Integration into EtherNet /IP Networks
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks2
INTRODUCTION 4
Overview 5
Pre-requisite Skills 6
RequiredHardware/Software 6
COMMUNICATION 6
VFDCommunicationMethods 6 Preparations&NetworkPlanners
EnableCommControlsConfiguration 7
RSLINX 8
StartingEDSWizard,Registering 9-11 EDS,andCompletingTask
STUDIO 5000 PART 1 12
ProjectConfiguration 13
CreatingYASKAWA 14 EtherNet/IPModule
YASKAWA TAG GENERATOR 17
Setup&Start 18
Configure 20
SaveCSV 21
STUDIO 5000 PART 2 24
ImportingYASKAWA’sI/0 25 GeneratedTags
ImportingYASKAWA’sAdd-On 27 Instruction&Map
UTLIZING THE AOI 29
CreatingRungLogicsandTest 30
APPENDICES A, B, C 33
INTRODUCTION
YASKAWA Integration into EtherNet/IP Networks4
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
OVERVIEWThepurposeofthisguideistohelptechniciansandengineersintegrateYaskawaVariableFrequencyDrives(VFD)intoaneworexistingEtherNet/IPnetwork,specificallyRockwellAutomation(RA)ProgrammableLogicControllers(PLC).EtherNet/IP(EIP)isbeingusedinawiderangeofindustriesandisoneofthefastestgrowingindustrialprotocolsintheUnitedStates.EtherNet/IPisanopensourceimplementation,thusallowingforthecontinuousdevelopmentandsupportfromindustryleaders(suchasYaskawa),ensuringthatthisindustrialapplicationlayerprotocolsupportsustainability.
InstructionsandexampleswillbebasedonYaskawaTagGenerator,Yaskawaadd-oninstructions,RSLINX,andaCompact/ControlLogix™PLCplatform,configuredwiththeRSLogix5000orStudio5000(RS5K)softwareenvironment.Thisguidewillnavigate,configureandexplorethefunctionalityofYaskawaTagGenerator.
TheYaskawaTagGeneratorwasdevelopedtoallowtechniciansandengineerstoselectmultipleYaskawaEtherNet/IPproducts,theirfunctions(pre-definedI/Oassemblies),andthenoutputthecompileddatatoaCommaSeparatedValue(CSV)file.OnceimportedintotheRS5Kenvironment,thesetagsarethenaliasedtogenerictagscreatedwhenaddingtheYaskawamodule[s],thussimplifyingintegrationandreducingcommissioningtime.
USE OF THIS INFORMATION/
DOCUMENTATIONNothinginthisdocumentoranyinformationordataderivedfromthisdocumentmaybepublished,distributedorcopied,normaytheinformationordatabeusedtocreatederivativeworks.Nouserofthisinformationordatamayalloworenableotherstoreverseengineer,decompile,disassembleorotherwiseattempttoreconstruct,identifyordiscoveranycode,underlyingideas,techniques,oralgorithmsfromthisinformation.Noconfidentialinformationorproprietaryrightsordatamayberemoved,obscuredoraltered.
AllproprietaryandownershiprightsbelongingtoEECOshallremainwithEECO,andnothinginthisdocumentshallrelinquishsuchrights,titleorinterest.
INDEMNIFICATION EECOshallbeindemnifiedandheldharmlessfromanyandallclaims,damages,lossesand/orexpenses,includingreasonableattorney’sfeesarisingfromanybreachofthisagreementortheuser’sobligationshereunder.
YASKAWA Integration into EtherNet/IP Networks5
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
WARRANTY DISCLAIMERThisdocumentistobeused“AsIs”withoutwarrantyofanykind.EECO,onbehalfofitselfandanyaffiliates,herebydisclaimsallrepresentations,promisesorwarranties,whetherexpressorimpliedwithrespecttotheinformationcontainedherein.EECOspecificallydisclaimsallimpliedwarrantiesormerchantability,non-infringement,suitabilityandfitnessforanypurpose.
PRE-REQUISITE SKILLS
Thisdocumentiswrittenandintendedfortechniciansandengineerswhowillbecommissioningand/orsupportingYaskawaVFD[s]ontheplantfloor.Theintendedusersshouldunderstand,attheveryleast,navigationthroughtheRS5Ksoftwareenvironment.
