1 of 4 These instructions cover the following parts: Installation Instructions PS914 Power Supply © 2010 Ingersoll-Rand Company 1-877-671-7011 44487056 Rev. 10/10_a 44487056 To avoid risk of electric shock, turn off AC power before installing or servicing PS914 power supply. DANGER: ! PS914 Power Supply Specifications: Input 120/240 VAC, 1.4 A, 50/60Hz, High Voltage Class 1 Wiring Required Output 4 Amp DC @ 12/24 VDC May be used to power Von Duprin & Falcon EL device at 24VDC, 16A, 300ms Enclosure 14” H x 12” W x 4” D (8 knockouts, 1/2” or 3/4” ) Temperature Range 32°-120° F (0°- 49° C) Fuse F1, T6.3A 250 VAC Compliance UL 294, ULC-S318, RoHS, & FCC Part 15, Class 2 Output Compatible Boards (Optional, 2 boards maximum) 900-2RS 900-2Q 900-4R 900-4RL 900-8F 900-8P Fire Alarm Input Board (Optional) 900-FA (Requires one option board above) Battery Backup Board (Optional) 900-BB AC Monitor Output Form C Contacts, 30 VDC, 1 Amp, Resistive Load For protection against risk of fire, replace fuse with same type and rating CAUTION: ! INST. INSTRUCTIONS - 44487056 INST. INSTRUCTIONS - 44487098 INST. INSTRUCTIONS - 44487106 INST. INSTRUCTIONS - 44487080 INST. INSTRUCTIONS - 44487106 INST. INSTRUCTIONS - 44487106 INST. INSTRUCTIONS - 44487072 INST. INSTRUCTIONS - 44487064 Inputs I1,I2 Dry contacts required (Closed = Active) Connect control contacts between SC (Signal Common) and any input Outputs O1,O2 • 12/24VDC, 3A (wet) when AC powered • 9.6-13.2VDC or 19.2-26.4VDC when battery powered • May be used with PS914 to power EL device at 24VDC, 16A, 300ms • Maximum load cannot exceed power supply ratings or 3A for outputs combined Board Input Power Board requires 0.1A max. of power supply output current to operate Temperature Range 32°-120° F (0°- 49° C) Compliance UL 294, ULC-S318, RoHS, & FCC Part 15 Fire Alarm Input Accepts 900-FA Fire Alarm Board (Optional) 900-2RS Specifications: 900-BB Battery Backup (optional) Page 3 900-2RS (optional) - Page 4 (2 Zone EL Control - Individual/Sequential) 900-KL Keylock (optional) Page 2 PS914 Power Supply Pages 1-3

Upload: others

Post on 28-Dec-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation PS914 Power Supply Instructions 44487056 DANGER

1 of 4

These instructions cover the following parts:

Installation InstructionsPS914 Power Supply

© 2010 Ingersoll-Rand Company1-877-671-7011 44487056 Rev. 10/10_a

44487056

To avoid risk of electric shock, turn off AC power before installing or servicing PS914 power supply.

DANGER:!

PS914 Power Supply Specifi cations:Input 120/240 VAC, 1.4 A, 50/60Hz, High Voltage Class 1 Wiring Required

Output 4 Amp DC @ 12/24 VDCMay be used to power Von Duprin & Falcon EL device at 24VDC, 16A, 300ms

Enclosure 14” H x 12” W x 4” D (8 knockouts, 1/2” or 3/4” )

Temperature Range 32°-120° F (0°- 49° C)

Fuse F1, T6.3A 250 VAC

Compliance UL 294, ULC-S318, RoHS, & FCC Part 15, Class 2 Output

Compatible Boards(Optional, 2 boards maximum)

900-2RS900-2Q 900-4R 900-4RL900-8F 900-8P

Fire Alarm Input Board (Optional) 900-FA (Requires one option board above)

Battery Backup Board (Optional) 900-BB

AC Monitor Output Form C Contacts, 30 VDC, 1 Amp, Resistive Load

For protection against risk of fi re, replace fuse with same type and rating CAUTION:!

