icaaet-960

Upload: pudhur-kannan-mani

Post on 10-Mar-2016

216 views

Category:

Documents


0 download

TRANSCRIPT

  • Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.

    Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.

    Power Quality Analysis and Recommendations Based on Real

    Field Measurement Datas

    1P.K.Mani,

    2Dr.K.Siddappa Naidu,

    1Associate Professor, Department of Electrical and Electronics Engineering, VEL TECH MULTITECH, Chennai-600062.

    2Professor, School of Electrical and Electronics Engineering, VEL TECH UNIVERSITY, Avadi, Chennai-600062.

    Abstract

    In years past, most electrical equipment operated on an ideal

    voltage and current waveform. However, in the past couple

    of decades there has been an explosion in the use of solid-

    state electronic technology. This new, highly efficient,

    electronic technology provides improved product quality

    with increased productivity by the use of smaller and lighter

    electrical components. Today we are able to produce

    products that cost less than in years past, but this new

    technology requires clean electric power and is highly

    sensitive to power distortions.

    Electronic equipment (switching power supplies) draws

    current differently than non-electronic equipment. Instead of

    a load having a constant impedance drawing current in

    proportion to the sinusoidal voltage, electronic devices

    change their impedance by switching on and off near the

    peak of the voltage waveform. Switching loads on and off

    during part of the waveform results in short, abrupt, non-

    sinusoidal current pulses during a controlled portion of the

    incoming peak voltage waveform. These abrupt pulsating

    current pulses introduce unanticipated reflective currents

    (harmonics) back into the power distribution system. The

    currents operate at frequencies other than the fundamental 50

    Hz. Harmonic currents can be likened to the vibration of

    water in a water line when a valve is open and closed

    suddenly. In this paper power quality analysis done based on

    the real field measurements in a spinning mill reported and

    the recommendations are suggested.

    Keywords: Power Quality, Harmonics, AHF, THD,

    Nonlinear loads.

    1. Introduction The actual problems of any Project will vary, depending on

    the types and number of installed harmonic producing loads.

    Most Projects can withstand nonlinear loads of up to 15% of

    the total electrical system capacity without concern, but,

    when the nonlinear loads exceed 15% some non-apparent

    negative consequences can be expected. For Projects that

    have nonlinear loading of more than 25%, particular

    problems can be become apparent. The following is a short

    summary of most, but not all of the problems caused by

    harmonics:

    Capacitor Failure - Harmonic Resonance

    Circuit Breakers Tripping - Inductive Heating and

    Overload

    Computer Malfunction or Lockup - Voltage

    Distortion

    Conductor Failure - Inductive Heating

    Electronic Equipment Shutting down - Voltage

    Distortion

    Flickering of Fluorescent Lights - Transformer

    Ballast Saturation

    Fuses Blowing for No Apparent Reason - Inductive

    Heating and Overload

    Motor Failures (overheating) - Voltage Drop

    Neutral Conductor and Terminal Failures - Additive

    Currents

    Overheating of Metal Enclosures - Inductive

    Heating

    Power Interference on Voice Communication -

    Harmonic Noise

    Transformer Failures - Inductive Heating

    The heating effects of harmonic currents can cause

    destruction of equipment, conductors, and fires. The results

    can be unpredictable legal and financial ramifications.

    Voltage distortions can lead to overheating of equipment,

    electronic equipment failure, expensive downtime, and

    maintenance difficulties. Harmonic currents and voltage

    distortion are becoming the most severe and complex

    electrical challenge for the electrical industry. The problems

    associated with nonlinear loads were once limited to isolated

    devices and computer rooms, but now the problem can

    appear throughout the power and utility system.

    Our work consists of the following:

    Power Quality Audit

    Graphical analysis

    Recommendations

    Conclusion.

    2. Scope of Work

    A. OBJECTIVE:

    To conduct Reactive Power Flow study and Power Quality

    Audit and measure the level of Harmonics and the reactive

    power requirement.

    To suggest a suitable solution to improve the Power Factor at

    the correct location and maintain the Power Quality in the

    Network as per International norms.

    B. INSTRUMENTS USED:

    METREL Power Quality Analyser Plus which displays and

    stores Active Power, Reactive Power, Apparent Power,

    Power factor, Displacement power factor, Total harmonic

    distortion of voltage and current each individual phase wise,

    Oscilloscope waveform of voltage and voltage harmonics,

    current and current harmonics, etc.

  • Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.

    Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.

    C. MEASUREMENT CONDITIONS:

    Measurements were carried out in the following locations:

    1. 33 KV HT TOTAL INCOMER

    2. TRANSFORMER -1, 2MVA

    a) F1 BLOW ROOM.

    b) F2 SPINNING G 5/1 M/C's 5-8.

    c) F3 PREPORATORY -1.

    d) F4 HUMIDIFICATION PLANT 1.

    e) F5 SPINNING G 5/1 M/C's 1-4.

    f) F6 COLONY LIGHTNING.

    g) F7 NEW PREPORATORY.

    h) F8 SPINNING G 5/1 M/C's 22-25.

    I) F9 SPINNING G 5/1 M/C's 9-12.

    j) F10 COMBER PLANT.

    k) F11 DOUBLING & SPINNING.

    l) F12 SPINNING 6/S M/C's 17-20.

    3. TRANSFORMER -2, 2MVA

    a) F13 SPINNING G 5/1 M/C's 17-21.

    b) F14 SPINNING G 5/1 M/C's 13-16.

    c) F15 HUMIDIFICATION PLANT 2 & LR 6/S Plant

    1&2.

    d) F16 PREPORATORY -2.

    e) F17 SPINNING LRD J/5 1-10(Pump House).

    f) F18 FACTORY LIGHTNING.

    g) F19 SPINNING LR 6/S M/C's 9-13.

    h) F20 CONE WINDING.

    i) F21 ACW 338-1-7.

    j) F22 SPINNING LR 6/S M/C's 14-17.

    k) F23 SPINNING LR 6/S M/C's 1-4.

    4. TRANSFORMER -3, 2MVA

    a) F45 RETIRE BLOW ROOM.

    b) F46 RETIRE PREPORATORY -1.

    c) F47 RETIRE PREPORATORY -2&3.

    d) F48 SPINNING LR 6 25-27 & H.PLANT.

    e) F49 K441 SPINNING 9-12.

    f) F50 SPINNING LR 6 22-24 & H.PLANT.

    g) F51 NEW AUTO CONE WINDING.

    h) F52 K441 SPINNING 5-8.

    i) F53 K441 SPINNING 1-4.

    j) F54 AUTO CONOR H.PLANT & RETIRE

    PREPORATORY.

    5. TRANSFORMER -4, 2MVA

    a) F37 LIGHTNING RETIRE PROJECT.

    b) F38 DJ/S SPINNING H.PLANT.

    c) F39 SPINNING LR 60 A 11-13.

    d) F40 SPARE.

    e) F41 SPINNING LR 60 A 1- 5.

    f) F42 SPINNING LR 60 A 6-10.

    D. MEASUREMENT TECHNIQUES:

    Using high speed Power Quality Analyzer, various

    instantaneous Power Parameters are recorded for Analysis &

    Evaluation of opt System. The Parameters logged includes

    Phase Voltage, Line Currents, Power Factor, Active Power,

    Reactive Power, Apparent Power, THD, Voltage Harmonics,

    THD Current Harmonics and Individual Voltage & Current

    Harmonics.

    These Parameters are logged on Individual Phase and 3

    Phase for proper analysis. The high speed analyzer measures

    128 Samples per cycle (20 milli seconds) and variations are

    recorded. The recording interval is selected as appropriate to

    the study, depending on the Loading pattern. We are

    summarizing the parameters recorded in Graphical Pattern

    for relevant parameters.

    E. DATA LOGGING

    For the above objective, data logging of Power, Waveform,

    Harmonic Parameters were carried out at the following

    locations:

    Measurements were carried out at Three Transformer nodes

    i.e., LV side of 2500 KVA. These transformers were being

    operated in parallel with LV side Bus couplers closed.

    Studies were carried out at all Incomers and major Feeders

    connected of Transformers.

    F. DATA REPRESENATION

    The following Graphical and Tabulation Forms of the

    Readings recorded are annexed which indicates the data

    logged:

    Load Flow Tables.

    Trend Graphs.

    Harmonic Spectrum Current.

    Waveforms of Current & Voltage.