REQUIRED HARDWARE/SOFTWARE1. YaskawaVFDwithOptionalCommunicationCard-
(CIMR-VU2A0001FAA-V1000withtheSI-EN3/Vinourcase)
2. PCwithRSLINXandRS5K
3. RockwellLogixPLC(1756-L71ControlLogixinourcase)
* Note: All Yaskawa EDS files and software may be downloaded from
Yaskawa.com via links provided in the Appendices.
COMMUNICATIONVFD COMM METHODS
InitialconnectiontotheYaskawaVFDcanbeaccomplishedinacoupleofways:
1. DirectconnectviaPLCtoVFD
2. CommonSwitchorRouterConnectviaportsonthesameswitch
3. Networkconnectionviamultipleswitchesand/orwireless access points
VFD DEFAULT CONFIGURATION AND PREPARATIONS
OpenDeviceNetVendorAssociation(ODVA),thegoverningbodyofEtherNet/IP,whichspecifiesthatallEIPsupportingdevices,includingYaskawaVFD,bydefaultmustbesettouseDynamicHostControllerProtocol(DHCP)togetthenetworksettings.
ThiscorrespondingrequirementisreflectedinparameterF7-13(AddressModeatStartup:2bydefault).IfaDHCPserverdoesnotexistwithinthenetworktopology,proceedtochangethenetworksettingsmanuallytoastaticsetting.
UsingthekeypadorDriveWizardIndustrialsoftware,theoptioncard’snetworksettings(IPAddress,SubnetMaskandDefaultGateway)canbeconfiguredundertheF7parameters.AdditionalUserSettingTableinformationcanbefoundwithintheYaskawaACDriveTechnicalManual–SIEPC71060618:E.3-page491.
YASKAWA Integration into EtherNet/IP Networks6
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA VFD NETWORK PARAMETERS:
• F7-01EthernetIPAddress1—192
• F7-02EthernetIPAddress2—168
• F7-03EthernetIPAddress3—1
• F7-04EthernetIPAddress4—1-254
• F7-05SubnetMask1—255
• F7-06SubnetMask2—255
• F7-07SubnetMask3—255
• F7-08SubnetMask4—0
• F7-09GatewayAddress1—192
• F7-10GatewayAddress2—168
• F7-11GatewayAddress3—1
• F7-12GatewayAddress4—1
• F7-13AddressModeatStartup—0from2to becomestatic,thencyclepower.
Toconfirmnetworksettingsafterthepowercycle,wecanverifythesettingsundertheMonitorparametersU6-80toU6-91.Valuesarepresetiftheoptioncardhasaconnectiontoanotherdevice.
ThenetworkLED(NS)shouldnowtransitiontoasolidgreenstate.
ENABLE COMM CONTROLS CONFIGURATION
Thefollowingparametersmustbechangedtoenablefieldbuscontrols.
• B1-01to3:OptionPCB(FrequencyReferenceSelection1)Defaultis=1AnalogInput
• B1-02to3:OptionPCB(RunCommandSelection1)Defaultis=1DigitalInput
*New values will accept immediately without a Power Cycle
PC CONFIGURATION
1. Open Network and Sharing CenterfromthetaskbarorunderControlPanel.
2. IfnoconnectionispresentonyourPCnetworkport(RJ45),selectchange adapter settingsontheleftsidebar.
3. Double click Local Area Connection,thenproperties,and double click on (TCP/IPv4)
4. ConfigurethePC’sstaticnetworksettingsbyselecting“Use the following IP Address:”
5. Inputanunused IP AddressthatisonthesamesubnetaspreviouslymentionedintheVFDconfiguredoption.
6. InputthesameSubnet mask and Default Gateway as previouslyusedintheVFDconfiguration.
7. Select OK and OKagainontheLocalAreaConnectionPropertieswindowandthesettingsareready.
ROCKWELLAUTOMATIONENVIORNMENTSRSLINX
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks8
Beginningwithv20 of RS5K,thismaybeaccomplishedwithotheradditionaloptionswithintheenvironmentundertheTools Menu.
