    Readers are advised to check that this Certificate has not been withdr awn or superseded by a later issue by cont acting theIrish Agr ment Board, NSAI, Glasnevin, Dublin 9 or online at http://www.nsai.ie/modules/certificates/uploads/pdf/IAB070264.pdf

    CERTIFICATE No. 07/0264

    Quinn Lite, Derrylin, Co. Fermanagh,Northern Ireland, BT92 9AUTel: 048 6774 8866Fax: 048 6774 8800Email: [email protected]

    Website: www.quinn-group.com

    CI/SfB (21) Ff4

    Quinn-Lite Aircrete Blocks: B3, B5 & B7

    Blocs: Bton cellulaire autoclavGasbetonsteinen

    The Irish Agrment Board is designated by Government to issue European Technical Approvals.

    Irish Agrment Board Certificates establish proof that the certified products are proper materials suitable fortheir intended use under Irish site conditions, and in accordance with the Buil ding Regulations 1997 to 2006.

    The Irish Agrment Board operates in association withthe National Standards Authority of Ireland (NSAI) as the National Member of UEAtc.

    PRODUCT DESCRIPTION:This Certificate relates to the Quinn-Lite Aircrete B3, B5and B7 blocks of nominal densities 480kg/m

    3, 650kg/m

    3

    and 760kg/m3

    respectively, and average compressivestrengths of 3MPa, 5MPa and 7MPa respectively.

    This Certificate certifies compliance with therequirements of the Building Regulations 1997 to 2006.

    USE:The blocks are for use in masonry wall construction as

    per IS 325-1:1996 Code of practice for use of masonry Structural use of unreinforced masonry, and IS 325-2:1995 Code of practice for use of masonry Masonryconstruction.

    MANUFACTURE AND MARKETING:The product is manufactured and marketed by:

    Quinn-Lite,Derrylin,Co. Fermanagh,Northern Ireland,BT92 9AU.Tel: 048 6774 8866Fax: 048 6774 8800Email: [email protected]

    Website: www.quinn-group.com

    mailto:[email protected]://www.quinn-group.com/http://www.quinn-group.com/mailto:[email protected]
  • 7/30/2019 IAB - Quinn-Lite Blocks

    2/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    Part One / Certification 1

    C4 Resistance to Weather and GroundMoisture

    1.1 ASSESSMENTIn the opinion of the Irish Agrment Board (IAB),Quinn-Lite Aircrete B3, B5 and B7, if used inaccordance with this Certificate can meet therequirements of the Building Regulations 1997 -2006 as indicated in Section 1.2 of thisCertificate.

    Quinn-Lite Aircrete B3, B5 and B7 when installedin compliance with the conditions indicated inPart 2 of this Certificate will not promote thepassage of moisture and will minimise the risk ofsurface of interstitial condensation.

    1.2 BUILDING REGULATIONS 1997 to 2006 Part E SoundE1 Airborne sound (Walls)

    REQUIREMENT: Walls constructed using Quinn-Lite Aircrete B5and B7 blocks in accordance with this Certificate,will meet the airborne sound requirements of thisRegulation.

    Part D Materials and WorkmanshipD3 Quinn-Lite Aircrete B3, B5 and B7, as

    certified in this Irish Agrment Certificate arecomprised of proper materials fit for theirintended use (see Part 4 of this Certificate).

    Part F VentilationF1 Means of Ventil ationAdequate ventilation openings can be provided inexternal and internal walls to meet thisrequirement.

    D1 Quinn-Lite Aircrete B3, B5 and B7, ascertified in this Certificate, can meet therequirements of the building regulations forworkmanship. F2 Condensation

    Adequate ventilation can be provided in order tomeet this requirement in respect of the preventionof condensation (see Part 4 of this Certificate).

    Part A StructureA1 LoadingQuinn-Lite Airecrete B3, B5 and B7, as certifiedin this Certificate, have adequate strength andstability (see Part 4 of this Certificate).

