SBC Source-Transfer In Gear Having “Rl” or “R2” Outdoor Distribution (14.4 kv and 25 kv) With Micro-AT’“ Control PMH Pad-Mounted Gear Replacing Type AT-1 2 Control Supplement to the Catalog Number INSTRUCTIONS For Field Replacement I TABLE OF CONTENTS I Section Page Number Section Page Number INTRODUCTION ............................. 1 REMOVING THE MECHANICAL ANTIPARALLELING CONTROL ................................ 2 INETALLING THE MICRO-AT SOURCE-TRANSFER REMOVING THE TYPE AT-12 SOURCE-TRANSFER FEATURE .............................. .10 c:oNTRoL ............................... 11 I INTRODUCTION I The equipment covered by this publication must be selected for a specificapplicationand it must be installed, operated, and maintained by qualified persons who are thoroughly trained and who understand any hazards that may be involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. This publication provides instructions for field removal of the Type AT-12 control which was originally furnished in S&C Source-Transfer PMH Pad-Mounted Gear having an “Rl” or “R2” supplement to the catalog number, and its replacement with Micro-AT Source- Transfer Control Catalog Number 39080. Before proceeding, refer to the catalog number of the pad-mounted gear, which is stamped on the nameplate affbed to the enclosure door. For retrofitting S&C Source-Transfer PMH Pad-Mounted Gear having an “R3” supplement to the catalog number, refer to S&C Instruction Sheet 663-51 1. For retrofitting S&C Source- Transfer PMH Pad-Mounted Gear hawing an “R4” supplement to the catalog number, refer to S&C Instruction Sheet 663-512. These instructions apply only in instances where the pad-mounted gear was furnished with Type AT-12 Source-Transfer Control Part Number TA-1360-1 through -16. They may also apply in instances where the pad-mounted gear was furnished with a special Type AT-12 Source-Transfer Control having a part number of the form “QTA-XXXX;” such applications must be reviewed and approved by S&C to vera their New Puhlicatlon ‘1993 suitability for retrofitting. Applications involving special pad-mounted gear (units having a catalog number of the form “CDA-XXXXXX” or “CD-XXXXXX,” or having an “-SXXX“ or “-QXXX“ suffi to the catalog number) must also be reviewed and approved by S&C. Refer to S&C InstmLction Sheet 515-500 for instruc- tions on fieldprogrammingandoperation of the Micro-AT Source-Transfer Control. Mechanical Antiparalleling Feature If the pad-mounted gear was furnished with optional m’echanical antiparalleling feature (Catalog Number Suffix “-CY or “-C17”), this feature must be discon- nected and permanently removed, in order to accom- modate the Micro-AT Source-Transfer Control. Instruc- tionsforremoval of themechanicalantiparalleling feature arealso contained in this publication. Retrofit Kit A retrofit kit is required for installing the Micro-AT Source-Transfer Control. For 14.4-kv pad-mounted gear, Retrofit Kit Catalog Number SDA-2393 is used. For 25-kv pad-mounted gear, Retrofit Kit Catalog Number SDA-2400 is used. Each retrofit kit contains parts for use with “Rl,” “RZ,” ”R3,” and “R4” vintages of pad-mounted gear. Thus, a number of parts will be le? ouer following the retrofit installation. When installing the Micro-AT Source-Transfer Control in 14.4-kv pad-mounted gear, the front panel assembly of thecontrolmustberemovedand subsequently reattached. The control is susceptible to damage from static charges during this process. For this reason, a 3M 8501 Portable Static-Dissipative Field S&C ELECTRIC COMPANY 0 Chicago S&C ELECTRIC CANADA 0 Toronto January 18,1993 INSTRUCTION SHEET 6631510 Page 1 of 23

Upload: others

Post on 20-Feb-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Instruction Sheet 663-510 - sandc.com

SBC Source-Transfer

In Gear Having “ R l ” or “R2” Outdoor Distribution (14.4 kv and 25 kv) With Micro-AT’“ Control PMH Pad-Mounted Gear Replacing Type AT-1 2 Control

Supplement to the Catalog Number

INSTRUCTIONS For Field Replacement

I TABLE OF CONTENTS I Section Page Number Section Page Number INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 REMOVING THE MECHANICAL ANTIPARALLELING

CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INETALLING THE MICRO-AT SOURCE-TRANSFER REMOVING THE TYPE AT-12 SOURCE-TRANSFER FEATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

c:oNTRoL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

I INTRODUCTION I

The equipment covered by this publication must be selected for a specific application and it must be installed, operated, and maintained by qualified persons who are thoroughly trained and who understand any hazards that may be involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment.