Let’sstartoffbyregisteringtheEATONEDSfilesintoRSLINXwiththeEDSWizard.
OpenthestartmenuandunderRSLINX
STEP 1: SelecttheEDS Hardware Installation Tool
STEP 2: Select add
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks9
SelectwhetheryouwouldliketoregisterasingleoradirectoryofEDSfiles.Ifthelatter,pleasetickLook in subfoldersaswell.
STEP 3: Browsetothefolderdirectorycontainingthe EDS[s]
STEP 4: Click next
Thesystemwilldoascanandpopulate a test result.
STEP 5: Selectthedesiredfile[s]toregister
STEP 6: Click next
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks10
Change the iconsifneeded
STEP 7: Click next
Afinaltasksummarywindowwillappear.Ensure the information is correct.
STEP 8: Click nexttocompletetheEDSregistration process
STUDIO5000 PART 1
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks12
STEP 5: Selectthechassis type
STEP 6: Click finish
STEP 1: Open or createanewprojectinRS5K.
Ifstartinganewproject-
STEP 2: Selecttheprocessorandnameyourproject
STEP 3: Browsetothedesiredprojectsavelocation
STEP 4: Click next
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks13
IntheControllerOrganizer-
STEP 7: Right clicktheprocessorBackplane (slot0)
STEP 8: Create a newEthernetmodule.
Forthisexample,the1756-EN2Twillbeused.Clickcreate
STEP 9: Name the EN2TandinputanunusedIP Address(192.168.0.2)
STEP 10: Click OK
AnEN2Tmodule(slot1)nowexistsundertheBackplane.
YASKAWA Integration into EtherNet/IP Networks14
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
A Yaskawa V1000 VFD will be added to the RS5K project.
STEP 11: Rightclickonthe1756-EN2T module and select create new module
TheSelectModuleTypewindowappears.ToentertheV1000asaGenericEthernetModule-
STEP 12: Deselect both filtersforCategoryandVendor
STEP 13: SelectonlyCommunication and Allen Bradley
STEP 14: Scrolldowntowardthebottomof thelistandselect ETHERNET-MODULE Generic Ethernet Module
STEP 15: Click create
STEP 16: Anewmodulewindowappears
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks15
STEP 17: Inputanamethatisdistinctiveyetsimple (V1000) as you will need to reuse this identical name in the Tag Generator Software
STEP 18: ChangetheCommFormatfromDINT >> INT
STEP 19: InputanunusedIPAddress(192.168.0.100) thatisonthesamesubnetastheEN2T,i.e. 192.168.0.x.{x=2-254}.
STEP 20: Input 71fortheInputAssemblyInstance, size = 2 bytes (INT) (pg. 41 in TOBPC73060092 Manual)
STEP 21: Input 21fortheOutputAssemblyInstance, size= 2 bytes (INT) (pg. 41 in TOBPC73060092 Manual)
STEP 22: Configurationassemblyisnotused,butthere mustbeavaluethereasaplaceholdersoinput 1 for ConfigurationAssemblyInstance,size = 0
YASKAWATAG GENERATOR
YASKAWA Integration into EtherNet/IP Networks17
STEP 1: InstallYaskawaTagGenerator.Onceinstalled,startthe programbydouble clicking the icon
STEP 2: ClickNewProjectinthetopmenu.
Thenewprojectwindowwillpopupandaskwhichsoftwaredoyouwanttocreatetagsfor.
STEP 3: TickLogix Designer/RSLogix 5000
STEP 4: Enter a project name and click New Project to create theproject.
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks18
Oncetheprojectiscreated,selectwhichfirmwareisrunningonthePLC.
STEP 5: Click Add New Node
STEP 6: SelecttheOption Cardonthenextwindow
STEP 7: Click next
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks19
STEP 8: SelecttheI/OAssemblypairthatwasused intheRS5Kproject(21-71)
STEP 9: DeletetheScopefieldtomakethetags accessibleglobally;otherwise,theywillonly beavailableinMainProgram
STEP 10: Enteranodename,V1000inthiscase
*(MUST BE AN IDENTICAL NAME USED IN RS5K).
