Steam injectors
-
7/28/2019 injektori
2/42
Steam injectors for boiler feedtank, hot waterand other industrial processheating requirements.
Vigorous mixing of steamand water takes placeinside the nozzle ensuringquiet operation.
Steam in
Hot water out
Cold water drawnin through radialports.
IN40M shown
Spirax Sarco steam injectors use steam to raise the temperature of water or other liquids. The injector draws in
cold liquid, mixes it with steam inside the injector and distributes the heated liquid in the tank. In many applications
the circulation induced by the injector is an advantage ensuring thorough mixing and avoiding temperaturestratification.
Boiler feedtank applicationsDissolved oxygen must be removed from boiler feedwater if corrosion is to be prevented in the boiler. Oxygen
can be removed either by chemicals or by heating. The dissolved oxygen content of water at 20C is 9 ppm,
at 60C is 5 ppm and at 90C is just under 2 ppm.
By heating the boiler feedwater to typically 85 - 90C to remove most of the oxygen, and introducing an oxygen
scavenging chemical into the boiler feedline to remove the small quantity of remaining oxygen, chemical usage
can be minimised. Additionally, boiler efficiency may be increased since blowdown requirements may be lowered.
FittingThe injectors can be fitted to the steam supply pipework or installed directly onto the tank wall using a female
threaded connection. For very large installations, multiple injectors may be used.
Range Nominal size End connections
IN40M 40 mm (1") Butt weld, screwed BSP or NPT
IN25M 25 mm (1") Butt weld, screwed BSP or NPT
IN15 15 mm (") Screwed BSP or NPT
-
7/28/2019 injektori
3/43
Typical injector systems - examplesA typical electropneumatic system and a self-acting control system are shown below. Self-acting controls offer
an economical solution for boiler feedtank applications. Pneumatic or electric systems can offer close temperature
control for process applications. Pipework can be routed inside or outside the tanks. Your local sales engineer
will be pleased to advise on the most suitable system for your plant requirements.
Steam in
Stop valve
Y-typestrainer
Vacuumbreaker
Controlvalve
Dialthermometer
Controland sensor
Injector
Pocket
Steam in
Stop valve
Y-typestrainer
Vacuum breaker
Control valve
Dialthermometer
Temperaturesensor
Injector
Pocket
O Complete mixing of steam within the injectorprovides quiet, efficient, and economic heating.
User benefits
O Avoids temperature stratification in tanks -maintains efficiency.
O 316 stainless steel injectors for long life andmaintenance free operation.
O Reduced need for oxygen scavenging chemicalsin boiler feedwater applications.
O Flexible control system packages,to suit individual applications.
Self-acting control system
Electropneumatic control system
Controller
Selecting a systemSpirax Sarco offers a wide range of valves,
controllers, sensors and ancillary equipment for
pneumatic, electric and self-acting control systems.
Literature describing these products is available on
request. The optimum choice of an efficient and
economical steam injection system depends on
many factors including temperature, steam flow,heating times and tank volume.
IN25M / IN40Mshown
IN15 shown
Your local Sales Engineer will be pleased to advise
on the most suitable equipment for your plant.
-
7/28/2019 injektori
4/44
Some of the products may not be available in certain markets.
Spirax-Sarco Limited, Charlton House,Cheltenham, Gloucestershire, GL53 8ER UK.
Tel: +44 (0)1242 521361 Fax: +44 (0)1242 573342E-mail: [email protected]
Internet: www.SpiraxSarco.com
Copyright 2006 Spirax Sarco is a registered trademark of Spirax-Sarco Limited
SB-P401-02 AB Issue 6
CapacitySteam injector capacities when heating tanks of up to 3 metresdeep and vented to atmospheric pressure. The choice of controlvalve can affect the steam capacity:
Injector type A B C Weight
IN15 " 205 28 0.4
IN25M 1" 84 71 0.8
IN40M 1 " 115 88 1.6
Dimensions / weights(approximate) in mm and kg
Limiting conditions
Estimating steamflowrates for water heating
Body design rating PN25Minimum operating pressure 0.5 bar g
Maximum saturated steam conditions 17.0 bar g @ 207 C
Example1. 'My tank size is 1.5 m x 2 m x 1.5 m.
I want to heat it from 20 C to 40 C in one hour'. Assume the tank is full.The tank volume = 4.5 m = 4 500 litre (4 500 kg).From the graph the required injected steam rate = 155 kg/ h.
2. 'My tank is the same as example 1, but I want to heat it in
20 minutes'. Since it is required to heat it up 3 times faster, thenthe injected steam rate will be three time as great i.e. 465 kg/ h.
3. 'I want to heat up my boiler hotwell from 30 C to 90 C, I havetwo boilers steaming all year round. They are each generatinga maximum of 10 000 lb/ h and my blowdown rate is 5 %'.Total steam generation rate = 20 000 lb/ h.Total blowdown rate = 5 % of 20 000 = 1 000 lb / h, hencefeedwater flowrate = 20 000 + 1 000 = 21 000 lb/ h.From the graph the required injected steam rate = 1 000 kg/ h
Injected steam rate lb / h
Injected steam rate kg / h
Tankcontentskg
(litre)
orBoilerfeedwaterflowrate
kg/h
The following chart enables an estimate to be made of the steam flowrate
required to heat up a tank in one hour or to produce a particular temperaturerise in a boiler feedtank.For boiler feedtanks note that feedwater flowrate equals steam generationrate plus blowdown rate.
100 000
70 000
50 000
30 000
20 000
10 000
7 000
5 000
3 000
2 000
1 000
700
500
300
200 300 500 1 000 2 000 5 000 10 000 20 000
50 70 100 200 300 500 1 000 2 000 5 000 10 000
200 000
100 000
70 000
50 000
30 000
20 000
10 000
7 0005 000
3 000
2 000
1 000
700
20C30
C50
C80
C10C
Example1
Example3
Water
temp
eratur
erise
Materials
How to orderExample:1 off Spirax Sarco IN25M steam injector in 316L gradestainless steel having a 1" screwed BSP connection.
SystemsFully engineered systems are available from Spirax Sarcoincluding controllers, valves and other ancillary products.
Austenitic stainless steel 316L
1" BSP Taper or NPT maleIN15
B
A
B
BSP/NPTfemale
IN25MIN40M
Injector type IN15 IN25M IN40M
Steam pressure at Saturated steaminlet of injector (bar g) capacity kg / h
0.5 11 75 222
1 20 135 4002 48 175 580
3 66 280 805
4 84 350 970
5 102 410 1 125
6 120 500 1 295
7 138 580 1 445
8 156 640 1 620
9 174 700 1 820
10 192 765 1 950
11 210 830 2 250
12 228 900 2 37013 246 975 2 595
14 264 1 045 2 710
15 282 1 095 2 815
16 300 1 170 3 065
17 318 1 225 3 200
Intermediate values may be obtained by linear interpolation.For higher capacities use two or more injectors in parallel.The information given is empirical and must not be used forcritical applications.
A
C
C
Tankcontentslb
orBoilerfeedwaterflowrate
lb/h
(Imperialgallon
=10lb)