INST. INSTRUCTIONS - 44487056INST. INSTRUCTIONS - 44487098INST. INSTRUCTIONS - 44487106INST. INSTRUCTIONS - 44487080INST. INSTRUCTIONS - 44487106INST. INSTRUCTIONS - 44487106

INST. INSTRUCTIONS - 44487072

INST. INSTRUCTIONS - 44487064

Inputs I1,I2 Dry contacts required (Closed = Active)Connect control contacts between SC (Signal Common) and any input

Outputs O1,O2 • 12/24VDC, 3A (wet) when AC powered • 9.6-13.2VDC or 19.2-26.4VDC when battery powered• May be used with PS914 to power EL device at 24VDC, 16A, 300ms • Maximum load cannot exceed power supply ratings or 3A for outputs combined

Board Input Power Board requires 0.1A max. of power supply output current to operate

Temperature Range 32°-120° F (0°- 49° C)

Compliance UL 294, ULC-S318, RoHS, & FCC Part 15

Fire Alarm Input Accepts 900-FA Fire Alarm Board (Optional)

900-2RS Specifi cations:

900-BB Battery Backup (optional)Page 3

900-2RS (optional) - Page 4(2 Zone EL Control - Individual/Sequential)

900-KL Keylock (optional)Page 2

PS914 Power Supply Pages 1-3

F1

DANGER

!

! DANGER:

! WARNING:

! WARNING:

Page 2: Installation PS914 Power Supply Instructions 44487056 DANGER

2 of 4

1 MOUNT POWER SUPPLY

1a Mark 2 Top Holes 1b Secure Enclosure with 4 Screws

MOUNTING NOTES

The PS914 must be installed in accordance with the article 760 of the National Electrical Code or NFPA 72,Canadian Electrical Code, or any other applicable codes.

Install the PS914 indoors within the protected premises.

Check national and local codes for additional installation requirements.

Enclosure must be fi rmly mounted to a solid surface using hardware suitable for the surface.

x

x

2 SECURE ENCLOSURE DOOR

If No Keylock Enclosure will be secured with 2 screws as shown (done as last step)

If Keylock Remove knockout and insert key cylinder, then slide in clip

ab

OR

Board not shown for clarity

Page 3: Installation PS914 Power Supply Instructions 44487056 DANGER

3 of 4

3 PS914 SETUP AND TESTING

F1

DC Output (Red LED)

12/24 VDCOutput Terminals

AC Input (Green LED)AC Monitor

Active when AC present and F1

fuse not open (Form C dry

contacts)

NC C NO

24

12

900-BB Connector

If AC LED is off, turn off AC breaker prior to checking F1 fuse

! DANGER:

High Voltage

If main board must beremoved, turn off AC powerand wait 8 minutes before removal

Do not remove this cover, noserviceable parts

DANGER!

3a Connect AC Wiring

NE

U LIN

E

Green (Ground)

White (Neutral)

Black (Hot)

AC (In)120/240

VAC

AC Input

Use Jumper to Select Use Jumper to Select 24 VDC or 12 VDC Output

3b

! DANGER: Ensure AC Breaker is Turned Off

OR

12 VDCOutput Setting

24 VDCOutput Setting

Minimum of 1/4” separationbetween AC and DC wiringas well as power limited andnon-power limited.

Note:

4 INSTALL 900-BB BATTERY BACKUP (IF INCLUDED)

4a Place Batteries in Box with

Terminals to the Left

4b Attach Wires from Battery Board

Red wires = (+) Black wires = (-)

Note: Allow 24 hours for batteries to fully charge

Battery 1

Battery 2

Black Wires = (-)

+

+BB LED(Amber)

On-Solid

AC On

BatteriesCharging

On-Blinking

AC Off

Batteries Supplying

Power

Battery Supervision Terminals(Form C Dry Contacts)

Active

AC On

Inactive

AC Off

(Shown AC Off)

NOCNC

Red Wires = (+)

Refer to 900-BB instructionsfor additional info

5 TURN ON AC BREAKER TO TEST POWER SUPPLY

• Verify AC LED is On = GREEN• Verify DC LED is On = RED• Verify BB LED (if applicable) is On = AMBER

Page 4: Installation PS914 Power Supply Instructions 44487056 DANGER

4 of 4

6 INSTALL 900-2RS OPTION BOARD (IF REQUIRED)

7 CONNECT WIRING TO 900-2RS OPTION BOARD

Sequential Mode - Typical Wiring

Input I1 will activate both outputs

Individual Mode - Typical Wiring

Input I1 will activate output 1Input I2 will activate output 2

EL Device 2(not polarized)

AccessControl

for Device 2

EPT-2/10

EL Device 1(not polarized)

AccessControl

for Device 1

EPT-2/10

SC I1 01 I2 02 GND 2RS

120/240 VAC50/60Hz

A

B

A

B

EL Device 1(not polarized)

AccessControl

forDevices 1 & 2

EPT-2/10

EL Device 2(not polarized)

EPT-2/10

SC I1 01 I2 02 GND 2RS

120/240 VAC50/60Hz

A

B

A

Note: Fail secure output onlyallowed if approved by Authority Having Jurisdiction

