ILJIN ElectricTRANSFORMER
http://www.iljinelectric.co.kr
www.iljinelectric.co.kr
Printed in korea 2009.10
ILJIN ElectricTRANSFORMER
ILJIN ELECTRIC TRANSFORMER
07 | Characteristics & Classification
09 | Manufacturing Process
11 | Single Phase Transformer / 345kV
13 | Three Phase Transformer / 230kV
15 | Three Phase Transformer / 154kV
17 | Three Phase Transformer / 66kV
19 | Three Phase Transformer / 22.9kV
21 | N2 Gas Type Transformer
23 | Furnace Transformer
25 | Scott Transformer
27 | Less Flammable Power Transformer
29 | Accessories
35 | Oil Preservation System
36 | Special Specifications & Packing
37 | Maintenance
38 | Performance Records
ContentsILJIN Electric Company’s long history brings “Accumulated technology and High Reliability” to its transformer.ILJIN, with its goal to contribute to stable supply of electric power, has been concentrating tocontinuously develop the required technology in this field. With the accumulated technology, ILJIN ismanufacturing transformers with high performance, low noise and sufficient protection against shortcircuit, which makes it suitable for various kinds of applications. The main transformers manufacturedby ILJIN Electric Company are the ultra high voltage transformer of 154kV and 345kV classes. ILJINElectric Company also has a wide range of production lines such as medium size transformers fortransmission and distribution, furnace transformers, less flammable transformers and Scotttransformers. Moreover, ILJIN Electric Company provides turn-key services, a total engineeringsolution which includes manufacturing, installment and tryout testing for electric transmission anddistribution.
ILJIN Electric Transformer
Program for Transformer Design
Title ofProgram Developer Function Remark
Calculation of Impedance, Loss and
Sort Circuit
2 FLD 8 Anderson (Norway). Eddy Loss
3 EMFIS Seoul National University (Korea). Electromagnetic Analysis Finite Element
4 ANSYS Ansys Company (U.S.A). Structure Analysis Finite Element
Designing, Optimising and Finite Element
Electromagnetic Analysis
MAXWELL Magnetostartic, Eddy Current,
2D/3D Transient EM, Loss, Force
7 SOLIDEDGE Siemens ( Germany) Designing
8 EDMAG 3D VIT (Ukraine) Stray Load Loss Analysis Finite Element
9 PTAN VIT (Ukraine) Seismic Analysis Finite Element
10 HARMONICS VIT (Ukraine) Harmonic Analysis Finite Element
ILJIN Electric TRANSFORMER
History of the company Oct. 1938 Establishment of Incheon Plant by Toshiba, Japan
(The First Transformer Factory in Korea)
Feb. 1956 Privatized and renamed to Leechun Electric Mfg. Co., Ltd.
Jul. 1958 Merged with Dae-Dong Industry, a major pump manufacturer
Jul. 1969 Establishment of Switchgear, a generator facility
Sep. 1973 Expansion of transformer and large size motors facilities
Oct. 1977 Completion of the 154kV, 345kV transformer plant
Mar. 1978 Establishment of small size motor and metal plate facility
Apr. 1978 Cooperation with Toshiba, Japan
Mar. 1979 Expansion of manufacturing facility
Jul. 1979 Production of Turbo Freon-resistant electric motors for Turbo-refrigerator
Jan. 1980 Certification for production of 345kV Ultra High Voltage class
Feb. 1981 Designated as manufacturer of parts for the electric railway
May. 1981 Designated as major manufacturer of parts for ships
Apr. 1983 Supplied mold transformers to the Seoul Subway
Mar. 1985 Manufactured pumps for nuclear power plants
Apr. 1985 Received Golden Tower Industry Medal on Electricity Day
Mar. 1989 Manufactured High Voltage High Speed motor (3050kW-2P)
Oct. 1989 Technical cooperation with Mitzubishi Heavy Industries
Mar. 1990 Received Culture Award in technical part
Jul. 1990 Obtained CSA Standard certification and 1st class Quality Management
Dec. 1990 Designated as quality control inspection organization
Jan. 1991 Manufactured submerged propeller pump motors
May. 1991 Expansion of Pump facility
Oct. 1993 Acquired KT certification for new technology
May. 1994 Obtained ISO 9001
Mar. 1996 Merged into Samsung group
Oct. 1997 Changed company name and CI
Dec. 1998 Merged into ILJIN Group
Jan. 1999 Changed company name and CI to ILJIN Heavy Industries. Co., Ltd.
Jun. 1999 Designated as maintenance company of Water Resource in Korea
Aug. 2002 Certification for high efficient energy components (200kW-4P/160kW-6P)
Dec. 2002 Renewal of ISO 9001 to the 2000 version
Oct. 2003 Development of 154kV Less Flammable Power Transformer
Dec. 2004 Development of the new concept Gate Pump
Dec. 2004 Supplied Ultra High Voltage Scott transformer for the electric railway
Nov. 2005 Received award from KEPCO
Dec. 2005 Approval of the new concept Gate Pump from the Minister of Commerce, Industry and
Energy
Feb. 2006 Obtained KT certification from Incheon Kyung-gi Machinery Industry Union
Aug. 2007 Changed company name and CI to ILJIN Electric Co., Ltd.
May. 2008 Carried out Mindanao Substation Expansion Project (Turn Key Project)
Mar. 2009 Completion of new transformer line
Oct. 2009 Aquired KEMA Certificate
1 FLD12 Anderson (Norway).
5 FLUXS 2D Cedrat (France).
6 Ansoft (USA)
ILJINElectricCompanyTransformer
ILJIN Transformer 8
CHARACTERISTICS & CLASSIFICATION
ILJIN Transformer7
High Reliability is maintained through stable design based onaccumulated technical power and new technology, excellentworking environment and facilities, strict work control andsystematic test and inspection process.
High Reliability
To remove moisture from deep inside, coil and coreassembly is fully dried using Vacuum Vapor Phase DryingPlant, which is controlled automatically according to presetoptimum condition.
Perfect Drying Process
Low no load loss and noise reduction is achieved by adoptingmiter joint construction and automatic core cutting in whichthe characteristics of grain oriented silicone steel is fullyutilized.
