installation instructions r--410a single package gas ... · pgd/s324--60 1&3phase ... be aware of...

48
INSTALLATION INSTRUCTIONS R--410A Single Package Gas/Electric Units PGD/S324--60 1 & 3 Phase These instructions must be read and understood completely before attempting installation Safety Labeling and Signal Words DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manual that may apply to the product. DANGER -- Immediate hazards which will result in severe personal injury or death. WARNING --Hazards or unsafe practices which could result in severe personal injury or death. CAUTION -- Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE -- Used to highlight suggestions which will result in enhanced installation, reliability, or operation. ! WARNING Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: The signal word CAUTION is used throughout this manual in the following manner: ! CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures or product labels. SAFETY CONSIDERATIONS 2 .................. RECEIVING AND INSTALLATION 2 .............. Step 1 -- Check Equipment 2 .................... Step 2 -- Provide Unit Support 3 .................. Step 3 -- Field Fabricate Ductwork 3 .............. Step 4 -- Provide Clearances 7 ................... Step 5 -- Rig and Place Unit 7 ................... Step 6 -- Connect Condensate Drain 10 ............ Step 7 -- Install Flue Hood 10 ..................... Step 8 -- Install Gas Piping 10 .................... Step 9 -- Install Duct Connections 11 .............. Step 10 -- Install Electrical Connections 12 ......... PRE--START--UP 14 ............................. START--UP 14 .................................. Step 1 -- Check for Refrigerant Leaks 14 ........... Step 2 -- Start--Up Heating andAdjustments 14 ..... Wiring Diagrams 17 ............................. Step 3 -- Start--Up Cooling and Adjustments 23 ..... Maintenance 39 ................................. Troubleshooting 43 .............................. Start--Up Checklist 47 ........................... IMPORTANT: Effective January 1, 2015, all split system and packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy. TABLE OF CONTENTS PAGE ! WARNING PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death. The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with proper tools and test instruments. Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part 1 CSA C.22.1. The National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1, and in Canada refer to the current editions of the National Standards of Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane Installation codes. 50901340303 03/2015

Upload: others

Post on 31-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • INSTALLATION INSTRUCTIONSR--410A Single Package Gas/Electric Units

    PGD/S324--601 & 3 Phase

    These instructions must be read and understood completely before attempting installation

    Safety Labeling and Signal WordsDANGER, WARNING, CAUTION, and NOTEThe signal words DANGER, WARNING,CAUTION, and NOTE are used to identify levels ofhazard seriousness. The signal word DANGER is onlyused on product labels to signify an immediate hazard.The signal wordsWARNING,CAUTION, andNOTEwillbe used on product labels and throughout this manualand other manual that may apply to the product.

    DANGER -- Immediate hazards which will result insevere personal injury or death.

    WARNING --Hazards or unsafe practices which couldresult in severe personal injury or death.

    CAUTION -- Hazards or unsafe practices which mayresult in minor personal injury or product or propertydamage.

    NOTE -- Used to highlight suggestions which will resultin enhanced installation, reliability, or operation.

    ! WARNING

    Signal Words in ManualsThe signal word WARNING is used throughoutthis manual in the following manner:

    The signal word CAUTION is used throughoutthis manual in the following manner:

    ! CAUTIONSignal Words on Product LabelingSignal words are used in combination with colorsand/or pictures or product labels.

    SAFETY CONSIDERATIONS 2. . . . . . . . . . . . . . . . . .RECEIVING AND INSTALLATION 2. . . . . . . . . . . . . .Step 1 -- Check Equipment 2. . . . . . . . . . . . . . . . . . . .Step 2 -- Provide Unit Support 3. . . . . . . . . . . . . . . . . .Step 3 -- Field Fabricate Ductwork 3. . . . . . . . . . . . . .Step 4 -- Provide Clearances 7. . . . . . . . . . . . . . . . . . .Step 5 -- Rig and Place Unit 7. . . . . . . . . . . . . . . . . . .Step 6 -- Connect Condensate Drain 10. . . . . . . . . . . .Step 7 -- Install Flue Hood 10. . . . . . . . . . . . . . . . . . . . .Step 8 -- Install Gas Piping 10. . . . . . . . . . . . . . . . . . . .Step 9 -- Install Duct Connections 11. . . . . . . . . . . . . .Step 10 -- Install Electrical Connections 12. . . . . . . . .PRE--START--UP 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . .START--UP 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Step 1 -- Check for Refrigerant Leaks 14. . . . . . . . . . .Step 2 -- Start--Up Heating and Adjustments 14. . . . .Wiring Diagrams 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . .Step 3 -- Start--Up Cooling and Adjustments 23. . . . .Maintenance 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Troubleshooting 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Start--Up Checklist 47. . . . . . . . . . . . . . . . . . . . . . . . . . .

    IMPORTANT: Effective January 1, 2015, all split system andpackaged air conditioners must be installed pursuant toapplicable regional efficiency standards issued by theDepartment of Energy.

    TABLE OF CONTENTS PAGE

    ! WARNINGPERSONAL INJURY, AND/OR PROPERTYDAMAGE HAZARDFailure to carefully read and follow this warningcould result in equipment malfunction, propertydamage, personal injury and/or death.Installation or repairs made by unqualifiedpersons could result in equipment malfunction,property damage, personal injury and/or death.

    The information contained in this manual isintended for use by a qualified service technicianfamiliar with safety procedures and equippedwith proper tools and test instruments.

    Installation must conform with local buildingcodes and with the national Electrical CodeNFPA70 current edition or Canadian ElectricalCode part 1 CSA C.22.1. The National Fuel GasCode (NFGC) NFPA 54/ANSI Z223.1, and inCanada refer to the current editions of theNational Standards of CanadaCAN/CSA--B149.1 and .2 Natural Gas andPropane Installation codes.

    50901340303 03/2015

  • 250901340303

    NOTE: Read the entire instruction manual before starting theinstallation.NOTE: Installer: Make sure the Owner’s Manual and ServiceInstructions are left with the unit after installation.

    Fig. 1 -- Unit PGD3/PGS3 (Low NOx models available)

    SAFETY CONSIDERATIONSImproper installation, adjustment, alteration, servicemaintenance, or use can cause explosion, fire, electrical shock,or other conditions which may cause death, personal injury, orproperty damage. Consult a qualified installer, service agency, oryour distributor or branch for information or assistance. Thequalified installer or agency must use factory--authorized kits oraccessories when modifying this product. Refer to the individualinstructions packaged with the kits or accessories wheninstalling.Follow all safety codes. Wear safety glasses, protective clothing,and work gloves. Have a fire extinguisher available. Read theseinstructions thoroughly and follow all warnings or cautionsincluded in literature and attached to the unit. consult localbuilding codes, the current editions of the National Fuel GasCode (NFGC) NFPA 54/ANSI Z223.1, and the National ElectricalCode (NEC) NFPA 70.In Canada refer to the current editions of the National Standardsof Canada CAN/CSA--B149.1 and .2 Natural Gas and PropaneInstallation codes, and Canadian Electrical Code CSA C22.1

    Recognize safety information. This is the safety--alert symbol .When you see this symbol on the unit and in instructions ormanuals, be alert to the potential for personal injury. Understandthese signal words: DANGER, WARNING, and CAUTION.These words are used with the safety--alert symbol. DANGERidentifies the most serious hazards which will result in severepersonal injury or death. WARNING signifies hazards whichcould result in personal injury or death. CAUTION is used toidentify unsafe practices which may result in minor personalinjury or product and property damage. NOTE is used tohighlight suggestions which will result in enhanced installation,reliability, or operation.

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal injury ordeath.

    Before installing or servicing system, always turn off mainpower to system and install lockout tag. There may be morethan one disconnect switch.

    ! WARNING

    FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBONMONOXIDE POISONING HAZARD

    Failure to follow this warning could result in personal injury orunit damage.

    A qualified installer or agency must use onlyfactory--authorized kits or accessories when modifying thisproduct.

    WARNING!

    CUT HAZARD

    Failure to follow this caution may result in personal injury.

    When removing access panels or performing maintenancefunctions inside your unit, be aware of sharp sheet metal partsand screws. Although special care is taken to reduce sharpedges to a minimum, be extremely careful and wearappropriate clothing, safety glasses, and gloves whenhandling parts or reaching into the unit.

    CAUTION!

    INTRODUCTIONThe PGD3/PGS3 units (see Fig. 1) are a fully self--contained,combination Category I gas heating/electric cooling unitdesigned for outdoor installation (See Fig. 3 and 4 for unitdimensions). All unit sizes have return and discharge openingsfor both horizontal and downflow configurations, and are factoryshipped with all downflow duct openings covered. Units may beinstalled either on a rooftop or on a cement slab. (See Fig. 5 forroof curb dimensions).Models with the number “1” in the 13th position of the modelnumber are dedicated Low NOx units designed for Californiainstallations. These models meet the California maximum oxidesof nitrogen (NOx) emissions requirements of 40 nanograms/jouleor less as shipped from the factory and must be installed inCalifornia Air Quality Management Districts or any other regionsin North America where a Low NOx rule exists.NOTE: Low NOx requirements apply only to natural gasinstallations.In gas heating mode, this unit is designed for a minimumcontinuous return--air temperature of 55F (13C) db and amaximum continuous return--air temperature of 80F (27C) db.Failure to follow these return--air temperature limits may affectreliability of heat exchangers, motors, and other components.

    RECEIVING AND INSTALLATIONStep 1 — Check Equipment

    Identify Unit

    The unit model number and serial number are stamped on theunit information plate. Check this information against shippingpapers.

    Inspect Shipment

    Inspect for shipping damage before removing packagingmaterials. If unit appears to be damaged or is torn loose from itsanchorage, have it examined by transportation inspectors beforeremoval. Forward claim papers directly to transportationcompany. Manufacturer is not responsible for any damageincurred in transit. Check all items against shipping list.Immediately notify the nearest equipment distribution office ifany item is missing. To prevent loss or damage, leave all parts inoriginal packages until installation.

  • 3 50901340303

    Step 2 — Provide Unit SupportIMPORTANT: The unit must be secured to the curb by installingscrews through the bottom of the curb flange and into the unitbase rails. When installing large base units onto the commoncurb, the screws must be installed before allowing the full weightof the unit to rest on the curb. A minimum of six screws arerequired for large base units. Failure to secure unit properlycould result in an unstable unit. See Warning near Rigging/Liftinginformation and accessory curb instructions for more details.For hurricane tie downs, contact distributor for details and PE(Professional Engineering) Certificate if required.

    Roof Curb

    Install accessory roof curb in accordance with instructionsshipped with curb (See Fig. 5). Install insulation, cant strips,roofing, and flashing. Ductwork must be attached to curb.IMPORTANT: The gasketing of the unit to the roof curb is criticalfor a watertight seal. Install gasketing material supplied with theroof curb. Improperly applied gasketing also can result in airleaks and poor unit performance.Curb should be level to within 1/4 in. (6.35 mm) (See Fig. 2). Thisis necessary for unit drain to function properly. Refer toaccessory roof curb installation instructions for additionalinformation as required.Accessory kits are available to aid in installing a new metal baserail unit on an old roof curb.Accessory kit number CPADCURB001A00, (small chassis) andaccessory kit number CPADCURB002A00, (large chassis)includes roof curb adapter and gaskets for the perimeter sealand duct openings. No additional modifications to curb arerequired when using this kit.

    Slab Mount

    Place the unit on a solid, level pad that is at least 2 in. (51 mm)above grade. The pad should extend approximately 2 in. (51mm) beyond the casing on all 4 sides of the unit. (See Fig. 2.)Do not secure the unit to the slab except when required by localcodes.