    G. PATTERN OF RECOMMENDATION

    The recommendations are on the following Pattern, taking

    into consideration the Mandatory IEC Guidelines &

    Statutory IEEE Guidelines for Voltage & Current

    Harmonics. The Recommendations are grouped as given

    below:

    Group I Level of Harmonics:

    Where the levels of Harmonics are lesser than IEEE / IEC

    Guidelines for Harmonics and Capacitors having specific

    guaranteed Harmonic Withstand Capability are

    recommended.

  • Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.

    Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.

    Group II Level of Harmonics:

    Where the levels of Harmonics are higher than the IEEE /

    IEC limits, recommendation is to provide Automatic

    Switched Harmonic Filter System which will consist of

    Capacitors & Reactors. These Automatic Operation of

    Capacitors and Harmonic Filters improve the power factor

    and also the Harmonic Filters suppress the Current

    Harmonics. Hence, the Average P.F will be maintained for

    the Loads with the suppression of Harmonics.

    3. Overall View of the plant

    4. Analysis of the readings at the 33kV HT indoor

    breaker (SAMPLE CASE)

    POWER PARAMETERS

    The KVA and KW are the

    normal running loads during

    the Time of study 3456 KW

    and 3524 KVA.

    The load currents are normal

    during the Time of study.

    800 amps VCB has been

    used.

    0.00

    0.03

    0.06

    0.08

    0.11

    0.14

    0.16

    0.19

    0.21

    0.24

    0.27

    0.29

    0.32

    0.35

    0.37

    0.40

    0.43

    0.45

    0.48

    0.50

    0.53

    09.02.2013. 14:42:00 09.02.2013. 14:47:45Relation 1 : 1

    St+ (MVA) Av g Pt+ (MW) Av g Qti+ (MVAr) Av g

    Periodic s (PAKSHALA.PMD)

  • Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.

    Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.

    POWER FACTOR

    The Reactive Power varies

    with the Active Power

    variation.

    The system with appx. - 687

    KVAR capacitors are

    connected Excess.

    The Power Factor are found

    at Leading 0.98C at the time

    of study.

    CURRENT

    WAVEFORM

    The variations in current

    harmonic levels are

    recorded.

    It is indicated that the

    Current Harmonic levels

    disturb the current

    waveform.

    Unbalance Current flows in

    each Phase.

    CURRENT

    The load currents are

    normal running loads

    during the Time of study.

    An Trms Current of 63

    Amps is measured.

    The Reactive Power varies

    with the Active Power

    variation.

    HARMONIC CURRENT

    The variations in current

    harmonic levels are

    recorded.

    The average Current

    Harmonic Distortion levels

    are measured as 12%

    It is indicated that the

    Current Harmonic levels are

    HIGHER the limits of

    standards for Harmonics.

    VOLTAGE

    WAVEFORM

    The variations in Voltage

    harmonic levels are

    recorded.

    It is indicated that the

    Voltage Harmonic levels

    disturb the Voltage

    waveform.

    Unbalance in Voltage is

    found each Phase.

    LOAD PARAMETER:

    KW

    KVA

    KV

    AR

    PF

    Volt

    -

    ag

    e

    Curr

    -ent

    TH

    D

    Volt

    age

    (%)

    TH

    D

    Cur

    rent

    (%)

    Freq

    -uency

    Neu

    tral

    Cur

    rent

    3456

    3524 -687 0.98

    C

    21.1

    KV

    63A 2 12 49.88

    Hz

    3.9

    RECOMMENDATION:

    Present P.F is in the range of 0.98

    Voltage harmonics recorded is approximately 2%, which is

    LOWER than the IEEE 519 Guidelines for Harmonics.

    Current harmonics recorded is approximately 12%, which is

    also MARGINALLY HIGHER than the IEEE 519 Guidelines

    for Harmonics.

    As per IEEE guidelines reading shows it is maintaining at

    LEADING Power Factor and the level of Current Harmonic

    is higher. As we having KVAH billing it is necessary to

    maintain unity PF at all time. So it is required to install ASHF

    at the Incomer of all Transformer secondary side.