This publication provides instructions for field removal of the Type AT-12 control which was originally furnished in S&C Source-Transfer PMH Pad-Mounted Gear having an “Rl” or “R2” supplement to the catalog number, and its replacement with Micro-AT Source- Transfer Control Catalog Number 39080.

Before proceeding, refer to the catalog number of the pad-mounted gear, which is stamped on the nameplate affbed to the enclosure door. For retrofitting S&C Source-Transfer PMH Pad-Mounted Gear having a n “R3” supplement to the catalog number, refer to S&C Instruction Sheet 663-51 1. For retrofitting S&C Source- Transfer PMH Pad-Mounted Gear hawing an “R4” supplement to the catalog number, refer to S&C Instruction Sheet 663-512.

These instructions apply only in instances where the pad-mounted gear was furnished with Type AT-12 Source-Transfer Control Part Number TA-1360-1 through -16. They may also apply in instances where the pad-mounted gear was furnished with a special Type AT-12 Source-Transfer Control having a part number of the form “QTA-XXXX;” such applications must be reviewed and approved by S&C t o v e r a their

New Puhlicatlon ‘1993

suitability for retrofitting. Applications involving special pad-mounted gear (units having a catalog number of the form “CDA-XXXXXX” or “CD-XXXXXX,” or having an “-SXXX“ or “-QXXX“ suf f i to the catalog number) must also be reviewed and approved by S&C.

Refer to S&C InstmLction Sheet 515-500 for instruc- tions on field programming and operation of the Micro-AT Source-Transfer Control.

Mechanical Antiparalleling Feature If the pad-mounted gear was furnished with optional m’echanical antiparalleling feature (Catalog Number Suffix “-CY or “-C17”), this feature must be discon- nected and permanently removed, in order to accom- modate the Micro-AT Source-Transfer Control. Instruc- tions for removal of the mechanical antiparalleling feature are also contained in this publication.

Retrofit Kit A retrofit kit is required for installing the Micro-AT Source-Transfer Control. For 14.4-kv pad-mounted gear, Retrofit Kit Catalog Number SDA-2393 is used. For 25-kv pad-mounted gear, Retrofit Kit Catalog Number SDA-2400 is used. Each retrofit kit contains parts for use with “Rl,” “RZ,” ”R3,” and “R4” vintages of pad-mounted gear. Thus, a number of parts will be l e ? ouer following the retrofit installation.

When installing the Micro-AT Source-Transfer Control in 14.4-kv pad-mounted gear, the front panel assembly of the control must be removed and subsequently reattached. The control is susceptible to damage from static charges during this process. For this reason, a 3 M 8501 Portable Static-Dissipative Field

S&C ELECTRIC COMPANY 0 Chicago S&C ELECTRIC CANADA LTD. 0 Toronto January 18,1993

INSTRUCTION SHEET 6631510 Page 1 of 23

Page 2: Instruction Sheet 663-510 - sandc.com

S&C Source-Transfer With Micro-AT’” Control PMH Pad-Mounted Gear Replacing Type AT-1 2 Control

In Gear Having “ R l ” or “R2” Outdoor Distribution (14.4 kv and 25 kv) Supplement to the Catalog Number

REMOVING THE TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued I step 10 (e) If the pad-mounted gear is furnished with optional

Remove the switch operator access panels from both decoupling feature (Catalog Number S u f f k V 8 ’ 7 : the left-hand and right-hand sides of the low-voltage Open the hinged cover labeled “Decoupling Socket” control compartment, using the following procedure. on each side. On the lt$-hand side m l g , mark the (a) Remove the bolted cover labeled ‘Terminal Blocks” position of the hinge plate on the bottom switch

on each side. See Figure 5. operator access panel, to facilitate reassembly. See (b) The top switch operator access panel on each side Figure 2. (The retrofit kit includes a replacement

is secured by four 1/4“-20 X 3/” hex-head stainless- bottom switch operator access panel for the right-

steel cap screws, lockwashers, and flat washers. hand side, so there’s no need to mark the position

See Figure 5. Two wire leads are connected to the of the hinge plate on the existing bottom switch

charging-shaft access port switch on the back of operator access panel on this side)

each panel. Remove the four screws and associated Ifthpad-mountedgear &furnished with Wt-al lockwashers and flat washers from each top switch decoupling feature (Catalog Number Suffirx: “-C8’7: operator access panel, taking care not to damage Remove the two 1/4”-20 X %” round-head stainless- the wire leads or to bend the terminals of the access steel screws that secure each hinge plate to its port switch. Retain the hardware. Mark the positions of the leads and disconnect them.