    Fig. 2 -- Slab Mounting Details

    OPTIONALRETURN

    AIROPENING

    OPTIONALSUPPLY

    AIROPENING

    EVAP. COIL COND. COIL

    2˝(50.8mm)

    Step 3 — Field Fabricate DuctworkSecure all ducts to roof curb and building structure on verticaldischarge units. Do not connect ductwork to unit. For horizontalapplications, unit is provided with flanges on the horizontalopenings. All ductwork should be secured to the flanges.Insulate and weatherproof all external ductwork, joints, and roofopenings with counter flashing and mastic in accordance withapplicable codes.Ducts passing through an unconditioned space must beinsulated and covered with a vapor barrier.If a plenum return is used on a vertical unit, the return should beducted through the roof deck to comply with applicable firecodes.Read unit rating plate for any required clearances aroundductwork. Cabinet return--air static shall not exceed --.25 IN.W.C.

  • 450901340303

    Fig. 3 -- PGD3/PGS324--36 Unit Dimensions

  • 5 50901340303

    Fig. 4 -- PGD3/PGS342--60 Unit Dimensions

  • 650901340303

    Fig. 5 -- Roof Curb Dimensions

    RETURNAIR

    SMALLBASEUNIT

    SUPPLYAIR

    LARGEBASEUNIT

    UNIT PLACEMENT ONCOMMON CURB

    LARGE CURB SMALL OR LARGE BASE UNIT

    SMALL/COMMON CURB

    ROOF CURB DETAIL

    Wood nailer*

    (field supplied)

    *Provided with roofcurb

    Cant stripfield supplied

    Roofing materialfield supplied

    Flashing fieldsupplied

    HVAC unitbase rails

    Roofcurb

    SealingGasket

    HVAC unitbasepan

    Anchor screw

    C

    B

    AF

    DE

    Dashed lines show cross supportlocation for large basepan units.

    G

    H

    C

    B

    AF

    D

    E

    G

    H

    UNITSIZE

    CATALOGNUMBER

    AIN. (mm)

    B (small /commonbase)

    IN. (mm)*B (large base)IN. (mm)*

    CIN. (mm)

    DIN. (mm)

    EIN. (mm)

    FIN. (mm)

    GIN. (mm)

    HIN. (mm)

    Smallor

    Large

    CPRFCURB010A00 11 (279)10 (254)

    14 (356) 16 (406) 47.8(1214)

    32.4 (822)2.7 (69)

    30.6 (778)46.1 (1170)CPRFCURB011A00 14 (356)

    LargeCPRFCURB012A00 11 (279)

    14 (356) 43.9(1116) 42.2 (1072)CPRFCURB013A00 14 (356)

    * Part Numbers CPRFCURB010A00 and CPRFCURB011A00 can be used on both small and large basepan units. The cross supports must be located based on whether theunit is a small basepan or a large basepan.NOTES:

    1. Roof curb must be set up for unit being installed.

    2. Seal strip must be applied, as required, to unit being installed.

    3. Roof curb is made of 16--gauge steel.

    4. Attach ductwork to curb (flanges of duct rest on curb).

    5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.

  • 7 50901340303

    Step 4 — Provide ClearancesThe required minimum operating and service clearances areshown in Fig. 3 and 4. Adequate combustion, ventilation andcondenser air must be provided.IMPORTANT: Do not restrict outdoor airflow. An air restriction ateither the outdoor--air inlet or the fan discharge may bedetrimental to compressor life.The condenser fan pulls air through the condenser coil anddischarges it through the top grille. Be sure that the fandischarge does not recirculate to the condenser coil. Do notlocate the unit in either a corner or under an overheadobstruction. The minimum clearance under a partial overhang(such as a normal house overhang) is 48--in. (1219 mm) abovethe unit top. The maximum horizontal extension of a partialoverhang must not exceed 48--in. (1219 mm).Do not place the unit where water, ice, or snow from anoverhang or roof will damage or flood the unit. Do not install theunit on carpeting or other combustible materials. Slab--mountedunits should be at least 2 in. (51 mm) above the highestexpected water and runoff levels. Do not use unit if it has beenunder water.

    Step 5 — Rig and Place UnitRigging and handling of this equipment can be hazardous formany reasons due to the installation location (roofs, elevatedstructures, etc.).Only trained, qualified crane operators and ground support staffshould handle and install this equipment.When working with this equipment, observe precautions in theliterature, on tags, stickers, and labels attached to theequipment, and any other safety precautions that might apply.Training for operators of the lifting equipment should include, butnot be limited to, the following:Follow all applicable safety codes. Wear safety shoes and workgloves.

    1. Application of the lifter to the load, and adjustment of thelifts to adapt to various sizes or kinds of loads.

    2. Instruction in any special operation or precaution.3. Condition of the load as it relates to operation of the lifting

    kit, such as balance, temperature, etc.

    Inspection

    Prior to initial use, and at monthly intervals, all rigging shackles,clevis pins, and straps should be visually inspected for anydamage, evidence of wear, structural deformation, or cracks.Particular attention should be paid to excessive wear at hoisthooking points and load support areas. Materials showing anykind of wear in these areas must not be used and should bediscarded.

    UNIT FALLING HAZARD

    Failure to follow this warning could result in personal injury ordeath.

    Never stand beneath rigged units or lift over people.

    ! WARNING

    PROPERTY DAMAGE HAZARD

    Failure to follow this warning could result in personalinjury/death or property damage.

    When straps are taut, the clevis should be a minimum of 36in. (914 mm) above the unit top cover.

    ! WARNING

    Rigging/Lifting of Unit (See Fig. 6)

    UNIT FALLING HAZARD

    Failure to follow this warning could result in personal injuryor death.

    Large base units must be secured to common curb beforeallowing full weight of unit to rest on curb. Install screwsthrough curb into unit base rails while rigging crane is stillsupporting unit.

    ! WARNING

    Lifting holes are provided in base rails as shown in Fig. 3 and 4.1. Leave top shipping skid on the unit for use as a spreader

    bar to prevent the rigging straps from damaging the unit. Ifthe skid is not available, use a spreader bar of sufficientlength to protect the unit from damage.

    2. Attach shackles, clevis pins, and straps to the base railsof the unit. Be sure materials are rated to hold the weightof the unit. (See Fig. 6).

    3. Attach a clevis of sufficient strength in the middle of thestraps. Adjust the clevis location to ensure unit is liftedlevel with the ground.

    After the unit is placed on the roof curb or mounting pad, removethe top skid.

  • 850901340303

    SMALL CABINET LARGE CABINET

    Unit *24 30 36

    Unit *42 48 60

    lb kg lb kg lb kg lb kg lb kg lb kgRigging Weight 311 141 316 143 326 148 Rigging Weight 420 191 428 194 450 204

    * For 460 volt units add 14 lb (6.35 kg) to the rigging weight.NOTE: See dimensional drawing for corner weights.

    ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.

    50CY502286 2.0

    CAUTION - NOTICE TO RIGGERSPRUDENCE - AVIS AUX MANIPULATEUR

    Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition

    SEAL STRIP MUST BE INPLACE BEFORE PLACINGUNIT ON ROOF CURB

    DUCTS

    DETAIL AVOIR DÉTAIL A

    MINIMUM HEIGHT: 36" (914.4 mm)HAUTEUR MINIMUM

    UNIT HEIGHTHAUTEUR D'UNITÉ

    SEE DETAIL AVOIR DÉTAIL A

    BANDE SCELLANT DOIT ÊTRE EN PLACE AVANT DE PLACER L'UNITÉ SUR LA BASE DE TOIT

    Fig. 6 -- PGD3/PGS3 Unit Suggested Rigging

  • 9 50901340303

    Table 1 – Physical Data -- Unit PGD3/PGS3UNIT SIZE 24040 24060 30040 30060 36060 36090 42060 42090NOMINAL CAPACITY (ton) 2 2 2---1/2 2---1/2 3 3 3---1/2 3---1/2SHIPPING WEIGHT** lb.SHIPPING WEIGHT** (kg)

    311141

    311141

    316143

    316143

    326148

    326148

    420191

    420191

    COMPRESSORSQuantity

    Scroll1

    REFRIGERANT (R---410A)Quantity lb.Quantity (kg)

    4.82.2

    4.82.2

    6.22.8

    6.22.8

    6.42.9

    6.42.9

    6.12.7

    6.12.7

    REFRIGERANT METERING DEVICE TXVOUTDOOR COILRows...Fins/in.Face Area (sq ft)

    1...2110.2

    1...2110.2

    1...2111.9

    1...2111.9

    1...2115.4

    1...2115.4

    1...2113.6

    1...2113.6

    OUTDOOR FANNominal CFMDiameter in.Diameter (mm)Motor Hp (Rpm)

    280024609.61/5 (810)

    280024609.61/5 (810)

    300024609.61/5 (810)

    300024609.61/5 (810)

    320024609.61/5 (810)

    320024609.61/5 (810)

    360026660.41/5 (810

    360026660.41/5 (810)

    INDOOR COILRows...Fins/in.Face Area (sq ft)

    2...173.7

    2...173.7

    3...173.7

    3...173.7

    3...173.7

    3...173.7

    3...174.7

    3...174.7

    INDOOR BLOWERNominal Cooling Airflow (Cfm)Size in.Size (mm.)Motor HP (RPM)

    800 800 1000 1000 1200 1200 1400 140080010x10254x2541/2 (1050)

    80010x10254x2541/2 (1050)

    100010x10254x2541/2 (1050)

    100010x10254x2541/2 (1050)

    120011x10279.4x2543/4 (1000)

    120011x10279.4x2543/4 (1000)

    140011x10279.4x2543/4 (1075)

    140011x10279.4x2543/4 (1075)

    FURNACE SECTION*Burner Orifice No. (Qty...Drill Size)Natural GasPropane Gas

    2...442...55

    2...382...53

    2...442...55

    2...382...53

    2...382...53

    3...383...53

    2...382...53

    3...383...53

    HIGH--PRESSURE SWITCH(psig) Cut--out Reset (Auto)

    650 +/-- 15420 +/-- 25

    LOSS--OF--CHARGE / LOW--PRESSURESWITCH (Liquid Line) (psig) cut--out Reset(auto)

    20 +/-- 545 +/-- 10

    RETURN---AIR FILTERS†}Throwaway Size in.

    (mm)20x20x1508x508x25

    20x24x1508x610x25

    24x30x1610x762x25

    Table 1—Physical Data Con’t -- Unit PGD3/PGS3UNIT SIZE 48090 48115 48130 60090 60115 60130NOMINAL CAPACITY (ton) 4 4 4 5 5 5SHIPPING WEIGHT** lbSHIPPING WEIGHT** kg

    428194

    428194

    428194

    450204

    450204

    450204

    COMPRESSORSQuantity

    Scroll1

    REFRIGERANT (R---410A)Quantity lbQuantity (kg.)

