installation, operation, and maintenance · all varitrane vav models with pneumatic, electronic,...
TRANSCRIPT
SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
VariTrane™
Single-Duct and Fan-Powered Units
Installation, Operation,
and Maintenance
All VariTrane VAV models with pneumatic, electronic, DDC controls, and diffusers.
VCCF04 - 24
VCEF04 - 24
VCWF04 - 24
VAV-SVX08E-ENSeptember 2014
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
The three types of advisories are defined as follows:
WARNINGIndicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTIONsIndicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE Indicates a situation that could result in equipment or property-damage only accidents.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
• Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
• When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.
• If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
© 2014 Trane All rights reserved VAV-SVX08E-EN
Introduction
Introduction
This manual describes the installation of VariTrane™ VAV units with recommended wiring, piping, and mounting of single-duct, dual-duct, fan-powered, low-height terminal units, and diffusers.
See also the following reference documents:
• BAS-SVX40A-EN —Wireless Comm IOM
• BAS-SVX55A-EN — Wireless Comm Network Design Best Practices Guide
Receiving and Handling
VariTrane units are shipped completely assembled with the exceptions of optional attenuators for fan-powered units and accessories.
Upon receiving the equipment, complete the following:
• Locate the nameplate and refer to the model and sales order number and check that the correct units have been delivered.
• Inspect the control enclosures and air valve casing for dents or punctures.
• Verify that all options have been included, such as filters, controls, heating coils, water valves, etc. Also check that the unit voltages agree with the building parameters.
• Manually rotate fan (if applicable) to assure that there are no obstructions within the housing.
• Claims for in-transit damage must be filed immediately with the delivery carrier.
• For hot water re-heat units, check the coil fins and make sure that coils are not damaged.
• Locate and verify that the correct zone sensors are with the order. These will be marked with an orange “Accessories Enclosed” label. Store in a secure location until needed. Accessories lost at the job site are NOT covered by Trane’s warranty.
• If a discrepancy occurs between what was ordered and what is received, contact you local Trane representative immediately.
• Read appropriate section in this manual for installation procedures prior to starting equipment.
Upon receiving the equipment, please inspect each unit and components for external or internal damage. Refer to the bill of lading to insure all equipment and accessories have been received. Contact your local Trane sales representative and notify the trucking company immediately of any short ship or damaged equipment.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
Trane, VariTrane and the Trane logo are trademarks or registered trademarks of Trane in the United States and other countries. Trane is a business of Ingersoll Rand. All trademarks referenced in this document are the trademarks of their respective owners.
LonTalk is a registered trademarks of Echelon Corporation.
Revision History
VAV-SVX08E-EN (16 Sep 2014)
Updated for universal mount project.
VAV-SVX08D-EN (11 Jul 2013)
Updated model number for Sinro valve.
VAV-SVX08D-EN (27 Jun 2013)
Added Bottom Access with Cam Lock configuration and stand alone control information for UCM 4.2, VV550 LonTalk, UC400, UC210 and WCI.
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers could result in respiratory, skin or eye irritation.
VAV-SVX08E-EN 3
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings, Cautions, and Notices . . . . . . . . 2
Important Environmental Concerns . . . . . 2
Important Responsible Refrigerant Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Receiving and Handling . . . . . . . . . . . . . . . 3
Model Number Descriptions . . . . . . . . . . . . . . 5
Single-Duct Units . . . . . . . . . . . . . . . . . . . . . . 5
Dual-Duct Units . . . . . . . . . . . . . . . . . . . . . . . 8
Fan-Powered Units . . . . . . . . . . . . . . . . . . . . 9
Unit Information . . . . . . . . . . . . . . . . . . . . . . . . 11
Single-Duct Units . . . . . . . . . . . . . . . . . . . 11
Dual-Duct Units . . . . . . . . . . . . . . . . . . . . 11
Fan-Powered and Fan-Powered Low-Height Units . . . . . . . . . . . . . . . . . . . 12
Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
(SCR) Motor Speed Control Adjustment Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . 28
Electrically Commutated Motor (ECM) . . 28
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . 42
Heaters with Contactors . . . . . . . . . . . . . . . 42
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Installation of Diffusers . . . . . . . . . . . . . . . . . . 53
General . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
T-Bar Ceiling . . . . . . . . . . . . . . . . . . . . . . . 53
Concealed Spline Ceiling . . . . . . . . . . . . . 53
Drywall/Plaster Ceiling . . . . . . . . . . . . . . . 54
4 VAV-SVX08E-EN
Model Number Descriptions
Single-Duct Units
Digit 1, 2 — Unit TypeVC = VariTrane Single Duct
Digit 3—ReheatC = Cooling Only E = Electric Heat W = Hot Water Heat
Digit 4—Development SequenceF = Sixth
Digit 5, 6—Primary Air Valve04 = 4" inlet (225 cfm) 05 = 5" inlet (350 cfm) 06 = 6" inlet (500 cfm) 08 = 8" inlet (900 cfm) 10 = 10" inlet (1400 cfm) 12 = 12" inlet (2000 cfm) 14 = 14" inlet (3000 cfm) 16 = 16" inlet (4000 cfm) 24 = 24" x 16" inlet (8000 cfm)
Digit 7, 8, 9—Not Used000= N/A
Digit 10, 11—Design Sequence** = Factory Assigned
Digit 12, 13, 14, 15—ControlsDD00 Trane Actuator Only and
Enclosure DD01= UCM4 Cooling Only Control DD02= UCM4 N.C. On/Off Hot Water DD03= UCM4 Prop. Hot Water DD04= UCM4 Staged On/Off E-Heat DD05= UCM4 Pulse Width MOD E-Heat DD07= UCM4 N.O. On/Off Hot Water DD11= VV550 DDC Controller - Cooling
Only DD12= VV550 DDC Ctrl to operate N.C.
On/Off water valve DD13= VV550 DDC Ctrl to operate Prop
water valve DD14= VV550 DDC Ctrl - On/Off Electric
Heat DD15= VV550 DDC Ctrl w/Pulse Width
Modulation DD16= VV550 DDC Controller -
Ventilation Flow DD17= VV550 DDC Ctrl to operate N.O.
On/Off Water Valve DD19= VV550 DDC Controller with Flow
Tracking DD20= VV550 DDC Vent Flow cntrl to
operate N.C. water valve DD21= VV550 DDC - Vent Flow w/ On/Off
Elec Heat DD22= VV550 DDC Vent Flow cntrl to
operate prop water valve DD23= VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote (Staged EH)
DD24= VV550 DDC-Basic plus- Local (Water heat- Modulating) Remote (Water- N.C. 2 position)
DD25= VV550 DDC-Basic plus- Local (Water heat- Modulating) Remote (Water- N.O. 2 position)
DD26= VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- Modulating)
DD27= VV550 DDC-Basic plus- Local (Water heat- N.C. 2-position) Remote (Water- Modulating)
DD28= VV550 DDC-Basic plus- Local (Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
DD29= VV550 DDC-Basic plus- Local (Water heat- N.C. 2-position) Remote (Water- NC 2-position)
DD30= VV550 DDC-Basic plus- Local (Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
DD31= VV550 DDC-Basic plus- Local (Water heat- N.C. 2-position) Remote (Water- N.O. 2-position)
DD32= VV550 DDC-Basic plus- Local (Electric heat- Staged) Remote (Staged EH)
DD33= VV550 DDC Vent Flow cntrl to operate N.O. On/Off water valve
DD41= UC400 DDC-Basic (No water or electric heat)
DD42= UC400 DDC-Basic (Water heat- N.C.- 2 position)
DD43= UC400 DDC-Basic (Water heat- Modulating)
DD44= UC400 DDC-Basic (Electric heat- staged)
DD45= UC400 DDC-Basic (Electric heat- PWM)
DD46= UC400 DDC Ventilation flow- cooling only
DD47= UC400 DDC-Basic (Water heat- N.O.- 2 position)
DD49= UC400 DDC-Flow Tracking (Cooling only)
DD50= UC400 DDC-Ventilation Flow (Water heat- N. C.- 2 position)
DD51= UC400 DDC-Ventilation Flow (Electric heat- staged)
DD52= UC400 DDC-Ventilation Flow (Water heat- Modulating)
DD53= UC400 DDC-Basic plus- Local (Electric heat- PWM) Remote (Staged EH)
DD54= UC400 DDC-Basic plus- Local (Water heat- Modulating) Remote (Water- N.C. 2 position)
DD55= UC400 DDC-Basic plus- Local (Water heat- Modulating) Remote (Water- N.O. 2 position)
DD56= UC400 DDC-Basic plus- Local (Water heat- N.O. 2-position) Remote (Water- Modulating)
DD57= UC400 DDC-Basic plus- Local (Water heat- N.C. 2-position) Remote (Water- Modulating)
DD58= UC400 DDC-Basic plus- Local (Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
DD59= UC400 DDC-Basic plus- Local (Water heat- N.C. 2-position) Remote (Water- N.C. 2-position)
DD60= UC400 DDC-Basic plus- Local (Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
DD61= UC400 DDC-Basic plus- Local (Water heat- N.C. 2-position)
Remote (Water- N.O. 2-position) DD62= UC400 DDC-Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD63= UC400 DDC-Ventilation Flow (Water heat- N.O. 2-position)
DD65= UC400 Basic (Electric HeatModulating SCR)
DD66= UC400 Basic plus-Local (Electric heat-Modulating SCR) Remote (Staged EH)
DD67= UC400 Ventilation Flow (Electric heat-Modulating SCR)
DD71= UC210 DDC-Basic (No water or electric heat)
DD72= UC210 DDC-Basic (Water heat- N.C.- 2 position)
DD73= UC400 DDC-Basic (Water heat- Modulating)
DD74= UC210 DDC-Basic (Electric heat- staged)
DD75= UC210 DDC-Basic (Electric heat- PWM)
DD76= UC210 DDC Ventilation flow- cooling only
DD77= UC210 DDC-Basic (Water heat- N.O.- 2 position)
DD79= UC210 DDC-Flow Tracking (Cooling only)
DD80= UC210 DDC-Ventilation Flow (Water heat- N. C.- 2 position)
DD81= UC210 DDC-Ventilation Flow (Electric heat- staged)
DD82= UC210 DDC-Ventilation Flow (Water heat- Modulating)
DD83= UC210 DDC-Basic plus- Local (Electric heat- PWM) Remote (Staged EH)
DD84= UC210 DDC-Basic plus- Local (Water heat- Modulating) Remote (Water- N.C. 2 position)
DD85= UC210 DDC-Basic plus- Local (Water heat- Modulating) Remote (Water- N.O. 2 position)
DD86= UC210 DDC-Basic plus- Local (Water heat- N.O. 2-position) Remote (Water- Modulating)
DD87= UC210 DDC-Basic plus- Local (Water heat- N.C. 2-position) Remote (Water- Modulating)
DD88= UC210 DDC-Basic plus- Local (Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
DD89= UC210 DDC-Basic plus- Local (Water heat- N.C. 2-position) Remote (Water- N.C. 2-position)
DD90= UC210 DDC-Basic plus- Local (Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
DD91= UC210 DDC-Basic plus- Local (Water heat- N.C. 2-position) Remote (Water- N.O. 2-position)
DD92= UC210 DDC-Basic plus- Local (Electric heat- Staged) Remote (Staged EH)
DD93= UC210 Ventilation Flow (Water heat- N.O. 2-position)
DD95= UC210 Basic (Electric HeatModulating SCR)
DD96= UC210 Basic plus-Local
VAV-SVX08E-EN 5
Model Number Descriptions
(Electric heat-Modulating SCR) Remote (Staged EH)
DD97= UC210 Ventilation Flow (Electric heat-Modulating SCR)
ENCL= Shaft Only in Enclosure ENON= Shaft Out Side for Electric Units FM00= Other Actuator and Control FM01= Trane Supplied Actuator, Other
Ctrl PC00= N.C. Actuator and Linkage Only PC04= N.C. with DA Stat, 3000 Series PC05= N.C. with RA STAT, 3000 Series PCSS= Normally Closed Special PN00= N.O. Actuator and Linkage Only PN04= N.O. 3000 Series, DA STAT PN05= N.O. 3000 Series, RA STAT PN11= Auto Dual Min. PN32= N.O. PNEU Constant Vol. PN34= N.O. 3000 Series Constant
Vol.,RA STAT PNON= Shaft Out Side for Pneumatic
Units PNSS= Normally Open SpecialN.C .= Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat
(by others) RA Stat = Reverse-acting pneumatic
t-stat (by others) PN = Pneumatic FM = Factory installation of customer-
supplied controller PVR = Pneumatic Volume Regulator
Digit 16—InsulationA = 1/2" Matte-faced B = 1" Matte-faced D = 1" Foil-faced F = 1" Double-wall G = 3/8" Closed-cell
Digit 17 & 18—Not Used00 = N/A
Digit 19—Outlet Plenum (Connection is Slip & Drive)
0 = None A = 1 Outlet RH B = 1 Outlet END C = 1 Outlet LH D = 2 Outlets, 1 RH, 1 END E = 2 Outlets, 1 LH, 1 END F = 2 Outlets, 1 RH, 1 LH H = 3 Outlets, 1 LH, 1 RH, 1 END J = 4 Outlets, 1 LH, 1 RH, 2 END
Note: See unit drawings for outlet sizes/damper information.
