instructions manual for dry- type transformers...

46
ABB ER-046/1/95 023/MA/07/00 INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS MITS/97

Upload: trinhxuyen

Post on 01-Feb-2018

257 views

Category:

Documents


9 download

TRANSCRIPT

Page 1: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

ABB

ER-046/1/95 023/MA/07/00

INSTRUCTIONS MANUAL FOR DRY-

TYPE TRANSFORMERS

MITS/97

Page 2: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: MITS/97 Page: 1 of 1

Dear client:

You have acquired an ABB Power Technology encapsulated dry-type

transformer of proven quality that offers the following advantages:

− Good resistance to short-circuits.

− Low flammability.

− Self-extinguishing.

− Unaffected by humidity.

− Great thermal inertia.

− Minimum partial discharges.

− Compact design.

− Lower installation costs.

− Low maintenance.

PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFOREPUTTING THE TRANSFORMER INTO OPERATION

Page 3: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: MITS/97 Page: 1 of 2

C O N T E N T S

1. DESIGN, MANUFACTURE AND TESTING

1.1 Individual or routine tests

1.2 Standard and special tests

2. CERTIFICATES AND HOMOLOGATION. QUALITY POLICY

2.1 Company Register certificate

2.2 Environmental certification

2.3 Acreditation of the tests laboratory

2.4 Product certifications obtained

2.5 Quality Policy

3. TEST RECORD SHEET

4. RELIABILITY

5. CONSTRUCTION DETAILS

6. TRANSPORT AND HANDLING, RECEPTION AND STORAGE

6.1 Reception

6.2 Transport and handling

6.3 Storage

7. INSTALLATION

7.1 Installation site and protection of persons

7.2 Transformer protection

7.2.1 Protection from overcurrents and overheating

7.2.2 Ventilation of transformer cell

7.2.3 Fire extinction systems

7.2.4 Protection from overvoltage

8. CONNECTIONS

8.1 Coupling

8.2 Parallel coupling

Page 4: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: MITS/97 Page: 2 of 2

9. PREVENTION OF NOISE AND DISRRUPTIVE DISCHARGES

9.1 Noises

9.2 Disruptive discharges

10. CHECKS TO BE CARRIED OUT BEFORE PUTTING THETRANSFORMER INTO OPERATION

10.1 Checks

10.2 Putting the transformer into operation

11. MAINTENANCE

11.1 Frequency of checks

11.2 Precautions

11.3 Checks

11.4 Tightening torque of connections

12. ENVIRONMENT.

12.1 Introduction

12.2 Environment policy

12.3 Environmental impact of the transformer in service

12.3.1 Electricity consumption.

12.3.2 Noise emission.

12.3.3. Increase of surrounding temperature.

12.4 Environmental impact in emergency situations.

12.5 Waste.

12.6 Fire.

13. REPAIRS

14. ACCESSORIES

14.1 Thermal protection

15. POSSIBLE ANOMALIES AND RECOMMENDED SOLUTIONS

16. NAME PLATE

17. GUARANTEE

18. TECHNICAL SERVICE

Page 5: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: MITS/97 Page: 3 of 2

19. NOTES

Page 6: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 1MITS/97 Page: 1 of 2

1. DESIGN, MANUFACTURE AND TESTING

The dry-type transformer whose test record sheet is enclosed, is manufacturedby ABB Power Technology, S.A. and has been designed and built to meet thecompulsory Standards stipulated by the High Voltage ElectrotechnicalRegulations in force on the date of its manufacture as well as complying with theclient’s specifications.

In order to check the above, the following tests have been carried out:

1.1 Individual or routine tests (accredited by ENAC with no. 262/LE591)

STANDARDS

UNE-EN IEC CENELEC

− Measurements of windings resistances 60.076-1 60076-1 HD398-1

− Transformation ratio measurement and

connection checking

60.076-1 60076-1 HD398-1

− Load loss and short-circuit impedance

measurements

60.076-1 60076-1 HD398-1

− No load loss and current measurements 60.076-1 60076-1 HD398-1

− Separate source voltage-withstand test UNE 20.101-3 60076-3 HD398-3

− Induced over voltage withstand test UNE 20.101-3 60076-3 HD398-3

− Partial discharges measurements UNE 20178 60726 HD464

1.2 Standard and special tests (accredited by ENAC with no.262/LE591).

Other tests such as standard and special tests can be carried out in theABB Power Technology test laboratory. These tests are normally carried outto check the quality in design and process changes. They can also beperformed on order when requested by our clients.

Page 7: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 1MITS/97 Page: 2 of 2

These tests are:

STANDARD

UNE-EN IEC CENELEC

− Temperature rise test 60076-2/20178 60076-2/60726 HD464

− Lightning impulse test 20101-3 60076-3 HD398-3

− Noise levelmeasurement

60551 60551 -

Some of the special tests that we can carry out at our facilities are:

− Measuring zero-sequence impedance.

− Measuring insulation resistance.

− Measuring of harmonics of the no-load current.

− Measuring of the parallel capacity of windings and tag δ

− Measurement of scape current.

− Anti-corrosion protection measurement.

These tests are carried out in accordance with the relative IEC and/orUNE standards and the internal test procedures at the disposal of our clients.

The ABB Power Technology, S.A. test laboratory satisfies standard UNE-EN-ISO/IEC 17025:2000.