    Part J Heat Producing AppliancesJ3 Protection of Building

    In the opinion of the Irish Agrment Board (IAB)Quinn-Lite Aircrete B3, B5 and B7, if used inaccordance with this Certificate, meet therequirements of the Building Regulations 1997 to2006.

    Part B Fire SafetyB2 Internal Fire Spread (Linings)Quinn-Lite Aircrete B3, B5 and B7 are non-combustible. Therefore with traditionalplasterboard finishes to ceilings, the blocks canbe used in buildings of all purpose groups,providing the buildings are adequately designedin respect of fire safety.

    Part L Conservation of Fuel and EnergyL1 - Conservation of Fuel and EnergyQuinn-Lite Aircrete B3, B5 and B7 will contributeto the thermal resistance of walls and to thereduction of surface condensation risks.B3 Internal Fire Spread (Structure)

    Walls using Quinn-Lite Aircrete B3, B5 and B7meet the requirement, provided the completedwalls comply with the conditions described inSection 4.1 of this Certificate.

    Part M Access for People with DisabilitiesM1 Access and UseThe provision of access, circulation and facilitiesas required under this Regulation is notcomprised through the use of Quinn-Lite AircreteB3, B5 and B7.

    B4 External Fire SpreadQuinn-Lite Aircrete B3, B5 and B7 have a Class 0surface spread of flame rating, and when used inthe context of this Certificate, can satisfy therequirements of this Regulation.

    Part C Site Preparation and Resistance toMoistureC3 Dangerous SubstancesWhere it is shown that protection from dangeroussubstances e.g. Radon, is required, an approvedgas resistant membrane and gas handlingsystem must be provided under the ground floor.

    Construction with Quinn-Lite Aircrete B3, B5 andB7 blocks permits the easy incorporation of theappropriate membrane, sump and gas handlingsystem.

  • 7/30/2019 IAB - Quinn-Lite Blocks

    3/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    Part Two / Technical Specification and Control Data 2

    2.1 PRODUCT DESCRIPTIONQuinn-Lite Aircrete B3, B5 and B7 blocks are foruse in masonry wall construction as per IS 325-1:1996 and IS 325-2:1995. The blocks areavailable in a range of sizes and strengths, asshown in Table 1.

    Length 440mm

    Height 215mm

    Thickness*100, 115, 125, 150, 215, 275 and300mm

    StrengthB3: 3MpaB5: 5MpaB7: 7MPa

    Dry DensityB3: 480kg/m

    3

    B5: 650kg/m3

    B7: 760kg/m3

    Thermal

    Conductivity ()B3: 0.12W/mKB5: 0.17W/mKB7: 0.19W/mK

    * Quinn-Lite blocks for foundations are 440 x 215 x 300mm

    Table 1: Product Range

    Quinn-Lite B3 is certified for use in theconstruction of internal walls, including use ininner leaf of cavity walls. The use of Quinn-Lite

    B3 blocks below dpc level is not recommended. Itcan be used as a foundation block under thecontrol of an engineer after checking the soil forsuitability in respect of sulphates.

    Quinn-Lite B5 and B7 are certified for use in theconstruction of loadbearing and non-loadbearinginternal and external walls above and below dpclevel, including use in inner and outer leaves ofcavity walls. If placing slabs on blocks, aminimum size of 150mm block is recommended,however approval must be obtained from anengineer to ensure the strength of the blocks willcarry the weight of the slabs.

    When used below dpc level, includingfoundations, it is recommended that the mortarfor the laying of the blocks be 1:1:4cement/lime/sand.

    For external build, Quinn-Lite Aircrete blocksmust be rendered using Weber.pral D render.Details of approved applicators must be obtainedfrom Weber Building Solutions Ltd.

    Quinn-Lite B3, B5 and B7 are CFC and HCFCfree and therefore have zero ozone depletionpotential (zero ODP).

    2.2 MANUFACTUREThe blocks are manufactured in accordance withthe test requirements of IS EN 771-3:2005Specification for masonry units Aggregate

    concrete masonry units (dense and lightweightaggregates) and IS EN 771-4:2005 Specificationfor masonry units Autoclaved aerated concretemasonry units.