Digit 20—Not Used0 = N/A
Digit 21—Water Coil0 = None 1 = 1-Row 2 = 2-Row 3 = 3-Row 4 = 4-Row A = 1-Row Premium B = 2-Row Premium C = 3-Row Premium D = 4-Row Premium
Digit 22—Electrical ConnectionsF = Flippable (can be flipped in the
field for LH or RH connections - VCEF only)
L = Left (Airflow hitting you in the face)
R = Right (Airflow hitting you in the face)
0 = Opposite side connection – coil and control (VCWF only)
Note: VCCF, VCWF can be flipped in field for opposite-hand connection
Digit 23—Transformer0 = None 1 = 120/24 volt (50 VA) 2 = 208/24 volt (50 VA) 3 = 240/24 volt (50 VA) 4 = 277/24 volt (50 VA) 5 = 480/24 volt (50 VA) 6 = 347/24 Volt (50 VA) 7 = 380/24 Volt (50 VA) 8 = 575/24 Volt (50 VA)
Note: For VCEF units with transformers the VA depends on the staging, control, and contactor type (ranges are 50 VA to 75 VA, for 1 and 3 phase)
Digit 24—Disconnect Switch0 = None W = With
Note: VCCF, VCWF – Toggle Disconnect; VCEF – Door Interlocking Power Disconnect
Digit 25—Power Fuse0 = None W = With
Digit 26—Electric Heat Voltage0 = None A = 208/60/1 B = 208/60/3 C = 240/60/1 D = 277/60/1 E = 480/60/1 F = 480/60/3 G = 347/60/1 H = 575/60/3 J = 380/50/3 K = 120/60/1
Digit 27 - 29—Electric Heat kW000= None 010 = 1.0 kW 015 = 1.5 kW 460 = 46.0 kW
Note: 0.5 to 8.0 kW – ½ kW increments 8.0 to 18.0 kW – 1 kW increments 18.0 to 46.0 kW – 2 kW increments
Digit 30—Electric Heat Stages0 = None 1 = 1 Stage 2 = 2 Stages Equal 3 = 3 Stages Equal
Digit 31—Electrical Heat Contactors
0 = None 1 = 24-volt magnetic 2 = 24-volt mercury 3 = PE with magnetic 4 = PE with mercury 5 = SCR heat UC400/UC210 6 = SCR heat FMTD/ENCL/DD00 A = 24-volt mercury (left hand) B = 24-volt mercury (right hand) C = PE with mercury (left hand) D = PE with mercury (right hand)
Digit 32 & 33—Not Used00 = N/A
Digit 34—Actuator0 = Standard A = Spring Return (Normally Open) B = Spring Return (Normally Closed) C = Belimo Actuator
Digit 35—Sensor Options0 = Standard (Wired) 1 = Factory Mounted Wireless
Receiver (Sensor Accessory) 2 = Wireless Comm Interface
Modular FM
Digit 36—Pre-Wired Factory Solutions0 = None 1 = Factory Mounted DTS 2 = HW Valve Harness 3 = Both DTS & HW Valve Harness 4 = Averaging DTS factory installed
in unit (Required for UC210/UC400 with SCR heat)
Digit 37—Bottom Access with Cam Locks 0 = None1 = Access Left Side Terminal Unit2 = Access Right Side Terminal Unit3 = Access Left Side Terminal Unit
with Water Connection on Right4 = Access Right Side Terminal Unit
with Water Coil Connection onLeft
6 VAV-SVX08E-EN
Model Number Descriptions
Digit 38—Piping Package0 = None A = 2-way Automatic Balancing) B = 3-way Automatic Balancing
Digit 39—Water Valve0 = None 1 = Proportional, HW Valve, 0.7 Cv 2 = Proportional, HW Valve, 2.7 Cv 3 = Proportional, HW Valve, 6.6 Cv 4 = Proportional, HW Valve, 8.0Cv
Digit 40—Flow Rate00 = None A = 0.5 gpm (0.03 l/s) B = 1.0 gpm (0.06 l/s) C = 1.5 gpm (0.09 l/s) D = 2.0 gpm (0.13 l/s) E = 2.5 gpm (0.16 l/s) F = 3.0 gpm (0.19 l/s) G = 3.5 gpm (0.22 l/s) H = 4.0 gpm (0.25 l/s) J = 4.5 gpm (0.28 l/s) K = 5.0 gpm (0.31 l/s) L = 5.5 gpm (0.35 l/s) M = 6.0 gpm (0.38 l/s) N = 6.5 gpm (0.41 l/s) P = 7.0 gpm (0.44 l/s) Q = 7.5 gpm (0.47 l/s) R = 8.0 gpm (0.50 l/s) S = 9.0 gpm (0.57 l/s) T = 10.0 gpm (0.63 l/s) U = 11.0 gpm (0.69 l/s) V = 12.0 gpm (0.76 l/s) W = 13.0 gpm (0.82 l/s) X = 14.0 gpm (0.88 l/s) Y = 15.0 gpm (0.95 l/s) Z = 16.0 gpm (1.01 l/s) 1 = 17.0 gpm (1.07 l/s) 2 = 18.0 gpm (1.14 l/s) 3 = 19.0 gpm (1.20 l/s) 4 = 20.0 gpm (1.26 l/s) 5 = 21.0 gpm (1.32 l/s) 6 = 22.0 gpm (1.39 l/s) 7 = 23.0 gpm (1.45 l/s)
VAV-SVX08E-EN 7
Model Number Descriptions
Dual-Duct Units
Digit 1, 2, 3—Unit TypeVDD= VariTrane dual-duct
Digit 4—Development SequenceF = Sixth
Digit 5, 6—Primary Air Valve05 = 5" inlet (350 cfm) 06 = 6" inlet (500 cfm) 08 = 6" inlet (900 cfm) 10 = 10" inlet (1400 cfm) 12 = 12" inlet (2000 cfm) 14 = 14" inlet (3000 cfm) 16 = 16" inlet (4000 cfm)
Digit 7, 8—Secondary Air Valve05 = 5" inlet (350 cfm) 06 = 6" inlet (500 cfm) 08 = 8" inlet (900 cfm) 10 = 10" inlet (1400 cfm) 12 = 12" inlet (2000 cfm) 14 = 14" inlet (3000 cfm) 16 = 16" inlet (4000 cfm)
Digit 9—Not Used0 = N/A
Digit 10, 11—Design Sequence** = Factory Assigned
Digit 12, 13, 14, 15—ControlsDD00= Trane Actuator Only DD01= UCM4 Cooling Only Control DD08= UCM4 Dual Duct
Constant Volume DD11= VV550 DDC Controller -
Cooling Only DD18= VV550 DDC Controller w
Constant Volume DD41= UC400 DDC-Basic (No water or
electric heat) DD48= UC400 DDC-Basic (Constant
Volume) DDSS= Digital Special ENON= Shaft Out Side for Electric
Units FM00= Other Actuator and Control FM01= Trane Supplied Actuator, Other
Ctrl PC03= NC Heating Valve, N.O. Cooling
Valve PCSS= Normally Closed Special PN08= N.O. Heat/Cool Actuators &
Linkage OnlyPN09= N.O. Heating, N.O. Cooling,
w/PVR’s PN10= N.O. Heating, N.O. Cooling,
w/PVR’s (CV DISCH) PNON= Shaft Out Side for Pneumatic
UnitsPNSS= Normally Open Special
Notes:N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customer-
supplied controller PVR = Pneumatic Volume Regulator
Digit 16—InsulationA = 1/2" Matte-faced B = 1" Matte-faced D = 1" Foil-faced F = 1" Double-wall G = 3/8" Closed-cell
Digit 17—Not Used0 = N/A
Digit 18—Not Used0 = N/A
Digit 19—Outlet Plenum (Connection is slip & drive)0 = none A = 1 outlet–RH B = 1 outlet–END C = 1 outlet–LH D = 2 outlets–1 RH, 1 END E = 2 outlets–1 LH, 1 END F = 2 outlets–1 RH, 1 LH G = 2 outlets - END H = 3 outlets–1 LH, 1 RH, 1 END J = 4 outlets–1 LH, 1 RH, 2 END
Note: See unit drawings for outlet sizes/damper information.
Digit 20—Not Used0 = N/A
Digit 21—Not Used0 = N/A
Digit 22—Not Used0 = N/A
Digit 23—Transformer0 = None 1 = 120/24 volt (50 VA) 2 = 208/24 volt (50 VA) 3 = 240/24 volt (50 VA) 4 = 277/24 volt (50VA) 5 = 480/24 volt (50 VA) 6 = 347/24 volt (50 VA) 7 = 575/24 volt (50 VA)
Digit 24—Disconnect Switch0 = None W = With Toggle
Digit 25—Power Fuse0 = None W = With
Digit 26—Not Used0 = N/A
Digit 27—Not Used0 = N/A
Digit 28—Not Used0 = N/A
Digit 29—Not Used0 = N/A
Digit 30—Not Used0 = N/A
Digit 31—Not Used0 = N/A
Digit 32—Not Used0 = N/A
Digit 33—Special Options0 = NoneX = Varies - Factory Assigned
Digit 34—ActuatorA = Belimo Actuator
Digit 35—Wireless Sensor0 = Sensor/Receiver Standard1 = Wireless Sensor/Receiver
Mounted
Note: All sensors selected in accessories
Digit 36—Duct Temp Sensor0 = None 1 = With Duct Temp Sensor
8 VAV-SVX08E-EN
Model Number Descriptions
Fan-Powered Units
Digit 1, 2—Unit TypeVP = VariTrane Fan-Powered Parallel VS = VariTrane Fan-Powered Series LP = VariTrane Fan-Powered
Low-Height ParallelLS = VariTrane Fan-Powered
Low-Height Series
Digit 3—ReheatC = Cooling OnlyE = Electric HeatW = Hot Water Heat
Digit 4—Development SequenceF = Sixth
Digit 5, 6—Primary Air Valve05 = 5" inlet (350 max cfm)06 = 6" inlet (500 max cfm)08 = 8" inlet (900 max cfm)10 = 10" inlet (1400 max cfm)12 = 12" inlet (2000 max cfm)14 = 14" inlet (3000 max cfm)16 = 16" inlet (4000 max cfm)RT = 8" x 14" inlet (1800 max CFM)
Note: 10, 12, 14, 16 Not Available on Low-Height
Digit 7, 8—Secondary Air Valve00 = N/A
Digit 9—FanP = 02SQ fan (500 nominal cfm)Q = 03SQ fan (1100 nominal cfm)R = 04SQ fan (1350 nominal cfm)S = 05SQ fan (1550 nominal cfm)T = 06SQ fan (1850 nominal cfm)U = 07SQ fan (2000 nominal cfm)V = 08SQ Fan (500 nominal cfm)W = 09SQ Fan (900 nominal cfm)X = 10SQ Fan (1800 nominal cfm)
Digit 10, 11—Design Sequence** = Factory assigned
Digit 12, 13, 14, 15—ControlsDD01= Cooling Only Control DD02= N.C. On/Off Hot WaterDD03= Prop. Hot WaterDD04= Staged On/Off E-HeatDD05= Pulse Width Mod of E-HeatDD07= N.O. On/Off Hot WaterDD11= VV550 DDC Controller - Cooling
Only DD12= VV550 DDC Ctrl w/N.C. On/Off
HW Valve DD13= VV550 DDC Ctrl w/Prop. HW
Valve DD14= VV550 DDC Ctrl - On/Off
Electric Heat DD15= VV550 DDC Ctrl w/Pulse Width
Modulation DD17= VV550 DDC Ctrl w/N.O. On/Off
HW Valve DD23= VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote(Staged EH)
DD28= VV550 DDC-Basic plus- Local(Water heat- N.O. 2-position)Remote (Water- N.O. 2-position)
DD29= VV550 DDC-Basic plus- Local(Water heat- N.C. 2-position)Remote (Water- N.C. 2-position)
DD30= VV550 DDC-Basic plus- Local(Water heat- N.O. 2-position)Remote (Water- N.C. 2-position)
DD31= VV550 DDC-Basic plus- Local(Water heat- N.C. 2-position)Remote (Water- N.O. 2-position)
DD32= VV550 DDC-Basic plus- Local(Electric heat- Staged) Remote(Staged EH)
DD41= UC400 DDC-Basic (No water orelectric heat)
DD42= UC400 DDC-Basic (Water heat-Normally Closed- 2 position)
DD43= UC400 DDC-Basic (Water heat-Modulating)
DD44= UC400 DDC-Basic (Electric heat-staged)
DD45= UC400 DDC-Basic (Electric heat-PWM)
DD47= UC400 DDC-Basic (Water heat-Normally Opened- 2 position)
DD53= UC400 DDC-Basic plus- Local(Electric heat- PWM) Remote(Staged EH)
DD58= UC400 DDC-Basic plus- Local(Water heat- N.O. 2-position)Remote (Water- N.O. 2-position)
DD59= UC400 DDC-Basic plus- Local(Water heat- N.C. 2-position)Remote (Water- N.C. 2-position)
DD60= UC400 DDC-Basic plus- Local(Water heat- N.O. 2-position)Remote (Water- N.C. 2-position)
DD61= UC400 DDC-Basic plus- Local(Water heat- N.C. 2-position)Remote (Water- N.O. 2-position)
DD62= UC400 DDC-Basic plus- Local(Electric heat- Staged) Remote(Staged EH)
DD65= Basic (Electric Heat- Modulating SCR)
DD66= Basic plus – Local (Electric heat – Modulating SCR) Remote (Staged EH)
DD71= UC210 DDC-Basic (Cooling only)
DD72= UC210 DDC-Basic (Water heat-nc 2pos)
DD73= UC210 DDC-Basic (Water heat-Modulating)
DD74= UC210 DDC-Basic (Electric heat-staged)
DD75= UC210 DDC-Basic (Electric heat-pwm) DD77= UC210 DDC-Basic
(Water heat-NO 2pos) DD83= UC210 DDC-Basic+ Local
(Electric heat-pwm) Remote (Staged)
DD84= UC210 DDC-Basic+ Local (Water heat Modulating) Remote (Water-NC 2pos)
DD85= UC210 DDC-Basic+ Local (Water heat Modulating) Remote (Water-NO 2pos)
DD86= UC210 DDC-Basic+ Local (Water heat NO 2pos)
Remote (Water-Modulating) DD87= UC210 DDC-Basic+ Local
(Water heat NC 2pos) Remote (Water-Modulating)
DD88= UC210 DDC-Basic+ Local (Water heat NO 2pos) Remote (Water-NO 2pos)
DD89= UC210 DDC-Basic+ Local (Water heat NC 2pos) Remote (Water-NC 2pos)
DD90= UC210 DDC-Basic+ Local (Water heat NO 2pos) Remote (Water-NC 2pos)
