installation...safety warning only qualified personnel should install and service the equipment. the...

48
SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. May 2015 Installation C-Series Outdoor Units Models: 4TUK4518A10N0A 4TUK4536A10N0A 4TUK4524A10N0A 4TUK4542A10N0A 4TUK4530A10N0A 4TUK4548A10N0A May 2015 MS-SVN045A-EN DB68-05153A(1)

Upload: others

Post on 10-Feb-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

May 2015

Installation

C-Series

Outdoor Units

Models: 4TUK4518A10N0A 4TUK4536A10N0A

4TUK4524A10N0A 4TUK4542A10N0A

4TUK4530A10N0A 4TUK4548A10N0A

May 2015 MS-SVN045A-ENDB68-05153A(1)

Page 2: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

2 MS-SVN045A-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

Copyright

This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

The three types of advisories are defined as follows:

WARNINGIndicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTIONsIndicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

NOTICEIndicates a situation that could result in equipment or property-damage only.

WARNING

Proper Field Wiring and Grounding Required!

Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.

WARNING

Personal Protective Equipment (PPE) Required!

Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

• Before installing/servicing this unit, technicians

MUST put on all PPE recommended for the work

being undertaken. ALWAYS refer to appropriate

MSDS sheets and OSHA guidelines for proper PPE.

• When working with or around hazardous chemicals,

ALWAYS refer to the appropriate MSDS sheets and

OSHA guidelines for information on allowable

personal exposure levels, proper respiratory

protection, and handling recommendations.

• If there is a risk of arc or flash, technicians MUST put

on all PPE in accordance with NFPA 70E or other

country-specific requirements for arc flash

protection, PRIOR to servicing the unit.

Page 3: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Table of Contents

Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Preparing for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Minimum Operating Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Location Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Moving the Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Wall Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Ground or Roof Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Wind Baffle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Air Guide Duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Selecting Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Pipe Diameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Pipe Thickness and Temper Grade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Refrigerant Piping Maximum Length and Height Differences . . . . . . . . . 18

Storing Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Installing Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Pipe Cutting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Nitrogen Flushing While Brazing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Flared Pipe Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Connecting Piping to the Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Installing a Grounding Rod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Installing the Grounding Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Communications Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

System Leak Testing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

System Evacuation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Insulating Refrigerant Pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Calculating the Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Charging the Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Connecting the Drain Hose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

MS-SVN045A-EN 3

Page 4: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Configuring the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Units A and B (24, 30, 36, 42, 48 MBH Capacity Models) . . . . . . . . . . . . . 38Unit C (18 MBH Capacity Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Monitoring System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Changing an Outdoor Unit Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Pre-Start Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Test Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Service: Pump Down Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Relocating the Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

For Trane C-Series Ductless Systems and Related Accessories . . . . . . . . . . 47

4 MS-SVN045A-EN

Page 5: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

MS-SVN045A-EN 5

Model Number Description

Digit 1: Refrigerant

Digit 2: Brand Name

Digit 3: System type

Digit 4: Configuration type

Digit 5: Family

Digit 6: Connection type

Digit 7, 8 = Nominal capacity (Btu/h x 1,000)

Digit 9: Major development sequence

Digit 10: Electric power supply characteristics

Digit 11: Reserve for future use

Digit 12: Region of sale

Digit 13: Reserved for future use

Digit 14: Minor design sequence

Digit 15: Service digit (not used for ordering)

4 T U K 4 5 1 8 A 1 0 N 0 A

1 2 3 4 5 6 7 8 9 10 11 12 13 14

4 = R-410A

T = Mini-split outdoor unit

U = Universal match heat pump

K = Heat pump

4 = Standard model

5 = Flare

18 = 18,000 Btu/h24 = 24,000 Btu/h30 = 30,000 Btu/h36 = 36,000 Btu/h42 = 42,000 Btu/h48 = 48,000 Btu/h

A = First development sequence

1 = 208–230/60/1

0 = Not currently used

N = North America (UL or ETL)

0 = Not currently used

A = First design sequence

A = First sequenceB = Second sequence

Page 6: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Preparing for Installation

Dimensions and Weights

Figure 1. Dimensional drawing for 24 and 30 MBH capacity units (Type A)

Figure 2. Dimensional drawing for 36, 42, and 48 MBH capacity units (Type B)

Table 1. Dimensions and weights for 24 and 30 MBH capacity units (Type A)

Outdoor unit

capacity (MBH) Model number

Dimensions (WxHxD)in. (mm)

Weightlb (kg)

Shipping dimensions (WxHxD)in. (mm)

Shipping weightlb (kg)

24 4TUK4524A10N0A37.01 (940) x 39.29 (1096) x 12.99 (426)

142.20 (64.50)

39.17 (995) x 43.15 (1096) x 16.77 (426)

153.22 (69.50)

30 4TUK4530A10N0A 154.22 (69.50)

163.14 (74.00)

Table 2. Dimensions and weights for 36, 42, and 48 MBH capacity units (Type B)

Outdoor unit

capacity (MBH) Model number

Dimensions (WxHxD)in. (mm)

Weightlb (kg)

Shipping dimensions (WxHxD)in. (mm)

Shipping weightlb (kg)

36 4TUK4536A10N0A37.01 (940) x 47.64 (1210) x 12.99 (330) 194.01

(88.00) 39.17 (995) x 54.65 (1388) x 16.77 (426) 216.05 (98.00)42 4TUK4542A10N0A

48 4TUK4548A10N0A

37.01 (940)

24.4 (620)

39.2

9 (1

096)

38.3

(97

3)

15.1

(38

4)

14.2

(36

1)

13.0

(33

0)

20.8

(52

8)21

.1 (

536)

26.6

(67

6)

24.4 (620)

46.7

(11

85)

15.1

(38

4)

14.2

(361

)

12.9

9 (3

30)

22.0

(55

9)22

.3 (

566)

34.8

(88

4)

47.6

4 (1

210)

37.01 (940)

6 MS-SVN045A-EN

Page 7: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Preparing for Installation

Figure 3. Dimensional drawing for 18 MBH capacity units (Type C)

Minimum Operating Clearances

Install units as shown in the illustrations below (Figure 4, p. 7, Figure , p. 8, and Figure 6, p. 9), observing ventilation and service requirements. Space requirements are based on cooling mode operation and an outdoor temperature of 95°F (35°C). More space is required if the outdoor temperature is higher than 95°F (35°C) or if the area is easily heated by solar radiation.

Note: The front of the unit is curved and has the name brand logo on it.

Figure 4. Air flow direction

Table 3. Dimensions and weights for 18 MBH capacity units (Type C)

Outdoor unit

capacity (MBH) Model number

Dimensions (WxHxD)in. (mm)

Weightlb (kg)

Shipping dimensions (WxHxD)in. (mm)

Shipping weightlb (kg)

18 4TUK4518A10N0A 34.65 (880) x 25.12 (638) x 12.20 (310) 99.2 (45.0) 40.28 (1023) x 29.53 (750) x 16.26 (413) 105.8 (48.0)

12.20 (310)

25.12 (638)

14.33 (364)

34.65 (880) 2.60 (66)

0.47 (12)25.98 (660) 0.90 (23)

Side viewTop view

Back

FrontFront Back

MS-SVN045A-EN 7

Page 8: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Preparing for Installation

Figure 5. Minimum operating clearances for a single unit installation

Notes:

• Clearances listed in this manual are minimum for system operation. All installations shall comply with codes and standards adopted by the Authority Having Jurisdiction (AHJ).