Failure to mark the original positions of the wire leads may result in improper reconnection that will render the pad-mounted gear inoperative.

663=5 1 0 INSTRUCTION SHEET Page 6 of 23 S&C ELECTRIC COMPANY Chicago January 18,1993 S&C ELECTRIC CANADA LTD. Toronto !a

Page 3: Instruction Sheet 663-510 - sandc.com

REMOVING THE TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued I

Operator target indicates whether stored-energyoperator is in switch-open or switch-closed posi-tion and whether quick-make, quick-breakmechanism is charged or discharged

Emergency-trip access cover

Open/close pushbuttons

Teirminal-blockcolmpartment

Top switch- operator

accesspanel

%”- 2 0 x vihex-head

/ stainless-steelcap screws,lockwashers,and flatwashers

Bottomswitchoperatoraccesspanel

Utility tool used for emergencymanual tripping and, if optionaldecoupling feature is furnished,for decoupling stored-energyoperator from interrupter switch

/Hinged cover provides access to reverse-drivehub and, if decoupling feature (CatalogNumber Suffix “-C8”) is furnished, to decou-pling sockets

/

IBolted cover provides access to theAT-12 control’s programming panel \

Decoupling indicator (furnishedwith optional decoupling feature)

Figure 5. Low-voltage control compartment.

INSTRUCTION SHEET 66315 10S&C ELECTRIC COMPANY l Chicago Page 7 of 23S&C ELECTRIC CANADA LTD. l Toronto January 18,1993

Page 4: Instruction Sheet 663-510 - sandc.com

S I C Source-Transfer

In Gear Having “ R l ” or “R2” Outdoor Distribution (14.4 kv and 25 kv) With Micro-AT’” Control PMH Pad-Mounted Gear Replacing Type AT-I 2 Control

Supplement to the Catalog Number

REMOVING THE TYPE AT-12 SOURCE-TRANSFER CONTROL - Continued 1 associated bottom switch operator access panel. See Figure 2. If the pad-mmnted gear is not furnished with optional decoupling feature: Remove the two ‘h””20 X ? h r r hex-head stainless- steel cap screws, lockwashers, and flat washers located near the center of each bottom switch operator access panel. See Figure 6. Retain the hardware. Detach the bottom switch operator access panel on each side by removing the three or four ?4’”20 X %” hex-head stainless-steel cap screws, lockwashers, and flat washers that secure each panel. See Figure 5. Retain the hardware. Discard the right-hand side bottom switch operator access panel.

Step 11 Disconnect the ground wire on the right side of the Type AT-12 Source-Transfer Control enclosure. See Figure 7.

Step 12 Remove the four ?4“-20 X 1“ hex-head zinc-plated cap screws, lockwashers, and flat washers at the top and bottom of the Type AT-12 Source-Transfer Control enclosure, which secure the control to the upper mounting bracket and to the lower-left and lower-right mounting brackets. See Figure 8. Discard the hardware.

Step 13 Remove the Type AT-12 Source-Transfer Control from the low-voltage control compartment by sliding it forward, to the right, and out from behind the center channel.

Step 14 The lower-left mounting bracket of the Type AT-12 Source-Transfer Control is secured by two weld studs and two 1/4”“20 zinc-plated serrated hex nuts. See Figure 8. Remove the hex nuts and rest the lower-left mounting bracket in the bottom of the low-voltage control compartment. Retain the hardware. Do not disconnect the w i r ing harnesses f r m the m n t i n g braclcet at this time.

Step 15 The lower-right mounting bracket of the Type AT-12 Source-Transfer Control is secured by a weld stud and a ‘h””20 zinc-plated serrated hex nut. See Figure 8. Remove and discard the lower-right mounting bracket. Retain the hardware.