Page 8: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 2MITS/97 Page: 1 of 3

2. CERTIFICATES AND HOMOLOGATION. QUALITY POLICY

2.1 Company register certificate.

On 21.02.95 ABB POWER TECHNOLOGY, S.A. was awarded theCompany Register certificate Nº ER-046/1/95 by AENOR which guaranteesthat our Quality Assurance System satisfies standard UNE-EN-ISO9001:2000 and is applied throughout the process, from the design anddevelopment stages to after-sales service, establishes management criteriaand procedures and processes that ensure that our transformers are free ofdefects. This system also includes suppliers and the application of the know-how and expertise obtained from research and from the standard andspecial tests carried out, guaranteeing homogeneity in the design ofproduct components, manufacturing procedures and tests, staff training andthe continuous improvement of the whole process.

2.2 Environmental certification.

The environmental certificate no. 023/MA/07/00 granted by ECA(Certification and Assurance Entity) guarantees that the environmentalmanagement system satisfies standard UNE-EN-ISO 14001-96 and isapplied to the design, production, after-sales service and repair phases oftransformers, and is developed as expressed by ABB in its environmentalpolicy

2.3 Accreditation of the tests laboratory.

Accreditation of the tests laboratory for the accomplishment of the routineand type tests defined in this manual and granted by ENAC with nº262/LE591, which indicates that the tests laboratory meets norm UNE-EN-ISO/CEI 17025:2000.

2.4 Product certifications obtained.

The following product certificates have been obtained by ABB PowerTechnology, S.A. (Zaragoza):

• The class F1 "Burning Behaviour" certificate obtained inhomologated tests in accordance with CENELEC-HD 464 S1/A3(November 1992), dated 07.07.97 in the laboratory of C.E.S.I. testnumber: BC-97/022127.

• The class C1 "Climatic" certificate in accordance with CENELEC-HDS1 1988/A2:1991 Appendix ZB.2 obtained in ABB Trafo BB GmbH on29.03.94, test no.: KI 715 W 009.

Page 9: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 2MITS/97 Page: 2 of 3

• The class E2 "Condensation and humidity" certificate, inaccordance with CENELEC-HD 464 S1:1988/A2.1991, AppendixZA.2.2A obtained en ABB Trafo BB GmbH on 29.03.94 test no.: KI715 W 009.

• It’s suitability to endure short-circuits according to UNE 20101-5/IEC76-5 certified by LABEIN dated on 29.04.98. Certificate no.9801B026-AI-LE-02.

• It’s suitability to endure short-circuits according to UNE 20101-5/IEC76-5 certified by LABEIN dated on 13.05.98. Certificate no.9801B025-AE-LE-01.

• It's suitability to endure short-circuits according to IEC 60076-5obtained in C.E.S.I. on 01.03.01, certificate no.: MP-A1/006927.

• The class C2 "Climatic" certificate, in accordance with CENELECHD464 S1:1988/A2 1991, obtained in LGAI with no. 20020462.

• Test Certificate of seismic qualification made by VIRLAB, S.A. with no.210971.

• Vibration test Certificate made by VIRLAB, S.A. with no. 221001.

Page 10: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 2MITS/97 Page: 3 of 3

2.5 Quality policy.

ABBQQQUUUAAALLLIIITTTYYY PPPOOOLLLIIICCCYYY

Our most important quality criterion is our customers'satisfaction.

Their requirements will be satisfied by our commitment and by productswhich fulfil the terms that have been agreed. Each product delivery and eachof our actions with regards to our customers should create a recommendationfor future business.

We will ensure that all of our employees are sources of quality andproductivity by means of:

Ø Quality improvement programmes which result from themotivation achieved through confidence, respect, participationand recognition.

Ø Education and training provided to ensure that each employeeunderstands, backs and contributes to the achievement of TotalQuality.

Ø Economically producing quality services and products which fullysatisfy customer needs and expectations.

We will ensure that our suppliers are an extension of our business. They willbe selected, appraised and acknowledged as suppliers on the basis of theirpotential value and real contribution towards satisfying the demands of ourtotal quality objective.

We will adhere to standards UNE-EN ISO 9001/2000, which establish thedemands for quality assurance in our business and we undertake to comply withthe legal, regulation and standard requirements of the customer.

R. PaniaguaGeneral Manager

ABB Power Technology, S.A. Distribution transformers

Page 11: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 3MITS/97 Page: 1 of 1

3. TEST RECORD SHEET

All the information on the tests that the transformer has undergone is recordedon the Test Record Sheet and included with the information accompanying thetransformer.

The Record Sheet indicates important data such as the no-load and load lossesas well as the impedance voltage, no-load current and the level of partialdischarges.

Each transformer manufactured by ABB Power Technology, S.A., withoutexception, has its own particular test record which is kept on file for a minimumperiod of 13 years and is at the disposal of our clients at their request.

The test protocol satisfies standard UNE-EN-ISO/CEI 17025 and is identifiedwith the ENAC logotype and approval no. 262/LE591, which means that the teststargeted by the document are approved by this organisation.

Page 12: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 4MITS/97 Page: 1 of 1

4. RELIABILITY

The transformer leaves the factory free of all defects (as shown by the tests ithas undergone) and ready to be put into operation for the whole of its working life.

This level of reliability must be maintained during its handling, storage, andtransport and the appropriate checks must be made when it is put into service,with the protections established by the H.V. Regulations from each country. Inaddition, the maintenance standards detailed within this manual must be applied.

At the installation site all the necessary measures must be taken to protectthose persons who work regularly, or from time to time, in the proximity of thetransformer whilst at the same time ensuring that all those persons not involved inits operation do not have access to it.