DD91= UC210 DDC-Basic+ Local (Water heat NC 2pos) Remote (Water-NO 2pos)
DD92= UC210 DDC-Basic+ Local (Electric heat-staged) Remote (Staged)
DD95= UC210 DDC-Ctrl w/Modulating SCR
DD96= UC210 DDC-Space Temp Ctrl w/ Local SCR & Remote Stge ElecHeat
DD00= Trane Actuator OnlyENCL= Shaft Only in EnclosureENON= Shaft Out Side for Electric UnitsFM00= Other Actuator and ControlFM01= Trane supplied actuator,
other control PN00= N.O. Actuator and Linkage OnlyPN05= N.O. 3000 Series, RA StatPN51= Pneumatic normally open
w/3011,DPS fanPN52= Pneumatic normally open
w/3011, DPM fanPNON= Shaft Out Side for Pneumatic
Units
Notes:N.C. = Normally-closedN.O. = Normally-openedDA Stat = Direct-acting pneumatic t-stat
(by others)RA Stat = Reverse-acting pneumatic
t-stat (by others)PN = PneumaticFM = Factory installation of customer-
supplied controllerPVR = Pneumatic Volume Regulator
Digit 16—InsulationA = 1/2” Matte-facedB = 1" Matte-facedD = 1" Foil-facedF = 1" Double-wallG = 3/8” Closed-cell
Digit 17—Motor TypeD = PSC MotorE = High-efficiency motor (ECM)
Digit 18—Motor Voltage1 = 115/60/12 = 277/60/13 = 347/60/14 = 208/60/15 = 230/50/1
VAV-SVX08E-EN 9
Model Number Descriptions
Digit 19—Outlet Connection1 = Flanged2 = Slip & Drive
Digit 20—Attenuator0 = No AttenuatorW = With Attenuator
Digit 21—Water Coil0 = None1 = 1-Row–Plenum inlet installed RH2 = 2-Row–Plenum inlet installed RH3 = 1-Row–Discharge installed, LH4 = 1-Row–Discharge installed, RH5 = 2-Row–Discharge installed, LH6 = 2-Row–Discharge installed, RH1 A = 1-Row–Premium water coil inletB = 2-Row–Premium water coil inletC = 1-Row–Premium hot coil
on discharge, LHD = 1-Row–Premium hot coil
on discharge, RHE = 2-Row–Premium hot coil
on discharge, LHF = 2-Row–Premium hot coil
on discharge, RH
Note: 1- and 2-row not available with Low-Height
Digit 22—Electrical ConnectionsL = Left (Airflow hitting you in the
face)R = Right (Airflow hitting you in the
face) W = Narrow Corridor LH, Hi-Volt Inlet
FacingX = Narrow Corridor RH, Hi-Volt Inlet
Facing
Note: (W & X) Fan Powered Series Only
Digit 23—Transformer0 = N/A (provided as standard)
Digit 24—Disconnect Switch0 = NoneW = WithElectric Reheat w/ door interlocking power disconnect, Cooling Only and Water Reheat w/ toggle disconnect
Digit 25—Power Fuse0 = NoneW = With
Digit 26—Electric Heat Voltage0 = NoneA = 208/60/1B = 208/60/3C = 240/60/1D = 277/60/1E = 480/60/1F = 480/60/3G = 347/60/1H = 575/60/3J = 380/50/3K = 120/60/1
Note: K not available with Low Height
Digit 27, 28, 29—Electric Heat kW000= None050 = 0.5 kW010 = 1.0 kW015 = 1.5 kW260 = 26.0 kW
Note: Electric Heat Voltage - 0.5 to 8.0 kW–½ kW increments8.0 to 18.0 kW –1 kW increments18.0 to 46.0 kW–2 kW increments
Digit 30—Electric Heat Stages0 = None1 = 1 Stage2 = 2 Stages Equal3 = 3 Stages Equal
Note: 3 not available with Low Height
Digit 31—Contactors0 = None1 = 24-volt magnetic2 = 24-volt mercury3 = PE with magnetic4 = PE with mercury5 = SCR heat UC400 6 = SCR heat FMTD/ENCL/DD00
Note: SCR cannot be selected with the following configuration:
• KW > 10, 208 volt 3 phase, Low Height
• KW > 22, 480 volt 3 phase, Low Height
• Voltage = 575 volt
Digit 32—Airflow Switch0 = NoneW = With
Digit 33—Not Used0 = N/A
Digit 34—Actuator0 = StandardA = Belimo actuator
Digit 35—Wireless Sensors0 = None1 = Factory Mounted Wireless
Receiver (Sensor Assembly)2 = Wireless Comm Interface
Modular FM
Note: All sensors selected in accessories
Digit 36—Pre-Wired Factory Solutions0 = None 1 = Factory Mounted DTS 2 = HW Valve Harness 3 = Both DTS & HW Valve Harness
Digit 37—Bottom Access0 = None W = Access Left Side of Terminal Unit
Digit 38—Piping Package0 = None A = 2-way Automatic Balancing) B = 3-way Automatic Balancing
Digit 39—Water Valve0 = None 1 = Proportional, HW Valve, 0.7 Cv 2 = Proportional, HW Valve, 2.7 Cv 3 = Proportional, HW Valve, 6.6 Cv 4 = Proportional, HW Valve, 8.0Cv
Digit 40—Flow Rate0 = None A = 0.5 gpm (0.03 l/s) B = 1.0 gpm (0.06 l/s) C = 1.5 gpm (0.09 l/s) D = 2.0 gpm (0.13 l/s) E = 2.5 gpm (0.16 l/s) F = 3.0 gpm (0.19 l/s) G = 3.5 gpm (0.22 l/s) H = 4.0 gpm (0.25 l/s) J = 4.5 gpm (0.28 l/s) K = 5.0 gpm (0.31 l/s) L = 5.5 gpm (0.35 l/s) M = 6.0 gpm (0.38 l/s) N = 6.5 gpm (0.41 l/s) P = 7.0 gpm (0.44 l/s) Q = 7.5 gpm (0.47 l/s) R = 8.0 gpm (0.50 l/s) S = 9.0 gpm (0.57 l/s) T = 10.0 gpm (0.63 l/s) U = 11.0 gpm (0.69 l/s) V = 12.0 gpm (0.76 l/s) W = 13.0 gpm (0.82 l/s)
10 VAV-SVX08E-EN
Unit Information
Single-Duct Units
The basic unit consists of a sheet metal casing with an air valve, which is used to modulate the air being delivered into the occupied zone. The unit is designed to modulate either cooling or heating air between the temperatures of 40°F and 140°F. Air enters the air valve through the round or rectangular inlet and exits into the sheet metal casing to be distributed to the zone either through integral round outlets in the casing or through rectangular duct attached to the discharge of the unit.
The basic unit can also be ordered with factory-mounted electric or hot water heating coils attached to the discharge. See Figure 2, p. 11.
These re-heat units are used primarily to reheat air-to-zone temperature when the load in the occupied space is low.
Primary air is modulated through the VariTrane air valve by rotating the damper blade. All air valves have a round/rectangular inlet for easy fit-up with incoming duct work.
Typical Single-Duct Units
Dual-Duct Units
Dual-duct units provide two air valves: one as heating primary air and the other as cooling primary air. Both discharge into the common outlet, which leads to the zone being controlled. See Figure 4, p. 11.
Units are provided with a slip and drive rectangular duct connection or can be ordered with integral outlet plenum.
Sequencing of hot and cold air valve is dependent on job requirements. One typical control is valves working in conjunction to respond to zone temperature.
When the cooling valve becomes fully closed or reaches a specified minimum, the heating valve will begin to modulate or vice versa. The typical result is that air flowing to the zone varies from maximum down to a minimum and back up to maximum as load varies and controls would cause one air valve to close and the other to open.
Another typical application is when the unit provides a constant volume to the zone. When the zone sensor is tied directly to the heating valve, it will modulate the heating valve according to the zone temperature.
When the heating valve is fully closed or there is a call for cooling in the zone, the cooling valve will be at constant supply. As the space becomes too cool, the heating valve will modulate open, decreasing the cooling valve flow. The typical result is that the air flowing into the zone stays at a constant flow whether the unit is heating or cooling.
Figure 1. Typical single duct unit — VCCF
Figure 2. Typical single duct unit — VCWF
Figure 3. Typical single duct unit — VCEF
Figure 4. Typical dual-duct unit: VDDF
VAV-SVX08E-EN 11
Unit Information
Fan-Powered and Fan-Powered Low-
Height Units
VariTrane fan-powered and low-height fan-powered units can be either parallel or series, with or without re-heat. (SeeFigure 5, p. 12 thru Figure 8, p. 12.)
Typical Fan-Powered Units
The fan on a series unit runs continuously whenever the main air handler unit is in operation. There are various options for starting the fan. The fan can be started three ways: 1) remotely, 2) by a duct pressure switch, or 3) by a combination of both. The particular fan control method may vary from unit to unit, depending upon job needs.
Typically, heater is off while air valve modulates primary air and responds to zone temperature. If zone temperature decreases to the point where a decrease in primary air will not maintain the desired temperature, the re-heat will be activated to increase the temperature of the discharge air.
On a parallel unit, the VariTrane air valve delivers primary cooling air to the unit outlet. When the space temperature decreases beyond air valve control, the fan is turned on as the first stage of heat. The fan delivers plenum air from above the occupied space to the unit outlet, which is mixed with primary air and delivered to the occupied space.
Note: Either the fan, the air valve, or both can deliver airflow into the occupied space. In order to prevent primary airflow from exiting through the fan when the fan is not running on a parallel unit, a back draft damper is provided. When the fan is not running, the efficiency of this system is the same as a standard single-duct VAV unit.
Typically, the control systems applied to parallel units cause the air valve to close to zero or a minimum flow before the fan is activated. After the fan is activated, the optional heat will be activated upon further reduction in zone temperature. Therefore, minimal primary air is mixed with the heated air.
VariTrane fan-powered unit fan sizes 02SQ–05SQ and 08SQ–10SQ were performance tested at .12 in. w.g. and sizes 06SQ and 07SQ were tested at .15 in. w.g. Units are not designed to operate unducted and below these tested static pressures.
Note: Fan-powered units are available with rectangular discharge connection only. The optional heater is mounted on the discharge of the unit. Hot water coils are connected to either the plenum inlet or on the discharge on parallel units, and to the discharge of series units.
Figure 5. Parallel fan-powered terminal unit (top) &
series fan-powered terminal units (bottom)
Figure 6. Low height series: LSCF (top) & low height
series: LSWF (bottom)
Figure 7. Low height series: LSEF (top) & low height
parallel: LPCF (bottom)
Figure 8. Low height parallel: LPWF (top) & low height
parallel: LPEF (bottom)
12 VAV-SVX08E-EN
Unit Installation
Due to their weight, the VAV terminal units should be suspended from the uppermost ceiling, independent of the false ceiling grid. Suspension devices are to be supplied by the installer. Units must be installed level and upright. Failure to level the unit properly may prevent proper operation of the controls and/or terminal unit. Units are not designed to be installed vertically. Consequently, this will also void the UL ratings and any warranty on the unit.
