instrument transformers 6.0...
TRANSCRIPT
155
CHAPTER 6
MODELLING AND ANALYSIS OF TRANSIENTS IN
INSTRUMENT TRANSFORMERS
6.0 INTRODUCTION:
The most adopted modeling of GIS components, to simulate Very
Fast Transients by digital program, make use of electrical equivalent
circuits composed of lumped elements (of capacitances, inductances and
resistances) and distributed parameter lines derived from their surge
impedances and travel times. The disconnector spark itself has to be
taken into account by a transient spark resistance and a subsequent arc
resistance of a few ohms. Dielectric losses in some components such as
bushing need to be taken into account because of very high frequencies.
From the point of view of the overall integrity of the GIS, it is
important to assess the over voltages set up not only locally but also at
various other points remote from the disconnector. In view of the
electrical and physical complexity of the substation layout, it is essential
to verify that the over voltages are unlikely to overstress the dielectric
medium. Therefore the entire mesh of the substation and the various
installations involved such as generator transformers, inter bus
transformers, SF6/Oil bushings, isolators, cable/overhead line
connections etc., and should be considered for analysis. Generally a
disconnector is provided in each arm of a circuit breaker. Enclosures are
arranged in several levels in a complex layout resulting in a large number
156
reflections and a model of study should take care of the physical
arrangements as closely as possible. Calculation of over voltages is by no
means easy because of the number of busbar sections and cables having
distributed parameters where as generators, transformers and capacitors
are considered as lumped elements. The method employed to calculate
must satisfactorily represent both lumped and distributed parameter, the
popular method used being the Bewley lattice method.
6.1 MODELLING CONCEPT
In the present work, modelling and analysis are confined to a
section of the GIS bay illustrated in Figure 6.4. The section chosen
consists of an air/SF6 bushing (through which an external circuit such
as a transmission line is connected), insulating spacers, disconnector
switch module and a busbar of 10 meters length. Fast transient
overvoltage wave forms generated during a closing operation of
disconnector have been considered for calculation.
All the distributed parameter lines are considered in the internal
mode (conductor-enclosure) only and the external enclosure is
considered to be perfectly earthed. At high frequencies earth connections
assume significant impedance values and this mode has not been
considered.
The insulating spacers used in this GIS are cone type insulators
supporting the inner conductor against the outer enclosure. These are
assumed to be disc type for approximate calculations of spacer
157
capacitance which comes out to a value of 3.07pF. Three spacers per
meter length have been considered.
The coaxial bus duct used is modeled as a series of pi – networks.
The inductance of bus duct is calculated from the diameters of the
conductor and enclosure. Capacitances are calculated on the basis of
actual diameters of inner and outer cylinder of central copper conductor
and outer enclosure.
The schematic diagram of the GIS section considered is shown in Figure
6.1.
Fig 6.1 The schematic diagram of the GIS section
The capacitance on the source side (sum of the capacitances of SF6
– air bushing and capacitance of the transformer) is assumed as 2000
Pico Farads and used in the calculation. Spark resistance is simulated
by a constant value of 2 ohms.
Any desired configuration is represented by an equivalent circuit of
the main components of the GIS after calculation of the parameters. A
trapped charge is assumed to be left on the floating section of the
158
switchgear due to a previous opening operation of the disconnector or
circuit breaker. This is simulated by a voltage of certain value on the
bus on one side of the switch. This is the most severe situation during
switching with a voltage collapse of 2 p.u. This pessimistic condition will
result in the maximum overvoltage for a particular configuration.
Therefore this simulation will ascertain the maximum value of the over
voltages in the particular GIS section due to the closing of a
disconnector. For a specific GIS section, in the parameters such as the
load side capacitance, length of load side busbar, source side
capacitance and length of source side busbar etc. decide the peak value
of over voltages.
6.2 CALCULATION OF R, L AND C:6.2.1 Calculation of Resistance:
When DC current flows through conductor, there will be uniform
distribution of current. Burt when AC current flows through it, a non-
uniform distribution occurs, i.e., more current concentrates on the
surface. Due to this there is a slight increase in resistance.
R = x L
A
The average value of resistance = 238.46 μΩ/ m
= 0.238 mΩ/m
The calculated value of specific resistances is 1.3189 X 10–8 Ω–m
159
6.2.2 Calculation of Inductance
The coaxial inner and outer conductors of a coaxial GIS are shown in
Figure 6.2.and the corresponding values are 260 mm and 80 mm
respectively.
Fig 6.2 Cross section of a typical GIS system
The calculated value of inductance is 0.2295 μH per meter of bus length.
