iec standards & power factor correction

Upload: sephorastone

Post on 05-Mar-2016

80 views

Category:

Documents


8 download

DESCRIPTION

ABB training material

TRANSCRIPT

  • ABB Group August 11, 2015 | Slide 1

    Lionel Ng, LPBS - Low Voltage Products

    Welcome To ABB Technical Sharing Session

  • Circuit BreakersStandards Guidelines IEC 60947-2

  • ABB Group August 11, 2015 | Slide 4

    IEC 60947-2Circuit Breaker Standard, for industrial application

    Definitions for MCCBs and ACBs

    Choice criteria based on rated and limit values

    Agenda

  • ABB Group August 11, 2015 | Slide 5

    International Standard IEC 60947

    European Standard EN 60947

    IEC 60947-1 Part 1: General rules

    IEC 60947-2 Part 2: Circuit breakers

    IEC 60947-3 Part 3: Switch disconnectors

    IEC 60947-4-1 Part 4: Contactors

    IEC 60947-5-1 Part 5: Control circuit devices

    IEC 60947-6-1 Part 6: Multifunction devices

    IEC 60947-7-1 Part 7: Auxiliary materials

    Standard for LV apparatus

    IEC 60947 Standard for industrial application

  • ABB Group August 11, 2015 | Slide 6

    A mechanical switching device capable of breaking, carrying and making currents under normal circuit conditions and also making, carrying, for a specified time, and breaking currents under specified abnormal circuit conditions such as those of short-circuit.

    BREAKING Breaking Capacity

    WITHSTAND Short time withstand

    MAKING Making Capacity

    IEC Standard definitions

    Circuit Breaker - IEC 60947-2

  • ABB Group August 11, 2015 | Slide 7

    A mechanical switching device capable of breaking, making and carrying currents under normal circuit conditions but only making and carrying, for a specified time, currents under specified abnormal circuit conditions such as those of short-circuit.

    BREAKING Breaking Capacity

    WITHSTAND Short time withstand

    MAKING Making Capacity

    IEC Standard definitions

    Switch Disconnector - IEC 60947-3

  • ABB Group August 11, 2015 | Slide 8

    Moulded case circuit breaker (MCCB): a circuit breaker having a supporting housing of moulding insulating material, forming an integral part of the circuit breaker (Tmax-XT & Formula).

    IEC Standard definitions

  • IEC Standard definitions

    ABB Group August 11, 2015 | Slide 9

    Air circuit breaker (ACB): a circuit breaker having a supporting housing of moulding insulating material and a metallic frame, forming an integral part of the circuit breaker (Emax & Emax 2).

  • ABB Group August 11, 2015 | Slide 10

    A circuit breaker with a break-time short enough to prevent the short-circuit current from reaching its peak value.

    Current limiting circuit breaker

    Current limiting circuit breaker (IEC 60947-2 def. 2.3)

    A current-limiting circuit breaker is able to reduce the stress, both thermal and dynamic, because it has been designed to start the opening operation before the short-circuit current has reached its first peak, and to quickly extinguish the arc between the contacts.

  • Current limiting circuit breaker

    ABB Group August 11, 2015 | Slide 11

    A = Direction of arc due to the magnetic fieldR= Repulsion of moving contacts due to the short circuit current

    A

    I

    A

    R

    R

  • ABB Group August 11, 2015 | Slide 12

    Time

    Current

    Current limiting circuit breaker

    Energy limitation

  • ABB Group August 11, 2015 | Slide 13

    Value of the limited peak of the short circuit current according to the value of the symmetrical short circuit current Irms.

    Current limiting circuit breaker

    Peak limitation curves

  • ABB Group August 11, 2015 | Slide 14

    Value of the let-through energy according to the value of the symmetrical short circuit current Irms.

    Current limiting circuit breaker

    I2t curves

  • ABB Group August 11, 2015 | Slide 15

    Protection against short-circuit (IEC 60364)To protect a cable against short-circuit, the specific let-through energy of the protective device must be lower or equal to the withstanding energy of the cable:

    where I2 t is the specific let-through energy of the protective device which can be read on the curves supplied by the manufacturer; S is the cable cross section [mm2]; in the case of conductors in parallel it is the cross section of the single conductor; k is a factor that depends on the cable insulating and conducting material.

    0.1kA 1kA 10kA 100kA

    1E-2MAs

    0.1MAs

    1MAs

    10MAs

    100MAs

    1E3MAs

    Specific let through energy curve LLL

    Current limiting circuit breaker

    Energy limitation

  • ABB Group August 11, 2015 | Slide 16

    Rated values (Iu, Ue)

    Limit values (Icu, Ics, Icw, Icm)

    Insulation values (Ui, Uimp)

    Choice criteria

    Rated values (Iu, Ue)

  • ABB Group August 11, 2015 | Slide 17

    the rated uninterrupted current of an equipment is a value of current, stated by the manufacturer, that the equipment can carry in uninterrupted duty (at 40 C)

    IEC 60947-1 def. 4.3.2.4

    Rated value Iu

    Rated uninterrupted current Iu

  • ABB Group August 11, 2015 | Slide 18

    Rated value Iu

    The rated uninterrupted current Iu is different from the rated current In, which is the rated current of the thermomagnetic or electronic trip unit and is lower or equal to Iu.A new concept for setting the current In: the rating plug

  • ABB Group August 11, 2015 | Slide 19

    XT1 160

    XT4 250

    Rated uninterrupted current IuSome factors may reduce the Iu of a circuit breakerlike temperature, altitude or frequency.

    Rated value Iu

  • ABB Group August 11, 2015 | Slide 20

    the rated operational voltage of an equipment is a value of voltage which, combined with a rated operational current, determines the application of the equipment and to which the relevant tests and the utilization categories are referred.

    IEC 60947-1 def. 4.3.1.1

    Rated value Ue

    Rated operational voltage Ue

  • ABB Group August 11, 2015 | Slide 21

    Breaking capacity is always referred to the operational voltage; the breaking capacity decreases when the voltage increases.

