The benefits of data center temperature monitoring

Ş. Albert, M.R.C. Truşcă, M.L. Soran

National Institute for Research and Development of Isotopic and Molecular Technologies, 67-103 Donat, 400293

Cluj-Napoca, Romania; e-mail: [email protected]

INCDTIM

Page 2: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

INCDTIM Datacenter • Grid site RO-14-ITIM

– 400 CPU Core, Storage 100 TB, Technology 1U servers + Blade system (IBM & HP)

• HPC Cluster (IBM iDataPlex unit) – 512 CPU Core (16 Core, 96 GB RAM, 450 GB

HDD / Computing unit), Storage 15 TB • Network infrastructure of the Institute

– Applications servers (e-mail, web, ftp, databases)

– Cisco Core switching system

2

INCDTIM

Presenter
Presentation Notes
The Grid site. Is named RO-14-ITIM
Page 3: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Network capabilities

• Layer 3 Core Switch - Cisco 6509E • 10 Gbps link to RoEduNet starting from 1 Feb. 2011 • Nexus switching system

– 40 Gbps inside the Grid site – 20 Gbps between Grid Site and Core Switch

3

INCDTIM

Presenter
Presentation Notes
The network is structured upon a Router Cisco 6509E and his Nexus system. The Interior communication in the Grid site in over 35 GBPs, The site is comunicating with the router with 20 GBps and the stable link between the Instiute and the Network Provider RoEduNet is 10 Gbps.
Page 4: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Why temperature monitoring?

the temperature is an important parameter for the equipment functioning.

the computer systems are designed to work efficiently when the ambient temperature is in the range 20 – 23°C.

constant temperature air conditioning systems power consumption

to minimize energy consumption

INCDTIM

Presenter
Presentation Notes
In order to minimize the energy
Page 5: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Practical implementation

The followed parameters:

• voltage power supply of the cooling units;

• temperature in different points of data center;

• humidity in different points of data center;

• state of functioning of the air conditioning unit fans.

INCDTIM

Page 6: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

1. digital power meter type UPT-210 (built by Algodue Elettronica, Italy) that provide information about power line parameters.

Hardware components INCDTIM

Electrical values measured are: The system voltage and the phase

voltages Phase currents, and current absorbed by

the system Power factor, Frequency Active, Reactive and the Apparent power

Page 7: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

2. microcontroller-based module (designed and built in INCDTIM) that measured temperatures, humidity and monitor the state of the AC units using different type of sensors.

INCDTIM

The temperature sensors, LM35 (National Semiconductor), allow to measure temperatures in the range -40 ... +150°C with 0.5°C accuracy without the need for calibration.

The humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%) for usual temperatures (0-70°C)

Page 8: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Electronic schema for adaptation board and sensors

INCDTIM

NEW: Humidity sensors

Block diagram of the monitoring system

Page 9: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Graphic interface for cooling system, temperature and humidity monitoring

Software components INCDTIM

Page 10: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Both software applications have a graphic interface and they are designed to: - read the watched parameters values and display them

online; - register all the values over the time; - generates an alarm when values are out of established

range; - implements 2 mechanisms: trigger an alarm by

authorized users and send an abort command.

INCDTIM

Page 11: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

R1 – R2 – network distribution racks

R3 – R8 – computing servers racks

R4 – HPC rack

R7 – GRID rack

- position of the temperature sensors

- position of the humidity sensors

- ventilation grids

Schema of Data Center INCDTIM

Page 12: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Variation of different parameters

0

10

20

30

40

50

60

9:18

:07

AM9:

54:2

3 AM

10:2

6:05

AM

11:0

2:50

AM

11:3

1:11

AM

11:5

9:11

AM

12:2

4:35

PM

12:5

5:28

PM

1:24

:16

PM1:

55:5

8 PM

2:23

:31

PM2:

51:5

6 PM

3:17

:46

PM3:

42:4

8 PM

4:10

:48

PM4:

51:1

4 PM

5:30

:02

PM6:

27:3

7 PM

8:43

:39

PM10

:27:

58 P

M1:

31:1

8 AM

3:22

:57

AM5:

11:2

7 AM

7:03

:41

AM7:

58:2

2 AM

8:28

:24

AM8:

57:1

3 AM

9:27

:07

AM9:

54:4

0 AM

10:2

3:05

AM

10:5

0:36

AM

11:2

6:28

AM

11:5

4:00

AM

12:2

4:28

PM

12:5

3:15

PM

1:27

:03

PM1:

57:3

1 PM

2:33

:52

PM3:

18:2

8 PM

3:51

:37

PM4:

23:4

5 PM

5:23

:50

PM7:

38:3

7 PM

9:05

:24

PM10

:50:

08 P

M1:

02:0

0 AM

3:32

:13

AM5:

22:4

7 AM

6:22

:52

AM7:

20:2

9 AM

8:00

:31

AM8:

29:4

3 AM

8:57

:41

AM9:

24:4

8 AM

9:50

:15

AM10

:20:

43 A

M10

:51:

36 A

M11

:24:

59 A

M12

:02:

