type to suit application and as approved by District.

2.3 FABRICATION

A. Sizing: Identify each photograph or other artwork and list sizes. Select uniform frame and size. Vary mat size if necessary to suit artwork. The following is an example of the frame and mat size proportions: Frame size 16 inches wide and 22 inches high for artwork 12 inches wide and 18 inches high. Verify actual dimensions in field.

Page 48: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 12125 - 3 1/31/06 Construction Bid Set Picture Framing

B. Accurately cut mats with bevel edges and glazing. Making sure that interior of glazing is clean before assembling. Assemble glazing, mat, artwork and backing in alignment and secure backing.

PART 3 - EXECUTION 3.1 INSTALLATION

A. Arrange pictures at locations as directed by the District and secure to wall. Completed installation shall result in frames accurately aligned, straight, and evenly spaced.

END OF SECTION

Page 49: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 12492 - 1

1/31/06 Construction Bid Set Vertical Louver Blinds

SECTION 12492

VERTICAL LOUVER BLINDS

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. New operating vertical louver blind installed between vertical mullions and

operating hardware to replace and to match existing. Includes removal of

existing vertical louver blinds.

B. See Bid Schedule: New blinds to replace existing at first floor Lobby Room 112

are subject of a bid alternate.

1.2 SUBMITTALS

A. Submit shop drawings indicating field-measured opening sizes, tolerances

required, installation of blind at window opening, method of attachment,

clearances, operation, and conditions between adjacent blinds.

B. Submit product data indicating physical and dimensional characteristics and

operating features.

C. Submit two samples, minimum 6 inches long, illustrating vane materials and

finish, color, cord type and color.

D. Submit manufacturer's installation instructions.

1.3 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing the products

specified in this Section with three years documented experience.

B. Installer Qualifications: Company specializing in installing products specified in

this Section with three years documented experience and approved by

manufacturer.

1.4 DELIVERY, STORAGE, AND HANDLING

A. Deliver blinds wrapped and crated in a manner to prevent damage to

components or marring of surfaces, in manufacturer's original unopened

packaging with labels intact.

B. Store in a clean, dry area free of corrosive fumes, dust, and away from

construction activities. Stack materials flat and blocked off ground to prevent

sagging, twisting, or warping.

Page 50: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 12492 - 2

1/31/06 Construction Bid Set Vertical Louver Blinds

1.5 EXTRA MATERIALS

A. Furnish ten additional vanes of each type and length.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Louverdrape. http://www.louverdrape.nl/e-louverdrape.detail.htm or equal.

2.2 BLINDS

A. Size: To match existing.

B. Material: Vinyl with ultraviolet inhibitors.

C. Color and Finish: As selected to match existing.

D. Product: Louverdrape to match existing.

2.3 COMPONENTS

A. Head Rail: To match existing. To be verified in the field: Extruded anodized

aluminum alloy, 1-5/16 inches wide by 1-7/16 inches high with capped ends and

sprocket wheels.

B. Carriers: To be verified in the field: Minimum 5/16-inch wide, traverse on wheels;

glides, or sliders. Snap-out vane stem design shall yield when subjected to

interference.

C. Spacer Links: To be verified in the field: Flexible stainless steel, 1/4-inch wide.

D. Vanes: Rotate 360 degrees and pack when traversed, into maximum 5/16-inch

per vane. When rotated, vanes shall overlap minimum 3/8-inch. Solid or

perforated to match existing at each room. To be verified in the field.

1. At private offices, provide solid or perforated in accordance with

preference of occupant. District will provide schedule in writing, listing

rooms and vane type.

E. Rotation Mechanism:

1. Bead Chain: No. 6 nickel-plated chain.

2. Gears: Minimum 8-to-1 mechanical advantage, shall keep vanes fixed

until reset by control; cord or 1-to-1 ratio mechanisms will not be

acceptable.

F. Traversing Mechanism:

1. Allow vertical blinds to traverse left to right, right to left or split.

2. Blinds shall traverse by means of non-stretch traverse cord.

Page 51: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 12492 - 3

1/31/06 Construction Bid Set Vertical Louver Blinds

G. Cord Weight: Molded ABS plastic filled for weight; readily removable without

detaching cord from head rail.

H. Control and Return End Caps: Provide covers to enclose sprockets and rotation

rod ends and rollers for traverse cord, molded to match aluminum extrusion

profile.

I. Installation Brackets: Provide for overhead or surface installation using thumb

clamps and angle brackets; designed to facilitate installation and removal of

track.

J. Vane Spacing: Provide nylon spacer arm integral with carriage body to provide

uniform vane spacing when blind is fully drawn.

2.4 FABRICATION

A. Fabricate units to completely fill openings, head to sill and jamb to jamb and to

match existing.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Do not commence fabrication until field measurements are confirmed.

B. Ensure structural supports are correctly placed.

C. Beginning installation indicates acceptance of existing conditions.

D. Notify A/E in writing of discrepancies which would affect proper installation and

operation of blind system.

E. Ensure dust producing operations, such as carpet removal and installation, are

complete prior to installation.

3.2 INSTALLATION

A. Remove existing units and install blinds in accordance with manufacturer's

instructions.

B. Secure in place with fasteners to match existing adjacent blinds.

C. Provide adequate clearance to permit unencumbered operation of blind and

hardware.

3.3 TOLERANCES

A. Maximum Variation of Gap at Window Opening Perimeter: 1/4-inch.

Page 52: INTERIOR RENOVATION PROJECT AC TRANSIT GENERAL OFFICE … · laminate cabinetry; and associated repair of surfaces and removal and disposal ... scratches, and to restore durable finish

C&B AC Transit GO Bldg 12492 - 4

1/31/06 Construction Bid Set Vertical Louver Blinds

B. Maximum Offset From Level: 1/8-inch.

3.4 ADJUSTING

A. Adjust blinds for smooth operation.

B. Clean vanes in accordance with manufacturer's instructions.

END OF SECTION