http www.spppumps
TRANSCRIPT
-
8/11/2019 Http Www.spppumps
1/103
WATER
FIRE
OIL & GAS
AUTOPRIME
STANDARD PRODUCTS
SERVICE
ENERGY
PARTS
TRANSFORMER OIL PUMPS
-
8/11/2019 Http Www.spppumps
2/103
DATA FORPUMP USERS
-
8/11/2019 Http Www.spppumps
3/103
2Contents
CONTACTS
Sales and Administration
1420 Lakeview
Arlington Business ParkTheale
Reading
Berkshire
RG7 4SA
Email: [email protected]
Tel: +44(0)118 932 3123
Fax: +44(0)118 932 3302
Manufacturing Centre
Crucible Close
Mushet Industrial Park
Coleford
Gloucestershire GL16 8PS
Email: [email protected]
Tel: +44(0)1594 832701Fax: +44(0)1594 836300
UK Service Centre Contact Directory
Western Service Centre
Tufthorn Avenue, Coleford
Gloucestershire
England GL16 8PJ
Tel: +44 (0) 1594 832701
Fax: +44 (0) 1594 810043
North West Service Centre
Greg Street, Reddish
Stockport
Cheshire
England SK5 7BU
Tel: +44 (0) 161 480 4955
Fax: +44 (0) 161 476 2193
Southern Service Centre
Unit 1 Stanstead Road
Boyatt Wood Industrial EstateEastleigh, Hampshire
England SO50 4RZ
Tel: +44 (0) 2380 616004
Fax: +44 (0) 2380 614522
Northern Ireland Service Centre
Unit 2 Oak Bank
Channel Commercial ParkQueens Road, Queens Island
Belfast
Northern Ireland
BT3 9DT
Tel: +44 (0) 2890 469802
Fax: +44 (0) 2890 466152
Scottish Service Centre
137 Deerdykes View
Cumbernauld
Scotland
G68 9HN
Tel: +44 (0) 1236 455035
Fax: +44 (0) 1236 455036
mailto:[email protected]:[email protected] -
8/11/2019 Http Www.spppumps
4/103
3Contents
France
SPP Pumps
2 rue du Chateau deau95450 US
France
Email: [email protected]
Tel: +33 (0) 1 30 27 96 96
Fax: +33 (0) 1 34 66 07 33
North and South America
SPP Pumps, Inc.6716 Best Friend Road
Norcross GA 30071, U.S.A.
Email:[email protected]
Tel: +1(770) 409-3280
Fax: +1(770) 409-3290
www.spppumpsusa.com
Middle East
SPP Pumps Limited (Middle East)
P O Box 61491, Jebel Ali
Dubai
United Arab Emirates
Email: [email protected]
Tel: +971 (0) 4 8838 733
Fax: +971 (0) 4 8838 735
Asia
SPP Pumps Limited (Asia)
152 Beach Road
Gateway East #05 - 01 to 04
Singapore 189721
Email: [email protected]
Tel: +(65) 6576 5725Fax: +(65) 6576 5701
South Africa
SPP Pumps (South Africa)
6c Roller StreetSpartan Ext 7 Kempton Park
Gautent
R.S.A
1619
Email: [email protected]
Tel: +27 (0) 860 777786
Fax: +27 11 970 2472
Italy
SPP Italy
Via Watt, 13/A
20143 Milano
Email: [email protected]
Tel: +(0039) 02 58111782
Fax: +(0039) 02 58111782Mobile: +(0039) 346 3204457
Poland
Email: [email protected]
Parent Company
Kirloskar Brothers Limited
YAMUNA
Plot No 98
(3-17), Baner
411045 Pune
India
Tel: +91 20 2721 4444
www.kbl.co.in
mailto:[email protected]:[email protected]://www.spppumpsusa.com/mailto:[email protected]:[email protected]://www.kbl.co.in/http://www.kbl.co.in/mailto:[email protected]:[email protected]://www.spppumpsusa.com/mailto:[email protected]:[email protected] -
8/11/2019 Http Www.spppumps
5/103
4Contents
USEFULWEBSITES
USEFUL WEBSITES
TRADE ASSOCIATIONS:
British Pump Manufacturers Association (BPMA)
www.bpma.org.uk
Construction Equipment Association (CEA)
www.coneq.org.uk
Fire Protection Association (FPA)
www.thefpa.co.uk
British Automatic Sprinkler Association
www.basa.org.uk
European Fire Sprinkler Network
www.eurosprinkler.org
Energy Industries Council
www.the-eic.com
Pump Centre
www.pumpcentre.com
REGULATORY AUTHORITIES:
Factory Mutual (FM)
www.fmglobal.com
Underwriters Laboratories
www.ul.com
Loss Prevention Certification Board
www.brecertification.co.uk
National Fire Protection Association
www.nfpa.org
Pump Distributors Association
www.the-pda.com
Pumps-Directory
www.pumps-directory.com
http://www.bpma.org.uk/http://www.coneq.org.uk/http://www.thefpa.co.uk/http://www.basa.org.uk/http://www.eurosprinkler.org/http://www.the-eic.com/http://www.pumpcentre.com/http://www.fmglobal.com/http://www.ul.com/http://www.brecertification.co.uk/http://www.nfpa.org/http://www.the-pda.com/http://www.pumps-directory.com/http://www.pumps-directory.com/http://www.the-pda.com/http://www.nfpa.org/http://www.brecertification.co.uk/http://www.ul.com/http://www.fmglobal.com/http://www.pumpcentre.com/http://www.the-eic.com/http://www.eurosprinkler.org/http://www.basa.org.uk/http://www.thefpa.co.uk/http://www.coneq.org.uk/http://www.bpma.org.uk/ -
8/11/2019 Http Www.spppumps
6/103
5Contents
-
8/11/2019 Http Www.spppumps
7/103
6Contents
CONTENTS
Introduction to SPP.................................8 -14
Manufacturing .................................................. 8
Test Faciylity ..................................................... 8 SPP Divisions .................................................... 9
SPP International ............................................ 13
Fire Protection and Approval Standards ........... 14
Pump Specification & Operation..... 16 36
Data Required When Buying Pumps ................ 16
Dimensions of Cast Iron Flanges to
BS EN 109221 ................................................ 18
Dimensions of Cast Iron Flanges to ASME/ANSI B16.1 ........................................... 21
Dimensions of Steel Flanges to
ASME/ANSI B16.5 ........................................... 23
Pump Installation ............................................ 25
Pump Operation .............................................. 25
Faults and Remedial Action ............................. 26
Vibration Tolerance ......................................... 28
Condition Monitoring ....................................... 30
Flow Estimation Methods ................................ 31
Application Dos and Donts ............................ 36
Hydraulic Design Data........................ 41 61
Pressure (bar) vs Head (m of Water) ................ 41
Calculation of Head for Pump Selection ........... 43
Autoprime Pumping Terms .............................. 46
Friction Loss for Water
Hazen-Williams Formula, C=140) .................... 48
Resistance in Fittings ...................................... 51
Quantities Passed by Pipes at
different Velocities .......................................... 52
Recommended Maximum Flow
through Valves (l/s) ......................................... 52
Water Discharged by Round Spray Holes in thin
walled Pipes Under Different Pressures ........... 53
Net Positive Suction Head (NPSH).................... 54
Maximum Suction Lift with Barometric Pressure
at Different Altitudes ....................................... 56
Liquid Viscosity and its Effect on Pump Performance ......................................... 57
Approximate Viscosity Conversion Schedule .... 59
Test Tolerances and Different Standards ......... 61
Velocity Head Correction................... 66 74
Electrical Design Data........................ 76 84
Average Efficiencies and Power Factors
of Electric Motors ............................................ 76
Approximate Full Load Speeds (RPM)
of AC Motors ................................................... 78
Starting AC Motors .......................................... 79
Whole Life Cost..................................... 82 84
Whole Life Cost Principles and Pump Design ... 82
Features of a Low Life-Cycle cost centrifugal pumps ........................................... 84
Energy..................................................... 87 90
Conversion Factors.............................. 92 97 Conversion Factor Tables ................................ 92
Vacuum Technical Data ................................... 96
Product / Application Charts ............................ 97
-
8/11/2019 Http Www.spppumps
8/103
7Contents
Engineered Pumping Solutions Focused on
Markets where Application Knowledge, Service and
Expertise Add Value
For more than 130 years SPP Pumps has been a leading manufacturer of
centrifugal pumps and associated systems. A global principal in design, supply
and servicing of pumps, pump packages and equipment for a wide range of
applications and industry sectors.
SPP pumps and systems are installed on all continents providing valuable high
integrity services for diverse industries, such as oil and gas production, water
and waste water treatment, power generation, construction, mines and forlarge industrial plants.
Major applications include water treatment & supply, sewage & waste water
treatment, fire protection, and mobile pumps for rental sectors, for which
our low life cost and environmental considerations are fundamental design
priorities.
Certificate Number: EMS111 Issue 1
-
8/11/2019 Http Www.spppumps
9/103
8Contents
MANUFACTURING
SPP requires the highest standards of manufacturing excellence from
its facilities around the world. This is crucial to the on-going growth and
development of the company. At the main manufacturing facility located in the
UK, SPP set the highest standards attainable in the industry for quality andreliability.
SPP distinguishes its product split between pre-engineered standard products
and fully customised equipment engineered and packaged to order. The
extensive manufacturing and testing capabilities reflect this wide and diverse
product range.
To ensure efficient use of production resources, an ERP manufacturingplanning system is utilised. Assembly areas are segregated into the main
product groups; standard pumps, industrial fire pumps, contractors pumps
and engineered products. The machine shop is planned in cell layout with
individual cells specialising in types, or ranges of components. CNC machines
are linked by a DNC system allowing programming to be carried out on the
machine or offline.
Lean manufacturing principles ensure that SPP are always focused oncontinuous improvement to support their Right First Time philosophy.
Customers are always welcome to visit the facility, either during
manufacturing or when equipment is on test.
TEST FACILITY
Testing, including witness testing,of all SPPs range of pumps is
performed at SPPs own extensive
in-house test facility. The main test
area has a 1.4 million litre test tank
with a depth of 6 metres. It can test
pressures up to 50 bar, flows up to
2000 l/s and powers up to 800kW
at 6.6kV, 400kW at 415V and 400kWat 60Hz. Generators can be used for
higher powers or voltages.
-
8/11/2019 Http Www.spppumps
10/103
-
8/11/2019 Http Www.spppumps
11/103
10Contents
SPP is a world leader in the design and manufacture of pumping equipment
for both onshore and offshore applications. In-house expertise ensures
compliance with all applicable specifications and regulations. SPP has also
established quality assurance and document control business systems allied
to the needs of the major oil and gas contractors and end users.
SPP is the packager as well as the pump manufacturer and takes full unit
responsibility for the complete scope of supply.
