YASKAWA Integration into EtherNet/IP Networks2

INTRODUCTION 4

Overview 5

Pre-requisite Skills 6

RequiredHardware/Software 6

COMMUNICATION 6

VFDCommunicationMethods 6 Preparations&NetworkPlanners

EnableCommControlsConfiguration 7

RSLINX 8

StartingEDSWizard,Registering 9-11 EDS,andCompletingTask

STUDIO 5000 PART 1 12

ProjectConfiguration 13

CreatingYASKAWA 14 EtherNet/IPModule

YASKAWA TAG GENERATOR 17

Setup&Start 18

Configure 20

SaveCSV 21

STUDIO 5000 PART 2 24

ImportingYASKAWA’sI/0 25 GeneratedTags

ImportingYASKAWA’sAdd-On 27 Instruction&Map

UTLIZING THE AOI 29

CreatingRungLogicsandTest 30

APPENDICES A, B, C 33

Page 3: Integration into EtherNet /IP Networks

INTRODUCTION

Page 4: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks4

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

OVERVIEWThepurposeofthisguideistohelptechniciansandengineersintegrateYaskawaVariableFrequencyDrives(VFD)intoaneworexistingEtherNet/IPnetwork,specificallyRockwellAutomation(RA)ProgrammableLogicControllers(PLC).EtherNet/IP(EIP)isbeingusedinawiderangeofindustriesandisoneofthefastestgrowingindustrialprotocolsintheUnitedStates.EtherNet/IPisanopensourceimplementation,thusallowingforthecontinuousdevelopmentandsupportfromindustryleaders(suchasYaskawa),ensuringthatthisindustrialapplicationlayerprotocolsupportsustainability.

InstructionsandexampleswillbebasedonYaskawaTagGenerator,Yaskawaadd-oninstructions,RSLINX,andaCompact/ControlLogix™PLCplatform,configuredwiththeRSLogix5000orStudio5000(RS5K)softwareenvironment.Thisguidewillnavigate,configureandexplorethefunctionalityofYaskawaTagGenerator.

TheYaskawaTagGeneratorwasdevelopedtoallowtechniciansandengineerstoselectmultipleYaskawaEtherNet/IPproducts,theirfunctions(pre-definedI/Oassemblies),andthenoutputthecompileddatatoaCommaSeparatedValue(CSV)file.OnceimportedintotheRS5Kenvironment,thesetagsarethenaliasedtogenerictagscreatedwhenaddingtheYaskawamodule[s],thussimplifyingintegrationandreducingcommissioningtime.

USE OF THIS INFORMATION/

DOCUMENTATIONNothinginthisdocumentoranyinformationordataderivedfromthisdocumentmaybepublished,distributedorcopied,normaytheinformationordatabeusedtocreatederivativeworks.Nouserofthisinformationordatamayalloworenableotherstoreverseengineer,decompile,disassembleorotherwiseattempttoreconstruct,identifyordiscoveranycode,underlyingideas,techniques,oralgorithmsfromthisinformation.Noconfidentialinformationorproprietaryrightsordatamayberemoved,obscuredoraltered.

AllproprietaryandownershiprightsbelongingtoEECOshallremainwithEECO,andnothinginthisdocumentshallrelinquishsuchrights,titleorinterest.

INDEMNIFICATION EECOshallbeindemnifiedandheldharmlessfromanyandallclaims,damages,lossesand/orexpenses,includingreasonableattorney’sfeesarisingfromanybreachofthisagreementortheuser’sobligationshereunder.

Page 5: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks5

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

WARRANTY DISCLAIMERThisdocumentistobeused“AsIs”withoutwarrantyofanykind.EECO,onbehalfofitselfandanyaffiliates,herebydisclaimsallrepresentations,promisesorwarranties,whetherexpressorimpliedwithrespecttotheinformationcontainedherein.EECOspecificallydisclaimsallimpliedwarrantiesormerchantability,non-infringement,suitabilityandfitnessforanypurpose.

PRE-REQUISITE SKILLS

Thisdocumentiswrittenandintendedfortechniciansandengineerswhowillbecommissioningand/orsupportingYaskawaVFD[s]ontheplantfloor.Theintendedusersshouldunderstand,attheveryleast,navigationthroughtheRS5Ksoftwareenvironment.