Single-Duct
Depending upon the size and weight of the single-duct unit, it may be capable of being supported by the ductwork that is connected to it. No hanger brackets are provided on these units since the unit should be supported by means of a hanger strap. The hanger strap should be secured directly to the unit casing as shown in Figure 9, p. 13.
For cooling only single-duct units or single-duct units with hot water coil, the unit may be rotated 180° for opposite side connections.
For units with electric heat, the unit can be flipped to either RH or LH connection orientation if model number digit 22 Electrical Connections = F.
Dual-Duct
Dual-duct units should be supported by either hanger straps or by using a threaded rod in conjunction with the hanger brackets that are provided on the unit. See Figure 10, p. 13.
Fan-Powered (Standard and Low-Height)
Fan-powered units should be supported by either hanger straps or by using a threaded rod in conjunction with the hanger brackets that are provided on the unit. Care should be exercised to insure that the hanging straps do not block the side access panel. See Figure 11, p. 16 thru Figure 18, p. 22.
Duct Connections
All VariTrane units should be provided with a minimum of 1.5-duct diameters of straight duct prior to the inlet of the unit. It is recommended that at least 48 inches of straight duct be provided from the discharge of the units prior to any take-offs or transitions.
Important: This is a requirement for electric heat fan-powered units used in applications with 100% downward discharge.
Note: In order to maintain good air distribution over the elements and not create turbulence which could cause a limit cutout there should be four feet of ductwork, consistent of the discharge dimensions of the heater. downstream of the reheat coil prior to any diffuser takeoffs for VariTrane™ electric coils.
1. After all connections are made, check that the entire ductwork system is airtight. In some high-pressure systems, duct sealer may be necessary.
Note: All inlet duct on the VAV boxes are sized approximately 1/8" smaller in diameter than the nominal size in order to allow the incoming duct to slide over the inlet of the VAV box.
2. Provide insulation around the entire inlet collar (all the way to the unit casing).
WARNING
Proper Structural Support Required!
Ceiling structure must be strong enough to support the weight of the unit. If unsure, check with a structural engineer. Refer toTable 1, p. 24 thruTable 6, p. 26 for unit weights. Failure to ensure proper structural ceiling support could result in unit failing from its location which could result in death or serious injury.
Figure 9. Single-duct hanging recommendations
.
Figure 10. Dual-duct hanger bracket locations
Inlet Size B C A
1.376" (35 mm)
25.154" (639 mm) 1.376" (35 mm) 37.25" (946 mm)
25.25" (641 mm) 23.154" (588 mm)
12" thru 16"
5" thru 10"
AIR VALVE
AIR VALVE
COOLING HEATING
C
A
B
TOP VIEW
VAV-SVX08E-EN 13
Unit Installation
Note: Use caution not to damage the flow tubes when making ductwork connections or insulating.
3. Cut “slits” in the insulation for the flow tubes and secure with duct tape.
4. If the unit is to be installed in a location with high humidity, external insulation around the heating coil should be installed as required.
Water Coil Connections
Note: The following coils have 3/8” OD water coil piping connections.
• Single Duct 1-row coils (inlet sizes 05, 05, 06, 08 or 10 only)
• Low Height Parallel Inlet 1-row
• Low Height Parallel Discharge 1-row
All others require a 7/8” OD water coil piping connections.
Note:
1. If necessary, you can change the coil connection from left-handed to right-handed (and vice-versa) by disconnecting the coil from the unit and rotating the coil “like a steering wheel” 180°.
Note: Exception - Coil connection cannot be changed on parallel fan powered unit with hot water coil on plenum inlet.
2. Use port at the bottom for inlet and top for outlet on single row coils. For multirow coils, always plumb in counter flow orientation.
• Water inlet is always on the airflow downstream side of the hot water coil.
• Water outlet is always on the upstream side of the hot water coil.
3. Care should be taken to properly support the water coil piping connections while connecting the adjoining pipe.
4. It is recommended that piping to the water coil should be done after field-mounted controls, external insulation, and ductwork connections have been completed.
Important: Do not connect water valve or pipe extensions to the water coil connections unless supported.
Unit Accessibility
• Single-duct and dual-duct units provided with hot water reheat have an access panel located on the side of the water coil. All other single-duct and dual-duct units are provided without access, as all functioning components are external to the unit.
• Fan-powered terminals are provided with a sliding side access.
• Low-height terminal units have a removable bottom panel.
Clearances
For proper service, it is recommended that at least 36” of side clearance be provided to service and access single-duct and dual-duct terminals units.
• Fan-powered VAV units have a plenum inlet that must be clear of obstructions. Allow at least 36” of clearance in front of the side access and plenum opening.
• Low-height fan-powered terminals require the same plenum clearance requirement that applies to the standard fan-powered units. However the access to the internal components is located on the bottom of the unit.
It is also recommended that 6” of clearance be provided to the top and bottom of all the units.
Note: The minimum clearance for controls and heater controls should be 36” for all models except units with 575-volt electric heaters, which require 48” of clearance. NEC and/or local codes override all clearance requirements.
Actuator Mounting
Important: When installing or replacing the actuator tighten the actuator set screw per the manufacturer’s instructions. Failure to follow the manufacturer’s specifications may result in unit malfunction.
Trane offers a factory-mounted actuator with a 90-second drive time. The actuator drives 1 degree per second. A field-installed actuator may be used if desired. The actuator shaft has a ½-inch diameter and is designed to travel clockwise to close the damper and counter-clockwise to open the damper. There is an indicator on the end of the actuator shaft that can be used to determine the position of the damper.
Stand Alone UCM 4.2
When there is no communication to the UCM control and the unit is in the stand alone mode the control action is determined by the auxiliary temperature sensor located on TB3-5 and TB3-6 terminals on the UCM board. In order for the auxiliary sensor to determine the control action (heat, cool) it must be located in the supply duct. The auxiliary temperature is then compared to the zone temperature. If the supply air temperature is 10 degrees above the zone temperature, then the control action will be heat. If the supply air temperature is less than or equal to the zone temperature, then the control action will be cool. If the supply air temperature is between the zone temperature and the zone temperature + 10ºF (5.5°C)(zone temperature < supply air temperature < zone temperature + 10ºF) (5.5°C), the control action remains the same and the UCM controls to the minimum flow set point. If an auxiliary sensor is not installed the UCM will retain the last control action in effect.
14 VAV-SVX08E-EN
Unit Installation
Stand Alone VV550 LonTalk™ Control
When there is no communication to the VV550 control and the unit is in the stand alone mode the control action is determined by the auxiliary temperature sensor located on TB3-5 and TB3-6 terminals on the VV550 board. The control must also be configured through the “Inputs Tab” of Analog Input 4 as “Primary Supply Air Sensor”. In order for the auxiliary sensor to determine the control action (heat, cool) it must be located in the supply inlet of the duct. The auxiliary temperature is then compared to the zone temperature. If the supply air temperature is 10 degrees above the zone temperature, then the control action will be heat. If the supply air temperature is less than or equal to the zone temperature, then the control action will be cool. If the supply air temperature is between the zone temperature and the zone temperature + 10ºF (5.5°C)(zone temperature < supply air temperature < zone temperature + 10ºF) (5.5°C), the control action remains the same and the UCM controls to the minimum flow set point. If an auxiliary sensor is not installed the UCM will retain the last control action in effect.
Stand Alone UC400
When there is no communication to the UC400 control and the unit is in the stand alone mode the control action is determined by the auxiliary temperature sensor located on AI5 terminals on the UC400 control. This input may have to be changed from AI4 (Discharge Air Input) as wired from the factory. In order for the auxiliary sensor to determine the control action (heat, cool) it must be located in the supply inlet of the duct. The auxiliary temperature is then compared to the zone temperature. If the supply air temperature is 10 degrees above the zone temperature, then the control action will be heat. If the supply air temperature is less than or equal to the zone temperature, then the control action will be cool. If the supply air temperature is between the zone temperature and the zone temperature + 10ºF (5.5°C)(zone temperature < supply air temperature < zone temperature + 10ºF) (5.5°C), the control action remains the same and the UCM controls to the minimum flow set point. If an auxiliary sensor is not installed the UCM will retain the last control action in effect.
VAV-SVX08E-EN 15
Unit Installation
Figure 11. Parallel hanger bracket locations sizes
WaterCoil
AirflowPlenum Inlet
Optional AttenuatorField Installed
PrimaryAirflow
TOP VIEWParallel Cooling & Hot Water
Flow RingTubing
AirValve
AirflowDischarge Outlet
A
B C
D
EF
A D E F
B
C
FAN SIZE02SQ
03SQ, 04SQ, 05SQ06SQ, 07SQ
26.75" (679 mm) 26.75" (679 mm)
26.75" (679 mm)26.75" (679 mm)29.75" (756 mm)
36.75" (933 mm)
41.154" (1041 mm)
41.154" (1041 mm)41.154" (1041 mm)
3.25" (83 mm)
3.25" (83 mm)3.25" (83 mm)
20.00" (508 mm)
20.00" (508 mm)20.00" (508 mm)
38.95" (989 mm)
38.95" (989 mm)38.95" (989 mm)
AirflowPlenum Inlet
Optional AttenuatorField Installed
PrimaryAirflow
TOP VIEWParallel Electric Heat
Flow RingTubing
AirValve
AirflowDischarge Outlet
A
D
EF
B
C
HeaterTerm
inal
Box
43.546(1106 mm)
16 VAV-SVX08E-EN
Unit Installation
Figure 12. Series hanger bracket locations
Water Coil
Airflow Plenum Inlet
Optional Attenuator Field Installed
TOP VIEW Series Cooling & Hot Water
Flow Ring Tubing
Air Valve
A
D
B
C
TOP VIEW Series Electric Heat
1.
1.
2.
1.625" (41 mm)
All attenuators are the same length and width.
Sizes 01 and 02 units are smaller than attenuators.
Airflow Plenum Inlet
Optional Attenuator Field Installed
Flow Ring Tubing
Air Valve
A B
Electric Heater
D
G
F
C
B
B C A D E FAN SIZE (Elec. Heat Only)
3.25" (83 mm)
3.25" (83 mm)
3.25" (83 mm)
3.25" (83 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
41.154" (1041 mm)
26.75" (679 mm)
26.75" (679 mm)
26.75" (679 mm)
26.75" (679 mm) 02SQ
06SQ, 07SQ
03SQ, 04SQ
05SQ 26.75" (679 mm)
20.75" (527 mm)
18.75" (476 mm)
27.25" (692 mm)
35.154 (740 mm)
23.875 (606 mm)
29.875" (759 mm)
28.966" (736 mm)
20.132" (511 mm)
Fan Inlet w/o Attenuator
Fan Inlet w/o Attenuator
F
C
E 2.
J
(Elec. Heat Only)
59.750” (1517 mm)
58.250" (1479 mm)
59.750" (1517 mm)
53.750" (1365 mm)
G(Elec. Heat Only)
19.00" (483 mm)
17.50" (445 mm)
19.00" (483 mm)
19.00" (483 mm)
J
VAV-SVX08E-EN 17
Unit Installation
Figure 13. Low-height parallel 08SQ/09SQ w/hot water or electric heat
31.65"(804 mm)
23.90"(607 mm)
13.00"(330 mm)
19.86"(504 mm)
AirflowPlenum Inlet
Optional AttenuatorField Installed
24.30"(617 mm)
PrimaryAirflow
AirflowDischarge Outlet
13.80"(350 mm)
4.00"(102 mm)
23.10"(587 mm)
3.35"(85 mm) TOP VIEW
TOP VIEW3.35"
(85 mm)
AirflowDischarge Outlet
31.65"(804 mm)
23.90"(607 mm)
13.00"(330 mm)
19.86"(504 mm)
AirflowPlenum Inlet
Optional AttenuatorField Installed
24.30"(617 mm)
PrimaryAirflow
13.80"(350 mm)
4.00"(102 mm)
23.10"(587 mm)
3.00"(76 mm)
Heater
Term
inal
Box
18 VAV-SVX08E-EN
Unit Installation
Figure 14. Low-height parallel 10SQ
PrimaryAirflow
AirValve
38.95"(989 mm)
1.625"(41 mm)
Flow RingTubing
5.625"(143 mm)
41.137"(1045 mm)
AirflowDischarge Outlet
Optional Heater Terminal Box5.625"
(143 mm)
TOP VIEW
38.75"(984 mm)
PlenumInlet
VAV-SVX08E-EN 19
Unit Installation
Figure 15. Low-height series 08SQ/09SQ w/hot water or electric heatg
19.86"(504 mm)
3.35"(85 mm)
31.65"(804 mm)
12.85"(326 mm)
10.13"(257 mm)4.00"
(102 mm)
34.30"(871 mm)
10.13"(257 mm)
3.35"(85 mm)
4.00"(102 mm)
27.00"(686 mm)
20.00"(508 mm)
PrimaryAirflow
AirValve
AirflowPlenum Inlet
Optional AttenuatorField Installed
WaterCoil
PrimaryAirflow
Airflow
TOP VIEW
19.86"(504 mm)
3.35"(85 mm)
31.65"(804 mm)
12.85"(326 mm)
34.30"(871 mm)
3.35"(85 mm)
27.00"(686 mm)
20.00"(508 mm)
AirValve
AirflowPlenum Inlet
Optional AttenuatorField Installed
OptionalElectric Heater
Airflow
TOP VIEW
20 VAV-SVX08E-EN
Unit Installation
Figure 16. Low-height series 10SQ w/hot water or electric heat
31.65"(804 mm)
19.86"(504 mm)
AirflowPlenum Inlet
Optional AttenuatorField Installed
31.65"(804 mm)
PrimaryAirflow
AirflowDischarge Outlet
10.12"(257 mm)
42.00"(1067 mm)
30.30"(770 mm)
3.35"(85 mm)
TOP VIEW
Optional AttenuatorField Installed
AirflowPlenum Inlet
19.45"(494 mm)
19.45"(494 mm)
19.86"(504 mm)
3.35"(85 mm)
3.50"(89 mm)
3.50"(89 mm)
31.65"(804 mm)
19.86"(504 mm)
AirflowPlenum Inlet
Optional AttenuatorField Installed
31.65"(804 mm)
PrimaryAirflow
AirflowDischarge Outlet
10.12"(257 mm)
42.00"(1067 mm)
30.30"(770 mm)
3.35"(85 mm)
TOP VIEW
Optional AttenuatorField Installed
AirflowPlenum Inlet
19.45"(494 mm)
19.45"(494 mm)
19.86"(504 mm)
3.35"(85 mm)
3.50"(89 mm)
3.50"(89 mm)
1.92"(49 mm)
Term
inal
Box
Plenum Area
OptionalHeater
VAV-SVX08E-EN 21
Unit Installation
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Figure 17. Attenuator installation - parallel units