Core Construction with High Performance
Sufficient mechanical strength against Short Circuit isachieved by maintaining a balance of ampere-turns betweenwindings and adopting materials suitable for mechanicalforce calculated by computer as well as exercising adequatecare in winding assembly.
Sufficient Mechanical Strength against Short Circuit
ILJIN has top class winding technology including all kinds ofdisc and layer winding with designs suitable for eachapplication with other abundant winding technology.
Advanced winding technology
Thanks to the combination of excellent core construction andassembly technique, ILJIN transformer can reach noise levelbelow the requirements of all International Standards as wellas Korea.
Transformer amicable to environment with Low Noise
Characteristics
Classification
Oil Type
Insulation Cooling System Voltage Application
ONAN ONAFOFAN
OFAF,ODAFOFWF,ODWF
345kV154kV22.9kV6.6kV3.3kV
Generation PlantTransmission & Distribution System
Electric FurnaceRectifierRectifier
Scott Connection
Surrounding Condition
Applied Standard
Numbers of Phases & Rated Frequency 1 or 3 / 50 or 60Hz
1 or 3 / 50 or 60Hz
International Standard
Tap Changer Type Tap Selecting Range
National Standard Association Standard
Ambient Temperature
Installing Site
Amplitude
Insulation Classification
-25~40
Indoor / Outdoor
1000m
A Class
IEC
ISO
NLTC
OLTC
Rated Voltage 2step x 5 or 2.5% or Option Range
Rated Voltage 8step x 1.25% or Option Range
KS
JEC
ANSI
BS
KMC
ES
NEMA, TR2
IEEE
JEMA
Frame
Oil Preservation System Cooling System Base
Conservator Type
N2 Sealing Type
Air Seal Cell Type
ONAF
OFAN
OFAF,ODAF
OFWF,ODWF
SKID
ROLLER
General Specification
ILJINHeavyIndustriesTransformer
ILJIN Transformer 10
Manufacturing ProcessTRANSFORMERELECTRICAL CHARACTERISTICS
ILJIN Transformer9
Manufacturing Progress
Core Slitting / 100m/minSlitting Machine
Core Slitting / with : 100~1000mmLength : 5000mm
Auto Core Cutting M/CCoil Winding(Vertical Winding)Control Weight : 20ton
Coil Winding M/C
Coil Winding(Horizontal Winding) Control Weight : 15ton
Coil Winding M/CVacuum Drying / Full automaticcontrol system
Vacuum Vapor Drying PlantVacuum Drying / HeatingAutoclave Size : L10m x W5m x H8m(7.2m)
Vacuum Vapor Drying Plant(Autoclave)
Erection Parts / Main : 200tonSub : 20ton
Overhead CraneOil purification & Vacuum Filling/ 10000L/Hr
Oil Vacuum PurifierBIL 2000kVTest Equipment
5075
100150200
(200)5)
300(400)5)
500(600)5)
(700)5)
750100015002000250030003500400045005000600070008000900010000
22.9kV-6.6 or 3.3kV
Io
22.9kV-Low Volt1)
Io
6.6 or 3.3kV-Low Volt1)
Io
Low Volt-Low Volt1)Item
Io4)3)2)
97.3597.4597.6597.6597.7597.8597.8598.0598.05
2.42.31.91.91.91.81.81.61.6
7.57.07.07.06.56.06.05.55.0
97.4597.5597.6697.6597.7597.8597.9598.0598.2098.3098.3098.3098.4098.5098.6098.6098.70
2.02.01.81.71.71.61.61.51.51.51.51.51.51.41.41.41.3
6.56.56.56.06.05.55.55.05.05.04.54.53.53.03.03.03.0
97.2597.3597.6597.6597.8597.9597.9598.0598.2598.2598.2598.3598.4598.4598.5598.5598.65
2.32.21.91.91.81.81.81.61.61.61.51.51.51.41.41.41.3
6.56.56.56.56.06.06.05.55.04.54.03.53.03.03.03.03.0
97.6597.6597.8597.9598.1098.2098.3098.3098.3098.4098.5098.6098.7098.8098.9098.9098.9098.9599.0099.1099.1099.1099.1099.20
1.91.91.81.81.81.61.61.61.51.51.51.41.41.21.21.21.11.11.11.11.11.11.11.1
6.56.56.06.06.05.55.05.04.53.53.53.03.03.03.03.02.82.82.82.82.82.52.52.0
Capa-city(kVA)
5075100150200
(200)5)
300(400)5)
500(600)5)
75010001500
22.9kV-6.6 or 3.3kV
Io
22.9kV-Low Volt1)
Note) 1) Low Volt : Nominal Voltage of 1.1kV and below 2) : Efficiency 3) : Voltage Variation rate 4) Io : Exciting Current 5) ( ) : Non-standard
Note) 1) Low Volt : Nominal Voltage of 1.1kV and below 2) : Efficiency 3) : Voltage Variation rate 4) Io : Exciting Current 5) ( ) : Non-standard
Io
6.6 or 3.3kV-Low Volt1)
Io
Low Volt-Low Volt1)Item
Io4)3)2)
97.6597.7597.85
3.02.52.0
6.05.55.0
98.2598.2598.2598.2598.2598.3598.3598.4598.45
1.51.51.51.51.51.41.41.31.3
1.61.51.55.55.55.04.54.54.5
97.7597.8597.9598.0598.0598.1598.2598.35
1.91.91.61.61.61.51.51.5
2.02.56.06.05.55.54.54.5
97.8597.8597.9598.0598.1598.2598.4598.4598.5598.5598.6598.75
1.81.81.61.61.51.51.41.41.41.31.31.2
3.03.55.04.54.54.54.04.04.03.53.53.0
Capa-city(kVA)
Three Phase
Single Phase
ILJINElectricCompanyTransformer
ILJIN Transformer 12
Drawing
TRANSFORMERULTRA HIGH VOLTAGE TRANSFORMER
345kV Class
ILJIN Transformer11