• If a wind baffle is installed, measure the clearance from the front of the unit rather than from the front of the wind baffle, as shown in the following illustrations.

12 (3

00)

12 (3

00)

60 (1

500)

60 (1

500)

80 (2000)

12 (3

00)

6 (150) 24 (600)

60 (1

500)

12 (300)

20 (5

00)

When the air outlet is opposite a wall When air outlet is toward a wall

When three sides are blocked by a wall Top of unit is blocked and the air outlet is toward a wall

When top of unit is blocked and the air outlet is opposite the wall When from and back of unit are blocked by walls

8 MS-SVN045A-EN

Page 9: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Preparing for Installation

Figure 6. Minimum operating clearances for a multiple-unit installation

Notes:

• Clearances listed in this manual are minimum for system operation. All installations shall comply with codes and standards adopted by the Authority Having Jurisdiction (AHJ).

• If a wind baffle is installed, measure the clearance from the front of the unit rather than from the front of the wind baffle, as shown in the following illustrations.

12 (300) 24 (600) 24 (600) 24 (600)

24 (600) 24 (600)

12 (3

00)

12 (3

00)

60 (1

500)

60 (1500) 24 (600) 120 (3000) 12 (300)120 (3000)

MS-SVN045A-EN 9

Page 10: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Preparing for Installation

Location Considerations

Choose an installation location based on the following considerations:

• Install the outdoor unit:

– On a supporting structure that can bear the weight of the outdoor unit.

– With sufficient clearances around the unit for service and repairs.

– On a flat surface that does not collect rain water.

– Upright (not on its side or upside down).

– In a well ventilated location.

– Away from strong wind.

– So that passageways and thoroughfares are not blocked.

– Where there is no risk of flammable gas leakage.

– Where there is no exposure to salt, machine oil, sulfide gas, or corrosive environmental conditions.

– Away from sea breeze.

Note: For seacoast applications, block the unit from direct exposure to sea breeze by installing the unit behind a structure (such as a building) or a protective wall that is 1.5 times higher than the unit, leaving 28 in. (700 mm) of space between the wall and unit for air circulation. Consult an installation expert about taking anti-corrosion measures, such as removing salinity on the outdoor coil and applying a rust inhibitor more frequently than once a year.

– At least 9.84 ft (3 m) away from equipment that generates electromagnetic waves.

– Maintaining sufficient clearances from equipment such as radios, computers, stereo equipment.

ODU

Sea breeze

Sea breeze

Sea

Sea

Sea

Sea breezeODU

ODU

ODU

ODU

Protection walls

10 MS-SVN045A-EN

Page 11: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

– Far enough away from people living and working nearby so that hot discharge air or noise do not disturb them. For installations other than roof or ground, the minimum recommended height is 6.6 ft (2 m) to prevent passersby from being exposed to hot discharge air.

– Away from flammable materials.

• Ensure that condensate water generated by the outdoor unit can drain smoothly away from the unit.

• Install the power and communication cables in a separately installed enclosure.

• If installing on a high place such as a roof, a fence or guard rail should be installed around it to safeguard it from falling.

• If there is a potential for accumulated snow to block the air inlet or heat exchanger, install the unit on a higher base.

• R-410A refrigerant is a safe, nontoxic and nonflammable refrigerant. However, if there is a concern about a dangerous level of refrigerant concentration in the case of refrigerant leakage, add extra ventilation.

• Avoid installing the outdoor unit where corrosive gases, such as sulfur oxides, ammonia, and sulfurous gas, are produced. If unavoidable, consult with an installation specialist about using a corrosion-proof or anti-rust additive to protect the unit coils.

Fuse

Outdoor unit

Stereo

60 (1524) or more

Indoor unit Control

Air guide duct(not provided by Trane)

40 (1

016)

or m

ore

40 (1

016)

or m

ore

60 (1

524)

or m

ore

60 (1524) or more

60 (1524) or more

Fuse

8 (203)

12 (305)

Unit: inch (mm)

MS-SVN045A-EN 11

Page 12: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Preparing for Installation

Moving the Outdoor Unit

Follow these guidelines when moving the outdoor unit:

• Before moving the unit, determine a path that can support its weight.

• Do not lay the unit on its side and do not slant the unit more than 30 degrees.

• Take care to avoid injury while moving the unit; the surface of the heat exchanger is sharp.

– If moving the unit with a crane, fasten the wire rope as shown in Figure 7. To protect damage or scratches to the unit, use a spreader bar.

– If the unit is being moved a short distance by hand, two people should lift and carry it together using the transportation handles on the side of the unit, as shown in Figure 7.

Figure 7. Moving the outdoor unit

Moving by hand

Wire rope/straps

Moving with a crane

Transportation handles

Spreader bar

Wood pallet

12 MS-SVN045A-EN

Page 13: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Unit Installation

Follow these guidelines for installing an outdoor unit.

Important: The manufacturer is not responsible for damage incurred for installations that have not followed these guidelines.

Wall Mounting

Important: If the unit weighs over 132.2 lb, suspending it from a wall is not recommended.

• If installing the unit on a wall, ensure that the wall is able to support the weight of the outdoor unit and rack.

• For better weight distribution, install the rack as close to a supporting column as possible.

• To reduce vibration and to minimize noise, install isolation grommets (not provided):

– Between the supporting rack and the wall.

– Beneath the feet of the unit.

– Between the unit and the rack.

Ground or Roof Installation

• If installing the unit on the ground or on a roof, secure it to a rigid and stable base using M10 anchor bolts.

• Use zinc-plated or stainless steel nuts and bolts.

• Use a rubber washer between the bolt and the unit to prevent bimetallic corrosion.

• Consult with the authority having jurisdiction regarding adopted building codes and standards that detail securing the unit to withstand wind and seismic interruptions.

• The anchor bolt must be 0.79 in. (20 mm) or higher from surface of the base.

• Make a drain pit around the base to ensure proper drainage.

Soft rubber grommet(not provided)

RackWall

Isolation grommets

MS-SVN045A-EN 13

Page 14: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

If you cannot attach the unit to the base or if the unit needs additional support, secure it with wires as follows:

1. Loosen the four screws at the top of the unit and wrap wire around each of them.

2. Tighten the screws.

3. Stake the wires to the ground.

Figure 8. Securing the unit with wire

Anchor bolt hole Units: in. (mm)

24.4 (620)

13.0

(33

0)

14.

2 (3

61)

15.

1 (3

84)

37.0 (940) Anchor bolt hole Units: in. (mm)

26.0 (660)

12.2

(31

0)

13.

4 (3

40)

14.

3 (3

63)

34.6 (879)

Types A and B

Type C

Outdoor unit support

Base surface

Outdoor unit

Anchor bolt

0.79

in.

(20

mm

)

14 MS-SVN045A-EN

Page 15: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Unit Installation

Wind Baffle

If the outdoor unit will be operated when the ambient temperature is less than 23°F (-5°C) DB or if the outdoor unit might be exposed to direct strong winds, a wind baffle should be installed.

Drill holes in the locations shown in Figure 9 and attach the wind baffle to the unit with screws.