Page 13: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 5MITS/97 Page: 1 of 1

5. CONSTRUCTION DETAILS

The dry-type transformer can be supplied with or without enclosure. The coolingsystem can be by natural air (AN) or forced air by means of fans (ANAF).

The insulating system is designed to withstand 100 K in the middle conductorand a maximum temperature of 155ºC, in accordance with class F defined inUNE-EN 60076 standard, part 2, and IEC 60076 standard, part 2.

Moreover, the construction details satisfy standard UNE 21538 and adapt to thetechnical requirements of our clients’ specifications.

The normal operating conditions are:

− Altitude ≤1000 m.

− Ambient temperature:

§ -5ºC up to +40ºC (C1 type)

§ -25ºC up to + 40ºC (C2 type)

The customer must specify all those environmental conditions that are notnormal, in order to include the necessary variations in the design.

Page 14: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 6MITS/97 Page: 1 of 3

6. TRANSPORT, HANDLING, RECEIPT AND STORAGE

6.1 Receipt.

The transformer is supplied totally mounted and ready to be connected tothe H.V. and L.V. lines and inside a plastic cover that protects it from dustand rain.

When the transformer is received, either at the client’s warehouse or at itsfinal site, the following points should be checked:

− The characteristics of the transformer, indicated on the Name Plate,should coincide with those that appear on the Test Record Sheetand these, in turn, should match the order specifications.

− Check that the transformer has the relevant safety warnings.

− Check the general state of the machine. There should be no dents inencapsulated phases or connections.

− The state of the paint: check that there is no flaking, scratches, etc.on the enclosure (if the transformer is of this type) or on metallicparts.

− Check all of the transformer’s accessories (wheels, thermometer,etc.) If any damage is observed or if any of these have been lostduring transport the transport company and manufacturer should beinformed immediately to determine who is responsible and tocalculate the cost involved.

− Before unpacking the transformer, especially during the winter orwhen the difference in temperature between the room and outdoorsis considerable, a prudential period of time should elapse (8 to 24hour) so that the transformer temperature has time to rise to thatroom. This is to prevent undesired condensation of the transformersurface.

Page 15: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 6MITS/97 Page: 2 of 3

IMPORTANT:

− In the event that an anomaly is discovered when the transformer isreceived, the manufacturer should be contacted immediately. If, withina period of 5 days, the manufacturer has not received notification ofanomalies or defects it will be considered that the transformer is inperfect condition and the manufacturer will not be liable for what mayoccur to the transformer during operation nor its consequences.

6.2 Transport and handling.

During transport the transformer should not be moved by pushing on coilsor connections. The transformer is fitted with four rings on the wheel baseprofiles for attaching cables to drag it. If the transformer has to be pushed,then this can be carried out by pushing on the flanges that hold the magneticcircuit in place.

The top flanges have 4 lifting eyes and hoisting can be carried out byattaching slings that form an angle of 50-70º to the eyes or to the transformerenclosure walls.

− The name plate indicates the total weight of the transformer. Thismust be taken into account when deciding on the elements to use forlifting.

− The attachment holes or lifting eyes have a minimum diameter of 40mm.

− The base and cooling elements are designed to ensure that thetransformer can be moved using a lever and do not impede handling;however, care must be taken not to push on the encapsulatedphases. If levers are used then we recommend using wooden stopsto protect these elements.

6.3 Storage.

The dry-type transformer is for indoor installation. Do not store in placeswhere it is exposed to effects of the weather.

If the transformer is not going to be put into operation immediately then itshould be stored bearing in mind the following recommendations:

Page 16: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 6MITS/97 Page: 3 of 3

6.3.1 The temperature in the storage place can´t be below than –25ºC(C1 and C2 type).

When C1 type transformers will be lengthy storage withtemperatures lower than –25ºC it must be consult with themanufacturer.

6.3.2 The place will be dry, clean and good ventilated.

When in storage this type of transformer should be remain inside itsplastic packaging cover.

In particularly damp places bags with humidity absorber productslike silicagel should be placed near the coils such an adequateventilation.

6.3.3 The indications given in point 6.2 will be followed for lift andtransport the transformer.

6.3.4 The indications given in point 6.2 will be taken into account duringtransport and handling. Do not exert pressure on the encapsulatedphases nor connections or terminals. Take care not to damagepaintwork.

6.3.5 If the transformer is lifted and transported by means of a fork-lifttruck, the prongs of the truck should be inserted inside the wheelcoupling profiles, protecting the cooling elements from anypossible damaged that could be caused by the lifting machine.

6.3.6 If the transformer is equipped with plug-in terminals, these shouldall have cone protectors to ensure that the terminal contactsremain clean and undamaged.

ABB Power Technology don't make responsible of the possibledamage if the storage conditions are not respects.

Page 17: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 7MITS/97 Page: 1 of 4

7. INSTALLATION

The transformer manufacturer is not responsible for its installation. Installationmust be carried out in accordance with the laws currently in force and following theinstructions given by the manufacturer.

The following points must be taken into account when installing the machine:

− Earth all voltageless metallic parts by means of the screw available for thispurpose.

− Connect the L.V. neutral to earth when this is compulsory or when it is arequirement of the earth fault protection system.

− Ensure that terminals and bridges are correctly connected and that all ofthe transformer’s mobile parts are securely fixed.

− In transformers with a dual ratio in H.V. or L.V. ensure that the transformeris connected at that which corresponds to the mains voltage or outputvoltage.

− Check that the position of the diverter switch is correct in accordance withthe mains.

− Consult the name plate when the position is changed.

− Connect the thermal protection system in accordance with the diagramsupplied.

