Instrument Power Cable Sizing
Sizingofinstrument cableshould be performed to ensure that instrument device such as
solenoid valveand its cabling works properly. There are two factors that should be checked
i.e. voltage drop and current carrying capacity.
Voltage drop iscalculatedas follows:
Vdrop = [Rio + (Rw x 2L) + Rins] x In
where:
Rio = Input resistance of I/O Card (Ohm)
Rw = Resistance ofwireat specified temperature per lenght (Ohm/m)
Rins = Resistance of instrument device (Ohm)
L = Length of cable / distance from instrument to cabinet in control room (m)
In = Load current (A), obtained from power consumption of instrument device divided by
power supply voltage.
Rins, Rio and Rw can be obtained from manufacturers catalog for instrument, I/O card and
cable respectively.
The cable suits the application if calculated voltage drop is less than maximum permissible
voltage drop by the system.
Current Carrying Capacity of a certain cable is defined as the maximum current that can
flow through a cable without melting the conductor or insulation. Current Carrying Capacity
varies depending on several factors such as conductor size, ambient temperature, and
cableinstallation. These factors are referred as derating factors and IEC has established
the values for each.The cable suits the application if nominal current (In) is less than current
carrying capacity.
Labels:bulk material,sizing
Posted by Instrumentcontrol at1:18 PM
Solenoid Valve Spray foam insulation Make money blogging
Address Send Email Blogs Contacts
1 comments:
Anonymous said...
Excellent information . Thanks a lot.
February 8, 2010 at 7:08 PM
Post a Comment
Home
Subscribe to:Post Comments (Atom)
.
Custom Search
Labels
materialbulk (1)
instrumentflow (1)
switchlimit (1)
regulator(1)
sizing(1)
solenoid(3)
system(2)
instrumenttemperature (1)
valve(4)
Syndication
Subscribe
International Society ofAutomation
Instrument EngineerReferences
Contact Us
Theblogauthor permits the content to be copied as longas source is mentioned and backlink is provided. Tocontactthe author,send emailto:[email protected] or by using below form
Name
EmailAddress
Message
Image Verification
Please enter the text fromthe image
[Refresh
Image]
Send Clear
Terms of Use and Privacy Policy
Thi s bl og cont ai ns not es of someone whoworks as an I nst r ument Engi neer i n EPCcompany.However, i t i s not guaranteed t hat
HOME
Search
Blog Archive
2010(1)
2009(2)
2008(7)
October(1)
September(4)
Loop Mode (1): De-Energized to Safe
Temperature Measurement: RTD or Thermocouple?
Instrument Power Cable Sizing
Solenoid Valve with Manual Reset
August(2)
0
Page 1 of 2Instrument and Control Engineering: Instrument Power Cable Sizing
3/16/2013http://instrument-control.blogspot.kr/2008/09/instrument-power-cable-sizing.html
-
8/13/2019 Instrument Cable Sizing
2/2
Instrument and Control Engineering
Blogspot TemplatebyIsnaini Dot Com
Page 2 of 2Instrument and Control Engineering: Instrument Power Cable Sizing
3/16/2013http://instrument-control.blogspot.kr/2008/09/instrument-power-cable-sizing.html