    Rated value Ue

    Rated operational voltage Ue

  • ABB Group August 11, 2015 | Slide 22

    Some factors may reduce the Ue of a circuit breaker

    Rated value Ue

  • ABB Group August 11, 2015 | Slide 23

    Rated values (Iu, Ue)

    Limit values (Icu, Ics, Icw, Icm)

    Insulation values (Ui, Uimp)

    Choice criteria

    Limit values (Icu, Ics, Icw, Icm)

  • ABB Group August 11, 2015 | Slide 24

    Breaking capacity according to a specified test sequence.Do not include after the short circuit test, the capability of the circuit breaker to carry its rated current continuously.

    - test sequence: O - 3 min - CO - dielectric withstand at 2 x Ue- verification of overload release at 2.5 x I1

    Limit value Icu

    Icu = RATED ULTIMATE SHORT CIRCUIT BREAKING CAPACITY

    IEC 60947-2 def. 4.3.5.2.1

  • ABB Group August 11, 2015 | Slide 25

    Breaking capacity according to a specified test sequence. Include after the short circuit test, the capability of the circuit breaker to carry its rated current continuously

    - test sequence: O - 3 min - CO - 3 min CO - dielectric withstand at 2 x Ue- verification of temperature rise at Iu- verification of overload release at 1.45 x I1- verification of the electrical life

    Ics = RATED SERVICE SHORT CIRCUIT BREAKING CAPACITY

    IEC 60947-2 def. 4.3.5.2.2

    Limit value Ics

  • ABB Group August 11, 2015 | Slide 26

    Limit values Icu and Ics

    The service breaking capacity Ics can be expressed as

    a value of breaking current, in kA;

    Standard ratios between Ics and Icu

    Relation between Ics and Icu This relation is always true!!!

    Ics Icu

    a percentage of Icu, rounded up to the lowest whole number, in accordance with the table (for example Ics = 25% Icu).

  • When is Icu required?

    Where continuity of service is not a fundamental requirement.

    For protection of single terminal load.

    For motor protection.

    Where maintenance work is easily carried out without much disruption.

    Generally for circuit breaker installed on terminals part of plant.

  • When is Ics required?

    Where continuity of service is a fundamental requirement.

    For installation in power center.

    Where is more difficult to make maintenance.

    When is difficult to manage spare breakers.

    Generally for installation in main distribution board immediately downstream transformer or generator.

  • ABB Group August 11, 2015 | Slide 29

    Main circuit breakers or circuit breakers for which a long out-of-service period can not be accepted

    (for example naval installation)

    CB selection based on

    Ics

    Icu

    circuit breakers tor termlnal circuits or circuit breakers for economic application

    Limit values Icu and Ics

    Icu and Ics: selection criteria

  • Icu or Ics ?

    Application of Icu / Ics circuit breakers

    X X X X X X

    X X X

    X

    4000A

    1600A

    630A 630A 630A

    Main incoming Board

    Sub Dist Board

    Icu breaker :Downstream devices

    Ics breaker :Incoming / upstream

    devices

  • When Isc = 100 % of Icu is not necessary ?

    When the real short circuit current in the point of installation is lower than the maximum Ics breaking capacity.

    U LOAD

    B

    ABreaker A:Icu =100 kAwith Ics = 100 % of Icu

    Breaker B:Icu = 100 kAwith Ics = 75 % of Icu

    70 kA

    50 kA !!!Please also considerthat short circuit current at the end of the line isstill lower

  • When Isc = 100 % of Icu is not necessary ?

    Motor Protection according to IEC 60947- 4-1

    Duty cycle:

    O - 3mins - CO at Iq current (maximum short circuit current)

    O - 3mins - CO at r current (critical short circuit current depending from the contactor size)

    Where:

    O: Tripping of the circuit breaker under short circuit condition.

    CO: Closing by the contactor under short circuit condition and tripping of the circuit breaker.

  • Icu or Ics ? Conclusion

    Consider that not always Ics = 100% of Icu is available for the full range for all the employed voltage range, i.e. (from 220 V a.c. to 690 V a.c.duty, and 250 V d.c.).

    Selection of circuit breaker with breaking capacity Icu or Icsmust be done according to the real technical installation requirement.

    Independently from the duty cycle selected the safety of the plant is strictly dependent from the maximum circuit breaking capacity (in most of cases Icu).

  • ABB Group August 11, 2015 | Slide 34

    Limit value Icw

    Icw = RATED SHORT-TIME WITHSTAND CURRENT

    IEC 60947-2 def. 4.3.5.4

    Example of use of category B circuit breakers in electrical plant

    Trafo 630kVAUcc%=4%

    400V

    ACB E1B12

    MCCB XT4

    22.7kA

    MCCB XT3

    The upstream circuit breaker can withstand the fault current up to 1 or 3 sec, thus guaranteeing an excellent selectivity with downstream apparatus

  • ABB Group August 11, 2015 | Slide 35

    Circuit breakers specifically intended for selectivity in short circuit conditions in relation to other protection devices in load-side series, that is with an intentional delay (adjustable) applicable in short circuit conditions.

    These circuit breakers have a specified rated short-time withstand current Icw.

    IEC 60947-2 Table 4

    CATEGORY BCIRCUIT BREAKER

    Limit value Icw

  • ABB Group August 11, 2015 | Slide 36

    Circuit-breakers not specifically intended for selectivity under short circuit conditions with respect to other protection devices in series on the load side, that is without intentional short-time delay provided for selectivity under short-circuit conditions.

    These circuit-breakers have not a specified rated short-time withstand current value Icw.

    Limit value Icw

    IEC 60947-2 Table 4

    CATEGORY ACIRCUIT BREAKER

  • ABB Group August 11, 2015 | Slide 37

    It is the value of short-time withstand current assigned to the circuit-breaker by the manufacturer under specified test conditions. This value is referred to a specified time (usually 1s or 3s).

