Compute Project HVDCHigh Voltage Direct Current12V Server Rack System Sept. 18, 2014 Onishi Hiroyuki HVDC-WG, OCPJ This material includes the information prepared by companies of HVDC-WG members, CTC Techno- Solutions, NTT Data Intellilink, NTT Facilities, Panasonic & Yutaka Electronics Industry. When referring to the content on this, please consult with each company.

Upload: others

Post on 20-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Compute Project

HVDC(High Voltage Direct Current)+ 12V Server Rack System

Sept. 18, 2014Onishi Hiroyuki HVDC-WG, OCPJ

This material includes the information prepared by companies of HVDC-WG members, CTC Techno-Solutions, NTT Data Intellilink, NTT Facilities, Panasonic & Yutaka Electronics Industry. When referring to the content on this, please consult with each company.

Compute Project

OCP-J HVDC-WGHVDC((High Voltage Direct Current) is one of technology reducing Power Loss between commercial power and IT equipment, and improving reliability in data centers.

HVDC-WG(1) Promotion Activity of HVDC + 12Vdc technology & solutions(2) Standardization Activity with GUTP(Green University of Tokyo project) DCIM-WG

HVDC-SWG

Action PlanBased on Standardization activities w/ GUTP & JDCC(planned),

- conduct the HVDC+12Vdc validation & Verification of inter-connectivity & performance on OCP OpenRack.

- study the feasibility with rack-mount & in-chassis battery- promote the product lineup including 12Vdc IT equipment & 12Vdc pass through box

[email protected]

Compute Project

Background

Exhibition: Fact-finding 2012 version of a datacenter market and power consumption

Data center

IT equip

CoolingLightingSecurity

MBUPS

GeneratorPower to DC

Power to IT

Power to MISC

Computing

Power consumption of AC/DC, DC/DC conversion in servers is approx. 30-35%⇒ 12Vdc

Power loss of AC/DC, DC/AC conversion in power feeding is approx. 20-30%⇒ HVDC

Compute Project

HVDC DC12V Power Supply System reduces AC/DC conversions between commercial power and IT Equipment. Power loss is reduced by 10-20%.

CPU/MEM/HDD

CPU/MEM/HDD

Energy Saving

100Vac-200Vac

340Vdc-380Vdc

Compute Project

Power Feeding inside Data Center - Virginia Tech

SW MGTインバータDC/AC

SW

SWSW

SW

変圧器

変圧器

変圧器変圧器

変圧器

変圧器

蓄電池

発電装置発電装置

アナログ

IC

LED

FAN

マイクロプロセッサ

DC/DC

AC/DC

非絶縁型DC/DC

DC/ACAC/DC

INV.

モータ

マイクロプロセッサ

モータ

分散型電源 SW

SW

SW 蓄電池

PFC整流器

PFC整流器

DC/DC

絶縁型DC/DC

蓄電池

DC/AC

AC/DC蓄電池

DC/AC

AC/DC SW

変圧器 INV.

SW

変圧器

SWアナログ

IC

LEDFAN

メモリ

デジタル

IC

ASIC

非絶縁型DC/DC

メモリ

デジタル

IC

ASIC

防災用照明設備 警報設備

通信用装置・電源

UPSサーバー

データコム装置

照明

空調設備

ファン・ポンプ

出典:バージニア工科大学、パワーエレクトロニクスセンタ資料を元に一部加工

DC -48V

AC 三相480V

AC 三相480V

AC 単相120V

AC 単相120V

AC 単相120V

AC 単相24V

AC 単相120V

AC 単相120V DC

48V

•非効率で無駄が多い•信頼性も低い•高価なシステム

受電

(注)SWは、切替盤、開閉器、遮断器、分電盤等を含む

SW MGTインバータDC/AC

SW

SWSW

SW

変圧器

変圧器

変圧器変圧器

変圧器

変圧器

蓄電池

発電装置発電装置

アナログ

IC

LED

FAN

マイクロプロセッサ

DC/DC

AC/DC

非絶縁型DC/DC

DC/ACAC/DC

INV.