Mounting Bracket
Optional AttenuatorField Installed
1. Attach attenuator as shown with provided mounting brackets.
Figure 18. Attenuator installation - series units
Optional AttenuatorField Installed
Mounting Bracket
1. Attach attenuator as shown with provided mounting brackets.
22 VAV-SVX08E-EN
Unit Installation
Notes: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Bottom Access
An optional bottom access can be provided in the casing of fan powered series or parallel terminal unit. See Figure 21.
The 22 ga. door is lined with 1” 26 ga. dual wall insulation and thermally lined with 1” – 1 lb. density fiberglass insulation with a 3.85 R-value.
Each door includes 4 to 6 cam locs that are used to secure the door to the casing.
The cam loc engages a metal encapsulated frame on the unit that encloses the unit insulation to prevent air erosion.
The cam loc engagements are interlocked using a flat head screwdriver. Once unlocked the entire door assembly can be removed for access.
Figure 19. Attenuator installation - low-height parallel units
1. Attach attenuator to unit as shown with provided mounting brackets.
MOUNTING BRACKET
OPTIONAL ATTENUATORFIELD INSTALLED
Figure 20. Attenuator installation - low-height series units
1. Attach attenuator to unit as shown with provided mounting brackets.
MOUNTING BRACKET
OPTIONAL ATTENUATORFIELD INSTALLED
MOUNTING BRACKET
OPTIONAL ATTENUATORFIELD INSTALLED
MOUNTING BRACKET
OPTIONAL ATTENUATORFIELD INSTALLED
Figure 21. Bottom access
VAV-SVX08E-EN 23
Unit Installation
Table 1. Single-duct units
Unit Size
VCCF (lbs/kg)
VCCF w/ Dual Wall (lbs/kg)
VCEF (lbs/kg)
VCEF w/Dual Wall
(lbs/kg)
VCWF 1-Row
(lbs/kg)
VCWF 2-Row
(lbs/kg)
VCWF3-Row
(lbs/kg)
VCWF4-Row
(lbs/kg)
VCWF 1-Row w/ Dual Wall (lbs/kg)
VCWF 2-Row w/ Dual Wall (lbs/kg)
VCWF3-Row w/Dual Wall(lbs/kg)
VCWF4-Row w/Dual Wall(lbs/kg)
4568
16/716/716/716/7
19/919/919/920/9
38/1738/1738/1738/17
48/2248/2248/2249/22
21/1021/1021/1021/10
22/1022/1022/1024/11
23/1123/1122/1024/11
24/1124/1124/1126/12
24/1124/1124/1125/11
25/1125/1125/1128/13
26/1226/1225/1128/13
27/1227/1227/1230/14
1012141624
22/1027/1232/1535/1652/24
27/1234/1541/1946/2163/29
46/2152/2460/2769/3184/38
60/2768/3180/3691/41106/48
29/1337/1744/2049/2270/32
32/1540/1848/2254/2477/35
32/1541/1951/2356/2576/35
36/1645/2055/2561/2882/37
34/1543/2053/2460/2781/37
37/1747/2157/2665/2988/40
37/1748/2260/2767/3087/40
41/1952/2464/2972/3393/42
Table 2. Dual-duct units
Unit Size VDDF (lbs/kg) VDDF w/Dual Wall (lbs/kg)
0505050606060508
54/2454/2454/2455/25
68/3168/3168/3168/31
0608051008080610
55/2556/2556/2556/25
69/3169/3170/3270/32
0810101006120812
57/2661/2857/2658/26
70/3274/3470/3271/32
1012121208141014
59/2760/2778/3579/36
72/3384/38102/46103/47
1214141408161016
80/3681/3779/3680/36
104/47105/48103/47104/47
121614161616
81/3782/3783/38
105/48105/48106/48
24 VAV-SVX08E-EN
Unit Installation
Table 3. Parallel fan-powered units
Unit Size
VPCF (lbs/kg)
VPCF w/Dual Wall (lbs/kg)
VPEF (lbs/kg)
VPEF w/Dual Wall (lbs/kg)
VPWF 1-Row (lbs/kg)
VPWF 2-Row (lbs/kg)
VPWF 1-Row w/Dual Wall
(lbs/kg)
VPWF 2-Row w/Dual Wall
(lbs/kg)
VPxF Attenuator (lbs/kg)
0502SQ0602SQ0603SQ0802SQ
81/3780/3683/3881/37
115/52114/52117/53115/52
110/550109/49112/51110/50
144/65143/65146/66144/65
92/4291/41105/4892/42
95/4394/43108/4995/43
126/57125/57139/63126/57
129/59128/58142/64129/59
46/2146/2148/2246/21
0803SQ0804SQ1002SQ1003SQ
83/3884/3882/3784/38
117/53118/54116/53118/54
112/51113/51111/50113/51
146/66147/67145/66147/67
105/48106/4893/42106/48
108/49109/4996/44109/49
139/63140/64127/58140/64
142/64143/65130/59143/65
48/2248/2246/2148/22
1004SQ1005SQ1006SQ1007SQ
85/3998/44114/52122/55
119/54132/60148/67156/71
114/52128/58144/65152/69
148/67162/73178/81186/84
107/49120/54127/58135/61
110/50123/56130/59138/63
141/64154/70161/73169/77
144/65157/71164/74172/78
48/2248/2254/2454/24
1203SQ1204SQ1205SQ1206SQ
85/3986/3999/45115/52
119/54120/54133/60149/68
114/52115/52129/59145/66
148/67149/68163/74179/81
107/49108/49121/55128/58
110/50111/50124/56131/59
141/64142/64155/70162/73
144/65145/66158/72165/75
48/2248/2248/2254/24
1207SQ1404SQ1405SQ1406SQ
123/5687/39100/45116/53
157/71121/55134/61150/68
153/69116/53130/59146/66
187/85150/68164/74180/82
136/62109/49122/55129/59
139/63112/51125/57132/60
170/77143/65156/71163/74
173/78146/66159/72166/75
54/2448/2248/2254/24
1407SQ1606SQ1607SQ
124/56117/53125/57
158/72151/68159/72
154/70147/67155/70
188/85181/82189/86
137/62130/59138/63
140/64133/60141/64
171/78164/74172/78
174/79167/76175/79
54/2454/2454/24
Table 4. Series fan-powered
Unit SizeVSCF
(lbs/kg)
VSCF w/ Dual Wall (lbs/kg)
VSEF (lbs/kg)
VSEF w/ Dual Wall (lbs/kg)
VSWF 1-Row
(lbs/kg)
VSWF 2-Row
(lbs/kg)
VSWF 1-Row
w/Dual Wall(lbs/kg)
VSWF 2-Row
w/Dual Wall(lbs/kg)
VSxF Attenuator (lbs/kg)
0402SQ0502SQ0602SQ0603SQ0604SQ
78/3578/3577/3576/3487/39
93/4293/4292/42100/45111/50
104/47104/47103/47105/48116/53
119/54119/54118/54129/59140/64
85/3985/3984/3888/4099/45
87/3987/3986/3992/42103/47
100/45100/4599/45112/51123/56
102/46102/46101/46116/53127/58
46/2146/2146/2148/2248/22
0802SQ0803SQ0804SQ1002SQ1003SQ
79/3677/3588/4081/3780/36
94/43101/46112/5196/44104/47
105/48106/48117/53107/49109/49
120/54130/59141/64122/55133/60
86/3989/40100/4588/4092/42
88/4093/42104/4790/4196/44
101/46113/51124/56103/47116/53
103/47117/53128/58105/48120/54
46/2148/2248/2246/2148/22
1004SQ1005SQ1006SQ1007SQ1203SQ
91/4192/42104/47117/5382/37
115/52116/53133/60146/66106/48
120/54121/55135/61148/67111/50
144/65145/66164/74177/80135/61
103/47104/47119/54132/6094/43
107/49108/49124/56137/6298/44
127/58128/58148/67161/73118/54
131/59132/60153/69166/75122/55
48/2248/2254/2454/2448/22
1204SQ1205SQ1206SQ1207SQ1404SQ
92/4294/43105/48118/5493/42
116/53118/54134/61147/67117/53
121/55123/56136/62149/68122/55
145/66147/67165/75178/81146/66
104/47106/48120/54133/60105/48
108/49110/50125/57138/63109/49
128/58130/59149/68162/73129/59
132/60134/61154/70167/76133/60
48/2248/2254/2454/2448/22
1405SQ1406SQ1407SQ1606SQ1607SQ
96/44106/48119/54107/49120/54
120/54135/61148/67136/62149/68
125/57137/62150/68138/63151/68
149/68166/75179/81167/76180/82
108/49121/55134/61122/55135/61
112/51126/57139/63127/58140/64
132/60150/68163/74151/68164/74
136/62155/70168/76156/71169/77
48/2254/2454/2454/2454/24
VAV-SVX08E-EN 25
Unit Installation
Table 5. Low-height parallel units
Unit SizeLPCF
(lbs/kg)
LPCF w/ Dual Wall (lbs/kg)
LPEF(lbs/kg)
LPEF w/ Dual Wall (lbs/kg)
LPWF1-Row
(lbs/kg)
LPWF2-Row
(lbs/kg)
LPWF 1-Row w/Dual Wall
(lbs/kg)
LPWF 2-Row w/DualWall
(lbs/kg)
LPxF Attenuator (lbs/kg)
0508SQ0608SQ0609SQ0808SQ
69/3168/3173/3369/31
89/4088/4093/4289/40
84/3883/3888/4084/38
104/47103/47108/49104/47
78/3577/3582/3778/35
81/3780/3685/3981/37
98/4497/44102/4698/44
101/46100/45105/48101/46
10/510/510/510/5
0809SQ0810SQ
14RT09SQ14RT10SQ
74/3490/4183/3897/44
94/43110/50103/47117/53
89/40105/4898/44112/51
109/49125/57118/54132/60
83/3899/4592/42106/48
86/39102/4695/43109/49
103/47119/54112/51126/57
106/48122/55115/52129/59
10/510/510/510/5
Table 6. Low-height series units
Unit SizeLSCF
(lbs/kg)
LSCF w/ Dual Wall (lbs/kg)
LSEF (lbs/kg)
LSEF w/ Dual Wall (lbs/kg)
LSWF1-Row
(lbs/kg)
LSWF2-Row
(lbs/kg)
LSWF 1-Row w/Dual Wall
(lbs/kg)
LSWF 2-Row w/Dual Wall
(lbs/kg)
LSxF Attenuator (lbs/kg)
0508SQ0608SQ0609SQ0808SQ
71/3270/3280/3671/32
86/3985/3995/4386/39
86/3985/3995/4386/39
101/45100/45110/50101/46
80/3679/3689/4080/36
82/3781/3791/4182/37
95/4394/43104/4795/43
97/4496/44106/4897/44
10/510/510/510/5
0809SQ0810SQ
14RT09SQ14RT10SQ
81/3795/4390/41105/48
96/44120/54105/48130/59
96/44120/54105/48130/59
111/50145/66120/54155/70
90/41111/5099/45121/55
92/42115/52101/46125/57
105/48136/62114/52146/66
107/49140/64116/53150/68
10/520/910/520/9
26 VAV-SVX08E-EN
Unit Setup
Fan Motor Amperage
Figure 22. Flow sensor P vs. airflow delivery
0.01
0.1
1
10
10 100 1,000 10,000
Airflow (CFM)
Flo
w S
enso
r D
iffer
entia
l Pre
ssur
e (in
ches
wat
er)
4
6 8"
5
10" 12" 14" 16"8" x 12"
16" x 24"
Table 7. Maximum ECM fan motor amperage (FLA)
Fan Size HP VAC 115 VAC 277 VAV
Parallel/Series 03SQ 1/3 4.5 2.4
Parallel/Series 04SQ 1/2 6.5 3.5
Parallel/Series 05SQ 1 10.1 5.4
Parallel/Series 06SQ 1 9.5 5.1
Low-height Parallel/Series 08SQ 1/2 2.0 1.1
Low-height Parallel/Series 09SQ 1/2 6.7 3.6
Low-height Series 10SQ 2 x 1/2 7.5 4.0
VAV-SVX08E-EN 27
Unit Setup
(SCR) Motor Speed Control Adjustment Procedure.
