icaaet-960
TRANSCRIPT
-
Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.
Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.
Power Quality Analysis and Recommendations Based on Real
Field Measurement Datas
1P.K.Mani,
2Dr.K.Siddappa Naidu,
1Associate Professor, Department of Electrical and Electronics Engineering, VEL TECH MULTITECH, Chennai-600062.
2Professor, School of Electrical and Electronics Engineering, VEL TECH UNIVERSITY, Avadi, Chennai-600062.
Abstract
In years past, most electrical equipment operated on an ideal
voltage and current waveform. However, in the past couple
of decades there has been an explosion in the use of solid-
state electronic technology. This new, highly efficient,
electronic technology provides improved product quality
with increased productivity by the use of smaller and lighter
electrical components. Today we are able to produce
products that cost less than in years past, but this new
technology requires clean electric power and is highly
sensitive to power distortions.
Electronic equipment (switching power supplies) draws
current differently than non-electronic equipment. Instead of
a load having a constant impedance drawing current in
proportion to the sinusoidal voltage, electronic devices
change their impedance by switching on and off near the
peak of the voltage waveform. Switching loads on and off
during part of the waveform results in short, abrupt, non-
sinusoidal current pulses during a controlled portion of the
incoming peak voltage waveform. These abrupt pulsating
current pulses introduce unanticipated reflective currents
(harmonics) back into the power distribution system. The
currents operate at frequencies other than the fundamental 50
Hz. Harmonic currents can be likened to the vibration of
water in a water line when a valve is open and closed
suddenly. In this paper power quality analysis done based on
the real field measurements in a spinning mill reported and
the recommendations are suggested.
Keywords: Power Quality, Harmonics, AHF, THD,
Nonlinear loads.
1. Introduction The actual problems of any Project will vary, depending on
the types and number of installed harmonic producing loads.
Most Projects can withstand nonlinear loads of up to 15% of
the total electrical system capacity without concern, but,
when the nonlinear loads exceed 15% some non-apparent
negative consequences can be expected. For Projects that
have nonlinear loading of more than 25%, particular
problems can be become apparent. The following is a short
summary of most, but not all of the problems caused by
harmonics:
Capacitor Failure - Harmonic Resonance
Circuit Breakers Tripping - Inductive Heating and
Overload
Computer Malfunction or Lockup - Voltage
Distortion
Conductor Failure - Inductive Heating
Electronic Equipment Shutting down - Voltage
Distortion
Flickering of Fluorescent Lights - Transformer
Ballast Saturation
Fuses Blowing for No Apparent Reason - Inductive
Heating and Overload
Motor Failures (overheating) - Voltage Drop
Neutral Conductor and Terminal Failures - Additive
Currents
Overheating of Metal Enclosures - Inductive
Heating
Power Interference on Voice Communication -
Harmonic Noise
Transformer Failures - Inductive Heating
The heating effects of harmonic currents can cause
destruction of equipment, conductors, and fires. The results
can be unpredictable legal and financial ramifications.
Voltage distortions can lead to overheating of equipment,
electronic equipment failure, expensive downtime, and
maintenance difficulties. Harmonic currents and voltage
distortion are becoming the most severe and complex
electrical challenge for the electrical industry. The problems
associated with nonlinear loads were once limited to isolated
devices and computer rooms, but now the problem can
appear throughout the power and utility system.
Our work consists of the following:
Power Quality Audit
Graphical analysis
Recommendations
Conclusion.
2. Scope of Work
A. OBJECTIVE:
To conduct Reactive Power Flow study and Power Quality
Audit and measure the level of Harmonics and the reactive
power requirement.
To suggest a suitable solution to improve the Power Factor at
the correct location and maintain the Power Quality in the
Network as per International norms.
B. INSTRUMENTS USED:
METREL Power Quality Analyser Plus which displays and
stores Active Power, Reactive Power, Apparent Power,
Power factor, Displacement power factor, Total harmonic
distortion of voltage and current each individual phase wise,
Oscilloscope waveform of voltage and voltage harmonics,
current and current harmonics, etc.