The SPP Autoprime range is a proven, versatile and comprehensive product
range suitable for use in a variety of applications worldwide. The Autoprime
is primarily sold to rental organisations, contractors, utility companies, open
cast mining companies and municipalities providing a durable solution.
Continual investment in market-led research and development ensure that
the products are designed to meet market requirements and legislation,
providing significant benefits and solutions to owners and users alike.
OIL & GAS
AUTOPRIME
-
8/11/2019 Http Www.spppumps
12/103
11Contents
STANDARD PRODUCTS
The SPP standard pump product range has been expertly designed to enable
you to fit them to any of your existing DIN Standard Pump Applications. SPPs
excellent modular pump design allows interchangeability across the rangeand with the ability to use standard shaft motors, gives much more flexibility
in terms of maintenance, stock holding and material options. SPP Standard
pumps can also be used for a variety of new pump application needs.
TRANSFORMER OIL PUMPS
SPPs transformer oil pump range is designed and manufactured to the
highest quality standards. SPP have been producing transformer oil pumpsfor more than sixty years. Life expectancy in many cases has exceeded forty
years. Applications include oil circulation in the following: power transmission,
distribution and electric traction locomotive transformers.
ENERGY
Through the use of proven systems and techniques, the Energy Division offers
a complete energy saving package that can be applied equally to new projects
and existing installations. The new division offers the following services:
Energy Audits, Customer Training, Energy Management, Surveys/reports/
analysis and recommendations. By monitoring and/or analysing the actual
requirement of the installation and comparing this with the specifications of
the equipment installed, SPP can make recommendations that can reduce
running costs (eg: power requirements), minimise maintenance costs
(eg: parts/servicing and downtime) and improve plant reliability (eg: upgradedmaterial specifications).
-
8/11/2019 Http Www.spppumps
13/103
12Contents
LorSERVICE
At SPP we are committed to providing the very best in customer support.
We have built our reputation by providing a fast, cost effective service whilst
maintaining continually high standards of workmanship and quality. Withstrategically located service centres in the UK and around the world, help is
never far away. Each service centre is fully equipped to offer a comprehensive
range of equipment repair and refurbishment techniques. Our support is
available 24 hours a day, and is only ever a phone call away.
SPP supports our customers around the globe through our extensive network
of field service engineers. SPP field service engineers have thousands of
hours of experience, backed by intensive product and applications training.Whatever your technical support requirement, we can help you get the best
performance from our equipment in your application Field service engineers
can provide.
Equipment installation and commissioning
Preventative maintenance
Equipment repair and upgrades
Product training
On SPP and other manufacturers pumps.
-
8/11/2019 Http Www.spppumps
14/103
13Contents
SPP INTERNATIONAL
USA
France
South
Africa
Ita
ly
Singapore
North
ern
Ireland
Poland
JebelAli
India
Abu
Dhabi
Reading
Stockport
Eastliegh
Coleford
SPPisatrulyglobalcompanywiththemainR&D,
manufacturingandtest
facilitiescentrallylocat
ed
intheUKandlocalsitesin
theUnitedStates,India
,France,
SouthAfrica,S
ingapore,Dubai,Italyand
Poland.
-
8/11/2019 Http Www.spppumps
15/103
14Contents
FIRE PROTECTION APPROVAL STANDARDS
SPP has one of the widest ranges of approved and listed equipment in
the world complying with the demanding requirements of the UL and FM
approval standards and meeting all the requirements of NFPA 20. Along with
these approvals, SPPs fire products are also approved for use in many othermarkets such as Europe, The Far East, The Middle East and Africa. Although
many pump companies can offer equipment designed to the various
locally applicable fire rules and regulations, only a very select few have had
their pumps subjected to the stringent performance and reliability tests of
specialist fire approval laboratories.
Being the first to achieve fire pump approval and listing by the internationally
recognised Loss Prevention Certification Board the company today has morepumps approved by the LPCB than any other manufacturer.
-
8/11/2019 Http Www.spppumps
16/103
15Contents
PUMP SPECIFICATIONAND OPERATION
-
8/11/2019 Http Www.spppumps
17/103
16Contents
PUMPSPECIFICATIONANDOPERATIO
N
SECTION 1
DATA REQUIRED WHEN BUYING PUMPS
Fundamentals
Number required.
Nature of service.
Whether continuous or intermittent.
Performance
Capacity (State whether total or per unit).
Total head or pressure to be developed.
Suction lift (including friction), inlet pressure or head, or NPSH available.
(State range of any variation in above items. Otherwise, send sketch or give
full details of lifts and pipe runs including lengths, bores, materials and class
of pipes and number and nature of bends, valves etc.).
Pumped Medium
Nature of liquid (if other than cold, clean water).
Values or ranges of actual pumping temperature with corresponding specific
gravities, viscosities (if greater than for water) and vapour pressures.
Any corrosive and/or abrasive properties.
Nature, proportion and maximum size of any solids content.
Driver
Nature of driver.
If driver to be supplied, give full specification.
If electric motor, state electricity supply details, any speed restriction.
Whether lining-up and connecting free issue driver required.
Details of starting equipment and/or other accessories required
system of control if automatic.
-
8/11/2019 Http Www.spppumps
18/103
17Contents
Other Data
If required to run in parallel with other units.
Is it to be self-priming with suction lift.
Pump type and arrangement.Fixed or portable.
Horizontal or vertical shaft.
Whether close-coupled, dry well, wet well or borehole (if vertical).
Borehole diameter or any other space restrictions.
If baseplate and coupling required.
Constructional / material specification required.Site conditions:
If altitude above 150m.
If ambient temperature above 30 C.
If to work outdoors.
Type of drive:
Direct or indirect (i.e. coupling, gearbox or V belt).
Direction of rotation (if restricted).
Official tests/inspection, packing and shipping requirements.
Tender receipt/material despatch date required.
Any other significant information.
Items printed in boldare minimum requirements for quotation of any standard
horizontal pump. All other items, so far as they apply, are necessary for the
correct execution of all orders and quotations other than standard horizontal
pumps.
-
8/11/2019 Http Www.spppumps
19/103
18Contents
SECTION 2
DIMENSIONS OF CAST IRON FLANGES TO BS EN 1092
Pumps and Fittings
NOM.
DIA.
FLANGE RAISED FACE BOLTS DRILLING NECK
D b d4 Fmax DIA. No d2 k d3 r
10 75 12 33 2 M10 4 11 50 26 4
15 80 12 38 2 M10 4 11 55 30 4
20 90 14 48 2 M10 4 11 65 38 4
25 100 14 58 3 M10 4 11 75 42 4
32 120 14 69 3 M12 4 14 90 55 6
40 130 14 78 3 M12 4 14 100 62 6
50 140 14 88 3 M12 4 14 110 74 6
65 160 14 108 3 M12 4 14 130 88 6
80 190 16 128 3 M16 4 18 150 102 8100 210 16 144 3 M16 4 18 170 130 8
125 240 18 174 3 M16 8 18 200 155 8
150 265 18 199 3 M16 8 18 225 184 10
200 320 20 254 3 M16 8 18 280 236 10
250 375 22 309 3 M16 12 18 335 290 12
300 440 22 363 4 M20 12 22 395 342 12
350 490 22 415 4 M20 12 22 445 385 12
400 540 22 463 4 M20 16 22 495 438 12
450 595 22 518 4 M20 16 22 550 492 12
500 645 24 568 4 M20 20 22 600 538 12
600 755 30 667 5 M24 20 26 705 640 12700 860 24 772 5 M24 24 26 810 740 12
800 975 24 878 5 M27 24 30 920 842 12
900 1075 26 978 5 M27 24 30 1020 942 12
1000 1175 26 1078 5 M27 28 30 1120 1045 16
PUMPSPECIFICATIONANDOPERATIO
N
BS EN 1092 TABLE PN6
NOTE - All dimensions listed below are in millimetres
-
8/11/2019 Http Www.spppumps
20/103
19Contents
BS EN 1092 TABLE PN10
NOM.
DIA.
FLANGE RAISED FACE BOLTS DRILLING NECK
D b d4 Fmx DIA. No d2 k d3 r
NOTE: FOR NOMINAL SIZES 10 - 150 USE PN6 TABLE200 340 24 266 3 M20 8 23 295 240 8
250 395 26 319 3 M20 12 23 350 392 8
300 445 26 370 4 M20 12 23 400 342 8
350 505 26 429 4 M20 16 23 460 396 8
400 565 26 480 4 M24 16 28 515 448 10
450 615 28 530 4 M24 20 28 565 498 10
500 670 28 582 4 M24 20 28 620 552 10
600 780 28 682 5 M27 20 31 725 654 10
700 895 30 794 5 M27 24 31 840 760 10
800 1015 32 901 5 M30 24 34 950 866 12
900 1115 34 1001 5 M30 28 34 1050 970 12
1000 1230 34 1112 5 M33 28 37 1160 1076 12
1200 1455 38 1328 5 M36 32 40 1380 1284 12
1400 1675 42 1530 5 M39 36 43 1590 1494 12
1600 1915 46 1750 5 M45 40 49 1820 1702 12
1800 2115 50 1950 5 M45 44 49 2020 1906 15
2000 2325 54 2150 5 M45 48 49 2230 2112 15
2200 2550 58 - - M52 52 56 2440 2320 20
BS EN 1092 TABLE PN16
NOM.
DIA.
FLANGE RAISED FACE BOLTS DRILLING NECK
D b d4 Fmx DIA. No d2 k d3 r
10 90 16 41 2 M12 4 14 60 74 4
15 95 16 46 2 M12 4 14 65 92 4
20 105 18 56 2 M12 4 14 75 105 4
25 115 18 65 3 M12 4 14 85 131 4
32 140 18 76 3 M16 4 18 100 56 6
40 150 18 84 3 M16 4 18 110 64 6
50 165 18 99 3 M16 4 18 125 74 665 185 18 118 3 M16 8 18 145 92 6
80 200 20 132 3 M16 8 18 160 105 8
100 220 20 156 3 M16 8 18 180 131 8
125 250 22 186 3 M16 8 18 210 156 10
150 285 22 211 3 M20 8 22 240 184 10
200 340 24 266 3 M20 12 22 295 235 12
250 405 26 319 3 M24 12 26 355 292 12
300 460 28 370 4 M24 12 26 410 344 12
350 520 30 429 4 M24 16 26 470 390 12
400 580 32 480 4 M27 16 30 525 445 12
450 640 40 548 4 M27 20 30 585 490 12500 715 44 609 4 M30 20 33 650 548 12
600 840 54 720 5 M33 20 36 770 652 12
700 910 36 794 5 M33 24 36 840 755 12
800 1025 38 901 5 M36 24 39 950 855 12
-
8/11/2019 Http Www.spppumps
21/103
20Contents
PUMPSPECIFICATIONANDOPERATIO
N
BS EN 1092 TABLE PN25
NOM.