6a Use Jumper to Select Use Jumper to SelectFunction

OR

Sequential Individual

6b Plug 2RS Cable into any Available Option Connector

6c Secure Board with Screws

Opt

ion

2

Opt

ion

1

1

2

If installing board in location 2, rotate board 180˚

Note: 24VDC output setting required when ELdevice connected

! DANGER: Ensure AC breaker is turned off when

installing or wiring option boards

NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK

Wire Ga(AWG)

Device Current(Amps DC)

Output*(max. ft)

Input(max. ft)

14 0.3 850

0.5 500

18 0.3 3401200

0.5 200

12 Using EL device with EPT or Door Loop(PS914 required)

200

14 100

12 Using EL device with Electric Hinge/Pivot(PS914 required)

150

14 75

Wire table (suggested maximum)

*Wiring allows for 10% voltage drop at device current at 12 or 24VDCMax. ft = one way distance between power supply and device

IF PS-914 HAS OTHER OPTION BOARDS,SEE THEIR INSTRUCTIONS

8

Page 5: Installation PS914 Power Supply Instructions 44487056 DANGER

44487080Installation

Instructions900-4RL Option Board

900-4RL Specifi cations:Inputs I1-I4 Dry contacts required (Closed = Active)

Connect control contacts between SC (Signal Common) and any input

Outputs O1-O4 • Form C contacts rated 30VDC, 3A (Dry) • 12/24VDC, 3A (Wet) when AC powered • 9.6-13.2VDC or 19.2-26.4VDC when battery powered • May be used with PS914 to power EL device at 24VDC, 16A, 300ms • Maximum load cannot exceed power supply ratings or 6A for outputs combined

Board Input Power Board requires 0.18A max. of power supply output current to operate

Temperature Range 32°-120°F (0°- 49° C)

Compliance UL 294, ULC-S318, RoHS, & FCC Part 15

Fire Alarm Input Accepts 900-FA Fire Alarm Board (Optional)

© 2010 Ingersoll-Rand Company1-877-671-7011 44487080 Rev. 10/10_a

1 INSTALL 4RL BOARD(S) INTO POWER SUPPLY

1a Review Available 900-4RLMounting Locations (Gray)

PS902

PS904

PS914

PS906

1

1 2

2

3

1

1b Plug 4RL Cable into any Available Option Connector

1c Secure Board(s) with Screws

Opt

ion

1

Opt

ion

2

Opt

ion

1

Opt

ion

3

Opt

ion

2

Opt

ion

1

PS902

PS904, 914

PS906

1

To avoid risk of electric shock, turn off AC power to power supply before installing or wiring option board

DANGER:!

Refer to installation instructions for compatible supply models - PS902, PS904, PS906, and PS914.

Note: For UL listed installations, use only UL listed locks and strikes

Page 6: Installation PS914 Power Supply Instructions 44487056 DANGER

2

1 2

1 2

1 2

ON

OFF

ON

OFF

ON

OFF

SW2

Function LED (D17)

SW1

1 2OF

F

ON

2 CHOOSE FUNCTION OF 900-4RL BOARD BY SETTING SW2 DIP SWITCHES

3 TO COMPLETE CONFIGURATION AND WIRING, GO TO APPROPRIATE SECTION

4TD

AO

SI

Four Zone Controller Function (4TD):Controls up to four inputs and four outputs with time delay. This is the default setting.Function LED will blink one time every 5 seconds

Auto Operator Function (AO):Coordinates the unlocking of one or two zones with the signaling of an auto operator.Function LED will blink two times every 5 seconds

Security Interlock Function (SI):Controls multi-door interlocks. Two through six doorsystems are possible (additional boards required for three to six doors).Function LED will blink three times every 5 seconds

For 4TD: Go to pages 3-4

For AO: Go to pages 5-6

For SI: Go to pages 7-8

Basic Troubleshooting: Go to page 8

Powered Outputs(Default)

Dry Contact Outputs(Optional)

(OPTIONAL) DRY CONTACT CONFIGURATION

Output 2

Output 4

Output 3

Output 1

Output 2

Output 4

Output 3

Output 1

Jumpers factoryinstal led

Jumperrotated 90˚

Zone 2

Zone 4

Zone 3

Zone 1

Zone 2

Zone 4

Zone 3

Zone 1

By defaul t , a l l outputs provide12/24VDC For dry contact outputs, remove appropr iate jumpers and rotate 90˚, then reinstal l (Zone 1 - Zone 4)

Page 7: Installation PS914 Power Supply Instructions 44487056 DANGER

3

4TD - SET TIME DELAY USING SW1 DIP SWITCHES

SWITCHNUMBER

4TD DIP SWITCH DEFINITIONSAll switches shown in “OFF” position in wiring diagram

Enable Time DelayAllows you to choose whichoutputs will have the below time delay.