-
Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.
Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.
C. MEASUREMENT CONDITIONS:
Measurements were carried out in the following locations:
1. 33 KV HT TOTAL INCOMER
2. TRANSFORMER -1, 2MVA
a) F1 BLOW ROOM.
b) F2 SPINNING G 5/1 M/C's 5-8.
c) F3 PREPORATORY -1.
d) F4 HUMIDIFICATION PLANT 1.
e) F5 SPINNING G 5/1 M/C's 1-4.
f) F6 COLONY LIGHTNING.
g) F7 NEW PREPORATORY.
h) F8 SPINNING G 5/1 M/C's 22-25.
I) F9 SPINNING G 5/1 M/C's 9-12.
j) F10 COMBER PLANT.
k) F11 DOUBLING & SPINNING.
l) F12 SPINNING 6/S M/C's 17-20.
3. TRANSFORMER -2, 2MVA
a) F13 SPINNING G 5/1 M/C's 17-21.
b) F14 SPINNING G 5/1 M/C's 13-16.
c) F15 HUMIDIFICATION PLANT 2 & LR 6/S Plant
1&2.
d) F16 PREPORATORY -2.
e) F17 SPINNING LRD J/5 1-10(Pump House).
f) F18 FACTORY LIGHTNING.
g) F19 SPINNING LR 6/S M/C's 9-13.
h) F20 CONE WINDING.
i) F21 ACW 338-1-7.
j) F22 SPINNING LR 6/S M/C's 14-17.
k) F23 SPINNING LR 6/S M/C's 1-4.
4. TRANSFORMER -3, 2MVA
a) F45 RETIRE BLOW ROOM.
b) F46 RETIRE PREPORATORY -1.
c) F47 RETIRE PREPORATORY -2&3.
d) F48 SPINNING LR 6 25-27 & H.PLANT.
e) F49 K441 SPINNING 9-12.
f) F50 SPINNING LR 6 22-24 & H.PLANT.
g) F51 NEW AUTO CONE WINDING.
h) F52 K441 SPINNING 5-8.
i) F53 K441 SPINNING 1-4.
j) F54 AUTO CONOR H.PLANT & RETIRE
PREPORATORY.
5. TRANSFORMER -4, 2MVA
a) F37 LIGHTNING RETIRE PROJECT.
b) F38 DJ/S SPINNING H.PLANT.
c) F39 SPINNING LR 60 A 11-13.
d) F40 SPARE.
e) F41 SPINNING LR 60 A 1- 5.
f) F42 SPINNING LR 60 A 6-10.
D. MEASUREMENT TECHNIQUES:
Using high speed Power Quality Analyzer, various
instantaneous Power Parameters are recorded for Analysis &
Evaluation of opt System. The Parameters logged includes
Phase Voltage, Line Currents, Power Factor, Active Power,
Reactive Power, Apparent Power, THD, Voltage Harmonics,
THD Current Harmonics and Individual Voltage & Current
Harmonics.
These Parameters are logged on Individual Phase and 3
Phase for proper analysis. The high speed analyzer measures
128 Samples per cycle (20 milli seconds) and variations are
recorded. The recording interval is selected as appropriate to
the study, depending on the Loading pattern. We are
summarizing the parameters recorded in Graphical Pattern
for relevant parameters.
E. DATA LOGGING
For the above objective, data logging of Power, Waveform,
Harmonic Parameters were carried out at the following
locations:
Measurements were carried out at Three Transformer nodes
i.e., LV side of 2500 KVA. These transformers were being
operated in parallel with LV side Bus couplers closed.
Studies were carried out at all Incomers and major Feeders
connected of Transformers.
F. DATA REPRESENATION
The following Graphical and Tabulation Forms of the
Readings recorded are annexed which indicates the data
logged:
Load Flow Tables.
Trend Graphs.
Harmonic Spectrum Current.
Waveforms of Current & Voltage.