− To revise the tight-fitting of all the screws according to the list of thechapter 11.4

The electric current that passes through the windings and the magnetisation ofthe magnetic circuit produce electric losses that are transformed into heat. Toprevent this heat from accumulating in the transformer with the consequent risksthat this involves, the transformer is designed to cool naturally, however, thereshould also be adequate ventilation at the installation site.

The transformer is designed and built to withstand abnormal situations ofovervoltage and overcurrents including those of a short-circuit in the secondarywinding; however, the magnitude and duration of these should be limited by meansof the appropriate elements.

7.1 Installation site and protection of persons.

Page 18: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 7MITS/97 Page: 2 of 4

The site conditions and design , both for technical reasons and for theprotection and safety of persons and property, are defined in the HighVoltage Regulations established by Spanish law (or the correspondingcountry law) in force at the time.

The instructions of the Electricity Company, which is familiar both with theRegulations and the specific characteristics of the system to which thetransformer is to be connected, must also be taken into account.

A horizontal base that can withstand the weight of the transformer withoutdeformation should be prepared. The total weight is indicated on thetransformer’s name plate.

The wheels should also be blocked to prevent the transformer from movingduring operation.

7.2 Transformer protection.

Although the H.V. Regulations from each country indicate the type ofprotection that the transformer must have, the following is essential to ensurethe reliability and operation of the transformer.

7.2.1 Protection from overcurrents and overheating.

The transformer must be protected from the thermal and dynamiceffects caused by overcurrents and shortcircuits.

For this purpose there should be an automatic diverter switch orshort-circuit fuses which take into account the possible overloads andare calibrated to prevent currents from passing that are 1.5 or 2 timesgreater than the assigned current (see name plate).

7.2.2 Ventilation of the transformer cell.

As has already been indicated, there should be suitable ventilationto stop the transformer from overheating above the limits establishedby the standards.

If the transformer is mounted inside a cell, it should be ensured thatit is well-ventilated and that it is of the correct size to allow air to passin and out.

The transformer must be located at least 100 mm from the cell wallsand its bushing must be at least 350 mm from the cell roof and walls.

The input E and output S surfaces should have at least the surfaceareas in m2 given by the following formulas:

Page 19: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 7MITS/97 Page: 3 of 4

E P H= / ,5 4 S E= 115,

Where:

H = Distance between the centres of openings, expressed inmetres.

P = The sum of the no-load and full-load losses of thetransformer in kW.

NOTE: This formula is valid for a maximum room temperature of40ºC and a maximum altitude of 1000 m.

The following should be avoided:

− The ambient air temperature should not exceed thatindicated by the standards.

− The transformer should not be installed in small rooms withblinds or metallic walls exposed to direct sunlight.

− The air for cooling the transformer should not be aspired orexpelled in the same room in which it is installed.

− The transformer should not be installed in premises that aredestined for other uses; in particular in those in which thereare machines that work at high temperatures: boilers,steam generators, etc.

− If the transformer cannot be installed in premises withsufficient natural ventilation, forced ventilation should beused.

7.2.3 Fire extinction systems.

It is not necessary to provide a device for collecting the dielectricliquid or to install fire extinction systems. These transformers shouldbe installed in such a way that the heat generated does not representa fire risk for the materials nearby.

7.2.4 Protection from overvoltages.

To protect the transformer from industrial frequency overvoltagesand those of an atmospheric origin, variable resistance lightningarresters should be used. The characteristics of the lightning arresterswill depend on the level of insulation of the transformer, characteristics

Page 20: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 7MITS/97 Page: 4 of 4

of the mains system. They will be earthed in accordance with H.V.Regulations from each country.

At this point it is essential to receive the collaboration of theElectricity Company to whose system the transformer is going to beconnected.

Page 21: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 8MITS/97 Page: 1 of 2

8. CONNECTIONS

8.1 Coupling.

When the transformer is connected to the H.V. and L.V. circuits theconnections should be carried out in such a way that they do not exert anystrain on the terminals and should have a large enough section to preventexcessive heating. They should also be able to dilate.

It is important to make sure of a suitable connection and tightening of allthe bolts.

− Using an ohmmeter check the continuity of the circuit with the tapchanger in all of the positions as well as checking that the bridgesare correctly fixed in the working position.

− The enclosure or lower flange of the transformer should be securelyand permanently connected to earth by means of the earthingscrews on the bottom right of the two larger, lower, opposite facesof the enclosure or flange. The earthing conductor should be of thedimensions indicated in the H.V. Regulations from each countryand in accordance with the characteristics of the transformer.

8.2 Parallel Coupling.

If the transformer has to be parallel-coupled to other transformers, checkthat it fulfils the voltage compatibility conditions established by the standards,check the position of diverter switches, impedance voltage and connectionsunit. See standards no. IEC 60076-4 y IEC 60606-4.

− Identical rated voltages and frequencies (voltage tolerance0,5%).

− The transformers should belong to the same vectorial group.

IMPORTANT

Check that the tap changer is in the correct position and, in the caseof multi-voltage transformers, that the H.V. winding is connected atwhat is going to be the working voltage.

THE TAP CHANGERS SHOULD ALWAYS BE MANIPULATEDWITHOUT VOLTAGE!

Page 22: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 8MITS/97 Page: 2 of 2

− Identical short-circuit voltage (tolerance ±10%).

− Power ratio of (maximum) 3/1 in d.c.