    It must be stated when the circuit-breaker is classified in category B and its value must be greater than:

    The highest value between 12 Iu and 5 kA for CBs with Iu d 2500A

    30 kA for CBs with Iu > 2500A

    Circuit breakers without Icw value are classified in category A

    Limit value Icw

    IEC 60947-2 Table 3

    Icw = RATED SHORT-TIME WITHSTAND CURRENT

  • Selectivity Categories

  • ABB Group August 11, 2015 | Slide 39

    IEC 60947-2 def. 4.3.5.1

    Icm = RATED SHORT-CIRCUIT MAKING CAPACITY

    Making capacity for which the prescribed conditions according to a specified test sequence include the capability of the circuit breaker to make the peak current corresponding to that rated capacity at the appropriate applied voltage.

    Limit value Icm

    It is always necessary to verify that:

    Icm t Ipeak

  • ABB Group August 11, 2015 | Slide 40

    Limit value Icm

    Icm n x Icu

    For a.c. the rated short-circuit making capacity of a circuit-breaker shall be not less than its rated ultimate short-circuit breaking capacity, multiplied by the factor n of the table.

    IEC 60947-2 Table 2

  • ABB Group August 11, 2015 | Slide 41

    16,8kA

    50kA

    54kA

    Peak

    Irms

    105kA

    10kA 100kA

    10kA

    100kA

    T6L800 In800

    XT2L 160 In160

    Example

    Current limiting circuit breaker

  • ABB Group August 11, 2015 | Slide 42

    If the cosM of the plant is higher than the standard prescribed value, it is not necessary to take into account the rated short-circuit making capacity of the circuit-breakers (Icm).

    If the cosM of the plant is lower than the standard prescribed value, usually near to the transformer and/or generator, it is necessary to verify Icm t Ipeak.

    Limit value Icm

  • ABB Group August 11, 2015 | Slide 43

    If the cosMk of the plant is equal to 0.16 (lower than the standard prescribed value) the evaluated Ip = 175 kA.

    Short circuit current of the plant is Icc = 75kA ; The used circuit breaker has an Icu = 75 kA; According to the table 2, cosMk=0.2 and n=2,2 so Icm = n x Icu = 165 kA.

    Since Ip > Icm the CB selected is not correct. I will use a CB with a greatervalue of Icu in order to have an Icm value suitable to the peak current of the plant.

    Sometimes it can happen

    Limit value Icm

  • ABB Group August 11, 2015 | Slide 44

    Limit value Icm

  • ABB Group August 11, 2015 | Slide 45

    Rated values (Iu, Ue)

    Limit values (Icu, Ics, Icw, Icm)

    Insulation values (Ui, Uimp)

    Choice criteria

    Insulation values (Ui, Uimp)

  • ABB Group August 11, 2015 | Slide 46

    IEC 60947-1 def. 4.3.1.2

    Ui = RATED INSULATION VOLTAGE

    The rated insulation voltage of an equipment is the value of voltage to which dielectric tests and creepage distances are referred.

    It shall be always verified that:

    Ue < Ui

    Limit value Ui

  • ABB Group August 11, 2015 | Slide 47

    IEC 60947-1 def. 4.3.1.3

    Uimp = RATED IMPULSE WITHSTAND VOLTAGE

    The peak value of an impulse voltage of prescribed form and polarity (1,2/50Ps) which the equipment is capable of withstanding without failure under specified conditions of test and to which the values of the clearances are referred.

    It shall be always verified that:

    Uimp > transient overvoltage in the plant

    Limit value Uimp

  • Temperature-rise for terminals and accessible parts

    ABB Group August 11, 2015 | Slide 48

    IEC 60947- 2 Table 7

  • Overload protection

    ABB Group August 11, 2015 | Slide 49 i

    t

    IEC 60947- 2 Table 6

  • Short circuit protection

    ABB Group August 11, 2015 | Slide 50

    i

    S

    I

    t

    IEC 60947- 2 8.3.3.1.2

  • Type Tests

    The tests to verify the characteristics of circuit breakers are:

    type tests carried out on samples:

    IEC 60947- 2 8.3

  • Type Tests

    ABB Group August 11, 2015 | Slide 52

  • Routine Tests

    ABB Group August 11, 2015 | Slide 53

    routine tests carried out on all circuit breakers and including the following tests:

    IEC 60947- 2 8.4

  • Tests of EMC for circuit breakers with electronic overcurrent protection

    Immunity

    Emission

    Electrostatic discharges

    Radiated radio-frequency electromagnetic fields

    Electrical fast transients/bursts

    Surges

    Conducted disturbances induced by radio-frequency fields

    Harmonics

    Voltage fluctuations

    Conducted disturbances

    Radiated disturbances

    Climatic testsDry heat test Damp heat test

    Temperature variation cycles at a specified rate of change

    Annex F - J

  • CE Marking

    ABB Group August 11, 2015 | Slide 55

    According to european directives:

    Low Voltage Directive 73/23 EEC

    Electromagnetic Compatibility 89/336 EEC

  • Annex H

    Test sequence for circuit-breakers for IT systems

    This test is intended to cover the case of a second fault to earth in presence of a first fault on the opposite side of a circuit breaker when installed in IT systems.

    In this test at each pole the applied voltage shall be the phase-to-phase voltage corresponding to the maximum rated operational voltage of the circuit breaker at which it is suitable for applications on IT systems.

  • Circuit BreakersStandards Guidelines IEC 60898

  • IEC Standard definitions

    International Standard References

    IEC 60898

    Applicable to circuit-breakers for protection of wiring installation in buildings and similar applications, and designed for use by uninstructed persons, and for not being maintained.

    Part 1: Circuit-breakers for a.c. operationPart 2: Circuit-breakers for a.c. and d.c. operation (additional requirements)

    Miniature Circuit Breakers MCB

  • Rated values (In, Ue)

    Limit values (Icn, Ics)

    Rated values (In, Ue)

    Choice criteria

  • Rated uninterrupted current (In):

    the rated uninterrupted current of an equipment is a valueof current, stated by the manufacturer, which the equipmentcan carry in uninterrupted duty, at a specified referenceambient air temperature (30 C).