G. PATTERN OF RECOMMENDATION
The recommendations are on the following Pattern, taking
into consideration the Mandatory IEC Guidelines &
Statutory IEEE Guidelines for Voltage & Current
Harmonics. The Recommendations are grouped as given
below:
Group I Level of Harmonics:
Where the levels of Harmonics are lesser than IEEE / IEC
Guidelines for Harmonics and Capacitors having specific
guaranteed Harmonic Withstand Capability are
recommended.
-
Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.
Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.
Group II Level of Harmonics:
Where the levels of Harmonics are higher than the IEEE /
IEC limits, recommendation is to provide Automatic
Switched Harmonic Filter System which will consist of
Capacitors & Reactors. These Automatic Operation of
Capacitors and Harmonic Filters improve the power factor
and also the Harmonic Filters suppress the Current
Harmonics. Hence, the Average P.F will be maintained for
the Loads with the suppression of Harmonics.
3. Overall View of the plant
4. Analysis of the readings at the 33kV HT indoor
breaker (SAMPLE CASE)
POWER PARAMETERS
The KVA and KW are the
normal running loads during
the Time of study 3456 KW
and 3524 KVA.
The load currents are normal
during the Time of study.
800 amps VCB has been
used.
0.00
0.03
0.06
0.08
0.11
0.14
0.16
0.19
0.21
0.24
0.27
0.29
0.32
0.35
0.37
0.40
0.43
0.45
0.48
0.50
0.53
09.02.2013. 14:42:00 09.02.2013. 14:47:45Relation 1 : 1
St+ (MVA) Av g Pt+ (MW) Av g Qti+ (MVAr) Av g
Periodic s (PAKSHALA.PMD)
-
Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.
Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.
POWER FACTOR
The Reactive Power varies
with the Active Power
variation.
The system with appx. - 687
KVAR capacitors are
connected Excess.
The Power Factor are found
at Leading 0.98C at the time
of study.
CURRENT
WAVEFORM
The variations in current
harmonic levels are
recorded.
It is indicated that the
Current Harmonic levels
disturb the current
waveform.
Unbalance Current flows in
each Phase.
CURRENT
The load currents are
normal running loads
during the Time of study.
An Trms Current of 63
Amps is measured.
The Reactive Power varies
with the Active Power
variation.
HARMONIC CURRENT
The variations in current
harmonic levels are
recorded.
The average Current
Harmonic Distortion levels
are measured as 12%
It is indicated that the
Current Harmonic levels are
HIGHER the limits of
standards for Harmonics.
VOLTAGE
WAVEFORM
The variations in Voltage
harmonic levels are
recorded.
It is indicated that the
Voltage Harmonic levels
disturb the Voltage
waveform.
Unbalance in Voltage is
found each Phase.
LOAD PARAMETER:
KW
KVA
KV
AR
PF
Volt
-
ag
e
Curr
-ent
TH
D
Volt
age
(%)
TH
D
Cur
rent
(%)
Freq
-uency
Neu
tral
Cur
rent
3456
3524 -687 0.98
C
21.1
KV
63A 2 12 49.88
Hz
3.9
RECOMMENDATION:
Present P.F is in the range of 0.98
Voltage harmonics recorded is approximately 2%, which is
LOWER than the IEEE 519 Guidelines for Harmonics.
Current harmonics recorded is approximately 12%, which is
also MARGINALLY HIGHER than the IEEE 519 Guidelines
for Harmonics.
As per IEEE guidelines reading shows it is maintaining at
LEADING Power Factor and the level of Current Harmonic
is higher. As we having KVAH billing it is necessary to
maintain unity PF at all time. So it is required to install ASHF
at the Incomer of all Transformer secondary side.