DIA.
FLANGE RAISED FACE BOLTS DRILLING NECK
D b d4 Fmx DIA. No d2 k d3 r
10 90 16 41 2 M12 4 14 60 28 415 95 16 46 2 M12 4 14 65 32 4
20 105 18 56 2 M12 4 14 75 40 4
25 115 18 65 3 M12 4 14 85 46 4
32 140 18 76 3 M16 4 18 100 56 6
40 150 18 84 3 M16 4 18 110 64 6
50 165 20 99 3 M16 4 18 125 74 6
65 185 22 118 3 M16 8 18 145 92 6
80 200 24 132 3 M16 8 18 160 105 8
100 235 26 156 3 M20 8 22 190 134 8
125 270 28 186 3 M24 8 26 220 162 8
150 300 30 211 3 M24 8 26 250 192 10200 360 32 274 3 M24 12 36 310 244 10
250 425 35 330 3 M27 12 30 370 298 12
300 485 38 389 4 M27 16 30 430 352 12
350 555 42 448 4 M30 16 33 490 398 12
400 620 46 403 4 M33 16 36 550 452 12
450 670 50 548 4 M33 20 36 600 500 12
500 730 56 609 4 M33 20 36 660 558 12
600 845 68 720 5 M36 20 39 770 660 12
700 960 50 820 5 M39 24 42 875 760 12
800 1085 54 928 5 M45 24 48 990 864 12
-
8/11/2019 Http Www.spppumps
22/103
21Contents
DIMENSIONS OF CAST IRON FLANGES to ASME/ANSI B16.1
ASME/ANSI B16.1 125lb RATING CAST IRON
NOM.
DIA.
FLANGE BOLTS DRILLING SPOTFACE
DIAMETER
HUB
D b DIA. No d2 k d3 r
1 4.25 0.44 0.50 4 0.62 3.12 1.00 1.94 0.12
1 1/4 4.62 0.50 0.50 4 0.62 3.50 1.00 2.31 0.12
1 1/2 5.00 0.56 0.50 4 0.62 3.88 1.00 2.56 0.12
2 6.00 0.62 0.62 4 0.75 4.75 1.25 3.06 0.25
2 1/2 7.00 0.69 0.62 4 0.75 5.50 1.25 3.56 0.25
3 7.50 0.75 0.62 4 0.75 6.00 1.25 4.25 0.25
3 1/2 8.50 0.81 0.62 8 0.75 7.00 1.25 4.81 0.25
4 9.00 0.94 0.62 8 0.75 7.50 1.25 5.31 0.25
5 10.00 0.94 0.75 8 0.88 8.50 1.50 6.44 0.25
6 11.00 1.00 0.75 8 0.88 9.50 1.50 7.56 0.258 13.50 1.12 0.75 8 0.88 11.75 1.50 9.69 0.25
10 16.00 1.19 0.88 12 1.00 14.25 1.62 11.94 0.25
12 19.00 1.25 0.88 12 1.00 17.00 1.62 14.06 0.25
14 21.00 1.38 1.00 12 1.12 18.75 1.88 15.38 0.25
16 23.50 1.44 1.00 16 1.12 21.25 1.88 17.50 0.25
18 25.00 1.56 1.12 16 1.25 22.75 2.12 19.62 0.25
20 27.50 1.69 1.12 20 1.25 25.00 2.12 21.75 0.38
24 32.00 1.88 1.25 20 1.38 29.50 2.25 26.00 0.38
30 38.75 2.12 1.25 28 1.38 36.00 2.25 - 0.38
ASME/ANSI B16.1 125lb RATING CAST IRON
250lb RATING CAST IRON
NOTE - All dimensions listed below are in inches
-
8/11/2019 Http Www.spppumps
23/103
22Contents
PUMPSPECIFICATIONANDOPERATIO
N
ASME/ANSI B16.1 250lb RATING CAST IRON
NOM.
DIA.
FLANGE BOLTS DRILLING SPOTFACE
DIAMETER
HUB
D b DIA. No d2 k d3 r
1 4.88 0.69 0.62 4 0.75 3.50 1.25 2.06 0.131 1/4 5.25 0.75 0.62 4 0.75 3.88 1.25 2.50 0.13
1 1/2 6.12 0.81 0.75 4 0.88 4.50 1.50 2.75 0.13
2 6.50 0.88 0.62 8 0.75 5.00 1.25 3.31 0.25
2 1/2 7.50 1.00 0.75 8 0.88 5.88 1.50 3.94 0.25
3 8.25 1.12 0.75 8 0.88 6.62 1.50 4.62 0.25
3 1/2 9.00 1.19 0.75 8 0.88 7.25 1.50 5.25 0.25
4 10.00 1.25 0.75 8 0.88 7.88 1.50 5.75 0.25
5 11.00 1.38 0.75 8 0.88 9.25 1.50 7.00 0.25
6 12.50 1.44 0.75 12 0.88 10.62 1.50 8.12 0.25
8 15.00 1.62 0.88 12 1.00 13.00 1.63 10.25 0.25
10 17.50 1.88 1.00 16 1.12 15.25 1.88 12.62 0.2512 20.50 2.00 1.12 16 1.25 17.75 2.13 14.75 0.25
14 23.00 2.12 1.12 20 1.25 20.25 2.13 16.25 0.25
16 25.50 2.25 1.25 20 1.38 22.50 2.25 18.38 0.25
18 28.00 2.38 1.25 24 1.38 24.75 2.25 20.75 0.25
20 30.50 2.50 1.25 24 1.38 27.00 2.25 23.00 0.38
24 36.00 2.75 1.50 24 1.62 32.00 2.75 27.25 0.38
30 43.00 3.00 1.75 28 2.00 39.25 34.00 34.00 0.38
-
8/11/2019 Http Www.spppumps
24/103
23Contents
NOM.
DIA.
FLANGE RAISED FACE BOLTS DRILLING SPOTFACE
DIAMETER
HUB
D b d4 Fmax No DIA. d2 k d3 r
1/2 3.50 0.44 - - 4 1/2 0.62 2.38 1.00 1.19 0.12
3/4 3.88 0.50 - - 4 1/2 0.62 2.75 1.00 1.50 0.12
1 4.25 0.56 2.00 1/16 4 1/2 0.62 3.12 1.00 1.94 0.12
1 1/4 4.62 0.62 2.50 1/16 4 1/2 0.62 3.50 1.00 2.31 0.12
1 1/2 5.00 0.69 2.88 1/16 4 1/2 0.62 3.88 1.00 2.56 0.12
2 6.00 0.75 3.62 1/16 4 5/8 0.75 4.75 1.25 3.06 0.25
2 1/2 7.00 0.88 4.12 1/16 4 5/8 0.75 5.50 1.25 3.56 0.25
3 7.50 0.94 5.00 1/16 4 5/8 0.75 6.00 1.25 4.25 0.25
3 1/2 8.50 0.94 5.50 1/16 8 5/8 0.75 7.00 1.25 4.81 0.25
4 9.00 0.94 6.19 1/16 8 5/8 0.75 7.50 1.25 5.31 0.25
5 10.00 0.94 7.31 1/16 8 3/4 0.88 8.50 1.50 6.44 0.25
6 11.00 1.00 8.50 1/16 8 3/4 0.88 9.50 1.50 7.56 0.25
8 13.50 1.12 10.62 1/16 8 3/4 0.88 11.75 1.50 9.69 0.25
10 16.00 1.19 12.75 1/16 12 7/8 1.00 14.25 1.62 12.00 0.25
12 19.00 1.25 15.00 1/16 12 7/8 1.00 17.00 1.62 14.38 0.25
14 21.00 1.38 16.25 1/16 12 1 1.12 18.75 1.88 15.75 0.2516 23.50 1.44 18.50 1/16 16 1 1.12 21.25 1.88 18.00 0.25
18 25.00 1.56 21.00 1/16 16 1 1/8 1.25 22.75 2.12 19.88 0.25
20 27.50 1.69 23.00 1/16 20 1 1/8 1.25 25.00 2.12 22.00 0.38
24 32.00 1.88 27.25 1/16 20 1 1/4 1.38 29.50 2.25 26.12 0.38
DIMENSIONS OF STEEL FLANGES TO ASME/ANSI B16.5
ASME/ANSI B16.5 150lb RATING - STEEL
NOTE - All dimensions listed below are in inches
ASME/ANSI B16.5 150lb RATING - STEEL
300lb RATING - STEEL
-
8/11/2019 Http Www.spppumps
25/103
24Contents
NOM.
DIA.
FLANGE RAISED FACE BOLTS DRILLING SPOTFACE
DIAMETER
HUB
D b d4 Fmax No DIA. d2 k d3 r
1/2 3.75 0.56 1.38 1/16 4 1/2 0.62 2.62 1.00 1.50 0.12
3/4 4.62 0.62 1.69 1/16 4 5/8 0.75 3.25 1.25 1.88 0.121 4.88 0.69 2.00 1/16 4 5/8 0.75 3.50 1.25 2.12 0.12
1 1/4 5.25 0.75 2.50 1/16 4 5/8 0.75 3.88 1.25 2.50 0.12
1 1/2 6.12 0.81 2.88 1/16 4 3/4 0.88 4.50 1.50 2.75 0.12
2 6.50 0.88 3.62 1/16 8 5/8 0.75 5.00 1.25 3.31 0.25
2 1/2 7.50 1.00 4.12 1/16 8 3/4 0.88 5.88 1.50 3.94 0.25
3 8.25 1.12 5.00 1/16 8 3/4 0.88 6.62 1.50 4.62 0.25
3 1/2 9.00 1.19 5.50 1/16 8 3/4 0.88 7.25 1.50 5.25 0.25
4 10.00 1.25 6.19 1/16 8 3/4 0.88 7.88 1.50 5.75 0.25
5 11.00 1.38 7.31 1/16 8 3/4 0.88 9.25 1.50 7.00 0.25
6 12.50 1.44 8.50 1/16 12 3/4 0.88 10.62 1.50 8.12 0.25
8 15.00 1.62 10.62 1/16 12 7/8 1.00 13.00 1.62 10.25 0.2510 17.50 1.88 12.75 1/16 16 1 1.12 15.25 1.88 12.62 0.25
12 20.50 2.00 15.00 1/16 16 1 1/8 1.25 17.75 2.12 14.75 0.25
14 23.00 2.12 16.25 1/16 20 1 1/8 1.25 20.25 2.12 16.75 0.25
16 25.50 2.25 18.50 1/16 20 1 1/4 1.38 22.50 2.25 19.00 0.25
18 28.00 2.38 21.00 1/16 24 1 1/4 1.38 24.75 2.25 21.00 0.25
20 30.50 2.50 23.00 1/16 24 1 1/4 1.38 27.00 2.25 23.12 0.38
24 36.00 2.75 27.25 1/16 24 1 1/2 1.62 32.00 2.75 27.62 0.38
ASME/ANSI B16.5 300lb RATING - STEEL
*NOTE:
The standard for Ductile Iron flanges is ASME/ANSI B16.42 150lb and 300lb rating.