In order to make units more convenient and efficient to balance, an SCR (silicone control rectifier) is provided as standard on all fan-powered units.
The SCR is located on the side of the fan control box. To adjust the speed of the motor, the external knob must be rotated either clockwise or counterclockwise depending on the desired speed adjustment.
There is an internal potentiometer (Figure 23, p. 28) setting on the SCR controller that can be accessed by removing the control box cover. This internal potentiometer is set at the factory to the specific motor voltage.
It may be necessary to adjust this in the field depending on the building’s power factor.
Note: Do not set this potentiometer below the voltage of the fan motor.
Electrically Commutated Motor (ECM)
Trane offers an energy efficient ECM motor as a motor option. Balancing of an ECM motor is accomplished through electronic control adjustments on the ECM control board (see Figure 24, p. 28). Potentiometer settings for a multitude of CFM settings are given in Table 9, p. 29 thru Table 21, p. 41. Other potentiometer settings can be determined either by interpolating from these tables or by using the following equation:
CFMsetting = CFMmin + {(Potentiometer Setting) x [(CFMmax - CFMmin)/100]}
There is an LED on the ECM control board, which will blink one time for every 100 CFM of motor setting. For example, the LED on a unit set for 790 CFM will blink 7 times. The LED on a unit set for 800 CFM will blink 8 times.
Note: This feature only verifies that the CFM is set properly. This feature does not indicate at what speed the motor is actually running.
The ECM must be “load tested.” In other words, the fan must be connected to properly test the ECM.
Table 8. Maximum PSC fan motor amperage (FLA)
Fan Size HP VAC115 VAC
277 VAV
347 VAC 208
Parallel/Series 02SQ 1/8 1.6 0.7 .7 -
Parallel/Series 03SQ 1/3 4.3 1.6 1.4 -
Parallel/Series 04SQ 1/3 5.5 2.0 1.8 -
Parallel/Series 05SQ 1/2 6.7 2.4 2.2 -
Parallel/Series 06SQ 1/2 - 3.8 3.3 4.6
Parallel/Series 07SQ 1 - 4.7 3.8 6.6
Low-height Parallel/Series 08SQ 1/3 5.5 2.5 1.8 -
Low-height Parallel/Series 09SQ 1/3 5.5 2.5 1.8 -
Series Low-height 10SQ 2 x 1/8 11.0 5.0 3.5 -
Parallel Low-Height 10SQ 2 x 1/8 9.4 3.5 3.0
Figure 23. SCR (L) & internal potentiometer (R)
DO NOT SET THISPOTENTIOMETERBELOW THE VOLTAGEOF THE FAN MOTOR.
Max
208 v–277 v
347 v
120 v
Figure 24. ECM control board
28 VAV-SVX08E-EN
Unit Setup
Table 9. VPxF 03SQ ECM CFM
Motor Min CFM: 160Motor Max CFM: 1085
CFM L/sec % Setting
160170179188198
7680848993
12345
207216226235244
98102107111115
678910
254263272282291
120124129133137
1112131415
300310319328338
142146151155159
1617181920
347356366375385
164168173177181
2122232425
394403413422431
186190195199204
2627282930
441450459469478
208212217221226
3132333435
487497506515525
230234239243248
3637383940
534543553562571
252256261265270
4142434445
581590599609618
274278283287292
4647484950
627637646655665
296300305309314
5152535455
674683693702711
318323327331336
5657585960
721730739749758
340345349353358
6162636465
767777786795805
362367371375380
6667686970
814823833842852
384389393397402
7172737475
861870880889898
406411415419424
7677787980
908917926936945
428433437442446
8182838485
954964973982992
450455459464468
8687888990
10011010102010291038
472477481486490
9192939495
10481057106610761085
494499503508512
96979899100
Table 9. VPxF 03SQ ECM CFM (continued)
Motor Min CFM: 160Motor Max CFM: 1085
CFM L/sec % Setting
VAV-SVX08E-EN 29
Unit Setup
Table 10. VPxF 04SQ ECM CFM
Motor Min CFM: 220Motor Max CFM: 1510
CFM L/sec % Setting
220233246259272
104110116122128
12345
285298311324337
135141147153159
678910
350363376389402
165171178184190
1112131415
415429442455468
196202208215221
1617181920
481494507520533
227233239245251
2122232425
546559572585598
258264270276282
2627282930
611624637650663
288294301307313
3132333435
676689702715728
319325331338344
3637383940
741754767780793
350356362368374
4142434445
806819832845859
381387393399405
4647484950
872885898911924
411417424430436
5152535455
937950963976989
442448454461467
5657585960
10021015102810411054
473479485491497
6162636465
10671080109311061119
504510516522528
6667686970
11321145115811711184
534540547553559
7172737475
11971210122312361249
565571577584590
7677787980
12621275128813021315
596602608614620
8182838485
13281341135413671380
627633639645651
8687888990
13931406141914321445
657663670676682
9192939495
14581471148414971510
688694700706713
96979899100
Table 10. VPxF 04SQ ECM CFM (continued)
Motor Min CFM: 220Motor Max CFM: 1510
CFM L/sec % Setting
30 VAV-SVX08E-EN
Unit Setup
Table 11. VPxF 05SQ ECM CFM
Motor Min CFM: 280Motor Max CFM: 1850
CFM L/sec % Setting
280296312327343
132140147155162
12345
359375391407423
170177184192199
678910
438454470486502
207214222229237
1112131415
518534549565581
244252259267274
1617181920
597613629645661
282289297304312
2122232425
676692708724740
319327334342349
2627282930
756772787803819
357364372379387
3132333435
835851867883898
394402409417424
3637383940
914930946962978
431439446454461
4142434445
9941009102510411057
469476484491499
4647484950
10731089110511201136
506514521529536
5152535455
11521168118412001216
544551559566574
5657585960
12311247126312791295
581589596604611
6162636465
13111327134213581374
619626634641649
6667686970
13901406142214381454
656664671678686
7172737475
14691485150115171533
693701708716723
7677787980
15491565158015961612
731738746753761
8182838485
16281644166016761691
768776783791798
8687888990
17071723173917551771
806813821828836
9192939495
17871802181818341850
843851858866873
96979899100
Table 11. VPxF 05SQ ECM CFM (continued)
Motor Min CFM: 280Motor Max CFM: 1850
CFM L/sec % Setting
VAV-SVX08E-EN 31
Unit Setup
Table 12. VPxF 06SQ ECM CFM
Motor Min CFM: 530Motor Max CFM: 2100
CFM L/sec % Setting
530546562577593
250258265273280
12345
609625641657673
287295302310317
678910
688704720736752
325332340347355
1112131415
768784799815831
362370377385392
1617181920
847863879895911
400407415422430
2122232425
926942958974990
437445452460467
2627282930
10061022103710531069
475482490497505
3132333435
10851101111711331148
512520527535542
3637383940
11641180119612121228
549557564572579
4142434445
12441259127512911307
587594602609617
4647484950
13231339135513701386
624632639647654
5152535455
14021418143414501466
662669677684692
5657585960
14811497151315291545
699707714722729
6162636465
15611577159216081624
737744752759767
6667686970
16401656167216881704
774782789796804
7172737475
17191735175117671783
811819826834841
7677787980
17991815183018461862
849856864871879
8182838485
18781894191019261941
886894901909916
8687888990
19571973198920052021
924931939946954
9192939495
20372052206820842100
961969976984991
96979899100
Table 12. VPxF 06SQ ECM CFM (continued)
Motor Min CFM: 530Motor Max CFM: 2100
CFM L/sec % Setting
32 VAV-SVX08E-EN
Unit Setup
Table 13. VSxF 03SQ ECM CFM
Motor Min CFM: 200Motor Max CFM: 1100
CFM L/sec % Setting
200209218227236
9499103107112
12345
246255264273282
116120124129133
678910
291300309318327
137142146150154
1112131415
336346355364373
159163167172176
1617181920
382391400409418
180185189193197
2122232425
427436446455464
202206210215219
2627282930
473482491500509
223227232236240
3132333435
518527536546555
245249253257262
3637383940
564573582591600
266270275279283
4142434445
609618627636646
287292296300305
4647484950
655664673682691
309313318322326
5152535455
700709718727736
330335339343348
5657585960
745755764773782
352356360365369
6162636465
791800809818827
373378382386390
6667686970
836845855864873
395399403408412
7172737475
882891900909918
416420425429433
7677787980
927936945955964
438442446451455
8182838485
97398299110001009
459463468472476
8687888990
10181027103610451055
481485489493498
9192939495
10641073108210911100
502506511515519
96979899100
Table 13. VSxF 03SQ ECM CFM (continued)
Motor Min CFM: 200Motor Max CFM: 1100
CFM L/sec % Setting
VAV-SVX08E-EN 33
Unit Setup
Table 14. VSxF 04SQ ECM CFM
Motor Min CFM: 275Motor Max CFM: 1500
CFM L/sec % Setting
275288300312325
130136142147153
12345
337350362374387
159165171177183
678910
399411424436449
188194200206212
1112131415
461473486498510
218223229235241
1617181920
523535548560572
247253258264270
2122232425
585597609622634
276282288293299
2627282930
646659671684696
305311317323328
3132333435
708721733745758
334340346352358
3637383940
770783795807820
363369375381387
4142434445
832844857869882
393399404410416
4647484950
894906919931943
422428434439445
5152535455
9569689809931005
451457463469474
5657585960
10181030104210551067
480486492498504
6162636465
10791092110411171129
509515521527533
6667686970
11411154116611781191
539544550556562
7172737475
12031215122812401253
568574579585591
7677787980
12651277129013021314
597603609615620
8182838485
13271339135213641376
626632638644650
8687888990
13891401141314261438
655661667673679
9192939495
14511463147514881500
685690696702708
96979899100
Table 14. VSxF 04SQ ECM CFM (continued)
Motor Min CFM: 275Motor Max CFM: 1500
CFM L/sec % Setting
34 VAV-SVX08E-EN
Unit Setup
Table 15. VSxF 05SQ ECM CFM
Motor Min CFM: 350Motor Max CFM: 2050
CFM L/sec % Setting
350367385402419
165173181190198
12345
436453470488505
206214222230238
678910
522539556573591
246254263271279
1112131415
608625642659676
287295303311319
1617181920
694711728745762
327335344352360
2122232425
779797814831848
368376384392400
2627282930
865882900917934
408416425433441
3132333435
95196898510031020
449457465473481
3637383940
10371054107110881106
489498506514522
4142434445
11231140115711741192
530538546554562
4647484950
12091226124312601277
570579587595603
5152535455
12951312132913461363
611619627635643
5657585960
13801398141514321449
651660668676684
6162636465
14661483150115181535
692700708716724
6667686970
15521569158616041621
732741749757765
7172737475
16381655167216891707
773781789797805
7677787980
17241741175817751792
814822830838846
8182838485
18101827184418611878
854862870878886
8687888990
18951913193019471964
895903911919927
9192939495
19811998201620332050
935943951959967
96979899100
Table 15. VSxF 05SQ ECM CFM (continued)
Motor Min CFM: 350Motor Max CFM: 2050
CFM L/sec % Setting
VAV-SVX08E-EN 35
Unit Setup
Table 16. VSxF 06SQ ECM CFM
Motor Min CFM: 700Motor Max CFM: 2500
CFM L/sec % Setting
700718737755773
330339348356365
12345
791809827846864
373382391399408
678910
882900918937955
416425433442451
1112131415
973991100910271046
459468476485493
1617181920
10641082110011181137
502511519528536
2122232425
11551173119112091227
545554562571579
2627282930
12461264128213001318
588596605614622
3132333435
13361355137313911409
