insulation coordination
TRANSCRIPT
-
5/28/2018 Insulation Coordination
1/11
1
Insulation Coordination
Insulation coordination consists of selecting insulation of various lines and equipment
that have to be interconnected into a system for desired operational requirement. The
system must be reliable and economical.
In high lightning-prone areas or in systems with heavy switching-surge conditions, the
selection of insulation levels will be different from areas with little or no lightning and
with shorter lines.
Normally, insulation systems are designed in a system for no flashovers, or if flashovers
cannot be prevented such flashovers should be restricted to places where damage is not
done, such as air gaps or in gap-type arresters. The flash-over should not disturb normal
system operation and must occur in resalable insulation structures. The over voltages that
can cause damage are due to external origin, namely lightning, and operation of thesystem itself which are at power frequency, earth faults, and switching operations. We
will consider here the insulation co-ordination principles based on lightning. These
insulation levels are known as Basic Impulse Insulation Levels or BIL. Those based on
switching-surge requirements are known as Switching Impulse Levels or SIL.
The lightning arrester is the foundation of protection in e.h.v. ranges, which is selected
for both lightning and switching-surge duty. It is usually of the magnetic blow-out
(current limiting) gap type, or in recent years the gapless ZnO type.
Insulation Coordination:
The process of bringing the insulation strengths of electrical equipment and buses intothe proper relationship with expected over voltages and with the characteristics of the
insulating media and surge protective devices to obtain an acceptable risk of failure.Insulation coordination means the correlation of the insulation of the various
equipments in a power system to the insulation of the protective devices used for the
protection of those equipments against over voltages. In a power system various
equipments like transformers, circuit breakers, bus supports etc. have different
breakdown voltages and hence the volt-time characteristics. In order that all theequipments should be properly protected it is desired that the insulation of the various
protective devices must be properly coordinated.
The basic concept of insulation coordination is illustrated in Fig. 7.27. Curve A is thevolt-time curve of the protective device and B the volt-time curve of the equipment to be
protected. Fig. 7.27 shows the desired positions of the volt-time curves of the protecting
device and the equipment to be protected. Thus, any insulation having a withstandvoltage strength in excess of the insulation strength of curve B is protected by the
protective device of curve A.
-
5/28/2018 Insulation Coordination
2/11
2
Insulation withstand capacity of any equipment must be higher than the maximumpossible over voltage.
Whatever the insulation withstand of a line, it is not 100% reliable.
Insulation Coordination defines the overvoltage stress and insulation requirementfrom equipment to equipment basis.
It also rates timing coordination and nature of o/v.Basic lightning impulse insulation level (BIL):
The electrical strength of insulation expressed in terms of the crest value of a standardlightning impulse under standard atmospheric conditions.
Basic switching impulse insulation level (BSL):
The electrical strength of insulation expressed in terms of the crest value of a standardswitching impulse.
Necessity of Insulation Coordination:
To ensure the reliability & continuity of service To minimize the number of failures due to over voltages To minimize the cost of design, installation and operation
Requirements of Protective Devices:
Should not usually flash over for power frequency over voltages Volt-time characteristics of the device must lie below the withstandvoltage of the protected apparatus Should be capable of discharging high energies in surges & recover
insulation strength quickly
Should not allow power frequency follow-on current.
-
5/28/2018 Insulation Coordination
3/11
3
Volt-Time Curve
The breakdown voltage for a particular insulation of flashover voltage for a gap isa function of both the magnitude of voltage and the time of application of the
voltage.
Volt-time curve is a graph showing the relation between the crest flashovervoltages and the time to flashover for a series of impulse applications of a given
wave shape.
Construction of Volt-Time Curve:
o Waves of the same shape but of different peak values are applied to theinsulation whose volt-time curve is required.
o If flashover occurs on the front of the wave, the flashover point gives onepoint on the volt-time curve.
o The other possibility is that the flashover occurs just at the peak value ofthe wave; this gives another point on the V-T curve.
o The third possibility is that the flashover occurs on the tail side of thewave.