Step 16 For pad-mounted gear models not furnished with optimal mechanical antiparalleling feature (Le., those models not hawing Catalog Number Sufffirr: “-C7” or ‘ ‘T17’9: To avoid interference with the Micro-AT control, it will be necessary to break off the two 5/16”-l8 X 1” weld studs on the back wall of the low- voltage control compartment, to which the lower mounting plate of the antiparalleling mechanism (on units having this option) is attached. See Figure 9 and Sections “A-A” and “B-B” on Drawing RD-3582 (furnished in the retrofit kit).

Attach a flat washer and hex nut to each of the two weld studs. Tighten each hex nut, using a deep-well socket, until the weld fails . . . the break must be within % inch of the back wall. Proceed to “INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL.”

Figure 6. Hardware to be removed near center of bottom switch operator access panel on pad-mounted gear models not furnished with optional decoupling feature.

663.5 1 0 INSTRUCTION SHEET Page 8 of 23 S&C ELECTRIC COMPANY Chicago January 18,1993 S&C ELECTRIC CANADA LTD. Toronto

Page 5: Instruction Sheet 663-510 - sandc.com
Page 6: Instruction Sheet 663-510 - sandc.com

S&C Source-Transfer

Outdoor Distribution (14.4 kv and 25 kv) With Micro-AT’” Control PMH Pad-Mounted Gear Replacing Type AT-I2 Control

In Gear Having “ R I ” or “R2” Supplement to the Catalog Number

REMOVING THE MECHANICAL ANTIPARALLELING FEATURE I If the pad-mounted gear is furnished with optional mechanical antiparalleling feature (Catalog Number Suffix “-C7” or “-C17”), this feature must be discon- nected and permanently removed using the following procedure, in order to accommodate the Micro-AT Source-Transfer Control.

Step 1 Remove and discard the l/ld’ X %” stainless-steel cotter pin which connects each link of the antiparalleling mechanism to its respective switch drive lever. See Figure 9.

Step 2 Remove and discard the four %.f-l8 zinc-plated serrated hex nuts which are used to attach the upper

and lower mounting plates of the antiparalleling mechanism. See Figure 9. Discard the antiparalleling mechanism.

Step 3 To avoid interference with the Micro-AT control, it wiLl be necessary to break off the two 5/16”-18 X 1“ weld studs on the back wall of the low-voltage control compartment, to which the lower mounting plate of the antiparalleling mechanism is attached. See Figure 9 and Sections “A-A” and “B-B” on Drawing RD-3582 (furnished in the retrofit kit).

Attach a flat washer and hex nut to each of the two weld studs. Tighten each hex nut, using a deep-well socket, until the weld fails . . . the break must be within Vi inch of the back wall.

I

I

Figure 9.

4 t

Removing mechanical antiparalleling feature.

663m5 1 0 INSTRUCTION SHEET Page 10 of 23 S&C ELECTRIC COMPANY Chicago January 18,1993 S&C ELECTRIC CANADA LTD. Toronto

Page 7: Instruction Sheet 663-510 - sandc.com

INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROLI

Step 1The ground wire, which was formerly connected to theType AT-12 Source-Transfer Control, must be reroutedacross the center channel to the left-hand side of thelow-voltage control compartment. Carefully cut the tiewraps securing the ground wire to the main wiringharness as necessary, and weave the ground wire acrossthe center channel and over to the left-hand side. SeeFigures 7 and 10.

Step 2Install Lower Mounting Bracket Assembly Part NumberSDA-2389 (furnished in the retrofit kit), using thefollowing procedure.

lower mounting bracket assembly. See Figure 10.Orient the receptacle so that the keyways are

(a) Attach the receptacle end of Input ExtensionWiring Harness “D” Part Number SDA-2363(furnished in the retrofit kit) to the back of the

positioned identically with those of the inputreceptacle on the lower-left mounting bracket forthe Type AT-12 Source-Transfer Control. Use two#6-32 X %” round-head stainless-steel machinescrews and self-locking hex nuts (furnished in theretrofit kit) to secure the receptacle.

(b) Attach the lower mounting bracket assembly to thethree weld studs which were formerly used toattach the lower-left and lower-right mountingbrackets for the Type AT-12 Source-TransferControl. See Figure 10. Use three l/Y’-20 zinc-platedserrated hex nuts to secure the lower mountingbracket assembly. Finger-tighten the hex nuts.