They are dimensionally the same as ASME/ANSI B16.5 including the raised face.
The standard for Copper Alloy flanges is ASME/ANSI B16.24 150lb and 300lb rating.
They are dimensionally the same as ASME/ANSI B16.5 except they are FLAT FACE.
PUMPSPECIFICATIONANDOPERATIO
N
-
8/11/2019 Http Www.spppumps
26/103
-
8/11/2019 Http Www.spppumps
27/103
26Contents
PUMPSPECIFICATIONANDOPERATIO
N
Potential Fault or Defect:
No liquid delivered.
Insufficient liquid delivered.
Liquid delivered at low pressure.
Loss of liquid after starting.
Excessive vibration.
Motor runs hotter than normal.
PROBABLE CAUSES
Pump not primed.
Speed too low.
Speed too high.
Air leak in suction pipework.
Air leak in mechanical seal.
Air or gas in liquid.
Discharge head too high (above rating).
Suction lift too high.
Not enough head for hot liquid.
Inlet pipe not submerged enough.
Viscosity of liquid greater than rating.
Liquid density higher than rating.
Insufficient nett inlet head.
Impeller blocked.
Wrong direction of rotation.
Excessive impeller clearance. Damaged impeller.
Rotor binding.
Defects in motor.
Voltage and/or frequency lower than rating.
Lubricating grease or dirty oil or contaminated.
Foundation not rigid.
Misalignment of pump and driver.
Bearing worn.
Rotor out of balance.
Shaft bent.
Impeller too small.
SECTION 5
Excessive noise from pump cavitation.
Pump bearings run hotter than normal.
FAULTS AND REMEDIAL ACTION
SPPs service division can carry out fault identification andrectification on a wide range of pumps.Contact your local SPP office for details
-
8/11/2019 Http Www.spppumps
28/103
27Contents
CAUSE REMEDIAL ACTIONPump not primed. Fill pump and suction pipe completely with fluid.
Speed too low.Check that the motor is correctly connected and receiving the full supply
voltage also confirm that the supply frequency is correct.
Speed too high. Check the motor voltage.
Air leak in suction pipework. Check each flange for suction draught, rectify as necessary.
Air leak in mechanical seal.
Check all joints, plugs and flushing lines, if fitted. Note that prolonged
running with air in the mechanical seal will result in damage and failure
of the seal.
Air or gas in liquid.It may be possible to increase the pump performance to provide
adequate pumping.
Discharge head too high (above
rating).
Check that valves are fully open and for pipe friction losses. An increase
in pipe diameter may reduce the discharge pressure.
Suction lift too high.
Check for obstruction of pump inlet and for inlet pipe friction losses.
Measure the static lift, if above rating, raise the liquid level or lower
the pump.
Not enough head for hot liquid. Reduce the positive suction head by raising the liquid level.
Inlet pipe not submerged
enough.
If the pump inlet cannot be lowered, provide a baffle to smother the inlet
vortex and prevent air entering with the liquid.
Viscosity of liquid greater than
rating.
Refer to SPP Pumps Ltd for guidance to increase the size or power of
the motor or engine.
Liquid density higher than
rating.
Refer to SPP Pumps Ltd for guidance to increase the size or power of
the motor or engine.
Insufficient nett inlet head.Increase the positive suction head by lowering the pump or raising the
liquid level.Impeller blocked. Dismantle the pump and clean the impeller.
Wrong direction of rotation. Check driver rotation with the direction arrow on the pump casing.
Excessive impeller clearance. Replace the impeller when clearance exceeds the maximum adjustment.
Rotor binding. Check for shaft deflection, check and replace bearings if necessary.
Defects in motor.Ensure that motor is adequately ventilated. Refer to manufacturers
instructions.
Voltage and/or frequency lower
than rating.
If voltage and frequency are lower than the motor rating, arrange for
provision of correct supply.
Lubricating grease or oil dirtyor contaminated.
Dismantle the pump, clean the bearings, reassemble the pump and fillwith new grease or oil.
Foundation not rigid.Ensure that the foundation bolts are tight, check that foundations match
SPP Pumps Ltd recommendations.
Misalignment of pump and
driver.Realign the pump and driver as specified.
Bearings worn.Remove the bearings, clean and inspect for damage and wear, replace
as necessary.
Rotor out of balance. Check impeller for damage, replace as necessary.
Shaft bent. Check shaft run-out and replace if necessary.
Impeller too small. Refer to SPP Pumps Ltd for options to fit a larger impeller.
SPPs service division can carry out fault identification and rectification on a wide range of pumps.Contact your local SPP office for details
-
8/11/2019 Http Www.spppumps
29/103
28Contents
SECTION 6
VIBRATION TOLERANCE
In every pump there are dynamic forces of hydraulic or mechanical origin that
will inevitably lead to a certain level of vibration. To maintain the integrity ofthe pump unit and associated equipment the level of vibration must be kept
within certain limits.
Acceptance Criteria
The following table defines the maximum allowable level of vibration
measured in mm/s RMS overall velocity during a factory acceptance test.
It should be noted that the factory acceptance test is not necessarily an
accurate representation of the vibration on site, when the unit is grouted inwith permanent pipe supports etc.
Pump Classes
Class 1 pumps will only include those that have been designed in full
accordance with A.P.I. 610, for use in critical applications. None of thestandard ranges of SPP fall into this class and pumps that meet it are only
available on an engineered to order basis.
Class 2 pumps will include all SPP general purpose industrial designs apart
from those specifically identified as class 3 below.
Class 3 pumps shall include any pumps with less than three impeller vanes,
split case pumps of the through bore type and any unit driven by a dieselengine of four or more cylinders. (Refer to SPP Engineering for units driven by
engines of three or less cylinders).
PUMPSPECIFICATIONANDOPERATIO
N
Application / Class Class 1 Class 2 Class 3
Continuousoperation over the preferred
operating range
3.0 4.7 7.1
Continuousoperation over the allowable
operating range3.9 5.6 9.0
Intermittent operation over the allowable
operaing range
Not applicable 9.0 13.0
-
8/11/2019 Http Www.spppumps
30/103
29Contents
Method
Vibration measurements will be made on the pump bearing housings, as close
as is practical to the bearing positions.
For each bearing position two measurements will be taken perpendicular tothe pump rotation axis. In addition an axial measurement will be taken at the
thrust bearing position.
The measurements will be of velocity, overall RMS values, in mm/s.
In order to reliably achieve the stated acceptance limits the pump must
be rigidly restrained, aligned to the driver within the coupling makers
recommendations, operating without cavitation or air entrainment. Pipe work
must be arranged to provide straight uniform flow into the pump and be
connected and anchored so as avoid strains and resonance.
SPPs field service engineers can undertake vibration analysis. Contact your
local SPP office for details
-
8/11/2019 Http Www.spppumps
31/103
30Contents
SECTION 7
CONDITION MONITORING
In order to minimise the ownership costs of capital
equipment, it is critical for the user to monitor andmaintain the equipment once installed. Failure to
do so will impact both on the mechanical integrity
and economic performance of the installed
equipment.
Early diagnosis of potential equipment failure
can result in considerable repair cost savings
and crucially a reduction in unplanned downtime.Monitoring of pump energy consumption and
system efficiency will bring visibility to pump
wear, operating efficiency and highlight any
system irregularities. All of these factors will
help minimise energy consumption and reduce
operating costs.
The SPP condition monitoring systems can providethis level of security by detecting, analysing and
evaluating key equipment performance. These
include the following:
Performance/Efciency degradation
Bearing vibration levels
Bearing element damage
Bearing operating temperatures
Driver alignment condition
Residual unbalance
Cavitation
The system provides considerable flexibility in the display and use of
the diagnostic output. The options include web based user configurabledashboard for live and trend data, automatic notification of alerts by text or
email and local download of data to PC for detailed evaluation.
PUMPSPECIFICATIONANDOPERATIO
N
-
8/11/2019 Http Www.spppumps
32/103
31Contents
SECTION 8
FLOW ESTIMATION METHODS
Many pumping systems are fitted with permanently installed flowmeters
which enable a reasonably accurate measurement of system flow to beobtained. Where permanent flowmeters are not installed, it is often possible
to use external clamp-on meters, insertion meters or thermodynamic testing
equipment to determine system flow. However, it is not always practical to
use these devices either for financial reasons or system layout constraints
and where this is the case, alternative indirect methods need to be used for
estimating system flow.
There are a number of methods available to enable an estimation of flow to bemade in the field. Each of these methods requires some form of knowledge of
the system or the pump, and all have inherent inaccuracies of varying degrees.
However, in the absence of any more accurate flow measuring apparatus,
these can be the only alternatives available.
There are four main indirect methods of determining pump flow in the field:
Pressure method
Power method Drop test
Suction pressure measurement
The Pressure and Power methods require the use of the pump curve, whilst the
drop test requires sump geometry and level details.
PRESSURE MEASUREMENT
This is the more accurate and simplest of the four methods, requiring suctionand delivery pressure gauge readings, a copy of the pump performance curve
at the correct operational speed and knowledge of the impeller diameter.
Determine the differential head across the pump by subtracting the suction
head from the discharge head. Then use the pump performance curve to
obtain the pump flow at the measured head and impeller diameter.
For example, if the suction head is measured as 3m and the discharge headas 63m, the pump differential head is 60m. Using the pump manufacturers
original test curve for the pump, the flow can be estimated as 150 l/s.
-
8/11/2019 Http Www.spppumps
33/103
32Contents
PUMPSPECIFICATIONANDOPERATIO
N
Over time, a pumps Flow/Head curve will change as wear occurs within the
pump. Therefore, the accuracy of this method will tend to reduce as the pump
gets older. However, this will remain a more accurate method than the others
detailed below.
Where existing installed site gauges are used, it should be remembered that
their accuracy may be far from ideal.
Remember that the pump Q/H curve is based on differential head, normally
pumping water with an SG of 1. If the site liquid being pumped has an SG
other than 1, SG correction should be applied to the site pressure readings to
match the performance curve being used.
POWER MEASUREMENT
Power meters are rarely available on site, but amps (I) and volts (V) are
commonly displayed at the control panel. These readings can be used to
calculate power, although this also requires motor efficiency and power factor
data - which will need to be estimated if motor manufacturers information is
not available.
Power (kW) = (1.732 x I x V x eff x pf)/1000Using this equation, the pump power can be calculated and from this, the flow
can be read off the pump curve.
-
8/11/2019 Http Www.spppumps
34/103
33Contents
Reading across the power scale on the pump manufacturers curve, the flow at
this absorbed power can be obtained 150 l/s in this example.