REQUIRED HARDWARE/SOFTWARE1. YaskawaVFDwithOptionalCommunicationCard-

(CIMR-VU2A0001FAA-V1000withtheSI-EN3/Vinourcase)

2. PCwithRSLINXandRS5K

3. RockwellLogixPLC(1756-L71ControlLogixinourcase)

* Note: All Yaskawa EDS files and software may be downloaded from

Yaskawa.com via links provided in the Appendices.

COMMUNICATIONVFD COMM METHODS

InitialconnectiontotheYaskawaVFDcanbeaccomplishedinacoupleofways:

1. DirectconnectviaPLCtoVFD

2. CommonSwitchorRouterConnectviaportsonthesameswitch

3. Networkconnectionviamultipleswitchesand/orwireless access points

VFD DEFAULT CONFIGURATION AND PREPARATIONS

OpenDeviceNetVendorAssociation(ODVA),thegoverningbodyofEtherNet/IP,whichspecifiesthatallEIPsupportingdevices,includingYaskawaVFD,bydefaultmustbesettouseDynamicHostControllerProtocol(DHCP)togetthenetworksettings.

ThiscorrespondingrequirementisreflectedinparameterF7-13(AddressModeatStartup:2bydefault).IfaDHCPserverdoesnotexistwithinthenetworktopology,proceedtochangethenetworksettingsmanuallytoastaticsetting.

UsingthekeypadorDriveWizardIndustrialsoftware,theoptioncard’snetworksettings(IPAddress,SubnetMaskandDefaultGateway)canbeconfiguredundertheF7parameters.AdditionalUserSettingTableinformationcanbefoundwithintheYaskawaACDriveTechnicalManual–SIEPC71060618:E.3-page491.

Page 6: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks6

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA VFD NETWORK PARAMETERS:

• F7-01EthernetIPAddress1—192

• F7-02EthernetIPAddress2—168

• F7-03EthernetIPAddress3—1

• F7-04EthernetIPAddress4—1-254

• F7-05SubnetMask1—255

• F7-06SubnetMask2—255

• F7-07SubnetMask3—255

• F7-08SubnetMask4—0

• F7-09GatewayAddress1—192

• F7-10GatewayAddress2—168

• F7-11GatewayAddress3—1

• F7-12GatewayAddress4—1

• F7-13AddressModeatStartup—0from2to becomestatic,thencyclepower.

Toconfirmnetworksettingsafterthepowercycle,wecanverifythesettingsundertheMonitorparametersU6-80toU6-91.Valuesarepresetiftheoptioncardhasaconnectiontoanotherdevice.

ThenetworkLED(NS)shouldnowtransitiontoasolidgreenstate.

ENABLE COMM CONTROLS CONFIGURATION

Thefollowingparametersmustbechangedtoenablefieldbuscontrols.

• B1-01to3:OptionPCB(FrequencyReferenceSelection1)Defaultis=1AnalogInput

• B1-02to3:OptionPCB(RunCommandSelection1)Defaultis=1DigitalInput

*New values will accept immediately without a Power Cycle

PC CONFIGURATION

1. Open Network and Sharing CenterfromthetaskbarorunderControlPanel.

2. IfnoconnectionispresentonyourPCnetworkport(RJ45),selectchange adapter settingsontheleftsidebar.

3. Double click Local Area Connection,thenproperties,and double click on (TCP/IPv4)

4. ConfigurethePC’sstaticnetworksettingsbyselecting“Use the following IP Address:”

5. Inputanunused IP AddressthatisonthesamesubnetaspreviouslymentionedintheVFDconfiguredoption.

6. InputthesameSubnet mask and Default Gateway as previouslyusedintheVFDconfiguration.

7. Select OK and OKagainontheLocalAreaConnectionPropertieswindowandthesettingsareready.

Page 7: Integration into EtherNet /IP Networks

ROCKWELLAUTOMATIONENVIORNMENTSRSLINX

Page 8: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks8

Beginningwithv20 of RS5K,thismaybeaccomplishedwithotheradditionaloptionswithintheenvironmentundertheTools Menu.

Let’sstartoffbyregisteringtheEATONEDSfilesintoRSLINXwiththeEDSWizard.