STEP 11: Click finish
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks20
STEP 12: Click Change Output Fileandbrowsetoafile locationtosavetheCSVoutputfile
STEP 13: Name CSVfile
STEP 14: Click save
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks21
STEP 15: Click Build Tag Listtogenerate
STEP 16: Click OKinthenotificationpop-up
YASKAWA Integration into EtherNet/IP Networks22
STEP 17: Provide a namefortheprojectinthepop- up window
STEP 18: Click Save
STEP 19: Theprojectmaynowbeaccessedatalater timeformodificaton.
STEP 20: Click Quitandthetaskiscompleted.
TheremainingtaskwillbecompletedintheRS5Kenvironment.
STEP 16: Click Save Project As
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
STUDIO5000PART 2
YASKAWA Integration into EtherNet/IP Networks24
NavigatebacktotheRS5Kenvironment-
STEP 1: GototheTools Menu > Import > Tags and Logic Comments
STEP 2: BrowsetothepreviouslysavedCSVfolderlocation,select, and import
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks25
Oncetheimporttaskiscompleted,youwillnoticethatthelowerErrorplaneprovidesfeedbackonhowmanytagswerecreated,inadditiontoanyerrorsandwarnings.
*If there are error[s], ensure that the names specified in the RS5K project and Yaskawa Tag Generator were identical, or re-run Tag Generator with the correct nomenclature.
AlsonoticethatthedescriptioncolumnisnowautomaticallypopulatedfromtheTagGeneratorgeneratedCSV.WhenEditTagsisselected,RS5Kwillalsoshowexactlywherethenewtagsarealiastointhegenerictags.ThefunctionalitiesoftheTagGeneratortoolgreatlycontributetothereductionofsetuporcommissioningtime,ultimatelyreducingdowntimeandincreasingproductivity.The import task is now completed.
YASKAWA Integration into EtherNet/IP Networks26
YaskawahastakenadditionalstepstosimplifyingintegrationofitsEtherNet/IPsupportedproductsbyofferingawiderangeofVFDAdd-OnInstruction(AOI)inconjunctionwithTagGenerator.Let’sproceedandexplorehowtechniciansandengineerscanuseYaskawa’sAOIs.
InRS5K-
STEP 3: NavigatetoFile > Import Component > Add-On Instruction
STEP 4: BrowsetotheAOI provided by Yaskawa
TheextensionofthefilewillbeaL5X.
STEP 5: YAI Assembly 71 21 is selected
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks27
TheImportConfigurationwindowappears.
STEP 6: Verify and select OK
STEP 7: IntheController Organizer > Add- On Instruction,theAOIhasbeensuccessfully imported and is now available for use in the Language Element Tool Bar > Add-On
UTILIZINGTHE AOI
YASKAWA Integration into EtherNet/IP Networks29
STEP 1: Next,openMainProgram–MainRoutine
STEP 2: Add a rung
STEP 3: TheninAdd-On,dragtheV1000AOItotherung0
OncetheV1000AOIblockisaddedtotherung,thetopthreeparametersintheAOIblockmustbemappedtoaspecificmodule
WithintheAOIblock-
STEP 4: Doubleclickthetop “?” nexttotheViewConfiguration Dialogbutton
STEP 5: InputV1000 > right click > select “New V1000”
STEP 6: AnewParameterorTagwindowwillappear
STEP 7: Confirmthenameandscope
STEP 8: Click create
Ensure that the Controller Tags and MainProgram windows are open and side-by-side.
STEP 9: SelectanddragV1000:I1 to the “?”intheNode_Input_ Assyrow
STEP 10: SelectanddragV1000:O1 to the “?”intheNode_ Output_Assyrow
ThesetupoftheAOIisnowcomplete.
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks30
Let’screateaDINT tag —
STEP 11: NameitInput_Output.
TheBooleanwithintheDINTwillbeusedaslogicalPushButtons.
STEP 12: Add a couple of rungstothe project
STEP 13: Enable remote FieldBus control oftheV1000bylatchingthe V1000_NetCtrl and V1000_NetRef bit
ToensurethatthePLChascontrolafterapowerloss,aFirstScanbitisusedforlatchingonapower-upcondition.