    5. Some sample cases of load parameter and

    recommendations

    A. F- 4, HUMIDIFICATION PLANT 1:

    LOAD PARAMETER:

    K

    W

    KV

    A

    K

    V

    A

    R

    PF

    Volt

    -age

    Cu

    rr

    -

    ent

    TH

    D

    Vo

    lta

    ge

    (%

    )

    T

    H

    D

    Cu

    rre

    nt

    (%

    )

    Freq

    -

    uency

    Ne

    utr

    al

    Cu

    rre

    nt

    36 60 48 0.60 247 85 6.2 20 50.04 3

    0.88

    0.89

    0.90

    0.91

    0.92

    0.93

    0.95

    0.96

    0.97

    0.98

    0.99

    1.00

    1.01

    1.02

    1.03

    1.05

    1.06

    1.07

    1.08

    1.09

    1.10

    09.02.2013. 14:42:00 09.02.2013. 14:47:45Relation 1 : 1

    Pftc + Av g Pfti+ Av g

    Periodic s (PAKSHALA.PMD)

    05.0

    10.015.020.025.030.035.040.045.050.055.060.065.070.075.080.085.090.095.0

    100.0t r igg t im e: 25. 12. 10. 12: 06: 28. 25

    %

    X ax is range: 1280 point strigg - 6399 points trigg - 5120 points

    12.55

    12.60

    12.65

    12.70

    12.75

    12.80

    12.85

    12.91

    12.96

    13.01

    13.06

    13.11

    13.16

    13.22

    13.27

    13.32

    13.37

    13.42

    13.47

    13.52

    13.58

    09.02.2013. 14:42:00 09.02.2013. 14:47:45Relation 1 : 1

    I1 (A) Av g I2 (A) Av g I3 (A) Av g

    Periodic s (PAKSHALA.PMD)

    0

    5.00

    10.00

    15.00

    20.00

    25.00

    30.00

    35.00

    40.00

    45.00

    50.00

    55.00

    60.00

    65.00

    70.00

    75.00

    80.00

    85.00

    90.00

    95.00

    100.00

    09.02.2013. 14:42:00 09.02.2013. 14:47:45Relation 1 : 1

    thdI1 (%) Max thdI2 (%) Max thdI3 (%) Max

    Periodic s (PAKSHALA.PMD) in %

    05.0

    10.015.020.025.030.035.040.045.050.055.060.065.070.075.080.085.090.095.0

    100.0t r igg t im e: 25. 12. 10. 12: 06: 28. 25

    %

    X ax is range: 1280 point strigg - 6399 points trigg - 5120 points

  • Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.

    Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.

    RECOMMENDATION:

    Present P.F is in the range of 0.6 lagging.

    Voltage harmonics recorded is approximately 6.2%, which is

    very much HIGHER than the IEEE 519 Guidelines for

    Harmonics. Current harmonics recorded is approximately

    20%, which is very much HIGHER than the IEEE 519

    Guidelines for Harmonics. Neutral Current of 3 Amps has

    been found flowing through Neutral.

    As per IEEE guidelines plant should be maintaining at Unity

    Power Factor. So it Necessary to add 60 KVAR Fixed Tuned

    Filter to increase PF and Harmonic Amplification.

    A. F2- SPINNING G 5/1 M/Cs 5-8:

    LOAD PARAMETER:

    K

    W

    KVA

    KV

    A

    R

    PF

    Vo

    lt

    -

    ag

    e

    Curr

    -ent

    T

    H

    D

    Vo

    lta

    ge

    (%

    )

    TH

    D

    Curr

    ent

    (%)

    Freq

    -

    uenc

    y

    Ne

    utr

    al

    Cu

    rre

    nt

    8

    0

    108 72 0.7

    4

    24

    3V

    158

    A

    5 15 49.9

    5Hz

    0

    RECOMMENDATION:

    Present P.F is in the range of 0.74 LAGGING

    Voltage harmonics recorded is approximately 5%, which is

    very much MARGINALLY HIGHER than the limit IEEE

    519 Guidelines for Harmonics. Current harmonics recorded

    is approximately 15%, which is very much HIGHER than the

    limit of IEEE 519 Guidelines for Harmonics. Neutral Current

    of 0 Amps has been found flowing through Neutral.

    As per IEEE guidelines plant should be maintaining at

    LEADING Power Factor, while capacitor are in ON

    condition. So it Necessary to add 100 KVAR Auto Switched

    Harmonic Filter panel in this DB.

    6. Things to be done for better power quality and

    savings in the plant

    1. AUTO SWITCHED HARMONIC FILTERS TO BE

    INSTALLED AT ALL THE INCOMERS.

    2. RING FRAME WITH INVERTER DRIVES SHOULD

    BE PROTECTED WITH LINE.

    3. BASED ON THE RECOMMENDATION, PASSIVE

    FILTERS SHOULD BE INSTALLED AT LOAD END.