OpenthestartmenuandunderRSLINX

STEP 1: SelecttheEDS Hardware Installation Tool

STEP 2: Select add

Page 9: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks9

SelectwhetheryouwouldliketoregisterasingleoradirectoryofEDSfiles.Ifthelatter,pleasetickLook in subfoldersaswell.

STEP 3: Browsetothefolderdirectorycontainingthe EDS[s]

STEP 4: Click next

Thesystemwilldoascanandpopulate a test result.

STEP 5: Selectthedesiredfile[s]toregister

STEP 6: Click next

Page 10: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks10

Change the iconsifneeded

STEP 7: Click next

Afinaltasksummarywindowwillappear.Ensure the information is correct.

STEP 8: Click nexttocompletetheEDSregistration process

Page 11: Integration into EtherNet /IP Networks

STUDIO5000 PART 1

Page 12: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks12

STEP 5: Selectthechassis type

STEP 6: Click finish

STEP 1: Open or createanewprojectinRS5K.

Ifstartinganewproject-

STEP 2: Selecttheprocessorandnameyourproject

STEP 3: Browsetothedesiredprojectsavelocation

STEP 4: Click next

Page 13: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks13

IntheControllerOrganizer-

STEP 7: Right clicktheprocessorBackplane (slot0)

STEP 8: Create a newEthernetmodule.

Forthisexample,the1756-EN2Twillbeused.Clickcreate

STEP 9: Name the EN2TandinputanunusedIP Address(192.168.0.2)

STEP 10: Click OK

AnEN2Tmodule(slot1)nowexistsundertheBackplane.

Page 14: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks14

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

A Yaskawa V1000 VFD will be added to the RS5K project.

STEP 11: Rightclickonthe1756-EN2T module and select create new module

TheSelectModuleTypewindowappears.ToentertheV1000asaGenericEthernetModule-

STEP 12: Deselect both filtersforCategoryandVendor

STEP 13: SelectonlyCommunication and Allen Bradley

STEP 14: Scrolldowntowardthebottomof thelistandselect ETHERNET-MODULE Generic Ethernet Module

STEP 15: Click create

STEP 16: Anewmodulewindowappears

Page 15: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks15

STEP 17: Inputanamethatisdistinctiveyetsimple (V1000) as you will need to reuse this identical name in the Tag Generator Software

STEP 18: ChangetheCommFormatfromDINT >> INT

STEP 19: InputanunusedIPAddress(192.168.0.100) thatisonthesamesubnetastheEN2T,i.e. 192.168.0.x.{x=2-254}.

STEP 20: Input 71fortheInputAssemblyInstance, size = 2 bytes (INT) (pg. 41 in TOBPC73060092 Manual)

STEP 21: Input 21fortheOutputAssemblyInstance, size= 2 bytes (INT) (pg. 41 in TOBPC73060092 Manual)

STEP 22: Configurationassemblyisnotused,butthere mustbeavaluethereasaplaceholdersoinput 1 for ConfigurationAssemblyInstance,size = 0

Page 16: Integration into EtherNet /IP Networks

YASKAWATAG GENERATOR

Page 17: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks17

STEP 1: InstallYaskawaTagGenerator.Onceinstalled,startthe programbydouble clicking the icon

STEP 2: ClickNewProjectinthetopmenu.

Thenewprojectwindowwillpopupandaskwhichsoftwaredoyouwanttocreatetagsfor.

STEP 3: TickLogix Designer/RSLogix 5000

STEP 4: Enter a project name and click New Project to create theproject.

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

Page 18: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks18

Oncetheprojectiscreated,selectwhichfirmwareisrunningonthePLC.

STEP 5: Click Add New Node

STEP 6: SelecttheOption Cardonthenextwindow

STEP 7: Click next

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

Page 19: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks19

STEP 8: SelecttheI/OAssemblypairthatwasused intheRS5Kproject(21-71)

STEP 9: DeletetheScopefieldtomakethetags accessibleglobally;otherwise,theywillonly beavailableinMainProgram

STEP 10: Enteranodename,V1000inthiscase

*(MUST BE AN IDENTICAL NAME USED IN RS5K).