    6.42.9

    6.42.9

    6.42.9

    10.04.5

    10.04.5

    10.04.5

    REFRIGERANT METERING DEVICE TXVOUTDOOR COILRows...Fins/in.Face Area (sq ft)

    1...2115.5

    1...2115.5

    1...2115.5

    2...2115.5

    2...2115.5

    2...2115.5

    OUTDOOR FANNominal CfmDiameter in.Diameter (mm)Motor Hp (Rpm)

    400026660.41/5 (810)

    400026660.41/5 (810)

    400026660.41/5 (810)

    320026660.41/5 (810)

    320026660.41/5 (810)

    320026660.41/5 (810)

    INDOOR COILRows...Fins/in.Face Area (sq ft)

    3...174.7

    3...174.7

    3...174.7

    3...175.7

    3...175.7

    3...175.7

    INDOOR BLOWERNominal Cooling Airflow (Cfm)Size in.Size (mm)Motor HP (RPM)

    1600 1600 1600 1750 1750 1750160011x10279.4x2541.0 (1075)

    160011x10279.4x2541.0 (1075)

    160011x10279.4x2541.0 (1075)

    175011x10279.4x2541.0 (1040)

    175011x10279.4x2541.0 (1040)

    175011x10279.4x2541.0 (1040)

    FURNACE SECTION*Burner Orifice No. (Qty...Drill Size)Natural GasPropane Gas

    3...383...53

    3...333...51

    3...313...49

    3...383...53

    3...333...51

    3...313...49

    HIGH--PRESSURE SWITCH(psig) Cut--out Reset (Auto)

    650 +/-- 15420 +/-- 25

    LOSS--OF--CHARGE / LOW--PRESSURESWITCH (Liquid Line) (psig) cut--out Reset(auto)

    20 +/-- 545 +/-- 10

    RETURN--AIR FILTERS Throwaway†} in.(mm)

    24x36x1610x914x25

    *Based on altitude of 0 to 2000 ft (0--610 m).{ Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/min-ute for throwaway type. Air filter pressure drop for non--standard filters must not exceed 0.08 IN. W.C.} If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.** For 460 volt units, add 14 lbs (6.35 kg) to the shipping weight.

  • 1050901340303

    Step 6 — Connect Condensate DrainNOTE: When installing condensate drain connection be sure tocomply with local codes and restrictions.Unit disposes of condensate water through a 3/4 in. NPT fittingwhich exits through the base on the evaporator coil access side.See Fig. 3 & 4 for location.Condensate water can be drained directly onto the roof inrooftop installations (where permitted) or onto a gravel apron inground level installations. Install a field--supplied 2--in. (51 mm)condensate trap at the end of condensate connection to ensureproper drainage. Make sure that the outlet of the trap is at least 1in. (25 mm) lower than the drain--pan condensate connection toprevent the pan from overflowing (See Fig. 7). Prime the trapwith water. When using a gravel apron, make sure it slopes awayfrom the unit.Connect a drain tube using a minimum of 3/4--in. PVC or 3/4--in.copper pipe (all field--supplied) at the outlet end of the 2--in. (51mm) trap. Do not undersize the tube. Pitch the drain tubedownward at a slope of at least 1--in. (25 mm) for every 10 ft (3.1m) of horizontal run. Be sure to check the drain tube for leaks.

    Fig. 7 -- Condensate Trap

    TRAPOUTLET

    1-in. (25 mm) min.

    2-in. (51 mm) min.

    Step 7 — Install Flue HoodThe flue assembly is secured and shipped in the return air duct.Remove duct cover to locate the assembly (See Fig. 9).NOTE: Dedicated low NOx models MUST be installed inCalifornia Air Quality Management Districts where a Low NOxrule exists.These models meet the California maximum oxides of nitrogen(NOx) emissions requirements of 40 nanograms/joule or less asshipped from the factory.NOTE: Low NOx requirements apply only to natural gasinstallations.

    CARBON MONOXIDE POISONING HAZARD

    Failure to follow this warning could result in personal injury ordeath.

    The venting system is designed to ensure proper venting. Theflue hood assembly must be installed as indicted in thissection of the unit installation instructions.

    ! WARNING

    Install the flue hood as follows:1. This installation must conform with local building codes

    and with NFPA 54/ANSI Z223.1 National Fuel Gas Code(NFGC), (in Canada, CAN/CGA B149.1, and B149.2)latest revision. Refer to Provincial and local plumbing orwastewater codes and other applicable local codes.

    2. Remove flue hood from shipping location (inside the returnsection of the blower compartment--see Fig. 9). Removethe return duct cover to locate the flue hood. Place fluehood assembly over flue panel. Orient screw holes in fluehood with holes in the flue panel.

    3. Secure flue hood to flue panel by inserting a single screwon the top flange and the bottom flange of the hood.

    Step 8 — Install Gas PipingThe gas supply pipe enters the unit through the access holeprovided. The gas connection to the unit is made to the 1/2--in.(12.7 mm) FPT gas inlet on the gas valve.Install a gas supply line that runs to the heating section. Refer tothe NFGC for gas pipe sizing. Do not use cast--iron pipe. It isrecommended that a black iron pipe is used. Check the localutility for recommendations concerning existing lines. Size gassupply piping for 0.5 in. w.c. maximum pressure drop. Never usepipe smaller than the 1/2--in. (12.7 mm) FPT gas inlet on the unitgas valve.For natural gas applications, the gas pressure at unit gasconnection must not be less than 4.0 in. w.c. or greater than 13in. w.c. while the unit is operating. For propane applications, thegas pressure must not be less than 11.0 in. w.c. or greater than13 in. w.c. at the unit connection.A 1/8--in. (3.2 mm) NPT plugged tapping, accessible for testgauge connection, must be installed immediately upstream ofthe gas supply connection to the gas valve.When installing the gas supply line, observe local codespertaining to gas pipe installations. Refer to the NFPA 54/ANSIZ223.1 latest edition (in Canada, CAN/CGA B149.1).NOTE: In the state of Massachusetts:

    1. Gas supply connections MUST be performed by alicensed plumber or gas fitter.

    2. When flexible connectors are used, the maximum lengthshall not exceed 36 inches (915 mm).

    3. When lever handle type manual equipment shutoff valvesare used, they shall be T--handle valves.

    4. The use of copper tubing for gas piping is NOT approvedby the state of Massachusetts.

    In the absence of local building codes, adhere to the followingpertinent recommendations:

    1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.(6.35 mm) for every 15 ft (4.6 m) of length to prevent traps.Grade all horizontal runs downward to risers. Use risers toconnect to heating section and to meter.

    2. Protect all segments of piping system against physicaland thermal damage. Support all piping with appropriatestraps, hangers, etc. Use a minimum of one hanger every6 ft (1.8 m). For pipe sizes larger than 1/2 in., followrecommendations of national codes.

    3. Apply joint compound (pipe dope) sparingly and only tomale threads of joint when making pipe connections. Useonly pipe dope that is resistant to action of liquefiedpetroleum gases as specified by local and/or nationalcodes. Never use Teflon tape.

    4. Install sediment trap in riser leading to heating section(See Fig. 8). This drip leg functions as a trap for dirt andcondensate.

    5. Install an accessible, external, manual main shutoff valvein gas supply pipe within 6 ft (1.8 m) of heating section.

    6. Install ground--joint union close to heating sectionbetween unit manual shutoff and external manual mainshut--off valve.

    7. Pressure test all gas piping in accordance with local andnational plumbing and gas codes before connecting pipingto unit.

  • 11 50901340303

    Table 2 – Maximum Gas Flow Capacity*NOMINALIRON PIPESIZE (IN.)

    INTERNALDIAMETER

    (IN.)

    LENGTH OF PIPE FT (m)†10(3)

    20(6)

    30(9)

    40(12)

    50(15)

    60(18)

    70(21)

    80(24)

    90(27)

    100(30)

    125(38)

    150(46)

    175(53)

    200(61)

    1/2 .622 175 120 97 82 73 66 61 57 53 50 44 40 — —3/4 .824 360 250 200 170 151 138 125 118 110 103 93 84 77 721 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135

    1- 1/4 1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 2801- 1/2 1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430

    *Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5--in. w..c. (based on a 0.60 specific gravity gas). Refer to Table, National FireProtection Association NFPA 54.{ This length includes an ordinary number of fittings.

    OUTTEE

    NIPPLE

    CAP

    IN

    Fig. 8 -- Sediment Trap

    NOTE: Pressure test the gas supply system after the gas supplypiping is connected to the gas valve. The supply piping must bedisconnected from the gas valve during the testing of the pipingsystems when test pressure is in excess of 0.5 psig. Pressuretest the gas supply piping system at pressures equal to or lessthan 0.5 psig. The unit heating section must be isolated from thegas piping system by closing the external main manual shutoffvalve and slightly opening the ground--joint union.

    FIRE OR EXPLOSION HAZARD

    Failure to follow this warning could result in personalinjury, death and/or property damage.

    --Connect gas pipe to unit using a backup wrench toavoid damaging gas controls.

    --Never purge a gas line into a combustion chamber.Never test for gas leaks with an open flame. Use acommercially available soap solution made specificallyfor the detection of leaks to check all connections.A fireor explosion may result causing property damage,personal injury or loss of life.

    --Use proper length of pipe to avoid stress on gascontrol manifold.

    --If a flexible connector is required or allowed byauthority having jurisdiction, black iron pipe shall beinstalled at furnace gas valve and extend a minimum of2 in. (51 mm) outside furnace casing.

    --If codes allow a flexible connector, always use a newconnector. do not use a connector which haspreviously serviced another gas appliance.

    ! WARNING

    8. Check for gas leaks at the field--installed andfactory--installed gas lines after all piping connectionshave been completed. Use a commercially available soap

    solution (or method specified by local codes and/orregulations).

    Step 9 — Install Duct ConnectionsThe unit has duct flanges on the supply-- and return--airopenings on the side and bottom of the unit. For downshotapplications, the ductwork connects to the roof curb (See Fig. 3and 4 for connection sizes and locations).

    Configuring Units for Downflow (Vertical) Discharge

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personalinjury or death.

    Before installing or servicing system, always turn offmain power to system and install lockout tag. Theremay be more than one disconnect switch.

    ! WARNING

    1. Open all electrical disconnects before starting any servicework.

    2. Remove horizontal (metal) duct covers to access vertical(downflow) discharge duct knockouts in unit basepan.

    3. To remove downflow return and supply knockout covers,break front and right side connecting tabs with ascrewdriver and hammer. Push cover down to break rearand left side tabs.

    NOTE: These panels are held in place with tabs similar to anelectrical knockout. Reinstall horizontal duct covers (Fig. 9)shipped on unit from factory. Insure openings are air andwatertight.

    NOTE: The design and installation of the duct system must be inaccordance with the standards of the NFPA for installation ofnonresidence--type air conditioning and ventilating systems,NFPA 90A or residence--type, NFPA 90B; and/or local codesand ordinances.

    Adhere to the following criteria when selecting, sizing, andinstalling the duct system:

    1. Units are shipped for horizontal duct installation (byremoving duct covers).

    2. Select and size ductwork, supply--air registers, andreturn--air grilles according to American Society ofHeating, Refrigeration and Air Conditioning Engineers(ASHRAE) recommendations.

    3. Use flexible transition between rigid ductwork and unit toprevent transmission of vibration. The transition may bescrewed or bolted to duct flanges. Use suitable gaskets toensure weather--tight and airtight seal.

    4. All units must have field--supplied filters or accessory filterrack installed in the return--air side of the unit.Recommended sizes for filters are shown in Table 1.

    5. Size all ductwork for maximum required airflow (eitherheating or cooling) for unit being installed. Avoid abrupt

  • 1250901340303

    duct size increases or decreases or performance may beaffected.

    6. Adequately insulate and weatherproof all ductwork locatedoutdoors. Insulate ducts passing through unconditionedspace, and use vapor barrier in accordance with latestissue of Sheet Metal and Air Conditioning ContractorsNational Association (SMACNA) and Air ConditioningContractors of America (ACCA) minimum installationstandards for heating and air conditioning systems.Secure all ducts to building structure.

    7. Flash, weatherproof, and vibration isolate all openings inbuilding structure in accordance with local codes andgood building practices.