631639648656665
3637383940
14271446146414821500
674682691699708
4142434445
15181536155515731591
717725734742751
4647484950
16091627164616641682
759768777785794
5152535455
17001718173617551773
802811820828837
5657585960
17911809182718461864
845854862871880
6162636465
18821900191819361955
888897905914922
6667686970
19731991200920272046
931940948957965
7172737475
20642082210021182136
97498399110001008
7677787980
21552173219122092227
10171025103410431051
8182838485
22452264228223002318
10601068107710851094
8687888990
23362355237323912409
11031111112011281137
9192939495
24272445246424822500
11461154116311711180
96979899100
Table 16. VSxF 06SQ ECM CFM (continued)
Motor Min CFM: 700Motor Max CFM: 2500
CFM L/sec % Setting
36 VAV-SVX08E-EN
Unit Setup
Table 17. LPxF 08SQ ECM CFM
Motor Min CFM: 100Motor Max CFM: 460
CFM L/sec % Setting
100103107111114
4749505254
12345
118121125129132
5657596162
678910
136140143147151
6466686971
1112131415
154158162165169
7375767880
1617181920
172176180183187
8183858788
2122232425
191194198202205
9092939597
2627282930
209212216220223
99100102104105
3132333435
227231234238242
107109111112114
3637383940
245249253256260
116117119121123
4142434445
263267271274278
124126128129131
4647484950
282285289293296
133135136138140
5152535455
300303307311314
142143145147148
5657585960
318322325329333
150152154155157
6162636465
336340344347351
159160162164166
6667686970
354358362365369
167169171172174
7172737475
373376380384387
176178179181183
7677787980
391394398402405
184186188190191
8182838485
409413416420424
193195196198200
8687888990
427431435438442
202203205207209
9192939495
445449453456460
210212214215217
96979899100
Table 17. LPxF 08SQ ECM CFM (continued)
Motor Min CFM: 100Motor Max CFM: 460
CFM L/sec % Setting
VAV-SVX08E-EN 37
Unit Setup
Table 18. LPxF 09SQ ECM CFM
Motor Min CFM: 250Motor Max CFM: 1025
CFM L/sec % Setting
250258265273281
118122125129133
12345
289297305312320
136140144147151
678910
328336344352359
155159162166170
1112131415
367375383391399
173177181184188
1617181920
406414422430438
192196199203207
2122232425
446453461469477
210214218221225
2627282930
485493500508516
229232236240244
3132333435
524532540547555
247251255258262
3637383940
563571579587594
266269273277281
4142434445
602610618626634
284288292295299
4647484950
641649657665673
303306310314317
5152535455
680688696704712
321325329332336
5657585960
720727735743751
340343347351354
6162636465
759767774782790
358362365369373
6667686970
798806814821829
377380384388391
7172737475
837845853861868
395399402406410
7677787980
876884892900908
414417421425428
8182838485
915923931939947
432436439443447
8687888990
955962970978986
450454458462465
9192939495
9941002100910171025
469473476480484
96979899100
Table 18. LPxF 09SQ ECM CFM (continued)
Motor Min CFM: 250Motor Max CFM: 1025
CFM L/sec % Setting
38 VAV-SVX08E-EN
Unit Setup
Table 19. LSxF 08SQ ECM CFM
Motor Min CFM: 100Motor Max CFM: 460
CFM L/sec % Setting
100103107111114
4749505254
12345
118121125129132
5657596162
678910
136140143147151
6466686971
1112131415
154158162165169
7375767880
1617181920
172176180183187
8183858788
2122232425
191194198202205
9092939597
2627282930
209212216220223
99100102104105
3132333435
227231234238242
107109111112114
3637383940
245249253256260
116117119121123
4142434445
263267271274278
124126128129131
4647484950
282285289293296
133135136138140
5152535455
300303307311314
142143145147148
5657585960
318322325329333
150152154155157
6162636465
336340344347351
159160162164166
6667686970
354358362365369
167169171172174
7172737475
373376380384387
176178179181183
7677787980
391394398402405
184186188190191
8182838485
409413416420424
193195196198200
8687888990
427431435438442
202203205207209
9192939495
445449453456460
210212214215217
96979899100
Table 19. LSxF 08SQ ECM CFM (continued)
Motor Min CFM: 100Motor Max CFM: 460
CFM L/sec % Setting
VAV-SVX08E-EN 39
Unit Setup
Table 20. LSxF 09SQ ECM CFM
Motor Min CFM: 240Motor Max CFM: 950
CFM L/sec % Setting
240247255262269
113117120123127
12345
276283290298305
130134137140144
678910
312319326333341
147151154157161
1112131415
348355362369376
164167171174178
1617181920
384391398405412
181184188191195
2122232425
419427434441448
198201205208211
2627282930
455462470477484
215218222225228
3132333435
491498505513520
232235239242245
3637383940
527534541548556
249252255259262
4142434445
563570577584592
266269272276279
4647484950
599606613620627
283286289293296
5152535455
635642649656663
299303306310313
5657585960
670678685692699
316320323327330
6162636465
706713721728735
333337340343347
6667686970
742749756764771
350354357360364
7172737475
778785792799807
367371374377381
7677787980
814821828835842
384387391394398
8182838485
850857864871878
401404408411415
8687888990
885893900907914
418421425428431
9192939495
921928936943950
435438442445448
96979899100
Table 20. LSxF 09SQ ECM CFM (continued)
Motor Min CFM: 240Motor Max CFM: 950
CFM L/sec % Setting
40 VAV-SVX08E-EN
Unit Setup
Table 21. LSxF 10SQ ECM CFM
Motor Min CFM: 400Motor Max CFM: 1800
CFM L/sec % Setting
400414428443457
189196202209216
12345
471485499513527
222229236242249
678910
542556570584598
256262269276282
1112131415
612626641655669
289296302309316
1617181920
683697711725740
322329336342349
2122232425
754768782796810
356362369376382
2627282930
824838853867881
389396402409416
3132333435
895909923937952
422429436442449
3637383940
96698099410081022
456462469476482
4142434445
10361051106510791093
489496502509516
4647484950
11071121113511501164
523529536543549
5152535455
11781192120612201234
556563569576583
5657585960
12491263127712911305
589596603609616
6162636465
13191333134813621376
623629636643649
6667686970
13901404141814321447
656663669676683
7172737475
14611475148915031517
689696703709716
7677787980
15311545156015741588
723729736743749
8182838485
16021616163016441659
756763769776783
8687888990
16731687170117151729
789796803809816
9192939495
17431758177217861800
823829836843850
96979899100
Table 21. LSxF 10SQ ECM CFM (continued)
Motor Min CFM: 400Motor Max CFM: 1800
CFM L/sec % Setting
VAV-SVX08E-EN 41
Wiring Diagrams
Note: See programming guides listed below for detailed wiring information on the following:
Heaters with Contactors
UCM 4.2: VAV-SVX01*-EN UC400: VAV-SVX07*-EN VV550: VAV-SVP01*-EN
Figure 25. Single-duct units (typical of single phase voltages - 1 leg)
42 VAV-SVX08E-EN
Wiring Diagrams
Figure 26. Single-duct units (typical of single phase voltages - 2 leg)
VAV-SVX08E-EN 43
Wiring Diagrams
Figure 30. Fan-powered control boxes
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
EXTERNAL TO CONTROL BOX.
OPTIONAL OR ALTERNATE CIRCUITRY
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
DETERMINED BY MOTOR VOLTAGE ON ORDER.
FUSE IS OPTIONAL.
VOLTAGE FOUND ON UNIT NAMEPLATE.
6.
5.
4.
CAPACITOR IS INSTALLED ON FAN HOUSING.
FACTORY INSTALLEDBY OTHERS
3.
2.
NOTES:
1.
NO
P.E. SWITCH-2
CC
P.E. SWITCH-1
BK
NC
BK
NC
BK NO
NO
NC
C
6.
6.
6.
2. 2.
2.
5. 5.
5.
3. 3.
3.
4. 4.
4.
}
BK
24V1 3
2 4
R
MOTORRELAY
BR
TRANSFORMER
FUSE
BK
BK W
GROUNDSCREW
GREEN
DISCONNECTSWITCH
BK W
L1 N
24V BKBL
Y
CONTROLLER
CAPACITOR
BR BR
FANMOTOR
BLOCKTERMINAL
W BK
BRR
BK
CONTROLSPEEDMOTOR
W
W
W-C
OM
BK
LINE VOLTAGE
OR FROM HEATER TERMINAL
TO VAV
Fan-powered Control Boxwith Electronic or DDC Controls
CAPACITOR MOTORFAN
SWITCHDISCONNECT
OR FROM HEATER TERMINAL
LINE VOLTAGE
Fan-powered Control Boxwith Pneumatic ControlsDuct Pressure Switch Option
BRBR
TERMINAL
W-C
OM
BKW
BK
BLOCK
R
24V1 3
TRANSFORMER
MOTOR
BK
BR
RELAY
24V BK
2 4
GREENGROUND
SCREW
CONTROLSPEEDMOTOR
W
W
FUSE
BK
BK
BK
W
W
BK
L1 N
DUCT PRESSURESWITCH
CAPACITOR MOTORFAN
Fan-powered Control Boxwith Pneumatic Controls
BRBR
P.E. SWITCH
TERMINAL
W-C
OM
W BK
BLOCK
BK
CONTROLSPEEDMOTOR
W
W
LINE VOLTAGE
SWITCHDISCONNECT
OR FROM HEATER TERMINAL
GREENGROUND
SCREW
FUSE
BK
BK
BK
BK
W
W
L1 N
BK
C
NO
NC
DUCT PRESSURE MAIN CONTROL
FAN CONTROL BOX FAN CONTROL BOX
FAN CONTROL BOX
CAPACITORS BEFORE SERVICING.DISCHARGE MOTOR START/RUN
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSESEVERE PERSONAL INJURY OR DEATH.
UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OF
FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
USE COPPER CONDUCTORS ONLY!
CONDUCTORS.
SERVICING.REMOTE DISCONNECTS BEFORE
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING
WARNINGWARNING
CAUTIONCAUTION
}
}
}
VAV-SVX08E-EN 47
Wiring Diagrams
Figure 31. Fan-powered units with ECM
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
EXTERNAL TO CONTROL BOX.
OPTIONAL OR ALTERNATE CIRCUITRY
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
DETERMINED BY MOTOR VOLTAGE ON ORDER.
FUSE IS OPTIONAL.
VOLTAGE FOUND ON UNIT NAMEPLATE.
5.
4.
3.
FACTORY INSTALLEDBY OTHERS
2.
NOTES:
1.
NO
P.E. SWITCH-2
CC
P.E. SWITCH-1
BK
NC
BK
NC
BK NO
5.
3.
4.
4.
4.
RED
NEUT.
W BK G R
RED
24V
BL
Y
RBK
NEUT.
RED
GW
RED
24V
BL
Y
1 24V 3
2 4
RED RED
GW BK R
24VNEUT.
BK
BOARDECM
ECMBOARD
MOTORRELAY
ECMBOARD
}
Fan-powered Control Box w/ ECM with Electronic or DDC Controls(Depending on the size of the unit, the ECM board may or may not be locatedin the fan control box.)
OR FROM HEATER TERMINAL
LINE VOLTAGE
Fan-powered Control Box with Pneumatic Controls
LINE VOLTAGE
OR FROM HEATER TERMINAL
DUCT PRESSURE MAIN CONTROL
CORRECTION
PRESSURE
SWITCH
DUCT
C
NC
TRANSFORMER
BK 24V
Y
BL
CHOKE
BL
NO BL
DISCONNECT
BK
SWITCH3.
FUSE
FACTORPOWER
W
BK W
SCREW
2.
GROUNDGREEN
GR
TERMINAL
BK
BLOCK
MOTOR
FAN
Fan-powered Control Box w/ ECM with Pneumatic ControlsDuct Pressure Switch Option
P.E. SWITCH
DISCONNECTSWITCH
C
FUSE
NC
CORRECTION CHOKE
TRANSFORMER
NO
BK BL
Y
24V
BK
POWER FACTOR
BLOCK
2.
W
BK W
FANMOTOR
TERMINAL
GR
GREENGROUNDSCREW
BK
5.
CORRECTION CHOKE
POWER FACTOR
FAN CONTROL BOX
TRANSFORMER
BK W
DISCONNECT
FUSE
3. W
2.
SWITCH
3.
24V
BL
Y
BLOCKTERMINAL
OR FROM HEATER TERMINAL
GR
L1
GROUNDSCREW
GREEN
N
LINE VOLTAGE
BKW
MOTORFAN
CONTROLLER
TO VAV
Y
BK
FAN CONTROL BOX
FAN CONTROL BOX
CAPACITORS BEFORE SERVICING.DISCHARGE MOTOR START/RUN
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSESEVERE PERSONAL INJURY OR DEATH.
UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OF
FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
USE COPPER CONDUCTORS ONLY!
CONDUCTORS.
SERVICING.REMOTE DISCONNECTS BEFORE
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING
CAUTIONCAUTION
WARNINGWARNING
} }
}
48 VAV-SVX08E-EN
Wiring Diagrams
Figure 32. Fan-powered low-height units
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
EXTERNAL TO CONTROL BOX.
OPTIONAL OR ALTERNATE CIRCUITRY
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
DETERMINED BY MOTOR VOLTAGE ON ORDER.
FUSE IS OPTIONAL.