(c) Attach the plug end of Extension Wiring Harness“C” Part Number SDA-2364 (furnished in theretrofit kit) to the shorting receptacle on the lowermounting bracket assemblv. See Figure 10.

I \Ground wire

Lower-left mountingbracket for Type AT-12Source-Transfer Control

#6-32 X ‘h”round-headstainless-steelmachine screwsand self-lockinghex nuts

1\ Extension Wiring Harness “C”

Part Number SDA-2364

Lower Mounting Bracket AssemblyPart Number SDA-2369

Figure 10. Installing lower mounting bracket assembly.

IiIINSTRUCTION SHEET 66315 10

S&C ELECTRIC COMPANY l Chicago Page 11 of 23S&C ELECTRIC CANADA LTD. l Toronto January 16,1993

Page 8: Instruction Sheet 663-510 - sandc.com
Page 9: Instruction Sheet 663-510 - sandc.com

INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL - Continued 1

(b) Loosely attach the upper mounting bracketassembly to the top of the Micro-AT Source-Transfer Control enclosure using two W-20 X W’zinc-plated serrated hex-head cap screws (fur-nished in the retrofit kit). See Figure 13.

(c) For pad-mounted gear models rated 25 kv, proceedto Step 8.

IUpper mounting bracket forType AT-12 Source-TransferControl

%“-16 X 1” zinc-platedhex-head cap screws, lock-washers, and flat washers

Figure 12. Removing hardware securing upper mountingbracket for Type AT-12 Source-Transfer Control on left-handside of low-voltage control compartment.

q S&C ELECTRtC COMPANY l ChicagoS&C ELECTRIC CANADA LTD. l Toronto

Bracket Part Number SD-2647

\

Shock-mount bushing

IAT Mounting BracketPart Number SD-2649

W - 2 0 zinc-platedserrated hex nut

-20 x ‘h”*ated hex.screw

zinc-l*head

Figure 13. Installing upper mounting bracket assembly.

INSTRUCTION SHEET 66315 10Page 13 of 23

January 16,1993

Page 10: Instruction Sheet 663-510 - sandc.com

S&C Source-Transfer With Micro-AT’” Control PMH Pad-Mounted Gear Replacing Type AT-1 2 Control

Outdoor Distribution (14.4 kv and 25 kv)

I INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL - Continued 1

In Gear Having “ R l ” or “R2” Supplement to the Catalog Number

Step 7 For pad-mounted gear models rated 14.4 kv: To avoid interference during installation, it will be necessary to temporarily remove the front panel assembly of the Micro-AT Source-Transfer Control. Since the control will then be susceptible to damage from static charges, a 3 M 8501 Portable Static-Dissipative Field Service Kit has been included in Retrofit Kit Catalog Number SDA-2393. The static-dissipative kit must be utilized until the front panel assembly is reattached in Step 12. Set up the static-dissipative kit and remove the front panel assembly of t he Micro-AT Source-Transfer Control using the following procedure. (a) Open up the static-dissipative work mat in front

of the low-voltage control compartment. See Fig- ure 14.

(b) Place the Micro-AT Source-Transfer Control on the static-dissipative work mat. See Figure 14.

(c) Attach the ground cord assembly onto the work mat by means of the large black snap. Attach the alligator clip on the shorter of the two wire leads to the aluminum clip on the gearbox mounting assembly, on the left-hand side of the low-voltage control compartment. See Figure 14.

(d) Slip on the elastic wrist strap and attach the band so that it fits snugly, but comfortably. Attach the longer of the two wire leads on the ground cord assembly to the wrist band by means of the small plastic snap. See Figure 14.

(e) Remove the four #8-32 hex nuts which secure the front panel assembly to the Micro-AT Source- Transfer Control enclosure. See Figure 14. Retain the hardware. Carefully disconnect the ribbon connector from the receptacle on the back of the front panel assembly. See Figure 17. Place the front panel assembly on the static-dissipative work mat.