1 Turn “ON” to enable time delay for Locking Device 1

2 Turn “ON” to enable time delay for Locking Device 2

3 Turn “ON” to enable time delay for Locking Device 3

4 Turn “ON” to enable time delay for Locking Device 4

Set Time Delay(0-75 seconds, 5 second increments)0 Sec: Switches 5-8 “OFF”75 Sec: Switches 5-8 “ON”

5 Adds 5 seconds to the time delay when “ON”

6 Adds 10 seconds to the time delay when “ON”

7 Adds 20 seconds to the time delay when “ON”

8 Adds 40 seconds to the time delay when “ON”

DIP switches on SW1 can be turned “ON” bymoving them in the direction that the arrow ispointing. Switches below shown in “OFF” position

Summary of Operation • Output turns “ON” when input is activated (closed). • Time delay begins when input is released (opened). • Locking Device output will remain “ON” during time delay. • If I1-I4 inputs are wired together, outputs will sequence.

SW1

1 2 3 4 5 6 7 8

ON

OFFSW1 SW2

12345678 12

4TD INPUT / OUTPUTTERMINAL BLOCK DEFINITIONS

Input 1 Access Control 1

Input 2 Access Control 2

Input 3 Access Control 3

Input 4 Access Control 4

Output 1* Lock 1

Output 2* Lock 2

Output 3* Lock 3

Output 4* Lock 4

*See page 2 for dry contacts

Page 8: Installation PS914 Power Supply Instructions 44487056 DANGER

4

4TD - WIRING EXAMPLE - FAIL SECURE

4TD - WIRING EXAMPLE - FAIL SAFE

GNDNC2C2NO2I2NC1C1NO1I1SC

GNDNC4

C4NO4

I4NC3

C3NO3

I3SC

4RL

120/240 VAC50/60Hz

AccessControl 2

EPT 2 or 10

EL Device 2(not polarized)

AccessControl 1

EPT 2 or 10

EL Device 1(not polarized)

PS914x 4RL

AccessControl 4

EPT 2 or 10

EL Device 4(not polarized)

AccessControl 3

EPT 2 or 10

EL Device 3(not polarized)

Note:To control EL1 & EL2 with Access Control 1, jumper I1-I2To control EL1 - EL4 with Access Control 1, jumper I1-I2-I3-I4

0-100 ft, use 14 gauge stranded wire0-200 ft, use 12 gauge stranded wire

Note: Fail secure output only allowed if approved by Authority Having Jurisdiction

GNDNC2C2NO2I2NC1C1NO1I1SC

GNDNC4

C4NO4

I4NC3

C3NO3

I3SC

4RL

120/240 VAC50/60Hz

AccessControl 2

Mag Lock 2

Mag Lock 1

AccessControl 1

PS902or

PS904or

PS906

AccessControl 4

Mag Lock 4

Mag Lock 3

AccessControl 3Note:

To control Mag Locks 1 & 2 with Access Control 1, jumper I1-I2To control Mag Locks 1 - 4 with Access Control 1, jumper I1-I2-I3-I4

Refer to Wire Table (page 7)

Page 9: Installation PS914 Power Supply Instructions 44487056 DANGER

5

AO - SET CONFIGURATION USING SW1 SWITCHES

SW1 SWITCHNUMBER

AO DIP SWITCH DEFINITIONSAll switches shown in “OFF” position in wiring diagram

Set Auto Operator Signaling OptionDetermines when the auto operator signal will be active

1 Off2 Off

Operator is signaled when latch monitor switch becomes active.Monitor switch required

1 On2 Off

Operator is signaled 0.5 seconds after control switchbecomes active. No monitor switch used.

1 Off2 On

Operator is signaled 1.0 seconds after control switchbecomes active. No monitor switch used.

1 On2 On

Operator is signaled 1.5 seconds after control switchbecomes active. No monitor switch used.

Not Used 3 Not used

Set Individual Mode or Sequential ModeIndividual Mode - One input will trigger one locking device.Sequential Mode - One input will trigger two locking devices.

4 Turn “OFF” (default) to enable Individual Mode (single doors). Turn “ON” to enable Sequential Mode (double doors).

Set Time Delay*(0-30 seconds, 2 second increments)0 Sec: Switches 5-8 “OFF”30 Sec: Switches 5-8 “ON”

5 Adds 2 seconds to the time delay when “ON”

6 Adds 4 seconds to the time delay when “ON”

7 Adds 8 seconds to the time delay when “ON”

8 Adds 16 seconds to the time delay when “ON”

DIP switches on SW1 can be turned “ON” bymoving them in the direction that the arrow ispointing. Switches below shown in “OFF” position

* Time Delay begins when an input is released.