    4. AFTER INSTALLING PASSIVE FILTERS,

    FURTHER FOR FINE TUNING PURPOSE, ACTIVE

    FILTERS SHOULD BE INSTALLED.

    7. Conclusion

    System has Higher Current Harmonic of 12% in 33KV, HT side.

    Due to the transportation of low linear path, Effect of Harmonic is more in linear load.

    By installing Filter in the Load end, improves the Lower PF and reduces cable losses. Our recommendation will help

    to increase the PF, decrease the cable losses and some

    percentage of Harmonic will be get filtered in load end itself.

    B phase Voltage and Current recorded as Higher and phase unbalance is also found.

    Excess Neutral Current is measured at the Incomer. Once three phase voltage and Current made balance, it will

    get reduced.

    Failure rate Electrical system will be reduced by installing tuned filters at the load end and default saving will

    be achieved as per the recommendation.

    REFERENCES

    [1] Mauricio Aredes, Klemens Heumann, Edson H.

    Watanabe, An Universal Active Power Line Conditioner,

    IEEE Transactions on Power Delivery, Vol. 13, No. 2, April

    1998.

    [2] B. Singh, and K. Al-Haddad, A review of active filters

    for power quality improvement,IEEE Transactions on

    Industrial Electronics, vol. 46, no. 5, pp. 960-971, Oct. 1999.

    [3] Charles. S, and G. Bhuvaneswari, Comparison of three

    phase shunt active power filter algorithms, International

    Journal of Computer and Electrical Engineering, vol. 2, no.

    1, pp. 175- 180, Feb. 2010.

    [4] S. P. Litran, P. Salmeron, J. R. Vazquez, and J. L.

    Flores, Compensation of voltage unbalance and current

    harmonics with a series active power filter, Renewable

    Energy & Power Quality Journal, no. 3, Mar. 2005.

    [5] L. Chen, and A. V. Jouanne, A comparison and

    assessment of hybrid filter topologies and control

    algorithms, IEEE/PESC Ann. Meeting Conf, vol. 2, pp. 565-

    570.

    [8] E. R. Ribeiro, and I. Barbi, Harmonic voltage

    reduction using a series active filter under different load

    conditions, IEEE Transactions on Power Electronics,

    vol. 21, no. 5, pp. 1394-1402, Sep. 2006.

    [9] KannanKarthik, and J.E.Quaicoe, Voltage

    Compensation and harmonic suppression using series active

    and shunt passive filters,Electrical and Computer

    Engineering, Canadian conference, vol. 1, 2000, p. 582-586.

  • Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.

    Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.

    [10] H. Fujita, and H. Akagi, A practical approach

    to harmonics compensation in power systems series

    connection of passive and active filters,IEEE Transactions

    on Industry Applications, vol. 27, no. 6, pp.1020-1025,

    Nov. 1991.

    [11] J.C.Das,"Power System Harmonics and

    Passive Filter Designs" IEEE Press Series on Power

    Engineering Series: Wiley; 2015

    About the authors

    P.K.Mani has completed his B.E.

    Electrical and Electronics Engineering

    and M.E. Power Systems Engineering at

    Anna University, Chennai. At present he

    is working as Associate Professor in

    Electrical and Electronics Engineering

    Dept, Vel Tech Multitech Dr.Rangarajan

    Dr.SakunthalaEngineering college, Chennai-

    600062.Currently he is doing Ph.D in Veltech

    Dr.RR&Dr.SRTechnical University in the field of power

    quality. Mobile. No: +91 9445260989.

    Email: [email protected].

    Dr.K.Siddappa Naidu finished his

    B.E.Electrical Engineering from Sri

    Venkateswara University, Tirupati in 1973

    and got post-graduation from IISC,

    Bangalore in 1976 and Ph.D. from the same

    institute in 1994. He has worked in various

    capacities in NGEF Transformers Research

    & Development from 1979 to 2000.He

    worked as HOD EEE, Vice Principal and Principal in different

    Engineering colleges from 2000 to 2012.Presently working as

    Dean, School of Electrical Engineering in Vel Tech Dr.RR

    Dr.SR Technical University, Avadi, Chennai-600062.He has

    published many papers in international and national journals.

    His research interests are partial discharge measurements in

    HV Insulation & Apparatus, online monitoring of HV power

    apparatus, Sub synchronous, Renewable energy systems and

    power quality.