Primary bushing
Local control panel
Radiator
A B H
100/133.3/166.7 7100 6520 7800 39000 175000
Dimensions(mm) Insulating Oil( )
Weight(kg)
Capacity(MVA)
Outline Dimensions No. Name of parts
H.V Bushing
Name Plate
Oil Temperature Indicator
Winding Temperature Indicator
Alchole Temperature
Ladder
Sudden Pressure Relay
Cooling Fan
1 -
2 -
3 -
4 -
5 -
6 -
7 -
8 -
Middle Voltage Bushing
Neutural Bushing
Pressure Relief Device
Oil Level Gauge (ROD type)
Dehydrating Breather for Main
L.V Bushing
Oil Pump
Local Control Panel
9 -
10 -
11 -
12 -
13 -
14 -
15 -
16 -
Drain Valve
Sampling Valve
Grounding Pad
Pulling eye
Jack Boss
Oil Level Gauge for O.L.T.C
Conservator for O.L.T.C
Filling Hole for O.L.T.C
17 -
18 -
19 -
20 -
21 -
22 -
23 -
24 -
Oil Level Gauge for Main
Conservator for Main
Protective Relay for O.L.T.C
O.L.T.C
Oil Flow Indecator
Filtering Valve for Main
Filling Hole for Conservator
Filling Hole for Main
25 -
26 -
27 -
28 -
29 -
30 -
31 -
32 -
Radiator
Radiator Valve
Lifting Hook for Main Tank
Dehydrating Breather for O.L.T.C
N2 Gas Valve
Oil Fiter Unit
Motor Drive Unit
33 -
34 -
35 -
36 -
37 -
38 -
39 -
Cooling Type : ONAN, ONAF, OFWF, OFAF
A B H
ILJINElectricCompanyTransformer
ILJIN Transformer 14
Drawing
TRANSFORMERULTRA HIGH VOLTAGE TRANSFORMER
230kV Class
ILJIN Transformer13
Conservator
Cooling Fan
Local control panel
H.V Bushing
Lifting Lug for Cover
Maintenance Hole
Ladder
L.V Bushing
Supporting Bracket ror
L.V Lightning Arrester
Supporting Bracket ror
H.V Lightning Arrester
1 -
2 -
3 -
4 -
5 -
6 -
7 -
Protective Relay for O.L.T.C
Conservator for O.L.T.C
Oil Level Gauge for O.L.T.C
O.L.T.C
Press Relief Device for Main
T.V Bushing
H.V.N Bushing
Lifting Lug for Main
Buchholtz Relay for Main
8 -
9 -
10 -
11 -
12 -
13 -
14 -
15 -
16 -
Conservator for Main (Air Seal Cell Type)
Oil Level Gauge for Main
Drain Valve for Conservator
Radiator
Cooling Fan
Supporting Bracket for Radiator
Drain Valve with Sampling Device
Base
Grounding Pad
17 -
18 -
19 -
20 -
21 -
22 -
23 -
24 -
25 -
Jack Boss
Breather for Main
Local Panel
ILJIN Mark
Sudden Pressure Relay
Filtering Valve with Sampling Device
Name Plate
Breather for O.L.T.C
Drain Valve for OLTC
26 -
27 -
28 -
29 -
30 -
31 -
32 -
33 -
34 -
Oil Thermometer
Winding Thermometer
Motor Unit
Gas & Water in Oil Monitor
Gas Release Device
Radiator Valve
Bushing for Core Grounding
35 -
36 -
37 -
38 -
39 -
40 -
41 -
Outline Dimensions No. Name of parts
60
75
125
240
8100 6300 7450 45000 128500
8850 7000 7300 49500 145000
9600 5900 8550 54700 219000
12950 7850 7350 85500 289000
Dimensions(mm) Insulating Oil( )
Weight(kg)
Capacity(MVA)
Cooling Type : ONAN, ONAF, OFWF, OFAF
ILJINElectricCompanyTransformer
ILJIN Transformer 16
Drawing
TRANSFORMERULTRA HIGH VOLTAGE TRANSFORMER
154kV Class
ILJIN Transformer15
OLTC Conservator
Motor drive unit
Outline Dimensions No. Name of parts
H.V Arrester
H.V Bushing
Filtering Valve
Lifting hook For Cover
Ladder
L.V Bushing
L.V Busduct Fange
1 -
2 -
3 -
4 -
5 -
6 -
7 -
Conservator for O.L.T.C
Oil Level Gauge for O.L.T.C
Protective Relay for O.L.T.C
Oil Filter Unit For O.L.T.C
O.L.T.C
Pressure Relief Device
H.V.N Bushing
8 -
9 -
10 -
11 -
12 -
13 -
14 -
Buchholz Relay
Conservator for Main
Oil Level Gauge for Main
Jack Boss
Base
Sudden Pressure Relay
Maintenence Hole
15 -
16 -
17 -
18 -
19 -
20 -
21 -
Local Panel
Lifting hook For Main Tank
Radiator
Cooling Fan
Name Plate
Dehydrating Breather for O.L.T.C
Dehydrating Breather for Main
22 -
23 -
24 -
25 -
26 -
27 -
28 -
Oil Temperature Indicator
Winding Temperature Indicator
Grounding Pad
Motor Drive Unit
Drain & Sampling Valve
29 -
30 -
31 -
32 -
33 -
A B H
10
15
25
35
40
60
100
120
170
6100 5300 5500 15300 44500
6500 4500 5350 13500 46000
6950 5400 5400 17500 51500
7000 5500 5800 20000 66000
7300 5800 6100 23000 79500
7650 7000 5900 44000 145000
8300 6800 6600 43000 140000
6650 6200 6800 33500 138000
9050 6950 6200 41000 173000
Dimensions(mm) Insulating Oil( )
Weight(kg)
Capacity(MVA)
Cooling Type : ONAN, ONAF, OFWF, OFAF
Capacity(KVA)
ILJINElectricCompanyTransformer
ILJIN Transformer 18
TRANSFORMERMEDIUM SIZE TRANSFORMER
66kV Class
ILJIN Transformer17
Primary Bushing
OLTC Conservator
Outline Dimensions No. Name of parts
Support for H.V Arrester
H.V Bushing
Buchholtz Relay
Pressure Relief Device
M.V Bushing
1 -
2 -
3 -
4 -
5 -
N.L.T.C Handle
Maintenance Hole
