impact of distributed generation units on short circuit capacity calculations by shabanzadeh
DESCRIPTION
Impact of Distributed Generation Units on Short Circuit Capacity Calculations by ShabanzadehTRANSCRIPT
-
In the name of Allah, Most Gracious, Most Merciful
Impact of Distributed Generation Unitson Short-Circuit Capacity (SCC) Calculations
By : Morteza ShabanzadehSupervisor : Professor Mahmoud-Reza Haghi-Fam
Morteza Shabanzadeh & TMU 2013
-
P t ti O tliPresentation Outline
Introduction Introduction SCC Calculation According to IEC 60909 Standard Impact of DGs on Fault Locating Methods DGs Effects in Different Types of Dis. Networks Limitation of Short-Circuit Power due to DGs
2/72MortezaShabanzadehandTMU2013
-
IntroductionIntroduction
Short-Circuit Currents : Initial symmetrical short-circuit current ( ) Peak short-circuit current ( ) Steady state short-circuit current ( )
3/72MortezaShabanzadehandTMU2013
-
IntroductionIntroduction
4/72MortezaShabanzadehandTMU2013
-
IntroductionIntroduction
Peak Short-Circuit Currents ( ):
Ip causes high dynamic and mechanical stresses on the components.
It ill b h d ithi 10 ft f th f lt It will be reached within 10 ms after occurrence of the fault.
Conventional circuit breakers in the network will not be fast enough tointerrupt this current and therefore components have to be designed suchinterrupt this current and therefore components have to be designed such
that they are able to withstand these currents.
6/72MortezaShabanzadehandTMU2013
-
IntroductionIntroduction
Initial & Steady-state Short-Circuit Currents ( , ):
They will result in large losses , And therefore cause thermal overloading.g
6/72MortezaShabanzadehandTMU2013
-
IntroductionIntroduction
Fault level calculations are indispensable tools during the Grid Design Phase.
The purpose of short-circuit calculations is to determine: Thermal effect of fault currents on grid components.g p Mechanical stresses on grid components. Coordination of protection devices.
7/72MortezaShabanzadehandTMU2013
-
IntroductionIntroduction
Distribution networks are characterized by: Max acceptable fault current (related to the switchgear) Thermal withstand capability (of the equipment) Mechanical withstand capability (of the equipment and constructions)
8/72MortezaShabanzadehandTMU2013
-
IntroductionIntroduction
Main inhibiting factor for the interconnection of DGs: Combined Isc contribution of the upstream grid and DGs should remain
below the network design value.
SCC of existing distribution network (esp. MV) is close to the design value(little margin for the connection of DGs).
9/72MortezaShabanzadehandTMU2013
-
IntroductionIntroduction
DGs Isc depends on : DGs size DGs control mode (Technology) The number of connection points of DGs in the system
10/72MortezaShabanzadehandTMU2013
-
P t ti O tliPresentation Outline
Introduction Introduction SCC Calculation According to IEC 60909 Standard Impact of DGs on Fault Locating Methods DGs Effects in Different Types of Dis. Networks Limitation of Short-Circuit Power due to DGs
11/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Basic Principles: Equivalent Voltage Source Method Several simplifications in calculation procedures Isc Calculation using Vn and rated values of the equipment Various correction factors Network neutral is earthed
12/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit current definitions: Initial Symmetrical Short-Circuit Current ( ):
rms value of the ac symmetrical component of a prospective
short-circuit current
Initial Symmetrical Short-Circuit Power ( ):
hasnophysicalmeaning
13/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit current definitions: Peak Short-Circuit Current ( ):
Max instantaneous value of the fault current.
Decaying aperiodic component ( ):
14/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit current definitions: Steady-state Short-Circuit Current ( ):
The rms value of the current after the decay of the transient
components.
For far-from-generator faults :
15/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Calculation of : Equivalent Voltage Source :
Voltage of an ideal source applied at the short-circuit location in positive
sequence system, whereas all other sources in the system are ignored
(short-circuited)(short-circuited).
16/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit Impedances :
17/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit Impedances :1) Equivalent impedance of the upstream network :
Fornetworkswithanominalvoltagehigherthan35kV,theIECStandardsuggestsRQ=0. Inallothercases,itrecommendsRQ/XQ=0.1asasafeassumption.
18/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit Impedances :2) Equivalent impedance of a Transformer:
These Eqs are also applicable to shortcircuit current limiting reactors
19/72MortezaShabanzadehandTMU2013
TheseEqs.arealsoapplicabletoshort circuitcurrentlimitingreactors.
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit Impedances :3) Equivalent impedance of Lines:
Theimpedanceofoverheadlinesandcables iscalculatedfromconductorandlinegeometrydataanditistypicallyknownforstandardlinetypes.