Figure 9. Wind baffle installation

Locations for drilling and attaching screws

Type B

Top view

7-7/8 in. (17.8 cm)or more

Locations for drilling and attaching screws

Type A

7-7/8 in. (17.8 cm)or more

Top view

Type A and B

24-5/8 in. (62.5 cm)

Width of screw strip: 5/8 in. (1.6 cm)

Type C

22-5/8 in. (62.5 cm)

Width of screw strip: 1/2 in. (1.27 cm)

Locations for drilling and attaching screws

Type C

7-7/8 in. (17.8 cm) or more

Top view

MS-SVN045A-EN 15

Page 16: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Unit Installation

Air Guide Duct

An air guide duct (not available through Trane) can be installed on the guard fan. Make sure that the installation screws for the air guide duct do not damage the copper piping.

Maintain clearances between the air guide duct and the unit as shown.

Outdoor unit

Air guide duct(not provided by Trane)

8 in. (203 mm)

12 in. (305 mm)

16 MS-SVN045A-EN

Page 17: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Refrigerant Piping

This section contains information on selecting, storing, and connecting refrigerant piping.

Selecting Refrigerant Piping

Refrigerant piping diameter, thickness, and temper is selected according to length, as specified in this section.

Notes:

• Use ACR piping, as specified in ASTM B280-13, Standard Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field Service.

• If there is a risk of decreased performance caused by pipe length, use piping that is one size larger than that specified in this section.

All systems must be selected through the manufacturer’s provided selection software and reviewed by the local sales office to ensure that all required components are accounted for and that system performance meets the specific job requirements.

Use the following procedure:

1. Obtain the selection report from the designer.

2. Mark the piping “tree” diagram with job site changes:

• Line length changes

• Vertical changes between components

• Indoor unit location changes

• Outdoor unit location changes

3. Submit changes to the designer and obtain the final report to ensure that the refrigeration lines are correctly sized and the system weigh-in charge is accurate.

Pipe Diameter

Table 4. Outdoor unit pipe diameter based on unit capacity

Outdoor unit capacity (MBH)

Liquid pipein. (mm)

Gas pipein. (mm)

181/4 in (6.35 mm)

1/2 in. (12.7 mm)

24

5/8 in. (15.88 mm)

30

3/8 in. (9.52 mm)36

42

48

MS-SVN045A-EN 17

Page 18: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Refrigerant Piping

Pipe Thickness and Temper Grade

Refrigerant Piping Maximum Length and Height Differences

Table 6 gives the maximum total refrigerant piping length and the allowable height differences between the outdoor and indoor unit.

Storing Refrigerant Piping

To prevent foreign materials or water from entering the pipe, storing method and sealing method (especially during installation) is very important. Apply correct sealing method depending on the environment (see Table 7).

CAUTION

Risk of Pipes Breaking!

If pipes with a diameter larger than 3/4 in. (19.05 mm) are specified, use semi-hard (C1220T-1/2H) or hard (C1220T-H) copper piping. If a softer copper pipe (C1220T-O) is used, the pipe may break due to its low pressure resistance and cause personal injury.

Table 5. Refrigerant pipe minimum thickness and temper grade based on pipe diameter

Outer diameterin. (mm)

Minimum thicknessin. (mm) Temper grade

1/4 (6.35) 0.028 (0.70)

Annealed(C1220T-O)

3/8 (9.52) 0.028 (0.70)

1/2 (12.70) 0.031 (0.80)

5/8 (15.88) 0.039 (1.00)

3/4 (19.05) 0.035 (0.9) Drawn(C1220T-1/2H or C1220T-H)7/8 (22.22) 0.035 (0.9)

Table 6. Maximum refrigerant piping length and height difference between indoor and outdoor units

Unit model(MBH)

Maximum total piping lengthft (m)

Maximum piping height difference between indoor and outdoor units

ft (m)

18 98 (30) 65 (20)

24164 (50.0)

98 (30)

30

36

246 (75)42

48

Table 7. Refrigerant pipe storage factors

Storage location Storage time Sealing type

OutdoorLonger than one month Pipe pinch

Shorter than one month Taping

Indoor — Taping

18 MS-SVN045A-EN

Page 19: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Refrigerant Piping

Installing Refrigerant Piping

Overview

1. Cut or extend field-supplied piping as needed. To extend pipes, braze or using flared pipe connections (not supplied). Refer to “Pipe Cutting” p. 19, “Nitrogen Flushing While Brazing” p. 20, and “Flared Pipe Connections” p. 20.)

2. Make sure that pipes are free of dirt, debris, and moisture, and do not leak. (Refer to “System Leak Testing Procedure” p. 29).

3. Braze or use flared pipe connections to install piping. Refer to “Connecting Piping to the Outdoor Unit” p. 22).

Pipe Cutting

Required tools:• Pipe cutter• Reamer• Pipe holder

1. Using a pipe cutter, cut the pipe so that the cut edge is at 90° to the side of the pipe.

2. Use a reamer to remove all burrs at the cut edge.

Examples of correctly and incorrectly cut pipes.

WARNING

Hazard of Explosion and Deadly Gases!

Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.

NOTICE:

System Component Damage!

Do not remove the seal caps from refrigerant connections, or open the service valves until prepared to braze refrigerant lines to the connections. Excessive exposure to atmosphere (> 5 min.) may allow moisture or dirt to contaminate the system, damaging valve seals and causing ice formation in system components.

Correct: 90º Oblique Rough Burr

MS-SVN045A-EN 19

Page 20: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Refrigerant Piping

Nitrogen Flushing While Brazing

While brazing refrigerant pipes, flush them with nitrogen gas. Use a pressure regulator to maintain a flow rate of 1.76 ft3/h (0.05 m3/h) or more.

Figure 10. Nitrogen flushing while brazing refrigerant pipes

Flared Pipe Connections

Clutch type and wing nut type flare tools are available for flared pipe connections.

1. Slide the flare nut over the pipe to be flared.

2. Slide the end of the pipe into the hole on the flaring bar that fits the pipe, leaving a length of pipe, determined by tool type (see table), extending above the flaring bar. Clamp it down.

NOTICE

Avoid Unit Damage!

Never braze pipe connections without performing nitrogen flushing. Failure to perform this procedure will damage the unit, resulting in capacity loss and reduced long-term reliability.

Flow meter

Pressure regulatorService valve

Nitr

ogen

Nitrogen

R-410A clutch typeConventional flare tool

Clutch type Wing nut type

0–0.020 in. 0.04–0.06 in. 0.06–0.08 in.

Length of pipe extending above flare bar

Pipe

Flaring bar

20 MS-SVN045A-EN

Page 21: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Refrigerant Piping

3. Attach the yoke to the flaring bar, centering the conical part over the end of the pipe that is extending above the flaring bar.

4. Tighten the yoke securely to flare the end of the pipe.

5. Remove the pipe. The end of the pipe that you flared should look like the end of a trumpet. See examples of correctly and incorrectly flared pipes.

6. Align the pipes and tighten the flare nuts manually and then with a spanner torque wrench, applying the torque according to pipe dimensions:

Outer diameterin. (mm)

Connectiontorque (ft·lb)

Flare dimension (in.) Flare shape (in.)

1/4 (6.35) 10.3–13.3 ft·lb 0.34–0.36

3/8 (9.52) 25.1–31.0 ft·lb 0.50–0.52

1/2 (12.70) 36.1–45.0 ft·lb 0.64–0.65

5/8 (15.88) 50.2–60.5 ft·lb 0.76–0.78

Yoke

Flaring bar

Copper pipeFlare nut

Inclined Damaged surface

Uneven thickness

Correct Cracked

R.016–.03145

°±2°

90°±

MS-SVN045A-EN 21

Page 22: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Connecting Piping to the Outdoor Unit

Pipes can be connected to the outdoor unit at the front, back, bottom, left, or right of the unit.