Lifting Hook for Cover
Lifting Hook for Main Tank
L.V Bushing
6 -
7 -
8 -
9 -
10 -
Ladder
Conservator
Oil Level Gauge
Jack Boss
Drain Valve
11 -
12 -
13 -
14 -
15 -
Grounding Pad
Foundation Bolt
Base
L.V Cable Box
Radiator
16 -
17 -
18 -
19 -
20 -
Dehydrating Breather
Filtering Valve
Oil Temperature Indicator
Name Plate
Terminal Box
Filling Hole
21 -
22 -
23 -
24 -
25 -
26 -
A B H
2000
3500
5000
7500
10000
15000
2850 2600 3450 3900 9500
2950 2900 3500 4300 12000
3200 3300 3700 5000 15000
3500 3700 3950 6300 19000
3850 4200 4300 7700 24000
4300 4900 4600 9900 31500
Dimensions(mm) Insulating Oil( )
Weight(kg)
Drawing
Cooling Type : ONAN, ONAF, OFWF, OFAF
ILJIN Transformer 20ILJIN Transformer19
ILJINElectricCompanyTransformer
Drawing
TRANSFORMERMEDIUM SIZE TRANSFORMER
22.9kV Class
Primary bushing
Local control panel
Cooling Fan
Outline Dimensions No. Name of parts
H.V.N Bushing
H.V Bushing
Dehydrating Breather
Base
Ladder
1 -
2 -
3 -
4 -
5 -
Lifting Hook for Cover
Buchholz Relay
N.L.T.C Handle
Pressure Relief Device
L.V Bushing
6 -
7 -
8 -
9 -
10 -
Conservator
Oil Level Gauge
ILJIN Mark
Filtering Valve
Lifting Hook for Main Tank
11 -
12 -
13 -
14 -
15 -
Radiator
Oil Temperature Indicator
Name Plate
Winding Temperature Indicator
Radiator Valve
16 -
17 -
18 -
19 -
20 -
Jack Boss
Local Control Panel
Drain Valve
Sampling Valve
Grounding Pad
Cooling Fan
21 -
22 -
23 -
24 -
25 -
26 -
1500
2000
2500
3000
5000
7500
10000
15000
1900 2300 2100 1350 4700
2000 2400 2300 1400 5000
2250 2650 2600 2000 7000
2400 2800 2700 2100 8000
2650 3500 2900 2900 11000
2900 3850 3100 3800 15000
3200 4200 3500 5500 20000
3600 4650 4000 7500 28000
22.9kV ~
6.6/3.3kV
1500
2000
2500
3000
5000
7500
10000
15000
1900 2350 2100 1400 4500
2000 2450 2300 1450 5200
2300 2900 2600 2200 7100
2500 3300 2800 2650 8200
1900 2400 2000 1400 4500
2100 2500 2300 1450 5000
2300 3000 2500 2200 7000
2500 3450 2700 2600 8100
InsulatingOil ( )
Weight(kg)
22.9kV~
Low Voltage
3.3/3.3kV~
Low Voltage
VoltageA B H
Dimensions(mm)Capacity(KVA)
InsulatingOil ( )
Weight(kg)Voltage
A B H
Dimensions(mm)Capacity(KVA)
Cooling Type : ONAN, ONAF, OFWF, OFAF
ILJIN Transformer 22ILJIN Transformer21
ILJINElectricCompanyTransformer
TRANSFORMERN2 GAS SEALED TYPE TRANSFORMER
Local control panel
Radiator & Cooling Fan
3P-42/56/70
3P-15/20/25
3P-60/80/100
3P-20MVA
3P-20/25
3P-15/20/25
3P-5/6.25
1P-8.2/70
1P-6.6/8.3
1P-5/6.251P-
3.3/4.16
154kV
154kV
115kV
115kV
66kV
66kV
33kV
33kV
33kV
33kV
33kV
7150 5450 5600 29500 111000
6000 4750 5150 22000 75500
7400 5500 6900 36500 137000
4400 3600 4900 14500 5600
6000 4200 4400 15300 58500
5150 3400 4900 15300 55000
3250 3000 4000 8000 26000
2300 2750 3550 3400 17500
2250 2500 3550 2650 15200
2100 2400 3550 2150 12000
1850 2000 3400 2000 9700
Insulating Oil( )
Weight(kg)Voltage
A B H
Dimensions(mm)Capacity (MVA)
Outline Dimensions No. Name of parts
Radiator
Maintenance Hole
H.V Bushing
L.V Bushing
Lifting Lug for Cover
Bushing for Core Grounding
1 -
2 -
3 -
4 -
5 -
6 -
Valve for Vacuum
Box for Core Grounding Bushing
Oil Level Gauge
Pressure Relief Device
Pressure Gauge
Upper Filter Valve
7 -
8 -
9 -
10 -
11 -
12 -
Name Plate
Oil Temperature Indicator
Grounding Pad
Base
Jacking Pad with Hauling Hole
Terminal Box
13 -
14 -
15 -
16 -
17 -
18 -
N2 Gas Equipment Control Box
Lower Filter / Drain Valve
Sudden Pressure Relay for Main Tank
Gas Sampling Valve
Lifting Hook
No Load Tap Changer
Radiator Valve
19 -
20 -
21 -
22 -
23 -
24 -
25 -
DrawingN2 Gas Class
Cooling Type : ONAN, ONAF, OFWF, OFAF
ILJIN Transformer 24ILJIN Transformer23
ILJINElectricCompanyTransformer
TRANSFORMERFURNACE TRANSFORMER
Furnace Transformer
Cu bushing
Cooler
Outline Dimensions No. Name of parts
Ladder
H.V Bushing
Unit Cooler
Oil Pump
Pressure Relief Device
Protective Relay for O.L.T.C
1 -
2 -
3 -
4 -
5 -
6 -
Conservator for O.L.T.C
Oil Level Gauge for O.L.T.C
O.L.T.C
Oil Level Gauge for Main
Conservator for Main
L.V Bushing
7 -
8 -
9 -
10 -
11 -
12 -
Buchholz Relay
Filtering Valve
Maintenance Hole
Lifting Hook for Main Tank
Base
Grounding Pad
13 -
14 -
15 -
16 -
17 -
18 -
Drain Valve
Jack Boss
Control Panel
Sudden Pressure Relay
Dehydrating Breather for Main
Name Plate
19 -
20 -
21 -
22 -
23 -
24 -
Dehydrating Breather for O.L.T.C
Oil Filter Unit for O.L.T.C
Oil Temperature Indicator
Winding Temperature Indicator
Pulling eye
Motor Drive Unit for O.L.T.C