20/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit Impedances :4) Equivalent of Synchronous Generators:
Xd isthesubtransientreactance.
21/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit Impedances :5) Equivalent of Power Station units with Syn. Generators:
TheimpedanceisreferredtotheHVside.
tr istheratedtransformationratiooftheunittransformer.
22/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit Impedances :6) Equivalent of Asynchronous Motors:
ILR/IrM istheratiooflockedrotor toratedcurrentofthemachine..
23/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Short-circuit Impedances :
Shuntcapacitorsandnonrotatingloadsareignored.
24/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Correction factors:
IEC60909introducesimpedancecorrectionfactorsfor:
Transformers(KT) Synchronousgenerators(KG) Powerstationunits(KS)
whichmultiplytherespectiveimpedancesinallcalculationformulae.
25/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:
o Resultingfaultlevelisthephasorsumofthemaxfaultcurrentsfrom: UpstreamGrid Step down Transformer StepdownTransformer VariousDGs
o AccordingtoIEC60909:Thegridcontributioniseasilycontributed,butThecontributionofnovelDGtypesisnotaddressedinthisStandard.
26/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
DG
Directly coupled
Decoupled via converter interface
Asynch. Generator
Synch. Generator
Static Conversion
Rotating Conversion
SCIG & DFIG wind generators
CHP Fuel CellPVDirect drive WTs
-CHP
27/72MortezaShabanzadehandTMU2013
g
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:1) Contributionoftheupstreamgrid
28/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:2) ContributionoftheDGstations
Type ITypeI TypeII TypeIII TypeIV
29/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:2) ContributionoftheDGstations
Type I :Synch.Generatorsdirectlycoupledtothegrid
Type ISHEP, CHP
30/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:2) ContributionoftheDGstations
Type II :ASynch.Generatorsdirectlycoupledtothegrid
Type IISmall SHEP,
constant speed WTs
31/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:2) ContributionoftheDGstations
Type III:DFIG,withpowerconvertersintherotorcircuit
Type IIIDFIG
(variable speed WTs)
32/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:2) ContributionoftheDGstations
Type III:DFIG,withpowerconvertersintherotorcircuit
LimitedovercurrentcapabilityofRotor Statorcurrentisdominant Crowbar protectionCrowbarprotection RoughlyapproximatedasTypeII Statorisdisconnectedafter30~50ms Isc(max)
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:2) ContributionoftheDGstations
Type IV:Powerconverterinterfacedunits,withorwithoutrotatinggenerator
Type IVPVs, -Turbines
variable speed WTs
34/72MortezaShabanzadehandTMU2013
-
Overview of the IEC 60909 StandardOverview of the IEC 60909 Standard
o Fault level calculation in networks with DG:2) ContributionoftheDGstations
Type IV:Powerconverterinterfacedunits,withorwithoutrotatinggenerator
AretreatedasASynch.Machines
orort isthedurationofthecontribution(100msmaybeadoptedhereaswell)
35/72MortezaShabanzadehandTMU2013
-
Case StudyCase Study
PLOAD =35MVA
T II
Type IV
PDG =17.16MW
Type I
Type II
Type III
36/72MortezaShabanzadehandTMU2013
-
Case StudyCase Study
Type IV
Type III
Type II
37/72MortezaShabanzadehandTMU2013
Type I
-
Case StudyCase Study
Results
Asexpected,thecontributionofTypeIVDGunitsismuchlowerthanallotherTypes.