As mentioned above, a pumps Flow/Head curve and efficiency curve will
change as wear occurs within the pump. This will affect the pumps power
curve and therefore, as with the pressure measurement method, accuracy will
tend to reduce as the pump gets older.
It should also be remembered that the installed instruments from which
readings are taken may themselves be inaccurate, as it is unlikely that they
will not have been calibrated to any significant accuracy since their originalinstallation.
As an alternative to the above calculation, taking a simple current ratio (actual
current/full load current) and applying it to the motor rated power can give
a reasonable estimation of the motor output power. In the above example,
assuming a 132kW motor with a full load current of 230A, this method would
result in a duty power of (165/230)*132 = 95kW, and a resultant flow of around
135 l/s.
For example, if the
current is read as 165A,
the voltage as 400V and
motor efficiency and pf
from manufacturersdata are 95% and
0.92 respectively,
the calculated power
becomes:
Power = (1.732 x 400 x
165 x 0.95 x 0.92)/1000
= 100kW
-
8/11/2019 Http Www.spppumps
35/103
-
8/11/2019 Http Www.spppumps
36/103
Contents35
fittings friction (K) factor is also required.
Convert the suction pressure drop (P in kPA) into a head drop (Zd in meters)
using the equation:
Zd = P x 0.102
sg
(note that this Zd calculation will change depending on your site measured units)
Obtain a total K factor for the suction fittings up to the measurement point.
Assuming there are no significant straight pipe losses in the suction, the
following equation can then be used to determine the flow velocity:
Zd = V2 x (1+K) 2g
Once the velocity is known, the flow rate can be calculated using the suction
diameter. This method can be adapted to suit a wide variety of suction and pump
configuration and the available locations for pressure measurement.
Although there are potential inaccuracies in determining K factors and internal
diameters, careful use of this method can allow the velocity to be estimated towithin a few percent.
CONCLUSION
There is no single simple and accurate method of determining flow in systems
where installed meters are not present, or where the use of alternative
temporary flow metering equipment cannot be fitted. Instead there are a number
of methods that can be utilised to obtain an approximate pumping rate, which inmany cases may be sufficient for the purposes required.
All these methods have limitations and inherent inaccuracies. Where these
methods need to be employed, it is worthwhile applying at least two methods to
get comparative results.
-
8/11/2019 Http Www.spppumps
37/103
36Contents
PUMPSPECIFICATIONANDOPERATIO
N
SECTION 9
APPLICATION DOS AND DONTS
Suction & Delivery Piping
Ensure that bolt grouting or chemical anchors are allowed to dry thoroughlybefore connecting any pipework.
Note that fire pumpsets have regulatory requirements for piping and these
must be strictly observed. Refer to the appropriate standard for details.
Both suction and discharge piping should be supported independently and
close to the pump so that no strain is transmitted to the pump when the
flange bolts are tightened. Use pipe hangers or other supports at intervalsnecessary to provide support. When expansion joints are used in the piping
system, they must be installed beyond the piping supports closest to the
pump.
Install piping as straight as possible, avoiding unnecessary bends. Where
necessary, use 45 or long sweep 90 bends to decrease friction losses.
Eccentric Reducer on a Split CasePump
Typical End Suction Pump PipingInstallation
-
8/11/2019 Http Www.spppumps
38/103
37Contents
Make sure that all piping joints are airtight. Where reducers are used, eccentric
or flat top reducers are to be fitted in suction lines and concentric or straight
taper reducers in discharge lines. The length of eccentric reducers should be
about four times the pump suction diameter. Undulations in the pipe runs are
also to be avoided. Failure to comply with this may cause the formation of airpockets in the pipework and thus prevent the correct operation of the pump
and measuring equipment.
The suction pipe should be as short and direct as possible, and should be
flushed clean before connecting to the pump. For suction lift applications, it is
advisable to use a foot valve. Horizontal suction lines must have a gradual rise
to the pump. If the pumped fluid is likely to contain foreign matter then a filter
or coarse strainer should be fitted to prevent ingress to the pump.
The discharge pipe is usually preceded by a non-return valve or check valve
and a discharge gate valve. The check valve is to maintain system pressure in
case of stoppage or failure of the driver. The discharge valve is used to prevent
back flow when shutting down the pump for maintenance.
COUPLING ALIGNMENT
Periodical checks of shaft alignments should be undertaken and if necessaryadjusted accordingly. In order to maintain the warranty status of your SPP
pump it is recommended to take out an SPP preventative maintenance
contract. SPPs field service engineers have extensive experience in pump and
coupling alignment. Refer to the pump and coupling
instruction manuals for details of shaft alignment
procedures and tolerances or proceed generally thus:
a) Lateral AlignmentMount a dial gauge on the motor shaft or coupling
with the gauge running on the outer-machined
diameter of the pump coupling. Turn the motor shaft
and note the total indicator reading.
b) Angular Alignment
Mount a dial gauge on the motor shaft or coupling
to run on a face of the pump coupling as near to theoutside diameter as possible. Turn the motor shaft and note the total indicator
reading at top & bottom and each side.
-
8/11/2019 Http Www.spppumps
39/103
38Contents
PUMPSPECIFICATIONANDOPERATIO
N
c) Confirm Lateral Alignment
Mount the dial gauge on the pump shaft or
coupling with the gauge running on the machined
outer diameter of the motor coupling. Turn the
pump shaft and note the total indicator reading.
d) Adjustment
The motor must be shimmed and re-positioned to align the shafts to the
coupling manufacturers specifications.
Note:
Shaft alignment must be checked again after the final positioning of the pump
unit and connection to pipework as this may have disturbed the pump ordriver mounting positions.
ENGINE DRIVEN PUMPS
Air is required for combustion and cooling purposes, with air and radiator
cooled engines in particular needing large volumes of air for cooling. Inlet
and outlet apertures, suitably sized and positioned to prevent air recirculation,
must be provided in the pump house structure. It is recommended that a low
level vent be matched by a high level vent in the opposite wall.
Exhaust runs should be as short as possible. Small bore pipe and/or excessive
length will cause backpressure on the engine, reducing engine performance
and therefore pump output.
Engine driven fire pumps should not be left unattended whilst undertaking
weekly test runs. The run-to-crash design of fire pump engines makes it
essential to that they are commissioned by experienced personnel to avoidpermanent damage. SPP offers fixed price fire pump commissioning services
PRE-COMMISSIONING CHECK
If SPP Pumps Ltd is contracted to carry out the commissioning, the following
check list shows items to be completed before the commissioning engineer
arrives.
SPP COMMISSIONING SERVICESSPP use qualified engineers to maintain approved systems, warranty and
approved parts.
-
8/11/2019 Http Www.spppumps
40/103
Contents39
CHECK LIST
1 Installation:
Mounting plinths comply with instructions for size, construction
and location The baseplate has been accurately levelled and adequately supported.
This prevents distortion and makes achievable the final shaft alignment
to within manufacturers specification
The xing bolts are grouted as instructed and tightened to the
required torque
The shaft alignment has been checked and set to within the stated
tolerances.
2 Suction and delivery pipework is adequately supported and NEGLIGIBLE
forces are transmitted to the pump casing.
3 Where applicable, all drain, minimum flow, and test pipelines are fitted,
together with valves gauges and flow meters.
4 The diesel engine exhaust has been fitted in line with recommendations.
5 The engine fuel tank is filled with sufficient fuel.
6 Batteries are filled and charged in accordance with the manufacturers
instructions.
7 All wiring to controls and to remote alarm panels is completed in line with
appropriate regulations & power supplies are connected.
8 The area is clear of all builders material and rubbish to allow access to
the pumps.
-
8/11/2019 Http Www.spppumps
41/103
40Contents
HYDRAULIC DESIGN DATA
40
-
8/11/2019 Http Www.spppumps
42/103
41Contents
SECTION 10
PRESSURE (bar) VS HEAD (mOF WATER)
bar
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.00
0.00
1.02
2
.04
3.06
4.08
5.10
6.12
7.14
8.16
9.18
1.00
10.19
11.22
12.24
13.26
14.28
15.30
16.32
17.33
18.35
19.37
2.00
20.39
21.41
22.43
23.45
24.47
25.49
26.51
27.53
28.55
29.57
3.00
30.59
31.61
32.63
33.65
34.67
35.69
36.71
37.73
38.75
39.77
4.00
40.79
41.81
42.83
43.85
44.87
45.89
46.91
47.93
48.95
49.97
5.00
50.99
52.00
53.02
54.04
55.06
56.08
57.10
58.12
59.14
60.16
6.00
61.18
62.20
63.22
64.24
65.26
66.28
67.30
68.32
69.34
70.36
7.00
71.38
72.40
73.42
74.44
75.46
76.48
77.50
78.52
79.54
80.56
8.00
81.58
82.60
83.62
84.64
85.65
86.67
87.69
88.71
89.73
90.75
9.00
91.77
92.97
93.81
94.83
95.85
96.87
97.89
98.91
99.93
100.9
5
10
20
30
40
50
60
70
80
90
100
bar
101.97
203.94
305.91
40
7.88
509.85
611.82
713.79
815.76
9
17.73
1019.70
metre
s
-
8/11/2019 Http Www.spppumps
43/103
42Contents
HYDRAULICD
ESIGNDATA
EXAMPLE
Find the metres head of water (1.0 s.g.) equivalent of 54.76 bar
From bottom two lines: 50.00 bar = 509.85m
Select 4 bar line in first column and
read along to figure under 0.7 in
top line, hence:
4.70 bar = 47.93m
For 0.06 bar, read under 0.6 top line:
hence 6.12m dividing both figures by 10:
0.06 bar = 0.612m
Thus by addition 54.76 bar = 558.392m
Note:For liquids with specific gravities differing from 1.0, answer must be divided by
actual specific gravity to obtain head in metres of liquid.
-
8/11/2019 Http Www.spppumps
44/103
43Contents
SECTION 11
CALCULATION OF HEAD FOR PUMP SELECTION
To fulfill a pumping duty a pump must develop sufficient head and meet the
suction conditions. The total head of a system must take into account thedifference in liquid levels at inlet and outlet, friction in the pipes, surface
pressure (or in some cases vacuum) on inlet and outlet and the velocity of
the fluid at discharge. The following diagram and example explains how to
calculate the system head taking all these factors into account.
hd = total discharge head
hsd = discharge static head
hpd = discharge surface pressure head
hfd = discharge friction head
hvd = discharge velocity head
System head = total discharge head -
total suction head
H = hd hs
The total discharge head is made fromfour separate heads:
hd = hsd + hpd + hfd + hvd
-
8/11/2019 Http Www.spppumps
45/103
44Contents
HYDRAULICD
ESIGNDATA
The total suction head consists of four separate heads
hs = hss + hps - hfs - hvs
hs = total suction head
hss = suction static head hps = suction surface pressure head
hfs = suction friction head
hvs = suction velocity head
Example
Calculate the total head of the
following pump system.