Oil Flow Indecator
25 -
26 -
27 -
28 -
29 -
30 -
31 -
Number of phase : Three phases or Single phase
Cooling Type : ONAN, ONAF, OFWF, OFAF, etc
Capacity : 100 ~ 100,000kVA
Primary Voltage : Low Voltage ~ 66kV
Secondary Voltage : Low Voltage as Customer s Requirements
Connection : Primary ---- or Y
Secondary or OPEN , /Y
Tap Changer : NLTC or OLTC as Customer s Requirements
Drawing
ILJIN Transformer 26ILJIN Transformer25
ILJINElectricCompanyTransformer
Drawing
TRANSFORMERSCOTT TRANSFORMER
Scott Transformer
bushing
Conservator
Outline Dimensions No. Name of parts
Radiator
H.V Bushing
Filtering Valve
FAN / MOTOR
H.V.N Arreester
H.V.N Bushing
Local Panel
1 -
2 -
3 -
4 -
5 -
6 -
7 -
Conservator for Mian
Oil Level Gauge for Main
Conservator for O.L.T.C
Oil Level Gauge for O.L.T.C
OIL FILTER UNIT
O.L.T.C
L.V Bushing
8 -
9 -
10 -
11 -
12 -
13 -
14 -
L.V Arrester
Ladder
Pressure Relief Device
Lifting Hook for Cover
Buchholz Relay
Protective Relay for OLTC
Dehydrating Breather for OLTC
15 -
16 -
17 -
18 -
19 -
20 -
21 -
Dehydrating Breather for Main
Lifting Lug
Jack Boss
Drain & Sampling Valve
L.V Surge Counter
Motor Drive Unit
22 -
23 -
24 -
25 -
26 -
27 -
Grounding Pad
Winding Temperature Indicator
Oil Temperature Indicator
H.V.N Surge Counter
Sudden Pressure Relay
Name Plate
28 -
29 -
30 -
31 -
32 -
33 -
The Scott Transformer is designed and manufactured using advanced technology based on Iljin
Electric Company’s long history of experience and accumulated technology.
Main application is the subway power supply achieving single phase from three phases.
1.Rated Capacity : 30/40, 45/60MVA
2. Tap Changer : OLTC
3. Cooling Type : ONAN, ONAF
4. Primaty Voltage : 154kV
5. Secondary Voltage : 55kV
6. Connection : Primary ---------T
Secondary ----- L
ILJIN Transformer 28ILJIN Transformer27
ILJINElectricCompanyTransformer
TRANSFORMERLESS FLAMMABLE POWER TRANSFORMER
Less Flammable Power Transformer
Conservator
Cooler
Drawing
In comparison with the power Transformer, the Less Flammable power Transformer can reduce the
possibility of fire accidents by using less flammable insulation oil. Iljin Electric Company
manufactures Less Flammable power Transformers by suitable designs based on simulation
systems, a technology acquired through long experiences and accumulated technology. Iljin has
also acquired KEPCO’s development & testing certification.
Using Less Flammable power Transformers can guarantee safety in high power spending facilities
such as urban substations.
1. Roted Capacity : 2,000~90,000kVA
2. Rated Voltage : 154kV~22.9kV
3. Rated Frequency : 60Hz or 50Hz
4. Tap Voltage Range : 20%(NLTC) or OLTC Type
Outline Dimensions No. Name of parts
L.V Arrester
Surge Counter
L.V.N Bushing
L.V Bushing
Bushing for Stablizing Winding
H.V Arrester
H.V.N Bushing
1 -
2 -
3 -
4 -
5 -
6 -
7 -
O.L.T.C
Local Control Panel
H.V Bushing
Pressure Relief Device
OLTC Protective Relay for OLTC
Oil Level Gauge
Conservator for Main
8 -
9 -
10 -
11 -
12 -
13 -
14 -
ILJIN Name Plate
OLTC Conservator
OLTC Oil Level Indicator
Lifting Hook
Dehydrating Breather for main tank
Ladder
OFWF Radiator
15 -
16 -
17 -
18 -
19 -
20 -
21 -
OFWF Radiator (stand-by)
Oil Pump
Motor Drive Unit
OLTC Filter
Drain and Sampling Valve
Gas Detective Relay
Sudden Pressure Relay
22 -
23 -
24 -
25 -
26 -
27 -
28 -
Name Plate (for single phase)
Name Plate(for three phases)
Local Control Panel
Winding Temperature Indicator
Oil Temperature Indicator
Oil Flow Indicator
Grounding Pad
29 -
30 -
31 -
32 -
33 -
34 -
35 -
ILJINElectricCompanyTransformer
ILJIN Transformer 30
TRANSFORMERACCESSORIES
ILJIN Transformer29
Bushing
Standard Accessories
Single Type : Applied for System with Voltage of 30KV and below
Condenser Type : Applied for System with Voltage of 46KV and above
Specification
Temperature Indicator
Oil Level Gauge
Pressure Relief Device
NLTC
Breather
Drain Valve
Hand Hole
Lifting Lug
Earthing Terminal
Radiator Valve
Paint
Rod Type
Dial Type
Rod Type
Dial Type
2500kVA ~
50~750kVA
50~750kVA
1,000~1,500kVA
1,000kVA
2,000kV~
1,500kVA
Enamel Paint or Customer s SpecificatioonSetting for delta Transformer Setting for star Transformer
Linear off- loadtap changer
Single-bridging off- load tap changer
Double-bridgingoff- load tapchanger
Tap can be adjusted from outside of the Tank. Various types are produced according to voltage and capacity.
