ieee519 says - controltrends · ieee 519 1992 defines a harmonic as, "a sinusoidal component of a...

23
IEEE519 SAYS IEEE519 SAYS IEEE 519 1992 defines a harmonic as, "A sinusoidal component of a periodic wave or quantity having a frequency that is an integral multiple of the fundamental frequency.” Harmonics are a function of the distribution system and the circuit configuration of the distorting load.

Upload: others

Post on 26-Jan-2021

12 views

Category:

Documents


0 download

TRANSCRIPT

  • IEEE519 SAYSIEEE519 SAYSIEEE 519 1992 defines a harmonic as,

    "A sinusoidal component of a periodic

    wave or quantity having a frequency

    that is an integral multiple of the

    fundamental frequency.”

    Harmonics are a function of the

    distribution system and the circuit

    configuration of the distorting load.

  • Definition of HarmonicsDefinition of Harmonics

    • They are AC currents or voltages at integer multiples of the fundamental frequency

    • The fundamental is the lowest frequency in the waveform, generally the repetition frequency

    • They cannot transfer power on the average• Harmonics are present in any non-sinusoidal

    waveform• More rapid changes in the waveform require the

    presence of higher order harmonics

  • Harmonics -- The Main Power Quality Issue for VFD’s

    Harmonics -- The Main Power Quality Issue for VFD’s

    • Where do they come from?• What are Harmonics?• What are the effects of Harmonics? • What are the current standards?• How do you measure Harmonics?• How do you know if there’s a harmonic problem?• How can they be controlled or eliminated?• Common myths and misconceptions• References

  • Sources of HarmonicsSources of Harmonics

    • They arise from non-linear loads in which current is not strictly proportional to voltage

    • Linear loads like resistors, capacitors and inductors do not produce harmonics

    • Since diodes and SCR’s are non-linear, those circuits generate harmonic currents

    • Other equipment which causes harmonics:

    – UPS, rectifiers, transformers, ballasts, welders, arc furnaces, and personal computers

  • Harmonic NoteHarmonic Note

    It is important to remember that harmonic

    phenomena are "periodic" which indicates

    their continuous nature.

    It is the continuous phenomena that is

    addressed in the IEEE guidelines.

  • Harmonic StandardsHarmonic Standards• IEEE-519 1992• Definitions:

    – Voltage total harmonic distortion (VTHD)– Current total harmonic distortion (CTHD)

    • K-Factor• Point of Common Coupling• VTHD Limits, Table 10.2• CTHD Limits, Table 10.3

    – Dilution by linear loads• There are no Susceptibility Limits!

  • THD Definitions from IEEE-519THD Definitions from IEEE-519

    Voltage Total Harmonic Distortion VTHD

    Current Total Harmonic Distortion CTHD

    Sum of squares of amplitudes of all voltage harmonics

    Sum of squares of amplitudes of all current harmonics

    Amplitude of fundamental voltage

    Amplitude of fundamental Current

  • IEEE519 Tables 10.2/3IEEE519 Tables 10.2/3

  • Point of Common CouplingPoint of Common Coupling

    • The point of common coupling is the location in

    the power distribution system where harmonic

    distortion is to be measured, usually where

    harmonic currents flow into a bus which feeds

    other equipment. Its location must be specified!

    • In the absence of a specified location, the POCC

    for current harmonics is the plant-utility interface

  • PCC ExamplePCC Example

  • The Three Phase Diode RectifierThe Three Phase Diode Rectifier

    • The three phase equivalent of the diode rectifier.

    Three phase diode rectifier, line voltage/current

    -700-600-500-400-300-200-100

    0100200300400500600700

    Voltage Current

    Model of Components in Non-Linear Three Phase Circuit

    Figure 11.1

    Figure 11.2

  • Generation of Harmonic Currents

    Generation of Harmonic Currents

  • PWM Power ConversionPWM Power Conversion

  • IEEE519 CommentIEEE519 Comment

    IEEE 519 1992IEEE 519 1992

    DON’T SAY IT UNLESS YOU MEAN IT

  • Harmonics are Site Specific and Dependant Upon:

    Harmonics are Site Specific and Dependant Upon:

    • Distribution transformer’s short circuit capacity

    • Distribution transformer’s impedance

    • Maximum demand load

    a. Linear load

    b. Non-linear load

    • Location of the PCC

  • ThereforeThereforeTo Properly Specify IEEE 519 1992 the following

    information must be known:

  • Examples VoltageExamples Voltage

  • Examples CurrentExamples Current

  • Ways to Decrease HarmonicsWays to Decrease HarmonicsWays to Decrease Harmonics

    • Load Segregation

    • Input Line Reactor

    • 5th Harmonic Filter

    • Active Filter

    • 12- Pulse Drive

    • 18- Pulse Drive

  • Helpful FormulasHelpful Formulas• From IEEE Std. 141-1993: Power is the product of in-

    phase current times the voltage or:

    • P60 = V60 * I60cos θ

    • In the case of harmonics:

    • Ph = Vh * Ihcos θ or S = (Sqrt(P2 + Q2 +D2)){R1]

    • Where P = Real Power, Q = Reactive Power and D = Distortion Power.

    • System losses will be higher due to the harmonic components, than with equivalent 60 kVA.

    • Ph = I2h * Rh

    • (Ohm’s law in harmonic-land)

    True Power Factor Representation - Expanded

    Appa

    rent P

    ower

    (kVA)

    *

    P Real Power (kW)Q

    Rea

    ctiv

    ePo

    wer

    X

    (kVA

    r)D D

    istortio

    n

    Figure 20.1

  • Helpful FormulasHelpful Formulas

    • Current flowing through system impedances (transformers, wire, inductors) create voltage drops at frequency. Therefore, when non-linear loads draw harmonic frequencies, drops at harmonic frequencies add to create voltage distortion.

    E = IR

    EDC = IDC R

    E60 = I60 (R+jXL60)

    E300 = I300 (R+jXL300)

    jXL = 2πfL

    Harmonic Currents Creating Voltage Distortion

    Figure 21.2

  • SUMMARYSUMMARY• The most important thing to remember is that in order to

    utilize the rules of IEEE519 is the full understanding of your power system and equipment.

    • The best way to understand your system is to perform a system analysis using the guidelines of IEEE519 or have a outside consultant do a analysis of your power system.

    • They are several companies that promote special harmonic filters, traps and guards.

  • Reference informationReference information• Many thanks to all the people / companies that have written

    articles pertaining to this subject.

    – IEEE519-1992– TCI– Mirus

    • Please contact us with any questions or if you would like to have a power analysis performed at your plant.