STEP 14: Addastart,stop and fault logictotheprogram,
STEP 15: Downloadtotheprocessor
The V1000 VFD is ready to be operated.
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA Integration into EtherNet/IP Networks31
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
MOTOR TESTING
• Page42ofTOBPC73060092
SPEED REFERENCE
• Speed Command
• Setsdrivespeedreference
• Speedreferencedata: Frequency reference/2SS (SS: Speed scale)
• Settingrange:0to0xFFFF
• Example:settingareferenceof4096withaspeedscaleof2: Speed reference data = 4096/22 = 1024 = 0x0400 Hex or 10.24 Hz
• Unitdependsono1-03
APPENDICESA, B, C
YASKAWA Integration into EtherNet/IP Networksa
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA RESOURCE DOWNLOADS LINKS
YASKAWA DOWNLOADS
https://www.YASKAWA.com/downloads
DRIVEWIZARD INDUSTRIAL
https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/drivewizard-industrial
ETHERNET/IP
https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-network-communication-protocols/ethernet-ip
YASKAWA NETWORK SUPPORT FILES - DOWNLOADS
https://www.YASKAWA.com/downloads?p_p_id=yasdocumentdownload_WAR_yasdocumentdownloadportlet&p_p_lifecycle=0&p_p_state=normal&p_p_mode=view&p_p_col_id=column1&p_p_col_count=1&_yasdocumentdownload_WAR_yasdocumentdownloadportlet_productGroup=Inverter+Drives&_yasdocumentdownload_WAR_yasdocumentdownloadportlet_productLine=Network+Comms-EtherNet-IP
CONFIGURED PRODUCT FOR A1000
DRIVE
https://www.YASKAWA.com/products/drives/industrial-ac-drives/general-purpose-drives/a1000-configured
U1000 INDUSTRIAL MATRIX DRIVE
https://www.YASKAWA.com/products/drives/industrial-ac-drives/general-purpose-drives/u1000-industrial-matrix-drive
G7 DRIVE
https://www.YASKAWA.com/products/drives/industrial-ac-drives/general-purpose-drives/g7-drive
G7 CONFIGURED
https://www.YASKAWA.com/products/drives/industrial-ac-drives/general-purpose-drives/g7-configured
DRIVEWORKS EZ SOFTWARE
https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/driveworks-ez-software
PROGRAMMING SIMULATOR
https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/programming-simulator
ENERGY SAVINGS PREDICTOR
https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/energy-
savings-predictor
HARMONICS ESTIMATOR
https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/harmonics-estimator
APPLICATION EXAMPLES
https://www.YASKAWA.com/downloads?p_p_id=yasdocumentdownload_WAR_yasdocumentdownloadportlet&p_p_lifecycle=0&p_p_state=normal&p_p_mode=view&p_p_col_id=column1&p_p_col_count=1&_yasdocumentdownload_WAR_yasdocumentdownloadportlet_lookupType=Software%2FApplication+Examples
TRAINING DOCUMENTS
https://www.YASKAWA.com/downloads?p_p_id=yasdocumentdownload_WAR_yasdocumentdownloadportlet&p_p_lifecycle=0&p_p_state=normal&p_p_mode=view&p_p_col_id=column1&p_p_col_count=1&_yasdocumentdownload_WAR_yasdocumentdownloadportlet_lookupType=Training+Documents
TRAINING: DRIVEWIZARD INDUSTRIAL
TIPS AND TRICKS
https://www.youtube.com/playlist?list=PLNAENlyEDCkxPasi-q_UbSCyqaU7Ryy0v
YASKAWA Integration into EtherNet/IP Networksb
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
YASKAWA SUPPORTED DRIVE PRODUCT SERIES
A1000
D1000
iQpump1000
MV1000
P1000
R1000
V1000
V1000-4X
U1000IndustrialMatrix
U1000Oil&Gas
F7
G7
YASKAWA Integration into EtherNet/IP Networksc
EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com
DIRECT CONNECT SERIAL PIN OUT
ApplicabletotheA1000,J1000,V1000,V1000-4X,J7,V7,E7,P7,G5,G7,andF7Drives
(Courtesy of YASKAWA)