    Fig. 9 -- Supply and Return Duct Opening

    Horizontal Duct Covers

    BasepanDownflow(Vertical)SupplyKnockout

    BasepanDownflow (Vertical)ReturnKnockout

    Step 10 — Install Electrical Connections

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal injury ordeath.

    The unit cabinet must have an uninterrupted, unbrokenelectrical ground. This ground may consist of an electricalwire connected to the unit ground screw in the controlcompartment, or conduit approved for electrical ground wheninstalled in accordance with NFPA 70 (NEC) (latest edition)(in Canada, Canadian Electrical Code CSA C22.1) and localelectrical codes.

    ! WARNING

    High--Voltage Connections

    When routing power leads into unit, use only copper wirebetween disconnect and unit. The high voltage leads should bein a conduit until they enter the duct panel; conduit termination atthe duct panel must be watertight.

    UNIT COMPONENT DAMAGE HAZARD

    Failure to follow this caution may result in damage to the unitbeing installed.

    1. Make all electrical connections in accordance withhNFPA 70 (NEC) (latest edition) and local electricalcodes governing such wiring. In Canada, all electricalconnections must be in accordance with CSAstandard C22.1 Canadian Electrical Code Part 1 andapplicable local codes. Refer to unit wiring diagram.

    2. Use only copper conductor for connections betweenfield--supplied electrical disconnect switch and unit.DO NOT USE ALUMINUM WIRE.

    3. Be sure that high--voltage power to unit is withinoperating voltage range indicated on unit rating plate.On 3--phase units, ensure phases are balanced within2 percent. Consult local power company for correctionof improper voltage and/or phase imbalance.

    4. Insulate low--voltage wires for highest voltagecontained within conduit when low--voltage controlwires are in same conduit as high--voltage wires.

    5. Do not damage internal components when drillingthrough any panel to mount electrical hardware,conduit, etc.

    ! CAUTION

    The unit must have a separate electrical service with afield--supplied, waterproof disconnect switch mounted at, orwithin sight from, the unit. Refer to the unit rating plate, NEC andlocal codes for maximum fuse/circuit breaker size and minimumcircuit amps (ampacity) for wire sizing.The field--supplied disconnect switch box may be mounted onthe unit over the high--voltage inlet hole when the standardpower and low--voltage entry points are used (See Fig. 3 and 4for acceptable location).NOTE: Field supplied disconnect switch box should bepositioned so that it does not cover up any of the unit gascombustion supply air louvers.See unit wiring label (Fig. 14, 15, 16, 17, 18 and 19) and Fig. 10for reference when making high voltage connections. Proceedas follows to complete the high--voltage connections to the unit.Single phase units:

    1. Run the high--voltage (L1, L2) and ground lead into thecontrol box.

    2. Connect ground lead to chassis ground connection.3. Locate the black and yellow wires connected to the line

    side of the contactor (if equipped).4. Connect field L1 to black wire on connection 11 of the

    compressor contactor.5. Connect field wire L2 to yellow wire on connection 23 of

    the compressor contactor.Three--phase units:

    1. Run the high--voltage (L1, L2, L3) and ground lead into thecontrol box.

    2. Connect ground lead to chassis ground connection.3. Locate the black and yellow wires connected to the line

    side of the contactor (if equipped).4. Connect field L1 to black wire on connection 11 of the

    compressor contactor.5. Connect field wire L3 to yellow wire on connection 13 of

    the compressor contactor.6. Connect field wire L2 to blue wire from compressor.

  • 13 50901340303

    Special Procedures for 208--v Operation

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal injury ordeath.

    Make sure the power supply to the unit is switched OFF andinstall lockout tag. before making any wiring changes. Withdisconnect switch open, move black wire from transformer(3/16 in. [4.8 mm]) terminal marked 230 to terminal marked208. This retaps transformer to primary voltage of 208 vac.

    ! WARNING

    ELECTRICAL SHOCK FIRE/EXPLOSION HAZARD

    Failure to follow this warning could result in personal injury ordeath and property damage.

    Before making any wiring changes, make sure the gassupply is switched off first. Then switch off the power supplyto the unit and install lockout tag.

    ! WARNING

    Control Voltage Connections

    Do not use any type of power--stealing thermostat. Unit controlproblems may result.Use no. 18 American Wire Gage (AWG) color--coded, insulated(35_C minimum) wires to make the control voltage connectionsbetween the thermostat and the unit. If the thermostat is locatedmore than 100 ft (30.5 m) from the unit (as measured along thecontrol voltage wires), use no. 16 AWG color--coded, insulated(35_C minimum) wires.

    Standard Connection

    Run the low--voltage leads from the thermostat, through the inlethole, and into unit low--voltage splice box.Locate six (seven for 3--phase) 18--gage wires leaving controlbox. These low--voltage connection leads can be identified bythe colors red, green, yellow, brown, blue, and white (See Fig.10). A gray wire is standard on 3--phase units for connection toan economizer. Ensure the leads are long enough to be routedinto the low--voltage splice box (located below right side ofcontrol box). Route leads through hole in bottom of control boxand make low--voltage connections (See Fig. 10). Secure all cutwires, so that they do not interfere with operation of unit.

    POWERSUPPLY

    FIELD-SUPPLIEDFUSED DISCONNECT

    HIGH VOLTAGEPOWER LEADS(SEE UNIT WIRINGLABEL)

    EQUIP GR

    3-PHASE SHOWN1-PHASE USES TWO POWER LEADS

    CONTROL BOX

    SPLICE BOX

    LOW-VOLTAGEPOWER LEADS(SEE UNITWIRING LABEL)

    W

    Y

    G

    R

    C

    WHT(W1)

    YEL(Y)

    GRN(G)

    RED(R)

    BRN(C)

    THERMOSTAT(TYPICAL)

    DHBLU(DH)

    GRA(Y2) 3-PhaseOnly

    Fig. 10 -- High-- and Control--Voltage Connections

    Heat Anticipator Setting (Electro--Mechanical Thermostats

    only)

    The room thermostat heat anticipator must be properly adjustedto ensure proper heating performance. Set the heat anticipator,using an ammeter between the W and R terminals to determinethe exact required setting.NOTE: For thermostat selection purposes, use 0.18 amp for theapproximate required setting. Failure to make a proper heatanticipator adjustment will result in improper operation,discomfort to the occupants of the conditioned space, andinefficient energy utilization; however, the required setting maybe changed slightly to provide a greater degree of comfort for aparticular installation.

    Transformer Protection

    The transformer is of the energy--limiting type, however a directshort will likely blow a secondary fuse. If an overload or short ispresent, correct overload condition and check for blown fuse onIndoor Fan board or Integrated Gas Controller. Replace fuse asrequired with correct size and rating.

    PRE--START--UP

    ENVIRONMENTAL, FIRE, EXPLOSION, ELECTRICALSHOCK HAZARD

    Failure to follow this warning could result in personal injury ordeath.

    1. Follow recognized safety practices and wear protectivegoggles when checking or servicing refrigerant system.

    2. Do not operate compressor or provide any electricpower to unit unless compressor plug is in place andsecured.

    3. Do not remove ccompressor plug until all electricalsources are disconnected and tagged.

    4. Relieve and recover all refrigerant from system beforetouching or disturbing compressor plug if refrigerantleak is suspected around compressor terminals.

    5. Never attempt to repair soldered connection whilerefrigerant system is under pressure.

    6. Do not use torch to remove any component. Systemcontains oil and refrigerant under pressure.To remove a component, wear protective goggles andproceed as follows:a. Shut off electrical power to unit and install lockout

    tag.b. Relieve and reclaim all refrigerant from system

    using both high-- and low--pressure ports.c. Cut component connecting tubing with tubing cutter

    and remove component from unit.d. Carefully unsweat remaining tubing stubs when

    necessary. Oil can ignite when exposed to torchflame.

    ! WARNING

    Use the Start--Up Checklist supplied at the end of this book andproceed as follows to inspect and prepare the unit for initialstart--up:

    1. Remove access panels.2. Read and follow instructions on all DANGER, WARNING,

    CAUTION, and INFORMATION labels attached to, orshipped with unit.

    3. Make the following inspections:a. Inspect for shipping and handling damage, such as

    broken lines, loose parts, disconnected wires, etc.b. Inspect for oil at all refrigerant tubing connections and

    on unit base. Detecting oil generally indicates a

  • 1450901340303

    refrigerant leak.c. Leak--test all refrigerant tubing connections using

    electronic leak detector, or liquid--soap solution. If arefrigerant leak is detected, see following Check forRefrigerant Leaks section.

    d. Inspect all field-- and factory--wiring connections. Besure that connections are completed and tight.

    e. Ensure wires do not touch refrigerant tubing or sharpsheet metal edges.

    f. Inspect coil fins. If damaged during shipping andhandling, carefully straighten fins with a fin comb.

    FIRE, EXPLOSION HAZARD

    Failure to follow this warning could result in personal injury,death or property damage.

    Do not purge gas supply into the combustion chamber. Donot use a match or other open flame to check for gas leaks.Use a commercially available soap solution made specificallyfor the detection of leaks to check all connections. A fire orexplosion may result causing property damage, personalinjury or loss of life.

    ! WARNING

    4. Verify the following conditions:a. Make sure gas line is free of air. Before lighting the unit

    for the first time, perform the following with the gasvalve in the OFF position:

    NOTE: If the gas supply pipe was not purged before connectingthe unit, it will be full of air. It is recommended that the groundjoint union be loosened, and the supply line be allowed to purgeuntil the odor of gas is detected. Never purge gas lines into acombustion chamber. Immediately upon detection of gas odor,retighten the union. Allow 5 minutes to elapse, then light unit.

    b. Ensure fan hub is positioned correctly with respect tomotor housing.

    c. Make sure that air filter(s) is in place.d. Make sure that condensate drain trap is filled with

    water to ensure proper drainage.e. Make sure that all tools and miscellaneous loose parts

    have been removed.

    START--UPStep 1 — Check for Refrigerant LeaksProceed as follows to locate and repair a refrigerant leak and tocharge the unit:

    1. Locate leak and make sure that refrigerant systempressure has been relieved and reclaimed from both high--and low--pressure ports.

    2. Repair leak following accepted practices.NOTE: Install a filter drier whenever the system has beenopened for repair.

    3. Add a small charge of R--410A refrigerant vapor to systemand leak--test unit.

    4. Recover refrigerant from refrigerant system and evacuateto 500 microns if no additional leaks are found.

    5. Charge unit with R--410A refrigerant, using an accuratescale. Refer to unit rating plate for required charge.

    Step 2 — Start--up Heating and Make AdjustmentsComplete the required procedures given in the Pre--Start--Upsection before starting the unit. Do not jumper any safety deviceswhen operating the unit. Make sure that burner orifices areproperly aligned. Unstable operation my occur when the burnerorifices in the manifold are misaligned.

    Follow the lighting instructions on the heating section operationlabel (located on the inside of the control access panel) to startthe heating section.NOTE: Make sure that gas supply has been purged, and that allgas piping has been checked for leaks.

    Pipe PlugManifold

    Fig. 11 -- Burner Assembly

    MANIFOLD

    BURNER

    BURNER FLAME

    Fig. 12 -- Monoport Burner

    Check Heating Control

    Start and check the unit for proper heating control operation asfollows (see furnace lighting instructions located on the inside ofthe control access panel):

    1. Place room thermostat SYSTEM switch in the HEATposition and the fan switch is placed in AUTO position.

    2. Set the heating temperature control of the thermostatabove room temperature.

    3. The induced--draft motor will start.4. On a call for heating, the main burner should light within 5

    sec. of the spark being energized. If the burners do notlight, there is a 22--sec. delay before another 5--sec. try. Ifthe burners still do not light, this sequence is repeated. Ifthe burners do not light within 15 minutes from the initialcall for heat, there is a lockout. To reset the control, breakthe 24--v power to W.