No Load Tap Changer
High Voltage Tap Changer and Circuit Diagran
Special High Voltage Tap Changer Circuit Diagram
Name PlateBushing
ILJINElectricCompanyTransformer
ILJIN Transformer 32
TRANSFORMERACCESSORIES
ILJIN Transformer31
This is applied for Continuous Voltage Change or Constant Voltage regardless of Input Voltage. Various types areproduced according to voltage and capacity. To be suitable for any operating condition, Motor Operating Device issupplied with both the manual and automatic operating method.
On Load Tap Changer
40
60
80
100
1200
20
Used for temperature indication of insulation oil and also equipped with Alarm and Trip Contact when required.
Oil Temperature Indicator
Used for temperature indication of Winding heated by the Bushing Current Transformer and Variable Resistance.Equipped with Alarm and Trip Contact when required.
Winding Temperature Indicator
ILJINElectricCompanyTransformer
ILJIN Transformer 34
TRANSFORMERACCESSORIES
ILJIN Transformer33
10.2
4(26
0)
0.63(16)10.31(262)
6 EQUALLY SPACEDLUGS 0N 9.25(235) DIA B.C
5.31
(135
)
1.77
(45)
0.47
(12)
1.02
MA
X.(
26)
RESET ARM
Used for indication of Oil level in Tank and Conservator. Panel Type for medium capacity and Magnetic Dial Typefor large capacity are equipped.
Oil Level Guage
This is used for relieving abnormal pressure from inside the Tank and can be equipped with Trip Contact whenrequired.
Pressure Relief Device
GAS RELEASE COCK
TERMINAL BOX
INSPECTION WINDOW
160
230
185
HOLE TAPPED CONDUIT
CHECKING ALARM SWITCH
CHECKINGBUTTON
160
51 110
140
6- 11
This is installed at mid connection pipe between Transformer and Conservator. In case of Gas Generation orchange in Flow Velocity due to internal abnormal condition, Buzzer is operated to give Alarm or Trip Signal.
Buchholtz Relay
This is a Preventing Device against Oil Deterioration by absorbing Penetrating Moisture from outside and consistsGlass Tube for Silicagel and Tube.
Dehydrating Breather
TRANSFORMEROIL PRESERVATION SYSTEM
ILJIN Transformer35
N2 Gas Sealed Type
N2 Gas is sealed in expansion Tank located at upper
and side part of Tank.
No penetration of Moisture and OxyzenRefilling is required when leakage happened
Option in Order
Air Seal Cell Type
Having Nitril Rubber Bag inside the Conservator,
Insulating Oil is completely isolated from the air
outside.
No pressure Sealing type
It is difficult to replace at the spot when the rubber
bag is damaged
More than 5MVA in order
Conservator Type
Conservator is installed at upper part of Tank with
Dehydrating Breather.
Easy for Maintenance
TRANSFORMERSPECIAL SPECIFICATIONS & PACKING
ONAN
Cooling Type
ONAN
ONAF
OFAF
Equipment
Panel Type Radiator
Panel Type Radiator, Cooling Fan, Control Panel
Unit Cooler : Cooling Pipe + Cooling Fan + Pump, Control Panel
Insulation Oil, when heated by the heat of the Core and Coil, moves up naturally into the
radiator through the upper part of the Tank. When it is cooled it moves back down
through the radiator and into the lower part of the Tank. This type is generally used for
easy maintenance.
Panel Type Radiator. This radiator is fabricated with two overlaid steel plates which arespot-welded at end and mid point and cut in preset size and expanded to form wantedshape. This construction have features of less oil contents, high mechanical strength andvacuum resistance.
ONAF
This uses the Cooling Fan attached to the Panel Type Radiator of ONAN, increasing
the cooling effect. This is also applied to double rating which ONAN is used for light
duty and ONAF is used for heavy duty. In this case, ONAF has output 120~140%
higher than ONAN s.
OFAF
This uses Unit Cooler which is constituted with Special Cooling Pipe, Oil Pump and Cooling Fan.
To increase cooling effect, Directed Oil Flow method with Zig-zag oil flow can be used when required.
OFWF & OFAF also can be suplied to overcome any restrictions at site
ILJIN Transformer 36
Radiator RadiatorTank
Radiator
Fan
Fan
Oil Pump
Fan
RadiatorTank
TankUnit Cooler
CoreandCoil
CoreandCoil
CoreandCoil
ILJINElectricCompanyTransformer
ILJIN Transformer 38
TRANSFORMERMAINTENANCE
ILJIN Transformer37
Daily Check-up
Main Tank
Bushing
Dehydration
Breather
Pressure
Relief Device
N2 Gas
Equipment
1. Temperature
2. Oil Level
3. Oil Leakage
4. Abnormal sound
vibration
1. Oil Leakage
2. Contamination of
insulator
1. Checking
Dehydration
2. Check cylinder
OiloN2 gas leakage
Gas pressure and
temperature
1) Oil temperature Indicator
2) Winding temperature indicator
3) Defects of temperature indicator
1) Oil level indicator2) Defects of Oil level indicatorCompare the relationship between oil temperatureand oil level with the graph
Checking bushing flange, valves, the radiator, the
gasket sealing of oil pipes and welding.
Comparing with normal sound, check if there is any
unusual sound or vibration.
Check the oil level and leakage
Check the adhesion of sodium chloride or cracksthrough checking the appearance.
Check the moisture level of dehydration material (ifthe blue color of the material turns to light pink, thatindicates dehydration)
Check the oil amount of cylinder
The pressure plate is a cover that protects againstexternal damage. Check the pressure plate to findN2 gas or oil leakage
Gas leakage can be monitored by pressure and
temperature graph.
In the case that the relationship between the temperature and
level of oil is contrary, following check-up is necessary.
Leakage from the main tank
Malfunction of Oil Temperature Indicator
Malfunction of temperature indicator
When there is internal defect of Oil temperature gauge and Oil
level indicator, they need to be replaced with new ones.
Tight the bolts of gaskets if the leakage is from gasket sealing, If
the leakage doesn t stop, replacement of the gasket is necessary.
In the case of leakage on welded parts, please contact us.
If abnormal sound or too much vibration is caused by loosened
attachment, tight the related parts or contact us.