STEP 11: Click finish

Page 20: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks20

STEP 12: Click Change Output Fileandbrowsetoafile locationtosavetheCSVoutputfile

STEP 13: Name CSVfile

STEP 14: Click save

Page 21: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks21

STEP 15: Click Build Tag Listtogenerate

STEP 16: Click OKinthenotificationpop-up

Page 22: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks22

STEP 17: Provide a namefortheprojectinthepop- up window

STEP 18: Click Save

STEP 19: Theprojectmaynowbeaccessedatalater timeformodificaton.

STEP 20: Click Quitandthetaskiscompleted.

TheremainingtaskwillbecompletedintheRS5Kenvironment.

STEP 16: Click Save Project As

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

Page 23: Integration into EtherNet /IP Networks

STUDIO5000PART 2

Page 24: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks24

NavigatebacktotheRS5Kenvironment-

STEP 1: GototheTools Menu > Import > Tags and Logic Comments

STEP 2: BrowsetothepreviouslysavedCSVfolderlocation,select, and import

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

Page 25: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks25

Oncetheimporttaskiscompleted,youwillnoticethatthelowerErrorplaneprovidesfeedbackonhowmanytagswerecreated,inadditiontoanyerrorsandwarnings.

*If there are error[s], ensure that the names specified in the RS5K project and Yaskawa Tag Generator were identical, or re-run Tag Generator with the correct nomenclature.

AlsonoticethatthedescriptioncolumnisnowautomaticallypopulatedfromtheTagGeneratorgeneratedCSV.WhenEditTagsisselected,RS5Kwillalsoshowexactlywherethenewtagsarealiastointhegenerictags.ThefunctionalitiesoftheTagGeneratortoolgreatlycontributetothereductionofsetuporcommissioningtime,ultimatelyreducingdowntimeandincreasingproductivity.The import task is now completed.

Page 26: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks26

YaskawahastakenadditionalstepstosimplifyingintegrationofitsEtherNet/IPsupportedproductsbyofferingawiderangeofVFDAdd-OnInstruction(AOI)inconjunctionwithTagGenerator.Let’sproceedandexplorehowtechniciansandengineerscanuseYaskawa’sAOIs.

InRS5K-

STEP 3: NavigatetoFile > Import Component > Add-On Instruction

STEP 4: BrowsetotheAOI provided by Yaskawa

TheextensionofthefilewillbeaL5X.

STEP 5: YAI Assembly 71 21 is selected

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

Page 27: Integration into EtherNet /IP Networks

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA Integration into EtherNet/IP Networks27

TheImportConfigurationwindowappears.

STEP 6: Verify and select OK

STEP 7: IntheController Organizer > Add- On Instruction,theAOIhasbeensuccessfully imported and is now available for use in the Language Element Tool Bar > Add-On

Page 28: Integration into EtherNet /IP Networks

UTILIZINGTHE AOI

Page 29: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks29

STEP 1: Next,openMainProgram–MainRoutine

STEP 2: Add a rung

STEP 3: TheninAdd-On,dragtheV1000AOItotherung0

OncetheV1000AOIblockisaddedtotherung,thetopthreeparametersintheAOIblockmustbemappedtoaspecificmodule

WithintheAOIblock-

STEP 4: Doubleclickthetop “?” nexttotheViewConfiguration Dialogbutton

STEP 5: InputV1000 > right click > select “New V1000”

STEP 6: AnewParameterorTagwindowwillappear

STEP 7: Confirmthenameandscope

STEP 8: Click create

Ensure that the Controller Tags and MainProgram windows are open and side-by-side.

STEP 9: SelectanddragV1000:I1 to the “?”intheNode_Input_ Assyrow

STEP 10: SelectanddragV1000:O1 to the “?”intheNode_ Output_Assyrow

ThesetupoftheAOIisnowcomplete.

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

Page 30: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks30

Let’screateaDINT tag —

STEP 11: NameitInput_Output.

TheBooleanwithintheDINTwillbeusedaslogicalPushButtons.

STEP 12: Add a couple of rungstothe project

STEP 13: Enable remote FieldBus control oftheV1000bylatchingthe V1000_NetCtrl and V1000_NetRef bit

ToensurethatthePLChascontrolafterapowerloss,aFirstScanbitisusedforlatchingonapower-upcondition.

STEP 14: Addastart,stop and fault logictotheprogram,

STEP 15: Downloadtotheprocessor

The V1000 VFD is ready to be operated.