    5. The evaporator fan will turn on 45 sec. after the flame hasbeen established. The evaporator fan will turn off 45 sec.after the thermostat has been satisfied. Please note thatthe integrated gas unit controller (IGC) has the capabilityto automatically reduce the evaporator “ON” delay and in-crease the evaporator “OFF” delay in the event of highduct static and/or partially--clogged filter.

  • 15 50901340303

    Check Gas Input

    Check gas input and manifold pressure after unit start--up (SeeTable 5). If adjustment is required proceed as follows:S The rated gas inputs shown in Table 5 are for altitudes from sea

    level to 2000 ft (610 m) above sea level. These inputs are basedon natural gas with a heating value of 1025 Btu/ft3 at 0.60specific gravity, or propane gas with a heating value of 2500Btu/ft3 at 1.5 specific gravity.

    IN THE U.S.A.:The input rating for altitudes above 2,000 ft (610 m) must bereduced by 4% for each 1,000 ft (305 m) above see level.For installations below 2,000 ft (610 m), refer to the unit ratingplate.For installations above 2,000 ft (610 m). multiply the input on therating plate by the derate multiplier in Table 3 for correct inputrate.If the natural gas is not derated by the gas utility company, referto Table 4 for correct orifice sizes and manifold pressures.

    Table 3 – Altitude Derate Multiplier for U.S.A.*

    ALTITUDE FT (M)PERCENT OFDERATE

    DERATE MULTIPLIERFACTOR{

    0--2000(0--610) 0 1.00

    2001--3000*(610--914) 8--12 0.90

    3001--4000(915--1219) 12--16 0.86

    4001--5000(1220--1524) 16--20 0.82

    5001--6000(1524 --1829) 20--24 0.78

    6001--7000(1829--2134) 24--28 0.74

    7001--8000(2134--2438) 28--32 0.70

    8001--9000(2439--2743) 32--36 0.66

    9001--10,000(2744--3048) 36--40 0.62

    *In Canada see Canadian Altitude Adjustment.{Derate multiplier factors are based on midpoint altitude for altituderange.

    IN CANADA:The input rating for altitudes from 2,000 (610 m) to 4,500 ft (1372m) above sea level must be derated 10% by an authorized GasConversion Station or Dealer.EXAMPLE:90,000 Btu/hr Input Furnace Installed at 4300 ft.

    Furnace Input Rate at SeaLevel

    X Derate MultiplierFactor

    = Furnace Input Rate at In-stallation Altitude

    90,000 X 0.90 = 81,000

    When the gas supply being used has a different heating value orspecific gravity, refer to national and local codes, or contact yourdistributor to determine the required orifice size.

    UNIT DAMAGE HAZARD

    Failure to follow this caution may result in reduced unit and/orcomponent life.

    Do Not redrill an orifice. Improper drilling (burrs,out--of--round holes, etc.) can cause excessive burner noiseand misdirection of burner flame. If orifice hole appearsdamaged or it is suspected to have been redrilled, checkorifice hole with a numbered drill bit of correct size.

    ! CAUTION

    Adjust Gas Input

    The gas input to the unit is determined by measuring the gasflow at the meter or by measuring the manifold pressure.Measuring the gas flow at the meter is recommended for naturalgas units. The manifold pressure must be measured todetermine the input of propane gas units.Measure Gas Flow (Natural Gas Units)Minor adjustment to the gas flow can be made by changing themanifold pressure. The manifold pressure must be maintainedbetween 3.2 and 3.8 IN. W.C.

    Table 4 – Natural Gas Orifice Sizes and Manifold Pressures

    Nameplate Input(Btu/hr)

    ALTITUDE OF INSTALLATION (FT. ABOVE SEA LEVEL) U.S.A.*0 to 2000(0--610 m)

    2001 to 3000*(611 to 914 m)

    3001 to 4000(915 to 1219 m)

    4001 to 5000(1220 to 1524 m)

    5001 to 6000(1524 to 1829 m)

    40000Orifice No. (Qty) 44 (2) 45 (2)† 48 (2)† 48 (2)† 48 (2)†Manifold Press. 3.2 3.2 3.8 3.5 3.2

    60000Orifice No. (Qty) 38 (2) 41 (2)† 41 (2)† 42 (2)† 42 (2)†Manifold Press. 3.6 3.8 3.4 3.4 3.2

    90000Orifice No. (Qty) 38 (3) 41 (3)† 41 (3)† 42 (3)† 42 (3)†Manifold Press. 3.6 3.8 3.4 3.4 3.2

    115000Orifice No. (Qty) 33 (3) 36 (3)† 36 (3)† 36 (3)† 38 (3)†Manifold Press. 3.8 3.8 3.6 3.3 3.6

    130000Orifice No. (Qty) 31 (3) 31 (3) 33 (3)† 33 (3)† 34 (3)†Manifold Press. 3.8 3.2 3.7 3.4 3.3

    *In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above Sea level.In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or dealer.For Canadian Installations from 2000 to 4500 ft, use U.S.A. column 2001 to 3000 ft.Note: Orifice sizes and manifold pressure settings are based on natural gas with a heating value of 1025 Btu/ft3 amd a specific gravity of .6.† Orifices available through your distributor.

  • 1650901340303

    REGULATOR COVER SCREW

    ADJUSTMENTSCREW

    REGULATOR SPRING(PROPANE - WHITE)NATURAL - SILVER)

    GAS PRESSURE REGULATOR ADJUSTMENT

    MANIFOLD PRESSURE TAP

    INLET PRESSURE TAP

    ON/OFF SWITCH

    PLASTIC

    (

    Fig. 13 -- Single--Stage Gas Valve

    If larger adjustments are required, change main burner orificesfollowing the recommendations of national and local codes.NOTE: All other appliances that use the same meter must beturned off when gas flow is measured at the meter.Proceed as follows:

    1. Turn off gas supply to unit.2. Remove pipe plug on manifold (See Fig. 11) and connect

    manometer. Turn on gas supply to unit.3. Record number of seconds for gas meter test dial to make

    one revolution.4. Divide number of seconds in Step 3 into 3600 (number of

    seconds in one hr).5. Multiply result of Step 4 by the number of cubic feet (cu ft)

    shown for one revolution of test dial to obtain cubic feet(cu ft) of gas flow per hour.

    6. Multiply result of Step 5 by Btu heating value of gas toobtain total measured input in Btuh. Compare this valuewith heating input shown in Table 5 (Consult the local gassupplier if the heating value of gas is not known).

    EXAMPLE: Assume that the size of test dial is 1 cu ft, onerevolution takes 32 sec, and the heating value of the gas is 1050Btu/ft3. Proceed as follows:

    1. 32 sec. to complete one revolution.

    2. 3600 32 = 112.5.3. 112.5 x 1 =112.5 ft3 of gas flow/hr.4. 112.5 x 1050 = 118,125 Btuh input.

    If the desired gas input is 115,000 Btuh, only a minor change inthe manifold pressure is required.Observe manifold pressure and proceed as follows to adjust gasinput:

    1. Remove regulator cover screw over plastic adjustmentscrew on gas valve (See Fig. 13).

    2. Turn plastic adjustment screw clockwise to increase gasinput, or turn plastic adjustment screw counterclockwise todecrease input (See Fig. 13). Manifold pressure must bebetween 3.2 and 3.8 in. w.c.

    FIRE AND UNIT DAMAGE HAZARD

    Failure to follow this warning could result in personal injury ordeath and/or property damage.

    Unsafe operation of the unit may result if manifold pressure isoutside this range.

    ! WARNING

    3. Replace regulator cover screw on gas valve (See Fig. 13).4. Turn off gas supply to unit. Remove manometer from

    pressure tap and replace pipe plug on gas valve. (SeeFig. 12.) Turn on gas to unit and check for leaks.

    Measure Manifold Pressure (Propane Units)Refer to propane kit installation instructions for properly checkinggas input.NOTE: For installations below 2,000 ft (610 m), refer to the unitrating plate for proper propane conversion kit. For installationsabove 2,000 ft (610 m), contact your distributor for properpropane conversion kit.

    Check Burner Flame

    With control access panel removed, observe the unit heatingoperation. Watch the burner flames to see if they are light blueand soft in appearance, and that the flames are approximatelythe same for each burner. Propane will have blue flame. Refer tothe Maintenance section for information on burner removal.

    Table 5 – Heating Inputs

    HEATING INPUT(BTUH)

    GAS SUPPLY PRESSURE (IN. W.C.) MANIFOLD PRESSURENUMBER OF ORI- Natural{ Propane*{

    MANIFOLD PRESSURE(IN. W.C.)NUMBER OF ORI

    FICES Min Max Min Max Natural{ Propane*†40,000 2 4.0 13.0 11.0 13.0 3.23.8 10.060,000 2 4.0 13.0 11.0 13.0 3.23.8 10.090,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0115,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0130,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0

    *When a unit is converted to propane, different size orifices must be used. See separate, natural--to--propane conversion kit instructions.{Based on altitudes from sea level to 2000 ft (610 m) above sea level. For altitudes above 2000 ft (610 m), reduce input rating 4 percent for each additional1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.

  • 17 50901340303

    Fig. 14 -- 208/230--1--60 Connection Wiring Diagram

    FIELD

    SUPPLY

    BK

    C F

    SCHEMATIC208/230-1-60

    1

    1

    SEE NOTE 5

    0G

    ENERGIZED

    T

    G

    DE-ENERGIZED

    0

    W

    45

    BR

    T

    W

    T+45

    BR

    ENERGIZED DE-ENERGIZED

    T+90

    HEATING FAN LOGICCOOLING FAN LOGIC

    LEGEND

    FIELD SPLICE

    TERMINAL (MARKED)

    TERMINAL (UNMARKED)

    SPLICE (IF USED)

    SPLICE (MARKED)

    FACTORY WIRING

    FIELD CONTROL WIRING

    FIELD POWER WIRING

    ACCESSORY OR OPTIONAL

    WIRING

    TO INDICATE COMMON

    POTENTIAL ONLY:

    NOT TO REPRESENT WIRING

    BLR BLOWER RELAY

    C CONTACTOR

    COMP COMPRESSOR MOTOR

    CR COMBUSTION RELAY

    EQUIP EQUIPMENT

    FS FLAME SENSOR

    FU FUSE

    GND GROUND

    GVR GAS VALVE RELAY

    HV TRAN HIGH VOLTAGE TRANSFORMER

    I IGNITOR

    IGC INTERGRATED GAS UNIT

    CONTROLLER

    IDM INDUCED DRAFT MOTOR

    IFM INDOOR FAN MOTOR

    LS1 PRIMARY LIMIT SWITCH

    MGV MAIN GAS VALVE

    OFM OUTDOOR FAN MOTOR

    QT QUADRUPLE TERMINAL

    RS ROLLOUT SWITCH

    TRAN TRANSFORMER

    EQUIP_GND

    CC1 C2

    IDM

    V

    Y

    BR

    G/Y

    CAP 2

    QT

    COMPC

    R

    S

    L2

    L2

    L2

    L1

    C

    J2

    W

    IFO

    G

    R

    RS

    RS

    LS

    LS

    CS

    CS

    GV

    GV

    C

    IGC

    GROUNDED

    THRU STANDOFF

    CM

    BM

    FS

    RT

    Y

    BR

    FS

    LS1

    13

    RS

    13

    LS2

    13R

    PRIMARY

    208/230V

    TRAN

    SECONDARY

    24 V 24VC

    230COM

    MGV

    M C

    OFM

    CAP1

    Y

    BR

    C

    11 21

    23 23

    BK

    Y

    BL

    COMPRESSOR PLUG

    Y

    Y

    BK

    V

    BK

    Y

    BL

    BL

    V

    V

    Y

    GY

    BR

    G/Y

    BR

    BL BR

    BR

    BK

    BK

    CCH

    G

    IF USED

    NOTES:

    1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE

    REPLACED, THEY MUST BE REPLACED WITH TYPE

    90 DEG. C WIRE OR ITS EQUIVALENT.

    2. SEE PRICE PAGES FOR THERMOSTAT AND SUBBASES.

    3. USE 75 DEG. COPPER CONDUCTORS FOR FIELD

    INSTALLATION.