    2.2.1 Quality Contro lQuality control checks are carried out on theincoming raw materials, during production and onthe finished product. These checks includecompressive strength, density and dimensionalaccuracy.

    2.3 DELIVERY, STORAGE AND MARKINGThe blocks are supplied banded and shrink-

    wrapped on pallets, with a label showing themanufacturers name, IAB identification mark andIAB Certificate number. Each block type has adifferent coloured band: yellow for B3, blue for B5and red for B7.

    The blocks must be stored clear of the ground ona firm level surface and protected from saturation.The shrink-wrapping should be kept in place untilthe blocks are ready for use.

    2.4 INSTALLATIONBedding Mortar Detail1:1:6 Cement/lime/sand mix must be used above

    dpc level 1:4 cement/sand with plasticizer is tobe used for below dpc level. Moisten lime to forma lime putty before adding the cement and sand.A dash of mortar mix may be added. Ifnecessary, dampen the blockwork with a brushto overcome surface absorption before laying themortar. Alternatively other designation IIIreadymix mortar can be used as listed in BS5628-3:2005 Code of practice for the use ofmasonry Materials and components, designand workmanship.

    LintelsSteel lintels are recommended when usingQuinn-Lite Aircrete blocks to prevent coldbridging. If full fill insulation is used in the cavity,concrete lintels can be used but metal lathingshould be placed over the face of the lintel(extending 300mm over each edge) beforeplastering. Concrete lintels can also be used overinternal doors.

    External FinishThe external render must be Weber.pral D, usedwith a Weber.rend aid stipple coat. Thisrendering system must be applied on site bytrained approved applicators (see Section 2.1).

    Chasing

    In accordance with the Building Regulations1997 to 2006, vertical chasing in walls should notbe deeper than one third the thickness of the

  • 7/30/2019 IAB - Quinn-Lite Blocks

    4/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    wall, and horizontal chasing not deeper than onesixth the thickness of the wall.

    Quinn-Lite Aircrete blocks are easily sawn,chased and drilled with standard tools. A discsaw is ideal for cutting tracks in the wall, and a

    chisel is then used to remove the excessmaterial. Tools with hammer actions must not beused to remove excess material.

    FixingsCut nails or spiral nails can be used forlightweight fixings. Figure 1: Cavity Wall Tie

    Nylon plugs, suitable for hanging kitchen unitsand frame fixers, can be used for heavyweightfixings. Expanded metal fixings or plastic plugsare not to be used.

    Not all standard fixings suitable for use with

    dense aggregate blocks can be used in similarsituations with aircrete blocks. Quinn-Litetechnical department should be contacted forfurther information on fixings.

    Movement JointsMovement joints to be used as per IS 325-2:1995The maximum recommended spacing ofmovement joints should be 5m and bed jointreinforcement should be used at window opes.

    Temporary propping should be considered wherehigh walls are being constructed. It is advisableto prop gable walls and any long stretches of wallwhere return walls have not yet been built untilpermanent bracing is provided by the roofstructure.

    Party WallsQuinn-Lite B5 or B7 blocks are suitable for use inparty wall construction. There are two types ofparty wall that can be used: a solid block 215mmthick, sheeted on both sides with 50mmMoyisover Calibel insulated plasterboard slab; ora cavity wall comprising two leaves of 100mmblock with a 75mm cavity between them, and50mm Moyisover Calibel board on the room sideof each leaf. The inner leaf of the perimeter wall(flanking wall) adjoining the party wall must also

    be lined with Moyisover Calibel board. The partywalls and flanking walls should be plastered priorto the fixing of the Moyisover Calibel boardswhich should cover all areas, including thespaces between ceiling joists. No cut-outs forservices such as electrical plugs and switchesshould be made in the Moyisover Calibel boards.

    Quinn-Lite B3 is suitable for use in theconstruction of internal walls, including use ininner leaf of cavity walls.