663m5 1 0 INSTRUCTION SHEET Page 14 of 23 S&C ELECTRIC COMPANY Chicago January 18,1993 S&C ELECTRIC CANADA LTD. 0 Toronto

Page 11: Instruction Sheet 663-510 - sandc.com

1 INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL - Continued

--

Statt~dlsslpatlvework mat

Figure 14. Setting up 3M 6501 Portable Static-Dissipative Field Service Kit prior to removing front panel assembly of Micro-ATSource-Transfer Control. Applicable only to pad-mounted gear models rated 14.4 kv.

q S&C ELECTRIC COMPANY l ChicagoS&C ELECTRIC CANADA LTD. l Toronto

INSTRUCTION SHEET 66315 10Page 15 of 23

January 16,1993

Page 12: Instruction Sheet 663-510 - sandc.com

S&C Source-TransferPMH Pad-Mounted GearOutdoor Distribution (14.4 kv and 25 kv)

Replacing Type AT-l 2 ControlWith Micro-AT’” ControlIn Gear Having “Rl” or “R2”Supplement to the Catalog Number

INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL - Continued

Step 8Attach the ground wire to the Micro-AT Source-Transfer Control enclosure. See Figure 15.

Step 9Install the Micro-AT Source-Transfer Control enclosurefrom the left-hand side of the low-voltage controlcompartment. Slide it across the center channel, andinto place. See Figure 16.

step 10Fasten the upper mounting bracket assembly on theMicro-AT Source-Transfer Control to the gearboxmounting flange and upper mounting bracket for theType AT-12 Source-Transfer Control with twoW’-16 X 1” zinc-plated hex-head cap screws, lock-

Figure 15. Connecting ground wire to Micro-AT Source-Transfer Control.

663-5 10 INSTRUCTION SHEET

washers, and flat washers (furnished in the retrofit kit).See Figure 16. Finger-tighten the cap screws.

step 11Loosely attach the Micro-AT Source-Transfer Controlenclosure to the lower mounting bracket assembly usinga W-20 X 1%” hex-head stainless-steel cap screw,lockwasher, flat washer, and Shock-Mount Insert PartNumber S-89795 (furnished in the retrofit kit). SeeFigure 16. There should be an approximate W’ gapbetween the top surface of the mounting bracketassembly and the bottom surface of the Micro-ATSource-Transfer Control enclosure. For pad-mountedgear models rated 25 kv, proceed to Step 13.

Flgure 16. Installing Micro-AT Source-Transfer Control.

S&C ELECTRIC COMPANY l Chicago -S&C ELECTRtC CANADA LTD. l Toronto la

Page 16 of 23January 16,1993

Page 13: Instruction Sheet 663-510 - sandc.com
Page 14: Instruction Sheet 663-510 - sandc.com

S&C Source-TransferPMH Pad-Mounted GearOutdoor Distribution (14.4 kv and 25 kv)

Replacing Type AT-12 ControlWith Micro-AT’” ControlIn Gear Having “Rl” or “R2”Supplement to the Catalog Number

INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL - Continued I

end of the ground bus, located under the capacitormounting bracket. Refer to Drawing RD-3617 (fur-nished in the retrofit kit). Route the Main WiringHarness along the existing wiring as required.

Step 16For pad-mounted gear models furnished with optionalremote indication feature (Catalog Number Suffk“-Y4 ‘7: Install Remote Indication Wiring Harness PartNumber SDA-2408 (furnished separately) by mating itsrectangular connector to the corresponding receptacle

on the side of the Micro-AT Source-Transfer Controlenclosure. See Figure 18. Do not twist thewiring harnessor remove any of the wire ties on it.

Step 17Install Partition Part Number SD-2883 (furnished inthe retrofit kit) in the right-hand side of the low-voltagecontrol compartment, using the following procedure.(a) Attach the top of the partition to the upper

mounting bracket for the Type AT-12 Source-Transfer Control using a L/4”-20 X 95” zinc-plated

‘14” -20 X %” zinc-plated ser-rated hex-head cap screwand serrated hex nut

Partition Part NumberSD-2883

Bottom

“L” Bracket Part Number SD

Two #lo-32 X 5/s” hex-headstainless-steel cap screws,two flat washers, and self-locking hex nuts

-2882

Figure 19. Installing partition.

6634 10 INSTRUCTION SHEETPage 18 of 23 S&C ELECTRIC COMPANY l ChicagoJanuary 18,1993 S&C ELECTRIC CANADA LTD. l Toronto

Page 15: Instruction Sheet 663-510 - sandc.com

I INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL - Continued _ _ _ _ _

1 serrated hex-head cap screw and serrated hex nut. See Figure 19 (top). Finger-tighten the screws.