Note: Make at least one loop to reduce noise and vibration.

1. Remove the pipe cover from the unit. See Figure 11.

Figure 11. Pipe connections on unit

2. Remove the knock-out that you are going to use. Unused knock-outs should remain closed to prevent damage to the unit.• Take care to prevent damage to the exterior of the unit.• Remove burrs from knock-out hole edges and apply rust inhibitor.

3. Connect the pipes to the unit using flared connections or by brazing. If brazing the pipe connection, avoid damaging the service valves by wrapping them with a wet cloth. • Avoid damaging the temperature sensor. • Ensure that the connected pipes do not touch each other or make contact with the unit.• Ensure that all pipe connections are accessible for servicing and maintenance.

Service valve: low pressure (gas side)

Service valve: high pressure (liquid side)

Radiant heat vents

Liquid pipe Gas pipe

Note: The unit may appear different than the one shown, depending on the model.

22 MS-SVN045A-EN

Page 23: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Electrical Wiring

• Make at least one loop in refrigerant piping to reduce noise and vibration.

4. After making electrical connections (see “Electrical Wiring” p. 23) and insulating the pipes (see “Insulating Refrigerant Pipes” p. 32), replace the pipe cover and close the remaining gap. Make sure the radiant heat vents (Figure 11, p. 22) are not blocked.

Electrical Wiring

Observe the following precautions when making electrical connections. Refer to Figure 12 for a typical system installation diagram.

• Make all electrical connections in accordance with electrical codes and ordinances.

• All wiring must be protected from weather and damage.

• Do not disconnect or change the factory wiring inside the unit.

Figure 12. Typical system installation wiring

Make at least one loop

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

NOTICE

Use Copper Conductors Only!

Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.

Indoor unitPower cable

Outdoor unit Communication cable

Grounding

DisconnectCircuit breaker

MS-SVN045A-EN 23

Page 24: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Electrical Wiring

Power Wiring

• Multi-pole circuit breaker or disconnect is required to fully isolate the unit from all power.

• Install circuit breakers/disconnects in accordance with local and national codes.

• Select the power cable in accordance with relevant local and national regulations.

• Power cable specifications are based on an underground/ambient temperature of 86ºF (30ºC) and single multi-conductor cables. If conditions are different from these, consult an electrical installation expert and re-select the power cable. If the length of power cable exceeds 164.04 ft (50 m), re-select the power cable considering the voltage drop.

• Do not use power cable that has exposed wire.

• Unbalanced power must be maintained within 2% of supply rating among all indoor units or the unit will stop and an error code will be generated. (Significantly unbalanced power may shorten the life of the system.)

• Use a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outer cover).

• Provide strain relief for power cables.

Follow this procedure:

1. Refer to Table 8 for power cable and circuit breaker specifications, and Table 9 for conduit specifications.

WARNING

Avoid Risk of Fire or Explosion!

Do not let the power cable come into contact with the pipes inside the outdoor unit. If the power supply cable touches the pipes, the vibration of the compressor will be transferred to the pipes and can damage the power supply cables or pipes. The damage could result in fire or explosion, causing death or serious injury.

Table 8. Circuit breaker and power cable specifications

Power

RLA

FLA

MCA MOPModel Hz V Fan1 Fan2

4TUK4518A10N0A

60 208/230 N/A

0.13 — 7.8 15

4TUK4524A10N0A 0.48 — 11.7 20

4TUK4530A10N0A 0.48 — 19.4 30

4TUK4536A10N0A 0.48 0.48 22.2 35

4TUK4542A10N0A 0.48 0.48 22.2 35

4TUK4548A10N0A 0.48 0.48 22.2 35

Notes:

• Voltage tolerance is ± 2%.• Abbreviations: RLA: Rated load ampere; FLA: Full load ampere; MCA: Minimum circuit amperes ; MOP: Maximum

overcurrent protective device (amperes).

Table 9. Cable conduit specifications

Name Temper grade Application conditions

Flexible PVC conduit PVC If conduit is installed indoors and not exposed to outside elements (embedded in concrete)

Class 1 flexible conduit Galvanized steel sheet If conduit is installed indoors but exposed to outside elements

Class 1 PVC-coated flexible conduit

Galvanized steel sheet and soft PVC compound If conduit is installed outdoors and requires waterproofing

24 MS-SVN045A-EN

Page 25: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Electrical Wiring

2. Cut the power cable to an appropriate length and connect it to terminals L1 and L2 in the power supply box with a solderless ring terminal (see Figure 13).

3. If two cables are connected to one terminal, place the cables back to back with the thin cable upward and the thick cable downward, as shown in the detail in Figure 13.

4. Secure the cable(s) with a cable tie and provide strain relief.

5. Replace the cover on the terminal board.

Note: Make sure that the section of the power supply cable that has the sheath removed is inside the power supply box. If this is not possible, connect the power cable conduit to the power supply box.

6. Pull the power cable through one of the designated knock-outs at the bottom right of the outdoor unit (refer to Figure 14, p. 26).

Figure 13. Power wiring terminals

Unit capacity ScrewTightening torque for

terminal Terminals

18 MBH M4 0.9–1.3 lbf/ft (1.2–1.8 N.m) AC power: L1, L2 and Communication: F1, F2

24, 30, 36, 42, 48 MBHM3 0.4–0.5 lbf/ft (0.5–0.7 N.m) Communication: F1, F2

M5 1.5–2.2 lbf/ft (2.0–3.0 N.m) AC power: L1, L2

1(L) 2(N) NL L1

L2

L1 L2 L1 L2

Indoor unit

Main power cableCable clamp

Outdoor unit

Indoor power

Communication cable

Cable ties

L1F2

V2

F4

F1

V1

F3

L2

Solderless ring terminal

Thin cable Thick cable

Cable tie

Detail for connecting two cables to one terminal

Detail for connecting two cables to one terminal

MS-SVN045A-EN 25

Page 26: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Electrical Wiring

Figure 14. Power cable knock-outs

Grounding

Important: Grounding must be done by a qualified electrician. The unit cannot be ground by a gas or water pipe, a lightning rod, or a telephone line grounding wire.

Ground the unit at an exclusive grounding terminal, at the electrical panel (see Figure 15), or—if the power distribution circuit is not grounded or its grounding does not comply with electrical codes and specifications—to a grounding rod.

Figure 15. Outdoor unit grounding examples

Installing a Grounding Rod

If the installation requires a grounding rod is required, follow this procedure:

1. Select a grounding rod that complies with national and local codes.

2. Select a location for the grounding rod that:

• Contains hard damp soil rather than loose sand or gravel.

• Is located away from underground structures such as gas and water pipes, telephone lines, and underground cables.

• Is at least 6.6 ft (2 m) away from a lightning conductor.

3. Install the grounding rod in accordance with national and local codes.

4. Proceed with “Installing the Grounding Cable.”

Installing the Grounding Cable

1. Select rated grounding cable by referring to the outdoor unit power cable specifications (Table 8, p. 24).

2. Connect the grounding cable to the grounding hole inside the power supply box and pull it through the designated grounding knock-out.

Notes:• Remove burrs from the knock-out hole.• Use cable conduit and bushing to prevent cables from being

damaged when passing through the knock-out holes.• Apply rust-resistant paint around the knock-out hole.