6.2.3 Calculation of Capacitance6.2.3.1 Capacitance of Bus Duct
The capacitance is calculated with the assumption that the
conductors are cylindrical and calculated.
The calculated value of capacitance is 51.22 Pico Farads per meter.
6.2.3.2 Spacer Capacitance CalculationSpacers are used for supporting the inner conductor with reference
to the outer enclosure. They are made with Alumina filled epoxy material
whose relative permittivity is 4. The thickness of the space is assumed to
be the length of the capacitance for calculation.
By using the above formula the spacer capacitance calculation is as
follows.
Capacitance of each spacer = 51.22x0.015x4=3.073pF
Assume three spacers per meter length.
Total capacitance of GIS bus per meter length is calculated as follows
160
= 51.22+3x3.073=60.44pF/meter.
The completed 123KV GIS configuration is shown in figure 6.3,
in which the experiments were carried out the analyzed GIS, enables the
realization of triple busbar system with corresponding bypass.
Fig 6.3 The completed 123 KV GIS configuration
Each bus bar system consists of three phases in one encapsulation.
The basic electric circuit of this substation is shown in figure 6.4. The
analysis of the transients generated during disconnector switch
operations are performed for the line feeder bay = E15.The line feeder
E15 bay and its geometrical structure is shown in figure 6.4.
161
Fig 6.4 Figure of the analyzed line feeder bay = E15.
Z1 : Source Impedance
Q8, Q51, Q52 : Earth Switch
Q9 : Outgoing Disconnector
T5 : Potential Transformer
T1 : Current Transformer
Q0 : Switch Gear
Q1, Q2, Q3, Q70 : Busbar Disconnector
In order to predict the transient electromagnetic phenomena
in the secondary circuits of voltage (T5) and current (T1) transformers,
several network models of GIS – components and physical effects in the
GIS have been developed the help of the models available. The
simulations of transients in GIS due to disconnector operation have been
carried out.
162
6.2.3.3 The Arc – Model of the Disconnector Operations:
In view of the generation of transients in GIS, the disconnector
operation has been modeled with the help of the modified Kopplin model,
which describes the disconnector arc resistance. The resistance of the
arc-discharge represents a substantial part of the damping of the whole
GIS-system. Normally the resistance is a frequency dependent parameter
due to the skin effect. In the case of arc-discharge there exists a strong
time-dependency according to temperature, diameter and losses of the
discharge. Thus the time behaviour of the spark’s resistivity has to be
evaluated correctly. The time behaviour of the conductivity g(t) is mainly
influenced by the time dependent temperature function T(t) of the arc-
discharge. Both the functions are displayed below.
1/g. dg/dt = 1/g(t) (ui/p (g)-1) -----------6.1
T (g) = T0 (1-e-(g/g0)) ---------------------6.2
Where u = voltage and i = current
p = the power of the arc
T0= initial temperature of the arc
g0= initial conductivity of the arc
This description of the physical arc-discharge process is valid from the
beginning of the discharge up to its end.
163
6.3 MODELING OF GIS COMPONENTS
Due to the traveling nature of the transients the modeling of
GIS makes use of electrical equivalent circuits composed by lumped
elements and especially by distributed parameter lines defines by surge
impedances and traveling times. The equivalent circuits can be derived
from the manufacturer’s drawings and from the internal physical
arrangement.
The inner system, which consists of the high voltage bus duct
and the Inner surface of the encapsulation, has been represented
thoroughly by line sections modeled as transmission lines with
distributed parameters. The phases and their inter phase coupling have
been investigated by applying the cable constants subroutine and the
method of modal components. This method permits the Calculation of
each phase and its coupling to the other phases separately.
More complex detailed models of the current and voltage transformers,
adopted particularly due to the accuracy to be reached and the
frequencies of interest, have been shown below. The transients are
transmitted to the secondary lines of the GIS by stray capacitances
which result of the construction of the protection electrodes in the
transformers.