モータ

マイクロプロセッサ

モータ

分散型電源 SW

SW

SW 蓄電池

PFC整流器

PFC整流器

DC/DC

絶縁型DC/DC

蓄電池

DC/AC

AC/DC蓄電池

DC/AC

AC/DC SW

変圧器 INV.

SW

変圧器

SWアナログ

IC

LEDFAN

メモリ

デジタル

IC

ASIC

非絶縁型DC/DC

メモリ

デジタル

IC

ASIC

防災用照明設備 警報設備

通信用装置・電源

UPSサーバー

データコム装置

照明

空調設備

ファン・ポンプ

SW MGTインバータDC/AC

SW

SWSW

SW

変圧器

変圧器

変圧器変圧器

変圧器

変圧器

蓄電池

発電装置発電装置

アナログ

IC

LED

FAN

マイクロプロセッサ

DC/DC

AC/DC

非絶縁型DC/DC

DC/ACAC/DC

INV.

モータ

マイクロプロセッサ

モータ

分散型電源 SW

SW

SW 蓄電池

PFC整流器

PFC整流器

DC/DC

絶縁型DC/DC

蓄電池

DC/AC

AC/DC蓄電池

DC/AC

AC/DC SW

変圧器 INV.

SW

変圧器

SWアナログ

IC

LEDFAN

メモリ

デジタル

IC

ASIC

非絶縁型DC/DC

メモリ

デジタル

IC

ASIC

防災用照明設備 警報設備

通信用装置・電源

UPSサーバー

データコム装置

照明

空調設備

ファン・ポンプ

出典:バージニア工科大学、パワーエレクトロニクスセンタ資料を元に一部加工

DC -48V

AC 三相480V

AC 三相480V

AC 単相120V

AC 単相120V

AC 単相120V

AC 単相24V

AC 単相120V

AC 単相120V DC

48V

•非効率で無駄が多い•信頼性も低い•高価なシステム

受電

(注)SWは、切替盤、開閉器、遮断器、分電盤等を含む

transformer transformerGenerator generator

3φ 480V

3φ 480V

Power Source INV

transformer transformer

transformertransformer transformer

Air Conditioner

1φ motor motor

Fan, Pump Light

batterybattery

1φ 1φ

Emergency Light Alarmtransformer

1φ 1φ

Server

battery

battery

Rctfy

RctfyDC/DC

DC/DCDC/DC microprocesser

microprocesser

MEM

MEM

Information ProcessingCommunication Processing

Reference: Virginia Tech Institute

Compute Project

Distributed Power Source Battery SW

SW

SW

SW

SW

MGT

DC/DC AC/DCBiDirDC/DC

BiDirAC/DC

DC/DC

DC/DC

DC/DC

DC/DC

INV.

INV.

Motor

Server

Motor

Server

Commercial Power

Server

Server

DC/DC

DC/DC

アナログ

IC

LED

メモリ

デジタル

IC

ASIC

FAN

CPU

DC/DC

アナログ

IC

LED

MEM

デジタル

IC

ASIC

CPU

FAN

アナログ

IC

LED

FAN

DC/DC

DC/DC

HVD

C #

0

HVD

C #

1

Power for 1st floor

Power for 2nd floor

DC 48V

DC 200Vバス

DC 200Vバス

DC 48V

Cooling, Fan, Pump

Light

Light

DC 12V

DC 3VDC0.8V

DC 12V

DC 3V

Emergency, AlarmComm EquipInformation Processing

Simplified HVDC Power Feeding – Virginia Tech

Cooling, Fan, Pump

Reference: Virginia Tech Institute

Compute Project

Prevailing HVDC

2009年

2014年

Compute Project

SERVER RACK

PS RACK

AC

HVDCTransformers

Battery

PowerOutage

six-phase full wave rectification DC340V

Phase shift 30°

Y結線3相交流

Δ結線3相交流

3 phase Delta Connection

3 phase Star Connection

Battery voltage DC288V

12V Server

12V Server

12V Server

48V Server

48V Server

48V Server

AC Server

AC Server

AC Server

DC/DC

340V - 12V

DC/DC

340V - 48V

DC/AC

340V - AC

HVDC - Basic system configuration

265Vac

340Vdc

Compute Project

Green Higher Reliabilityw/ Safe Technology for DC future Technology

90+% Power-feeding Efficiency Incremental Rack-Mounting of

Centralized Power Unit Space Saving

Simple Architecture Maintenance w/o Shutdown No Switching at Blackout Few Power Components