    The rated current doesnt exceed the 125A.

    IEC 60898-1 def. 5.2.2

    Rated value In

  • Rated operational voltage (Ue):

    The rated operational voltage of a circuit-breaker is the value of voltage, assigned by the manufacturer, to which its performances (particularly the short-circuit performance) are referred.

    The rated operational voltage doesnt exceed the 440Vac 220Vdc.

    IEC 60898-1 def. 5.2.1.1

    Rated value Ue

  • Rated values (In, Ue)

    Limit values (Icn, Ics) Limit values (Icn, Ics)

    Choice criteria

  • The rated short-circuit capacity is the value of the ultimate short-circuit breaking capacity for which the prescribed conditions, according to a specified test sequence, do not include the capability of the circuit-breaker to carry 0.85 times its non-tripping current for the conventional time.

    The rated short circuit capacity doesnt exceed the 25kA in ac and 10kA in dc

    test sequence: O - 3 min - CO - leakage current at 1.1 Ue (< 2 mA)- dielectric strength test at 900 V - verification of overload release at 2.8 x In

    IEC 60898-1def. 5.2.4

    Icn = RATED SHORT CIRCUIT CAPACITY

    Limit value Icn

  • The service short-circuit capacity of a circuit-breaker is the value of the breaking capacity for which the prescribed conditions according to a specified test sequence include the capability of the circuit-breaker to carry 0.85 times its non-tripping current for the conventional time.

    IEC 60898-1def. 3.5.5.2

    Ics = RATED SERVICE SHORT CIRCUIT CAPACITY

    Limit value Ics

  • Service Short Circuit capacity (Ics):

    - test seq. : O - 3 min - O - 3 min CO (for one or two poles cb)O - 3 min - CO - 3 min CO (for three or four poles cb)

    - leakage current at 1.1 Ue (< 2 mA)- dielectric strength test- verification of no tripping at 0,85 x In

    A circuit-breaker with a rated short-circuit capacity (Icn) has a corresponding service short-circuit capacity (Ics) as from this table:

    The circuit breaker with Icn < 6000A Ics is equal to 1xIcn 6000A < Icn < 10000A Ics is equal to 0,75xIcn Minimum value of Ics is 6000A. Icn > 10000A Ics is equal to 0,5xIcn Minimum value of Ics is 7500A.

    Limit value Ics

  • Ics Test

  • The main difference between the overload protection curve of the CBs responding to IEC 60947 or IEC 60898 are referred to the conventional non tripping current.The prescibed conditions are given in this table:

    Overload characteristics

    Tripping Curves

  • The CBs according to IEC 60947 usually have the instantaneous threshold at 5 or 10 times the rated current with a tolerance of + 20%.

    The CBs according to IEC 60898-1 (ac applications) have different instantaneous threshold referred to the type B , C , D as indicated in the table below:

    Magnetic characteristics

    Tripping Curves

  • Tripping Curves

  • In some cases, the conditions IB < In < IZand I2 < 1.45 IZ do not guarantee complete protection, e.g. when overcurrents are present for long periods which are smaller than I2. They also do not necessarily lead to an economical solution. It is therefore assumed that the circuit is designed so that minor overloads of a long duration will not occur regularly.

    IEC 60364-4-43

    Tripping Curves

  • Trip lever

    Hammer-impactelectromagnetic coil

    Toggle

    Switching mechanism

    Label

    Bi-directional-cylinder-lift-terminal

    Thermally-delayedbimetal

    Arc quenching chamber

    Fixed contact

    Moving contactEasy releasesnap-on catch

    Bi-directional-cylinder-lift-terminal

    Miniature Circuit Breakers

  • 0.5 ms after short-circuit current is released

    Miniature Circuit BreakersTripping of an MCB

    0.5 ms

  • 1 ms after short-circuit current is released

    Miniature Circuit BreakersTripping of an MCB

    1 ms

  • 1.5 ms after short-circuit current is released

    Miniature Circuit BreakersTripping of an MCB

    1.5 ms

  • 2 ms after short-circuit current is released

    Miniature Circuit BreakersTripping of an MCB

    2 ms

  • 2.5 ms after short-circuit current is released

    Miniature Circuit BreakersTripping of an MCB

    2.5 ms

  • 3 ms after short-circuit current is released

    Miniature Circuit BreakersTripping of an MCB

    3 ms

  • IEC 60947-2 IEC 60898-1

    People Instructed UninstructedMaintenance Possible Not possible

    Rated Voltage (Ue)< 1000 Vac

    < 1500 Vdc

    < 440 Vac

    < 220 VdcAmbient

    Temperature 40 C 30 C

    Rated CurrentNo limits

    (Iu < 6300 A)In = 125 A

    Short circuit breaking current No limits for Icu

    Icn = 25 kA (ac)

    Icn = 10 kA (dc)

    Comparison IEC 60947-2 vs IEC 60898

  • Generalities about the main electrical parameters Dont forget Ue t Un Icu or Ics t Ik Icm t Ip

    Ue, Icu, Ics, Icm?

    Selection of protective Devices

  • Protection of feeders against overloadIb In or I1 Iz

    against short-circuitI2t k2S2

    In

    Iz S

    Ib

    Selection of protective Devices

  • The correct circuit breaker must be selected to satisfy the following conditions:

    It must own short circuit breaking power (lcu or eventually lcs) greater or equal to the short circuit current lcc

    It must use a protection release so that its overload setting current ln (l1) satisfies the relation lB < ln < lZ

    The let through energy (l2t) that flows through the circuit breaker must be lesser or equal to the maximal one allowed by the cable (KS)

    Selection of protective Devices

  • Selection of protective Devices

  • As far as the verification required by IEC 60364, according to which theoverload protection must have an intervention current lf that assures theoperation for a value lesser than 1,45 lz (lf < 1,45 lz), we must state that itis always verified for ABB Circuit breakers, since according to IEC 60947-2the required value is less than 1,3 ln.