Page 23: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 9MITS/97 Page: 1 of 2

9. PREVENTION OF NOISE AND DISRUPTIVE DISCHARGES

9.1 Noises.

− When the transformer is connected to the mains, check that the positionof the diverter switch and the H.V. winding connection (if there is morethan one) is that of the working voltage. Otherwise the magnetic circuitmay become over saturated and the noise level will increase notably.

− Check that the transformers four wheels are firmly resting on the ground.

− Do not attach grids or guards to the metallic walls of the transformer.

− Fit flexible L.V. cables, held in place by means of insulating brackets.

Power noise level dB(A)(UNE 21538)

Rated power

kVAHasta 24 kV 36 kV

50

100

160

250

400

630

1000

1600

2500

59

59

62

65

68

70

73

76

81

-

-

66

67

69

71

73

76

81

The acoustic power level values indicated in the table are the maximumadmissible and are determined based on the acoustic pressure values measuredin the transformer axles in four positions at 0.3 m according to standard UNE-EN60551.

9.2 Disruptive discharges.

To prevent disruptive discharges, maintain the distances indicated in thetable, between H.V. and L.V. or metallic parts.

Page 24: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 9MITS/97 Page: 2 of 2

These distances are:

HIGHEST VOLTAGE FOREQUIPMENT (kV)

DISTANCE (X)(mm)

From insulated parts

12

24

36

50

120

200

x H.V.

X

X

(L.V.)

It is very important to maintain the minimum distance x from the insulatingparts of the High Voltage windings to the metallic parts or Low Voltage, toavoid a possible breakdown.

For distances between High Voltage non-insulation parts and LowVoltage metallic parts will be taken the suitable values in the High Voltageregulations or applicable standards in each country.

ABB Power Technology does not accept any liability for possiblefailures if this distance is not respected.

VERY IMPORTANT

The insulation of the coils does not guarantee thesafety of persons in the event of accidental contact.For this reason these transformers should not beinstalled in easily accessible places.

Warning and danger signs that are easily visibleshould be placed on the coil covering.

Page 25: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 10MITS/97 Page: 1 of 2

10. CHECKS TO BE CARRIED OUT BEFORE PUTTING THETRANSFORMER INTO OPERATION

10.1 Checks.

The transformer is supplied ready for installation but before proceeding toput it into operation the following checks should be carried out:

− All of the recommendations indicated in Chapters: 7. Installation, 8.Connections, and 9. Prevention of noise and disruptive dischargesshould be checked.

− The transformer should also be cleaned using a vacuum cleaner toeliminate any dust.

− Check the thermal protection device (see Chap. 14 "Accessories").

− Check insulation resistance according to the following table:

Insulation between: Test Voltage Minimum Value in MΩ

H.V./L.V. 5.000 v 1 per kV A.T.

H.V./Earth 5.000 v 1 per kV A.T.

L.V./Earth 2.000 v 2

10.2 Putting the transformer into operation.

Once the transformer has been connected to the H.V. mains:

− Voltage will be applied in a non-load state and observed for onehour. No anomalies should occur during this period of time.

− Afterwards storage or disconnection during a prolonged period,first it is recommendable to connect the transformer during fourhours in no-load for loss the possible damp with the coreheating. After this period it can be put into a normal operation.

− The voltage will be measured at the L.V. terminals to check thecorresponding output voltage depending on the transformationratio.

Page 26: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 10MITS/97 Page: 2 of 2

− To Apply the load progressively until the rated power is reachedand check the increase in temperature.

Page 27: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 11MITS/97 Page: 1 of 3

11. MAINTENANCE

11.1 Frequency of checks.

Annually: in normal environments.

Quarterly: environments that are contaminated with dust or industrialfumes, and also the transformers placed in windmills and having vibrations.

11.2 Precautions.

All the precautions stipulated by current legislation must be taken. Thefollowing measures are amongst the most important ones.

Before examining or carrying out maintenance on the transformer:

− Disconnect the H.V. and L.V. switches so that the transformer isde-energised and out of service.

− Using an insulating rod the transformer bushings should beearthed to ensure that there is no remaining static charge .

− The bushings are then short-circuited and earthed.

11.3 Checks.

− Check and tighten screws, connections and voltage change bridges.

− Clean any dust from surfaces using a vacuum cleaner or by blowing withdry air or nitrogen (maximum pressure 3 Kg/cm2). Nitrogen bottles asnormally supplied, equipped with a pressure reducer, can also be used.

− Check the thermal protection device that includes the sensors (Pt100type or thermistors) and the measuring control unit (see chapter 14"Accessories").

ATTENTION!

This is a low-maintenance transformer

The above indicated points do not imply the exemption from fulfilling therequirements established by current laws concerning Transformation Centreswith regards to:

Page 28: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 11MITS/97 Page: 2 of 3

The protection of persons and the integrity and functionality of the goodsthat may be affected by the installations themselves.

11.4 Tightening torque of connections.

INSTRUCTIONS TO MAKE SCREWED JOINTS IN LOW AND HIGH VOLTAGE

L.V. SCREWED CONNECTIONS

Indoors Outdoors

Quality of nuts and bolts 8.8 8.8 Stainless steelA2 or A4

Protection degree of nutand bolt

Zinc or cadmiumplated

Hot galvanised -

Tapered washer DIN 6796 Zinc or cadmiumplated

Zinc or cadmiumplated

Zinc or cadmiumplated

Thick washer DIN 7349 Zinc or cadmiumplated

Zinc or cadmiumplated

Zinc or cadmiumplated

Lubricant for nut and bolt Oil SAE 30 or 40

Vaseline grease

Molybdenum bisulphide grease(MoS2)

Grip torques (Nm)

M 8 10 15 20

M 10 20 30 40

M 12 40 60 75

M 16 80 120 140

When one or both of the bars to be joined together are aluminum, thelayer of aluminium oxide must be removed by brushing or sandpapering with"Scotch Brite" or similar. This layer is practically invisible and extremely

This inspection must be carried out on all transformers. In thecase of those in which less than ten years has passed since theirmanufacture, the inspection must be carried out in contact withthe manufacturer who should be informed of the results in order tobe able to recommend corrective actions, if necessary.