The total friction through suction
pipes and fittings is equivalent
to 1m head and through delivery
pipes and fittings is equivalent to
10m head.
The header tank and discharge
pipe is open to atmosphere at sea
level.
The suction velocity head is 0.1m
and the discharge velocity head
is 0.5m
Pumped fluid is cold clean water.
-
8/11/2019 Http Www.spppumps
46/103
45Contents
First we calculate the total delivery head, hsd and hss from the diagram we
can see that the discharge static head is 40m and the suction static head is
5m hpd
millimeters of mercury x = meters of liquid
pressure at sea level is approx. 760mm Hg, specific gravity of cold clean water
is 1, so 760 x 0.014/1 = 10.6m
so hpd is 10.6m, the header tank is also open to atmosphere so hps is also
10.6m
hd = hsd + hpd + hfd + hvd
= 40 + 10.6 + 10 + 0.5
= 61.1 m
hs = hss + hps - hfs - hvs
= 5 + 10.6 - 1 - 0.1
= 14.5 m
Total system head H = hd hs
= 61.1 14.5
= 46.6 m
Note:
Gauge readings need correcting for height of gauge mounting. For this purposeit is important that pressure gauges should be full of liquid. Where a vacuum
gauge is used for a suction lift, the gauge pipe should be left empty and
correction made from the point of connection, not from the gauge itself.
0.014
specific gravity
-
8/11/2019 Http Www.spppumps
47/103
46Contents
HYDRAULICD
ESIGNDATA
AUTOPRIME PUMPING TERMS
Head
Total Head from all Causes is the combination of both Total Suction Head
and Total Discharge Head.
When static heights are kept to a minimum and pipework of the correct size
for the pump is used, performance will be maintained and running costs
minimised.
Suction head will be affected by changes in liquid viscosity and specific
gravity and in the vapour pressure resulting from increased liquid
temperature.
Net Positive Suction Head (NPSH)
NPSHr: minimum liquid head (pressure) required by the pump at the impeller
to pump the liquid, this is determined by the pump design. NPSHa: minimum
liquid head (pressure) available from the atmosphere to deliver the liquid to
the impeller for pumping.
Example:
NPSHa (Available) 10.5 m
less Static Lift 3.0 m
Friction & Vapour Loss 1.5 m
NPSHr (Required) 2.0 m
Therefore leaving for Suction Lift 4.0 m
-
8/11/2019 Http Www.spppumps
48/103
47Contents
TYPICAL SUCTION LIFT CONFIGURATION
AUTOPRIME
TOTAL
HEAD
FROM
ALL
CAUSES
TotalDischarge
Head
Discharge
Hose
Friction
Static
Delivery
Head
StaticSuction
Lift
Suction
HoseFriction
-
8/11/2019 Http Www.spppumps
49/103
-
8/11/2019 Http Www.spppumps
50/103
49Contents
For other types of pipe, multiply foregoing figures as below, for pipes in smooth
and new condition.
Galvanised iron 1.33
Uncoated cast iron 1.23
Coated cast iron, wrought iron, coated steel 1.07
Coated spun iron 1.04
Smooth pipe (lead, brass, copper, stainless steel, glass, plastic) 0.88
Friction losses are affected to an even greater degree by deviations of actualbore from the standard dimensions represented in the foregoing table.
To correct for actual bore, multiply also by
(D/d)4.87
Where D = Standard (nominal) bore.
d = Actual internal diameter.
Multiplying factors for grey iron pipes to BS 4622 (both sand mould cast and
spun): ductile iron pipes to BS 4772: and uPVC pipes to BS 3505 taking into
account the corrections both for type of pipe and for actual bore, are as follows
on the next page.
-
8/11/2019 Http Www.spppumps
51/103
50Contents
Nomina
lboremm
20
25
32
40
50
65
80
100
125
150
175
200
225
250
300
(in)
()
(1)
(1)
(1)
(2)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(12)
GreyIron,BS4622:
Class
1(spun)
-
-
-
0.84
0.90
-
0.93
-
0.95
-
0.96
0.97
Class
2(spun)
-
-
-
0.91
0.97
-
0.99
-
1.00
-
1.00
1.00
Class
3(spun)
-
-
-
0.99
1.04
-
1.04
-
1.04
-
1.04
1.04
Class
4(spun)
-
-
-
1.18
1.21
-
1.16
-
1.14
-
1.13
1.12
Forsandmouldcastpipesmultiplyby1.03:alsoforuncoatedborep
ipesby1.15
DuctileIron,BS4722:
Cla
ssK9
-
-
-
0.73
0.97
-
0.77
-
0.78
-
0.80
0.78
ClassK12
-
-
-
0.82
0.88
-
0.85
-
0.86
-
0.87
0.84
uPVC,
BS3505:
ClassB
-
-
-
0.78
0.65
0.68
0.68
0.73
0.74
0.77
0.75
0.80
ClassC
-
0.57
0.6
8
0.83
0.72
0.79
0.79
0.84
0.85
0.88
0.86
0.90
ClassD
0.66
0.64
0.7
8
0.96
0.84
0.92
0.92
0.98
0.97
1.03
0.98
1.04
ClassE
0.75
0.75
0.9
1
1.12
0.97
1.06
1.07
1.13
1.10
1.16
1.12
1.19
SteelTub
es,BS1387
medium;
alsoX1.24
forga
lvanised
0.79
0.75
0.64
0.90
0.84
0.8
5
1.06
0.87
0.92
0.93
-
-
-
-
-
HYDRAULICD
ESIGNDATA
-
8/11/2019 Http Www.spppumps
52/103
51Contents
SECTION 13
RESISTANCE IN FITTINGS
As in straight pipe, having length of following multiples of pipe diameter:
Flush sharp-edged entry 22
Slightly rounded entry 11
Flush bellmouth entry 4
Sharp entry projecting into liquid 36
Bellmouth entry projecting into liquid 9
Footvalve with strainer 113
Round elbow 45
Short radius bend 34Medium radius bend 18
Close return bend 100
Tee: straight through 11
side outlet, sharp angled 54
side outlet, radiused (swept tee) 22
Branch piece, straight through 7
Branch piece, flow to branch 45
Branch piece, flow from branch 22
Sluice (gate) valve 7
Reflux (back pressure, non-return) valve 45
Angle valve 225
Globe valve 450
Bellmouth outlet 9
Sudden enlargement 45
Taper, divergence angle above 60 45
Taper, divergence angle 15 - 60 22
Taper increaser or reduced with less than 15 divergence angle: Equivalent to pipe of mean
diameter.
Flap 0.06m Head
Note:
Multiplying factor for type and class of pipe to be applied to above equivalent
lengths for pipe fittings (elbows, bends, tees etc) but notto those for valves.
-
8/11/2019 Http Www.spppumps
53/103
52Contents
SECTION 14
QUANTITIES PASSED BY PIPES AT DIFFERENT VELOCITIES
SECTION 15
RECOMMENDED MAXIMUM FLOW THROUGH VALVES (l/s)
Actual bore of pipe, mm
Velocity
of flow,
m/s
50 80 100 125 150 175 200 225 250 300
l/s
1 1.96 5.03 7.85 12.27 17.67 24.1 31.4 39.7 49.1 70.7
1.5 2.95 7.54 11.78 18.41 26.51 36.1 47.1 59.6 73.6 106.1
2 3.93 10.05 15.71 24.54 35.34 48.1 62.8 79.5 98.2 141.4
2.5 4.91 12.57 19.64 30.68 44.18 60.1 78.5 99.4 122.7 176.7
3 5.89 15.08 23.56 36.82 53.02 72.2 94.3 119.3 147.3 212.1
3.5 6.87 17.59 27.49 42.95 61.85 84.2 110 139.2 171.8 247.4
4 7.85 20.11 31.42 49.09 70.69 96.2 125.7 159.0 196.4 282.8
5 9.82 25.13 39.27 61.36 88.36 120.3 157.1 198.8 245.4 353.4
Size of Valve, mm 50 65 80 100 125 150 175 200 250 300
Foot valve with
strainer
2.2 4.0 6.0 12.0 20.0 30.0 40.0 55.0 90.0 130.0
Back pressure valve 3.0 5.0 8.0 15.0 25.0 37.5 50.0 70.0 110.0 160.0
Sluice valve 5.5 10.0 15.0 25.0 40.0 60.0 80.0 100.0 160.0 220.0
HYDRAULICD
ESIGNDATA
-
8/11/2019 Http Www.spppumps
54/103
53Contents
SECTION 16
QUANTITIES OF WATER DISCHARGED BY ROUND SPRAY HOLES IN THIN
WALLED PIPES UNDER DIFFERENT PRESSURES
Pre
ssure
(bar)
Head
(mw
ater)
Sizeofhole(mm)
3
4
5
6
8
10
12
l/sperhole
0.5
5.1
0.04
3
0.077
0.120
0.173
0.307
0.48
0.69
1.0
10.2
0.06
1
0.109
0.170
0.245
0.435
0.68
0.98
1.5
15.3
0.07
5
0.133
0.208
0.300
0.532
0.83
1.20
2.0
20.4
0.08
6
0.154
0.240
0.346
0.615
0.96
1.38
2.5
25.5
0.09
6
0.172
0.269
0.387
0.688
1.07
1.55
3.0
30.6
0.10
6
0.188
0.294
0.424
0.754
1.18
1.70
3.5
35.7
0.11
4
0.204
0.318
0.458
0.814
1.27
1.83
4.0
40.8
0.12
2
0.218
0.340
0.489
0.870
1.36
1.96
5.0
51.0
0.13
6
0.243
0.380
0.546
0.972
1.52
2.19
6.0
61.2
0.15
0
0.266
0.416
0.600
1.065
1.67
2.40
-
8/11/2019 Http Www.spppumps
55/103
54Contents
SECTION 17
NET POSITIVE SUCTION HEAD (NPSH)
For a pump to fulfil a particular duty it must first be able to get the required
quantity in. For example, a pump may work satisfactorily when installed at agiven height above the liquid level on the suction side, but no longer do so if
it is placed higher, even though the total head remains unaltered in view of a
corresponding reduction in the height of lift on the delivery side.
The criteria for this is termed NPSH, which has two aspects, the NPSH the
installation and operating conditions provide (NPSH available) and the NPSH
needed to get stable flow into the pump impeller (NPSH required). The
installation conditions and pump selection must be reconciled so that theNPSH required does not exceed the NPSH available.
Fluid not being sensibly cohesive, it cannot be towed. To be made to flow, it
must be pressed from behind. There must, therefore, be either an extraneous
pressure on the liquid and/or a head of the liquid itself, which is sufficient to
cover losses as far as the pump inlet and then overcome pump inlet losses
and create the requisite velocity into the impeller vanes.