    Selection of protective Devices

  • Selection of protective Devices

  • Protection of generators Ingen I1 I3 or I2 2.5-4 x Ingen

    G

    Selection of protective Devices

  • Protection of transformers InT I1 Upstream CB I3 or I2 t Iinrush

    Selection of protective Devices

  • Steps determining the short-circuit

    currents choosing the CB setting of the MV overcurrent

    protection setting of the LV overcurrent

    protection

    20kV

    400V

    Selection of protective Devices

  • 20kV

    400V

    Selection of protective Devices

  • 20kV

    400V

    Selection of protective Devices

  • As to be able to protect LV/MV transformers LV side, we must mainly take into account:

    Rated current of the protected transformer, LV side, from which the rated current of the circuit breaker and the setting depend on (In);

    The maximum estimated short circuit current in the installation point which defines the minimal breaking power of the protection circuit breaker (Isc).

    Protection of Transformers

  • Sn

    In

    Isc

    U20

    Protection of TransformersSwitchboards with one transformer

    The rated current of the transformers LV side is defined by the following expression

    whereSn = rated power of the transformer [kVA]U20 = rated secondary voltage (no load) of the transformer [V]ln = rated current of the transformer, LV side [A]

    In = Sn x 103

    3 x U20

  • The full voltage three-phase short circuit current immediately after the LV side of the transformer can be expressed by the following relation once we suppose infinite power at the primary:

    whereUcc %= short circuit voltage of the transformer [%]ln = rated current, LV side, [A]lsc = three-phase rated short circuit current, LV side, [A]

    Isc = In x 100Ucc %

    Protection of Transformers

  • The short circuit current is normally lesser than the preceding deduced value if the circuit breaker is installed at a certain distance by means of a cable or bar connection, according to the connection impedance.

    Protection of Transformers

  • The following table shows some possible choices within the SACE Emax ACB range according to the characteristics of the CB to protect.

    AttentionThose indications are valid at the conditions that we declare in the table; different conditions will lead us to repeat calculations and modify the choices.

    Protection of Transformers

  • (1) For values of the percent short circuit voltage Ucc% different from the Ucc% values as per table, the rated three-phase short circuit current Icn becomes:

    (2) The calculated values refer to a U20 voltage of 400 V. for different U20 values, do multiply In and Isc the following k times:

    Isc =Ucc %

    Ucc %Isc

    U20 [V] 220 380 400 415 440 480 500 660 690

    k 1.82 1.05 1 0.96 0.91 0.83 0.8 0.606 0.580

    Protection of Transformers

    Sn [kVA] 500 630 800 1000 1250 1600 2000 2500 3150

    Ucc (1) % 4 4 5 5 5 6,25 6,25 6,25 6,25

    In (2) [A] 722 909 1154 1443 1804 2309 2887 3608 4547

    Isc (2) [kA] 18 22.7 23.1 28.9 36.1 37 46.2 57.7 72.7

    SACE Emax E1B08 E1B12 E1B12 E2B16 E2B20 E3B25 E3B32 E4S40 E6H50

  • Protection of TransformersSwitchboards with more than 1 transformer in Parallel

    Circuit breaker B

    I1 I2 I3

    1 2 3

    Isc2 + Isc3

    Isc1 + Isc2 + Isc3

    I4 I5

    Circuit breaker A

    Isc1

  • As far as the calculation of the rated current of the transformer isconcerned, the rules beforehand indicated are completely valid.

    The minimum breaking capacity of each circuit breaker LV side must begreater than the highest of the following values: (the example refers tomachine 1 of the figure and it is valid for the three machines in parallel):

    lsc 1 (short circuit current of transformer 1) in case of faultimmediately downstream circuit breaker 1;

    lsc2 + lsc3 (short circuit currents of transformer 2 and 3) in case offault immediately upstream circuit breaker 1;

    Protection of Transformers

  • Circuit breakers l4 and l5 on the load side must have a short circuitcapacity greater than lsc1 + lsc2 + lsc3; naturally every transformercontribution in the short circuit current calculation is to be lessened by theconnection line transformer - circuit breaker (to be defined case by case).

    Protection of Transformers

  • ABB Group August 11, 2015 | Slide 100

    Low voltage selectivitywith ABB circuit breakersSelectivity definitions and Standards

  • Definitions and Standards Selectivity techniques Definitions and Standards

    Back-up protection

    AgendaLow voltage selectivity with ABB circuit breakers

  • Selectivity (or discrimination)

    is a type of coordination of two or more protective devices in series.

    Selectivity is done between one circuit breaker on the supply side and one circuit breaker, or more than one, on the load side.

    A is the supply side circuit breaker (or upstream)

    B and C are the load side circuit breakers (or downstream)

    IntroductionWhat is selectivity?

  • Better selectivity

    FAULT CONTINUITY OF SERVICEDAMAGE REDUCTION

    Fast fault elimination

    Reduce the stress and prevent damage Minimize the area and the duration of

    power loss

    IntroductionProtection system philosophy

  • Selective coordination among devicesis fundamental for economical and technical reasons

    It is studied in order to: rapidly identify the area involved in the problem; bound the effects of a fault by excluding just the affected zone of the

    network; preserve the continuity of service and good power quality to the sound

    parts of the network;

    provide a quick and precise identification of the fault to the personnel in charge of maintenance or to management system, in order to restore the service as rapidly as possible;

    achieve a valid compromise between reliability, simplicity and cost effectiveness.

    Main purposes of coordinationSelectivity purpose

  • The definition of selectivity

    Trip selectivity (for overcurrent) is a coordination between the operating characteristics of two or more overcurrent protection devices, so that, when an overcurrent within established limits occurs, the device destined to operate within those limits trips whereas the others do not trip

    IEC 60947-1 Standard: Low voltage equipment

    Part 1: General rules for low voltage equipment

    Standards definitionSelectivity

    IEC 60947-1 def. 2.5.23

  • In occurrence of a fault (an overload or a short circuit)

    if selectivity is provided

    only the downstream circuit breaker opens.

    Overcurrent selectivityExample

  • All the system is out of service!