In the case of oil leakage or if the oil level is lowered, contact us.
Clean-up when there are foreign materials on insulator.
Contact us, when crack or breakage is found.
When the color is changed, it needs to be dried out or replaced.
If the oil amount is not sufficient, fill the oil after clean up.
In the case of N2 gas or oil leakage due to natural depletion of
pressure plate, it needs to be replaced.
In the case of decreasing pressure, gasket sealing or pressure
plate of pressure relief device needs to be checked.
In the case of low pressure, supplement the N2 gas.
This is the check-up list for a user. The check-up period can be decided depending on the importance and operating time of the machinery. The
check-up should be carried on only in uninterrupted condition. Information should be recorded on the check-up sheet including the date of check-
up, climate, temperature, name of machinery being checked-up, serial number (on the name plate), and inspector s information.
Items List Methods Proper measures
Periodic Checking
Parts
Bushing
1 year
1 year
1 year
1 year
1 year
2~3
year
1 year
Appearance inspectionContamination on the panel.Internal dew condensation
Check the temperature indicator
Check switches
Appearance inspection
Movement testMovement of float and indicatorBehavior of Micro Switch
Appearance inspectionLeakageGas inside of inspection windowPaint condition
Behavior test of contact Check ON-OFF condition with the test button.
Appearance inspectionCrack or distortion of pressure plateOil or gas leakage
Movement test at the contact pointOpening the cover of pressure plate, Check ON-OFF at the contact point.
Appearance inspectionContamination on the panel or dew condensation
Pressure indicationCheck 0 point under the atmospheric pressure.
Relay alarm testStart and stop test of a cooling fanInsulation resistance test of wiresThorough eye inspection of wires
1 Crack on insulatorDamageOil leakageOver heatingOccurrence of tarnish
1. Dial temperature indicator
2. Dial oil level indicator
3. Buchholtz relay
4. Pressure relief device
5. Pressure indicator(N2 gas filled type)
6. Check-up on controlprotection circuit
AppearanceInspection
In the case of contamination on panel orinternal dew condensation, it needs to bereplaced.
Same as Dial temperature indicator Make sure the float and the indicator movesmoothly and turns on at the contact withinthe range of 0~5%
The gasket needs to be replaced if oil leaksfrom the gasket sealing.The relay needs to be replaced if the relay atthe contact point (ON-OFF) is not workingproperly.
The pressure plate needs to be replaced,when there is leakage or crack on it.Micro Switch needs to be replaced when thecondition of contact point (ON-OFF) is poor.
In the case of contamination on panel orinternal dew condensation, the indicatorneeds to be replaced.The indicator also needs to be replaced whenZero point adjustment is not working.
There should be no defects.Insulation resistance should be more than500V megger and 2M
There should be no defects.The gasket needs to be replaced if oil leaksfrom the gasket sealing.Insulator needs to be replaced when cracked.
This is the checklist that Manufacturer s inspector (user s witness inspection when necessary) performs depending on the importance and
operating time of the machinery (Check-up period listed on the table below). The procedure should be carried on only in blackout condition. It is
recommended to inspect all the transformers or related transformers in the premise on a blackout day for the periodic check-up.
Category Items Procedure Criterion and proper measuresCheckingperiod
ILJINElectricCompanyTransformer
ILJIN Transformer 40
TRANSFORMERMaintenance
ILJIN Transformer39
Maintenance of Insulation Oil
The main cause of depletion of insulation oil is oxidation. The insulation oil gets oxidized due to the contact with the air. The oxidation causestemperature rise of a transformer, catalysis of metal, effluent of insulation varnish. Moreover, due to chemical reaction such as decomposition andpolymerization, it generates sludge, which settles on the bottom of the tank and interferes cooling that makes temperature rise. The increase of thetemperature leads T.A.N to increase, and volume resistivity and insulation destruction voltage to decrease.
Criterion for T.A.N Moisture
Category
New oil
Transformer oil of over 66kV
Transformer oil of under 33kV
Caution
Defect
Standard (mgKOH/g)
Under 0.02
Ok if under 0.2
OK if under 0.3
0.3 ~ 0.5
Over 0.5
Condition
OK
Caution
Defect
Standard (ppm)
Under 40
40 ~ 50
Over 50
Remark
When abnormality is found,
not only the replacement of
insulation oil but also
reconstruction of core and coil
(internal structure) is required.
Criterion of Insulation Destruction Voltage
Gas in oil
Type of Abnormality and Gas Occurred
Category
Transformers rated over
66kV (No direct contact
with other machinery)
Otherwise
Condition
Ok
Cautious
Poor
Ok
Cautious
Poor
Standard (kV/205mm)Over 35
30~35
Under 30
Over 30
20~30
Under 20
Type
Overheat of insulation oil
Overheat of sunken solid insulation material
Discharge during insulation
Discharge of sunken solid insulation material
Main gas occurredHydrogen(H2), Methane(CH4), Ethylene(C2H4), Ethane(C2H6), Propane(C3H8), Propylene(C3H6)
Carbon Monoxide(CO), Carbon dioxide(CO2), Hydrogen(H2), Methane(CH4), Ethylene(C2H4), Ethane(C2H6), Propane(C3H8), Propylene(C3H6)
Hydrogen(H2), Methane(CH4), Ethylene(C2H4), Acetylene(C2H2), Propylene(C3H6)
Carbon Monoxide(CO), Carbon dioxide(CO2), Hydrogen(H2), Methane(CH4), Acetylene(C2H2), Ethylene(C2H4), Propylene(C3H6)
Category
TCG and Amountof Each Gas Defect
TCG IncreaseTendancy
CO2+CO Amount
Condition
Cautious
Poor
Cautious
Poor
Cautious
Poor
TCG
1000
700
TCG
2000
1400
H2
400
400
H2
800
800
CH4
200
150
CH4
400
300
C2H6
150
150
C2H6
300
300
C2H4
300
200
C2H4
600
400
CO
300
300
CO
600
600
Gas Amount (ppm)
Gas Amount (ppm)
Capacity of TR TCG Increase Rate / year
350
250
TCG Increase Rate / month
100
70
In the case of Opening type (use dehydration breather)
Capacity of TR
Capacity of TR
Under 10MVA
Over 10MVA
Capacity of TR
Under 10MVA
Over 10MVA
Under 10MVA
Over 10MVA
Under 10MVA
Over 10MVA
0.42~1.7 /g
Over 1.7 /g
Standard
OK: continuously usable Cautious: reproduction or replacement if possible Poor: immediate reproduction or replacement
OK: continuously usable Cautious: reproduction or replacement if possible Poor: immediate reproduction or replacement
Maintenance of Accessory
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
15
10
15
15
15
15
15~20
3
15~20
15~20
10
15
3
15
15
15
15
15
20
*15
*15
*10/20
15
5
Including RTD and dehydrating breather
After 3 years, all units need to be replaced if
abnormal sound occurs from one unit
After 10 years, all units need to be replaced if
abnormal sound occurs from one unit
After 3 years, all units need to be replaced if
abnormal sound occurs from one unit
Thorough inspection and maintenance after disassembly on a 10year basis. Replacement on a 20 year basis
Gasket
Rubber bag for the conservator
Gauges and relays
Valves
Radiator
Air forced unitcooler
Water forced unit cooler
Oil Pump
Cooling Fan
BCT
Terminal box, Terminal board
Wires
Small Screws
Single Bushing
Condensor Bushing
OLTC Handle
OLTC
Motor Drive Unit
Oil Filter Unit
NBR
Rubber Cell
Main body
Bearing for the Fan
Main body
Bearing for the pump
Main body
Bearing for the Fan
Main body
Bearing for the pump
The items needs to be replaced as follows when there is a problem.