The pressure available behind a liquid for creating movement is the absolute
pressure on the liquid free surface, less the liquids own pressure to move in
the opposite direction, i.e. to evaporate into the spaces above the free surface
this is called vapour pressure. The head available at the pump inlet for
getting the flow into the pump impeller is therefore:-
Absolute pressure on liquid free surface Ha
Plus height of liquid free surface above pump impeller + hs Less liquid vapour pressure - hv
Less losses between liquid free surface and pump inlet - hl
(All expressed in metres head of the liquid).
HYDRAULICD
ESIGNDATA
-
8/11/2019 Http Www.spppumps
56/103
55Contents
Note:+hs becomes negative if the liquid free surface is below the pump impeller.
Care must be taken to state NPSH available taking all these factors into
account, even though in particular cases the two may equalise each other, e.g.
with a liquid at boiling point hv equals Ha and they thus cancel each other out.Otherwise confusion may arise through statement of NPSH, which is plainly
inconsistent with the circumstances, e.g. a figure being quoted as NPSH when
head over suction hs is meant.
The velocity required at inlet to the impeller vanes is a function of flow
quantity, area at vane inlets and velocity induced by impeller rotation.
Consequently the NPSH required varies with pump type and size, and increases
with both capacity and speed.
To maintain NPSH required within given limits, the permissible speed reduces
approximately as the square root of capacity increases.
The increased vapour pressure of warm water often affects suction as
indicated by the following table.
Negative figures represent minimum requirement of head of liquid above
impeller eye.
Note:The above figures are intentionally conservative in order to cover varyingsuction capabilities of different pumps. Better values may be obtainable
especially when the normal capacity of the pump is above the output required,
but to allow investigation, full details should be submitted, and the possibility
of the temperature being underestimated should not be overlooked.
Temp of water oC 40 50 60 70 75 80 85 90 95 100
Suction limit (m) 6.25 5.75 4.75 3.25 2.5 1.5 0.25 -1 -2 -3
-
8/11/2019 Http Www.spppumps
57/103
56Contents
SECTION 18
MAXIMUM SUCTION LIFT WITH BAROMETRIC PRESSURE AT
DIFFERENT ALTITUDES
SECTION 19
THERMOMETER SCALES
Temperature Conversion Formulae:-oF = (oC x 9/5) + 32 oC = (oF 32) x 5/9
Comparison values in oF and oC Scales of temperature
Altitude (m)
Barometric pressure Equivalenthead of
water (m)
Practicalmaximum suctionlift of pumps (m)bar mm Hg
Sea level 1.013 760 10,33 6.5
500 0.954 716 9.73 6
1000 0.899 674 9.16 5.5
1500 0.846 634 8.62 5
2000 0.796 597 8.12 4.5
oF
oC
oF
oC
oF
oC
-40 -40 113 45 302 150
-31 -35 122 50 320 160
-22 -30 131 55 338 170
-4 -20 140 60 356 180
5 -15 149 65 374 19014 -10 158 70 392 200
23 -5 167 75 410 210
32 0 176 80 428 220
41 5 185 85 446 230
50 10 194 90 464 240
59 15 203 95 482 250
68 20 212 100 500 260
77 25 230 110 518 270
86 30 248 120 536 280
95 35 266 130 554 290
104 40 284 140 572 300
HYDRAULICD
ESIGNDATA
-
8/11/2019 Http Www.spppumps
58/103
-
8/11/2019 Http Www.spppumps
59/103
58Contents
In the last column of the schedule, indications have been given of the
approximate minimum practical size of centrifugal pump corresponding to
each viscosity. In general, for greater viscosities exceeding 25 stokes, pumps
of a positive displacement type should be used.
HYDRAULICD
ESIGNDATA
-
8/11/2019 Http Www.spppumps
60/103
59Contents
APPROXIMATE VISCOSITY CONVERSION SCHEDULE
Kinem
atic
Viscosity
Stokes
Kinematic
Viscosity
Centistokes
Redwo
od
No1
Secon
ds
Saybolt
Universal
Seconds
Engler
Second
s
Engler
Degrees
Redwood
Admiralty
Seconds
Saybolt
Furol
S
econds
Barbey
Fluidity
Minim
umS
ize
Centrifugal
Pump(mm)
0.01
1
29.0
31.0
51.3
1.00
-
-
6200
Noreasonable
lim
itation
0.02
2
30.9
33.5
57.5
1.12
-
-
3100
0.03
3
33.0
36.2
62.6
1.22
-
-
2067
0.04
4
35.3
39.1
67.2
1.31
-
-
1550
0.05
5
37.9
42.3
71.3
1.39
-
-
1240
0.06
6
40.5
45.5
75.9
1.48
-
-
1033
0.07
7
43.2
48.7
80.1
1.56
-
-
886
0.08
8
46.0
52.0
84.7
1.65
-
-
775
0.09
9
48.8
55.4
89.3
1.74
-
-
689
0.1
10
51.7
58.6
93.9
1.83
-
-
620
0.2
20
85.0
97.5
147
2.87
9
15.0
310
20-25
0.3
30
123
141
209
4.07
12
18.5
207
25-32
0.4
40
163
186
274
5.33
16
22.2
153
32-40
0.5
50
203
231
340
6.61
20
26.0
124
40-50
0.6
60
244
277
406
7.90
24
30.5
103
40-50
0.7
70
284
323
473
9.21
28
35.0
88.6
50-65
0.8
80
324
370
559
10.5
32
39.5
77.5
50-65
0.9
90
364
416
606
11.8
36
44.0
68.9
50-65
-
8/11/2019 Http Www.spppumps
61/103
60Contents
Kinematic
Viscos
ity
Stokes
Kinematic
Viscosity
Centistokes
Redwo
od
No1
Secon
ds
Saybolt
Universal
Seconds
Engler
Seconds
Engler
Degrees
Redwood
Admiralty
Seconds
Saybolt
Furol
S
econds
Barbey
Fluidity
MinimumS
ize
Centrifugal
Pump
(mm)
1
100
405
462
677
13.2
41
48.5
62.0
50
-80
2
200
810
924
1350
26.3
81
94.7
31.0
80-
100
3
300
1215
1386
2030
39.5
122
141
20.7
125
-150
4
400
1620
1848
2700
52.6
162
188
15.5
150
-175
5
500
2025
2310
3580
65.8
203
235
12.4
175
-200
6
600
2430
2772
4060
78.9
243
282
10.3
200
-250
7
700
2835
3234
4730
92.1
284
329
8.9
200
-250
8
800
3240
3696
5390
105
324
376
7.8
250
-300
9
900
3645
4158
6060
118
365
423
6.9
250
-300
10
1000
4050
4620
6770
132
405
470
6.2
300
-350
0
2000
8100
9240
13500
263
810
940
3.10
400
-450
30
3000
12150
13860
20300
395
1215
1410
2.07
Pos
itive
displacement
pum
prequired
40
4000
16200
18480
27000
526
1620
1880
1.55
50
5000
20250
23100
33800
658
2025
2350
1.24
60
6000
24300
27720
40600
789
2430
2820
1.03
70
7000
28350
32340
47300
921
2835
3290
80
8000
32400
36960
53900
1050
3240
3760
90
9000
36450
41580
60600
1180
3645
4230
100
10000
40500
46200
67700
1316
4050
4700
HYDRAULICD
ESIGNDATA
-
8/11/2019 Http Www.spppumps
62/103
-
8/11/2019 Http Www.spppumps
63/103
62Contents
HYDRAULICD
ESIGNDATA
Hydraulic Institute Test Standards
In making tests under this standard no minus tolerance or margin shall be
allowed with respect to capacity, total head or efficiency at the rated or
specified conditions.
The following tolerances shall apply:
At rated head +10% of rated capacity
OR
At rated capacity +5% of rated head under 500 feet
+3 % of rated head 500 feet and over
Conformity with only one of the above tolerances is required. It should be
noted that there might be an increase in horsepower at the rated condition
when complying to plus tolerances for head or capacity.
For a fire pump the following tolerances from NFPA 20 shall also apply:
At 150% of rated capacity, head will range from minimum of 65% to
maximum of just below rated head.
Shutoff head will range from minimum of 101% to maximum of 140% of
rated head.
Exception
If available suction supplies do not permit the flowing of 150% of rated
capacity, the fire pump shall be operated at maximum allowable discharge
to determine if it is acceptable. This reduced capacity shall not constitute an
unacceptable test.
-
8/11/2019 Http Www.spppumps
64/103
Contents63
ISO 9906:2000 (grade 1) Table 10
The following tolerances shall apply at duty flow rate: -
Rate of ow 4.5 %
Pump Total head 3 %
Pump Efciency - 3 %
Speed of rotation 1 %
ISO 9906:2000 (grade 2) Table 10
The following tolerances shall apply at duty flow rate: -
Rate of ow 8 %
Pump Total head 5.5 %
Pump Efciency - 5 %
Speed of rotation 1 %
ISO 9906:2000 (grade 2) Annex A.1 Pumps produced in series.