    In occurrence of a fault (an overload or a short circuit)

    if selectivity is not provided

    both the upstream and the downstream circuit breakers could open

    Overcurrent selectivityExample

  • A and B connected in series:

    partial selectivity and total selectivity.

    Standards definitionPartial and total selectivity

    IEC 60947-2 def. 2.17.2 - 2.17.3

  • Partial selectivity is an overcurrent selectivity where, in thepresence of two protection devices against overcurrent in series,the load side protection device carries out the protection up to agiven level of overcurrent, without making the other device trip.

    B opens only according to fault current lower than a certain current value; values equal or greater than Iswill give the trip of both A and B.

    Is is the ultimate selectivity value!

    Is = ImA

    Standards definition Partial selectivity

  • Only B trips for every current value lower or equal to the maximum short-circuit current.

    Total selectivity is an overcurrent selectivity where, in thepresence of two protection devices against overcurrent in series,the load side protection device carries out the protection withoutmaking the other device trip.

    B A

    Is = Ik

    Standards definitionTotal selectivity

  • Upstream circuit breaker A

    T4N 250 PR221DS In = 250 (Icu = 36kA)

    Downstream circuit breaker B

    S 294 C100 (Icu = 15kA)

    Standards definitionPartial and total selectivity

  • Overload zone

    Thermal protectionL protection

    Short-circuit zone

    Magnetic protection

    S, D, I and EF protections

    Time-current selectivity

    Current, time, energy, zone, directional, zone directional selectivity

    Selectivity analysisTime-current curves

  • Real currents circulating through the circuit breakers

    I>A

    B I> I> I>

    A

    B

    I>

    I>

    I>

    I> I>

    A

    B

    I>

    I>

    IA = IB

    IA IB

    tA

    tB

    tAtB

    IAIBIA=IB

    tA

    tB

    IA = IB + Iloads IA = (IB + Iloads) / 2

    Selectivity analysisReal currents

  • ABB Group, BU Breakers and Switches August 11, 2015 | Slide 114

    Definitions and Standards Selectivity techniques Selectivity techniques Back-up protection

    AgendaLow voltage selectivity with ABB circuit breakers

  • ABB Group, BU Breakers and Switches August 11, 2015 | Slide 115

    Current selectivity

    Time selectivity

    Energy selectivity

    Zone (logical) selectivity

    IntroductionSelectivity techniques

  • The ultimate selectivity value is equal to the instantaneous trip threshold of the upstream protection device

    Other methods are needed to have a total selectivity

    AB

    ImB ImA

    Current selectivity: closer to the power supply the fault point is, higher the fault current is

    In order to guarantee selectivity,the protections must be set to different values of current thresholds

    Ultimate selectivity value

    1kA

    3kA

    tB

    tAtA

    Current selectivityBase concept

  • AB

    Here the selectivity is a total selectivity, because it is guaranteed up to the maximum value of the short-circuit current, 1kA.

    Circuit breaker A will be set to a value which does nottrip for faults which occur on the load side of B.(I3Amin >1kA)

    Circuit breaker B will be set to trip for faults whichoccur on its load side (I3Bmax < 1kA)

    0.1kA 1kA 10kA

    10-2s

    10-1s

    1s

    10s

    102s

    103s

    104s

    3kA

    Is Is = I3Amin

    Current selectivityExample

  • PlusEasy to be realized

    EconomicInstantaneous

    MinusSelectivity is often only partial

    Current thresholds rise very quickly

    CURRENT SELECTIVITY

    Current selectivity Plus and minus

  • Time selectivity is based on a trip delay of the upstream circuit breaker, so to let to the downstream protection the time suitable to trip

    B A

    Setting strategy:progressively increase the trip delays getting closer to the power supply source

    On the supply side the S function is required

    Time selectivityBase concept

  • 0.1kA 10kA 100kA10-2s

    10-1s

    1s

    10s

    102s

    103s

    104s

    1kA

    The ultimate selectivity value is:

    Is = IcwA (if function I = OFF)

    Is = I3minA (if function I = ON)

    Ik

    A will be set with the current threshold I2adjusted so as not to create trip overlappingand with a trip time t2 adjusted so thatB always clears the fault before A

    B will be set with an instantaneous tripagainst short-circuit

    BI2

    t2

    Is

    Time selectivityExample

  • 0.1kA 10kA 100kA10-2s

    10-1s

    1s

    10s

    102s

    103s

    104s

    1kA

    The network must withstand high values of let-through energy!

    If there are many hierarchical levels, the progressive delays could be significant!

    Ik

    Which is the problem of time selectivity?

    In the case of fault occurring at the busbars, circuit breaker A takes a delayed trip time t2

    B

    t2

    Time selectivity Example

  • PlusEconomic solutionEasy to be realized

    Minus

    TIME SELECTIVITY

    Time selectivityPlus and minus

    Quick rise of setting levelsHigh values of let-through energy

  • Energy selectivity is based on the current-limiting characteristics of some circuit breakers

    A

    B

    0.1kA 1kA 10kA

    10-2s

    10-1s

    1s

    10s

    102s

    103s

    104s

    Current-limiting circuit breakerhas an extremely fast trip time,short enough to prevent thecurrent from reaching its peak

    The ultimate current selectivity valuesis given by the manufacturer (Coordination tables)

    Energy selectivityBase concept

  • 1kA 10kA0.1kA10-2s

    10-1s

    1s

    10s

    102s

    103s

    104s

    Circuit breaker A conditions:

    I3=OFF

    S as for time selectivity

    A

    B

    Is = 20kA

    Energy selectivityExample

  • PLUS

    MINUS

    ENERGY SELECTIVITY

    Energy selectivityPlus and minus

    High selectivity valuesReduced tripping times

    Low stress and network disturbance

    Increasing of circuit breakers size

  • Zone selectivity is an evolution of the time selectivity, obtained by means of a electrical interlock between devices

    The circuit breaker which detects a fault communicates this to the one on the supply side,sending a locking signal