SW1

1 2 3 4 5 6 7 8

ON

OFFSW1

12345678 12

SW2

AO INPUT / OUTPUTTERMINAL BLOCK DEFINITIONS

Input 1 Access Control 1

Input 2 Lock Monitor 1

Input 3 Access Control 2

Input 4 Lock Monitor 2

Output 1* Lock 1

Output 2* AO Signal 1

Output 3* Lock 2

Output 4* AO Signal 2

*See page 2 for dry contacts

Page 10: Installation PS914 Power Supply Instructions 44487056 DANGER

6

GNDNC2C2NO2I2NC1C1NO1I1SC

GNDNC4

C4NO4

I4NC3

C3NO3

I3SC

4RL

120/240 VAC50/60Hz

PS914x 4RL

AccessControl

for Device 2

EL-LX Device 2

Auto Operator 2

ELLX

(Optional)

EPT 10Gray

White

AccessControlfor Device 1

EL-LX Device 1

Auto Operator 1

ELLX(Optional)

EPT 10Gray

White

0-100 ft, use 14 gauge stranded wire0-200 ft, use 12 gauge stranded wire

AO - WIRING EXAMPLE - TWO SINGLE DOORS

Summary of OperationFor each door, access control input unlocks door.Latch monitor (LX) triggers auto operator.

Single Door Board Confi guration1. Position jumpers for dry contact for outputs 2 and 4 (see page 2).2. Turn on switches 5 and 6 on SW1 (6 second time delay).3. If LX is not used, turn on switch 1 on SW1.

AO - WIRING EXAMPLE - DOUBLE DOORS

Summary of OperationAccess control input unlocks both doors.Both latch monitors (LX) trigger auto operators.

Double Door Board Confi guration1. Position jumpers for dry contact for outputs 2 and 4 (see page 2).2. Turn on switches 4, 5, and 6 on SW1 (6 second time delay).3. If LX is not used, turn on switch 1 on SW1.

SW1 SW2

1 2 3 4 5 6 7 8

ON

OFF

1 2

SW1

1 2 3 4 5 6 7 8

ON

OFF

SW2

1 2

AccessControl

for Devices1 & 2

EPT 10

EL-LX Device 1 EL-LX Device 2

Auto Operator Auto Operator

White

Gray

EL EL

EPT 10

GNDNC2C2NO2I2NC1C1NO1I1SC

GNDNC4

C4NO4

I4NC3

C3NO3

I3SC

4RL

120/240 VAC50/60Hz

PS914x 4RL

Gray

White

Second auto operator,if needed

LX(Optional)

LX (Optional)

0-100 ft, use 14 gauge stranded wire0-200 ft, use 12 gauge stranded wire

Note: Fail secure output only allowed if approved by Authority Having Jurisdiction

Refer to Wire Table (page 7)

Page 11: Installation PS914 Power Supply Instructions 44487056 DANGER

7

SI - CONFIGURE SW1 DIP SWITCHES

DIP switches on SW1 can be turned “ON” bymoving them in the direction that the arrow ispointing. Switches below shown in “OFF” position

SW1

1 2 3 4 5 6 7 8

ON

OFFSW1

12345678 12

SW2

SWITCHNUMBER

SI DIP SWITCH DEFINITIONSAll switches shown in “OFF” position in wiring diagram

Enable Time DelayAllows you to choose whichoutputs will have the below time delay.

1 Turn “ON” to enable time delay for Locking Device 1

2 Turn “ON” to enable time delay for Locking Device 2

Enable Interlock

3 Turn “ON” to remove O2 from interlock (Allows a single independent door)

4 Turn “ON” for global interlock (interlocks with other SI boards that have thisswitch “ON”)

Set Time Delay (Output Active)*(0-30 seconds, 2 second increments)0 Sec: Switches 5-8 “OFF”30 Sec: Switches 5-8 “ON”

5 Adds 2 seconds to the time delay when “ON”

6 Adds 4 seconds to the time delay when “ON”

7 Adds 8 seconds to the time delay when “ON”

8 Adds 16 seconds to the time delay when “ON”

SI INPUT / OUTPUTTERMINAL BLOCK DEFINITIONS

Input 1 Access Control 1

Input 2 Access Control 2

Input 3 Lock Monitor 1

Input 4 Lock Monitor 2

Output 1* Lock 1

Output 2* Lock 2

Output 3* Follows Output 1 by .5 Sec

Output 4* Follows Output 2by .5 Sec

*See page 2 for dry contacts

GLOBAL INTERLOCKSWITCH SETTING EXAMPLES

SI Board #1

SI Board #2

SI Board #3

Application

SW1-3 SW1-4 SW1-3 SW1-4 SW1-3 SW1-4

Off Off Off Off Off Off Each SI board is a standalone, 2-door interlock.