NO Item Replacement period Remark
Footnote (1) The replacement period above varies depending on condition and environment of operation. It is limited to a condition that the Daily and
Periodic check-up has been carried out constantly as advised.
(2) Gaskets of parts needs to be replaced on a 10-year basis.
(3) The replacement time of OLTC and a motor drive unit can be decided either on the number of operation or operation years, whichever comes
first. However, specific application base on the number of operation should be performed according to the instruction manual.
(1)
(2)
(3)
(3)
ILJINElectricCompanyTransformer
ILJIN Transformer 42
TRANSFORMERPERFORMANCE RECORDS
ILJIN Transformer41
Standard1 , 15/20MVA, 154/23KV 2000
1 166.7MVA 345/ 3/161/ 3/23KV 2000
3 , 45/50MVA, 154/22.9KV 2001
3 , 15MVA, 22.9/3.3KV 2001
1 , 15/20MVA, 154/23KV 2002
1 , 15/20MVA, 154/23KV 2002
1 166.7MVA, 345/161/23KV 2003
1 345/161/23KV 2003
3 , 30/40MVA 154/6.6KV 2004
3 , 37.6/49MVA, 158KV/13.8KV 2004
3 , 15/20MVA, 154/6.6KV 2004
3 , 100/133.3/166.7MVA, 345/161/23kV 2004
3 , 100/120MVA, 154/22.9KV 2005
3 , 9/12MVA, 154/16kV 2005
3 , 15/20MVA, 154/23kV 2005
3 , 25/30MVA 154/6.6KV 2006
3 , 30/40MVA, 154/135.67KV 2006
3 , 30/40MVA, 154/6.6KV 2006
3 , 15/20MVA, 154/23kV 2006
3 , 100/133.3/166.7MVA, 345/161/23kV 2007
3 , 130/160MVA, 154/22kV 2007
3 , 90/116MVA 154/10.2KV 2008
3 , 25MVA 22.9KV/148V 2008
3 , 60/70MVA 154kVA 2008
3 , 30/45MVA, 154KV/22.9KV 2008
3 , 40MVA 22kV/210V 2008
3 , 130/150MVA, 154/22.9KV 2008
3 ,, 25/30MVA, 154KV/6.6KV 2008
3 , 30/35MVA 33/6.6KV 2008
3 , 200MVA 154/33kV 2008
3 , 27MVA/30MVA 33kV/6.6kV 2008
3 , 30/40MVA, 154KV/22.9KV 2008
3 , 60MVA 33/11kV 2008
3 , 47MVA 33/6.9kV 2008
3 , 28MVA 22/6.9KV 2008
3 , 30/40MVA 154/22.9KV 2009
3 , 60MVA 154KV/22KV 2009
3 , 30/40MVA 154KV/22.9KV 2009
3 , 23/30.5MVA 22.9/6.6KV 2009
3 , 20/26MVA, 154KV/6.9KV 2009
3 , 76/100MVA, 154KV/22.9KV 2009
3 , 70/90MVA 154/11kV 2009
3 , 80/100MVA 154KV/22KV 2009
3 , 70/90MVA 154KV/11KV 2009
3 , 60/70MVA 154kV/11kV 2009
3 , 130/173MVA 154/16.5kV 2009
3 , 20MVA, 22/148V 2003
3 , 25MVA, 22.9KV/160V 2005
3 , 9000kVA, 22900/100V 2005
3 ,10MVA, 22.9kV/100V 2005
KEPCO
KEPCO
ILJIN Copper Foil
Young-Poong
KEPCO
KEPCO
KEPCO
KEPCO
Samsung
Dea-Lim
Seoul Water
KEPCO
POSCO
West Inchon Power Plant
KEPCO
Samsung
Korea Airport
Hwan Young steel
KEPCO
KEPCO
POSCO
Daewoo
Dongil
Dongil
Kumho
Dong-Bu
Hanyoung
Samsung
Hyundai
Dong-Bu
Hyundai Steel
Hanhwa
Hyundai Steel
Hyundai Steel
POSCO
KAIST
POSCO
Kolon
Ssangyoung
Lotte
Lotte
POSCO
POSCO
POSCO
Hyundai Steel
POSCO
Dong-Bu
Dong-Bu
Dongil
Dong-Bu
Category
154-345kV
Korea Overseas Supply Record for Transformer
MYANMAR
KOREA
PHILIPPINES
INDONESIA
USA
TRINIDADPANAMA
CANADA
NIGERIA
KENYATHAILAND
SAUDI
IRAN BANGLADESH
INDIA
Type / Rating Customer Year
EGYPTPAKISTAN