(b) Attach, to the bottom of the partition, “L” Bracket Part Number SD-2882 using two #10-32 X %“hex- head stainless-steel cap screws, two flat washers, and self-locking hex nuts. See Figure 19 (bottom). Finger-tighten the screws.

(c) Attach the “ L bracket to the lower mounting bracket assembly using two #10-32 X W hex-head stainless-steel cap screws, two flat washers, and self-locking hex nuts. See Figure 19 (bottom). Securely tighten all the screws.

Step 18 Refer to Drawing RD-3617 Sheet 1 of 2 (furnished in the retrofit kit) and perform the rewiring procedure indicated for the existing wiring in the left-hand side of the low-voltage control compartment.

Step 19 Refer to Drawing RD-3617 Sheet 2 of 2 (furnished in the retrofit kit) and perform the rewiring procedure indicated for the existing wiring in the right-hand side of the low-voltage control compartment.

Step 20 Connect the left-hand switch compartment plug and the right-hand switch compartment plug to the preferred-source receptacle and alternate-source receptacle on Main Wiring Harness Part Number SDA-2333, based on the settings noted previously. See Figure 20. for pad-mwuntedgear models furnished with optional rensnte indication feature (Catalog Number Suflix “-Y4 ‘71: Connect the remote indication plug to the receptacle on Remote Indication Wiring Harness Part Number SDA-2408.

step 21 Temporarily reconnect the wire leads to the charging- shaft access port switches on the back of the top switch operator access panels for the left-hand and right-hand sides. See Figure 22. Loosely reattach the access panels. Then remove the input plug from the shorting receptacle and immediately transfer it to the input receptacle. See Figure 20.

1 Failure to immediately place the input plug on the input receptacle may result in damage to the voltage ;sensors and voltage limiters that will render the automatic-transfer scheme inoperative.

Step 22 Refer to S&C Instruction Sheet 515-500 and perform the field adjustment and programming procedures for the Micro-AT Source-Transfer Control as outlined therein. Then perform the operational testing as outlined therein.

1 If the pad-mounted gear is not furnished with &coupling feature, operational testing will result in temporary service interruptions.

INSTRUCTION SHEET 6634 10 S&C ELECTRIC COMPANY Chicago Page 19 of 23 S&C ELECTRIC CANADA LTD. 0 Toronto January 18,1993

Page 16: Instruction Sheet 663-510 - sandc.com
Page 17: Instruction Sheet 663-510 - sandc.com
Page 18: Instruction Sheet 663-510 - sandc.com

S&C Source-TransferPMH Pad-Mounted GearOutdoor Distribution (14.4 kv and 25 kv)

Replacing Type AT-1 2 ControlWith Micro-AT’” ControlIn Gear Having “Rl” or “R2”Supplement to the Catalog Number

INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL - Continued I

(c> Ifthe pad-mounted gear isfurnished with opticmadecouplingfeature (Catalog Number Suffti “T8’9:Reattach the hinged covers to the bottom switchoperator access panels for the left-hand and right-hand sides by securing each hinge plate using twoW-20 X %” round-head screws. See Figure 2. Ifthe pad-mounted gear is not furnished withoptional decoupling feature: Replace the twoW-20 X W hex-head stainless-steel cap screws,lo&washers, and flat washers located near thecenter of each bottom switch operator access panel.See Figure 6.

(d) Reconnect the wire leads to the charging-shaftaccess port switch on the back of the top switchoperator access panel for the left-hand side. SeeFigure 22. Then reattach this access panel withfour W-20 X %” hex-head stainless-steel capscrews, lo&washers, and flat washers. Be sure thatthe emergency-trip shaft and operator target arecentered in their respective port openings. See Fig-ure 21.

(e) Reconnect the wire leads to the charging-shaftaccess port switch on the back of the top switchoperator access panel for the right-hand side. SeeFigure 22. Then reattach this access panel with fourW-20 X 3/” hex-head stainless-steel cap screws,lockwashers, and flat washers. Be sure that theemergency-trip shaft and operator target arecentered in their respective port openings. See Fig-ure 21.

Step 26Replace the terminal-block access covers on the left-hand and right-hand sides of the low-voltage controlcompartment.