VOLTAGE FOUND ON UNIT NAMEPLATE.
6.
5.
4.
FACTORY INSTALLEDBY OTHERS
2.
NOTES:
1.
NO
P.E. SWITCH-2
CC
P.E. SWITCH-1
BK
NC
BK
NC
BK NO
6.
BLOCKTERMINAL
24V
24V
1
W
2
W
3
4
CAPACITOR IS INSTALLED ON FAN HOUSING.3.
Fan-Powered Low-Height Control Box with Electronic or DDC Controls
Fan-Powered Low-Height Control Box with Pneumatic Controls
DUCT PRESSURE MAIN CONTROL
Fan-Powered Low-Height Control Box with Pneumatic ControlsDuct Pressure Switch Option
BR
MOTOR
CONTROL
BLOCKTERMINAL
SPEED
P.E. SWITCH
CNC
NO
BK
BK
FUSE
BK
4.
SWITCH
DISCONNECT
BK
W
2.
GREEN
SCREW
GROUND
W
L1 N
2.
BR3.
FAN CONTROL BOX
W
BR
W
W
W W
BR
CAPACITOR W
CAPACITORBK
BK
MOTORFAN
3.
MOTOR 2(SIZE 10 ONLY)
FAN
OR FROM HEATER TERMINAL
LINE VOLTAGE 5.
CAPACITOR
MOTOR
CONTROL
MOTOR
RELAY
SPEED
NO
PRESSURE
SWITCH
DUCT
BL C
NC TRANSFORMER
BL Y
FUSE
BK
BK
L1
DISCONNECT
BK
BK
SWITCH
SCREW
GROUND
2.
N
GREEN
BR
FAN CONTROL BOX
BL
BK
BK
W
W
BK
W W
BR
2.
BR
W
BRW
BK
3.
MOTOR
FAN
CAPACITOR
3.
LINE VOLTAGE
OR FROM HEATER TERMINAL
5.
MOTOR
W or BR
24V1
R
3
BR
FUSE
4.
TERMINAL
RELAY
MOTOR2
BK
BK
4
BK WBR
BLOCK
SWITCH
DISCONNECT
SCREW
GROUND
GREEN
WBK
2.
L1 N
CONTROL
SPEED
MOTOR
BR
2.
BR
CAPACITOR
3.
TRANSFORMER
FAN CONTROL BOX
TO VAV
R
BR
BK 24V
BL
Y
W
W
W W
W BK
WBK
BR
CAPACITOR
FAN
BR
3.
OR FROM HEATER TERMINAL
LINE VOLTAGE5.
CONTROLLER
BK
(SIZE 10 ONLY)MOTOR 2
FAN
(SIZE 10 ONLY)MOTOR 2
FAN
4.
6.
CAUTIONCAUTION
WARNINGWARNING
}
BR
UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.
FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
USE COPPER CONDUCTORS ONLY!
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSESEVERE PERSONAL INJURY OR DEATH.
REMOTE DISCONNECTS BEFORE
DISCHARGE MOTOR START/RUN CAPACITORS BEFORE SERVICING.
SERVICING.
}
}
VAV-SVX08E-EN 49
Wiring Diagrams
Figure 33. Fan-powered low-height units with ECM
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
EXTERNAL TO CONTROL BOX.
OPTIONAL OR ALTERNATE CIRCUITRY
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
DETERMINED BY MOTOR VOLTAGE ON ORDER.
FUSE IS OPTIONAL.
VOLTAGE FOUND ON UNIT NAMEPLATE.
5.
4.
3.
FACTORY INSTALLEDBY OTHERS
2.
NOTES:
1.
NO
P.E. SWITCH-2
CC
P.E. SWITCH-1
BK
NC
BK
NC
BK NO
5.
W GBK R
NEUT.
RED
24V
RED
BL
NEUT.
RED
24V
RED
RBKW G
BL
BL
4
W G RBK
NEUT.
RED
BK
24V
RED
24V 31
2
BOARDECM
BOARDECM
MOTORRELAY
BOARDECM
OR FROM HEATER TERMINAL
LINE VOLTAGE
Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls
DUCT PRESSURE MAIN CONTROL
Fan-Powered Low-Height Control Box w/ ECM with Pneumatic ControlsDuct Pressure Switch Option
(SIZE 10 ONLY)
DISCONNECTSWITCH
FUSE
3.
TRANSFORMER
BK
BLOCKTERMINAL
W
2.
24V
BL
Y
BK W
FANMOTOR
GR
GREENGROUNDSCREW
4.
W BK BK
W
MOTOR 2FAN
TO VAV
OR FROM HEATER TERMINAL
LINE VOLTAGE
MOTOR
BL
DUCT
SWITCH
PRESSURE
TRANSFORMER
BLBK 24V
Y
BL
C
NC
NO
FUSE
3.
BK
BK
DISCONNECTSWITCH
2.
W
W
SCREWGROUNDGREEN
GR
W BK
4.
Y
BK
TERMINALBLOCK
W
FAN FAN
(SIZE 10 ONLY)MOTOR 2
CONTROLLER
NO
P.E. SWITCH
C
NC
DISCONNECTSWITCH
FUSE
3.
BK W
TRANSFORMER
BK 24V
BL
Y
BLOCKTERMINAL
2.
W
GROUNDSCREW
GREEN
BKW
GR
4.FAN
MOTOR
Y
WBK
(SIZE 10 ONLY)MOTOR 2
FANLINE VOLTAGE
OR FROM HEATER TERMINAL
5.
Fan-Powered Low-Height Control Box w/ ECM with Electronic or DDC Controls(Depending on the size of the unit, the ECM board may or may not be locatedin the fan control box.)
Y
CAUTIONCAUTION
WARNINGWARNING
}
}
FAN CONTROL BOX FAN CONTROL BOX
FAN CONTROL BOX
CAPACITORS BEFORE SERVICING.DISCHARGE MOTOR START/RUN
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSESEVERE PERSONAL INJURY OR DEATH.
UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OF
FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
USE COPPER CONDUCTORS ONLY!
CONDUCTORS.
SERVICING.REMOTE DISCONNECTS BEFORE
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING
}
}
50 VAV-SVX08E-EN
Maintenance
Periodic maintenance of the VariTrane product is minimal, but necessary for efficient operation. Routine maintenance consists of inspecting/replacing the air filters of the fan-powered terminals.
Motors
Both the PSC (permanent split capacitor) and the ECM (Electrically Commutated Motor) require no lubrication during its normal life of operation.
Fan Wheel
Periodically, the fan wheel should be inspected for dirt or debris and cleaned as necessary.
Filter
The filter on fan-powered terminals will need to be inspected/replaced routinely depending on the environmental conditions of the plenum.
Filter Change Out
• To remove the filter, turn each of the filter retaining clips 90° (CW or CCW)
• Remove the filter and replace with new filter of the same frame size.
• Return the filter clips to their retainng position by turning them 90° (CW or CCW) back to their original position.
Water Coil
Water coils should be inspected and the fins should be cleaned periodically.
Water coils have been provided with an access panel as standard to assist with inspection and cleaning.
Fan Motor Replacement
Standard height fan-powered series and parallel fan motors are replaceable through the filter opening and the standard sliding side access panel. To access the fan motor, the fan housing must be detached by removing the mounting bolts that hold the housing to the fan board. Removing the entire housing allows the fan motor, fan housing, and fan wheel to be re-aligned on a workbench or floor and prevent any possible fan wheel rubbing that may occur. Removing the housing will provide access to the motor shaft set screw that holds the fan wheel to the motor shaft.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN.
Figure 34. Standard motor removal
VAV-SVX08E-EN 51
Maintenance
The low-height fan assembly was designed with an inlet ring that assists with removal of the fan motor. To access the fan motor assembly, the bottom panel must be removed. The inlet ring is held in place by six bolts and three motor mount bolts. Remove these bolts and the motor and fan wheel will come out of the fan housing.
SCR Assembly
SCR solid state relays are used to switch a single heater stage on and off. An intelligent (Master) relay is used for all single phase applications. For three phase applications, a Master-Slave configuration is used to switch two legs of three phase power to the heater stage. The Master Relay controls one leg independently, and provides a control signal to the Slave Relay, which controls the second leg.
Every Master or Master/Slave relay combination is mounted on a heat sink to prevent the relays from overheating during normal operation. The SCR assembly must always be mounted with the heat sink fins oriented vertically (See Figure 36, p. 52), with a minimum clearance of ½" on all sides of the heat sink for cooling. Where additional cooling slots are provided in the heater, the VAV unit must be mounted with a minimum of 1" clearance in front of the slots.
When the 0-10 VDC control voltage is present at the Master relay in both single and three phase applications, an "ON" indicating LED light on the Master relay will blink continually (approximately 0.5 seconds on, 1.0 seconds off). If the load side voltage is also present at the relay(s), the Master relay LED and the Slave relay LED blink rate will increase as the control signal increases. When the control signal reaches a maximum of 10VDC, all LEDs will be lit continuously, indicating that the relays are full-open and continuously conducting. If the control signal is present in three phase applications while the load side voltage is not, only the Master relay LED will light and the blink rate will be constant.
If the SCR assembly does not appear to be functioning properly, verify that all required voltages are present and all that all wiring is properly connected. If all these conditions are verified, and the SCR LED(s) does not light and/or the SCR relay(s) does not conduct, the entire SCR heat sink assembly should be changed out. Individual Master or Slave relays should not be replaced.
Figure 35. Low-height motor removal
Figure 36. Typical heat sink fin orientation
Bottom View
52 VAV-SVX08E-EN
Installation of Diffusers
General
All units must be installed upright and level as indicated bythe arrow on the side of the units. Return air slots shouldbe placed perpendicular and offset to the slot diffusers toavoid short-circuiting of air distribution patterns.
Place the unit in its approximate final position and checkthat it is upright and level. For single-slot units, engagethe back of the diffuser over the t-bar with an edge andboth ends resting on the t-bar. For double-slot units,slide the unit over the t-bar. For center-notch units, placediffuser over the t-bar, straddling it across a t-bar andresting on the units ends.
If the unit has a fire damper, make sure that the damper isstill fully open. Diffuser discharge must always be flushwith the ceiling tiles to assure the proper airflow (Coandaeffect).
Diffusers require specific installation information whenmounting to a desired ceiling type. Select the ceiling typethat closely matches the job site application and use thefollowing procedures.
T-Bar Ceiling
Finish installation of the diffuser in t-bar ceiling. (SeeFigure 37, p. 53.) Follow these procedures before theceiling construction is completed.
1. Position the diffuser at each end resting directly on thestructural t-bar for support and the t-bar fitting into thechannel provided at the unit discharge air throw.
2. A ceiling tile support flange is provided on each side ofthe discharge slot of the unit.Trim ceiling tileapproximately 1½ inches each to allow for width ofdischarge slot. For revealed edge ceilings, tile must becut in a “Z” pattern.
3. Install ceiling tiles in usual manner with cut edgesresting on the flanges of the air slot.
Concealed Spline Ceiling
Follow these procedures to finish installation of controland satellite diffusers and concealed spline for suspensionceilings before completing the ceiling construction(Figure 38, p. 53).
Place the units in their approximate final positions. If usingthe trim angle diffuser, its slots must be even with thespline level. If applying the trim accessory, the bottom ofthe diffuser must be level with the finished ceiling.
If installing the trim accessory, insert the trim into theceiling opening from below and engage the diffuser slot tothe trim t-bar structure. With bottom flange of trimaccessory against the ceiling, and using the pre-drilledholes in the flange as a guide, drill holes in the flange of thediffuser. Join the diffuser and trim accessory with self-taping sheet metal.
Figure 37. Diffuser installation in t-bar ceiling
Figure 38. Diffuser with trim accessory installation in
concealed spline ceiling
VAV-SVX08E-EN 53
Installation of Diffusers
Drywall/Plaster Ceiling
Finish installation of diffusers in plaster ceiling. Followthese procedures before completing the ceilingconstruction (Figure 39, p. 54).
1. Suspend the units above the intended ceiling level andtheir approximate horizontal positions and finishrunning flexible ductwork.
2. After drywall and/or plaster is installed, cut openings toreceive the diffuser air outlets. Also, allow for accessopenings to complete installation and service of theunit.
3. Slide the trim accessory up and into the ceilingopening. Using the rim accessory as a template, drillfour guide holes in the lip of the diffuser slot. Lowerunit onto trim frame and attach with sheet metalscrews.
Note: The bottom of the throat section must be parallel tothe ceilings for proper air distribution.
NOTICE:
Equipment Damage!
Do not install trim frame into ceiling using screws.When diffuser is placed on the trim frames, it will pullout.
Figure 39. Diffuser with trim accessory installation in
plaster ceiling
Plaster trim frame attaches with 2–4tension clips on the side of the diffuser.
Trim Accessory
Diffuser Flange
54 VAV-SVX08E-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
We are committed to using environmentally
conscious print practices that reduce waste.
© 2014 Trane All rights reserved
VAV-SVX08E-EN 16 Sep 2014
Supersedes VAV-SVX08D-EN (27 Jun 2013)