To find the point on the V-T curve, draw a horizontal line from the peak value ofthis wave and also draw a vertical line passing through the point where the
flashover takes place
The intersection of the horizontal and vertical lines gives the point on the V-Tcurve.
-
5/28/2018 Insulation Coordination
4/11
4
Insulation Coordination for L.A(Lightning Arrester)
L.A. plays a major role in insulation coordination L.A. is not used for power frequency o/v, but used for transient o/v Rated voltage of L.A. is maximum temporary o/v (rms)
-
5/28/2018 Insulation Coordination
5/11
5
Temporary over voltage
VT(rms) = 0.8 x 3 x Vphase
= 1.38 x Vphase
For L.A.:
Temporary o/v is taken as 1pu Switching o/v is taken as 1.6 times of temporary o/v Impulse o/v is taken as 1.8 times of temporary o/v
BIL of L.A.>=Vb
>=VT(rms) x 2 x 1.8 x Margin
(LA)BIL
(min)= VT(rms)x 2 x 1.8 x Margin
(LA)BIL (min)/(LA rating)= 2x1.8x1.15
=2.9217
=Protective Ratio(PR)
Protective ratio may vary from 2.75 t0 3.5
-
5/28/2018 Insulation Coordination
6/11
6
If PR is less than 2.75, L.A. may operates at temporary overvoltages.
If PR is higher than 2.75 LA may operate for impulse overvoltages that means equipment
insulation level is increased generally which is most costly.
Insulation Coordination for Transformer
Insulation of Transformer is kept slightly greater than L.A.
BIL of Transformer = TPR x BIL of L.A.
TPR : Transformer Protection Ratio
Discharge current through L.A.
The lightning current passing through the arrester material is calculated as follows:Consider a travelling wave of voltage Vw, crest, which is accompanied by a current wave
Ion a line with surge impedance Z, Fig. 9.11. They strike an arrester whose duty is to
hold the voltage across it constant at the protective level V. Now, by using Thevenin'stheorem, with the arrester terminals open, the incident travelling wave will give a voltage
2Vpdue to total reflection. The Thevenin's impedance looking through the open arrester
terminals is equal to the surge impedanceZof the line.
-
5/28/2018 Insulation Coordination
7/11
7
Therefore, with the arrester connected, the current through it will be
Ia= (2VwV)/ZThe maximum value the travelling-wave voltage Vpcan reach is the flashover voltage of
the line insulation. Also, it is assumed that Vpstays fairly constant at all current values
discharged by the arrester.
Example :For a 750 kV line, take Vw= 3000 kV, crest, travelling on the line and V
=1700kV. The line surge impedance is Z = 300 ohms. Calculate and discuss (a) thecurrent flowing in the line before reaching the arrester, (b) the current through the
arrester, and (c) the value of arrester resistance for this condition and verify the reflection
and refraction coefficients giving rise to the voltage and current conditions.
Solution.(a)Iw= Vw/Z= 3000/300 = 10 kiloamperes.(b)
Ia=(2Vw -V)/2Z= (60001700)/300 = 14.33 kA.
(c)The reflected current in the line is + 4.33 kA.
This gives rise to a reflected voltage of 4.33 300 = 1300 kV. Under theseconditions, the arrester resistance is
Ra= Vp/Ia= 1700 kV/14.33 kA=118.6 ohms. (120 is taken ohms).
-
5/28/2018 Insulation Coordination
8/11
8
Example: For the above example , if an 80% arrester is used, calculate the protective
ratioNp= Vp/V.
.
Solution.For rated line-to-line voltage of 750 kV, arrester rating is
Va= 0.8 750 = 600 kV (R.M.S.).
Protective ratioNp= 1700/600 = 2.83.