Type IV
Type III
38/72MortezaShabanzadehandTMU2013
-
Case StudyCase StudyResults
Type II
Type I
39/72MortezaShabanzadehandTMU2013
-
Case StudyCase Study
Resulting fault level at the MV busbars :
Algebraic sum
Phasor sum (with contribution of WF1 added algebraically)(with contribution of WF1 added algebraically)
40/72MortezaShabanzadehandTMU2013
-
DGs short-circuit current SimulationDGs short-circuit current Simulation
Technical Softwares to simulate DGs Protection behavior:
DIgSILENTPowerFactory PSCAD ATPEMTP
41/72MortezaShabanzadehandTMU2013
-
Example (2) :Example (2) :
Resulting fault level in Netherland test network:
Peak Short Circuit Current (KA)
42/72MortezaShabanzadehandTMU2013
-
Solutions for fault level reductionSolutions for fault level reduction
1. Increasethedesignmaximumfaultlevel
2. Reducetheprospectiveshortcircuitcurrentofthegrid Reconfigurationofthenetwork Increasetheshortcircuitimpedanceofthetransformers Reduce the prospective shortcircuit current of the DGReducetheprospectiveshort circuitcurrentoftheDG
3.ReducetheprospectiveshortcircuitcurrentoftheDG Selectequipmentwithincreasedshortcircuitimpedance Installation of current limiting reactors Installationofcurrentlimitingreactors Connectionviapowerelectronicsconverters
4.Activelimitationoftheshortcircuitcurrent
43/72MortezaShabanzadehandTMU2013
-
P t ti O tliPresentation Outline
Introduction Introduction SCC Calculation According to IEC 60909 Standard Impact of DGs on Fault Locating Methods DGs Effects in Different Types of Dis. Networks Limitation of Short-Circuit Power due to DGs
44/72MortezaShabanzadehandTMU2013
-
Impact of DGs on Fault Locating MethodsImpact of DGs on Fault Locating Methods
o Effect of DG on Impedance Measurement Based Method :
Single-line diagram of network DG unit placed at upstream DG unit placed at downstream
45/72MortezaShabanzadehandTMU2013
-
Impact of DGs on Fault Locating MethodsImpact of DGs on Fault Locating Methods
o Simulation Result :
Scenario (2): Inverter based DG = 5 MW
Scenario (1): Synchronous DG = 30 MW
46/72MortezaShabanzadehandTMU2013
single-phase to ground fault
-
Impact of DGs on Fault Locating MethodsImpact of DGs on Fault Locating Methods
o Simulation Result :Calculation error with DG at upstream of fault Calculation error with DG at downstream of fault
d
o
w
n
s
t
r
e
a
m
f
f
a
u
l
t
u
p
s
t
r
e
a
m
f
f
a
u
l
t
D
G
a
t
d
o
f
D
G
a
t
o
f
1. InverterbasedDGsinjectless shortcircuitcurrenttothefault.
47/72MortezaShabanzadehandTMU2013
2. UpstreamDGshavemorenegative effectsonfaultlocatingmethodsincomparisontodownstreamDGs.
-
P t ti O tliPresentation Outline
Introduction Introduction SCC Calculation According to IEC 60909 Standard Impact of DGs on Fault Locating Methods DGs Effects in Different Types of Dis. Networks Limitation of Short-Circuit Power due to DGs
48/72MortezaShabanzadehandTMU2013
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
o Three types of distribution systems:
RadialL Loop
Network
49/72MortezaShabanzadehandTMU2013
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
A. RadialC (1) C (2)C (3)Case(1) Case(2)Case(3)
50/72MortezaShabanzadehandTMU2013
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
A. RadialDGat7,PF
DGat7,VC
DGat2~7,
u
.
)
,5MW,PFDGat2~7,5MW,VC
B
u
s
V
o
l
t
a
g
e
(
p
.
u
B #
51/72MortezaShabanzadehandTMU2013
Bus#
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
A. Radial
Isc (KA)
We can see that the more connection points of DG in the system, the lower values
52/72MortezaShabanzadehandTMU2013
of short circuit currents.
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
B. Loop
h f h d d d b f l d
53/72MortezaShabanzadehandTMU2013
The case of shared sized DG at two connection points provides better profile around 1.0 p.u.
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
B. Loop
Isc (KA)
d f l d h f l l f f h d
54/72MortezaShabanzadehandTMU2013
As expected, fault currents decrease as the fault location gets far away from the grid.
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
C. Network
55/72MortezaShabanzadehandTMU2013 34.5 kV network type test system
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
C. Network
56/72MortezaShabanzadehandTMU2013
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
C. Network
57/72MortezaShabanzadehandTMU2013
-
DGs Effects in Different Types of Dis NetworksDGs Effects in Different Types of Dis. Networks
Dispersedlylocated DGresultsinbettervoltageprofilecomparedtosinglespotlocatedDG.
If di t ib ti t h t id ti f lt t t Ifadistributionsystemhasastronggridconnection,faultcurrentsmaynotsignificantlyincreasewiththeadditionofDG.
AnumberofDGhavingaunitarypowerfactorcontrolshouldbelocatedalongg y p f gdistributionsystemsothatbettervoltageprofileisobtained.
58/72MortezaShabanzadehandTMU2013
-
P t ti O tliPresentation Outline
Introduction Introduction SCC Calculation According to IEC 60909 Standard Impact of DGs on Fault Locating Methods DGs Effects in Different Types of Dis. Networks Limitation of Short-Circuit Power due to DGs
59/72MortezaShabanzadehandTMU2013
-
Limitation of Short-Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
Fault Current Limiters (FCLFCL) :
The most important requirements of an FCL are1) Limitation of peak current (Ip) within 10ms.
(The minimum opening time of the circuit breakers is much longer
, and therefore they are not able to protect the components)
2) Ratio between nominal current and limited short-circuit current.
3) Low impedance and low losses in normal situation.