5. Some sample cases of load parameter and
recommendations
A. F- 4, HUMIDIFICATION PLANT 1:
LOAD PARAMETER:
K
W
KV
A
K
V
A
R
PF
Volt
-age
Cu
rr
-
ent
TH
D
Vo
lta
ge
(%
)
T
H
D
Cu
rre
nt
(%
)
Freq
-
uency
Ne
utr
al
Cu
rre
nt
36 60 48 0.60 247 85 6.2 20 50.04 3
0.88
0.89
0.90
0.91
0.92
0.93
0.95
0.96
0.97
0.98
0.99
1.00
1.01
1.02
1.03
1.05
1.06
1.07
1.08
1.09
1.10
09.02.2013. 14:42:00 09.02.2013. 14:47:45Relation 1 : 1
Pftc + Av g Pfti+ Av g
Periodic s (PAKSHALA.PMD)
05.0
10.015.020.025.030.035.040.045.050.055.060.065.070.075.080.085.090.095.0
100.0t r igg t im e: 25. 12. 10. 12: 06: 28. 25
%
X ax is range: 1280 point strigg - 6399 points trigg - 5120 points
12.55
12.60
12.65
12.70
12.75
12.80
12.85
12.91
12.96
13.01
13.06
13.11
13.16
13.22
13.27
13.32
13.37
13.42
13.47
13.52
13.58
09.02.2013. 14:42:00 09.02.2013. 14:47:45Relation 1 : 1
I1 (A) Av g I2 (A) Av g I3 (A) Av g
Periodic s (PAKSHALA.PMD)
0
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
50.00
55.00
60.00
65.00
70.00
75.00
80.00
85.00
90.00
95.00
100.00
09.02.2013. 14:42:00 09.02.2013. 14:47:45Relation 1 : 1
thdI1 (%) Max thdI2 (%) Max thdI3 (%) Max
Periodic s (PAKSHALA.PMD) in %
05.0
10.015.020.025.030.035.040.045.050.055.060.065.070.075.080.085.090.095.0
100.0t r igg t im e: 25. 12. 10. 12: 06: 28. 25
%
X ax is range: 1280 point strigg - 6399 points trigg - 5120 points
-
Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.
Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.
RECOMMENDATION:
Present P.F is in the range of 0.6 lagging.
Voltage harmonics recorded is approximately 6.2%, which is
very much HIGHER than the IEEE 519 Guidelines for
Harmonics. Current harmonics recorded is approximately
20%, which is very much HIGHER than the IEEE 519
Guidelines for Harmonics. Neutral Current of 3 Amps has
been found flowing through Neutral.
As per IEEE guidelines plant should be maintaining at Unity
Power Factor. So it Necessary to add 60 KVAR Fixed Tuned
Filter to increase PF and Harmonic Amplification.
A. F2- SPINNING G 5/1 M/Cs 5-8:
LOAD PARAMETER:
K
W
KVA
KV
A
R
PF
Vo
lt
-
ag
e
Curr
-ent
T
H
D
Vo
lta
ge
(%
)
TH
D
Curr
ent
(%)
Freq
-
uenc
y
Ne
utr
al
Cu
rre
nt
8
0
108 72 0.7
4
24
3V
158
A
5 15 49.9
5Hz
0
RECOMMENDATION:
Present P.F is in the range of 0.74 LAGGING
Voltage harmonics recorded is approximately 5%, which is
very much MARGINALLY HIGHER than the limit IEEE
519 Guidelines for Harmonics. Current harmonics recorded
is approximately 15%, which is very much HIGHER than the
limit of IEEE 519 Guidelines for Harmonics. Neutral Current
of 0 Amps has been found flowing through Neutral.
As per IEEE guidelines plant should be maintaining at
LEADING Power Factor, while capacitor are in ON
condition. So it Necessary to add 100 KVAR Auto Switched
Harmonic Filter panel in this DB.
6. Things to be done for better power quality and
savings in the plant
1. AUTO SWITCHED HARMONIC FILTERS TO BE
INSTALLED AT ALL THE INCOMERS.
2. RING FRAME WITH INVERTER DRIVES SHOULD
BE PROTECTED WITH LINE.
3. BASED ON THE RECOMMENDATION, PASSIVE
FILTERS SHOULD BE INSTALLED AT LOAD END.
4. AFTER INSTALLING PASSIVE FILTERS,
FURTHER FOR FINE TUNING PURPOSE, ACTIVE
FILTERS SHOULD BE INSTALLED.
7. Conclusion
System has Higher Current Harmonic of 12% in 33KV, HT side.