  • 7/30/2019 IAB - Quinn-Lite Blocks

    5/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    12.5mm plaster

    Figure 2: Typical Bui ld for B5 Party Wall (5N)

    Figure 3: Typical Build for B5 Party Wall (5N) Plan View

    50mm MoyisoverCalibel board

    Quinn-Lite100mm B5

    75mm cavityQuinn-Lite

    215mm B5

    Flexible cavity closerQuinn-Lite100mm B5

    12.5mm plaster

    50mm MoyisoverCalibel board

    Note: The inner leaf of the perimeter wall, adjoiningthe separating/party wall must also be linedwith Moyisover Calibel board. The board onthis wall must continue until it joins the nextpartition wall or party wall.

    Note: Spaces left at the junction of the floor and theMoyisover Calibel board must be filled withglass wool before skirting goes on. The boardmust continue to be fitted between joists.Joist hangers to be used instead ofpenetrations in block work.

    75mm cavity

  • 7/30/2019 IAB - Quinn-Lite Blocks

    6/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    DPC

    Quinn Therm PIRInsulation

    Normal external render

    Radon barrier Flooring

    Dense concrete blockSand blinding

    Figure 4: Quinn-Lite Foundation Block

    Note: 150mm above and below groundlevel requires minimum B5 block

    HardcoreQuinn-Lite FoundationBlock B5 or B7 (B3subject to siteinvestigation)

    Radon resistingsealing tape

    Concrete slab

  • 7/30/2019 IAB - Quinn-Lite Blocks

    7/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    Two layers of austenitic stainlesssteel bed joint reinforcementabove and below openings

    Figure 5: External Wall Detail

    Figure 6: Lintel Detail

    Movement joints inserted every 5m

    Weber pral.Dexternal render

    Steel lintel

    Quinn-Lite 100mm B5 Quinn-Lite 100mm B5

    Dry lining plasterboard toprevent cold bridging

    Steel lintel

    Quinn Therm PIR Insulation

  • 7/30/2019 IAB - Quinn-Lite Blocks

    8/13

  • 7/30/2019 IAB - Quinn-Lite Blocks

    9/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    Part Three / Design Data 3

    3.1 STRENGTH AND STABILITYStrength properties of Quinn-Lite Aircrete B3, B5and B7blocks are shown in Table 1.

    The design loads to be taken should bedetermined in accordance with BS 6399-1:1996Loading for buildings Code of practice for deadand imposed loads, BS 6399-2:1997 Loading forbuildings Code of practice for wind loads andBS 6399-3:1988 Loading for buildings Code ofpractice for imposed roof loads.

    Wind loads should be based on the windexposure map shown in Diagram 15 of Technical

    Guidance Document to Part A of the BuildingRegulations 1997 to 2006. Snow loads should bebased on the map shown in Diagram 14 of TGDto Part A of the Building Regulations 1997 to2006.

    Cavity BarriersA Quinn-Lite cavity wall can be treated the sameas a conventional masonry cavity wall, i.e.Diagram 17 of TGD to Part B of the BuildingRegulations 1997 to 2006 applies.

    3.2 STRUCTURAL FIRE SAFETYQuinn-Lite Aircrete blocks are non-combustible

    and have a Class 0 surface spread of flamerating in accordance with Part B of the BuildingRegulations 1997 to 2006.

    Acrylic renders are not approved for use with theQuinn-Lite blocks.

    3.3 FOUNDATION DESIGNFoundation design should be in accordance withBS 8004:1986 Code of practice for foundations,BS 8103-1:1995 Structural design of low-risebuildings Code of practice for stability, siteinvestigations, foundations and ground floorslabs, and Part A of the Building Regulations1997 to 2006.

    3.4 IMPACT RESISTANCEThe external walls are finished on the outsidewith Weber.pral D render. With this render on thesubstrate of the Quinn-Lite Aircrete blocks, thereis little risk of external impact damage to thestructure. With regard to internal impacts, theplaster on the Quinn-Lite Aircrete blocks has adurability to impact similar to traditional masonry.