Page 29: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 11MITS/97 Page: 3 of 3

resistant, so its presence prevents making a good contact. This operationmust be repeated if the connection bars are dismounted for any reason.

Once clean, apply a very fine coat of special grease for contacts.

Then make the connection and tighten the bolts according to the abovetable.

Aluminium/copper joints must have a bi-metal plate.

The grip torques, indicated on the table, correspond to greased bolts.

Greasing oil or white vaseline grease can be used, in order not to soil thearea around the connection.

Molybdenum bisulphide grease must be used for stainless or hotgalvanised nuts and bolts. Any excess must be cleaned after tightening.

H.V. SCREWED CONNECTIONS

Nuts/bolts M6 M8 M10 M12

Grip torques (Nm) 8 15 30 60

H.V. bolts must not be greased

Page 30: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 12MITS/97 Page: 1 of 5

12. ENVIRONMENT

12.1 Introduction.

ABB Power Technology, S.A., has implemented and certified at its plantin Zaragoza, an Environmental Management System as per standard UNE-EN-ISO 14001 and it has identified the possible accidents, incidents andsituations that could produce environmental effects that are detrimental to theEnvironment.

The environmental management system is applied both in themanufacturing processes and in the product operation as set out in theenvironmental policy.

Our commitment is for continuous improvement and within this context weoffer our customers environmental information that affects the product andwhich we develop in points 3, 4 and 5 of this chapter. This information isbased on our current knowledge always with the commitment to improve it asour knowledge increases.

We inform you, too, that the existing legislation is broad and extensive andis continuously evolving, which makes it difficult to offer an updated overviewof it. However, you will find legislation of the European community, of thecountry itself and of the autonomous communities and Town Councils.

The Quality and Environment Dept. of ABB Power Technology Zaragozaplaces itself at the disposal of its customers to answer any queries or giveassistance on Environment-related issues.

If you access to www.canalmedioambiental.com you can follow thecurrent situation of the company and the environment day-to-day and free ofcharge. News, legislation, documentary background, company directory,novelties, courses and seminars, among others.

Page 31: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 12MITS/97 Page: 2 of 5

12.2 Environmental Policy.

ABBEEENNNVVVIIIRRROOONNNMMMEEENNNTTTAAALLL PPPOOOLLLIIICCCYYYOur criterion with regards to the Environment is to

respect Nature and Life

All activities, processes, and services are directed towards compliance withenvironmental requisites, towards continuous improvement, and towardscontamination prevention.

We commit ourselves to:

` Comply with regulatory requisites and legislation.

` Avoid contaminating the atmosphere, water, and soil.

` Evolve towards a continuous improvement system regarding the Environment.

` Minimise and prevent damaging environmental effects.

` Publish environmental objectives, goals, and reports.

` Minimise waste production and endeavour to use reusable materials.

` Update the Environmental Policy, making it public and internally andexternally accessible.

` Involve suppliers and subcontracted companies.

We will ensure that the above aspectsare understood and accepted at all levelsof the organisation, by means of trainingand continuous improvement programmes.

We adhere to standards UNE-EN ISO14001/1996 and applicable Regulations ofthe Environmental Management System thatestablish the environmental requirements inour business.

R. PaniaguaGeneral Manager

ABB Power Technology, S.A. Distribution transformers

Page 32: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 12MITS/97 Page: 3 of 5

12.3 Environmental impact of the transformer in use.

Environmental impacts identified with the transformer in use:

− Electricity consumption.

− Noise emission.

− Increase of surrounding temperature.

12.3.1 Electricity consumption.

The transformer is a static electrical machine, which has anefficiency of approximately 98%. This 2% power lost is inverted intolosses in its magnetic circuit and in the windings.

These losses dissipate into heat in the surrounding environmentand they are limited and subject to compliance with Standards and/orspecifications of our customers.

12.3.2 Noise emission.

The transformer has a magnetic circuit, which, due to the effect ofmagneto-striction caused by the magnetic flow, issues a noise, whichmay be troublesome for people, as well as vibrations, which aretransmitted through the floor or structure causing noises in placesclose to the location of the transformer.

The sound level of the transformers is regulated by the relativeUNE-EN/IEC standards, as well as by town council regulations, whichdepend on whether it is located in urban or industrial areas.

We can limit its impact if we follow the instructions given in chapter9MITS/97.

Environmental impact

This is any action, whether it be harmful orbeneficial, that transforms the environment,said action being caused by directly by theactivities, products and services.

Page 33: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 12MITS/97 Page: 4 of 5

12.3.3 Increase of the surrounding temperature.

The dissipation of losses in the magnetic core and in the windingsgives rise to an increase in the temperature around the transformer,which, in turn, is dissipated into the medium helped by the lowersurrounding temperature.

The non-existent emission of gases or losses of coolant make theenvironmental impact minimum.

12.4 Environmental aspects in emergency situations.

Electricity consumption.

Causes: Excessive voltage or current supply.

Excessive noise level.