Grounded to exclusive grounding terminal that is part of the structure

Grounding at the electrical panel

Grounded to grounding rod

26 MS-SVN045A-EN

Page 27: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Electrical Wiring

Note: If the grounding cable length needs to be extended, make the cable connection in accordance with national and local codes.

3. If a grounding rod was installed to ground the unit, measure the resistance with a ground resistance tester. Refer to Table 10 for resistance requirements.

• If the resistance is above the requirements, drive the grounding rod deeper into the ground or increase the number of grounding rods until the resistance requirement is achieved.

• If you have grounded the unit to a grounding terminal or electrical panel, ensure that the resistance meets the requirements.

Table 10. Grounding resistance requirements

Power condition at installation site High or average humidity Low humidity

Voltage to ground is ≤ 150 V • Ensure that the grounding resistance is <100 .• If a circuit breaker is installed that disconnects the

circuit within 0.5 seconds, the allowable grounding resistance is 30–500 .

• Ideally, grounding resistance should be <100 and should not exceed 250 .

Voltage to ground is > 150 V

• Ensure that the grounding resistance is <100 .• If a circuit breaker is installed that disconnects the

circuit within 0.5 seconds, the allowable grounding resistance is 30–500 .

MS-SVN045A-EN 27

Page 28: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Communications Wiring

Use 18 AWG, 25 pF/ft nom., 60.7 impedance, braid or foil shielded, twisted pair wire for communications wiring.

Refer to Table 9, p. 24 for cable conduit specifications.

1. Connect the communications cable wires to terminals F1 and F2, as shown in Figure 16.

Notes:

• Ensure that more than 1 in. (20 mm) of the outer sheath of the power and communication cable conduit are inside the electrical component box.

• To reduce interference, ensure that power and communication cables run in parallel with a minimum space of 2 in. (50 mm) between the cables or, if crossing is necessary, cross at 90 degrees.

• The communication cable between outdoor units and between indoor and outdoor units has no polarity.

Figure 16. Wiring terminals for communication between indoor and outdoor units

2. Provide strain relief for the communications cable.

3. Pull the communications cable through the designated knock-out at the bottom right of the outdoor unit (refer to Figure 14, p. 26).

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

1(L) 2(N) NL

L1L2

L1 L2 L1 L2

Indoor unit

Main power cableCable clamp

Outdoor unit

Indoor power

Communication cable

Cable ties

L1

F2

V2

F4

F1

V1

F3

L2

F1,F2 terminals on outdoor unit

F1,F2 terminals on indoor unit

28 MS-SVN045A-EN

Page 29: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

System Leak Testing Procedure

Before leak testing pipe connections, read all safety precautions and notes.

Notes:

• All required piping pressure tests must be completed in accordance with national and/or local codes.

• When leak-testing refrigerant systems, observe all safety precautions.

• Leak test only one circuit at a time to minimize system exposure to potentially harmful moisture in the air.

• Use R-410A refrigerant gas as a tracer for leak detection and use oil-pumped dry nitrogen to develop required test pressures.

• Use tools rated for R-410A.

• Do not remove the valve core of the charging port.

• Perform the leak test with the outdoor unit service valves closed.

WARNING

Confined Space Hazards!

Do not work in confined spaces where refrigerant or other hazardous, toxic or flammable gas may be leaking. Refrigerant or other gases could displace available oxygen to breathe, causing possible asphyxiation or other serious health risks. Some gases may be flammable and or explosive. If a leak in such spaces is detected, evacuate the area immediately and contact the proper rescue or response authority. Failure to take appropriate precautions or to react properly to such potential hazards could result in death or serious injury.

WARNING

Explosion Hazard!

Never use an open flame to detect gas leaks. It could result in an explosion. Use a leak test solution for leak testing. Failure to follow recommended safe leak test procedures could result in death or serious injury or equipment or property-only-damage.

Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or serious injury or equipment or property-only damage.

Do not exceed unit nameplate design pressures when performing a leak test. Failure to follow these instructions could result in an explosion causing death or serious injury.

MS-SVN045A-EN 29

Page 30: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Use the following procedure for leak testing pipe connections.

1. Connect the refrigerant manifold gauge hoses to the liquid side and gas side service ports on the unit, and connect the center hose to a nitrogen gas tank fitted with a pressure regulator (see Figure 17).

Figure 17. Leak testing pipe connections with a manifold gauge

2. Fill the lines with nitrogen to no more than 594.6 psi (4.1 MPa).

3. Monitor the pressure periodically for a minimum of 24 hours. If the pressure drops, use soapy water to check for leaks. Bubbles will occur if joints are not tight.

4. Release pressure in pipelines gradually.

5. Repair leaks.

6. Repeat the previous steps until the pressure remains constant.

7. Maintain 145 psi (1.0 MPa) of pressure for 15 minutes and check for further leakage. If the pressure drops, check for leaks and repair them. Repeat this step as necessary until 145 psi (1.0 MPa) of pressure is maintained for 15 minutes.

8. Remove hoses from service ports.

NOTICE

Refrigerant Pipe Damage!

When performing a leak test, use a pressure regulator to prevent an excess amount of nitrogen (over 594.6 psi [4.1 MPa]) from entering the pipes. If the pipe is filled with more than the specified amount of nitrogen in a short period of time, pipe damage may occur.

High-pressure side

Nitrogen gas

Low-pressure side

Service ports

Low-pressure (gas side) service valve

High-pressure (liquid side) service valve

30 MS-SVN045A-EN

Page 31: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

System Evacuation Procedure

After performing a leak test, use a vacuum pump to triple evacuate the system as described in the following flow chart:

Notes:

• Use a vacuum pump with a check valve to prevent pump oil from flowing backward while the vacuum pump is closed.

• Completely close the liquid-gas side service valve of the outdoor unit.

Using vacuum-rated hoses, connect the manifold gauges to the liquid and suction (and high-pressure, if applicable, gas pipes.

Evacuate the system to 750 microns.Hold for 5 minutes.

Check for leaks and repair as necessary.

Yes

Break the vacuum by applying10 psi (0.07 MPa) of nitrogen.

Over 750 microns?

No

Evacuate the system to 500 microns.Hold for 5 minutes.

YesOver 500 microns?

No

Evacuate the system to 200 microns. Wait for 15 minutes. A rise of no morethan 200 microns is acceptable.

YesOver 400 microns?

No

Break the vacuum by applying10 psi (0.07 MPa) of nitrogen.

Check for leaks and repair as necessary.

Check for leaks and repair as necessary.

Continue holding the vacuum fora total of 2.5 hours.

The system is ready for refrigerant charging.

No

Over 400 microns?(Or, if left overnight, over 750 microns?)

Check for leaks and repair as necessary.

Yes

MS-SVN045A-EN 31

Page 32: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Insulating Refrigerant Pipes

After determining that there are no leaks in the refrigerant pipes, insulate them as described:

1. Use Table 11 to select the insulation thickness according to pipe size and humidity conditions.

2. Wrap insulation around the entire surface of each pipe, including the refrigerant pipes from the indoor unit to the service valves inside the outdoor unit, the branch joints, distribution header, and connection points on each pipe.

• Do not wrap the gas and liquid refrigerant pipes together.

• If gas and liquid pipes are in contact with one another, use thicker insulation and make sure the pipes are not pressing tightly against one another.

• Overlap insulation to avoid gaps.