    4. SEE INSTALLATION INSTRUCTIONS

    FOR PROPER HEATING AND COOLING CONNECTIONS

    FOR YOUR UNIT. INDOOR FAN MOTOR PLUGS- IDO NOT DISCONNECT UNDER LOADI

    5. ON SMALL BASE MODELS LS1 AND LS2 ARE WIRED

    IN SERIES. LARGE BASE MODELS HAVE LS1 ONLY.

    6. INDUCER CAPACITOR AND WIRING ON CERTAIN MODELS ONLY.

    IF CAP2 IS PRESENT, YELLOW WIRES FROM IGC AND IDM CONNECT

    ON SAME SIDE OF CAP2.

    7. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257003.

    8. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257005.

    H

    L2

    L1

    SEE

    NOTE 4

    BL

    P

    R

    O

    BK

    BKBK

    Y

    BR

    BKBK

    Y

    O

    DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING

    Y

    R

    G

    BL

    Y

    R

    G

    DH

    COLOR CODE

    BK BLACK

    BL BLUE

    BR BROWN

    GY GRAY

    G GREEN

    O ORANGE

    P PINK

    R RED

    V VIOLET

    W WHITE

    Y YELLOW

    I

    BR C

    Y

    CAP 1 CAPACITOR, COMP

    CAP 2 CAPACITOR, INDUCERPRS PRESSURE SWITCH

    3C

    X5

    W

    4Y

    R 24V

    P2

    12

    HIGH

    LOW

    G46

    W Y1/Y

    RC

    3 2 1

    P1

    COM C

    C

    FUSE

    COM

    R

    3A

    24VAC

    IFB

    R

    W

    RBR

    IFM

    GND

    N

    L

    COM

    1 24 35

    BR

    Y

    BK

    GY

    LPSHPSBLBK

    PRS

    SEE

    NOTE 6

    GND

    1

    1

    1

    1

    1

    SEE NOTE 4

    O O

    IFB INDOOR FAN BOARD

    LGPS LOW GAS PRESSURE SWITCH (WHEN USED)

    LGPS (WHEN USED)

    LS2 SECONDARY LIMIT SWITCH

    T’STAT THERMOSTAT

    BK

    BK

    BK

    BR

    R

    5A FUSE

    SEE

    NOTE 7

    SEE NOTE 8

    GASHEAT

    W W

    T’STAT1

    5Y2/DH

    G/Y

    TO IFM

  • 1850901340303

    Fig. 15 -- 208/230--1--60 Ladder Wiring Diagram

    SEE NOTE 4

    Y

    BK

    CCH

    (IF USED)

    COMP

    RC

    S

    C R

    S

    OFM

    CAP

    F

    C

    BK

    BR

    BK Y

    BR

    BL

    H

    DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING

    48VL500172

    IFM

    Y

    VRV

    Y

    C21

    L1

    208/230 VAC, 60 HZ, 1PH

    CONT

    11

    2323

    FIELD SUPPLY

    BK

    Y

    Y

    Y

    BK BK

    L2

    BKG/YUSE COPPER CONDUCTORS ONLY

    G

    11

    G/Y

    TRAN

    PRIMARY 208/230V230

    24V

    COM

    C

    BRIDM

    CAP2

    CR CM

    Y

    G/Y

    SECONDARY 24V

    5A FUSERT

    FS

    RS

    RS

    LS

    LS

    GV

    1

    2

    3

    R

    G

    W

    BL BL

    RS

    LS1 LS2

    MC

    MGV

    GY

    BR

    G/Y

    L2

    IGC

    IGC

    C

    GV

    C

    CONT

    C1 C2

    BR

    1

    1

    1

    1

    R

    G

    W

    Y

    C

    T’STAT

    BK Y

    V

    BK

    Y

    BR

    CS

    CS

    IFO

    24VAC R

    FUSE

    3A

    P2-1IRIP1-1IRI

    P1-4IGI

    P2-5IXI

    P1-6IWI

    P2-3IWI

    P2-4IRI

    P1-3IY1/YI

    LOW

    HIGH

    HPS

    BK

    LPS

    BK BL

    Y 12

    435 IFM

    PRS

    BL

    O

    BR

    COM C

    P2-2ICI

    C

    COM

    P1-2ICI

    L1

    SEE NOTE 6IFB

    IFB

    E

    11

    11

    23

    23Y

    IGC

    IGC

    Y

    BR

    GY

    W

    R

    BK

    R

    R

    O O

    BL

    BR

    PR

    BK

    LGPS (WHEN USED)

    FS

    (SEE NOTE 5)

    IFB

    OFM

    CONTROL BOX AREA

    COMP

    C

    S

    R

    CAP 1

    H CF

    IFM

    1 UNIT COMPONENT ARRANGEMENT

    OUTDOOR FAN

    SECTION

    COMPRESSOR

    SECTION

    INDOOR FAN

    SECTION

    TRAN

    C

    21 23

    2311

    LS1

    LS1

    IGC

    CAP 2

    IDM

    PRS

    I

    MGV

    MC

    FS

    RS

    GAS

    SECTION

    (SMALL

    CABINET)

    (LARGE)

    LS2 (SMALL)

    LPS

    HPS

    SEE NOTE 7

    SEE NOTE 8

    GAS HEAT

    Y

    R

    G

    W

    1

    DH

    P1-5IY2/DHI

    BL

  • 19 50901340303

    Fig. 16 -- 208/230--3--60 Connection Wiring Diagram

    FIELD

    SUPPLY

    C F

    SCHEMATIC

    208/230-3-60

    1

    1

    SEE NOTE 5

    0

    G

    ENERGIZED

    T

    G

    DE-ENERGIZED

    0

    W

    45

    BR

    T

    W

    T+45

    BR

    ENERGIZED DE-ENERGIZED

    T+60

    HEATING FAN LOGIC

    COOLING FAN LOGIC

    LEGENDFIELD SPLICE

    TERMINAL (MARKED)

    TERMINAL (UNMARKED)

    SPLICE (IF USED)

    SPLICE (MARKED)

    FACTORY WIRING

    FIELD CONTROL WIRING

    FIELD POWER WIRING

    ACCESSORY OR OPTIONAL

    WIRING

    TO INDICATE COMMON

    POTENTIAL ONLY:

    NOT TO REPRESENT WIRING

    BLR BLOWER RELAY

    C CONTACTOR

    COMP COMPRESSOR MOTOR

    CR COMBUSTION RELAY

    EQUIP EQUIPMENT

    FS FLAME SENSOR

    FU FUSE

    GND GROUND

    GVR GAS VALVE RELAY

    HV TRAN HIGH VOLTAGE TRANSFORMER

    I IGNITOR

    IGC INTERGRATED GAS UNIT

    CONTROLLER

    IDM INDUCED DRAFT MOTOR

    IFM INDOOR FAN MOTOR

    LS1 PRIMARY LIMIT SWITCH

    MGV MAIN GAS VALVE

    OFM OUTDOOR FAN MOTOR

    QT QUADRUPLE TERMINAL

    RS ROLLOUT SWITCH

    TRAN TRANSFORMER

    EQUIP_GND

    IDM

    V

    Y

    BR

    G/Y

    CAP 2

    QT

    COMP

    T1

    T2

    T3

    GROUNDED

    THRU STANDOFF

    Y

    BR

    FS

    LS1

    13

    RS

    13

    LS2

    13R

    PRIMARY

    208/230V

    TRAN

    SECONDARY

    24V C24V

    230COM

    MGV

    M C

    OFM

    CAP1

    Y

    BR

    C

    11 21

    13 23

    BK

    Y

    COMPRESSOR PLUG

    Y

    Y

    BK

    V

    BK

    Y

    BL

    BL

    GY

    BR

    G/Y

    BK

    BK

    CCH

    G

    IF USED

    L3

    L1

    SEE

    NOTE 4

    BL

    P

    R

    O

    BK

    R

    BR

    R

    BK

    BK

    Y

    BK

    BR

    BKBK

    Y

    O

    Y

    R

    G

    W

    Y1

    R

    G

    W

    T’STAT

    COLOR CODE

    BK BLACK

    BL BLUE

    BR BROWN

    GY GRAY

    G GREEN

    O ORANGE

    P PINK

    R RED

    V VIOLET

    W WHITE

    Y YELLOW

    I

    BR C

    Y

    CAP 1 CAPACITOR, COMP

    CAP 2 CAPACITOR, INDUCER

    PRS PRESSURE SWITCH

    3

    CX5

    W

    4Y

    R 24V

    P2

    12

    HIGH

    LOW

    G4

    Y1/Y

    RC

    3 2 1

    P1

    COM C

    C

    FUSE

    COM

    R

    3A

    24VAC

    IFB

    R

    W

    RBR

    IFM

    GND

    L2

    L1

    COM

    1 24 35

    BR

    Y

    BK

    GY

    SEE

    NOTE 6

    GND

    1

    1

    IFB INDOOR FAN BOARD

    LGPS LOW GAS PRESSURE SWITCH

    (WHEN USED)

    BL

    L2

    L2

    L2

    L2

    L1

    C

    J2

    W

    IFC

    G

    R

    RS

    RS

    LS

    LS

    CS

    CS

    GV

    GV

    C

    IGCCM

    BM

    FS

    RT

    V

    V

    LGPS (WHEN USED)

    CC1 C2

    LS2 SECONDARY LIMIT SWITCH

    T’STAT THERMOSTAT

    BR

    BR

    BR

    5A FUSE

    SEE

    NOTE 7

    SEE NOTE 8

    7 7

    6 6

    11 11

    10 10

    8 8

    2 2

    3 3

    4 4

    1 1

    5 5

    9 9

    12 12

    ECONOMIZER PLUG

    BL

    SAT

    BL

    BL

    ECON

    Y

    BR

    Y

    GY

    BKR

    P

    P

    Y2GY

    PRSO

    Y

    O

    BL

    LPS

    HPS

    BK

    BL

    BK

    GASHEAT

    DH DEHUMIDIFICATION MODE

    ECON ECONOMIZER

    Y2/DH

    5

    BL DH

    NOTES:

    1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE

    REPLACED, THEY MUST BE REPLACED WITH TYPE

    90 DEG. C WIRE OR ITS EQUIVALENT.

    2. SEE PRICE PAGES FOR THERMOSTAT AND SUBBASES.

    3. USE 75 DEG. COPPER CONDUCTORS FOR FIELD

    INSTALLATION.