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

Page 31: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networks31

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

MOTOR TESTING

• Page42ofTOBPC73060092

SPEED REFERENCE

• Speed Command

• Setsdrivespeedreference

• Speedreferencedata: Frequency reference/2SS (SS: Speed scale)

• Settingrange:0to0xFFFF

• Example:settingareferenceof4096withaspeedscaleof2: Speed reference data = 4096/22 = 1024 = 0x0400 Hex or 10.24 Hz

• Unitdependsono1-03

Page 32: Integration into EtherNet /IP Networks

APPENDICESA, B, C

Page 33: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networksa

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA RESOURCE DOWNLOADS LINKS

YASKAWA DOWNLOADS

https://www.YASKAWA.com/downloads

DRIVEWIZARD INDUSTRIAL

https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/drivewizard-industrial

ETHERNET/IP

https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-network-communication-protocols/ethernet-ip

YASKAWA NETWORK SUPPORT FILES - DOWNLOADS

https://www.YASKAWA.com/downloads?p_p_id=yasdocumentdownload_WAR_yasdocumentdownloadportlet&p_p_lifecycle=0&p_p_state=normal&p_p_mode=view&p_p_col_id=column1&p_p_col_count=1&_yasdocumentdownload_WAR_yasdocumentdownloadportlet_productGroup=Inverter+Drives&_yasdocumentdownload_WAR_yasdocumentdownloadportlet_productLine=Network+Comms-EtherNet-IP

CONFIGURED PRODUCT FOR A1000

DRIVE

https://www.YASKAWA.com/products/drives/industrial-ac-drives/general-purpose-drives/a1000-configured

U1000 INDUSTRIAL MATRIX DRIVE

https://www.YASKAWA.com/products/drives/industrial-ac-drives/general-purpose-drives/u1000-industrial-matrix-drive

G7 DRIVE

https://www.YASKAWA.com/products/drives/industrial-ac-drives/general-purpose-drives/g7-drive

G7 CONFIGURED

https://www.YASKAWA.com/products/drives/industrial-ac-drives/general-purpose-drives/g7-configured

DRIVEWORKS EZ SOFTWARE

https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/driveworks-ez-software

PROGRAMMING SIMULATOR

https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/programming-simulator

ENERGY SAVINGS PREDICTOR

https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/energy-

savings-predictor

HARMONICS ESTIMATOR

https://www.YASKAWA.com/products/drives/industrial-ac-drives/industrial-software-tools/harmonics-estimator

APPLICATION EXAMPLES

https://www.YASKAWA.com/downloads?p_p_id=yasdocumentdownload_WAR_yasdocumentdownloadportlet&p_p_lifecycle=0&p_p_state=normal&p_p_mode=view&p_p_col_id=column1&p_p_col_count=1&_yasdocumentdownload_WAR_yasdocumentdownloadportlet_lookupType=Software%2FApplication+Examples

TRAINING DOCUMENTS

https://www.YASKAWA.com/downloads?p_p_id=yasdocumentdownload_WAR_yasdocumentdownloadportlet&p_p_lifecycle=0&p_p_state=normal&p_p_mode=view&p_p_col_id=column1&p_p_col_count=1&_yasdocumentdownload_WAR_yasdocumentdownloadportlet_lookupType=Training+Documents

TRAINING: DRIVEWIZARD INDUSTRIAL

TIPS AND TRICKS

https://www.youtube.com/playlist?list=PLNAENlyEDCkxPasi-q_UbSCyqaU7Ryy0v

Page 34: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networksb

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

YASKAWA SUPPORTED DRIVE PRODUCT SERIES

A1000

D1000

iQpump1000

MV1000

P1000

R1000

V1000

V1000-4X

U1000IndustrialMatrix

U1000Oil&Gas

F7

G7

Page 35: Integration into EtherNet /IP Networks

YASKAWA Integration into EtherNet/IP Networksc

EECO | 1440 Diggs Dr. Raleigh, NC 27603 | 919-828-5411 | www.eecoonline.com

DIRECT CONNECT SERIAL PIN OUT

ApplicabletotheA1000,J1000,V1000,V1000-4X,J7,V7,E7,P7,G5,G7,andF7Drives

(Courtesy of YASKAWA)