• Avoid compressing the insulation as much as possible.

• Be sure there are no cracks or deformities in the insulation at bends in pipes or where hangers are attached to pipes.

• If necessary, double the insulation to prevent condensation from forming in warm or humid areas.

Table 11. Pipe insulation selector

PipePipe sizein. (mm)

Insulation Type

Standard conditions 86°F (30°C), < 85%

High humidity conditions(a) 86°F (30°C), 85%

EPDM or NBR(in. (mm)

Liquid pipe1/4 (6.35) – 3/8 (9.52) 3/8 (9) 3/8 (9)

1/2 (12.70) – 2 (50.80) 1/2 (13) 1/2 (13)

Gas pipe(b)

1/4 (6.35) 1/2 (13) 3/4 (19)

3/8 (9.52)

3/4 (19) 1.0 (25)1/2 (12.70)

5/8 (15.88)

3/4 (19.05)

(a) When installing insulation in any of the following environments, use insulation required for high humidity conditions: Buildings with close proximity to bodies of water or hot springs or on the side of a hill in which the building is partly covered by earth; ceilings frequently exposed to moisture such as in restaurants, saunas, swimming pools, and corridors of dormitories or studios near a frequently used outdoor exit; buildings with no ventilation system.

(b) Internal temperature of gas pipe is higher than 248°F (120°C).

InsulationInsulation

Gas pipe

Liquid pipe

32 MS-SVN045A-EN

Page 33: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

3. Clamp insulation tightly to pipes.

4. Cut off excess insulation.

ClampInsulation

Gas side pipe

Liquid side pipe

MS-SVN045A-EN 33

Page 34: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Refrigerant

After successful leak testing and vacuum drying, calculate the amount of refrigerant needed and then charge the system, as specified in this section.

Calculating the Refrigerant

The unit is shipped from the factory with the refrigerant holding charge given in Table 12.

Refer to Table 13 for the additional refrigerant charge quantity.

Table 12. Refrigerant holding charge for each outdoor unit model

Model

4TUK4518A10N0A 4TUK4524A10N0A 4TUK4530A10N0A 4TUK4536A10N0A 4TUK4542A10N0A 4TUK4548A10N0A

Refrigerant holding charge:lb (kg)

2.87 (1.3) 4.63 (2.1) 5.73 (2.6) 6.17 (2.8) 6.17 (2.8) 6.17 (2.8)

Note: The holding charge amount takes into account the indoor unit and 25 ft (7.5 m) of pipe.

Table 13. Total additional refrigerant charge for each outdoor unit model

Model

4TUK4518A10N0A 4TUK4524A10N0A 4TUK4530A10N0A 4TUK4536A10N0A 4TUK4542A10N0A 4TUK4548A10N0A

Additional refrigerant

charge: oz/ft (g/ft)

0.11 (3.1) 0.24 (6.8) 0.35 (9.9)

34 MS-SVN045A-EN

Page 35: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Charging the Refrigerant

After calculating the correct amount of refrigerant needed by the system (see “Calculating the Refrigerant” p. 34), charge the system as described in the following procedure:

1. Attach the liquid manifold hose to the liquid side service port and open the manifold gauge valve.

2. Add the liquid refrigerant, making sure the refrigerant bottle is held in an upright position. Use a scale to determine that the correct amount has been added.

3. Close the refrigerant container immediately after adding the refrigerant.

Figure 18. Charging additional refrigerant

4. Open the outdoor unit service valves to release the charge from the outdoor unit.

5. After charging the refrigerant, replace the caps.

WARNING

Hazard of Explosion and Deadly Gases!

Do not heat the refrigerant container to speed up the charging process. An explosion could result, resulting in death or serious injury.

NOTICE

Risk of Unit Malfunction!

Do not leave the front panel open while charging refrigerant. If the front panel is open, the amount charged into the unit will be incorrect.

NOTICE

Unit Component Damage!

Open the gas side and liquid side service valves completely after charging the refrigerant. If you operate the unit with the service valves closed, the unit may be damaged.

Manifold gauge

MS-SVN045A-EN 35

Page 36: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Connecting the Drain Hose

Condensed water must be safely drained away from the unit through a drain hose.

To install the drain hose:

Note: A minimum space of 1.96 in. (50 mm) must be allowed between the bottom of the outdoor unit and the supporting base to facilitate drain hose installation.

1. Insert the drain connector into the drain hole on the underside of the outdoor unit.

2. Connect the drain hose to the drain connector.

3. Plug the unused drain holes with drain plugs.

3.15 in. (80 mm)

0.51 in. (13 mm)

Drain hose

Bottom of outdoor unit

Drain plug

Types A and B Type C

Drain hole (2)

Drain plug (5)

Drain hole (1)

Drain plug (4)

36 MS-SVN045A-EN

Page 37: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Control System

The functions of the 7-segment display, DIP switches, and K buttons are explained in this section.

Refer to Figure 19 for how they are identified on the control board.

Figure 19. Location of 7-segment display, DIP switches, and K buttons on control board

WARNING

Hazardous Voltage!

Before making contact with the inverter circuit board, wait for at least 15 minutes after powering down the outdoor unit to allow the unit to fully discharge high DC voltage. Failure to allow the high DC voltage to discharge completely could result in death or serious injury.

K5 K6 K7 K8 K9 K10 K11 K12

K1 K2 K3 K4

SW507 SW508

Type A and B models: 24, 30, 36, 42, and 48 MBH

7-segment display, two DIP switches, four K buttons

K1 K2 K3 K4

7-segment display, one DIP switch, four K buttons

Type C models: 18 MBH

MS-SVN045A-EN 37

Page 38: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Control System

Configuring the System

Units A and B (24, 30, 36, 42, 48 MBH Capacity Models)

Type A and B units have a control board with two DIP switches (Figure 19 shows their locations). DIP switch configurations are explained in Table 15 and Table 14.

Table 14. Units A and B: DIP switch SW508 (K9–K12)

SW508 On (default) Off

K9 Auto Silence Mode(a)

(a) Auto Silence Mode requires a locally purchased time relay, which enables remote control of this function.

Manual Silence Mode(b)

(b) Manual Silence Mode requires further configuration using DIP switch SW507 (see Table 15).

K10

Not used.K11

K12

Table 15. Units A and B: DIP switch SW507 (K5–K8)

SW507 Setting Function description

Snow prevention control

K6On Disables snow prevention control (default)

Off Enables snow prevention control(a)

(a) When snow prevention control is enabled, eco mode (standby mode) is not functional.

Silence mode control (for manual function; see Table 14)

K7 OnDisable silence mode option

K8 On

K7 OnSilence mode 1st step

K8 Off

K7 OffSilence mode 2nd step

K8 On

K7 OffSilence mode 3rd step

K8 Off

ON

1 2 3 4K5 K6 K7 K8

ON

1 2 3 4K9K10 K11 K12

SW507 SW508

38 MS-SVN045A-EN

Page 39: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Control System

Unit C (18 MBH Capacity Models)

Type C units have a control board with one DIP switch (Figure 19 shows its location). DIP switch configurations are explained in Table 16.

Table 16. Unit C: DIP switch SW02 (K1–K4)

DIP switch Setting Function description

Snow prevention control

K1On Disables snow prevention control (default)

Off Enables snow prevention control(a)

(a) When snow prevention control is enabled, eco mode (standby mode) is not functional.