165
Table 6.1 Equivalent Circuit of Current Transformer
L1, L2, L3: The conductors of theCT inner system
Table 6.2 Equivalent Circuit of Potential Transformer
DFK: The Pressure Spring Contact.CK: Coupling CapacitorLM1, LM2: Conductors of theSecondary Circuit
165
Table 6.3 Equivalent Circuits Of the GIS Components
6.4 RESULTS AND DISCUSSIONS:
The simulations have been made for the analyzed bay = E15, the
busbar disconnectors Q1, Q2, Q3 and Q70, as well as the switchgear Q0
were switched off. The transients caused by closing operation of the
outgoing disconnector Q9 of the line feeder bay E15, have been
determined by applying the SIMULINK module of the MATLAB software
with the basic circuit of the line feeder bay E15, AC voltage source
applied 123kV, 50 Hz, with a source impedance (z1) of 10 micro henrys
considered. To make on/off the breaker with a specified timing, here the
timer is on at 2 micro Seconds and switched off at 4 micro Seconds. The
breaker (Q9) Resistance at on is 0.001ohm. The values of Q0, Q1 Q51
and open disconnector in the circuit considered as 50 Pico Farads. With
this basic circuit due to switching operation of Q9 breaker the transient
166
voltages at the secondary circuit of CT across the load terminals around
16 kV and across the PT was about 26kV.
By adding series line impedance (Z) 0.212 micro Henry and shunt
capacitance of Q2=Q3=50 Pico Farads in between the breaker Q9 and
Potential transformer and the length of the cable of the secondary circuitry
of CT/PT considered as 1meter only. Due to switching operation of Q9
breaker the transient voltages at the secondary circuit of CT across the
load terminals around 0.67 kV and across the PT was about 4.53 kV.
The transient voltages across the secondary circuit of C.T and P.T are
measured for the following cases
Fig 6.5 Basic circuit of the line feeder bay
167
6.5 Case 1: Analysis of VFTO’s across CT and PT for different ofthe Control circuit Cable:
In the basic circuit shown in figure 6.5, the length of control circuit
cable is varied to 1m, 5m and 10m respectively by keeping all other
values are fixed.
The source impedance =Z1=10 micro henrys.
Earth switch Q8 =Q51=Q52=1nano farads
Series impedance =Z=0.212 micro Henry
Shunt capacitance =Q2=Q3= 50 Pico Farads
6.5.1 Case (i) Analysis of VFTOs across CT and PT for Length ofthe control circuit Cable is 1 meters
For length of the cable 1 meter andLm1=Lm2=Lm3=Lm4=0.5
μH/1metre, the transient voltages across the load terminals of secondary
circuit of current transformer (CT) and the potential transformer (PT) is
0.69kV and 4.53 kV respectively as shown in figures 6.6 and 6.7
Fig 6.6 VFTO’s across secondary circuit of current transformer
168
Fig 6.7 VFTO’s across secondary circuit of potential transformer
6.5.2 Case (ii) Analysis of VFTOs across CT and PT for Length ofthe control circuit Cable is 5 meters
For the length of cable 5metres and the values of
Lm1=Lm2=Lm3=Lm4= 2.5 micro Henry /5 meters, then the transient
voltages across the load terminals of secondary circuit of current
transformer (CT) and the potential transformer (PT) is 2.84kV and 29.6
kV respectively as shown in figures 6.8 and 6.9.
Fig 6.8 VFTO’s across secondary circuit of current transformer
169
Fig 6.9 VFTOs across secondary circuit of potential transformer
6.5.3 Case (iii) Analysis of VFTOs across CT and PT for Length of theCable is 10 meters
For the length of cable 10 meters and the values of
Lm1=Lm2=Lm3=Lm4= 5 micro Henry /10 meters, then the transient
voltages across the load terminals of secondary circuit of current
transformer (CT) and the potential transformer (PT) is 5.90kV and 118.9
kV respectively as shown in figures 6.10 and 6.11
Fig 6.10 VFTO’s across secondary circuit of current transformer
170
Fig 6.11 VFTO’s across secondary circuit of potential transformer
As the length of the cable of the secondary circuitry of
CT/PT increases the transient voltages induced across the load terminals
of CT/PT also increased abnormally.
The VFTO’S across secondary circuit of CT & PT are estimated for
different lengths of control circuit cable and are shown in table 6.5
Table 6.4 Transient voltages across CT & PT for different cable lengths
S.No DescriptionTransient
voltages acrossCT
Transientvoltages across
PT1 Length of the control cable
=1 meter 0.67 kV 004.53 kV
2 Length of the control cable= 5 meters 2.84 kV 029.66 kV
3 Length of the control cable= 10 meters 5.90 kV 118.90 kV
6.6 CASE (2) Case (i): Analysis of VFTOs across CT and PT for fixedValue of high voltage capacitance (C1) and differentvalues of Winding Capacitance (C2) of the currenttransformer (CT).
The transient voltages across CT & PT are estimated for different
Values of winding capacitance (C2=300pF, 500pF and 700pF) and fixed
value of high voltage capacitance (C1=1pF) for 1meter length of control
171
circuit cable by keeping the other values remain constant in the modelled
circuit shown in figure 6.5.