Off On Off On Off On 6-door interlock by setting all boards “global”.

Off On On On A three-door interlock, plus an additional independent door on output 2 of SI Board #2.

Off On Off On Off Off 4-Door interlock (SI Board #1,2) and a standalone 2-door interlock (SI Board #3).

Wire Ga(AWG)

Device Current(Amps DC)

Output*(max. ft)

Input(max. ft)

14 0.3 850

0.5 500

18 0.3 3401200

0.5 200

12 Using EL device with EPT or Door Loop(PS914 required)

200

14 100

12 Using EL device with Electric Hinge/Pivot(PS914 required)

150

14 75

Wire table (suggested maximum)

*Wiring allows for 10% voltage drop at device current at 12 or 24VDC

Max. ft = one way distance between power supply and device

Page 12: Installation PS914 Power Supply Instructions 44487056 DANGER

8

SI - WIRING EXAMPLE - 2 TO 6 DOOR INTERLOCK, NORMALLY LOCKED

GNDNC2C2NO2I2NC1C1NO1I1SC

GNDNC4

C4NO4

I4NC3

C3NO3

I3SC

4RL

120/240 VAC50/60Hz

AccessControl 2

Mag Lock 2Mag Lock 1

AccessControl 1

DPS 2(contact shownwith door closed)

DPS 1(contact shown

with door closed)

PS904x 4RL

Note: Fail secure output only allowed if approved by Authority Having Jurisdiction

Refer to Wire Table(page 7)

SI Confi guration1.Turn on switches 1, 2, 4, 5, and 6 on SW1.2. Install 2 doors per SI board.3. Add up to 2 additional SI boards for a total of 6 door interlock per power supply: PS902 (2 doors maximum) PS904 (4 doors maximum) PS906 (6 doors maximum)

1 2 3 4 5 6 7 8

ON

OFF

1 2

SW1 SW2

BASIC TROUBLESHOOTING FOR ALL FUNCTIONS

Symptom Check

900-4RL Function LED (yellow) is not blinking, and inputs and outputs are inactive

Verify 900-4RL cable is plugged into an “option” connector on the main board.

Check AC wiring and AC breaker.

Check PS-900 main board F1 fuse.

Use voltmeter to verify 12 VDC or 24 VDC output on PS-900 main board.

900-4RL Function LED (yellow) is blinking, but inputs and outputs are inactive

If 900-FA option is installed onto 900-4RL, verify fi re alarm contacts are closed across FA1 and FA2.

If 900-FA option is not installed, then verify jumper wire is installed into FA-JMPR connector on the 4RL board.

Inputs and outputs behaving incorrectly. Verify 2-position DIP switch is set for proper function.Watch yellow LED to confi rm 4RL function setting . See page 2. (Verify each DIP switch is pushed into its fully-on or fully-off position.)

Verify 8-position DIP switch is set properly for your application. If you are unsure of proper settings, contact Technical Services for assistance. (Verify each DIP switch is pushed into its fully-on or fully-off position.)

Verify wiring for all input and output hardware is connected to proper terminals. (Reminder: If 900-4RL is mounted in location 1, top terminals will be GND. If 900-4RL mounted in location 2 or 3, top terminals will be SC.)

NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK

Page 13: Installation PS914 Power Supply Instructions 44487056 DANGER

Installation Instructions900-FA Fire Alarm Input

© 2010 Ingersoll-Rand Company1-877-671-7011 44487072 Rev. 10/10_a

The 900-FA Fire Alarm board can be installed on any one of the following power supply or option boards(refer to installation instructions):

(900-2RS option board shown)

• If 900-FA was factory installed, go to step 2• If installing to option board, go to 1a• If installing to PS902 main board, go to 1b

1a IF INSTALLING TO OPTION BOARD

44487072

900-2RS(2 Relay)

PS902Power Supply

900-2Q(2 Relay w/com)

900-4R(4 Relay)

900-4RL(4 Relay w/logic)

900-8F(8 Zone

Distribution-fuse)

900-8P(8 Zone

Distribution-PTC)

F1

DANGER

!