Silence mode control

K3 OnDisable silence mode option

K4 On

K3 OnSilence mode 1st step

K4 Off

K3 OffSilence mode 2nd step

K4 On

K3 OffSilence mode 3rd step

K4 Off

ON

1 2 3 4K1 K2 K3 K4

SW02

MS-SVN045A-EN 39

Page 40: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Control System

Monitoring System Settings

Button K4 is pushed once to view system settings, as described in Table 17

Table 17. Button K4: System settings

Number of times

button K4 is pressed Setting

7-segment display

UnitDigit 1 Digit 2 Digit 3 Digit 4

1 Order frequency 1 Hundreds’ digit Tens’ digit Ones’ digit Hz

2 Current frequency 2 Hundreds’ digit Tens’ digit Ones’ digit Hz

3Number of connected indoor units

3 0 0 1 Each

4 Sensor for outdoor intake 4 ± Tens’ digit Ones’ digit °C

5 Discharge sensor 5 Hundreds’ digit Tens’ digit Ones’ digit °C

6 Eva-Mid sensor 6 ± Tens’ digit Ones’ digit °C

7 Condensate sensor 7 ± Tens’ digit Ones’ digit °C

8 Current 8 Tens’ digit Ones’ digit Tenths’ digit (decimal) A

9 Fan speed 9 Thousands’ digit Hundreds’ digit Tens’ digit rpm

10Target discharge sensor

A Hundreds’ digit Tens’ digit Ones’ digit °C

11 MAIN EEV B Hundreds’ digit Tens’ digit Ones’ digit step

12 Capacity sum of indoor units C Tens’ digit Ones’ digit Tenths’ digit

(decimal) kW

13 Protective control D

0: Cooling1: Heating

Protective control0: No protective control1: Freezing2. Non-stop defrosting3: Overload4: Discharge5: Total electric current

Frequency status0: Normal1: Hold2: Down3: Up limit4: Down limit

14Temperature of heat radiating plate

E Hundreds’ digit Tens’ digit Ones’ digit —

15 Software version F — — — —

40 MS-SVN045A-EN

Page 41: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Control System

Button K4 is pushed in sequence to view software versions and unit addresses, as described in Table 18.

Changing an Outdoor Unit Address

If multiple outdoor units are connected to a central control—VRF SC, VRF SC+BACnet®, or a VRF Touchscreen—it may be necessary to manually address the outdoor units. Addresses available for outdoor units range from 00 to 15. Refer to Table 19.

Table 18. Button K4: Software versions and unit addresses

Button K4 is pressed in sequence

(number of times)Software version/

Unit address

7-segment display

Digit 1: Year (Hex)

Digit 2: Month (Hex)

Digit 3: Date (Tens’ digit)

Digit 4: Date (Ones’ digit)

1, and held 3 seconds Main circuit board version

1 Inverter board version

1 EEPROM version

Digit 1 Digit 2 Digit 3 Digit 4

1 Automatically assigned unit addresses A 0 0 1

1 Manually assigned unit addresses A 0 0 1

Table 19. Address change for multiple outdoor units on VRF Central Control or Touchscreen Control

Button K2 action Operation Display view

Press K2 and hold for 2 seconds

Displays outdoor unit address.

If auto addressed, 00 AU will appear.

If manually addressed, the display will show 00 00 through 00 15.

The example in the next column shows that the address was manually set to 03.

Press and release K2 repeatedly

Cycles through OD unit addresses:00 00, 00 01, 00 02, . . . 00 15, then back to 00 AU.

Press K2 and hold until display flashes and relays click.

Saves the address that appears on the display.

The example in the next column shows that the address was manually set to 02.

Notes:

• To exit without saving, press and release K1.• After saving the address setting, wait at least 3 minutes before starting the system• After the manually set address is saved, the display will begin scrolling through the indoor unit addresses.

MS-SVN045A-EN 41

Page 42: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Pre-Start Checks

After installation and before the test operation is conducted, perform the following pre-start checks:

• Ensure that the auxiliary circuit breaker is providing power to the outdoor unit: 1-phase power supply (L1,L2).

• Ensure that the thermistor sensor, drain pump and hose, and wireless receiver are correctly connected.

• Ensure that the power and communication cables of the indoor and outdoor units are properly connected.

• Before supplying power, use a resistance tester to verify that resistance to ground is greater than 30 M.

• Ensure that the indoor unit is connected.

• Check for a short-circuit between the communication terminal and ground.

• Ensure that the pre-start checklist (Table 20) has been completed.

NOTICE

Avoid Damage to the Communication Circuit!

Do not measure the communication terminal with an insulation tester. Doing so will damage the communication circuit.

Table 20. Pre-start checklist

Installation

Outdoor unit

• Have you checked the external surface and the inside of the unit for damage?• Is there any possibility of short circuit due to the heat produced by the outdoor unit?• Is the place well-ventilated and meets recommended requirements for clearances and service?• Is the outdoor unit installed securely to withstand external forces?

Indoor unit• Have you checked the external surface and the inside of the indoor unit?• Is there enough space for service?• Have you ensured that the center of the indoor unit is installed horizontally and is level?

Refrigerant pipe

• Have you selected the correct pipes?• Are the liquid and gas valve open?• Is the total number of connected indoor units within the allowable range?• Are the length and the height difference between the refrigerant pipes within the allowable

range?• Has the connection of liquid and gas pipes been correctly performed?• Have you selected correct insulator for pipes and insulated them correctly?• Is the pipe or connection part properly insulated?• Is the quantity of the additional refrigerant correctly weighed in? (You must record the amount

of additional refrigerant charging on the service record paper placed outside the outdoor unit.)

Drain pipe

• Have you checked whether the drain pipes of the indoor unit and outdoor unit are connected together?

• Have you completed the drain test?• Is the drain pipe properly insulated?

Electrical

• Are the power cable and communication cable tightened firmly on the terminal board within the rated torque recommendations?

• Have you checked for cross connection of the power and communication cables?• Have the outdoor unit been properly grounded?• Is the communication cable shielded?• Is the wire length within the recommended limit?• Is the wiring route correct?

Setting address• Are the address of the indoor and outdoor units properly set?• Are the address of the indoor and outdoor units properly set, if multiple remote controllers are

to be used?

Option • Ensure that the vibration-isolation structure is correctly installed or if one needs to be installed.

42 MS-SVN045A-EN

Page 43: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Test Operation

After all pre-start checks (refer to “Pre-Start Checks” p. 42) have been have been completed, run the test operation under the following conditions:

1. Before powering the unit, heed the precautions given above for the test operation.

Note: When power is supplied to the outdoor unit, it will check for and verify communications with the indoor unit.

2. Ensure that the front of the outdoor unit is closed.

WARNING

Hazardous Voltage, Rotating Components!

Do not operate the product with the panel or duct outlet protection net off. There is risk of personal injury from parts that rotate or contain high voltage.

CAUTION

Risk of Burn or Frostbite!

Refrigerant pipe may be hot or cold during or right after the operation depending on the status of the refrigerant which flows through the refrigerant pipe, compressor, and other parts of the refrigerant cycle. Do not touch the refrigerant pipe during or immediately after the operation to avoid getting burned or frostbitten.

NOTICE

Avoid Unit Damage!

Wait at least 5 minutes before turning off the main power after the test operation is finished. If you do not, water leakage or other problems may occur.

Wait at least 3 hours after power is supplied to the outdoor unit before operating it to allow time for the crank case heater to pre-heat. If the crank case heater is not pre-heated before operation, unit parts are at risk of being seriously damaged.

