hvac vavselect-90min part1

Upload: mohdnazir

Post on 03-Apr-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 HVAC Vavselect-90min Part1

    1/20

    Selecting VAV Terminals for

    Acceptable IAQ

    Selecting VAV Terminals forSelecting VAV Terminals for

    Acceptable IAQAcceptable IAQ

    Dan Int-HoutChief Engineer, Krueger

    Richardson, Texas

  • 7/28/2019 HVAC Vavselect-90min Part1

    2/20

    Where We Are Today:Where We Are Today:

  • 7/28/2019 HVAC Vavselect-90min Part1

    3/20

    The Rules

  • 7/28/2019 HVAC Vavselect-90min Part1

    4/20

    Air Distribution DeviceAir Distribution Device

    Selection GuidelinesSelection Guidelines

    The ASHRAE fundamentals handbook, chapter 20 (AirDistribution), provides guidance on several methods of airdistribution.

    Methods include overhead fully mixed, as well as fullystratified and partially mixed systems from below, and even

    task /ambient personal air delivery systems. Described delivery systems include constant and variable

    volume, UFAD, displacement ventilation and chilled beamsystems.

    All have advantages and disadvantages, which must beunderstood by the design engineer and architect.

  • 7/28/2019 HVAC Vavselect-90min Part1

    5/20

    Well Mixed system design

  • 7/28/2019 HVAC Vavselect-90min Part1

    6/20

    Air Distribution DeviceAir Distribution Device

    Selection GuidelinesSelection Guidelines

    For overhead well mixed systems, one shouldselect a unit with throw at max, and minimum, flowthat meets ADPI guidelines based on diffuserspacing and T50 (throw to 50 fpm).

    Additionally, select for maximum mixing:

    Noise can be good.

    Dirt on the ceiling is not bad.

    Air Distribution Effectiveness (ADE) is a new term

    describing room air mixing, and is a parameterwith all delivery methods.

  • 7/28/2019 HVAC Vavselect-90min Part1

    7/20

    ADE (Ez)ADE (Ez)

    Air Distribution Effectiveness replaces ventilationefficiency and other terms.

    Older ASHRAE 62-99 minimum outside air quantitieswere based on an Ez = 1.

    Tests using ASHRAE 129 show that with ceilingcooling systems, Ez always = 1.

    Heating system performance, however, can reduce Ezto less than 70% (as low as 20%).

    Current Std 62 (from addendum N) wording sets Ez =0.8 when heating when rules not followed.

  • 7/28/2019 HVAC Vavselect-90min Part1

    8/20

    POORLY ADJUSTED / SELECTED DIFFUSER

    THERMOSTAT

    Air Distribution, Poor PatternAir Distribution, Poor Pattern

    ExampleExample

  • 7/28/2019 HVAC Vavselect-90min Part1

    9/20

    Air Distribution, Poor PatternAir Distribution, Poor Pattern

    ExampleExample

    THERMOSTAT

    POORLY ADJUSTED / SELECTED DIFFUSER

  • 7/28/2019 HVAC Vavselect-90min Part1

    10/20

    PROPERLY ADJUSTED DIFFUSER

    THERMOSTAT

    Good Pattern ExampleGood Pattern Example

  • 7/28/2019 HVAC Vavselect-90min Part1

    11/20

    ADPI Air DiffusionADPI Air Diffusion

    Performance IndexPerformance Index Single Number Rating: % of points in a room that meet a

    comfort criteria based on temperature differences andairspeeds.

    In practice, a measure of well mixed.

    In ASHRAE fundamentals since 1967.

    Agrees with ASHRAE & ISO comfort requirements.

    Can be predicted from a table in ASHRAE fundamentals,Chapter 20.

    Can be measured using ASHRAE 113.

    Selection to achieve acceptable ADPI was first recommended inreview draft of std 62-89, and is in the current ASHRAE

    Fundamentals handbook, Chapter 20. ADPI is the ONLY means of documenting compliance to

    Standard 55 in the design phase.

  • 7/28/2019 HVAC Vavselect-90min Part1

    12/20

    ASHRAE Journal, 2004ASHRAE Journal, 2004

  • 7/28/2019 HVAC Vavselect-90min Part1

    13/20

    2 x L2 x L

    (Separation)(Separation)

    Area Conditioned by DiffuserArea Conditioned by Diffuser

    44--way Diffuserway Diffuser

    SelectionSelection

  • 7/28/2019 HVAC Vavselect-90min Part1

    14/20

    Perforated 24X24, 10 inlet, 4 way, 20 Delta-T

    2

    4

    6

    8

    10

    12

    14

    16

    0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

    CFM/Sq.Ft.

    1/2UnitSeparationDis

    tance

    420350

    300

    250

    160

    Range

    Spacing for 80% ADPI

    NC=35

    CFM

  • 7/28/2019 HVAC Vavselect-90min Part1

    15/20

    Prism 24x24

    0

    4

    8

    12

    16

    20

    24

    0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6

    cfm/SqFt

    1

    /2

    U

    nitS

    e p a ra tio n

    Dis

    ta nc e ,L

    600

    545

    436

    273

    109

    10in. Neck

    NC=37

  • 7/28/2019 HVAC Vavselect-90min Part1

    16/20

    ADPI and LEED

  • 7/28/2019 HVAC Vavselect-90min Part1

    17/20

    THERMOSTATCold

    Outside

    Window

    Common Overhead Heating Design

  • 7/28/2019 HVAC Vavselect-90min Part1

    18/20

    Perimeter Considerations:Perimeter Considerations:

    Maximum delta-t for effective mixing when heating,per ASHRAE handbook = ?.

    = 15F (90F discharge), continuous operation.

    Throw toward and away from glass.

    150 FPM should reach 4-5 feet from the floor.

    ASHRAE 62.1 requires that ventilation be increasedby 25% when heating, if the above rules are notfollowed.

    Typical perimeters require only 8Fdelta-t @ 1 cfm/sq.Ft.

  • 7/28/2019 HVAC Vavselect-90min Part1

    19/20

    Perimeter Considerations:Perimeter Considerations:

    From 2009 ASHRAE Fundamentals, Chapter 20:

    Diffusers should be located such that the published 150 fpm

    isothermal throw (which is typically unaffected by t) extends

    to within 4.5 ft of the floor.

    According to ASHRAE Standard62.1, if throw does not meet

    this requirement, and the discharge-to-room temperature

    differential exceeds 15F, the ventilation rate must be increased

    by 25%. Furthermore, when the room-to-discharge differential

    exceeds 15F, it is unlikely that the vertical temperature

    limitation of ASHRAE Standard55 will be met.

  • 7/28/2019 HVAC Vavselect-90min Part1

    20/20

    ASHRAE Standard 62.1ASHRAE Standard 62.1

    Table 6.2Table 6.2