Fig 6.12 VFTO’s across secondary circuit of current transformer
Fig 6.13 VFTOs across secondary circuit of potential transformer
From the above figures 6.12 and 6.13, it has been observed that the
transient voltages across the load terminals of the CT and PT are 0.67 kV
and 4.50 kV respectively for 1meter control circuit cable length. It means
by keeping the high voltage capacitance (C1) constant and changing the
value of winding capacitance (C2) will not affect the transient voltages in
the secondary circuit of the CT/PT across the load terminals.
172
6.6.1 Case (ii) Analysis of VFTO’s across CT and PT for differentValues of high voltage capacitance (C1) and fixedvalue of Winding Capacitance (C2) of the currenttransformer (CT).
The transient voltages across CT & PT are estimated for fixed
value of winding capacitance (C2=300pF ) and different values of high
voltage capacitance (C1=1pF,5pF and 10pF) for 1meter length of control
circuit cable by keeping the other values remain constant in the
modeling circuit shown in figure 6.5.
Fig 6.14 VFTOs across secondary circuit of Current transformer(c1=1pF, c2=300pF)
Fig 6.15 VFTOs across secondary circuit of Potential transformer(c1=1pF, c2=300pF)
173
Fig 6.16 VFTO’s across secondary circuit of Current transformer(c1=5pF, c2=300pF)
Fig 6.17 VFTO’s across secondary circuit of potential transformer(c1=5pF, c2=300pF)
Fig 6.18 VFTO’s across secondary circuit of Current transformer(c1=10pF, c2=300pF)
174
Fig 6.19 VFTO’s across secondary circuit of Potential transformer(c1=10pF, c2=300pF)
From the figures 6.14 to 6.19, it has been observed that the
transient voltages across the load terminals of the CT are 0.67 kV, 2.78
kV and 5.73 kV and the transient voltages across the load terminals of
the PT are 4.53 kV, 4.51 kV and 4.53 kV respectively for fixed value of
winding capacitance (C2=300pF) and different values of high voltage
capacitance (C1=1pF, 5pF and 10pF) for 1meter length of control circuit
cable.
That means by keeping the value of winding capacitance (C2)
constant and changing the high voltage capacitance (C1) will affect the
transient voltages in the secondary circuit of the CT across the load
terminals only.
175
Fig 6.20 VFTOs across secondary circuit of Current transformer(c1=1pF, c2=500pF)
Fig 6.21 VFTOs across secondary circuit of Potential transformer(c1=1pF, c2=500pF)
Fig 6.22 VFTOs across secondary circuit of Current transformer(c1=1pF, c2=700pF)
176
Fig 6.23 VFTOs across secondary circuit of potential transformer(c1=1pF, c2=700pF)
From the figures 6.20 to 6.23, it has been observed that the transient
voltages across the load terminals of the CT are 0.67 kV, and the
transient voltages across the load terminals of the PT are 4.54 kV
respectively for different values of winding capacitance (C2=300pF,
500pF and 700pF) and fixed value of high voltage capacitance (C1=1pF)
for 1meter length of control circuit cable.The transient voltages across
load terminals of CT and PT are calculated for fixed values of C1 by
varying C2 and vice –versa. The results are tabulated in table 6.6.
Table 6.5 Transient voltages across CT & PT for different values ofC1 and C2
S. No. Value of highvoltages cap. (C1)
Value ofwindingcap. (C2)
Transientvoltages
across (CT)
Transientvoltages
across (PT)1 1pF 300 pF 0.67 kV 4.53 kV2 1pF 500 PF 0.67 kV 4.54 kV3 1pF 700 PF 0.67 kV 4.54 kV4 1pF 300 PF 0.67 kV 4.53 kV5 5 pF 300 PF 2.78 kV 4.50 kV6 10 pF 300 PF 5.73 kV 4.53 kV
177
6.7 CASE (3): EFFECT OF BURDEN CT/PT
The transient voltages across CT & PT are estimated by varying
burden on secondary circuit of CT and for fixed value of burden on PT
and vice -versa in the modeling circuit shown in figure 6.5.
The length of the control cable is considered as 1 meter and the other
Values are Lm1=Lm2=Lm3=Lm4=0.5 micro Henry/meter, and
C1=1PF and C2=300 PF.