122 (50)

104 (40)

86 (30)

68 (20)

50 (10)

32 (0)

14 (-10)

-4 (-20)41 (5) 50 (10) 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40) 113 (45)

Cooling

Heating

Indoor temperature: °F (°C)

Out

door

tem

pera

ture

: °F

(°C

)

Notes:

• Within the temperature range marked with hashed lines, system protection control may trigger during the test operation. If this occurs, test results may be inaccurate.

• If the unit responds to outdoor conditions by operating in defrost mode, test results may be inaccurate.• If the temperature is outside of the guaranteed range, test accuracy may decrease to the borderline area shown in

the graph.

MS-SVN045A-EN 43

Page 44: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Test Operation

3. Press buttons K1 or K2 to run the test operation as described in the Table 21, p. 44 and Table 22, p. 44.

4. The first two digits of the 7-segment display respond as shown in the last column of the tables.

5. After 12 minutes of stable operation, check the following:

• Cooling mode (indoor unit check): Inlet air temperature–outlet air temperature 18°F (–7.8°C) (reference only)

• Heating mode (indoor unit check): Inlet air temperature–outlet air temperature 19.8°F (–6.8°C) (reference only)

• In heating mode, the indoor fan motor can remain off to avoiding blowing cold air into the heated space.

6. Press the K3 button for more than 1 second to reset the outdoor unit power supply, to de-activate test mode, or to reset an error code.

Table 21. Button K1

Number of times K1 is pressed Operation

7-segment display: Digits 1 and 2

1 Heating test mode

2 Defrost test mode

Table 22. Button K2

Number of times button K2 is

pressed Operation7-segment display:

Digits 1 and 2

1 Cooling test mode

2Inverter check function(load control board inspection operation).

3 Pump down in cooling mode

44 MS-SVN045A-EN

Page 45: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Service: Pump Down Procedure

1. Remove the cap from the low pressure side.

2. Close the gas side service valve, connect a manifold gauge to the valve, and open the valve again.

3. Press the K2 button once on the outdoor unit control board to set the unit to the cooling test mode. (Make sure the compressor is running.)

4. Close the liquid side service valve.

5. When the manifold gauge indicates that the pressure is lower than 0 psig (0 MPa), close the gas side service valve.

6. Press the K3 button once to reset the system and stop the pump down procedure.

7. Remove the manifold gauge.

8. Cap each valve.

WARNING

Refrigerant under High Pressure!

Failure to follow code concerning could result in an explosion which could result in death or serious injury or equipment damage. The refrigerant container used to collect refrigerant from the system must be one that is exclusively designed for that purpose.

NOTICE

Equipment Damage!

Do not allow the amount of system refrigerant that is pulled into the outdoor unit during the pump down process to exceed the capacity of the outdoor unit or equipment damage may occur.

High-pressure (liquid) side

Low-pressure (gas) side

Type A and B units (24, 30, 36, 42, 48 MBH)

High-pressure (liquid) side

Low-pressure (gas) side

Type C units (18 MBH)

MS-SVN045A-EN 45

Page 46: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Relocating the Outdoor Unit

If the outdoor unit is to be moved to a different location, follow this procedure:

1. Perform the pump down procedure (“Service: Pump Down Procedure” p. 45).

2. Remove the power cord.

3. Disconnect the assembly cable from the indoor and outdoor units.

4. Remove the flare nut that connects the indoor unit to the refrigerant pipe and disconnect them.

5. Cap or plug the disconnected pipes to keep foreign matter out of them.

6. Disconnect the refrigerant pipe from the outdoor unit.

7. Cap or plug the disconnected pipes to keep foreign matter out of them.

8. Store the connection pipes with the cables, making sure you do not bend the pipes.

9. Move the indoor and outdoor units to the new location.

10. Remove the mounting plate for the indoor unit and move it to a new location.

46 MS-SVN045A-EN

Page 47: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

Warranty

Warranty

For Trane C-Series Ductless Systems and Related Accessories

Products Covered—This warranty is extended by Trane, and applies to all Trane C-Series Ductless Systems and Accessories for these products which are sold by Trane and applied in accordance with Trane specifications.

Basic Warranty—The warrantor warrants for a period of 10 years from the initial start-up or 10 years and 6 months from date of shipment, whichever is less, against failure due to defects in material and manufacture and that it has the capacities and ratings set forth in Company's catalogs and bulletins ("Warranty").

If any part of your C-Series Ductless System fails because of a manufacturing defect under normal use and maintenance within the Limited Warranty Period, the Company will furnish the required replacement part. If the compressor, outdoor coil or indoor coil should be the part that fails during the Limited Warranty Period, the affected unit will be replaced. The purchaser must pay for any and all shipping and handling charges and other costs of warranty service for the replacement part including, but not limited to, any related service labor, diagnosis calls and refrigerant.

Exclusions and Limitations—Exclusions from this Warranty include damage or failure arising from: wear and tear; corrosion, erosion, deterioration; modifications made by others to the Equipment; repairs or alterations by a party other than Company that adversely affects the stability or reliability of the Equipment; vandalism; neglect; accident; adverse weather or environmental conditions; abuse or improper use; improper installation; commissioning by a party other than Company; unusual physical or electrical or mechanical stress; operation with any accessory, equipment or part not specifically approved by Company; refrigerant not supplied by Company; and/or lack of proper maintenance as recommended by Company. Company shall not be obligated to pay for the cost of lost refrigerant or lost product. Company's obligations and liabilities under this Warranty are limited to furnishing replacement equipment or parts, at its option, FCA (Incoterms 2000) factory or warehouse (f.o.b. factory or warehouse for US domestic purposes) at Company-designated shipping point, freight-allowed to Company's warranty agent's stock location, for all non-conforming Company-manufactured Equipment (which have been returned by Customer to Company. Returns must have prior written approval by Company and are subject to restocking charge where applicable. Equipment, material and/or parts that are not manufactured by Company are not warranted by Company and have such warranties as may be extended by the respective manufacturer. COMPANY MAKES NO REPRESENTATION OR WARRANTY, EXPRESS OR IMPLIED, REGARDING PREVENTION OF MOLD/MOULD, FUNGUS, BACTERIA, MICROBIAL GROWTH, OR ANY OTHER CONTAMINATES. No warranty liability whatsoever shall attach to Company until Customer's complete order has been paid for in full and Company's liability under this Warranty shall be limited to the purchase price of the Equipment shown to be defective. EXCEPT FOR COMPANY'S WARRANTY EXPRESSLY SET FORTH HEREIN, COMPANY DOES NOT MAKE, AND HEREBY EXPRESSLY DISCLAIMS, ANY WARRANTIES, EXPRESS OR IMPLIED CONCERNING ITS PRODUCTS, EQUIPMENT OR SERVICES, INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF DESIGN, MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE, OR OTHERS THAT ARE ALLEGED TO ARISE FROM COURSE OF DEALING OR TRADE.

If you wish further help or information concerning this warranty, contact: Trane-Warrantor, 2701 Wilma Rudolph Blvd., Clarksville, TN. 37040.

MS-SVN045A-EN 47

Page 48: Installation...SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning

The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufactureroffers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com.

The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

We are committed to using environmentally

conscious print practices that reduce waste.

© 2015 Trane. All rights reserved.

MS-SVN045A-EN 29 May 2015

(NEW)