! DANGER:

! WARNING:

! WARNING:

Remove Jumper from Option Board

Install 900-FA to Option Board

Choose Option Board where 900-FA is to be Installed

1

2

3

Option board may be in any of these three locations.

Note: If using battery backup, location 3 is not available.

To avoid risk of electric shock, turn off AC power to power supply before installing or wiring 900-FA board. In the event a fi re alarm is active, this board will remove power from the PS902 DC output and any 900-series option board output.

DANGER:!

Input (Fire Alarm) Dry contacts required (Closed = no fi re alarm) Connect control contacts between FA1 and FA2

Output (Supervision) 30VDC, 1A resistive dry contact

Board Input Power Board requires 0.05A max. of power supply output current to operate

Temperature Range 32°-120° F (0°- 49° C)

Compliance UL 294, ULC-S318, RoHS, & FCC Part 15

Page 14: Installation PS914 Power Supply Instructions 44487056 DANGER

NC FA2FA1NOC

One 900-FA Board - Automatic Reset

Two 900-FA Boards on one power supplyAutomatic Reset

NC FA2FA1NOC

NC FA2FA1NOC

NC FA2FA1NOC

One 900-FA Board - Manual Reset

Two 900-FA Boards on two power suppliesAutomatic Reset

NC FA2FA1NOC

NC FA2FA1NOC

Supervision OutputContacts Shown FA Active (open)

Fire Alarm Input

NC C NO FA1 FA2Terminal Definitions

Fire Alarm ContactClosed = no fire

Open = fire

Manual Reset (Temporarily close to reset)

Fire Alarm ContactClosed = no fire

Open = fire

Fire Alarm ContactClosed = no fire

Open = fire

Fire Alarm ContactClosed = no fire

Open = fire

Note: Use 18 gauge wire for all wiring. Wire length dependent on physical layout.

Remove Jumper Install 900-FA Here

Note: Complete power failure shall result in a fail safe operation. When connected to a fire alarm releasing control unit, total loss of power for the locking mechanisms shall be configured for a fail safe operation.

1b IF INSTALLING TO PS902 MAIN BOARD

2 900-FA WIRING

NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK

Page 15: Installation PS914 Power Supply Instructions 44487056 DANGER

Installation Instructions900-BB Battery Backup

© 2010 Ingersoll-Rand Company1-877-671-7011 44487064 Rev. 10/10_a

44487064

1 INSTALL 900-BB ONTO MAIN CIRCUIT BOARD AND SECURE WITH SCREW

Plug Connector Here

Secure with Screw Here

(PS914 main board shown)

BATTERY SPECIFICATIONS

Battery Life Model PS906 = 6A @ 24V Model PS904 = 4A @ 24V Model PS902 = 2A @ 24V Model PS914 = 4A @ 24V

Battery Type 12VDC, 7Ah Gel Sealed Rechargeable Battery (2 included)5 Year Service Life

Replacement Part Number Schlage 991280

To avoid risk of electric shock, turn off AC power to power supply before installing or

wiring 900-BB board

DANGER:!

Charge only Schlage 991280 batteries. Other types may burst, causing personal injury

and damage. Observe the proper polarity when connecting the batteries.

CAUTION:!

}

Refer to installation instructions for compatible supply models - PS902, PS904, PS906, and PS914.

Suitable for Canadian Class IV standby power for access control

Page 16: Installation PS914 Power Supply Instructions 44487056 DANGER

2b Place Batteries in Box with

Terminals to the Left

2c Attach Wires from Battery Board

Red wires = (+) Black wires = (-)

2d Verify That Battery LED is On

If LED is not on, cycle AC power off and then back on.

2 INSTALL AND CONNECT BATTERIES

Note: Allow 24 hours for batteries to fully charge

2a Turn On AC Breaker to

Energize Power Supply

Battery 1

Battery 2

Black Wires = (-)

+

+BB LED(Amber)

On-Solid

AC On

BatteriesCharging

On-Blinking

AC Off

Batteries Supplying

Power

Battery Supervision Terminals(Form C Dry Contacts)

Active

AC On

Inactive

AC Off

(Shown AC Off)

NOCNC

Red Wires = (+)

NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK

Incorrect connection may cause damage to the batteries

WARNING:!

Page 17: Installation PS914 Power Supply Instructions 44487056 DANGER

Installation Instructions900-FA Fire Alarm Input

© 2010 Ingersoll-Rand Company1-877-671-7011 44487072 Rev. 10/10_a

The 900-FA Fire Alarm board can be installed on any one of the following power supply or option boards(refer to installation instructions):

(900-2RS option board shown)

• If 900-FA was factory installed, go to step 2• If installing to option board, go to 1a• If installing to PS902 main board, go to 1b

1a IF INSTALLING TO OPTION BOARD

44487072

900-2RS(2 Relay)

PS902Power Supply

900-2Q(2 Relay w/com)

900-4R(4 Relay)

900-4RL(4 Relay w/logic)

900-8F(8 Zone

Distribution-fuse)

900-8P(8 Zone

Distribution-PTC)

F1

DANGER

!