    Fault

    locking signal

    Only the downstream circuit breaker opens, with no need to increase the intentional time delay

    Zone selectivityBase concept

  • A Does Not Open

    B Does Not Open

    C Opens

    A

    B

    C

    Zone

    1Zo

    ne 2

    Zone

    3Zone selectivityExample

  • Is up to 100kA for Tmax

    Is up to Icw for Emax It is possible to obtain zone selectivity between Tmax and Emax

    Zone

    1Zo

    ne 2

    Zone

    3

    Zone selectivity needs:

    a shielded twisted pair cable

    an external source of 24V

    dedicated trip units PR223EF for Tmax T4, T5 and T6

    PR332/P for Tmax T7 and T8

    PR122/P and PR123/P for Emax

    PR332/P and PR333/P for X1

    Zone selectivitySpecifications

  • PLUS

    MINUS

    ZONE SELECTIVITY

    Zone selectivityPlus and minus

    Trip times reducedLow thermal and dynamic stress

    High number of hierarchical levels Can be made between same size circuit breakers

    Cost and complexity of the installationAdditional wiring and components

  • ABB Group, BU Breakers and SwitchesAugust 11, 2015 | Slide 130

    Definitions and Standards Selectivity techniques Back-up protection Back-up protection

    AgendaLow voltage selectivity with ABB circuit breakers

  • Back-up protection (or cascading)

    is a type of coordination of two protective devices in series which is done in electrical installations where continuous operation is not an essential requirement.

    Back-up protectionWhat is back-up protection?

    Back-up protection excludes the use

    of selectivity!!!

  • The definition of back-up is given by the

    Back-up is a coordination of two overcurrent protective devices in series, where the protective device on the supply side, with or without the assistance of the other protective device, trips first in order to prevents any excessive stress on downstream devices.

    IEC 60947-1 Standard: Low voltage equipment

    Part 1: General rules for low voltage equipment

    Back-up protectionStandards definition

    IEC 60947-1 def. 2.5.24

  • Back-up is used by those who need to contain the plant costs

    The use of a current-limiting circuit breaker on the supply side permits the installation of lower performance circuit breakers on the load side

    Both the continuity of service and the selectivity are sacrificed

    Back-up protectionBase concept

  • T4L 250

    T1N 160 T1N 160 T1N 160

    Ik = 100 kA

    T4L 250 T4L 250 T4L 250 Icu = 120kA

    Icu = 36kA

    Icu (T4L+T1N) = 100kA

    Back-up protection Application example

  • Back-up protection tables

  • T4L 250

    T1N 160 T1N 160 T1N 160Ik = 100kA

    Icu (T4L+T1N) = 100kA

    Ik = 100kA

    A

    B C D

    Back-up protection Application example

    General power supply is always lost

  • PlusEconomic solution Quick tripping times

    MinusNo selectivity

    Low power quality

    BACK-UP PROTECTION

    Back-up protectionPlus and minus

  • Incoming = T5H 630A (70kA rating) Outgoing = T3N 160A (36kA rating)

    Results: The co-ordination resulted in a conditional short-circuit of 65kA for the T3 mccb!

    The discrimination is up to 20kA.

    Example of Selectivity

    Iz

    T5H 630A 70kA

    T3N 160A 36kA

    65kA

    ~

  • Example of Selectivity

    Discrimination

  • Example of Selectivity

    Back-Up

  • T5H 70kA

    T3N 36kA

    Example of Selectivity Meaning of Selectivity Value

    T3N 36kA

    T5H 70kA

    Y is 20kA

    Fault level at Y is 20kA

  • T3N 36kA

    T5H 70kA T5H

    T3N 20kA

    Example of Selectivity Meaning of Selectivity Value

  • 5kA

    T5H T3N 5kA fault ON Trip

    T3N 36kA

    T5H 70kA

    Example of Selectivity Meaning of Selectivity Value

  • T5H T3N 5kA fault ON Trip

    10kA fault ON Trip

    10kA

    T3N 36kA

    T5H 70kA

    Example of Selectivity Meaning of Selectivity Value

  • T3N 36kA

    20kA

    T5H 70kA T5H T3N 5kA fault ON Trip

    10kA fault ON Trip 20kA fault Trip Trip

    Example of Selectivity Meaning of Selectivity Value

  • T3N 36kA36kA

    T5H 70kA T5H T3N 5kA fault ON Trip

    10kA fault ON Trip 20kA fault Trip Trip 36kA fault Trip Trip

    Example of Selectivity Meaning of Selectivity Value

  • T3N65kA

    T5H 70kA T5H T3N 5kA fault ON Trip

    10kA fault ON Trip 20kA fault Trip Trip 36kA fault Trip Trip 65kA fault Trip Trip

    36kA

    Example of Selectivity Meaning of Selectivity Value

  • Motor co-ordination ABB offers co-ordination tables

    MV/LV Transformer SubstationsSelection of Protective & Control Devices

  • Co-ordination between CBs and switch-disconnectors

    T2S160

    T1D160

    400V

    MV/LV Transformer SubstationsSelection of Protective & Control Devices

  • ABB Group August 11, 2015 | Slide 150

    Power Factor Correction

  • ABB GroupAugust 11, 2015 | Slide 151

    Power Factor CorrectionGeneralities on Power Factor Correction

    In alternating current circuits, current is absorbed by a load which can be represented by two components:

    The Active component

    In phase with the supply voltage Directly related to the output

    The Reactive component Quadrature to the voltage

    Used to generate the flow necessary for the conversion of powers through the electric or magnetic field

    In most installations the presence of inductive type loads, the current lags the active component (IR).

    Generalities

  • ABB GroupAugust 11, 2015 | Slide 152

    In order to generate and transmit active power (P) a certain reactive power (Q) is essential for the conversion of the electrical energy but is not available to the load.

    The power generated and transmitted make up the apparent power (S).

    Power factor (cos M) is defined as the ratio between the active component (IR) and the total value of current (I).

    Mis the phase angle between the voltage and the current.