  • 7/30/2019 IAB - Quinn-Lite Blocks

    10/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    Part Four / Technical Investigations 4

    4.1 BEHAVIOUR IN FIREQuinn-Lite Aircrete B3, B5 and B7 blocks have aClass 0 fire rating. The required thickness ofmasonry wall for a lightweight concrete block fora particular duration of fire resistance is given inTable 16a of IS 325-2:1995. The table shows thata Quinn-Lite Aircrete block has the sameperformance as a conventional dense aggregateblock.

    4.2 PHYSICAL EFFECTS OF MOISTUREWhen used externally, the blockwork shall berendered as detailed in Part 2 of this Ceritifcate inaccordance with IS EN 13914-1:2005 Design,

    preparation and application of external renderingand internal plastering External rendering. Theadvice of IS 325-2:1995 should be followed inrespect of exposure analysis and building details.

    4.3 SOUND INSULATIONThe sound insulation of Quinn-Lite B5 and B7used in party wall construction (as detailed inPart 2 of this Certificate) have been assessedand shown to be in compliance with Part E of theBuilding Regulations 1997 to 2006.

    4.4 THERMAL INSULATIONThe thermal conductivities of Quinn-Lite B3, B5

    and B7 are shown in Table 1. Typical U-valuesare shown in Table 2, calculated in accordancewith Part L of the Building Regulations 1997 to2006.

    4.5 CONDENSATIONCalculations in accordance with BS 5250:2002Code of practice for control of condensation inbuildings, show that the level of insulationprovided by the Quinn-Lite block masonry wallswith Weber.pral D render externally and 13mmlightweight plaster internally should minimise therisk of surface or interstitial condensation in allnormal environments in dwellings. As with all wallconstruction, care must be taken when installingthe dpc below windows to ensure that anycondensation occurring on the window is drainedoutwards.

    4.6 DURABILITYBuildings constructed using Quinn-Lite B3, B5and B7, when constructed in accordance with themanufacturers instructions and the requirementsof this Certificate and all relevant codes ofpractice, will have a design life of60 years inaccordance with BS 7543:2003 Guide todurability of buildings and building elements,products and components. Buildings based onthe manufacturers recommendations, provided

    they are properly erected and that construction iscarried out properly and accurately, should givegood performance under all relevant headingsthroughout their working life.

    Element Thickness (mm)Calculated U-Value(W/m

    2K)

    Render 15

    Quinn-Lite B5 100

    Cavity 25

    Polyisocyanurate 45

    Quinn-Lite B7 100

    Plaster 12.5

    0.27

    Render 15

    Quinn-Lite B5 100

    Cavity 25

    Polyisocyanurate 60

    Quinn-Lite B7 100

    Plaster 12.5

    0.23

    Render 15

    Quinn-Lite B5 100

    Cavity 25

    Polyisocyanurate 45

    Quinn-Lite B5 100

    Plaster 12.5

    0.27

    Render 15

    Quinn-Lite B5 100

    Cavity 25

    Polyisocyanurate 60

    Quinn-Lite B5 100

    Plaster 12.5

    0.22

    Render 15

    Quinn-Lite B5 100

    Cavity 25

    Polyisocyanurate 40

    Quinn-Lite B3 100

    Plaster 12.5

    0.27

    Render 15

    Quinn-Lite B5 100

    Cavity 25

    Polyisocyanurate 60

    Quinn-Lite B3 100

    Plaster 12.5

    0.21

    Render 20

    Dense blockwork 100

    Cavity 25

    Polyisocyanurate 75

    Quinn-Lite B5 150

    Plaster 12.5

    0.20(A-Rated House: refFigure 8)

    Table 2: Estimated U-values

  • 7/30/2019 IAB - Quinn-Lite Blocks

    11/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    4.7 TESTS AND ASSESSMENTS WERE CARRIEDOUT TO DETERMINE THE FOLLOWING:

    Dimensional accuracy

    Dry density

    Compressive strength

    Assessment of freeze/thaw resistance

    Thermal conductivity

    Acoustic performance

    Drying shrinkage

    4.8 OTHER INVESTIGATIONS(i) Existing data on product properties in relation

    to fire, toxicity, environmental impact and theeffect on mechanical strength/stability anddurability were assessed.