Fig 6.24 VFTOs across secondary circuit of current transformer
Fig 6.25 VFTOs across secondary circuit of potential transformer
178
Fig 6.26 VFTOs across secondary circuit of current transformer
Fig 6.27 VFTOs across secondary circuit of potential transformer
Fig 6.28 VFTOs across secondary circuit of potential transformer
Fig 6.29 VFTO’s across secondary circuit of potential transformer
179
From the figures 6.24 to 6.29, it has been observed that the transient
voltages across the load terminals of CT and PT are 0.67 kV and 4.53 kV
and are constant by changing CT secondary burden of load inductance
and load capacitance for fixed burden on PT.
Further, it is observed that the transient voltages across the load
terminals of CT and PT are 0.67 kV and 4.53 kV and are constant by
changing PT secondary burden of load inductance and load capacitance
for fixed burden on CT. All simulation results obtained for change of
burden on CT and PT are tabulated in table 6.6
So, the transient voltages across the load terminals of CT/PT are
constant even though the burden on CT/PT is increased.
6.6 Transient voltages across CT & PT for change in burden:
Table 6.6 Transient voltages across CT & PT for change in burden
S.No Burden ofCT
Burden ofPT
Transientvoltages across
CT
Transientvoltages
across PT1 LB=2.8μH
CB=20pFLB=170mHCB=600pF
0.67 kV 4.5 kV
2 LB=4 μHCB=30pF
LB=170mHCB=600pF
0.67 kV 4.5 kV
3 LB= μHCB=40pF
LB=170 mHCB=600pF
0.67 kV 4.5 kV
4 LB= μHCB=80pF
LB=170 mHCB=600pF
0.67 kV 4.5 kV
5 LB=15 μHCB=80pF
LB=300 mHCB=800pF
0.67 kV 4.5 kV
6 LB=15 μHCB= 80pF
LB=600 mHCB=1000pF
0.67 kV 4.5 kV
180
6.8 Case (4): Effect of length of the GIS Section between CurrentTransformer (CT) and potential Transformer (PT):
As the length of the GIS Section increases the series impedance also
increases and the shunt capacitance also considered accordingly
6.8.1 By adding one Pi-section as shown in figure 6.30 i.e. shuntcapacitance, and series inductance values are 50 pF, 0.212µHenry, respectively in between CT and PT.
The transient voltages across the load terminals of CT and PT are
observed as 0.62kV and 4.08kV from figures 6.31 and 6.32 respectively
due to switching operation of circuit breaker.
Fig 6.30 Simulink modeled circuit for addition of one pi-section
181
Fig 6.31 VFTO’s across secondary circuit of current transformerFor adding one pi-section
Fig 6.32 VFTOs across secondary circuit of potential transformer for
adding one pi-section
6.8.2 By adding two Pi-sections i.e. a shunt capacitance and a seriesInductance of each pi- section values are 50pF and 0.212μHrespectively in between CT and PT as shown in figure 6.33.
The transient voltages across the load terminals of CT and PT are
observed as 0.80kV and 4.54 kV from figures 6.34 and 6.35 respectively
due to switching operation of circuit breaker
182
Fig 3.33 Simulink modeled circuit for addition of two pi-sections
Fig 6.34 VFTO’s across secondary circuit of current transformerFor adding two pi-sections
Fig 6.35 VFTO’s across secondary circuit of potential transformers
For adding two pi-sections
183
6.8.3 By adding three Pi-sections i.e. a shunt capacitance and aseries inductances of each pi- section value are 50pF and0.212μH respectively in between CT and PT as shown in figure6.36.The transient voltages across the load terminals of CT and PT are
observed as 1.02kV and 4.2 kV from figures 6.37 and 6.38 respectively
due to switching operation of circuit breaker
Fig 6.36 Simulink modeled circuit for addition of three pi-sections
Fig 6.37 VFTOs across secondary circuit of current transformersFor adding three pi-sections
184
Fig 6.38 VFTO’s across secondary circuit of potential transformersFor adding three pi-sections
As the length of the GIS section increases in between CT and PT,
due to switching operations the transient voltages across the load
terminals of CT and PT are also increased. The transient voltages across
the load terminals of CT and PT are estimated for addition of pi- sections
(length of GIS) in between CT and PT and are tabulated in table 6.7
Table 6.7 Transient voltages across CT & PT for change in length of GISsection
S.NO
Increasing the length ofthe GIS in between CT
and PT
Transient voltageacross the loadterminals of CT
Transientvoltages
across theload
terminals ofPT
1 One pi-section 0.62 kV 4.08 kV
2 Two pi-sections 0.80 kV 4.54 kV
3 Three pi-sections 1.02 kV 4.20 kV