    Generalities on Power Factor CorrectionPower Factor CorrectionGeneralities

  • ABB GroupAugust 11, 2015 | Slide 153

    Generalities on Power Factor CorrectionPower Factor CorrectionGeneralities

  • ABB GroupAugust 11, 2015 | Slide 154

    Typical Power Factors of some electrical equipmentPower Factor CorrectionGeneralities

  • ABB GroupAugust 11, 2015 | Slide 155

    Advantages of Power Factor Correction Power Factor CorrectionGeneralities

  • ABB GroupAugust 11, 2015 | Slide 156

    Advantages of Power Factor Correction

    Better utilization of electrical machines

    Generators & transformers are sized according to the apparent power (S). With the same active power (P), the smaller the reactive power (Q) delivered, the apparent power will be smaller.

    Better utilization of cables

    The reduction in current allows the use of smaller cables in the installation.

    Power Factor CorrectionGeneralities

  • ABB GroupAugust 11, 2015 | Slide 157

    Reduction in losses

    By improving the power factor, power losses is reduced in all parts of the installation.

    Reduction in voltage drop

    The higher the power factor the Voltage drop will be lower at the same level of Active power.

    Power Factor CorrectionGeneralities

  • ABB GroupAugust 11, 2015 | Slide 158

    Economical savings

    Power supply utilities apply penalties for energy used with poor factor. An improved power factor will reduce such penalties from the utilities.

    Power Factor CorrectionGeneralities

  • ABB GroupAugust 11, 2015 | Slide 159

    Advantages of Power Factor Correction

    Improve capacity of transformers and cables By improving the power factor, you reduce the kVA load on the

    transformer and the current carried by the cables

    Thus additional transformer capacity is available if upgrade or expansion is required in the future

    Or new cables might not be needed if new loads are connected to an existing switchboard

    Apparent Power (VA)e.g 2MVA Transformer

    At 100% capacity

    Real Power (W)eg. 500kW Load

    Reactive Power (VAR)e.g Motors (inductive)

    100kW at 0.7pf = 102kVAR

    Reactive Power (VAR)eg. 50kVAR Capacitors

    Power Factor CorrectionGeneralities

  • ABB GroupAugust 11, 2015 | Slide 160

    Distributed power factor correction

    It is achieved by connecting a capacitor bank properly sized according to the load and is connected directly to the terminals of the load.

    Power Factor CorrectionDifferent Methods

  • ABB GroupAugust 11, 2015 | Slide 161

    Group power factor correction

    It is achieved by connecting a capacitor bank properly sized according to a group of loads and is connected to the upstream of the loads to be corrected.

    Power Factor CorrectionDifferent Methods

  • ABB GroupAugust 11, 2015 | Slide 162

    Types of Power Factor correction

    Centralized power factor correction

    It is achieved by installing an automatic power factor correction bank capacitor bank directly to the main distribution boards.

    Power Factor CorrectionDifferent Methods

  • ABB GroupAugust 11, 2015 | Slide 163

    Types of Power Factor correction

    Combined power factor correction

    This solution is derived from a compromise between a distributed & centralized power factor correction.

    Distributed power factor correction is used mainly for higher loads and a smaller centralized power factor correction is used for the small loads.

    Power Factor CorrectionDifferent Methods

  • ABB GroupAugust 11, 2015 | Slide 164

    Switching and Protection

    Electrical switching phenomena

    The switching of a capacitor bank causes an electric transient due to the phenomena of electric charging of the bank.

    The overcurrents at the moment of switching depends greatly on both the inductance of the upstream network as well as from the number of connected capacitor banks.

    Power Factor CorrectionCapacitor Switching

  • ABB GroupAugust 11, 2015 | Slide 165

    Switching and Protection

    Choice of protective device

    Power Factor CorrectionCapacitor Switching

  • In

    Resistance

    In

    Motor

    In

    Capacitor

    AC-1 AC-3 AC-6b

    Power Factor CorrectionCapacitor Switching

  • Single step capacitor

    In

    30 times In

    Power Factor CorrectionCapacitor Switching

  • Multi steps capacitor bank

    In

    > 100 times In

    Power Factor CorrectionCapacitor Switching

  • Ith = 1.3 x 1.15 x Inc = 1.5 Inc

    Thermal currentUp to 30% for harmonics and voltage fluctuations on main

    Up to 15% for tolerances on capacitor power

    Contactor have to support Ith

    Contactor sizing: Thermal current + peak current

    Power Factor CorrectionContactor Sizing

  • ABB GroupAugust 11, 2015 | Slide 170

    Example Power Factor CorrectionExample

    kVARh is billed if it is higher than the contracted level.

    Apparent power (kVA) is significantly higher than the Active power (kW)

    The excess current causes losses (kWh) which is billed.

    The design of the installation has to be over-dimensioned.

    The installation requires 850kW at power factor of 0.75.

    The transformer will have to be overloaded to 850k / 0.75 = 1.133MVA.

    Current taken by the system is

    Losses in the cables

    P = I2R

    The Transformer, Circuit breaker & Cable has to be increased.

    PI =

    3 * U * Cos M= 1636A

    I = 1636A

    Cos M

    kVA

    kW kVar

    Cos M kW Load

    1MVA

    400V

  • ABB GroupAugust 11, 2015 | Slide 171

    Example Power Factor CorrectionExample

    kVARh is reduced to lower than the contracted level or eliminated.

    Apparent power (kVA) is significantly higher than the Active power (kW)

    The charges based on the contracted kVA demand is close to the active power.

    The installation requires 850kW at a power factor of 0.9.

    The transformer will not be overloaded to 850k / 0.90 = 945 kVA.

    Current taken by the system is

    Losses in the cables

    P = I2R

    There is not need to increase the Transformer, Circuit breaker & Cable.

    PI =

    3 * U * Cos M= 1364A

    I = 1364A

    Cos M

    kVA

    kW kVar

    Cos M kW Load

    1MVA

    400V

  • ABB GroupAugust 11, 2015 | Slide 172

    Technical Application Paper Power Factor Correction