    (ii) The manufacturing process was examinedincluding the methods adopted for qualitycontrol, and details were obtained of thequality and composition of the materials used.

    (iii) Site visits were conducted to assess thepracticability of installation and the history ofperformance in use of the product.

    (iv) A condensation risk analysis was performed.

  • 7/30/2019 IAB - Quinn-Lite Blocks

    12/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    Part Five / Conditions of Certification 5

    5.1 National Standards Authority of Ireland 5.4 This Certificate does not comprise installation("NSAI") following consultation with the IrishAgrment Board ("IAB") has assessed theperformance and method of installation of theproduct/process and the quality of the materialsused in its manufacture and certifies theproduct/process to be fit for the use for which it iscertified provided that it is manufactured,installed, used and maintained in accordancewith the descriptions and specifications set out inthis Certificate and in accordance with themanufacturer's instructions and usual tradepractice. This Certificate shall remain valid for fiveyears from date of issue so long as:

    instructions and does not replace themanufacturer's directions or any professional ortrade advice relating to use and installation whichmay be appropriate.

    5.5 Any recommendations contained in thisCertificate relating to the safe use of the certifiedproduct/process are preconditions to the validityof the Certificate. However the NSAI does notcertify that the manufacture or installation of thecertified product or process in accordance withthe descriptions and specifications set out in thisCertificate will satisfy the requirements of the

    Safety, Health and Welfare at Work Act. 1989, orof any other current or future common law duty ofcare owed by the manufacturer or by theCertificate holder.

    (a) the specification of the product is unchanged.

    (b) the Building Regulations 1997 to 2006 andany other regulation or standard applicable tothe product/process, its use or installationremains unchanged.

    5.6 The NSAI is not responsible to any person orbody for loss or damage including personalinjury arising as a direct or indirect result of theuse of this product or process.(c) the product continues to be assessed for the

    quality of its manufacture and marking byNSAI. 5.7 Where reference is made in this Certificate to

    any Act of the Oireachtas, Regulation madethereunder, Statutory Instrument, Code ofPractice, National Standards. Manufacturer's

    instructions, or similar publication, it shall beconstrued as reference to such publication in theform in which it is in force at the date of thisCertification.

    (d) no new information becomes available whichin the opinion of the NSAI, would preclude the

    granting of the Certificate.

    (e) the product or process continues to bemanufactured, installed, used and maintainedin accordance with the description,specifications and safety recommendationsset out in this certificate.

    (f) the registration and/or surveillance fees dueto IAB are paid.

    5.2 The IAB mark and certification number mayonly be used on or in relation toproduct/processes in respect of which a validCertificate exists. If the Certificate becomesinvalid the Certificate holder must not use the IABmark and certification number and must removethem from the products already marked.

    5.3 In granting Certification, the NSAI makes norepresentation as to;

    (a) the absence or presence of patent rightssubsisting in the product/process; or

    (b) the legal right of the Certificate holder tomarket, install or maintain theproduct/process; or

    (c) whether individual products have beenmanufactured or installed by the Certificateholder in accordance with the descriptionsand specifications set out in this Certificate.

  • 7/30/2019 IAB - Quinn-Lite Blocks

    13/13

    Certificate No. 07/0264 / Quinn-Lite Aircrete Blocks: B3, B5 & B7

    The Irish Agrment Board

    This Certificate No. 07/0264is accordingly granted by the NSAI to Quinn-Lite on behalf of The Irish AgrmentBoard.

    Date of Issue: February 2007

    Signed

    Director of the Irish Agrment Board

    Readers may check that the status of this Certificate has not changed by contacting the Irish AgrmentBoard, NSAI, Glasnevin, Dublin 9, Ireland. Telephone: (01) 807 3800, Fax: (01) 807 3842, www.nsai.ieRevisions: May 2007:

    Inclusion of new illustrations for party wall and external wall details.

    Amendments to sections related to sound and external finish.