57 P

M12

:43:

00 P

M1:

14:1

8 PM

T(0C)

Hour (hh:mm:ss)

12-14.02.2014

T1

T2

T3

T4

0

5

10

15

20

25

30

35

40

45

9:17

:24

AM10

:10:

45 A

M11

:04:

07 A

M11

:57:

28 A

M12

:50:

50 P

M1:

44:1

1 PM

2:37

:32

PM3:

30:5

4 PM

4:24

:15

PM5:

17:3

7 PM

6:10

:58

PM7:

04:1

9 PM

7:57

:41

PM8:

51:0

2 PM

9:44

:24

PM10

:37:

45 P

M11

:31:

06 P

M12

:24:

28 A

M1:

17:4

9 AM

2:11

:11

AM3:

03:3

1 AM

3:56

:53

AM4:

50:1

4 AM

5:43

:35

AM6:

36:5

7 AM

7:30

:18

AM8:

23:4

0 AM

9:20

:01

AM10

:13:

22 A

M11

:06:

43 A

M12

:00:

05 P

M12

:53:

26 P

M1:

46:4

8 PM

2:40

:09

PM3:

33:3

0 PM

4:26

:52

PM5:

20:1

3 PM

6:13

:35

PM7:

06:5

6 PM

8:00

:18

PM8:

53:3

9 PM

9:47

:00

PM10

:40:

22 P

M11

:33:

43 P

M12

:27:

05 A

M1:

20:2

6 AM

2:13

:47

AM3:

07:0

9 AM

4:00

:30

AM4:

53:5

2 AM

5:47

:13

AM6:

40:3

5 AM

7:33

:56

AM8:

27:1

7 AM

9:20

:39

AM10

:14:

00 A

M11

:07:

22 A

M12

:00:

43 P

M12

:54:

04 P

M

P(kW)

Hour (hh:mm:ss)

12-14.02.2014

P

P1

P2

P3

a)

b)

a) registered temperatures in the fixed points; b) power consumption in the same period

T1 - rack site GRID T2 - HPC cluster rack T3 - temperature of the heat agent of AC unit T4 - outside ambient temperature

12

Page 13: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Test periods for reducing energy consumption

Page 14: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Simulation of data center operating using experimental data registered

Page 15: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Hour 07.02.2015 12.02.2015 14.02.2015

tDC(°C) text (°C)

no. of AC units tDC(°C) text

(°C) no. of

AC units tDC(°C) text (°C)

no. of AC units

1 - 4 21,35 9 3 21,37 8 3 20,31 9 1 5 21,24 7 3 21,22 7 3 20,42 9 1 6 21,21 6 3 21,20 7 3 20,45 9 1 7 21,18 6 3 21,17 7 3 20,47 8 1 8 21,17 7 3 21,15 8 3 20,42 9 1 9 21,15 8 3 21,14 9 3 20,53 9 1

10 21,13 9 3 21,15 10 3 20,57 9,5 1 11 21,37 11 3 21,13 11 3 20,61 9,5 1 12 21,09 12 3 21,11 15 3 20,64 9,5 2 13 21,08 14 3 21,02 20 3 20,64 10 2 14 21,07 14 3 21,17 21 3 20,65 12 2

15-18 21,07 14 3 21,12 23 3 20,68 13 2 19 20,98 15 2 21,02 16 3 20,69 9 2

20-21 20,91 10 2 20,99 15 2 20,71 9 2 22-23 20,89 9 2 21,00 12 3 20,73 9 2

Presenter
Presentation Notes
In acest tabel sunt prezentate cateva dintre datele obtinute in urma simularii variatiei temperaturii in DC. In ruma acestor simulari am putut determina numarul minim al unitatilor de AC necesar a fi in functiune astfel incat temperatura in DC sa fie mentinuta constanta in jurul valorii de 21°C. Aceste valori au fost comparate cu cele gasite experimental si s-a constatat ca exista o stransa corelatie intre ele, fiind astfel dovedita functionalitatea si utilitatea programuylui de simulare creat.
Page 16: INCDTIM The benefits of data center temperature monitoringThe humidity sensors, SYH-2R, allow determining the humidity in the range 10 ... 95% with an acceptable accuracy (3 to 5%)

Conclusions INCDTIM

• The device allows to register some parameters in different points of Datacenter and monitoring of these parameters can be achieved in real-time.

• The variation of the parameters values can be followed by data interpretation on different period of time and season.

• Advantages of the temperature monitoring: - simulation of the Datacenter operation based on recorded data for

long periods of time; - setting a schedule for operation of the air conditioning system; - maintaining Datacenter environmental conditions in the range in

which computer systems work efficiently; - reducing energy consumption;

• It can be determined and implemented a system of functioning of the entire system, in order to improve resource utilization.

The authors would like to express appreciation for the support of the Romanian National Authority for Scientific Research, CNCS – UEFISCDI, through the projects 8EU/2012 and IUCN-DUBNA.

ACKNOWLEDGEMENTS

Presenter
Presentation Notes
The data can be used to take all necessary measures in order to control those two parameters and maintaining their values in a narrow range