Due to the transportation of low linear path, Effect of Harmonic is more in linear load.
By installing Filter in the Load end, improves the Lower PF and reduces cable losses. Our recommendation will help
to increase the PF, decrease the cable losses and some
percentage of Harmonic will be get filtered in load end itself.
B phase Voltage and Current recorded as Higher and phase unbalance is also found.
Excess Neutral Current is measured at the Incomer. Once three phase voltage and Current made balance, it will
get reduced.
Failure rate Electrical system will be reduced by installing tuned filters at the load end and default saving will
be achieved as per the recommendation.
REFERENCES
[1] Mauricio Aredes, Klemens Heumann, Edson H.
Watanabe, An Universal Active Power Line Conditioner,
IEEE Transactions on Power Delivery, Vol. 13, No. 2, April
1998.
[2] B. Singh, and K. Al-Haddad, A review of active filters
for power quality improvement,IEEE Transactions on
Industrial Electronics, vol. 46, no. 5, pp. 960-971, Oct. 1999.
[3] Charles. S, and G. Bhuvaneswari, Comparison of three
phase shunt active power filter algorithms, International
Journal of Computer and Electrical Engineering, vol. 2, no.
1, pp. 175- 180, Feb. 2010.
[4] S. P. Litran, P. Salmeron, J. R. Vazquez, and J. L.
Flores, Compensation of voltage unbalance and current
harmonics with a series active power filter, Renewable
Energy & Power Quality Journal, no. 3, Mar. 2005.
[5] L. Chen, and A. V. Jouanne, A comparison and
assessment of hybrid filter topologies and control
algorithms, IEEE/PESC Ann. Meeting Conf, vol. 2, pp. 565-
570.
[8] E. R. Ribeiro, and I. Barbi, Harmonic voltage
reduction using a series active filter under different load
conditions, IEEE Transactions on Power Electronics,
vol. 21, no. 5, pp. 1394-1402, Sep. 2006.
[9] KannanKarthik, and J.E.Quaicoe, Voltage
Compensation and harmonic suppression using series active
and shunt passive filters,Electrical and Computer
Engineering, Canadian conference, vol. 1, 2000, p. 582-586.
-
Proceedings of International Conference on Advances in Applied Engineering and Technology 2015, May 14-16, 2015.
Organized by Syed Ammal Engineering College, Ramanathapuram, Tamilnadu, India.
[10] H. Fujita, and H. Akagi, A practical approach
to harmonics compensation in power systems series
connection of passive and active filters,IEEE Transactions
on Industry Applications, vol. 27, no. 6, pp.1020-1025,
Nov. 1991.
[11] J.C.Das,"Power System Harmonics and
Passive Filter Designs" IEEE Press Series on Power
Engineering Series: Wiley; 2015
About the authors
P.K.Mani has completed his B.E.
Electrical and Electronics Engineering
and M.E. Power Systems Engineering at
Anna University, Chennai. At present he
is working as Associate Professor in
Electrical and Electronics Engineering
Dept, Vel Tech Multitech Dr.Rangarajan
Dr.SakunthalaEngineering college, Chennai-
600062.Currently he is doing Ph.D in Veltech
Dr.RR&Dr.SRTechnical University in the field of power
quality. Mobile. No: +91 9445260989.
Email: [email protected].
Dr.K.Siddappa Naidu finished his
B.E.Electrical Engineering from Sri
Venkateswara University, Tirupati in 1973
and got post-graduation from IISC,
Bangalore in 1976 and Ph.D. from the same
institute in 1994. He has worked in various
capacities in NGEF Transformers Research
& Development from 1979 to 2000.He
worked as HOD EEE, Vice Principal and Principal in different
Engineering colleges from 2000 to 2012.Presently working as
Dean, School of Electrical Engineering in Vel Tech Dr.RR
Dr.SR Technical University, Avadi, Chennai-600062.He has
published many papers in international and national journals.
His research interests are partial discharge measurements in
HV Insulation & Apparatus, online monitoring of HV power
apparatus, Sub synchronous, Renewable energy systems and
power quality.