! DANGER:

! WARNING:

! WARNING:

Remove Jumper from Option Board

Install 900-FA to Option Board

Choose Option Board where 900-FA is to be Installed

1

2

3

Option board may be in any of these three locations.

Note: If using battery backup, location 3 is not available.

To avoid risk of electric shock, turn off AC power to power supply before installing or wiring 900-FA board. In the event a fi re alarm is active, this board will remove power from the PS902 DC output and any 900-series option board output.

DANGER:!

Input (Fire Alarm) Dry contacts required (Closed = no fi re alarm) Connect control contacts between FA1 and FA2

Output (Supervision) 30VDC, 1A resistive dry contact

Board Input Power Board requires 0.05A max. of power supply output current to operate

Temperature Range 32°-120° F (0°- 49° C)

Compliance UL 294, ULC-S318, RoHS, & FCC Part 15

Page 18: Installation PS914 Power Supply Instructions 44487056 DANGER

NC FA2FA1NOC

One 900-FA Board - Automatic Reset

Two 900-FA Boards on one power supplyAutomatic Reset

NC FA2FA1NOC

NC FA2FA1NOC

NC FA2FA1NOC

One 900-FA Board - Manual Reset

Two 900-FA Boards on two power suppliesAutomatic Reset

NC FA2FA1NOC

NC FA2FA1NOC

Supervision OutputContacts Shown FA Active (open)

Fire Alarm Input

NC C NO FA1 FA2Terminal Definitions

Fire Alarm ContactClosed = no fire

Open = fire

Manual Reset (Temporarily close to reset)

Fire Alarm ContactClosed = no fire

Open = fire

Fire Alarm ContactClosed = no fire

Open = fire

Fire Alarm ContactClosed = no fire

Open = fire

Note: Use 18 gauge wire for all wiring. Wire length dependent on physical layout.

Remove Jumper Install 900-FA Here

Note: Complete power failure shall result in a fail safe operation. When connected to a fire alarm releasing control unit, total loss of power for the locking mechanisms shall be configured for a fail safe operation.

1b IF INSTALLING TO PS902 MAIN BOARD

2 900-FA WIRING

NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK

Page 19: Installation PS914 Power Supply Instructions 44487056 DANGER

Installation Instructions900-BB Battery Backup

© 2010 Ingersoll-Rand Company1-877-671-7011 44487064 Rev. 10/10_a

44487064

1 INSTALL 900-BB ONTO MAIN CIRCUIT BOARD AND SECURE WITH SCREW

Plug Connector Here

Secure with Screw Here

(PS914 main board shown)

BATTERY SPECIFICATIONS

Battery Life Model PS906 = 6A @ 24V Model PS904 = 4A @ 24V Model PS902 = 2A @ 24V Model PS914 = 4A @ 24V

Battery Type 12VDC, 7Ah Gel Sealed Rechargeable Battery (2 included)5 Year Service Life

Replacement Part Number Schlage 991280

To avoid risk of electric shock, turn off AC power to power supply before installing or

wiring 900-BB board

DANGER:!

Charge only Schlage 991280 batteries. Other types may burst, causing personal injury

and damage. Observe the proper polarity when connecting the batteries.

CAUTION:!

}

Refer to installation instructions for compatible supply models - PS902, PS904, PS906, and PS914.

Suitable for Canadian Class IV standby power for access control

Page 20: Installation PS914 Power Supply Instructions 44487056 DANGER

2b Place Batteries in Box with

Terminals to the Left

2c Attach Wires from Battery Board

Red wires = (+) Black wires = (-)

2d Verify That Battery LED is On

If LED is not on, cycle AC power off and then back on.

2 INSTALL AND CONNECT BATTERIES

Note: Allow 24 hours for batteries to fully charge

2a Turn On AC Breaker to

Energize Power Supply

Battery 1

Battery 2

Black Wires = (-)

+

+BB LED(Amber)

On-Solid

AC On

BatteriesCharging

On-Blinking

AC Off

Batteries Supplying

Power

Battery Supervision Terminals(Form C Dry Contacts)

Active

AC On

Inactive

AC Off

(Shown AC Off)

NOCNC

Red Wires = (+)

NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK

Incorrect connection may cause damage to the batteries

WARNING:!