    4. SEE INSTALLATION INSTRUCTIONS

    FOR PROPER HEATING AND COOLING CONNECTIONS

    FOR YOUR UNIT. INDOOR FAN MOTOR PLUGS

    - IDO NOT DISCONNECT UNDER LOADI

    5. LS2 USED ON SMALL CHASSIS ONLY.

    6. INDUCER CAPACITOR AND WIRING ON CERTAIN MODELS ONLY.

    IF CAP2 IS PRESENT, YELLOW WIRES FROM IGC AND IDM

    CONNECT ON SAME SIDE OF CAP2.

    7. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257003.

    8. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257005.

    9. DEHUMIDIFICATION FEATURE CANNOT BE USED WHEN

    ECONOMIZER IS INSTALLED.

    SEE NOTE 4

    SEE NOTE 9

  • 2050901340303

    Fig. 17 -- 208/230--3--60 Ladder Wiring Diagram

    12

    435 IFMBL

    O

    PR

    BK

    SEE NOTE 4

    Y

    LS1 (LARGE)

    LS2 (SMALL)

    BK

    BK Y

    BR

    DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING

    48VL500173

    IFM

    Y

    VRV

    Y

    C21

    L1

    208/230 VAC, 60 HZ, 3PH

    CCH

    (IF USED)CONT

    11

    13

    COMP

    C R

    S

    CAP

    F

    C

    23

    T3T1

    T2

    OFM

    FIELD SUPPLY

    BK

    Y

    Y

    Y

    BK

    BK BK

    L3BK G/Y

    BR

    USE COPPER CONDUCTORS ONLY

    G

    11

    G/Y

    TRAN

    PRIMARY 208/230V

    230

    24V

    COM

    C

    BRIDM

    CAP2

    CR CM

    Y

    G/Y

    SECONDARY 24V

    FS

    RS

    RS

    LS

    LS

    GV

    1

    2

    3

    R

    G

    W

    BL BL

    RS

    LS1 LS2

    MC

    MGV

    GY

    BR

    G/Y

    L2

    IGC

    IGC

    C

    GV

    C

    CONT

    C1 C2

    BR

    1

    1

    1

    1

    R

    G

    W

    Y1

    C

    T’STAT

    BK Y

    V

    BK

    Y

    BR

    CS

    CS

    IFO

    24VAC R

    FUSE

    3A

    P2-1IRIP1-1IRI

    P1-4IGI

    P2-5IXI

    P1-6IWI

    P2-3IWI

    P2-4IRI

    P1-3IY1/YI

    LOW

    HIGH

    Y

    BR

    COM C

    P2-2ICI

    C

    COM

    P1-2ICI

    L1

    SEE NOTE 6IFB

    IFB

    C

    11

    11 13

    13Y

    IGC

    IGC

    BR

    GY

    W

    R

    BK

    R

    R

    BR

    BL

    L2

    FS

    (SEE NOTE 5)

    5A FUSERT

    IFB

    OFM

    CONTROL BOX AREA

    COMP

    T1

    T2

    T3

    CAP 1

    H CF

    IFM

    3 UNIT COMPONENT ARRANGEMENT

    OUTDOOR FAN

    SECTION

    COMPRESSOR

    SECTION

    INDOOR FAN

    SECTION

    TRAN

    C

    21 23

    1311

    LS1

    IGC

    CAP 2

    IDM

    I

    MGV

    MC

    FS

    RS

    GAS

    SECTION

    (SMALL

    CABINET)

    SEE NOTE 7

    SEE NOTE 8

    4

    2

    3

    7

    5

    6

    8

    Y2V

    R

    YECON

    HARNESS

    COM C

    BK

    BR

    P BL

    P BLSAT

    HPS LPS

    BK BL BL

    PRS

    Y

    O O

    LGPS (WHEN USED)

    BK

    1

    DH P1-5IY2/DHI

    G

    W

    Y

    BL

    R

    LPS

    HPS

    PRS

    GAS HEAT

    SEE NOTE 9

  • 21 50901340303

    Fig. 18 -- 460--3--60 Connection Wiring Diagram

    R BK

    7 7

    6 6

    11 11

    10 10

    8 8

    2 2

    3 3

    4 4

    1 1

    5 5

    9 9

    12 12

    ECONOMIZER PLUG

    BL

    Y

    0

    G

    ENERGIZED

    T

    G

    DE-ENERGIZED

    0

    W

    45

    BR

    T

    W

    T+45

    BR

    ENERGIZED DE-ENERGIZED

    T+60

    HEATING FAN LOGIC

    COOLING FAN LOGIC

    COLOR CODE

    BK BLACK

    BL BLUE

    BR BROWN

    GY GRAY

    G GREEN

    O ORANGE

    P PINK

    R RED

    V VIOLET

    W WHITE

    Y YELLOW

    FIELD

    SUPPLYC F

    SCHEMATIC

    460-3-60

    1

    1

    SEE NOTE 5

    LEGENDFIELD SPLICE

    TERMINAL (MARKED)

    TERMINAL (UNMARKED)

    SPLICE (IF USED)

    SPLICE (MARKED)

    FACTORY WIRING

    FIELD CONTROL WIRING

    FIELD POWER WIRING

    ACCESSORY OR OPTIONAL

    WIRING

    TO INDICATE COMMON

    POTENTIAL ONLY:

    NOT TO REPRESENT WIRING

    BLR BLOWER RELAY

    C CONTACTOR

    COMP COMPRESSOR MOTOR

    CR COMBUSTION RELAY

    EQUIP EQUIPMENT

    FS FLAME SENSOR

    FU FUSE

    GND GROUND

    GVR GAS VALVE RELAY

    HV TRAN HIGH VOLTAGE TRANSFORMER

    I IGNITOR

    IGC INTERGRATED GAS UNIT

    CONTROLLER

    IDM INDUCED DRAFT MOTOR

    IFM INDOOR FAN MOTOR

    LS1 PRIMARY LIMIT SWITCH

    MGV MAIN GAS VALVE

    OFM OUTDOOR FAN MOTOR

    QT QUADRUPLE TERMINAL

    RS ROLLOUT SWITCH

    TRAN TRANSFORMER

    EQUIP_GND

    IDM

    V

    Y

    BR

    G/Y

    CAP 2

    QT

    COMP

    T1

    T2

    T3

    Y

    BR

    FS

    LS1

    13

    RS

    13

    LS2

    13R

    PRIMARY

    460V

    TRAN

    SECONDARY

    24V 2424

    460460

    MGV

    M C

    OFM

    CAP1

    Y

    BR

    C

    11 21

    13 23BK

    Y

    COMPRESSOR PLUG

    Y

    BK

    V

    BK

    Y

    BL

    BL

    GY

    BR

    G/Y

    BK

    BK

    CCH

    G

    IF USED

    NOTES:

    1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE

    REPLACED, THEY MUST BE REPLACED WITH TYPE

    90 DEG. C WIRE OR ITS EQUIVALENT.

    2. SEE PRICE PAGES FOR THERMOSTAT AND SUBBASES.

    3. USE 75 DEG. COPPER CONDUCTORS FOR FIELD

    INSTALLATION.

    4. SEE INSTALLATION INSTRUCTIONS

    FOR PROPER HEATING AND COOLING CONNECTIONS

    FOR YOUR UNIT. INDOOR FAN MOTOR PLUGS

    - IDO NOT DISCONNECT UNDER LOADI

    5. LS2 USED ON SMALL CHASSIS ONLY.

    6. INDUCER CAPACITOR AND WIRING ON CERTAIN MODELS ONLY.

    IF CAP2 IS PRESENT, YELLOW WIRES FROM CONTACTOR AND IDM

    CONNECT ON SAME SIDE OF CAP2.

    7. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257003.

    8. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257005.

    9. THESE FUSES ARE MANUFACTURED BY COOPER BUSSMAN,

    P/N FNQ-R-5.

    10. DEHUMIDIFICATION FEATURE CANNOT BE USED WHEN

    ECONOMIZER IS INSTALLED.

    L3

    L1BKBK

    Y

    O

    DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING

    I

    Y

    CAP 1 CAPACITOR, COMP

    CAP 2 CAPACITOR, INDUCER

    PRS PRESSURE SWITCH

    3

    CX5

    W

    4Y

    R 24V

    P2

    12

    LOW

    G4

    Y1/Y

    RC

    3 2 1

    P1

    COM C

    C

    FUSE

    COM

    R

    3A

    24VAC

    IFB

    R

    W

    RBR

    IFM

    GND

    L2

    L1

    COM

    1 24 35

    BR

    GY

    SEE

    NOTE 6

    GND

    SEE NOTE 4

    IFB INDOOR FAN BOARD

    LGPS LOW GAS PRESSURE SWITCH

    (WHEN USED)

    BL

    L2

    L1

    C

    J2

    W

    IFC

    G

    R

    RS

    RS

    LS

    LS

    CS

    CS

    GV

    GV

    C

    IGCCM

    BM

    FS

    RT

    V

    V

    CC1 C2

    SEE

    NOTE 4

    BL

    P

    R

    O

    BK

    LS2 SECONDARY LIMIT SWITCH

    T’STAT THERMOSTAT

    BR

    BK

    BR

    BR

    5A FUSER

    SEE

    NOTE 7

    SEE NOTE 9

    SAT

    BL

    BL

    ECON

    BR

    Y

    GY

    BK

    R

    BR

    R

    P

    P

    Y2

    FU1 5 AMP

    FU2 5 AMP

    R

    BK

    41 2 3

    230V460VCC

    AUTOTRANSFORMER

    BK

    R

    SEE NOTE 9

    BK

    R

    BK

    BK

    Y

    Y

    GY

    BL

    LPS

    HPS

    BK

    BL

    GROUNDED

    THRU STANDOFF

    PRSO

    Y

    O

    LGPS (WHEN USED)

    DH DEHUMIDIFICATION SIGNAL

    HIGH

    Y2/DH

    5

    Y

    R

    G

    W

    Y1

    R

    G

    W

    T’STAT

    BR C

    1

    1

    BL DH

    ECON ECONOMIZER

    SEE

    NOTE 10

  • 2250901340303

    Fig. 19 -- 460--3--60 Ladder Wiring Diagram

    BK

    COMP

    C R

    S

    CAP

    F

    C

    T3T1

    T2

    OFM

    Y

    Y

    BK

    BR

    DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING

    48VL500174

    IFM

    Y

    VRV

    Y

    C21

    L1

    CCH

    (IF USED)CONT

    11

    1323

    BK

    Y

    R BK

    L3BK G/Y

    G

    11

    G/Y

    460V

    24V

    460V

    24V

    BRIDM

    CAP2

    CR CMY

    G/Y

    SECONDARY 24V

    FS

    RS

    RS

    LS

    LS

    GV

    1

    2

    3

    R

    G

    W

    BL BL

    RS

    LS1 LS2

    MC

    MGV

    GY

    BR

    G/Y

    IGC

    C

    GV

    C

    CONT

    C1 C2

    BR

    1

    1

    1

    1

    R

    G

    W

    Y1

    C

    T’STAT

    BK Y

    V

    BK

    Y

    BR

    CS

    CS

    IFO

    24VAC R

    FUSE

    3A

    P2-1IRIP1-1IRI

    P1-4IGI

    P2-5IXI

    P1-6IWI

    P2-3IWI

    P2-4IRI

    P1-3IY1/YI

    LOW

    HIGH

    Y

    BR

    COM C

    P2-2ICI

    C

    COM

    P1-2ICI

    L1

    SEE NOTE 6IFB

    IFB

    C

    11

    11 13

    13Y

    IGC

    IGC

    BR

    GY

    W

    R

    BK

    R

    R

    BR

    BL

    L2

    12

    435 IFMBL

    O

    PR

    BK

    SEE NOTE 4

    FS

    (SEE NOTE 5)

    5A FUSERT

    IFB

    OFM

    CONTROL BOX AREA

    COMP

    T1

    T2

    T3

    CAP 1

    H CF

    IFM

    3 UNIT COMPONENT ARRANGEMENT

    OUTDOOR FAN

    SECTION

    COMPRESSOR

    SECTION

    INDOOR FAN

    SECTION

    TRAN

    C

    21 23

    1311

    LS1

    IGC

    CAP 2

    IDM

    I

    MGV

    MC

    FS

    RS

    GAS

    SECTION

    (SMALL

    CABINET)

    LS1 (LARGE)

    LS2 (SMALL)

    SEE NOTE 7

    SEE NOTE 8

    4

    2

    3

    7

    5

    6

    8

    Y2 V

    R

    YECON

    HARNESS

    COM C

    BK

    BR

    P BL

    P BLSAT

    460 VAC, 60 HZ, 3PH

    FIELD SUPPLY

    USE COPPER CONDUCTORS ONLY

    TRAN

    PRIMARY 460V

    HPS LPS

    BK BL BL

    PRS

    Y

    O O

    LGPS (WHEN USED)

    PRS

    LPS

    HPS

    1

    DHP1-5IY2/DHI

    R

    G

    W

    Y

    BL

    GAS HEAT

    SEE NOTE 10

  • 23 50901340303

    Normal Operation

    An LED (light--emitting diode) indicator is provided on theintegrated gas unit controller (IGC) to monitor operation. The IGCis located by removing the control access panel. During normaloperation, the LED is continuously on (See Table 6 for errorcodes).