Causes: Excessive voltage supply. Slackening of the magneticcore. Foreign objects close to the transformer, bad location of thetransformer near reflecting objects. Bad seating. Rigid connectionin L.V.

Excessive heating.

Causes: Excessive voltage or current supply, nearby objects thatprevent the natural cooling and/or foreign bodies are blocking thecooling channels.

Fire.

Causes: Faulty operation of the transformer. Internal short-circuit.

The trafo is self-extinguishing.

Combustion gases.

Causes: Fire.

These gases are not harmful for health nor for the environment.

12.5 Waste.

This type of transformer does not generate waste in normal operation.

The packaging is plastic and/or wood and is made of elements that canbe recycled, if correctly managed.

Page 34: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 12MITS/97 Page: 5 of 5

During their maintenance they do not generate waste and at the end oftheir lifespan the following can be generated:

− Encapsulated windings. Any aluminium or copper scrap can berecovered if the resin coating is destroyed. The resin is managedin the same way as inert urban waste and the copper or aluminiumcan be recycled.

− Copper or aluminium L.V. windings. They can be recycled byeliminating the insulating coating adhered to its surface.

− The magnetic plate can be eliminated as scrap or to retrain.

− The flanges, casings, wheels, nuts and bolts and in general themetal parts can be eliminated as scrap or to retrain.

12.6 Fire.

This transformer is self-extinguishing and resistant to burning;nevertheless, the following measures must be taken into account toextinguish it:

EXTINGUISHING MEANS: Carbon dioxide

Foam

Dry powder.

WARNING!

Do not use WATER to try to fightthe fire

Page 35: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 13MITS/97 Page: 1 of 1

13. REPAIRS

− If an anomaly in the operation of the transformer is observed, this shouldbe reported to the manufacturer who will then advise the appropriateactions.

− If, having checked the transformer, it is found that it has to be repaired oraltered, these operations will be carried out by the manufacturer.

NOTE:

If these instructions are not followed, the original manufacturer is nolonger responsible for the functioning of the transformer and its reliability.This responsibility falls on the person who has carried out the repair.

Page 36: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 14MITS/97 Page: 1 of 3

14. ACCESSORIES

The transformer is fitted with the following accessories, in accordance withcurrent UNE standards or customer specifications.

Name plate.

Two earth terminals.

Safety warning notices.

Thermal protection. Temperature sensors mounted in a compartment onthe L.V. phases with a control unit for temperature measurement.

Fans.

Enclosure.

14.1 Thermal Protection.

The thermal protection system or temperature control is supplied packedalong with the transformer so that our clients can install it wherever required.

2 protection systems are used:

− Protection consisting of thermistors with alarm and triggeringsignal in control unit Diagram 1.

− Protection consisting of Pt100 sensors with measuring andalarm and triggering signals in control unit. Diagram 2.

The instructions for the adjustment of control units and for changing alarmand trigger signals are indicated in the information supplied with the controlunit.

The advised programmed temperature values for the alarm and tripsignals, when speaking of an average winding heating of 100 K and amaximum ambient temperature of 40ºC, are:

Sensor Pt100 Thermistor

Alarm 130 130 Blue-Blue

Trip 150 150 Black-Black

Fans (Connect./disconnect.)

120 110 Brown-Brown

Page 37: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 14MITS/97 Page: 2 of 3

INTERCONNECTION BETWEEN TRANSFORMER AND CONTROLTEMPERATURE UNIT

The interconnection between the transformer terminal strip and the controltemperature unit is carried out with three wires.

The plugs marked 1, 2 and 4 on the transformer and those on the controltemperature unit should be connected.

CONTROL TEMPERATURE UNIT STRIP

TRANSFORMER STRIP

PTC/FAN (OPTIONAL)

Diagram 1

1 2 3 4

1 2 3 4

L1 FANL2

L1 FANL2

U

V

W

Page 38: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 14MITS/97 Page: 3 of 3

CONNECTION BETWEEN THE TRANSFORMER AND THE CONTROLTEMPERATURE UNIT

The transformer includes three Pt-100 sensors, one per phase, which must beconnected to the control temperature.

The connection of the three Pt-100 sensors from the transformer to theexchange is carried out with nine wires.

The nine transformer terminals and the exchange are numbered in exactly thesame way: 13,14,15,16,17,18,19,20,21

Channel 1 of the control temperature unit corresponds to the U phase of thetransformer, channel 2 to the V phase and channel 3 to the W phase

TERMINALS IN THE CONTROLTEMPERATURE UNIT

Diagram 2

TERMINALS IN THE TRANSFORMER

Pt-100 SENSORS INTHE TRANSFORMER

TRANSFORMER

13 14 15

CH1

16 17 18

CH2

19 20 21

CH3

22 23 24

CH4

13 14 15 16 17 18 19 20 21 22 23 24≡ ≡ ≡

U phase

CH4 - Fans or fourth sensor in core (optional)

V phase W phase

Page 39: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 14MITS/97 Page: 4 of 3

These interconnections may vary depending on the model of exchange used.The numbers indicated on the terminal strip always coincide with the numbers onthe exchange.

Page 40: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 15MITS/97 Page: 1 of 3

15. POSSIBLE ANOMALIES AND RECOMMENDED SOLUTIONS

The following table briefly describes anomalies which may be found duringoperation or when periodic checks are carried out and indicates how to resolvethem.

SYMPTOMSAFFECTED ELEMENTS

PROBABLE CAUSES SOLUTIONS

Low insulation resistance Dielectric. Presence ofhumidity on surface ofwindings.

Clean with dry air.Ventilate.