60/72MortezaShabanzadehandTMU2013
-
Limitation of Short-Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
The most important types of FCLFCL :
1. Choke coil
2. Superconductorsp
3. Semiconductors
4. Magnetic fault current limiter
5. Is Limiter
61/72MortezaShabanzadehandTMU2013
-
Limitation of Short-Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
The most important types of FCLFCL :
1. Choke coil
(high) impedance( g ) p simple and robust voltage drop & losses during normal operation big size
62/72MortezaShabanzadehandTMU2013
-
Limitation of Short-Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
The most important types of FCLFCL :
2. Superconductors
use the relationship between the resistance and temperature to limit Ip, Ik.
R = 0 (when they are cooled below their critical temperature)
During fault, due to losses their temperature will increase and FCL will get a much higher R.
low losses very fast response (Ip can be limited quite well) very expensive are still in development stage (not commercially available yet) are still in development stage (not commercially available yet)
63/72MortezaShabanzadehandTMU2013
-
Limitation of Short-Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
The most important types of FCLFCL :
3. Semiconductors
use semiconductor switches
good controllability fast response losses in the semiconductors
64/72MortezaShabanzadehandTMU2013
-
Limitation of Short-Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
The most important types of FCLFCL :
4. Magnetic fault current limiter
Based on the fact that a coil, or transformer, has a very low impedance when it is in saturation At the moment a fault occurs the large fault current forces the coil out of saturation, implying a muchAt the moment a fault occurs the large fault current forces the coil out of saturation, implying a much
higher impedance.
reliable operation gradual and smooth change of impedance good limiting capabilities (R8) commercially available large dimensionsg high price
65/72MortezaShabanzadehandTMU2013
-
Limitation of Short-Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
The most important types of FCLFCL :
5. Is Limiter consists of two conductors in parallel.
The main conductor carries the nominal current
(up to 5kA).
After tripping the parallel fuse limits Ip in a very short time
( 1 )(< 1 ms).
66/72MortezaShabanzadehandTMU2013
-
Limitation of Short-Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
The most important types of FCLFCL :
5. Is Limiter very fast good R-ratio small size low losses after each operation fuses have to be replaced;
h lThis implies :
relatively high costs longer interruption times incorrect operation incorrect operation
67/72MortezaShabanzadehandTMU2013
-
Limitation of Short Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
SelectionofFCLFCL:
ThegoaloftheprocedureistofindaconfigurationforwhichCtot isaslowaspossible(i.e.findingmin[Ctot]):
thecostsofrepairing orreplacing componentswhichhavebeendestroyedbecauseoftohighfaultcurrents,butalsothecostsof
68/72MortezaShabanzadehandTMU2013
customerminuteslost.
-
Limitation of Short Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
SelectionofFCLFCL:10 d l h b FCL10stepproceduretoselectthebestFCL:
Step1. Createalistofpossiblefaultlocations;Step2. Foreachofthepossiblefaultlocations,
conductashortcircuitcalculationusingIEC(60)909;
Step7.Determinepossiblefaultcurrentlimiterlocations;Step8.Foreach(combination)ofthelocations:calculate
thetotalcostsofafault,usingthetwodifferentco duc a s o c cu ca cu a o us g (60)909;Step3. Removethefaultlocationsforwhichnopeakfault
currentproblemoccurs;Step4. Foreachoftheremainingfaultlocations:
Determinetheprobabilityofafaulttooccur;St 5 S l t th f lt l ti ith th hi h t f lt
e o a cos s o a au , us g e o d e etypesoffaultcurrentlimitersatthelocation(s);
Step9.Selectthesituationwiththelowesttotalcostscausedbyafaultandpermanentlyaddthefaultcurrentlimiter.
St 10 R th f lt l ti f th li t dStep5. Selectthefaultlocationwiththehighestfaultoccurrenceprobability.
Step6.Calculatethetotalcostsofafaultatthislocation,withoutaddingfaultcurrentlimiting.
Step10.Removethefaultlocationfromthelistandrestartfromstep2,repeatinguntilthereisnofaultlocationleftinthelist
69/72MortezaShabanzadehandTMU2013
-
Limitation of Short Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
SelectionofFCLFCL: CHP
CHP
The rated Ipeak of the substation is 50kATheratedIpeak ofthesubstationis50kA
70/72MortezaShabanzadehandTMU2013
ArealnetworkinthesouthwesternpartoftheNetherlands
-
Limitation of Short Circuit Power due to DGsLimitation of Short-Circuit Power due to DGs
SelectionofFCLFCL:Theresultsaccordingto10stepprocedure:
71/72MortezaShabanzadehandTMU2013
-
th h t l ithose who struggle in our cause, we will surely guide them to our ways;
and Allah is with those who do good.
AL ANKABOOT (6 )AL-ANKABOOT (69)
72/72MortezaShabanzadehandTMU2013