(no electrolytic capacitor, no fans) No PSUs on IT equipment

Arc Suppression Fluctuation Suppression Mid-point grounding with high

resistances 12Vdc IT equipment

Photovoltaic Generation(Solar Power) Fuel Cell Super Conductor Feeding LED light (Trouble Indication) LED communication

dcDC(direct current Data Center) Advantage

Compute Project

ACDCACACIn

DC

Battery

Switch

UPS

DCACMother Board

AC ITE ( Server )

DCAC

DCACACIn

Battery HVDC

MotherBoard

DC12V ITE ( Server )

Path-ThroughDCDC

Non-Voltage Flicker, Non-Stop, Non-

Interruptible Power through N+1

Redundant Operation

Failure Point

Failure Point

Failure Point

Failure PointFailure Point

Non-Voltage Flicker, Non-Stop, Non-

Interruptible Power through N+1

Redundant Operation

Simple Architecture = less component & failure points

HVDC + DC12V

Reliability

Compute Project

High Voltage Arc

Compute Project

Safety Technology

Server Rack

Battery

PS Rack

DCAC~

PDU

HVDC

AC DC12V Mother BoardCPU Memory HDD

Server(DC12V)

Key Technology : Middle Point GroundKey Technology : Bus Bar

DCHVDCDC340VDC340V

Key Technology : Arc Suppression Circuit (video)

Plug & Receptacle

Key Technology : Arc Suppression Circuit (video)

Plug & Receptacle

Central Redundant

Power Supply

Compute Project

Arc Suppression

13

Compute Project

Safety (HVDC Plug & Receptacle)

Socket-OutletPlug

PowerSource

ICTEquipment

PinTerminal

Electrical Shock

Undesired or unintended DC arcing interlock

switch

Compute Project

AC(UPS)

OCP Openrack@CTC TSC lab

AC⼊⼒

6φ AC

HVDC

HVDC Power SourceHVDC cabinetController, Rectifier, Battery)

ΔY Transformer10kW

HVDC trial w/ Openrack

From Sept. to Dec., 2014CTC TSC, Kudan, TOKYO

Rack-Mount LiB will be installed in Nov.

ACtoDC converter

dc12VOCP

Servers

dc12VOCP

Servers

HVDCtoDCconverter

LiB

Compute Project

Efficiency HVDC+12Vdc vs 200Vac

Safety Electrification mid-point ground & leak detector Arc measures

Reliability Trouble incl. Blackout Features Maintenability (Rectifier, PSU)

Validation, Verification & Demonstration

60.0 %

65.0 %

70.0 %

75.0 %

80.0 %

85.0 %

90.0 %

95.0 %

12.5% 25.0% 37.5% 50.0% 62.5% 75.0% 87.5% 100.0%

効 率

負荷率 ( % )

効率⽐較

9.0%

18.0%

8.4%

60.0 %

65.0 %

70.0 %

75.0 %

80.0 %

85.0 %

90.0 %

95.0 %

12.5% 25.0% 37.5% 50.0% 62.5% 75.0% 87.5% 100.0%

効 率

負荷率 ( % )

効率⽐較

9.0%

18.0%

8.4%

Compute Project

Sept. 19, 2014 Lab TourTime

Round 1 14:00 pm - 15:10 pmRound 2 15:30 pm - 16:40 pm

PlaceCTC TSC(Technical Solution Center)Kurita-Kudan bldg., Fujimi 1-11-5,Chiyoda, TOKYOhttp://www.ctc-g.co.jp/about/corporate/access/tsc_kudan.html

Agenda - Round 1(Round 2)14:00 pm(15:30pm)

welcome - Onishi, NTT Comware14:10 - 14:30(15:40 - 16:00)TSC overview - Koizumi-san, CTC

HVDC trial Overview - Mura-san, NTT Data Intellink14:30 - 15:00(16:00 - 16:30)

Lab tour & demonstaration- Thakur-san & Koizumi-san, CTC- Mura-san, NTT Data Intellink

15:00 - 15:10(16:30 - 16:40)Wrap Up