Step 27Remove the input plug from the shorting receptacleand immediately transfer it to the input receptacle.See Figure 20.

Failure to immediately place the mput plug on theinput receptacle may result in damage to the voltagesensors and voltage limiters that will render theautomatic-transfer scheme inoverative.

663-5 10 INSTRUCTION SHEETPage 22 of 23January 18,1993

step 28Attach the access cover assembly on the right-handside of the low-voltage control compartment, using thefollowing procedure.(a) For moo5A.s rated 14.4 kv: Attach Access Cover

Assembly Part Number SDA-2384 (furnished in theretrofit kit). See Figure 21. Secure the access coverat the top with a knurled screw, retainer, neoprenewasher, and nut; secure it at the bottom with aW-20 X 3/4” hex-head stainless-steel cap screw,lockwasher, and flat washer.

(b) For m~oMs rated 25 kv: Attach Access CoverAssembly Part Number SDA-2396 (furnished in theretrofit kit). See Figure 21. Secure the access coverat the top with a knurled screw, retainer, neoprenewasher, and nut; secure it at the bottom with aW-20 X W hex-head stainless-steel cap screw,lockwasher, and flat washer.

Figure 22. Reconnecting wire leads to charging-shaft accessport switch on the back of top switch operator access panel.

S&C ELECTRIC COMPANY l Chicago *S&C ELECTRIC CANADA LTD. l Toronto q

Page 19: Instruction Sheet 663-510 - sandc.com

I INSTALLING THE MICRO-AT SOURCE-TRANSFER CONTROL - Continued I Step 29 (,a:)

Attach the cover assembly for the Micro-AT Source- Transfer Control on the left-hand side of the low-voltage control compartment, using the following procedure. (b‘)

For models rated 14.4 kv: Attach Cover Assembly Part Number SDA-2386 (furnished in the retrofit kit). See Figure 21. Secure the cover assembly at the top and bottom with a knurled screw, retainer, neoprene washer, and nut. The front panel assembly of the Micro-AT Source-Transfer Control should be approximately centered in the opening (,:) of the cover assembly and the connectors of the Main Wiring Harness should not be exposed. If necessary, loosen the hardware which retains the Micro-AT Source-Transfer Control enclosure, reposition the enclosure, and then securely retighten the hardware. For models rated 25 kv: Attach Cover Assembly Part Number SDA-2397 (furnished in the retrofit kit). See Figure 21. Secure the cover assembly at the top and bottom with a knurled screw, retainer, neoDrene washer. and nut. The front Dane1

. _

Place the manual/automatic operation selector switch on the Micro-AT Source-Transfer Control in the “ M A N U A L ” position. Make sure that the stored-energg operators are in the same positions (open or closed) as their associated Mini-Rupter Switches by obsenring ~IJB switch-psition and operator-position targets. See Figure 2. If required, use the open/close pushbut- tons (provided control power is available) to reposition the operator(s). For each stored-energy operator, open the hinged cover labeled “Decoupling Socket.” Insert the utility tool furnished all the way into the socket to depress the spring-loaded locking pin. While maintaining the locking pin depressed, turn the utility tool clockwise 5 t o 7 complete turns, until firm resistance is felt and the “COUPLED“ target is centered in the indicator port. See Figure 2. Remove the tool. Then close the hinged cover and secure it with the knurled screw.

Step 31 asse-mbly of the Micro-AT Source-Transfer Control Place the manual/automatk operation selector switch should be approximately centered in the opening on the Micro-AT Source-Transfer Control in the of the cover assembly and the connectors of the “AUTOMATIC” posit ion and confirm that the Main Wiring Harness should not be exposed. If automatic-transfer “ready” indicator lamp is necessary, loosen the hardware which retains the illuminated. Micro-AT Source-Transfer Control enclosure, reposition the enclosure, and then securely Step 32 retighten the hardware. CLose and padlock the doors to the low-voltage control

Step 30 compartment. Make sure that the doors to the high- If tb pad-mwun&d gear is furnished with optional voltage compartments are also closed and padlocked. decoupling feature (Catalog Number Su&ik “-C8’9: Couple each stored-energy operator, using the following procedure.

INSTRUCTION SHEET 663151 0 S&C ELECTRIC COMPANY Chicago Page 23 of 23 S&C ELECTRIC CANADA LTD. Toronto January 18,1993