Dielectric. Ageing, dirt. Contact manufacturer.Clean with dry air.

The automatic protectiondevice is triggered at thetransformer connection

Windings. Defective windings. Contact manufacturer.

Tap diverter switch

The primary voltage does notcoincide with the diverterswitch position.

Check that the position ofthe switch coincides withthe primary voltage.

Fuses

Incorrectly calibrated Change fuse.

Protection relays

Timing and/or current isincorrectly adjusted.

Check timing and currentsetting.

Abnormal secondaryvoltage

Primary Voltage

Absence of primary voltage. Check installation andcontact ElectricityCompany.

Tap diverter switch

Incorrectly positioned. Change positioning.

Page 41: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 15MITS/97 Page: 2 of 3

SYMPTOMS AFFECTED ELEMENTS

PROBABLE CAUSESSOLUTIONS

Windings

No continuity in windings. Contact manufacturer.

Very low voltage Primary voltage

Very low Check installation andcontact ElectricityCompany.

Very high voltage Primary voltage

Very high Check installation andcontact ElectricityCompany.

Unbalanced voltage Tap diverter switch

Incorrectly positioned in oneof the phases.

Check the position of the 3switches.

Check installation andcontact the ElectricityCompany.

Fuse

Fuse has blown. Change fuse.

Windings

No continuity in windings. Contact manufacturer.

L.V. installation

Load imbalance.

Incorrect coupling.

Check L.V. installation.

Check L.V. connections.

Spurious triggeringduring operation

Thermometer

Incorrect operation.

Triggering and alarmincorrect set.

Check. Change.

Check setting. Correct.

Page 42: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 15MITS/97 Page: 3 of 3

SYMPTOMSAFFECTED ELEMENTS

PROBABLE CAUSESSOLUTIONS

Pt100 sensors or thermistors

Defect of sensors orthermistors.

Check sensors orthermistors.

Windings

Perforation of insulatingmaterial.

Contact manufacturer.

Fuse

Blown fuse Change fuse.

Relays

Incorrect timing. Check timing.

Abnormal operatingtemperature

Installation premises

Insufficient ventilation.

High ambient temperature.

Check ventilation ofpremises.

L.V. mains

Overloaded Check for possible powerincreases and dischargethe trafo.

High level of noise Magnetic core

High supply voltage

Loose accessories

Certain elements have beenpoorly mounting, producingvibrations.

Adjust diverter switch orregulator.

Check over. Re-tighten.

Not enough distance towalls

Reflecting elements.

Remove elements.

Study of the area.

Page 43: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 16MITS/97 Page: 1 of 1

16. RATING PLATE

All of the transformers have a name plate indicating and defining all of its basiccharacteristics.

This plate is placed (unless indicated otherwise by our clients) on the L.V. sideand is riveted, stuck or screwed to the top flange on a welded bracket or on thecasing of the transformer.

Page 44: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 17MITS/97 Page: 1 of 1

17. GUARANTEE

On behalf and in representation of ABB Power Technology, S.A., DistributionTransformers at its site in Zaragoza, the manager of Quality Assurance andEnvironment

Certifies:

That the transformer indicated in the attached record sheet has beenmanufactured and tested in accordance with order specifications and applicablestandards and codes, obtaining satisfactory results.

and thus,

Guarantees:

Said transformer from all manufacturing defects for a period of twelve monthsfrom its commissioning or eighteen months from its date of dispatch.

This guarantee does not cover the effects caused by the mistreatment ormisuse of the transformer.

Quality Assurance and EnvironmentManager

ABB Power Technology, S.A.Distribution Transformers

Page 45: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 18MITS/97 Page: 1 of 1

18. TECHNICAL SERVICE

ABB Power Technology, S.A. has a 24 hour Technical Service. In the event ofany query or anomaly we are at your entire disposal at the following telephonenumbers and departments:

TECHNICAL SERVICE

Mr. Vicente Cerezuela Tel.: +34 976 76 93 05

Mobile tel.: + 34 616 97 19 29

Fax: +34 976 76 93 06

E-mail: [email protected]

COMMERCIAL

Mr. Fernando Aparicio Tel.: +34 976 76 93 30

Fax: +34 976 76 93 06

E-mail: [email protected]

EXPORT SALES

Mr. Alfredo Parres Tel.: +34 976 76 93 36

Fax: +34 976 76 93 06

E-mail: [email protected]

MANUFACTURE

Mr. Antonio Peiro Tel.: +34 976 76 93 10

Fax: +34 976 76 93 06

E-mail: [email protected]

DISPATCH

Mr. Manuel Gonzalo Tel.: +34 976 76 93 32

Fax: +34 976 76 93 06

E-mail: [email protected]

QUALITY AND ENVIRONMENT

Mr. Santos Zaurin Tel.: +34 976 76 93 27

Fax: +34 976 76 93 08

E-mail: [email protected]

A T T E N T I O N !

Your complaints or claims will be well received and will help us to improve.Please pass on any complaints to the above indicated persons.

Page 46: INSTRUCTIONS MANUAL FOR DRY- TYPE TRANSFORMERS …vfservis.cz/files/000147_Mits97_ingles_Nov02.pdf · INSTRUCTIONS MANUAL FOR DRY-TYPE TRANSFORMERS MITS/97. INSTRUCTIONS MANUAL ABB

INSTRUCTIONS MANUAL ABB

Revised: Quality departmentApproved: Quality assurance manager

Revision: 6Date: November 2002

Number: 19MITS/97 Page: 1 of 1

19. NOTES