    Airflow and Temperature Rise

    The heating section for each size unit is designed and approvedfor heating operation within the temperature--rise range stampedon the unit rating plate.Table 10 shows the approved temperature rise range for eachheating input, and the air delivery cfm at various temperaturerises for a given external static pressure. The heating operationairflow must produce a temperature rise that falls within theapproved range.Refer to Indoor Airflow and Airflow Adjustments section to adjustheating airflow when required.

    Heating Sequence of Operation

    (See Fig. 14--19 and unit wiring label.)On a call for heating, terminal W of the thermostat is energized,starting the induced--draft motor. When the pressure switchsenses that the induced--draft motor is moving sufficientcombustion air, the burner sequence begins. This function isperformed by the integrated gas unit controller (IGC). The indoor(evaporator)--fan motor is energized 45 sec after flame isestablished. When the thermostat is satisfied and W isde--energized, the burners stop firing and the indoor (evaporator)fan motor shuts off after a 45--sec time--off delay. Please notethat the IGC has the capability to automatically reduce theindoor fan motor on delay and increase the indoor fan motor offdelay in the event of high duct static and/or partially--cloggedfilter.

    Limit Switches

    Normally closed limit switch (LS) completes the control circuit.Should the leaving--air temperature rise above the maximumallowable temperature, the limit switch opens and the controlcircuit “breaks.” Any interruption in the control circuit instantlycloses the gas valve and stops gas flow to the burners and pilot.The blower motor continues to run until LS resets.When the air temperature at the limit switch drops to thelow--temperature setting of the limit switch, the switch closes andcompletes the control circuit. The direct--spark ignition systemcycles and the unit returns to normal heating operation.

    Table 6 – LED Indications

    STATUS CODE LED INDICATIONNormal Operation2 On

    No Power or Hardware Failure OffLimit Switch Fault 2 FlashesFlame Sense Fault 3 Flashes

    Four Consecutive Limit Switch Faults 4 FlashesIgnition Lockout Fault 5 FlashesPressure Switch Fault 6 FlashesRollout Switch Fault 7 FlashesInternal Control Fault 8 Flashes

    Temporary 1 hr auto reset1 9 Flashes

    NOTES:1.This code indicates an internal processor fault that will reset itself in onehr. Fault can be caused by stray RF signals in the structure or nearby.This is a UL requirement.2. LED indicates acceptable operation. Do not change ignition controlboard.3. When W is energized the burners will remain on for a minimum of 60sec.4. If more than one error code exists they will be displayed on the LED insequence.

    Rollout Switch

    The function of the rollout switch is to close the main gas valve inthe event of flame rollout. The switch is located above the mainburners. When the temperature at the rollout switch reaches themaximum allowable temperature, the control circuit trips, closingthe gas valve and stopping gas flow to the burners. The indoor(evaporator) fan motor (IFM) and induced draft motor continue torun until switch is reset. The IGC board is in a hard lockout andunit will require power reset to remove the hard lockout function.The IGC LED will display FAULT CODE 7.

    Step 3 — Start--up Cooling and Make AdjustmentsComplete the required procedures given in the Pre--Start--Upsection before starting the unit. Do not jumper any safety deviceswhen operating the unit. Do not operate the compressor whenthe outdoor temperature is below 40F (4.4C) (unlessaccessory low--ambient kit is installed). Do not rapid--cycle thecompressor. Allow 5 minutes between on cycles to preventcompressor damage.

    Checking Cooling Control Operation

    Start and check the unit for proper cooling control operation asfollows:

    1. Place room thermostat SYSTEM switch in OFF position.Observe that blower motor starts when FAN switch isplaced in ON position and shuts down when FAN switch isplaced in AUTO position.

    2. Place SYSTEM switch in COOL position and FAN switchin AUTO position. Set cooling control below roomtemperature. Observe that compressor, condenser fan,and evaporator blower motors start. Observe that coolingcycle shuts down when control setting is satisfied. Theevaporator fan will continue to run for 90 sec.

    IMPORTANT: Three--phase, scroll compressors are directionoriented. Unit must be checked to ensure proper compressor3--phase power lead orientation. If not corrected within 5minutes, the internal protector will shut off the compressor. The3--phase power leads to the unit must be reversed to correctrotation. When turning backwards, the difference betweencompressor suction and discharge pressures will be minimal.

  • 2450901340303

    Checking and Adjusting Refrigerant Charge

    The refrigerant system is fully charged with R--410A refrigerantand is tested and factory sealed. Allow system to operate aminimum of 15 minutes before checking or adjusting charge.NOTE: Adjustment of the refrigerant charge is not requiredunless the unit is suspected of not having the proper R--410Acharge.The charging label and the tables shown refer to systemtemperatures and pressures in cooling mode only. A refrigerantcharging label is attached to the inside of the compressor accesspanel. The chart includes the required liquid line temperature atgiven discharge line pressures and outdoor ambienttemperatures.An accurate thermocouple-- or thermistor--type thermometer,and a gauge manifold are required when using the subcoolingcharging method for evaluating the unit charge. Do not usemercury or small dial--type thermometers because they are notadequate for this type of measurement.

    UNIT DAMAGE HAZARD

    Failure to follow this caution may result in unit damage.

    When evaluating the refrigerant charge, an indicatedadjustment to the specified factory charge must always bevery minimal. If a substantial adjustment is indicated, anabnormal condition exists somewhere in the cooling system,such as insufficient airflow across either coil or both coils.

    ! CAUTION

    Proceed as follows:1. Remove caps from low-- and high--pressure service

    fittings.2. Using hoses with valve core depressors, attach low-- and

    high--pressure gauge hoses to low-- and high--pressureservice fittings, respectively.

    3. Start unit in Cooling Mode and let unit run until systempressures stabilize.

    4. Measure and record the following:a. Outdoor ambient--air temperature (F [C] db).b. Liquid line temperature (F [C]).c. Discharge (high--side) pressure (psig).d. Suction (low--side) pressure (psig) (for reference only).

    5. Using “Cooling Charging Charts,” compare outdoor--airtemperature(F [C] db) with the discharge line pressure(psig) to determine desired system operating liquid linetemperature (See Table 8).

    6. Compare actual liquid line temperature with desired liquidline temperature. Using a tolerance of 2F (1.1C), addrefrigerant if actual temperature is more than 2F (1.1C)higher than proper liquid line temperature, or removerefrigerant if actual temperature is more than 2F (1.1C)lower than required liquid line temperature.

    NOTE: If the problem causing the inaccurate readings is arefrigerant leak, refer to the Check for Refrigerant Leaks section.

    Indoor Airflow and Airflow Adjustments

    UNIT OPERATION HAZARD

    Failure to follow this caution may result in unit damage.

    For cooling operation, the recommended airflow is 350 to450 cfm for each 12,000 Btuh of rated cooling capacity. Forheating operation, the airflow must produce a temperaturerise that falls within the range stamped on the unit ratingplate.

    CAUTION!

    NOTE: Be sure that all supply--and return--air grilles are open,free from obstructions, and adjusted properly.

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal injury ordeath.

    Disconnect electrical power to the unit and install lockout tagbefore changing blower speed.

    ! WARNING

    This unit has independent fan speeds for gas heating andcooling. In addition, this unit has the field-selectable capability torun two different cooling fan speeds: A normal cooling fan speed(350~400 CFM/Ton) and an enhanced dehumidification fanspeed (As low as 320 CFM/Ton) for use with either adehumidistat or a thermostat that supports dehumidification.This unit is factory-set up for use with a single cooling fan speed.The cooling speed is marked “LOW” on the interface fan board(IFB) (Fig. 20) . The factory-shipped settings are noted in Table10. There are 3 additional speed tap wires available for use ineither gas heating or cooling (For color coding on the indoor fanmotor leads, see Table 7). The additional 3 speed tap wires areshipped loose with vinyl caps and are located in the control box,near the interface fan board (IFB) (Fig. 20).

    Gas Heating Fan Speed Set-up

    To change the gas heating speed:1. Remove the vinyl cap off of the desired speed tap wire

    (Refer to Table 7 for color coding). Table 10 shows thetemperature rise associated with each fan speed for agiven static pressure. Make sure that the speed chosendelivers a temperature rise within the rise range listed onthe unit rating plate.

    2. Remove the current speed tap wire from the “GAS HEAT”terminal on the interface fan board (IFB) (Fig.20) andplace vinyl cap over the connector on the wire.

    3. Connect the desired speed tap wire to the “GAS HEAT”terminal on the interface fan board (IFB).

    Single Cooling Fan Speed Set-up (Dehumidification featurenot used)To change cooling speed:

    1. Remove the vinyl cap off of the desired speed tap wire(Refer to Table 7 for color coding). Add the wet coilpressure drop in Table 10 to the system static todetermine the correct cooling airflow speed in Table 9 thatwill deliver the nominal cooling airflow as listed in Table 1for each size.

    2. Remove the current speed tap wire from the “LOW”terminal on the interface fan board (IFB) (Fig. 20) andplace vinyl cap over the connector on the wire.

    3. Connect the desired speed tap wire to the “LOW” terminalon the interface fan board (IFB).

  • 25 50901340303

    Two Cooling Fan Speeds Set-up (Dehumidification feature)IMPORTANT: Dehumidification control must open control circuiton humidity rise above set point.Use of the dehumidification cooling fan speed requires use ofeither a 24 VAC dehumidistat or a thermostat which includescontrol of a 24 VAC dehumidistat connection. In either case, thedehumidification control must open the control circuit on humidityrise above the dehumidification set point. Dehumidificationcontrols are available with the reverse logic; these must not beused.

    1. Remove fan speed tap wire from the “LOW” terminal onthe interface fan board (IFB) (Fig. 20).

    2. Determine correct normal cooling fan speed for unit andapplication. Add the wet coil pressure drop in Table 10 tothe system static to determine the correct cooling airflowspeed in Table 10 that will deliver the nominal coolingairflow as listed in Table 1 for each size.

    3. Remove the vinyl cap off of the desired speed tap wire(R