Voltage Across Equipment Protected by ArresterIn the ideal case, the arrester must be located adjacent to the equipment which is usually a
large transformer or shunt reactor. In practice, however, there may be a length of the linebetween the two extending to 20 to 40 meters. This results in a slightly higher voltage
across the equipment due to repeated reflections. The high inductance of a transformer or
reactor represents nearly an open-circuit to a surge. The excess voltage experienced is
given by an empirical equation and depends on the line length and the rate of rise of thevoltage, thus:
V= (dVw/dt). (l/150) kV
Where l= length of line in meters anddVw /dt= steepness of wave front in kV/ms of the incoming wave. This can be taken as
approximately 500 kV/ms for lines with overhead ground wiresand 1000 kV/ms when a
line conductor is hit.(A line without earth wires).
Example .A transformer is connected by a length of 20 meters of line to an arrester.
The rate of rise of voltage is 700 kV/microsecond. The arrester voltage is 1700 kV.
Calculate the voltage across the transformer.
Solution.V= (700) (20/150) = 93 kV.Transformer voltage = 1700+93 kV=1793 kV, impulse crest.
Very important Numerical:
For 400 kV line having effectively grounded system with L.A. of protection ratio 3.
L.A. is put 30 m from transformer and transformer protection ratio is 1.25, surge
impedance Zc=350 . Lightning current equals to 10 kA at an arrester with peak
time of 1 s. Check whether the transformer insulation is properly co-ordinated
with the arrester or not. If not, also find maximum possible separation between
Transformer & L.A. for proper co-ordination.
-
5/28/2018 Insulation Coordination
9/11
9
Solution:
Temporary o/v=400*0.8*1.05=336kV=LA rating
BIL of L.A. Va =PR x LA rating=3*336 kV=1008kV
BIL of Transformer =TPR x BIL of L.A. =1.25*1008 kV=1260kV
Excess voltage experienced in protected device
V=(dv/dt)*(l/150)=(di/dt)*Zc*(l/150)=700kV
Vb=Va + V=1008 kV+700 kV=1708kV
Here BIL of transformer is less than the voltage experienced by it Vb= 1708 kV
thats why it is not properly co-ordinated.
Now boundary condition for proper co-ordination is
BIL of transformer= voltage experienced by it
Vb=1260 kV
Va +(dv/dt)*(l/150)=1260
1008+(di/dt)*Zc*(l/150)=1260
(di/dt)*Zc*(l/150)=252
10*350*(l/150)=252
Therefore l=10.8 m is the maximum possible separation between L.A and transformer forproper co-ordination. Also for safe operation distance should be less than 10.8 m for safe
operation.
-
5/28/2018 Insulation Coordination
10/11
10
Example:
In 132 kV transmission line having Zc= 400, effectively grounded system, the
proposed L.A. has the following specification:
Residual voltage Option1 Option2At discharging current 0f 10 kA 300 kV 300 kV
At discharging current 0f 20 kA 360 kV 320 kV
Residual voltage: voltage across LA when discharging current flows
i. Compute BIL withstand voltage if maximum current that could strike atthe arrester is 20 kA and 50 kA
ii. Compute the lightning maximum permissible over voltage if themaximum residual voltage of a arrester is to be limited to that of 20 kA
discharge current.
Solution:
Arrester current I=
For lightning arrester:
Residual voltage V=
For option 1:
300= k10x
360= k20x
Solving we get,
x=0.263
k=163.727
Therefore V=163.727 I0,263
For 20 kA lightning current discharge current of L.A.
L.A. withstand capacity = kIx= 163.727 * 38.10.263=429.366 kV
For 50 kA discharge current
Va=163.727 * 500.263= 458.05 kV
-
5/28/2018 Insulation Coordination
11/11
11
BIL of LA= 163.727 * 98.8550.263= 547.987 k
Do same for option 2[ ans: for 20kA, Va=340.512 kV, for 50 kA Va= 371.22 kV]
(ii)I=
Option 1: 20=
V=4180 kV
Option 2:
V=4160 kV