The following tolerances shall apply at duty flow rate: -
Rate of ow 9 %
Pump Total head 7 %
Pump Input Power + 9 %
Driver Input Power + 9 %
Pump Efciency - 7 %
ISO 9906:2000 (grade 2) Annex A.2 Pumps with a driver powerinput less than 10 kW
The following tolerances shall apply at duty flow rate: -
Rate of ow 10 %
Pump Total head 8 %
-
8/11/2019 Http Www.spppumps
65/103
-
8/11/2019 Http Www.spppumps
66/103
65Contents
VELOCITY HEADCORRECTION
-
8/11/2019 Http Www.spppumps
67/103
66Contents
TABLES OF VELOCITY HEAD CORRECTION (BAR)
Flow (Litres/Minute)
Di Dd 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900
50 80 0.305 0.369 0.440 0.516 0.598 0.687 0.782 0.882 0.989 1.102
65 80 0.071 0.086 0.102 0.120 0.139 0.160 0.182 0.206 0.231 0.257
80 100 0.032 0.039 0.047 0.055 0.064 0.073 0.083 0.094 0.105 0.117
80 150 0.051 0.061 0.073 0.085 0.099 0.114 0.129 0.146 0.164 0.182
100 125 0.013 0.016 0.019 0.022 0.026 0.030 0.034 0.038 0.043 0.048
100 150 0.018 0.022 0.026 0.031 0.035 0.041 0.046 0.052 0.059 0.065
100 200 0.021 0.026 0.030 0.036 0.041 0.047 0.054 0.061 0.068 0.076
100 250 0.022 0.027 0.032 0.037 0.043 0.049 0.056 0.063 0.071 0.079
125 150 0.005 0.006 0.007 0.008 0.009 0.011 0.012 0.014 0.015 0.017
125 200 0.008 0.009 0.011 0.013 0.015 0.018 0.020 0.023 0.025 0.028
125 250 0.009 0.010 0.012 0.015 0.017 0.019 0.022 0.025 0.028 0.031
150 175 0.002 0.002 0.003 0.003 0.004 0.005 0.005 0.006 0.007 0.007
150 200 0.003 0.004 0.004 0.005 0.006 0.007 0.008 0.009 0.010 0.011150 250 0.004 0.005 0.006 0.007 0.008 0.009 0.010 0.011 0.013 0.014
150 300 0.004 0.005 0.006 0.007 0.008 0.009 0.011 0.012 0.014 0.015
175 200 0.001 0.001 0.001 0.002 0.002 0.002 0.003 0.003 0.003 0.004
200 225 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.002 0.002 0.002
200 250 0.001 0.001 0.001 0.001 0.002 0.002 0.002 0.002 0.003 0.003
200 300 0.001 0.001 0.002 0.002 0.002 0.003 0.003 0.003 0.004 0.004
250 300 0.000 0.000 0.000 0.001 0.001 0.001 0.001 0.001 0.001 0.001
300 350 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
350 400 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Di - Smaller diameter (mm)
Dd - Larger diameter (mm)
Gauge pressure variations, where the flow is from :-the smaller diameter to the larger diameter, then VAR. is POS(+) or,
the larger diameter to the smaller diameter, then VAR. is NEG(-)
-
8/11/2019 Http Www.spppumps
68/103
67Contents
VELOCITYHE
ADCORRECTION
Flow (Litres/Minute)
Di Dd 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900
50 80 1.2211 1.3463 1.4776 1.6149 1.7584 1.9080 2.0637 2.2255 2.3934 2.5674
65 80 0.2847 0.3138 0.3444 0.3765 0.4099 0.4448 0.4811 0.5188 0.5579 0.5985
80 100 0.1298 0.1431 0.1571 0.1717 0.1869 0.2028 0.2194 0.2366 0.2544 0.2729
80 150 0.2021 0.2228 0.2445 0.2673 0.2910 0.3158 0.3415 0.3683 0.3961 0.4249
100 125 0.0532 0.0586 0.0643 0.0703 0.0766 0.0831 0.0899 0.0969 0.1042 0.1118
100 150 0.0723 0.0797 0.0874 0.0956 0.1041 0.1129 0.1221 0.1317 0.1417 0.1520
100 200 0.0844 0.0931 0.1022 0.1117 0.1216 0.1319 0.1427 0.1539 0.1655 0.1775
100 250 0.0878 0.0968 0.1062 0.1161 0.1264 0.1371 0.1483 0.1599 0.1720 0.1845125 150 0.0191 0.0211 0.0231 0.0253 0.0275 0.0298 0.0323 0.0348 0.0374 0.0402
125 200 0.0313 0.0345 0.0378 0.0413 0.0450 0.0488 0.0528 0.0570 0.0613 0.0657
125 250 0.0346 0.0381 0.0418 0.0457 0.0498 0.0540 0.0584 0.0630 0.0678 0.0727
150 175 0.0082 0.0090 0.0099 0.0108 0.0118 0.0128 0.0138 0.0149 0.0160 0.0172
150 200 0.0122 0.0134 0.0147 0.0161 0.0175 0.0190 0.0206 0.0222 0.0238 0.0256
150 250 0.0155 0.0171 0.0187 0.0205 0.0223 0.0242 0.0262 0.0282 0.0303 0.0326
150 300 0.0167 0.0184 0.0202 0.0221 0.0240 0.0261 0.0282 0.0304 0.0327 0.0351
175 200 0.0040 0.0044 0.0048 0.0053 0.0057 0.0062 0.0067 0.0072 0.0078 0.0084
200 225 0.0021 0.0023 0.0026 0.0028 0.0030 0.0033 0.0036 0.0039 0.0041 0.0044
200 250 0.0033 0.0037 0.0040 0.0044 0.0048 0.0052 0.0056 0.0061 0.0065 0.0070
200 300 0.0045 0.0050 0.0055 0.0060 0.0065 0.0071 0.0076 0.0082 0.0089 0.0095
250 300 0.0012 0.0013 0.0014 0.0016 0.0017 0.0019 0.0020 0.0022 0.0023 0.0025
300 350 0.0005 0.0006 0.0006 0.0007 0.0007 0.0008 0.0009 0.0009 0.0010 0.0011
350 400 0.0002 0.0003 0.0003 0.0003 0.0004 0.0004 0.0004 0.0005 0.0005 0.0005
-
8/11/2019 Http Www.spppumps
69/103
68Contents
Flow (Litres/Minute)
Di Dd 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900
50 80 2.7475 2.9338 3.1261 3.3245 3.5291 3.7397 3.9564 4.1793 4.4083 4.6433
65 80 0.6405 0.6839 0.7287 0.7750 0.8227 0.8718 0.9223 0.9742 1.0276 1.0824
80 100 0.2921 0.3119 0.3323 0.3534 0.3752 0.3976 0.4206 0.4443 0.4686 0.4936
80 150 0.4547 0.4855 0.5174 0.5502 0.5840 0.6189 0.6548 0.6917 0.7295 0.7684
100 125 0.1196 0.1277 0.1361 0.1448 0.1537 0.1628 0.1723 0.1820 0.1920 0.2022
100 150 0.1626 0.1736 0.1850 0.1968 0.2089 0.2213 0.2342 0.2474 0.2609 0.2748
100 200 0.1900 0.2029 0.2162 0.2299 0.2440 0.2586 0.2736 0.2890 0.3048 0.3211
100 250 0.1975 0.2108 0.2247 0.2389 0.2536 0.2688 0.2843 0.3003 0.3168 0.3337125 150 0.0430 0.0459 0.0489 0.0520 0.0552 0.0585 0.0619 0.0654 0.0689 0.0726
125 200 0.0703 0.0751 0.0800 0.0851 0.0903 0.0957 0.1013 0.1070 0.1129 0.1189
125 250 0.0778 0.0831 0.0885 0.0942 0.0999 0.1059 0.1121 0.1184 0.1248 0.1315
150 175 0.0184 0.0197 0.0210 0.0223 0.0237 0.0251 0.0265 0.0280 0.0296 0.0311
150 200 0.0274 0.0292 0.0311 0.0331 0.0351 0.0372 0.0394 0.0416 0.0439 0.0462
150 250 0.0348 0.0372 0.0396 0.0422 0.0448 0.0474 0.0502 0.0530 0.0559 0.0589
150 300 0.0375 0.0401 0.0427 0.0454 0.0482 0.0511 0.0540 0.0571 0.0602 0.0634
175 200 0.0089 0.0095 0.0102 0.0108 0.0115 0.0122 0.0129 0.0136 0.0143 0.0151
200 225 0.0048 0.0051 0.0054 0.0058 0.0061 0.0065 0.0069 0.0072 0.0076 0.0080
200 250 0.0075 0.0080 0.0085 0.0090 0.0096 0.0102 0.0108 0.0114 0.0120 0.0126
200 300 0.0102 0.0109 0.0116 0.0123 0.0131 0.0138 0.0146 0.0155 0.0163 0.0172
250 300 0.0027 0.0029 0.0031 0.0032 0.0034 0.0037 0.0039 0.0041 0.0043 0.0045
300 350 0.0012 0.0012 0.0013 0.0014 0.0015 0.0016 0.0017 0.0018 0.0018 0.0019
350 400 0.0006 0.0006 0.0006 0.0007 0.0007 0.0008 0.0008 0.0009 0.0009 0.0009
Di - Smaller diameter (mm)
Dd - Larger diameter (mm)
Gauge pressure variations, where the flow is from :-
the smaller diameter to the larger diameter, then VAR. is POS(+) or,
the larger diameter to the smaller diameter, then VAR. is NEG(-)
-
8/11/2019 Http Www.spppumps
70/103
69Contents
VELOCITYHE
ADCORRECTION
Flow (Litres/Minute)
Di Dd 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900
50 80 4.8845 5.1318 5.3852 5.6447 5.9102 6.1820 6.4598 6.7437 7.0337 7.3298
65 80 1.1386 1.1963 1.2553 1.3158 1.3777 1.4411 1.5058 1.5720 1.6396 1.7086
80 100 0.5193 0.5456 0.5725 0.6001 0.6283 0.6572 0.6867 0.7169 0.7477 0.7792
80 150 0.8084 0.8493 0.8912 0.9342 0.9781 1.0231 1.0691 1.1160 1.1640 1.2130
100 125 0.2127 0.2235 0.2345 0.2458 0.2574 0.2692 0.2813 0.2936 0.3063 0.3192
100 150 0.2891 0.3037 0.3187 0.3341 0.3498 0.3659 0.3823 0.3991 0.4163 0.4338
100 200 0.3377 0.3548 0.3724 0.3903 0.4087 0.4274 0.4467 0.4663 0.4863 0.5068
100 250 0.3510 0.3688 0.3870 0.4057 0.4247 0.4443 0.4642 0.4846 0.5055 0.5268125 150 0.0764 0.0803 0.0842 0.0883 0.0924 0.0967 0.1010 0.1055 0.1100 0.1146
125 200 0.1250 0.1314 0.1379 0.1445 0.1513 0.1583 0.1654 0.1726 0.1801 0.1876
125 250 0.1383 0.1453 0.1525 0.1599 0.1674 0.1751 0.1830 0.1910 0.1992 0.2076
150 175 0.0327 0.0344 0.0361 0.0378 0.0396 0.0414 0.0433 0.0452 0.0472 0.0491
150 200 0.0486 0.0511 0.0536 0.0562 0.0589 0.0616 0.0643 0.0672 0.0700 0.0730
150 250 0.0619 0.0651 0.0683 0.0716 0.0749 0.0784 0.0819 0.0855 0.0892 0.0929
150 300 0.0667 0.0701 0.0736 0.0771 0.0807 0.0844 0.0882 0.0921 0.0961 0.1001
175 200 0.0159 0.0167 0.0175 0.0184 0.0192 0.0201 0.0210 0.0219 0.0229 0.0239
200 225 0.0085 0.0089 0.0093 0.0098 0.0102 0.0107 0.0112 0.0117 0.0122 0.0127
200 250 0.0133 0.0140 0.0147 0.0154 0.0161 0.0168 0.0176 0.0184 0.0191 0.0199
200 300 0.0181 0.0190 0.0199 0.0209 0.0219 0.0229 0.0239 0.0249 0.0260 0.0271
250 300 0.0048 0.0050 0.0053 0.0055 0.0058 0.0060 0.0063 0.0066 0.0069 0.0072
300 350 0.0020 0.0022 0.0023 0.0024 0.0025 0.0026 0.0027 0.0028 0.0029 0.0031
350 400 0.0010 0.0010 0.0011 0.0011 0.0012 0.0013 0.0013 0.0014 0.0014 0.0015
-
8/11/2019 Http Www.spppumps